Paint Shop and Spray Room Drawings.pdf
PDF 5 MB Posted
- Attached to
- Paint Shop and Spray Room Construction
- Solicitation number
- 24-350SOS-SOS35-B-37577
- Issued by
- St. Clair County, Illinois
About this file
This document is an Invitation for Bid (IFB) from the Illinois Secretary of State for the renovation of an existing pre-engineered metal building to convert it into a maintenance paint and finishing shop. The project is located at 315 N. Klein Street in Springfield, Illinois. The work includes demolition, new construction, mechanical, electrical, and plumbing systems. No quantities are provided, but the full scope of work is detailed in the attached drawings and project manual. The bid is due on April 26, 2023. No site visit or bidder's conference is indicated. The contract award date is not specified. The contract term is not provided.
The IFB does not include any details on pricing terms, set asides, incumbents, funding requirements or sources, or other salient financial information. The document indicates this is a design-build contract, so the contractor will be responsible for providing a fully code compliant and coordinated system as part of the bid.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Limbaugh Notice of Award For BidBuy.pdf | ||
| Paint Shop Addenda No. 1~1.pdf | ||
| Project Manual Paint Shop and Spray Room.pdf | ||
| Paint Shop Addenda No. 2.pdf | ||
| Paint Shop and Spray Room IFB.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
212 North Illinois Avenue Carbondale, Illinois 62901-1452
Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 27 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C.
316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
D R e v it P ro je c ts
\R E
V
IT
\2
-0
H \2
-0
H
.r v t
TITLE SHEET AND LOCATION PLANSECRETARY OF STATE PAINT SHOP & SPRAY
ROOM
22.09
04-21-2023
BPC JEL G0.0
INDEX OF DRAWINGS
STATE LOCATION PLAN
KANKAKEE
VERMILION
LAWRENCE
PIATT
MORGAN
GREENE
MONROE
C A L H O U N
JERSEY
SCOTT
PIKE
BROWN
JEFFERSON
FRANKLIN
WILLIAMSON
JOHNSON
A L E X A N D E R
PULASKI
UNION
WASHINGTON
RANDOLPH PERRY
JACKSON
HARDIN
MASSAC
POPE
GALLATIN
WHITEHAMILTON
SALINE
WAYNE
WABASH
EDWARDS
MACON
SHELBY
MARION
MONTGOMERY
MADISON
ST CLAIR
BOND
CLINTON
FAYETTE
SANGAMON
MACOUPIN
CASS
MENARD
CHRISTIAN
JASPER
CUMBERLAND
CLAY
EFFINGHAM
RICHLAND
CRAWFORD
DOUGLAS
COLES
MOULTRIES
EDGAR
CLARK
HANCOCK
ADAMS
SCHUYLER
McDONOUGH
SON
HENDER-
MERCER
WARREN
ROCK ISLAND
LA SALLE
DE WITT
PEORIA
MASON
FULTON
LOGAN
TAZEWELL
WOODFORD
BUREAU
KNOX STARK
HENRY
MARSHALL
PUTNAM
IROQUOIS
FORD
CHAMPAIGN
McLEAN
GRUNDY
KENDALL
LIVINGSTON
WILL
WINNEBAGOSTEPHENSON
WHITESIDE
JO DAVIESS
CARROLL
LEE
OGLE
McHENRY
DE KALB
BOONE
KANE
DUPAGE
LAKE
COOK
CHICAGO
ST. LOUIS
SPRINGFIELD
NO SCALE
N
TITLE SHEET & LOCATION PLAN
DEMOLITION PLAN
HEALTH/ LIFE SAFETY PLAN
FLOOR PLAN
REFLECTED CEILING PLAN
WALL SECTIONS
DOOR SCHEDULE, ELEVATIONS, AND DETAILS
PLUMBING SYMBOLS, NOTES, ABBREVIATIONS, SCHEDULES AND DETAILS
PLUMBING DEMOLITION AND NEW WORK
PLUMBING SITE UTILITIES
PLUMBING DETAILS AND SCHEMATICS
FIRE PROTECTION DETAILS AND NOTES
FIRE PROTECTION FLOOR PLAN
MECHANICAL SYMBOLS AND DETAILS
MECHANICAL FLOOR PLAN
MECHANICAL SCHEDULES
MECHANICAL FLOOR PLANS
ELECTRICAL SYMBOLS AND ABBREVIATIONS
ELECTRICAL SITE PLAN
FIRST FLOOR ELECTRICAL DEMOLITION PLAN
FIRST FLOOR LIGHTING PLAN
FIRST FLOOR POWER PLAN
FIRST FLOOR SYSTEMS PLAN
ELECTRICAL ONE-LINE DIAGRAM
ELECTRICAL SCHEDULES
ELECTRICAL DETAILS
ELECTRICAL DETAILS
G0.0 D1.0 A0.0 A1.0 A2.0 A3.0 A4.0 P0.0 P1.0 P1.1 P2.0 F0.0 F1.0 M0.0
DM1.0
M0.1 M1.0 E0.0 E1.0
DE1.0
E2.0 E3.0 E4.0 E5.0 E6.0 E7.0 E7.1
SECRETARY OF STATE PAINT
SHOP & SPRAY ROOM
BUILDING LOCATION PLAN
NO SCALE
N
FOR:
SECRETARY OF STATE JOB NO. 22.09
APPLICABLE CODES:
2012 INTERNATIONAL BUILDING CODE
2012 INTERNATIONAL MECHANICAL CODE
2012 INTERNATIONAL FUEL GAS CODE
2018 ILLINOIS ENERGY CONSERVATION CODE
2014 ILLINOIS STATE PLUMBING CODE
2020 NATIONAL ELECTRICAL CODE
2012 INTERNATION FUEL GAS CODE
2006 FIRE CODE
316 NORTH KLEIN STREET
SPRINGFIELD, ILLINOIS 62702
316 NORTH KLEIN STREET
(AREA OF WORK)
ENGINEER
RTM ENGINEERING CONSULTANTS LLC,
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, ILLINOIS 62220
PHONE: (618) 277-5200
FAX: (618) 277-5227
CONTACT JIM LABLANCE
SEISMIC:
SITE CLASS D
OCCUPANCY CATAGORY II
DESIGN CATAGORY C
IMPORTANCE FACTOR 1.0
MAPPED SPECTRAL ACCELERATION AT SHORT PERIODS SS: 0.31
MAPPED SPECTRAL ACCELERATION AT 1-SECOND S1: 0.12
DESIGN SPECTRAL ACCELERATION AT SHORT PERIODS SDS: 0.25
DESIGN SPECTRAL ACCELERATION AT 1 SECOND SD1: 0.17
ARCHITECT
WHITE AND BORGOGNONI ARCHITECTS, P.C.
212 NORTH ILLINOIS AVENUE
CARBONDALE, ILLINOIS 62901-1452
PHONE: (618) 529-3691
ILLINOIS STATE CAPITAL BUILDING
(NO WORK)
E. MADISON ST.
E. MASON ST.
SIGNED 04/26/2023
LICENSE EXPIRES 11/30/23
SIGNED 04/26/2023
LICENSE EXPIRES 11/30/23
SIGNED 04/26/2023
LICENSE EXPIRES 11/30/23
ssatterlee Stamp
FD
FDFD
FDFD
070707
19 21
OVERLAP
4" MIN
1'
4"
MIN
6"
MIN
6"VARIES
PROVIDE NEW 4" CONCRETE
SLAB REINFORCED WITH #4
REBAR @ 16" O.C. IN 15 MIL POLY
VAPOR BARRIER ON
COMPACTED AGGREGATE
INFILL. COORDINATE WITH
PLUMBING DRAWINGS - TYPICAL.
PLAN VIEW
OVERLAP
4" MIN
MIN
6"
MIN
6"
VARIES
SECTION
PROVIDE 15 MIL POLY
VAPOR BARRIER.
EXISTING CONCRETE SLAB
TO REMAIN - TYPICAL.
EXISTING CONCRETE SLAB
TO REMAIN - TYPICAL.
SEE PLUMBING DRAWINGS FOR
UNDERSLAB BACKFILL DETAIL.
PROVIDE #4 REBAR.
DOWEL INTO EXISTING
CONCRETE SLAB,
STAGGER, AND TIE
TOGETHER @ 16 O.C.
212 North Illinois Avenue Carbondale, Illinois 62901-1452 Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 23 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C. 316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
T
CETIHCRADESNE
CI
OFETATS
ILLI
I
NO
SEXP.
L VAN V.
VOYLES
001-012444
/21
/20
11/30/24
DEMOLITION PLANSECRETARY OF STATE PAINT SHOP AND
SPRAY ROOM
22.09
04-21-2023
CIM VVV D1.0
D1.0
1 DEMOLITION PLAN
0' 2' 4' 8'
SCALE: 1/4" = 1-0'
N
KEYNOTE LEGEND
MARK KEYNOTE TEXT
03 REMOVE EXISTING DOOR, FRAME, AND HARDWARE.
06 REMOVE EXISTING EXHAUST FAN AND HOOD. SEE MEP DRAWINGS.
07 REMOVE EXISTING CONTROL EQUIPMENT. SEE MEP DRAWINGS.
08 REMOVE EXISTING EXHAUST FAN LOUVERS. SEE MEP DRAWINGS.
14 REMOVE PORTION OF EXISTING 8" CMU PARTITION TO INSTALL NEW
DOOR AND FRAME.
19 SAW-CUT, REMOVE, AND DISPOSE OF EXISTING CONCRETE SLAB.
EXCAVATE AS REQUIRED TO REMOVE EXISTING AND PROVIDE NEW
PLUMBING. PROVIDE NEW FILL AND CONCRETE SLAB, SEE DETAIL
2/D1.0. COORIDINATE WITH PLUMBING DRAWINGS.
21 REMOVE PORTION OF EXISTING EXTERIOR WALL INCLUDING EXTERIOR
METAL SIDING, INSULATION, AND INTERIOR METAL SIDING PANEL,
COORDINATE WITH NEW CONSTRUCTION.
D1.0
2 CONCRETE SLAB INFILL DETAIL
0'6"1' 6" 1'
SCALE: 1 1/2"=1'-0"
3"9"
WHITE & BORGOGNONI ARCHITECTS, P.C. ILLINOIS LICENSED PROFESSIONAL SERVICE CORPORATION #184.003602
CONTRACTOR SHALL OBTAIN AND VERIFY ALL DIMENSIONS AND CONDITIONS AT THE JOB SITE AND BE FULLY REPSPONSIBLE FOR THE SAME.
FDFD
FDFD
SUPPLY PLENUM
DROP OFF / PREP
EXHAUST PLENUM
OFFICE
STORAGE /
COMPRESSOR
TOILET
MECHANICAL
ROOM
DRYING / PICK UP
PAINT ROOM
101.2
102.3
101.1
100.2
100.1
C/O
451 GSF
÷ 100 GSF/OCCUPANTS
= 5 OCCUPANTS
524 GSF
÷ 100 GSF/OCCUPANTS
= 6 OCCUPANTS
61 GSF
÷ 100 GSF/OCC.
= 1 OCC.
178 GSF
÷ 100 GSF/OCCUPANTS
= 2 OCCUPANTS
208 GSF
÷ 100 GSF/OCCUPANTS
= 3 OCCUPANTS
811 GSF
÷ 100 GSF/OCCUPANTS
= 9 OCCUPANTS
MAX. EXIT ACCESS TRAVEL DISTANCE
=98' - 0" (250' ALLOWABLE)
FE
FE
FE
102.1
102.2
MAX. EXIT ACCESS TRAVEL DISTANCE
=98' - 0" (250' ALLOWABLE)
Room name
ROOM NAME - SEE ROOM FINISH SCHEDULE
ROOM NUMBER - SEE ROOM FINISH SCHEDULE
DOOR NUMBER - SEE DOOR SCHEDULE
WALL MOUNT FIRE EXTINGUISHER (FURNISHED
AND INSTALLED BY OWNER. SEE DETAIL 2/A1.0.
FE
1 HR FIRE RATED ASSEMBLY.
SEE PARTITION TYPES, SHEET A1.0
2 HR FIRE RATED ASSEMBLY.
SEE PARTITION TYPES, SHEET A1.0
212 North Illinois Avenue Carbondale, Illinois 62901-1452 Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 23 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C. 316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
T
CETIHCRADESNE
CI
OFETATS
ILLI
I
NO
SEXP.
L VAN V.
VOYLES
001-012444
/21
/20
11/30/24
HEALTH/LIFE SAFETY PLANSECRETARY OF STATE PAINT SHOP AND
SPRAY ROOM
22.09
04-21-2023
CIM VVV A0.0
0' 2' 4' 8'
SCALE: 1/4" = 1-0'
NA0.0
1 HEALTH/LIFE SAFETY PLAN
APPLICABLE CODES
BUILDING SUMMARY
KEY
INTERNATIONAL BUILDING CODE 2018
INTERNATIONAL FIRE CODE 2018
NATIONAL FIRE PROTECTION ASSOCIATION 33
OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION 1926.66
IBC CONSTRUCTION TYPE: TYPE IIIB
IBC USE GROUP OCCUPANCY:
GROUP F-1 (MODERATE HAZARD FACTORY, INDUSTRIAL)
ALLOWABLE BUILDING AREA (SF/FLOOR):
40,000 SF, 2,422 SF ACTUAL
ALLOWABLE BUILDING HEIGHT:
75 FEET, 18 FT. ACTUAL
3 STORIES, 1 ACTUAL
NOTE: ALL DOORS AND CORRIDORS
EASILY EXCEED REQUIRED EXIT CAPACITY.
CONTRACTOR SHALL OBTAIN AND VERIFY ALL DIMENSIONS AND CONDITIONS AT THE JOB SITE AND BE FULLY REPSPONSIBLE FOR THE SAME.
FDFD
FDFD
SUPPLY PLENUM
DROP OFF / PREP
EXHAUST PLENUM
OFFICE
STORAGE /
COMPRESSOR
TOILET
MECHANICAL
ROOM
DRYING / PICK UP
PAINT ROOM
A3.0
101.2
102.3
101.1
100.2
100.1
A
F A
A
A
A
F
CO
7/
8"
7/ 8"
9'
3/
8"
7/ 8"
5'
/8
1/
4"
5/ 8" 6"
3 3/4" 3 5/8"12' - 2 1/8"
3 3/4" 1' - 6"3' - 0"12' - 11 7/8"4 7/8"6' - 4 1/8"
3 5/8" 4 1/4"
3'
3/
8"
1/ 4"
/8
1/
4" 3'
3/ 8"
A2.0
A3.0
FE
B
B
D
B
B
C
143 141A2.03
A3.0
11' - 8 3/4"
/8
11' - 8 3/4"8 1/2"8' - 10 1/8"4 7/8"15' - 7 3/4"
E
E
EXG
CMU
102.1
ACTIVE LEAF
A3.0
C
102.2
FE
FE
C
171171
172 172
A3.0
3'
8"
C
B
PROVIDE NEW 5/8" TYPE 'X' GYPSUM BOARD, FINISHED AND PAINTED.
PROVIDE NEW ACOUSTICAL BATT INSULATION.
PROVIDE NEW 3-5/8" METAL STUDS AT 1'-4" O.C. (MAX.)
PROVIDE NEW 5/8" TYPE 'X' GYPSUM BOARD, FINISHED AND PAINTED.
7/
8"
5/ 8"
5/
8" 5/
8"
UL DESIGN U419 (1 hr. Rated)
3' -6
" T O
T O
P O
F
EX
TI
N
G U
IS
H
ER
AT
B R
AC
KE
T M
O U
N
TE
D T
YP
E
SURFACE
MOUNTED FIRE
EXTINGUISHER
BRACKET.
Room name
KEY
ROOM NAME - SEE ROOM FINISH SCHEDULE
ROOM NUMBER - SEE ROOM FINISH SCHEDULE
DOOR NUMBER - SEE DOOR SCHEDULE
PARTITION TYPE. SEE SHEET A1.0
DETAIL NUMBER
SHEET NUMBER
WALL MOUNT FIRE EXTINGUISHER (FURNISHED
AND INSTALLED BY OWNER. SEE DETAIL 2/A1.0.
A
FE
A1.0
SIM
CO PLUMBING CLEANOUT.
FD FLOOR DRAIN.
PROVIDE NEW 5/8" TYPE 'X' GYPSUM BOARD, FINISHED AND PAINTED.
PROVIDE NEW 3-5/8" METAL STUDS AT 1'-4" O.C. (MAX.)
1/
4"
5/ 8"
5/ 8"
EXISTING WALL TO REMAIN.
PROVIDE NEW 5/8" TYPE 'X'
GYPSUM BOARD.
6"
1"1 1/
2" 5/
8" 5/
8"
5/
8"
5/ 8"
EXISTING WALL TO REMAIN.
PROVIDE NEW 1" GYPSUM LINER
PANEL.
PROVIDE NEW 2 1/2" C-H STUDS,
24" OC.
PROVIDE NEW STEEL PANEL ADHERED
TO GYPSUM BOARD.
UL DESIGN U415 System B (2 hr. Rated)
PROVIDE NEW 5/8" TYPE 'X' GYPSUM BOARD.
PROVIDE NEW 3-5/8" METAL STUDS AT 1'-4" O.C. (MAX.)
PAINT ROOM 102
PROVIDE (2) NEW 5/8" TYPE 'X'
GYPSUM BOARD.
PROVIDE NEW 1" GYPSUM LINER PANEL.
PROVIDE NEW 2 1/2" C-H STUDS, 24" OC.
5/ 8"
5/ 8"
1/
2" 1"
UL DESIGN U415 System B (2 hr. Rated)
PROVIDE (2) NEW 5/8" TYPE 'X' GYPSUM BOARD.
PROVIDE NEW ACOUSTICAL BATT INSULATION.
PROVIDE NEW 6" METAL STUDS AT 1'-4" O.C. (MAX.)
PROVIDE (2) NEW 5/8" TYPE 'X' GYPSUM BOARD, FINISHED AND PAINTED.
1/
2" 5/
8" 5/
8" 6"
5/ 8"
5/ 8"
UL DESIGN U419 (2 hr. Rated)
PROVIDE NEW STEEL PANEL ADHERED
TO GYPSUM BOARD.
PAINT ROOM 102
SYMBOL / LOCATION SIGNAGE TYPETEXT / GRAPHICS
ADJACENT TO
DOOR
INDICATED ON
PLAN, 5'-0"
ABOVE FLOOR
TO C OF SIGN
L
9 1/2" HIGH X 7" WIDE
PLASTIC SIGN WITH
GRADE 2 BRAILLE, AND
5/8" MIN. HIGH CAPITAL
LETTERS RAISED 1/32".
PICTOGRAM(S) AS
SHOWN (MIN.)
(SEE SPECIFICATION 10 14 01)
STORAGE
3" HIGH X 8" WIDE
PLASTIC SIGN WITH GRADE 2
BRAILLE, AND 5/8" MIN. HIGH
CAPITAL LETTERS RAISED
1/32".
PROVIDE ROOM NUMBER PER
FLOOR PLAN
ADJACENT TO
DOOR, 5'-0"
ABOVE FLOOR
TO TOP OF SIGN
OFFICE
3" HIGH X 8" WIDE
PLASTIC SIGN WITH GRADE 2
BRAILLE, AND 5/8" MIN. HIGH
CAPITAL LETTERS RAISED
1/32".
PROVIDE ROOM NUMBER PER
FLOOR PLAN
ADJACENT TO
DOOR, 5'-0"
ABOVE FLOOR
TO TOP OF SIGN
MECHANICAL
3" HIGH X 8" WIDE
PLASTIC SIGN WITH GRADE 2
BRAILLE, AND 5/8" MIN. HIGH
CAPITAL LETTERS RAISED
1/32".
PROVIDE ROOM NUMBER PER
FLOOR PLAN
ADJACENT TO
DOOR, 5'-0"
ABOVE FLOOR
TO TOP OF SIGN
GENDER NEUTRAL
RESTROOM
SIGNAGE SCHEDULE
PAINT ROOM
3" HIGH X 8" WIDE
PLASTIC SIGN WITH GRADE 2
BRAILLE, AND 5/8" MIN. HIGH
CAPITAL LETTERS RAISED
1/32".
PROVIDE ROOM NUMBER PER
FLOOR PLAN
ADJACENT TO
DOOR, 5'-0"
ABOVE FLOOR
TO TOP OF SIGN
PAINT ROOM 102
PROVIDE NEW STEEL PANEL ADHERED TO GYPSUM BOARD.
PROVIDE NEW 5/8" TYPE 'X' GYPSUM BOARD
PROVIDE NEW 3-5/8" METAL
STUDS AT 1'-4" O.C. (MAX.)
5/
8" 5/
8"
A1.0
1 FLOOR PLAN
212 North Illinois Avenue Carbondale, Illinois 62901-1452 Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 23 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C. 316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
T
CETIHCRADESNE
CI
OFETATS
ILLI
I
NO
SEXP.
L VAN V.
VOYLES
001-012444
/21
/20
11/30/24
FLOOR PLANSECRETARY OF STATE PAINT SHOP AND
SPRAY ROOM
22.09
04-21-2023
CIM VVV A1.0
0' 2' 4' 8'
SCALE: 1/4" = 1-0'
Room Finish Schedule
Room Number Room Name Flooring Base
Walls Fire Rating RemarksNorth East South West
100 DROP OFF / PREP EXG CONCRETE EXG PAINT EXG EXG EXG EXG ---
101 DRYING / PICK UP EXG CONCRETE EXG / VINYL EXG PTD GYP PTD GYP / PAINT EXG PTD GYP --- 102 PAINT ROOM EXG CONCRETE NONE METAL PANEL METAL PANEL METAL PANEL METAL PANEL 2 HR
103 OFFICE EXG CONCRETE VINYL PTD GYP PTD GYP PTD GYP PTD GYP ---
104 STORAGE / COMPRESSOR EXG CONCRETE VINYL PTD GYP PTD GYP PTD GYP PTD GYP 1 HR
105 TOILET EXG CONCRETE VINYL PTD GYP PTD GYP PTD GYP PTD GYP ---
106 MECHANICAL ROOM EXG CONCRETE VINYL PTD GYP PTD GYP PTD GYP PTD GYP 1 HR
A1.0
2 FIRE EXTINGUISHER DETAIL (BY OWNER)
N
WALL TYPE C
WALL TYPE D
WALL TYPE B
WALL TYPE A
KEYNOTE LEGEND
MARK KEYNOTE TEXT
140 EMERGENCY EYE WASH STATION - SEE PLUMBING DRAWINGS.
141 DRYING RACK - BY OWNER.
142 NEW PLUMBING FIXTURE, SEE PLUMBING DRAWINGS.
143 WORKBENCH - BY OWNER.
144 UPPER WALL CABINETS - BY OWNER.
165 ADJUST HINGES AND/OR LOCKSET SO THAT DOOR OPERATES
AND CLOSES PROPERLY.
171 FLAMMABLES CABINET - BY OWNER.
172 SEAL TOP OF WALL TO DECK.
189 PROVIDE NEW REINFORCED CONCRETE SLAB. 1/4" PER 12" MAX
SLOPE. SUPPORT REIFORCING ON CHAIRS. DOWEL TO EXISTING
SLAB BELOW. WIDTH OF SLAB TO BE WIDTH OF DOOR (MIN.),
DEPTH TO BE 3'-8" FROM DOOR THRESHOLD.
WALL TYPE E
0'6"1' 6" 1'
SCALE: 1 1/2"=1'-0"
3"9"
WALL TYPE F
CONTRACTOR SHALL OBTAIN AND VERIFY ALL DIMENSIONS AND CONDITIONS AT THE JOB SITE AND BE FULLY REPSPONSIBLE FOR THE SAME.
MECHANICAL
ROOM
GYP BD
9' - 0"
TOILET
GYP BD
9' - 0"
STORAGE /
COMPRESSOR
GYP BD
9' - 0"
OFFICE
GYP BD
9' - 0"
DROP OFF / PREP
EXPOSED
STRUCTURE
PAINT ROOM
METAL PANEL
10' - 0"
DRYING / PICK UP
EXPOSED
STRUCTURE
1'
3/
8" 2'
1"
4'
3" 1'
6"
A2.03
9'
0"
903903
9'
0"
906 906
903903
9'
0"
PAINT ROOM
KEY
ROOM NAME - SEE ROOM FINISH SCHEDULE
ROOM NUMBER - SEE ROOM FINISH SCHEDULE
METAL PANEL
10' - 0"
CEILING MATERIAL / FINISH
CEILING HEIGHT
EXHAUST FAN - SEE MEP DRAWINGS
FAN COIL UNIT - SEE MEP DRAWINGS
LIGHT FIXTURE - SEE MEP DRAWINGS
GYPSUM BOARD
METAL PANELING
1 HR FIRE RATED ASSEMBLY.
SEE PARTITION TYPES, SHEET A1.0
2 HR FIRE RATED ASSEMBLY.
SEE PARTITION TYPES, SHEET A1.0
ABBREVIATIONS
METAL PANEL
GYP BD
EXPOSED
STRUCTURE
METAL INTERIOR WALL AND CEILING PANEL
SYSTEMS - SEE SPECS
5/8" TYPE X GYPSUM BOARD.
FINISHED AND PAINTED. - SEE SPECS
EXPOSED STRUCTURE, INSULATION, AND MEP.
212 North Illinois Avenue Carbondale, Illinois 62901-1452 Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 23 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C. 316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
T
CETIHCRADESNE
CI
OFETATS
ILLI
I
NO
SEXP.
L VAN V.
VOYLES
001-012444
/21
/20
11/30/24
REFLECTED CEILING PLANSECRETARY OF STATE PAINT SHOP AND
SPRAY ROOM
22.09
04-21-2023
CIM VVV A2.0
0' 2' 4' 8'
SCALE: 1/4" = 1-0'
NA2.0
1 REFLECTED CEILING PLAN
A2.0
5 LARGE SCALE PLAN - TOILET
0' 2' 4' 8'
SCALE: 1/2" = 1-0'
A2.0
2 TOILET INTERIOR ELEVATION
A2.0
3 TOILET INTERIOR ELEVATION
A2.0
4 TOILET INTERIOR ELEVATION
KEYNOTE LEGEND
MARK KEYNOTE TEXT
160 PROVIDE NEW VINYL BASE. SEE SPECS.
900 PROVIDE NEW 3'-0" LONG, 1-1/2" DIAMETER GRAB BAR.
MOUNT 2'-10" TO TOP FROM FINISH FLOOR, LOCATED TO
EXTEND FROM THE CENTERLINE OF THE WATER CLOSET
12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM
ON THE OTHER SIDE. SEE SPECS.
901 PROVIDE NEW 3'-6" LONG, 1-1/2" DIAMETER GRAB BAR.
MOUNT 2'-10" TO TOP FROM FINISH FLOOR, LOCATED 12
INCHES MAXIMUM FROM THE REAR WALL AND EXTENDING
54 INCHES MINIMUM FROM THE REAR WALL. SEE SPECS.
902 PROVIDE NEW SURFACE MOUNTED TWO ROLL TOILET
TISSUE DISPENSER. MOUNT 2'-0" TO C.L. FROM FINISH
FLOOR AND 2'-6" TO C.L. FROM REAR WALL. SEE SPECS.
903 PROVIDE NEW PLUMBING FIXTURE. SEE PLUMBING
DRAWINGS AND SPECS, TYPICAL.
904 PROVIDE NEW METAL FRAMED MIRROR 24" WIDE X 36"
HIGH. SEE SPECS. MOUNT 40" FROM FINISHED FLOOR
SURFACE (MAX.).
906 PROVIDE NEW TOWEL DISPENSER. MOUNT 44" TO
BOTTOM OF UNIT. SEE SPECS.
913 PROVIDE NEW SOAP DISPENSER. MOUNT 44" TO BOTTOM
OF UNIT. SEE SPECS.
0' 2' 4' 8'
SCALE: 1/2" = 1-0'
0' 2' 4' 8'
SCALE: 1/2" = 1-0'
0' 2' 4' 8'
SCALE: 1/2" = 1-0'
WHITE & BORGOGNONI ARCHITECTS, P.C. ILLINOIS LICENSED PROFESSIONAL SERVICE CORPORATION #184.003602
CONTRACTOR SHALL OBTAIN AND VERIFY ALL DIMENSIONS AND CONDITIONS AT THE JOB SITE AND BE FULLY REPSPONSIBLE FOR THE SAME.
N
6"
1" 1 1/2"
5/8"5/8"
3 5/8" 5/8"
154150
177177
181181
181181
13' - 10 1/2"113' - 5 1/2" +/-
FIELD VERIFY
10' - 5"110' - 0"
D
4 1/4" 3 5/8"
13' - 10 1/2"
0' - 5"
113' - 5 1/2" +/-
FIELD VERIFY
100' - 0"
ASSUMED
151151
181181
181181
9' - 4 7/8"109' - 0"
FIELD VERIFY
C
150150150
8 1/2"
10' - 5"110' - 0"
E
178178
177177
181181
181181
13' - 10 1/2"113' - 5 1/2" +/-
FIELD VERIFY
9' - 4 3/8"109' - 0"
C
4 1/4" 3 5/8"
A3.0
A3.0
NEW
EXG
EXTERIORINTERIOR
NEW
EXG
183111
EXTERIORINTERIOR
NEW
EXG
EXTERIORINTERIOR
187187
212 North Illinois Avenue Carbondale, Illinois 62901-1452 Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 23 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C. 316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
T
CETIHCRADESNE
CI
OFETATS
ILLI
I
NO
SEXP.
L VAN V.
VOYLES
001-012444
/21
/20
11/30/24
WALL SECTIONSSECRETARY OF STATE PAINT SHOP AND
SPRAY ROOM
22.09
04-21-2023
CIM VVV A3.0
A3.0
3 PAINT BOOTH EXT. WALL SECTION
0'6"1' 6" 1'
SCALE: 1"=1'-0"
3"9"
KEYNOTE LEGEND
MARK KEYNOTE TEXT
108 PROVIDE NEW 3-5/8" METAL STUDS AT 1'-4" O.C. MAX.
111 PROVIDE NEW BATT INSULATION BETWEEN STUDS.
131 PROVIDE NEW 8" METAL STUDS AT 1'-4" O.C. MAX.
150 PROVIDE TWO (2) NEW LAYERS OF 5/8" TYPE 'X'
GYPSUM BOARDS.
151 PROVIDE NEW 18 GA. GALVANIZED STEEL EDGE TRIM,
UNFINISHED.
152 PROVIDE NEW 18 GA. GALVANIZED SHEET STEEL,
UNFINISHED.
153 PROVIDE NEW PARTITION WALL CONSTRUCTED WITH
METAL STUDS 1'-4" ON CENTER MAXIMUM, TWO (2)
LAYERS 5/8" GYPSUM BOARD EACH SIDE, 18ga.
GALANIZED SHEET STEEL PAINT ROOM SIDE,
UNFINISHED. AND ACOUSTICAL BATT INSULATION
BETWEEN. PAINT CORRIDIR SIDE.
154 PROVIDE NEW 8" x 2" METAL STUDS, 18 GA, @ 16" O.C.
AS CEILING JOISTS. ALIGN WITH STUDS ON BEARING
WALLS.
155 PROVIDE NEW 6" METAL STUDS, 18 GA.
157 PROVIDE NEW 5/8" TYPE 'X' GYPSUM BOARD.
160 PROVIDE NEW VINYL BASE. SEE SPECS.
161 PROVIDE NEW BATT INSULATION. TYP.
163 PROVIDE NEW 2 1/2" CH METAL STUDS @ 24" O.C.
164 PROVIDE NEW 1" GYPSUM LINER PANEL.
167 PROVIDE NEW HORITZONTAL BRIDGING @ 48" O.C.
(MAX.)
177 EXISTING STEEL COLUMN TO REMAIN. TYP.
178 EXISTING STEEL BEAM TO REMAIN. TYP.
179 EXISTING METAL ROOFING TO REMAIN. TYP.
180 EXISTING INSULATION SYSTEM TO REMAIN. TYP.
181 EXISTING EXTERIOR WALL TO REMAIN. TYP.
182 EXISTING METAL SIDING TO REMAIN. TYP.
183 PROVIDE NEW COLOR COATED METAL SIDING PATCH
TO MATCH EXISTING. FASTEN TO NEW METAL STUDS.
SEE SPECS. SEE DETAILS 5, 6, & 7/SHEET A3.0
184 PROVIDE NEW SEALANT AT AROUND ALL EDGES OF
NEW SIDING. SEE SPECS.
185 PROVIDE NEW COLOR COATED DRIP FLASHING. FASTEN
TO STRUCTURE BEHIND. CAULK CONTINUOUS WITH
SEALANT. SEE SPECS.
187 FASTEN EXISTING METAL SIDING TO STRUCTURE
BEHIND. PROVIDE NEW METAL STUDS AS REQUIRED.
188 PROVIDE NEW COLOR COATED SPLICING FLASHING.
194 REMOVE AND DISPOSE OF EXISTING METAL TRIM.
A3.0
1 RESTROOM EXT. WALL SECTION
0'6"1' 6" 1'
SCALE: 1"=1'-0"
3"9"
A3.0
2 PAINT BOOTH CORRIDOR WALL SECTION
0'6"1' 6" 1'
SCALE: 1"=1'-0"
3"9" A3.0
4 STORAGE/COMPRESSOR EXT. WALL SECTION
0'6"1' 6" 1'
SCALE: 1"=1'-0"
3"9"
A3.0
5 EXTERIOR WALL LOUVER INFILL PANEL - HEAD
A3.0
6 EXTERIOR WALL LOUVER INFILL PANEL - JAMB
A3.0
7 EXTERIOR WALL LOUVER INFILL PANEL - SILL
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
CONTRACTOR SHALL OBTAIN AND VERIFY ALL DIMENSIONS AND CONDITIONS AT THE JOB SITE AND BE FULLY REPSPONSIBLE FOR THE SAME.
4 7/8"
5 3/4"
2"
5/8" 3 5/8" 5/8"
4 7/8"
5 3/4"
2"
5/8" 3 3/4" 5/8"
5 3/4"
4"
NEW
EXG
7 5/8"
5 3/4"
2"
7 5/8"
NEW
EXG
3' - 0"
7'
0"
7'
0"
7' - 0"
A B
3' - 6" 3' - 6"
3'
5" 2'
9"
"6" 3"
3' - 0"
7'
0"
C
7'
0"
7' - 0"
D
2'
9" 3'
5"
3" 6"
3' - 4"
2" 3' - 0" 2"
7'
2" 2"
7'
0"
7' - 4"
2" 7' - 0" 2"
7'
4"
4" 7'
0"
A B
170170 174175
152152 152152PAINT ROOM
195195
5/8" 5/8" 6" 5/8" 5/8"
8 1/2"
5/8" 5/8" 6" 5/8" 5/8"
8 1/2"
2"
5/8" 5/8" 6" 5/8" 5/8"
8 1/2"
9 1/2"
5/8" 5/8" 6" 5/8" 5/8"
2"
8 1/2"
9 1/2"
1"
2" 3/
8" 136
107193 106
1"
2" 3/
8" 136
107193 106
10 1/2"
191191
191191
192192
212 North Illinois Avenue Carbondale, Illinois 62901-1452 Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 23 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C. 316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
T
CETIHCRADESNE
CI
OFETATS
ILLI
I
NO
SEXP.
L VAN V.
VOYLES
001-012444
/21
/20
11/30/24
DOOR SCHEDULE, ELEVATIONS, & DETAILSSECRETARY OF STATE PAINT SHOP AND
SPRAY ROOM
22.09
04-21-2023
CIM VVV A4.0
A4.0
3 TYPICAL DOOR HEAD DETAIL
A4.0
4 TYPICAL DOOR JAMB DETAIL
A4.0
5 CMU DOOR HEAD DETAIL
A4.0
6 CMU DOOR JAMB DETAIL
Door Schedule
Door Number Door Size
Door Elev.
Door Mat.
Frame Elev.
Frame Mat.
Details Glazing
Hardware Group
Fire Rating RemarksHead Jamb Sill
100.1 3'-0" x 7'-0"x1 3/4" - EXG - EXG - - - - 7 - EXG DOOR, ADD NEW ELECTRIC STRIKE
100.2 8'-0" x 10'-0" - EXG - EXG - - - - - - EXG DOOR, ADD NEW DOOR OPERATOR 101 3'-0" x 7'-0"x1 3/4" - EXG - EXG - - - - 6 -
101.1 7'-0" x 7'-0" x 1 3/4" 9B/A4.0 HM 10B/A4.0 HM 5/A4.0 6/A4.0 - SAFETY 1 -
101.2 8'-0" x 10'-0" - EXG - EXG - - - - - - EXG DOOR, ADD NEW DOOR OPERATOR
102.1 3'-0" x 7'-0" x 1 3/4" 9C/A4.0 HM 10A/A4.0 HM 1/A4.0 2/A4.0 - FIRE RATED 5 1-1/2 HR
102.2 3'-0" x 7'-0" x 1 3/4" 9C/A4.0 HM 10A/A4.0 HM 1/A4.0 2/A4.0 - FIRE RATED 5 1-1/2 HR
102.3 7'-0" x 7'-0" 9D/A4.0 STEEL - - 7/A4.0 8/A4.0 - - - 1-1/2 HR 103 3'-0" x 7'-0" x 1 3/4" 9A/A4.0 HM 10A/A4.0 HM 3/A4.0 4/A4.0 - NONE 2 - 104 3'-0" x 7'-0" x 1 3/4" 9A/A4.0 HM 10A/A4.0 HM 3/A4.0 4/A4.0 - NONE 3 3/4 HR 105 3'-0" x 7'-0" x 1 3/4" 9A/A4.0 HM 10A/A4.0 HM 3/A4.0 4/A4.0 - NONE 4 - 106 3'-0" x 7'-0" x 1 3/4" 9A/A4.0 HM 10A/A4.0 HM 3/A4.0 4/A4.0 - NONE 3 3/4 HR
KEYNOTE LEGEND
MARK KEYNOTE TEXT
106 PROVIDE NEW DOOR.
107 PROVIDE NEW HOLLOW METAL DOOR FRAME. FILL FRAME
WITH BATT INSULATION.
109 PROVIDE NEW METAL STUD HEADER.
110 PROVIDE NEW DOUBLE STUD AT JAMBS.
111 PROVIDE NEW BATT INSULATION BETWEEN STUDS.
112 PROVIDE NEW 5/8" TYPE 'X' GYPSUM BOARD. FINISH AND
PAINT.
113 PROVIDE NEW SEALANT.
133 PROVIDE NEW HOLLOW METAL FRAME.
134 PROVIDE NEW MASONRY ANCHOR. THREE PER JAMB.
135 GROUT HOLLOW METAL FRAME SOLID. SEE SPECS.
-TYPICAL.
136 PROVIDE NEW BACKER ROD AND SEALANT. -TYPICAL.
137 PROVIDE NEW 8" CMU TO MATCH ADJACENT WALL
CONSTRUCTION. TOOTH-IN NEW MASONRY AS REQUIRED
-TYPICAL. NOTCH WEB AS REQUIRED TO RECEIVE STEEL
LINTEL.
138 EXISTING 8" CMU WALL CONSTRUCTION TO REMAIN.
139 PROVIDE (2) NEW 3-1/2" X 3-1/2" X 3/8" STRUCTURAL STEEL
LINTEL. WELDED & PAINTED. SEE SPECS.
A4.0
9 DOOR ELEVATIONS
A4.0
10 DOOR FRAME ELEVATIONS
A4.0
11 METAL PANEL DETAIL
A4.0
8 COILING DOOR JAMB DETAIL
A4.0
7 COILING DOOR HEAD DETAIL
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
0' 2' 4' 8'
SCALE: 1/4" = 1-0'
0' 2' 4' 8'
SCALE: 1/4" = 1-0'
A4.0
1 DOOR HEAD DETAIL
A4.0
2 DOOR JAMB DETAIL
A4.0
13 EXTERIOR DOOR HEAD DETAIL
A4.0
14 EXTERIOR DOOR JAMB DETAIL
01' 9" 3"6"
SCALE: 3"=1'-0"
01' 9" 3"6"
SCALE: 3"=1'-0"
A4.0
12 EXTERIOR DOOR SILL DETAIL
01' 9" 3"6"
SCALE: 3"=1'-0"
KEYNOTE LEGEND
MARK KEYNOTE TEXT
150 PROVIDE TWO (2) NEW LAYERS OF 5/8" TYPE 'X' GYPSUM
BOARDS.
151 PROVIDE NEW 18 GA. GALVANIZED STEEL EDGE TRIM,
UNFINISHED.
152 PROVIDE NEW 18 GA. GALVANIZED SHEET STEEL,
UNFINISHED.
157 PROVIDE NEW 5/8" TYPE 'X' GYPSUM BOARD.
169 PROVIDE NEW OUTSIDE CORNER. 18ga. GALVANIZED SHEET
STEEL, UNFINISHED.
170 PROVIDE NEW ADHESIVE. SEE SPECS.
173 PROVIDE NEW DOOR. SEE DOOR SCHEDULE.
174 PROVIDE NEW INSIDE CORNER. 18ga. GALVANIZED SHEET
STEEL, UNFINISHED.
175 PROVIDE NEW SPLICE TRANSITION. 18ga. GALVANIZED
SHEET STEEL, UNFINISHED.
176 PROVIDE NEW OVERHEAD COILING DOOR SYSTEM.
181 EXISTING EXTERIOR WALL TO REMAIN. TYP.
182 EXISTING METAL SIDING TO REMAIN. TYP.
185 PROVIDE NEW COLOR COATED DRIP FLASHING. FASTEN TO
STRUCTURE BEHIND. CAULK CONTINUOUS WITH SEALANT.
SEE SPECS.
189 PROVIDE NEW REINFORCED CONCRETE SLAB. 1/4" PER 12"
MAX SLOPE. SUPPORT REIFORCING ON CHAIRS. DOWEL TO
EXISTING SLAB BELOW. WIDTH OF SLAB TO BE WIDTH OF
DOOR (MIN.), DEPTH TO BE 3'-8" FROM DOOR THRESHOLD.
190 PROVIDE 1/2" EXPANSION MATERIAL WITH CONTINUOUS
SEALANT AT TOP/EXPOSED EDGE.
191 EXISTING CONCRETE SLAB TO REMAIN.
192 EXISTING FOUNDATION WALL TO REMAIN. MODIFY AS
NECESSARY TO ALLOW INSTALLATION OF NEW EXTERIOR
DOOR AT THIS LOCATION ONLY.
193 PROVIDE NEW COLOR COATED METAL TRIM. SEE SPECS.
195 SEE WALL TYPE 'E' , SHEET A1.0 FOR WALL CONSTRUCTION.
CONTRACTOR SHALL OBTAIN AND VERIFY ALL DIMENSIONS AND CONDITIONS AT THE JOB SITE AND BE FULLY REPSPONSIBLE FOR THE SAME.
PIPE
SUPPORTS
(TYPICAL)
2" DOMESTIC WATER
SERVICE TO SYSTEM
PRESSURE
GAUGE
BALL
VALVE
(TYP)
FINISH FLOOR
4" COMBINATION
FIRE &
DOMESTIC
SERVICE
TERMINATE
RELIEF
OVERFLOW
DRAIN
2" DR.
VALVE
LINK SEAL FLOOR
PENETRATIONS
BFP
BY F.P.C.
RPZ
PROVIDE BLIND FLANGE TEE FOR
POSSIBLE FUTURE CONNECTION
TO COOLING TOWER MAKEUP.
CHECK VALVE (TYP)
SHUTOFF
VALVE (TYP)
HEAT TRAP EXPANSION TANK
AMTROL "THERM-X-
TROL" #ST-12
T&P VALVE
SAME SIZE AS VALVE
TO FD
DRAIN VALVE
FINISHED FLOOR
4" HIGH CONCRETE
HOUSEKEEPING PAD
UNION (TYP)
EWH
THERMOMETER (TYP)
1"
1"
1"
1"
1/2"
212 North Illinois Avenue Carbondale, Illinois 62901-1452
Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 27 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C.
316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
D R e v it P ro je c ts
\R E
V
IT
\2
-0
H \2
-0
H
.r v t
PLUMBING SYMBOLS, NOTES,
ABREVIATIONS, SCHEDULES AND DETAILS
SECRETARY OF STATE PAINT SHOP & SPRAY
ROOM
22.09
04-21-2023
JRV JRV P0.0
PLUMBING AND FIRE PROTECTION GENERAL NOTES
1 DUE TO THE LIMITED SPACE AVAILABLE FOR THE INSTALLATION OF ALL THE PLUMBING WORK, COORDINATION BETWEEN ALL OTHER TRADES IS OF THE UTMOST IMPORTANCE.
2 THIS CONTACTOR SHALL VISIT THE PROJECT SITE, AND VERIFY LOCATIONS, ELEVATIONS AND SIZES OF ALL UTILITIES AT SITE PRIOR TO PROCEEDING WITH WORK. EXISTING SYSTEMS AND
STRUCTURE SHALL BE INVESTIGATED FOR BEST POSSIBLE ROUTING OF COLD WATER, HOT
WATER, SANITARY WASTE AND VENT, STORM AND MEDICAL/LABORATORY GAS PIPING.
3 THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THE ONLY AVAILABLE INFORMATION HAS
BEEN OBTAINED FROM EXISTING PLANS, SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT
LOCATION OF PIPING, FIXTURES, AND EQUIPMENT MAY DEVIATE FROM THE LOCATION INDICATED
ON THESE DRAWINGS, EXTREME ACCURACY IS NOT GUARANTEED. THIS CONTRACTOR SHALL BE
PREPARED TO MAKE ALTERATIONS TO NEW AND/OR EXISTING SERVICES TO FIT JOB CONDITIONS.
THIS CONTRACTOR SHALL FURNISH A COMPLETE AND CODE COMPLYING SYSTEM. THIS
CONTRACTOR SHALL REPORT, IN WRITING, ANY DISCREPANCIES WHICH PREVENT THE
INSTALLATION OF WORK AS SHOWN.
4 IF THIS CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS OR IS NOT COMPLETELY
SURE OF THEIR MEANING, THIS CONTRACTOR SHOULD OBTAIN THE ENGINEER'S WRITTEN
EXPLANATION AND/OR INTERPRETATION PRIOR TO SUBMITTING BIDS, SINCE THIS CONTRACTOR
WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE ENGINEER.
5 IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO REPAIR THE EXISTING SURFACES TO REMAIN WHERE THEIR WORK HAS BEEN COMPLETED. REPAIR SHALL INCLUDE, BUT NOT LIMITED TO, ANY EXISTING WALL, CEILING OR FLOOR THAT IS SCHEDULED TO REMAIN. REPAIR, PAINTING, AND
PATCHING SHALL BE COMPLETED BY AN APPROPRIATE CONTRACTOR QUALIFIED FOR THIS TYPE
OF WORK.
6 THE OWNER SHALL MAINTAIN ALL SALVAGE RIGHTS OF FIXTURES. EQUIPMENT AND MATERIALS
REMOVED. HOWEVER, ALL FIXTURES, EQUIPMENT AND MATERIALS NOT CLAIMED BY THE OWNER
SHALL BE REMOVED FROM THE PREMISES AND PROPERLY DISPOSED OF BY THE DEMOLITION
CONTRACTOR.
7 CEILING REMOVAL, STORAGE, AND REPLACEMENT FOR NEW PIPING INSTALLATION SHALL BE BY
THE GENERAL CONTRACTOR.
8 IF HAZARDOUS MATERIALS (ASBESTOS) ARE ENCOUNTERED DURING DEMOLITION OPERATIONS, THE CONTRACTOR WILL STOP WORK AT THE PARTICULAR LOCATION AND NOTIFY BUILDING
OWNER OF THE HAZARDOUS MATERIAL. THE CONTRACTOR WILL CONTINUE WORK AFTER
REMOVAL OF HAZARDOUS MATERIALS IS COMPLETED.
9 TEMPORARY CONNECTIONS SHALL BE PROVIDED BY RESPECTIVE PLUMBING AND FIRE
PROTECTION CONTRACTORS WHEN EXTENDED INTERRUPTIONS OF SERVICES AND UTILITIES
SUCH AS WATER, WASTE AND FIRE PROTECTION WHICH SERVE OTHER AREAS ARE NECESSARY.
10 COORDINATE WITH MAINTENANCE PERSONNEL AS TO SOURCE OF UTILITIES AND TEMPORARILY
DISCONNECT OR SHUT OFF SERVICES OR UTILITIES AT NEAREST MAIN. TEMPORARY AND
ACCESSIBLE ISOLATION VALVES SHALL BE INSTALLED CLOSE TO THIS POINT OF WORK.
11 IT IS ESSENTIAL THAT BUILDING OPERATIONS CONTINUE WITH MINIMAL INTERRUPTIONS. IT IS
NECESSARY THAT OPERATION OF EXISTING SYSTEMS BE INTERFACED WITH AS LITTLE
DISRUPTION AS POSSIBLE EXCEPT IN AREAS VACATED FOR CONTRUCTION WORK. WORK WHICH
WILL INTERFERE WITH OPERATION OF EXISTING FIRE SUPPRESSION AND PLUMBING SYSTEMS OR
WHICH REQUIRE DOWNTIME, WILL BE SCHEDULED ONLY AFTER CONSULTATION WITH AND
PERMISSION GIVEN BY THE OWNER. ALLOW 10 DAYS PRIOR TO ANTICIPATED INTERRUPTION OF
SYSTEMS. WORK MAY BE REQUIRED TO BE PERFORMED OUTSIDE NORMAL WORKING HOURS.
12 ARCHITECTURAL DEMOLITION DRAWINGS AND SPECIFICATIONS SHALL BE READ IN CONJUNCTION
WITH THESE DRAWINGS.
13 ALL PIPE HANGERS AND SUPPORTS SHALL BE REMOVED ALONG WITH PIPING BEING REMOVED.
14 THE CONTRACTOR SHALL COORDINATE DEMOLITION WORK WITH PROJECT’S PHASING SCHEDULE
PRIOR TO COMMENCEMENT OF ANY WORK.
15 WHEN PLACING NEW PLUMBING FIXTURES, CONTRACTOR SHALL VERIFY LOCATIONS OF PLUMBING VENTS. OFFSET VENTS THAT TERMINATE WITHIN 25 FEET OF HVAC UNITS OUTDOOR AIR INTAKES.
CONTRACTOR SHALL FIELD VERIFY PRIOR TO BID WHERE THE INTERFERENCE’S ARE AND PRICE
ACCORDINGLY OR MAKE ALLOWANCES IN BID.
16 USE CAUTION WHEN SAW-CUTTING THROUGH EXISTING CONCRETE FLOOR OR WALL
CONSTRUCTION FOR THE INSTALLATION OF PLUMBING SYSTEMS TO AVOID CUTTING REBAR AT
EDGE OF OPENING. LEAVE SUFFICIENT REBAR EXPOSED TO TIE NEW REINFORCING FOR
REPLACEMENT CONCRETE AND/OR OTHER STRUCTURAL ATTACHMENTS FOR NEW
CONSTRUCTION.
17 CONTRACTOR SHALL BE RESPONSIBLE FOR ANY REVISIONS, TRANSITIONS, OFFSETS, ETC., TO
AVOID DUCTWORK, PIPING, EQUIPMENT, OR STRUCTURE NEW OR EXISTING AND TO MAKE A
COMPLETE AND FUNCTIONING SYSTEM.
PLUMBING SYMBOLS & ABBREVIATIONS
NOT ALL SYMBOLS ARE USED FOR THIS PROJECT
TRAPPED CONNECTION
STRAINER
BALANCING VALVE
CLEANOUT (CO)
OS & Y GATE VALVE
TEMPERATURE GAUGE
THERMOSTATIC MIXING VALVE
REDUCED PRESSURE BACKFLOW PREVENTER
HOSE BIBB/WALL HYDRANT
DOMESTIC COLD WATER PIPING (CW)
DOMESTIC HOT WATER PIPING (HW)
DOMESTIC HOT WATER RETURN PIPING (HWR)
SANITARY PIPING
VENT PIPING
EXISTING FIXTURE TO BE REMOVED
EXISTING FIXTURE
NEW FIXTURE
FLOOR DRAIN/FLOOR SINK (FD/FS)
CIRCULATION PUMP
X
P501
COMMON PFP SYMBOLS & ABBREVIATIONS
NOT ALL SYMBOLS ARE USED FOR THIS PROJECT
DIRECTION OF FLOW
BRANCH CONNECTION, BOTTOM
BRANCH CONNECTION, TOP
ELBOW, TURNED DOWN
ELBOW, TURNED UP
SHUTOFF VALVE
CHECK VALVE
PRESSURE REDUCING VALVE
PRESSURE GAUGE
UNION
PIPING CAP
EXISTING PIPING TO BE REMOVED
MATCH LINE
CONNECTION TO EXISTING
DETAIL DESIGNATION
RISER DESIGNATION
KEYED NOTE
REVISION NOTE
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITIES HAVING JURISDICTION
AP ACCESS PANEL
BOP BOTTOM OF PIPE
DIA DIAMETER
DN DOWN
EX OR EXIST EXISTING
FFE FINISHED FLOOR ELEVATION
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HP HORSEPOWER
IE OR INV. ELEV INVERT ELEVATION
NC NORMALLY CLOSED
NTS NOT TO SCALE
PSI POUNDS PER SQUARE INCH
RPM REVOLUTIONS PER MINUTE
RI ROUGH-IN
SOV SHUTOFF VALVE
TDH TOTAL DYNAMIC HEAD
VIF VERIFY IN FIELD
DOMESTIC WATER HEATER SCHEDULE
PLAN
MARK
DESCRIPTION MANUFACTURER MODEL STORAGE RECOVERY
TEMPERATURE
RISE
ELECTRICAL TEMPERATURE NOTES
EWH-1
ELECTRIC WATER
HEATER
A O SMITH DEN-52 55 GAL 55 GPH 90 DEG 6.0 KW 130 DEG
DRAIN SCHEDULE
PLAN MARK DESCRIPTION MANUFACTURER MODEL BODY STRAINER NOTES
FS-1 FLOOR SINK ZURN Z1900 COATED CAST IRON 1/2 NICKEL BRONZE
PLUMBING FIXTURE SCHEDULE
PLAN
MARK
DESCRIPTION MANUFACTURER MODEL TRIM DRAIN/TRAP
CONNECTION SCHEDULE
NOTES
HOT WATER COLD WATER SANITARY VENT
EEW-1 EMERGENCY EYEWASH GUARDIAN G1750P TMV-1 - 3/4" 3/4" 2" 2"
HB-1 HOSE BIBB PRIER P156NP.75 - - - 3/4" - -
L-1 WALL HUNG LAVATORY ZURN Z5310 ZURN Z6913-XL-N 1-1/2" 1/2" 1/2" 2" 2" PROVIDE WITH TMV-2, SEE SPECS
MB-1 24X24 MOP BASIN FIAT MSB2424
CHICAGO FAUCET
540-LD897SW
2" DEEP SEAL 1/2" 1/2" 2" 2" PROVIDE WITH HOSE BRACKET.
SS-1 SERVICE SINK ELKAY ESS23192 ZURN Z843M2-XL 1-1/2" 1/2" 1/2" 2" 2" PROVIDE WITH SEDIMENT/PAINT TRAP
UR-1 WALL HUNG URINAL ZURN Z5755-U
ZURN
ZER6003-AV-TM-ULF
INTERGRAL - 1" 2" 2"
WC-1
FLOOR MOUNTED WATER
CLOSET
ZURN Z5615-BWL
ZURN
ZER6000AV-TM-HET
INTERGRAL - 1-1/4" 4" 2"
THERMOSTATIC MIXING VALVE SCHEDULE
PLAN
MARK
DESCRIPTION MANUFACTURER MODEL
FLOW LEAVING
TEMPERATURE
NOTES
MINIMUM GPM GPM @ 15 PSI LOSS
TMV-1 EYEWASH TMV GUARDIAN G6020 3.0 8.0 80 DEG.
P0.0 NONE
1 WATER SERVICE ENTRANCE - DOMESTIC
P0.0 NONE
2 DOMESTIC WATER HEATER - ELECTRIC
BACKFLOW PREVENTER SCHEDULE
PLAN
MARK
DESCRIPTION MANUFACTURER MODEL
MAX DROP PEAK FLOW SIZE NOTES
BFP-1
DOUBLE CHECK BACKFLOW
PREVENTER
WATTS LF007-S
10 PSI 75 GPM 2" DOMESTIC WATER
SERVICE
RPZ-1
REDUCED PRESSURE ZONE
BACKFLOW PREVENTER
WATTS 994-OSY
12 PSI 250 GPM 4" FIRE WATER
SERVICE
SIGNED: 4/26/23
LICENSE EXPIRES: 11/30/23
FDFDFD FD
FD
FD FD
FD
FD
FD
FD
FD
FD
FDFD
FDFDFD FD
FDFD
FD
FD
FD FD
FD
EX. FCO
MECHANICAL
ROOM
TOILET
DRYING / PICK
UP
STORAGE /
COMPRESSOR
OFFICE
DROP OFF /
PREP
PAINT ROOM
EX. FCO
L-1
UR-1
WC-1 FS-1
FS-1
SS-1
4"CW
2"V
3"S
2"V
3"S
EX. FD
EX. FD EX. FD
EWH-1
AC-1
EEW-1
TMV-1
HB-1
HB-1
3/4"HW
3/4"CW
1/2"HW
1"CW
1"HW
1"CW
1 1/4"CW
1"CA
1/2"CA
1/2"CA
3/4"CA
BFP-1
4"S
3"S-UP TO FS
3"S-UP TO FS
4"S-UP TO FCO
4"S-UP TO YCO
1"NG
FCO
FCO
RPZ-1
2"V
1/2"CA
1/2"CA
S
MB-1
2"S-UP TO MB
2"V-UP
3"S-UP TO FS
3"S
FS-1
(ABOVE)
(BELOW)
10 10
212 North Illinois Avenue Carbondale, Illinois 62901-1452
Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 27 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C.
316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
D R e v it P ro je c ts
\R E
V
IT
\2
-0
H \2
-0
H
.r v t
PLUMBING DEMOLITION AND NEW WORKSECRETARY OF STATE PAINT SHOP & SPRAY
ROOM
22.09
04-21-2023
JRV JRV P1.0
1 EXISTING 12" DIAMETER FLOOR DRAIN; TO
REMAIN.
DEMOLISH EXISTING GAS REGULATOR AND
INTERIOR GAS PIPING. EXISITNG 1"Ø GAS
UNDERGROUND FROM MAIN POWER PLANT TO
BE REUSED IN NEW WORK.
EXISTING VENT THRU ROOF; TO REMAIN.
EXISTING ABOVE FLOOR SLAB VENT PIPING; TO
REMAIN AND BE CONNECTED/EXTENDED IN
NEW WORK.
EXISTING FLOOR CLEANOUT; TO REMAIN.
1" COLD WATER MAIN DROPPING THRU FLOOR;
CAP AT FLOOR LEVEL.
EXISTING HOSE BIBB TO BE REMOVED.
EXISTING OVERHEAD COLD WATER LINE TO BE
REMOVED.
DASHED LINES SHOW THE EXTENT OF
SAWCUTTING EXISTING FLOOR REQUIRED TO
PERFORM PLUMBING WORK. PLUMBING
CONTRACTOR IS RESPONSIBLE FOR MARKING,
SAWCUTTING, SLAB REMOVAL, EXCAVATION
AND BACKFILL. COORDINATE SLAB
REPLACEMENT AND MATCHING FLOOR FINISH
WITH G.C.
REMOVE FLOOR DRAIN AND CAP EXISTING
SANITARY PIPING. PATCH FLOOR TO MATCH
EXISTING.
KEYED NOTES
P1.0 1/8" = 1'-0"
1 PLUMBING NEW WORK FLOOR PLAN
P1.0 1/8" = 1'-0"
2 PLUMBING DEMOLITION FLOOR PLANS
ABOVE GROUND FLOOR PLAN
BELOW GROUND FLOOR PLAN
ABOVE GROUND FLOOR PLAN
BELOW GROUND FLOOR PLAN
1 ASSUMED ROUTING OF EXISTING
UNDERGROUND PIPING BASED UPON VISIBLE
ABOVEGROUND PIPING. PIPING ROUTE TO BE
CONFIRMED VIA CAMERA LOCATING. TYPICAL
ALL UNDERGROUND PIPING. THE EXISTING
UNDERGROUND PIPING IS ROUTED TO AN OIL
INTERCEPTOR LOCATED ACROSS THE LOT
NEXT TO THE POWER PLANT. THIS PIPING TO
REMAIN AS-IS.
DASHED LINES SHOW THE EXTENT OF
SAWCUTTING EXISTING FLOOR REQUIRED TO
PERFORM PLUMBING WORK. PLUMBING
CONTRACTOR IS RESPONSIBLE FOR MARKING,
SAWCUTTING, SLAB REMOVAL, EXCAVATION
AND BACKFILL. COORDINATE SLAB
REPLACEMENT AND MATCHING FLOOR FINISH
WITH G.C.
REMOVE FLOOR DRAIN AND CAP EXISTING
SANITARY PIPING. PATCH FLOOR TO MATCH
EXISTING.
KEYED NOTES
1 PROVIDE NEW GAS REGULATOR TO REDUCE
9PSI DELIVERY PRESSURE TO 2PSI DELIVERY
PRESSURE. PROVIDE AN ADDITIONAL 3
PRESSURE REGULATORS AT THE INLET TO THE
MAKEUP AIR UNIT BURNERS TO REDUCE 2PSI
TO 14"W.C. BURNER INLET REQUIREMENTS.
TOTAL MAKEUP AIR UNIT GAS CAPACITY
EQUALS 1,200,000 BTU. ROUTE PIPING ABOVE
DOORS, AROUND CORNER AND THEN DOWN TO
UNIT ON GRADE.
PROVIDE 1/2" CA QUICK-CONNECT FITTING ON A
TEE WITH DRIP LEG.
PROVIDE 3/4"Ø NORMALLY-CLOSED SOLENOID
VALVE, 115V/40VAC POWER. SOLENOID SHALL
BE LOCATED OUTSIDE OF PAINT ROOM.
SOLENOID SHALL BE CONTROLLED BY PAINT
ROOM AIR VELOCITY. COORDINATE CONTROLS
REQUIREMENTS WITH CONTROLS
CONTRACTOR.
KEYED NOTES
1 NEW 4" COMBINED FIRE AND DOMESTIC WATER
SERVICE TO BUILDING. COORDINATE SERVICE
AND METER REQUIREMENTS WITH CWLP.
KEYED NOTES
EXISTING VTR
EXISTING VTR
EXISTING VTR
FCO
6" NEW SANITARY LATERAL
TIE INTO EXISTING 18"Ø CLAY SEWER IN ALLEY.
CONTRACTOR SHALL CLOSE ALLEY AND PROVIDE
PROPER BARRICADES. EXISTING SEWER LINE
APPROXIMATELY 13 FEET DEEP.
EXISTING
CHAINLINK
FENCE
4" NEW WATER SERVICE. CONTACT CWLP.
212 North Illinois Avenue Carbondale, Illinois 62901-1452
Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 27 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C.
316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
D R e v it P ro je c ts
\R E
V
IT
\2
-0
H \2
-0
H
.r v t
PLUMBING SITE UTILITIESSECRETARY OF STATE PAINT SHOP & SPRAY
ROOM
22.09
04-21-2023
JRV JRV P1.1
P1.1 1/8" = 1'-0"
1 PLUMBING NEW WORK SITE PLAN
P1.1
NEW WORK WATER SERVICE SITE PLAN - FOR REFERENCE ONLY - CONTACT CWLP
HOUSEKEEPING PAD
AUTOMATIC DRAIN.
TERMINATE OVER
FLOOR DRAIN
FINISH FLOOR
PRESSURE SWITCH SET
FOR 175 PSI DISCHARGE
PRESSURE FROM
FACTORY
TWO (2) 1.0 MICRON
FILTER/DRYERS (45 CFM EACH).
MOUNT VIA UNISTRUT TO WALL.
PRESSURE GAUGE
CA
175 PSI TO
SYSTEM
ANCHOR, SEE
SPECIFICATIONS
UNION (TYP)
SHUTOFF VALVE (TYP)
A
IR
C O
M P
R E
S S
O R
3/4"
3/4"
FILTER FLOAT DRAIN
OUTLET. TERMINATE
OVER FLOOR DRAIN.
CALIBRATED
BALANCING VALVE
SHUTOFF VALVE
(TYPICAL)
SEE PLANS
FOR PIPE SIZE
UNION
CALIBRATION
CONNECTION
POINTS
CHECK
VALVE
1/8 BEND
BALANCE OF PIPING
SAME AS
CLEANOUT
TO GRADE
FLOOR CLEAN OUT (FCO)
1/8 BEND
BALANCE OF PIPING
SAME AS
CLEANOUT
TO GRADE
STACK CLEAN OUT (CO)
CLEANOUT AND NICKEL BRONZE ACCESS
COVER WITH COUNTERSUNK HEAD.
TOP OF COVER TO BE FLUSH
WITH TOP OF FLOOR AND COMPATIBLE
WITH FLOORING MATERIAL
FINISHED FLOOR
MAY EXTEND AS VENT
LINE SIZE CLEANOUT
CHROME
WALLCOVER
AND SCREW
WALL
PLUGGED TEE/CLEANOUT
FINISHED FLOOR
1/8 BEND
SAN. LINE
LENGTH TO
SUIT
SAN
1/8 BEND
IF CLEANOUT OCCURS AT END OF LINE,
USE 'T' FOR EXTERIOR CLEANOUT
CLEANOUT TO GRADE (YCO)
BRASS CLEANOUT PLUG
WITH COUNTERSUNK
HEAD
16" SQUARE CONCRETE PAD
TROWEL SMOOTH AND
EDGE
FINISHED GRADE
NOTE:
RIGIDLY MOUNT COMPRESSED
AIR DROP PIPING AND
ACCESSORIES WITH
UNISTRUCT ATTACHED TO
BUILDING STRUCTURE TO
PREVENT MOVEMENT.
SEE PLANS FOR MAIN SIZE
VERIFY CONNECTION SIZE
AND LOCATION PRIOR TO
INSTALLATION.
REGULATOR WITH 125 PSI GAUGE
1/2" QUICK
CONNECT
COUPLING
DRAIN VALVE
1/2" BRANCH
DROPS
BALL VALVE
F 154-330
E 114-154
D 61-113
C 33-60
B 12-32
1-11A
SINGLE/ DOUBLE FIXTURE
FIXTURE
UNIT LOAD
PIPE
SIZE
WHA
SIZE
1/2"
3/4"
1"
1 1/4"
1 1/2"
2"
HOT OR
COLD
WATER
SUPPLY
IF BRANCH IS GREATER THAN 20'
LONG, PROVIDE AN ADDITIONAL WHA
IN MIDDLE OF RUN. EACH SIZED
FOR HALF THE FIXTURE UNITS.
IF HORIZONTAL BRANCH IS
LESS THAN 20' LONG,
PROVIDE
ONE WHA AT END OF LINE.
FIXTURE (TYPICAL)
NOTE: INSTALL PER
MANUFACTURER'S
INSTRUCTIONS. PROVIDE A WHA AT
ALL QUICK-CLOSING VALVES.
SHUTOFF VALVE
DIRT LEG
EQUIPMENT UNION
SEE PLANS
FOR SIZING
PRESSURE
PORT
2 PSI TO INCHES GAS
PRESSURE REGULATOR.
INTERIOR EQUIPMENT
REQUIRES RELIEF VENT PIPING
EXTENDED TO EXTERIOR WALL
AND TERMINATED WITH
DOWNTURNED ELBOW AND
INSECT SCREEN.
212 North Illinois Avenue Carbondale, Illinois 62901-1452
Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 27 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C.
316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
D R e v it P ro je c ts
\R E
V
IT
\2
-0
H \2
-0
H
.r v t
PLUMBING DETAILS AND SCHEMATICSSECRETARY OF STATE PAINT SHOP & SPRAY
ROOM
22.09
04-21-2023
JRV JRV P2.0
P2.0 NONE
1 AIR COMPRESOR
P2.0 NONE
3 CALIBRATED BALANCING VALVE
P2.0 NONE
5 CLEANOUT DETAILS
P2.0 NONE
6 COMPRESSED AIR DROP/ OUTLET
P2.0 NONE
4 WATER HAMMER ARRESTOR SCHEMATIC
P2.0 NONE
2 GAS CONNECTION AT EQUIPMENT
SIGNED: 4/26/23
SIGNED 04/26/2023
BRANCH LINE
1" NIPPLE
1" ELBOW
CORRUGATED STAINLESS STEEL HOSE
WITH STAINLESS STEEL BRAID - MINIMUM 1"
I.D.
ADJUSTABLE HUB
CLIP TO CEILING GRID SYSTEMMOUNTING BRACKET
CEILING TILE SPRINKLER HEAD
NOTE:
ALL HEADS ON WET SYSTEM UTILIZE FLEXIBLE ASSEMBLY WHERE
POSSIBLE WHEN CLEARANCES ARE TIGHT - FINISH DROPS ARE HARD
PIPED.
1/2" MAX.
RECESSED SPRINKLER HEAD
1" X 1/2" REDUCING
COUPLING
ONE (1) INCH
DROP - LENGTH
AS REQUIRED
ONE (1) INCH
DROP - LENGTH
AS REQUIRED
ONE (1) INCH
DROP - LENGTH
AS REQUIRED
TYP SPRINKLER
BRANCH LINE
WITH ONE (1) INCH
OUTLET TEES
TYPICAL SPRINKLER BRANCH
LINE WITH ONE (1) INCH
OUTLET TEES
ONE (1) INCH RISER NIPPLE
LENGTH AS REQUIRED
1" X 1/2" REDUCING
COUPLING
UPRIGHT SPRINKLER HEAD
EQ EQ
EQ EQ
EQ EQ
36" 12"
36" 12"
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
24" X 48"
CEILING TILE
12" X 48"
CEILING TILE
12" X 12" / 24" X 24"
CEILING TILE
12" X 48"
CEILING TILE
24" X 48"
CEILING TILE
NOTE:
INDICATES CENTERLINE OF SPRINKLER HEAD
TO FIRE
SUPPRESSION
SYSTEM
INJECTION POINT
FLOW SWITCH
JUNCTION BOX (BY E.C.)
MANUAL SWITCH (BY E.C.)
TO INDEPENDENT 115 VOLT,
15 AMP POWER SUPPLY (BY
E.C.)
PUMP
TANK
MIC-TREAT
SYSTEM A
P P
R O
X
A .F
.F
CHECK VALVE
FIRE
DEPARTMENT
CONNECTION
3/4"
BALL DRIP
D
4"
45 DEG. ELBOW W/ INSECT SCREEN.
TERMINATE 18" ABOVE GRADE.
INSPECTOR'S TEST
VALVE IN READILY
ACCESSIBLE LOCATION
FROM END
OF REMOTE
BRANCH LINE
45° ELL
DOWNTURNED 45°
ELBOW W/ S.S. INSECT
SCREEN
212 North Illinois Avenue Carbondale, Illinois 62901-1452
Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 27 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C.
316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
D R e v it P ro je c ts
\R E
V
IT
\2
-0
H \2
-0
H
.r v t
FIRE PROTECTION DETAILS AND NOTESSECRETARY OF STATE PAINT SHOP & SPRAY
ROOM
22.09
04-21-2023
JRV JRV F0.0
F0.0 NONE
2 FLEXIBLE SPRINKLER DROP
F0.0 NONE
1 RECESSED SPRINKLER HEAD
F0.0 NONE
3 UPRIGHT SPRINKLER HEAD
F0.0 NONE
4 SPRINKLER HEAD LOCATION
F0.0 12" = 1'-0"
5 MIC TREATMENT SCHEMATIC
FS
FV
FIRE PROTECTION SYMBOLS & ABBREVIATIONS
NOT ALL SYMBOLS ARE USED FOR THIS PROJECT
AIR VENT (AUTOMATIC)
DOUBLE CHECK VALVE ASSEMBLY
ELECTRONIC SUPERVISED INDICATING VALVE
FIRE DEPARTMENT VALVE (FDV)
FLOW SWITCH
PRESSURE RELIEF VALVE
DRAIN LINE
FIRE MAIN (BULK)
SPRINKLER MAIN/BRANCH PIPING
DRIP CONNECTION
FIRE DEPARTMENT CONNECTION-WALL MOUNT
FLUSH TYPE FIRE DEPARTMENT INLET CONNECTION
SPRINKLER HEAD (SEE SCHEDULE FOR TYPE)
SIDEWALL SPRINKLER HEAD (SEE SCHEDULE FOR TYPE)
AC AIR COMPRESSOR
DCV DOUBLE CHECK VALVE
FDC FIRE DEPARTMENT CONNECTION
FDV FIRE DEPARTMENT VALVE
FEC FIRE EXTINGUISER CABINET
AS AUTOMATIC SPRINKLER
NAS NO AUTOMATIC SPRINKLERS
TS TAMPER SWITCH
D
F
SPR
AAV
FIRE PROTECTION GENERAL NOTES
1 THE WORK COVERED CONSISTS OF FURNISHING ALL LABOR AND MATERIALS NECESSARY TO
INSTALL, COMPLETE AND READY FOR CONTINUOUS OPERATION, THE FIRE PROTECTION SYSTEMS, APPARATUS AND EQUIPMENT FOR THIS PROJECT, AS SHOWN ON THE DRAWINGS, PLUS AS
REQUIRED BY NFPA 13 AND THE AUTHORITY HAVING JURISDICTION.
2 FURNISH AND INSTALL TAMPER SWITCHES ON ALL INDICATING VALVES AS PER NFPA 13
REQUIREMENTS.
3 THE CONTRACTOR SHALL PERFORM A FLOW TEST PRIOR TO THE DESIGN AND SUBMITTAL OF THE
HYDRAULICALLY CALCULATED SYSTEM IF THE PROVIDED TEST IS GREATER THAN 1 YEAR OLD
FROM THE DATE OF CONSTRUCTION.4. THE CONTRACTOR SHALL SUBMIT ALL DRAWINGS AND
CALCULATIONS TO THE FIRE DEPARTMENT, GOVERNING AGENCIES, AND INSURING AGENCY AND
RECEIVE APPROVAL PRIOR TO SUBMITTING DESIGN SHOP DRAWINGS.
4 THE CONTRACTOR SHALL SUBMIT ALL DRAWINGS AND CALCULATIONS TO THE FIRE DEPARTMENT, GOVERNING AGENCIES, AND INSURING AGENCY AND RECEIVE APPROVAL PRIOR TO SUBMITTING
DESIGN SHOP DRAWINGS.
5 THE CONTRACTOR SHALL FURNISH DRAIN VALVE AND INSPECTOR’S TEST CONNECTIONS AS
REQUIRED BY NFPA 13 REQUIREMENTS AND AT THE DISCRETION OF THE FIRE MARSHAL,
ENGINEER, OR GOVERNING AGENCY.
6 UNLESS OTHERWISE NOTED, IT IS THE INTENT OF THESE DOCUMENTS THAT ALL AREAS WITHIN SCOPE OF WORK WILL BE PROVIDED WITH AN AUTOMATIC WET TYPE FIRE SUPPRESSION SYSTEM
MEETING NFPA #13.
7 ROUTING OF SPRINKLER MAINS, BRANCHES AND HEADS SHALL BE THOROUGHLY COORDINATED
WITH ALL OTHER TRADES AND BUILDING STRUCTURE PRIOR TO SUBMISSION OF COORDINATED
SHOP DRAWINGS. FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR COORDINATING,
PREPARING, AND SUBMITTING COORDINATION DRAWINGS FOR APPROVAL/REVIEW.
8 ALL OPENINGS THROUGH FIRE RATED FLOORS AND WALLS OR PARTITIONS SHALL BE FIRE
STOPPED WITH UL RATED ASSEMBLIES OF EQUAL OR GREATER FIRE RATING.
9 SUBMIT ACCURATE AS BUILT DRAWINGS TO THE ENGINEER AND OWNER.
10 ALTHOUGH ALL PIPING MAY NOT BE INDICATED ON THE FLOOR PLANS, IT IS THE INTENT THAT THE ENTIRE EXISTING SPRINKLER SYSTEM BE DEMOLISHED BACK TO THE NEAREST FIRE/BULK/BRANCH
MAIN.
11 THE FIRE PROTECTION BID IS A DESIGN/BUILD CONTRACT. BEFORE SUBMITTING HIS BID THE
CONTRACTOR SHALL VISIT THE SITE AND BECOME THOROUGHLY FAMILIAR WITH ALL EXISTING
CONDITIONS. THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ANY ASSUMPTIONS,
OMISSIONS OR ERRORS HE MAKES AS A RESULT OF HIS FAILURE TO BECOME FULLY FAMILIAR
WITH EXISTING CONDITIONS.
12 THE CONTRACTOR SHALL INCLUDE IN HIS BID, A FULLY CODE COMPLIANT AND COORDINATED SPRINKLER SYSTEM. HEAD LOCATIONS ARE SHOWN TO ESTABLISH TYPE, QUANTITY, AND DESIRED LOCATION. EXACT QUANTITY OF HEADS IS CONTRACTOR’S RESPONSIBILITY. PROJECT SHALL BE
DESIGNED AND CONSTRUCTED PER NFPA 13 AND/OR FACTORY MUTUAL GLOBAL REQUIREMENTS.
13 THE CONTRACTOR IS RESPONSIBLE FOR SUBMITTAL TO ALL GOVERNING AGENCIES AND THE
INSURING AGENCY.
FIRE PROTECTION EQUIPMENT SCHEDULE
FIRE SPRINKLER PIPING SCHEDULE
PIPING MATERIAL SCHEDULE HAZARD OCCUPANCY REMARKSPIPE SIZE
1-1/2" AND SMALLER BLACK STEEL LIGHT / ORDINARY40
2" AND UP BLACK STEEL 10 LIGHT / ORDINARY
DESCRIPTION
FIRE DEPARTMENT CONNECTION
WET PIPE ZONE VALVE
LOCATION
WEST FACADE
MECHANICAL 100A
QUANTITY
REMARKS
DUAL INLET, EXPOSED, MOUNTED ON WALL
FM APPROVED; THREADED FITTINGS
FM APPROVED; ROLLED GROOVED ENDS AND FITTINGS
WATER TREATMENT SYSTEM P-SERIES MICTREAT SYSTEM
SEE
REMARKS
VARIOUSTAMPER SWITCH
ELECTRICALLY SUPERVISED TAMPER SWITCH ON EACH VALVE IN SYSTEM. CONFIRM NUBMER OF VALVES
WITH FIRE ALARM CONTRACTOR.
1MECHANICAL 100A
FLOW SWITCH (FS) MECHANICAL 100A 1 ELECTRICALLY SUPERVISED, PADDLE OPERATED, FIELD ADJUSTABLE RETARD ELEMENT
WET PIPE VALVE, SHUT OFF VALVE, TEST & DRAIN VALVE COMBINATION, PRESSURE GAUGES AS DETAILED.
SPRINKLER HEAD SCHEDULE
STYLE
ELEMENT BULB
RESPONSE TEMP. CLASS
COVERAGE
OCCUPANCY
RATING
FINISH ESCUTCHEON REMARKS
STYLE RESPONSE TEMP. CLASS COVERAGE OCCUPANCY RATING FINISH ESCUTCHEON
ORDINARY
ORDINARY
ORDINARY
QR
QR
QR
SC LH W C
SC LH C/U X
SC OH C/U X
RP
U
U
F (FLAT)
R (RECESSED)
E (2 PC. EXTENDED)
C (CONCEALED COVER PLATE)
X (NO ESCUTCHEON)
U (UNFINISHED)
C (CHROME)
W (BRIGHT WHITE)
B (BLACK)
LH (LIGHT HAZARD)
OH (ORDINARY HAZARD)
SC (STANDARD)
EC (EXTENDED)
ORDINARY
(135°-170°F)
INTERMEDIATE
(175°-225°F)
HIGH
(250°-300°)
SR (STANDARD 5mm)
QR (QUICK 3mm)
C (CONCEALED PENDENT)
P (PENDENT)
RP (RECESSED PENDENT)
U (UPRIGHT)
SW (SIDEWALL)
RSW (RECESSED SIDEWALL)
INTERMEDIATEQR SC OH C/U XU
REMARKS:
1. PROVIDE STANDARD DUTY SPRINKLER GUARDS ON ALL SPRINKLERS LOCATED IN MECHANICAL ROOMS, ELECTRICAL ROOMS, STORAGE ROOMS, AND JANITOR
CLOSETS.
2. SPRINKLERS SHALL BE PERMITTED TO BE COVERED ONLY BY CELLOPHANE BAGS HAVING A THICKNESS OF 0.08MM OR LESS OR BY THIN PAPER BAGS. THESE COVERINGS SHALL BE REPLACED FREQUENTLY SO THAT HEAVY DEPOSITS OF RESIDUE DO NOT ACCUMULATE.
INTERMEDIATESR SC OH C/U XP
F0.0 NONE
6 FIRE DEPARTMENT CONNECTION PIPING
F0.0 1/8" = 1'-0"
7 INSPECTION TEST
INTERMEDIATESR SC EH C/U XP
EH (EXTRA HAZARD
GROUP 2)
MECHANICAL
ROOM
TOILET
DRYING / PICK
UP
STORAGE /
COMPRESSOR
OFFICE
DROP OFF /
PREP
PAINT ROOM
2 4
FV
F
F
F
FDC
4" FIRE WATER
SERVICE TO SYSTEM
PADDLE
FLOW SWITCH
2" MAIN
DRAIN VALVE
FS
TS RPZ
TS
CHECK VALVE
PIPE
SUPPORTS
AS
REQUIRED
BY F.P.C. BY P.C.
INDICATING VALVE WITH
TAMPER SWITCH (TYP) BY F.P.C.
FINISH FLOOR
4" COMBINATION
FIRE &
DOMESTIC
SERVICE
M A
X
TO FDC
PRESSURE GAUGE
TS
212 North Illinois Avenue Carbondale, Illinois 62901-1452
Telephone (618) 529-3691 www.wb-architects.com
PROJECT:
LOCATION:
SHEET TITLE: SOS PROJECT NO.
DATE:
DRAWN: APPR:
REVISIONS:
SHEET NUMBER
OF 27 SHEETS
WHITE & BORGOGNONI ARCHITECTS, P.C.
316 NORTH KLEIN STREET
SPRINGFIELD, IL 62702
100 EAST WASHINGTON, SUITE 220
BELLEVILLE, IL 62220
TEL 618.277.5200
FAX 618.277.5227
IL DESIGN FIRM REG. #
184.006777-0002
ISSUED FOR BID
D R e v it P ro je c ts
\R E
V
IT
\2
-0
H \2
-0
H
.r v t
FIRE PROTECTION FLOOR PLANSECRETARY OF STATE PAINT SHOP & SPRAY
ROOM
22.09
04-21-2023
JRV JRV F1.0
F1.0 1/4" = 1'-0"
1 FIRE PROTECTION NEW WORK FLOOR PLAN
FIRE PROTECTION GENERAL NOTES
FIRE PROTECTION CONTRACTOR SHALL PROVIDE A COMPLETE CODE COMPLIANT AUTOMATIC WET
PIPE SYSTEM.
ALL AREAS ARE TO BE CONSIDERED LIGHT HAZARD, UNLESS NOTED OTHERWISE, WITH A MINIMUM SPRINKLER DISCHARGE DENSITY OF 0.10 GMP/SQ. FT. FOR THE MOST HYDRAULICALLY REMOTE 1500 SQ. FT. SPRINKLER SPACING SHALL NOT EXCEED MAXIMUM SPACING DISTANCES SET FORTH BY NFPA 13.
SUBMIT COORDINATION DRAWINGS PRIOR TO INSTALLATION.
AREAS NOTED BY A DIAGONAL HATCH: PROVIDE AREA WITH ORDINARY HAZARD GROUP 2, WITH A MINIMUM SPRINKLER DISCHARGE DENSITY OF 0.2 GPM/SQ. FT. FOR THE MOST HYDRAULICALLY REMOTE 1500 SQ. FT. SPRINKLER SPACING SHALL NOT EXCEED MAXIMUM SPACING DISTANCES SET
FORTH BY NFPA 13.
A.
B.
C.
D.
PAINT BOOTH 102 SHALL BE PROTECTED TO AN EXTRA HAZARD, GROUP 2 LEVEL, WITH A MINIMUM SPRINKLER DISCHARGE OF 0.40 GPM/SQ. FT. FOR THE ENTIRETY OF THE AREA. SPRINKLER SPACING SHALL NOT EXCEED MAXIMUM SPACING DISTANCES SET FORTH BY NFPA 13. QUICK RESPONSE-TYPE
SPRINKLER HEADS ARE NOT ALLOWED WITHIN THE SPACE COVERAGE.
PROVIDE PENDANT SPRINKLERS WITHIN THE EXHAUST DUCTWORK SERVING PAINT BOOTH 102.
SPRINKLERS SHALL BE SPACES AT MAXIMUM 10 FT. CENTERS BEGINNING NO MORE THAN 5 FT FROM THE DUCT ENTRANCE. A SPRINKLER HEAD SHALL BE LOCATED AT THE TOP OF THE RISER WITHIN THE
HEATED ENVELOPE.
PROVIDE PENDANT SPRINKLERS WITHIN THE EXHAUST PLENUM.
PROVIDE ACCESS PANELS ON EXHAUST DUCTWORK TO ALLOW INSPECTION OF EACH SPRINKLER
HEAD. COORDINATE LOCATIONS OF ACCESS PANELS WITH M.C.
PROVIDE LISTED CONTROL VALVE FOR EXHAUST DUCT AND PLENUM SPRINKLERS.
RPZ PROVIDED BY P.C. COORDINATE HYDRAULIC REQUIREMENTS WITH P.C.
NORTH OF THIS DOTTED LINE,…