P15PS01955 – Amendment 000003 Summary of Changes

A. The following are questions/inquiries from interested offerors, and the official Government responses to those questions/inquiries. NOTE: Any questions received in the future, may or may not be answered at the discretion of the Government.

Q1. On drawing sheet E1 it states the existing conductor is 2.4Kv, would you please provide the specific size and type of this conductor?

Is there any specific type of splice required for the rerouting of these conductors?

A1. It is not the intent of this contract to reconnect the 2.4 kV feeders. They are to be cut and terminated in Manholes 1 and 2 with enough slack to allow for future splices. Contractor is to verify they are not active before cutting. The only circuit to be maintained is the street lighting circuit. The splicing requirements are covered in the specifications.

End of Amendment