PCS_Palm_Harbor_University_Heat_Recovery_CH-4_Option_A_Submittal.pdf
PDF 976 KB Posted
- Attached to
- Chiller Replacement State and local contract opportunity
- Solicitation number
- 25-CR-052
- Issued by
- Pinellas County, Florida
About this file
This document is a Carrier heat recovery chiller submittal for the Pinellas County Schools Bid 24-CR-030 project at Palm Harbor University High School, dated 1/9/2025. The submittal contains detailed technical specifications for a CH-4 Option A water-cooled screw chiller with model number 30HXC261, manufactured in Charlotte, NC. The chiller has a capacity of 263.8 tons, uses R513A refrigerant, operates on 460V three-phase power, and includes multiple accessories such as min load control, suction service valves, BACnet communication, and vibration isolation pads. The unit offers a minimum capacity of 10% and features two independent refrigerant circuits with 8 capacity control steps.
The performance data demonstrates the chiller's efficiency across various load conditions, with an Integrated Part Load Value (IPLV) of 0.5400 kW/Ton and a Non-Standard Part Load Value (NPLV) of 0.5158 kW/Ton. The chiller comes with a comprehensive warranty, including parts-only coverage for the first year and parts and labor coverage for years 2-10 in the US and Canada. The detailed performance summary includes metrics such as cooling capacity, input power, efficiency (EER), saturated condenser and evaporator temperatures, and fouling factors at different load percentages. The documentation is AHRI certified and complies with AHRI Standard 550/590 (I-P) and Standard 551/591 (SI), ensuring the unit meets industry performance standards.
View the file
Other files for this state and local contract opportunity
Show all 50
Chiller Replacement has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Pinellas County Schools
Project Bid 24-CR-030 Palm Harbor University High School
Date 1/9/2025
Mechanical Engineer Phoenix Engineering
Sales Engineer Mohamed Abdel-Aziz
Submittal Heat Recovery Chiller 4 Option A mohamed.abdelaziz@carrier.com; 813-404-2573
Table of Contents
Unit Report 1
Unit Performance 3
Drawings 8
Unit Report
Unit Report For CH-4 Option A Project: PCS - Palm Harbor 01/08/2025 Prepared By: 06:23PM
Unit Information Tag Name: CH-4 Option A Model Number: 30HXC261 Condenser Type: Water Cooled Compressor Type: Screw Nameplate Voltage: 460-3-60 V-Ph-Hz Quantity: 1 Manufacturing Source: Charlotte, NC USA Refrigerant: R513A Independent Refrigerant Circuits: 2 Capacity Control Steps: 8 Minimum Capacity: 10.0 % Shipping Weight: 10190 lb Operating Weight: 10944 lb Unit Length: 153 in Unit Width: 37 in Unit Height: 74 in
Accessories and Installed Options Min Load Control (to 10% capacity) Suction Service Valves R-513A Charge, Standard Evaporator Pass Y-Delta Starter & Non-Fused Disconnect BACnet Communication Option Thermistor (5k Ohm) - 4 inch Water Temperature Sensor Thermistor Well - 4 inch Compressor Blanket Kit Vibration Isolation Pads
Chiller Warranty Information (Note: for US & Canada only) First Year - Parts Only (Standard) Start-up, First Unit Complete Unit Years 2-5 Parts & Carrier CCS Labor Complete Unit Year 2-10 Parts Parts & Labor
Ordering Information
Part Number Description Quantity 30HXC261SZU6-1KA Packaged Chiller 1
Base Unit Min Load Control (to 10% capacity) Suction Service Valves R-513A Charge, Standard Evaporator Pass Y-Delta Starter & Non-Fused Disconnect BACnet Communication Option
HH79NZ029 Thermistor (5k Ohm) - 4 inch Water Temperature Sensor 2 10HB50106802 Thermistor Well - 4 inch 2
P916-A-30HX-261 Compressor Blanket Kit 1 30HX-900---010 Vibration Isolation Pads 1
Packaged Chiller Builder NACO 3.74 Page 1 of 1
Unit Performance
Detailed Performance Summary For CH-4 Option A
Prepared By: 06:24PM
PackagedChillerReport:DoNotEdit;
AquaForceTM Water-Cooled Screw Chiller Unit Information Tag Name: CH-4 Option A Model Number: 30HXC261 Condenser Type: Water Cooled Compressor Type: Screw Nameplate Voltage: 460-3-60 V-Ph-Hz Quantity: 1 Manufacturing Source: Charlotte, NC USA Independent Refrigerant Circuits: 2 Capacity: 263.8 Tons Comp. Input Power: 191.0 kW Unit Input Power: 191.0 kW Capacity control steps: 11 Minimum Capacity: 10.00 % Input: 0.7238 kW/Ton Unit Efficiency (EER): 16.58 BTU/Wh IPLV.IP: 0.5400 kW/Ton NPLV.IP: 0.5158 kW/Ton Refrigerant: R513A Shipping Weight: 10190 lb Operating Weight: 10944 lb Unit Length: 153 in Unit Width: 37 in Unit Height: 74 in
Evaporator Information Fluid Type: Fresh Water Fluid Entering Temperature: 55.00 °F Fluid Leaving Temperature: 45.00 °F Fluid Flow Rate: 632.6 gpm Fluid Pressure Drop: 17.9 ft H2O Fluid Velocity: 6.0 ft/s Fouling Factor: 0.000100 (hr-sqft-F)/BTU Fouling Factor Temp Adj.: 0.32 °F Saturated Evaporator Temp.
Circuit A: 43.8 °F Circuit B: 43.7 °F
Condenser Information Fluid Type: Fresh Water Fluid Entering Temperature: 80.00 °F Fluid Leaving Temperature: 100.00 °F Fluid Flow Rate: 382.5 gpm Fluid Pressure Drop: 6.27 ft H2O Fluid Velocity: 3.4 ft/s Fouling Factor: 0.000250 (hr-sqft-F)/BTU Fouling Fact. Temp. Adj.: 0.40 °F Saturated Condenser Temp.
Circuit A: 100.0 °F Circuit B: 101.9 °F
Integrated Pump Information No Pump Selected
Accessories and Installed Options Min Load Control (to 10% capacity) Suction Service Valves R-513A Charge, Standard Evaporator Pass Y-Delta Starter & Non-Fused Disconnect BACnet Communication Option Thermistor (5k Ohm) - 4 inch Water Temperature Sensor Thermistor Well - 4 inch Compressor Blanket Kit Vibration Isolation Pads
Chiller Electrical Information Unit Voltage: 460-3-60 V-Ph-Hz Power Supply to control circuit: 115 Volts Power Supply to control circuit: 1 Phases
Electrical Electrical Amps Circuit 1 Circuit 2
MCA 316.8 ---
MOCP 400.0 ---
Max. ICF 451.8 --- Control Circuit Fuse Amps
15.0 ---
Packaged Chiller Builder NACO 3.74 Page 1 of 4
Prepared By: 06:24PM
Packaged Chiller Builder NACO 3.74 Page 2 of 4
Prepared By: 06:24PM
Integrated Part Load Value (AHRI) IPLV.IP: 0.5400 kW/Ton
Integrated Part Load Value (AHRI)
Cond. Ent. Water Temp., °F 85.00 75.00 65.00 65.00 Percent of Full Load Capacity, % 100.00 75.00 50.00 25.00 Cooling Capacity, Tons 263.9 197.8 131.9 65.93 Input Power, kW 174.2 126.6 64.25 30.81 Input, kW/Ton 0.6600 0.6398 0.4873 0.4673 Efficiency (EER), BTU/Wh 18.18 18.76 24.63 25.68 Saturated Condenser Temp.
Circuit A: 95.27 82.56 69.17 67.13 Circuit B: 95.37 84.14 70.95 70.95 Saturated Evaporator Temp.
Circuit A: 42.77 43.52 42.64 43.21 Circuit B: 42.72 41.96 24.45 25.30 Condenser Fouling Fact. Temp. Adj., °F 0.59 0.48 0.47 0.24 Total Inside Surface Area, Sq.Ft.
Circuit A: 534 534 534 534 Circuit B: 356 356 356 356 Evaporator Fouling Fact. Temp. Adj., °F 0.32 0.26 0.25 0.13
Circuit A: 381 381 381 381 Circuit B: 254 254 254 254
Nonstandard Part-Load Value NPLV.IP: 0.5158 kW/Ton NPLV.IP: 23.26 BTU/Wh
Nonstandard Part-Load Value
Cond. Ent. Water Temp., °F 80.00 72.50 65.00 65.00 Percent of Full Load Capacity, % 100.00 75.00 50.00 25.00 Cooling Capacity, Tons 263.8 203.4 135.6 67.80 Input Power, kW 191.0 121.4 63.89 30.53 Input, kW/Ton 0.7238 0.5971 0.4712 0.4503 Efficiency (EER), BTU/Wh 16.58 20.10 25.47 26.65 Saturated Condenser Temp.
Circuit A: 100.0 79.94 70.65 69.15 Circuit B: 101.9 81.44 71.50 71.50 Saturated Evaporator Temp.
Circuit A: 43.79 44.48 44.45 43.62 Circuit B: 43.70 43.00 43.64 24.34 Condenser Fouling Fact. Temp. Adj., °F 0.40 0.49 0.36 0.48
Circuit A: 534 534 534 534 Circuit B: 356 356 356 356 Evaporator Fouling Fact. Temp. Adj., °F 0.32 0.27 0.21 0.25
Packaged Chiller Builder NACO 3.74 Page 3 of 4
Prepared By: 06:24PM
Circuit A: 381 381 381 381 Circuit B: 254 254 254 254
Sound pressure level data used to develop this program was determined in accordance with AHRI Standard 575-2008 for water chillers in a free field.
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org
Packaged Chiller Builder NACO 3.74 Page 4 of 4
Drawings
CONDENSER
STANDARD
CONDENSER
MINUS ONE PASS
CONDENSER
STANDARD
CONDENSER
MINUS ONE PASS
CONDENSER
STANDARD
CONDENSER
MINUS ONE PASS
CONDENSER
EVAPORATOR
STANDARD
EVAPORATOR
STANDARD
EVAPORATOR
PLUS ONE
PASS EVAPORATOR
PLUS ONE
PASS EVAPORATOR
MINUS ONE
PASS EVAPORATOR
MINUS ONE
PASS EVAPORATOR
OVERALL LENGTH
152.54 [3875] 160.00 [4064] 160.00 [4064] 160.00 [4064] 160.00 [4064] 160.00 [4064]
NOTES:
1. Operating weight includes weight of water and refrigerant.
2. Denotes center of gravity.
3. Dimensions are in inches (mm).
4. Recommended service clearance around machine is 36 in. (914.4 mm).
5. Victaulic nozzles are standard on all models. Flow switch factory installed in evaporator inlet Victaulic nozzle.
30HXC206-271
UNIT
OPERATING
WEIGHT - lb
(kg)
A
WT. DISTIBUTION AT EACH
MOUNTING PLATE - lb (kg)
1 2 3 4 5 6
30HXC206
11056 (5015)
33.88 (860)
(449)
(1140)
(589)
(569)
(1485)
(782)
30HXC246
11144 (5056)
34.38 (873)
(454)
(1159)
(601)
(531)
(1510)
(799)
30HXC261
11167 (5066)
34.38 (873)
(454)
(1161)
(604)
(531)
(1513)
(802)
30HXC271
11204 (5083)
34.38 (873)
(454)
(1165)
(608)
(531)
(1518)
(806)
D im e n s io n s (c o n t)
Note: Evaporator head can be swapped by the contractor or Carrier Service in the field if needed.
File details come from the government source that posted it. Updated .