P14 Cost-Free Design Analysis - 38 pages.pdf
PDF 4 MB Posted
- Solicitation number
- 36C26326B0012
About this file
This is a 100% Contract Documents Design Analysis for a domestic water system repair project at the Fargo VA Health Care System intended to prevent Legionella disease. The project is under Architect/Engineer Contract No. 36C26319D0045/36C26324N0529, Project Number 437-23-165, with a contract documents due date of February 14, 2025. FourFront Design, Inc. serves as the architecture/mechanical/electrical engineering firm with a team including Ray Dawes (Mechanical/Electrical Engineer), Jared Lott (Project Manager), Will Wangen (Electrical Engineer), Pat Morgan (Mechanical Engineer), Joel Simonyak (Principal Architect), and Milena Dahlstedt (Interior Designer). The Contracting Officer Representative is Chad Holman, with Cliff Halvorson as the alternate.
The project scope encompasses upgrading seven existing water monitoring stations across buildings 1, 9, 46, and the building 10 Boiler Plant to BAS-monitored stations capable of monitoring and controlling water pressure, temperature, pH, conductivity, and disinfectant concentration. Each station will integrate into the existing Fargo BAS via BACnet and include disinfectant injection capability. Thermostatic mixing valves will be added to approximately 175 existing plumbing fixtures, with existing pedal-operated faucets and sinks to be replaced with new wall-mount sinks and wrist blade-operated faucets. Design criteria reference the VA Plumbing Design Manual (rev 02/24), VHA Directive 1061 (amended 03/24), and North Dakota Plumbing Code (2018 UPC amended). Electrical work involves minor power modifications at monitoring station locations, with all systems powered from single-phase 120V circuits. Level II and Level III ICRA (Infection Control Risk Assessment) requirements apply to specified rooms throughout the facility. The document includes specifications for water monitoring equipment from Lutz-JESCO (Topax MC4 Controller), chemical feed pumps, flow meters, thermostatic mixing valves, wall-mount lavatories, and wrist blade faucets, with detailed technical specifications and performance requirements for all components.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Repair Domestic Water System to Prevent Legionella
Fargo VA Health Care System
Design Analysis
Architect/Engineer Contract No: 36C26319D0045/ 36C26324N0529 Project
Number: 437-23-165
Design Phase: 100% Contract Documents
Due Date: 14 February 2025
100% Contract Documents - System Repair to Prevent Legionella
Project Team
Owner:
Chad Holman Contracting Officer Representative Fargo VA Health Care System 2101 Elm Street North Fargo, ND 58102 701-239-3700 Ext. 3552
Cliff Halvorson Alternate Contracting Officer Representative Fargo VA Health Care System 2101 Elm Street North Fargo, ND 58102 701-232-3241 Ext. 3905 Clifford.Halvorson@va.gov
Architecture/Mechanical/Electrical Engineering Team:
FourFront Design, Inc.
517 Seventh St.
Rapid City, SD 57701 Phone: (605) 342-9470 Ray Dawes, Mechanical/Electrical Engineer | ray.dawes@fourfrontdesign.com Jared Lott, Project Manager | jared.lott@fourfrontdesign.com Will Wangen, Electrical Engineer | will.wangen@fourfrontdesign.com Pat Morgan, Mechanical Engineer | pat.morgan@fourfrontdesign.com Joel Simonyak, Principal Architect | joel.simonyak@fourfrontdesign.com Milena Dahlstedt, Interior Designer | milena.dahlstedt@fourfrontdesign.com
TABLE of CONTENTS
1. Introduction……………………………………………………………………………………………………………………………………………….2
1.1 Purpose of Design Analysis………………………………………………………………………………………………………………….2
1.2 Project Overview…………………………………………………………………………………………………………………………………2
1.3 Authority…………………………………………………………………………………………………………………………………………….2
1.4 Request for Information………………………………………………………………………………………………………………………3
1.6 ICRA Information………………………………………………………………………………………………………………………………….4
2. Primary Facilities or Facility………………………………………………………………………………………………………………………..4
2.1 Building Organization…………………………………………………………………………………………………………………………..4
2.2 Parametric Design Analysis........................…………………………………………………………………………………………..4
2.2.1 Architectural & Interior Design………………………………………………………………………………………………………….4
2.2.2 Plumbing……………………………………………………………………………………………………………………………………………5
2.2.3 Electrical……………………….…………………………………………………………………………………………………………………..5
4. Appendices…………………………………………………………………………………………………………………………………………………..7
Appendix A Plumbing Cut Sheets
Appendix B Specifications Table of Contents
Appendix C Project Schedule
1.0 Introduction
1.1 Purpose of Design Analysis
The purpose of this design analysis is to develop a comprehensive and fully coordinated plan to upgrade the Domestic Water Monitoring Systems at the Fargo VA Health Care System to help prevent Legionella Disease (LD). The analysis will identify and address existing system issues, propose specific upgrade solutions for water system components, and ensure that the design incorporates automated monitoring and control systems to enhance water quality and safety. The design will prioritize improvements in water system monitoring, control, and equipment programming to minimize risks associated with water stagnation, heat loss, and contamination, ensuring compliance with VHA Directive 1061.
1.2 Project Overview
1.2.1 Purpose and Scope
FourFront is committed to supporting the Fargo VA Health Care System in its efforts to reduce or eliminate the risk of Legionella Disease (LD) by upgrading the Domestic Water Monitoring Systems across its facilities. FourFront has conducted an on-site evaluation of the 7 existing water monitoring stations in the basement of the Medical Center and the lower level of the Boiler Plant. FourFront has also conducted on-site documentation and inventory of approximately 175 plumbing fixtures to determine the need for adding thermostatic mixing valves to existing fixtures or replacing existing faucets. Our goal is to provide design recommendations that will bring these systems up to optimum standards, focusing on preventing water contamination and ensuring the safety of both employees and patients.
As part of a multi-step solution, the first step involves increasing the water temperature at the water heaters while lowering it at point-of-use fixtures. This will be achieved by installing thermostatic mixing valves to reduce temperature, effectively minimizing the risk of Legionella growth.
1.3 Authority
FourFront will execute the project under Contract No. 36C26319D0045/ 36C26324N0529, dated 9 May
Document Updates and Status
Revision Date Description Author Reviewed Approved Notes
4 16-Aug-24 Schematic Design 35% JL RD X
14-Nov-24 Design Documents 65% JL PM X
7-Jan-25 Construction Development 95%
JL RD X
13-Feb-25 Contract Documents 100% JL RD X
1.4 Request for Information
This section is a log of Design RFI asked during the SD/DD/CD process from FourFront Design to the VA. VA response status are as of design narrative submittal date.
RFI #1 Date Submitted: 16-May-2024
Current Fargo VA floorplans with amended floorplans up to date with respect to recent construction projects in any sort of autocad .dwg or .dxf format, or alternatively Revit .rvt model file.
Answered: Yes
Current Fargo VA updated as-built plumbing plans that show all water mains and branches in any sort of autocad .dwg or .dxf format, or alternatively Revit .rvt model file.
Any plumbing isometric or single line as-built plans in autocad .dwg or .dxf format showing sizes of piping and their areas served, alternatively .pdf format would be beneficial as well.
RFI #2 Date Submitted: 16-May-2024
VA provide hospital locations, water branch, or fixture locations that have the required sensitivity to risk of infectious control for ultra-sensitive conditions or people who need extra protection at a faucet or potable water distribution point.
RFI #3 Date Submitted: 16-Aug-2024
Please clarify section 1.21, "VA Tririga CPMS," in Specification 01 00 00 General Requirements, and confirm if it applies to this project?
1.6 ICRA Information
The following ICRA requirements were received from the Fargo VAHCS Safety and Occupational Health Specialist Rachel Peters via the 65% review meeting and email on January 6, 2025:
Level II ICRA requirements will be implemented for the following rooms: 1A, 1A-30C, 1D-06, 1D-07, 1D- 115, 1D-117, 1D-126, 1D-127A, 1D-127B, 1D-13, 1D-133, 1D-14, 1D-18, 1D-20, 1D-23, 1D-24, 1D-25, 1D-26, 1D-28, 1D-29, 1D-30, 1D-31, 1D-32, 1D-33, 2B-03, 2C-58A, 2C-70, 2C-72, 2C-76, 3C-24, 3C-26, 3C-79, 3C-88, 3C-89, and 4B-36.
Level III ICRA requirements: 2C-43, 2C-44, and 2C-46.
2. Primary Facilities or Facility
2.1 Building Organization
2.1.1 Facility Description
The Fargo VAMC has basement through four floors and an attic / mechanical penthouse. Work will take place throughout buildings 1, 9, and 46 for water monitoring station upgrades as well as thermostatic mixing valve additions and faucet/sink replacements. Work in the building 10 Boiler Plant to take place in the lower level of the North end for upgrades of the water monitoring station.
2.2 Parametric Design Analysis
2.2.1 Architecture & Interior Design
Architectural and interior design requirements will be minimal. At the locations impacted by replacement of pedal-operated faucets, finishes will be patched or replaced to match existing surrounding finishes. Depending on the location, these finish patches will include welded sheet flooring, resilient base, tile, and wall paint. Noted finishes are for basis of design only, based on Fargo VA station standards and client-provided information.
Contractors are to verify finishes in field.
2.2.2 Plumbing
2.2.2.1 Design Criteria:
VA Plumbing Design Manual (rev 02/24)
VHA Directive 1061 (amended 03/24) for Legionella Prevention
North Dakota Plumbing Code (2018 UPC amended)
2.2.2.2 Domestic Water:
A total of 7 existing water monitoring stations are to be replaced and upgraded to BAS monitored stations to monitor and control water pressure, temperature, pH, conductivity, and disinfectant concentration. Each station will be able to inject disinfectant (e.g. chlorine, chloramine) at each station location. Each monitoring station is to be integrated into the existing Fargo BAS via BACnet. Water monitoring manufacturer is to provide startup and commissioning of each station in lieu of 3rd party commissioning.
2.2.2.3 Plumbing Fixtures
Thermostatic mixing valves are to be added to the existing fixtures noted in the plumbing drawings that do not currently have them installed. The existing stops are to be used to isolate the fixture to allow for installation of the mixing valve. Existing pedal operated faucets and sinks noted in the plumbing drawings are to be replaced with new wall mount sinks, wrist blade operated faucets, and new thermostatic mixing valves to allow for temperature mixing control. The domestic hot and cold-water piping will be modified to replace the existing closely spaced stops to allow for installation of new water stops and supply lines to the wrist blade faucet. Since the submittal of the 65% documents, there have been additional thermostatic mixing valves installed in-house by the VA plumbing staff as well as requests to replace four existing sensor faucets and lavatories. These changes have been reflected for the 95% submittal.
2.2.3 Electrical
2.2.3.1. Design Criteria and References
NFPA 70: National Electrical Code (2024)
VA Electrical Design Guide (December 1, 2019)
2.2.3.2 Functional and Technical Requirements
2.2.3.2.1 Summary of Scope
Fargo VA hospital is updating multiple domestic water monitoring systems to help prevent the buildup of Legionella. Electrically this will involve minor power modifications at monitoring station replacement locations and power for Water monitoring stations.
2.2.3.2.2 Illumination Levels
No new lighting is intended for this project.
2.2.3.2.3 System Voltage
All water monitoring stations and BAS systems to be powered from single phase 120V circuits.
2.2.3.3 Design Objectives and Provisions
2.2.3.3.1 Electrical Characteristics
Design includes only minor power modifications for power to new water monitoring stations. Existing receptacles/homeruns and panels are shown currently for reuse with new water monitoring stations. Existing duplex receptacle serving water monitoring station in the boiler plant to be replaced with a GFI receptacle.
2.2.3.3.2 Voltage Drop
Voltage drop calculations are not intended to be performed for this project due to the very short distances intended for any added branch circuits.
2.2.3.3.3 Conductors
All new interior conductors and cables will be THHN or THHW and heat resistant 60 or 75-degree C (140 and/or 167-degree F) type cable.
2.2.3.3.4 Wiring System
All wiring will be installed in conduit. EMT will be utilized for all new branch circuits. Flexible metal conduit will be allowed for installation within existing walls or for final connection to equipment with a maximum length of six feet. Use set screw fittings.
2.2.3.3.5 Special Power Outlets
Ground Fault Circuit Interrupter (GFI) outlet to replace existing duplex outlet serving the water monitoring station in the boiler plant.
4. Appendices Appendix A Plumbing Cut Sheets
Appendix C Project Schedule
Appendix A Plumbing Cut Sheets
This Monitoring and Disinfection system must be able to operate from 1 single system.
PROCESS ANALYZER AND CONTROLLER
Lutz-JESCO Topax MC 4 Controller and Analyzer will must have the following:
● Measure and control total chlorine 0-10 mg/l Measure and control free chlorine 0-15 mg/l / Chlorine Dioxide 0-15 mg/l
● Measure and control of Conductivity value
● Measure and control of pH value
● Measure of the temperature (5-60c)
Analyzer shall have the following characteristics.
1. Performance:
● Continuous total chlorine residual analysis, 0-10, up 15 psig
● Continuous free chlorine/Chlorine Dioxide residual analysis, DMZ3.1, up 90 psig
● Conductivity 0-2000 uS (0.1%)
● Single rod pH measurement 0.00-14.00
● P, PI, and PID Controller Performance (fixed set-point or 2-sided)
● Temperature measurement with Pt100 (-10 to 90 deg. C)
2. Features:
● Protection Class
● IP65
● 3-point control with position feedback
● Potentiometer value 1…10Kohm
● Continuous Current output 0/4…20mA
● Current for chart recorder 0/4…20mA
● Disturbance Variable (OPTIONAL)0/4…20mA or 20…. 4mA
● 200 Ohm Influence of disturbance variable or ratio feed
● Ratio setting 1:0.1 to 1:10
● Computer interface RS 485
Power requirements for the Topax Controllers shall consist of 120/230V, 1 phase, 60 HZ supply.
MS-1
WATER MONITORING
STATION
WATER SAMPLING STATION
Lutz-JESCO EASYPRO Water Sampling Station that will contain the Topax Controller Model MC4 Total Chlorine analyzer, pH electrode, FREE chlorine/Chlorine Dioxide measuring cell, Conductivity electrode and rotameter to guarantee consistent flow through the sampling station. The Water Sampling Station shall have the following characteristics.
● Sensor holders to accommodate the free chlorine sensor, temperature sensor, conductivity electrode and pH probe.
● Basket Strainer
● Durable Polypropylene Wall panel
● SCH 80 PVC plumbing
● True union ball valves to adjust and isolate flow.
● Tubing compression connections for Inlet, Outlet and Waste.
● Locally wired to the analyzer, measuring cell and temperature probe.
CHLORINE/CHLORINE DIOXIDE MEASURING MODULE
Lutz-JESCO will supply a self cleaning chlorine/chlorine dioxide measuring module that will act as an input amplifier for the Chlorine/Chlorine DIoxide analyzer. The input amplifier will convert and process the signal from the chlorine/chlorine dioxide-measuring cell. The measuring range of the process will be fully adjustable by simple program settings in the Topax MC 4. Units with less than 1% accuracy will not be accepted
● Range 0-10/15 mg/l
The sensor shall be constructed of PMMA with both a platinum and copper electrode. Self-cleaning will be accomplished by glass balls located inside the PMMA cell and rotated by the continuous flow of the sample water. The sensor must have the ability to measure in a range of 0…15 mg/l Chlorine measuring units that require reagents will not be accepted. Membrane style units will not be accepted. Units that are not self cleaning will not be accepted
MS-1
Monitoring and Control System
Monitor & Control Solutions
● CELLULAR 4G LTE Category 6
● TECHNOLOGY Bands: 1, 2, 3, 4, 5, 7, 8, 12, APPROVALS FCC, IC, CE, PTCRB
● Verizon, AT&T, T-Mobile, Sprint, US Cellular
● Bell, Rogers, Telus
POSITION LOCATION
● GPS, GLONASS
HOST INTERFACES 10/100 Ethernet (RJ45)
● 10/100 Ethernet (RJ45)
● 1 RS-232 (Terminal Block)
● 1 RS-485 (Terminal Block)
● 1 Full-Speed USB (Type A)
● 1 High-Speed Micro-USB OTG
INPUT/OUTPUT
● 4 user configurable
● Digital/Analog Inputs
● (0-5v/4-20mA)
● 2 Digital Outputs
● * Expandable with Z1201S I/O Module
MEMORY
● 256 MB SLC NAND Flash
● 1 microSD Slot (Externally Accessible)
13, 20, 25, 26, 29, 30, 41
● 3G WCDMA
● Bands: 1, 2, 3, 4, 5, 8
● Multi-Carrier, Auto-Configuring
● Dual-SIM 2FF
● DL MIMO/Rx Diversity Support
MS-1
● 128 MB DDR2 RAM
PLATFORM
● Linux 4.xx Operating System
● Atmel ARM9 Processor
● Ctek Web Manager 2.0
● Ctek SkyCloud Services
● Ctek Automation Application
POWER Input:
● 9 - 24 VDC
● Power: 190mA (Typical)*
ENVIRONMENTAL
● Operating Temperature: -30 to +70 ̊C
● Humidity: 90% Non-Condensing
DIMENSIONS
● 5.48L x 4.72W x 1.45H (inches)
WARRANTY/SUPPORT
● 3 Year Standard Warranty
Chemical Feed Pump
The SMART Digital DDA is a compact positive displacement, diaphragm dosing pump with variable-speed drive (stepper motor) and intelligent control electronics with minimum energy consumption.
The SMART Digital Dosing series operates at full stroke length to ensure optimum accuracy, priming and suction, even for high-viscosity or degassing liquids.
The duration of each discharge stroke varies according to the capacity set, resulting in optimum smooth and continuous discharge flow.
The click-stop mounting plate allows installation in three different positions without using any additional accessories.
The control cube can be turned easily into the front, left or right position.
MS-1
The click wheel and the multi-coloured backlit graphical, plain-text LC display make commissioning and operation intuitive.
The control elements are protected by a transparent cover.
The dosing head is composed of:
● Long lifetime and universal, chemically resistant full-PTFE diaphragm.
● Double ball valves for highest dosing accuracy.
● Deaeration valve for easy start-up.
Operation modes:
● Manual dosing in ml/h, I/h or g/h.
● Pulse control in ml/pulse (incl. memory function).
● Analog control 0/4-20 mA (scalable).
● Pulse-based batch function in ml, l or gal.
● Timer-based batch function (Dosing timer, cycle or week).
● Fieldbus control (Genibus prepared for ProfibusDP E-box).
Other features:
● Auto deaeration during pump standby to avoid breakdowns due to air-locking.
● Two SlowMode steps (anti-cavitation), 50 % (maximum flow: 0.9906 US gal/hour) and 25 % (maximum flow
● Service information display to show when service and which wear-part order number is required.
● Two-step key lock function to protect the pump against unauthorized access.
● Additional display function to provide further information, e.g. the actual mA input signal.
● Counter for total dosed volume (resettable), operating hours, etc.
● Save and load custom settings as well as reload of factory settings.
Signal inputs/outputs:
● Input for pulse, analog 0/4-20mA, external stop.
● Input for low-level and empty-tank signals.
● Two potential-free output relays for max. 30 V AC/DC (configurable, e.g.
alarm, stroke signal, pump dosing, timer etc.)
● Output analog 0/4-20mA.
MS-1
● Fieldbus communication interface (GeniBus, also for additional Profibus DP E-box to retrofit).
Ultrasonic Transit Time Flow Meter
Non-invasive clamp-on ultrasonic transit time flow meter used to measure volumetric flow rate, total, and heating/cooling energy rates in liquids.
FEATURES:
● Clamp-on transducers -Pipe sizes 0.5 to 100 inches
● Bi-directional flow
● Install with no process shutdown
● No pressure head loss
● No moving parts to maintain or replace
● Reynolds, sound speed & temp compensation
● Display flow rate, total, temp, BTU
● Data logging stored on 8GB Micro SD Card
● Outputs 4-20mA, Pulse
● Communications Modbus, BACnet & more
*No Components of this system are to be proprietary
MS-1
E q u i p m e n t I n f o r m a t i o n
W W W . G A R R A T T C A L L A H A N . C O M
TOPAX® MC CONTROLLER
DESCRIPTION:
The TOPAX® MC is Lutz-Jesco’s latest multi-channel controller. Its modular design makes it an adaptable and extremely effective solution for all your measurement and control technology requirements.
Whether you need to measure chlorine dioxide, chlorine, the pH value, the Redox(ORP) value or the pH value four times, the modular design permits any combination.
The outputs can also be freely selected. Users can actuate the dosing pumps using an optocoupler or relay and servomotors by using a relay or a 20 mA output.
The high-resolution 5-inch color display has a user-friendly operating interface - simple touch control and intuitive navigation menu that can be set to multiple languages.
You can choose: You can use the four analogue outputs (0/4 – 20 mA) or the network capability to transfer the measured values to a web browser or a tele-maintenance point. A programmable interval timer can be used to set an automatic alert for wear-related sensor change.
TECHNICAL DATA:
Housing dimensions (W x H x D) inches 12 x 9.5 x 4.25
Voltage supply 100 – 240 V AC, 50/60 Hz
Power Consumption W max. 20
Analogue outputs for remote transmission 4 x 0/4 – 20 mA, working resistance max. 500 Ω
Disturbance variable input mA 0/4 – 20
Interfaces Ethernet TCP/IP or RS485 Modbus RTU (optional)
Protection Class IP65
Ambient Temperature °F 23 to 113 (no exposure to direct sunlight)
Control characteristic
P, PI, PID or PD behavior, control direction selectable with disturbance variable feed forward, 2-side control selectable
Number of sensor inputs (depending on version) up to 4*
Free Chlorine
Amperometric 3-electrode measuring cell with potentiostat
(DMZ3.1)
mg/l 0 – 15 (dependent on the measuring cell transconductance)
S120 excess chlorine meas. cell mg/l 0 – 10 (dependent on the measuring cell transconductance)
Diaphragm-covered meas. cell mg/l 0 – 10 (dependent on the measuring cell)
Chlorine
Dioxide
Amperometric 3-electrode measuring cell with potentiostat
(DMZ3.1)
mg/l 0 – 15 (dependent on the measuring cell transconductance)
CS120 excess chlorine meas. cell mg/l 0 – 10 (dependent on the measuring cell transconductance)
Diaphragm-covered meas. cell mg/l 0 – 2 (dependent on the measuring cell)
Total Chlorine Diaphragm-covered meas. cell mg/l 0 – 10 (dependent on the measuring cell) pH Value pH single-rod measuring cell pH 0 – 14 (dependent on the single-rod measuring chain)
Redox Value Redox single-rod measuring cell mV 0 – 1000 (dependent on the single-rod measuring chain)
EB1600 11/19
MS-1
W W W . G - C . C O M
DDA SMART
PUMP
The SMART Digital DDA is a compact positive displacement, diaphragm dosing pump with variable-speed drive (stepper motor) and intelligent control electronics with minimum energy consumption. The SMART Digital Dosing series operates at full stroke length to ensure optimum accuracy, priming and suction, even for high-viscosity or degassing liquids. The duration of each discharge stroke varies according to the continuous discharge flow capacity set, resulting in optimum smooth and continuous discharge flow.
The click-stop mounting plate allows installation in three different positions without using any additional accessories. The control cube can be turned easily into front, left or right position. The click wheel and the multi-colored backlit graphical, plain-text LC display make commissioning and operation intuitive. The control elements are protected by a transparent cover.
Features:
• Scalable control input signals (up to 1:3000 turndown ration) to meet the widest flow rates in one model.
• Slow mode to improve the max viscosity up to 2500 CPS
• Stepper motor driven with universal power supply (1x100-240VAC, 50/60 Hz)
• Auto deaeration during pump standby to avoid breakdowns due to air-locking.
• Two SlowMode steps (anti-cavitations), 50 % (maximum flow: 0.9908 US gal/hour) and 25 %
(maximum flow: 0.4967 US gal/hour), e.g. for high-viscosity or degassing liquids.
• Service information display to show when service and which wear-part order number is required.
• Two-step key lock function to protect the pump against unauthorized access.
• Additional display function to provide further information, e.g. the actual mA input signal.
• Counter for total dosed volume (resettable), operating hours, etc.
• Save and load customized settings as well as reload of factory setting
• Reliable dosing of fluids that off-gas (sodium hypochlorite, etc.)
• NSF approved
Specifications:
MODEL DDA 7.5-16 DDA 12-10 DDA 17-7 DDA 30-4
DELIVERY 0.0006 to 2 GPH 0.0031 to 3.1 GPH 0.0045 to 4.5 GPH 0.008 to 8 GPH
MAX PRESSURE 232 PSI 150 PSI 100 PSI 60 PSI
HEAD PVDF PVDF PVDF PVDF
DIAPHRAGM Teflon Teflon Teflon Teflon
SEATS/FITTINGS
/BALLS
Teflon/PVDF/
Ceramic Teflon/PVDF/
Ceramic Teflon/PVDF/
Ceramic Teflon/PVDF/
Ceramic
DIMENSIONS
Max. H. 7-3/4” Max. W. 11”
Max. H. 7-7/8” Max. W. 11”
Max. H. 7-7/8” Max. W. 11”
Max. H. 8” Max. W. 11-5/8”
EB2929 9/13
DESCRIPTION
The NCMB2-F/E Series is a non-invasive clamp-on ultrasonic transit time flow meter used to measure volumetric flow rate, total, and heating/cooling energy rates in liquids.
FEATURES:
-Clamp-on transducers -Pipe sizes 0.5 to 100 inches -Bi-directional flow -Install with no process shutdown -No pressure head loss -No moving parts to maintain or replace -Reynolds, sound speed & temp compensation -Display flow rate, total, temp, BTU -Data logging stored on 8GB Micro SD Card -Outputs 4-20mA, Pulse -Communications Modbus, BACnet & more
TECHNOLOGY:
The NCMB2 ultrasonic transit time flow meter clamps onto the outside of pipes and does not contact the internal liquid. It operates on clean liquids as well as those with small amount of suspended solids or aeration. It utilizes the latest innovations in non-contact flow metering technology to optimize the performance of your flow monitoring, process control, balancing or batching applications.
The NCMB2 is available in two versions:
NCMB2-F: Flow Meter model indicates flow rate and total with a pulse, 4-20mA output, Modbus RTU or BACnet MS/TP communications. Other communications options available. Typical applications are water, sewage, cooling water, and chemicals.
NCMB2-E: Energy model indicates flow rate, total, temperature, BTU with a pulse, 4-20mA output, Modbus RTU or BACnet MS/TP communications.
Other communications options available.
Typical applications are heating/cooling hydronic loops.
Product Data Sheet
Ultrasonic Transit Time Flow Meter NCMB2-F/E series
NCMB2-F/E Transmitter
NCMTX-C-RZ-AC-WW Transducer
NCMTX-C-RZ-AC-WW Transducer
MS-1
SPECIFICATIONS
System
Liquid Types Most clean liquids or liquids containing small amounts of suspended solids or gas bubbles Flow Accuracy Medium and Large Pipes ± 0.5% ± 0 0.049 ft/s (0 015 m/s)
Small Pipes 1 in (25 mm) and larger = ±1% ± 0 03 ft/s (0 009 m/s) 3/4 in (20 mm) and smaller = ±1% of full scale
Repeatability 0.2% above 1.5 ft/s Velocity Medium and Large Pipes Up to 40 ft/s, depending on pipe and fluid
Small Pipes Up to 20 ft/s, depending on pipe and fluid Straight Run Requirements
10 diameters upstream, 5 diameters downstream from single elbow - typically for flow rates of 10 fps (3.048m/s)
Certification and Compliance
General Safety (all models): cCSAus, CE, Pollution Degree 2, CE compliance to Low Voltage Directive, 2014/35/EU U.S./Canada Hazardous Location transmitter and transducers:
CSA-c-us Class I Division 2 Groups ABCD T4 Requires flexible conduit Not available with UZ ATEX/IECEx Hazardous Location transmitters and transducers:
II 3 G Ex ec nC ic IIC T4 Gc II 3 D Ex tc IIIC T100 °C Dc Not available with UZ, HZ transducers; flexible conduit, Auxiliary Dry Contact card
Transmitter
Power Options 24V DC/AC 9…28V DC @ 8 W max or 20…26 AC 47…63 Hz @ 0 5 A max, 2 Amp slow-blow fuse, not field replaceable
Mains AC 85…264V AC 47…63 Hz @ 24VA max 1 Amp slow-blow fuse, manually field replaceable
Display Keypad 4-button navigation, keypad with tactile feedback; polyester film Display Flow rate / Total. 128 × 64 pixel LED backlit graphical display; adjustable brightness and timeout; polycarbonate window
Enclosure NEMA Type 4X, IP67. Aluminum construction; painted; wall, panel or pipe mounting; stainless steel fasteners and mounting hardware; EPDM gasket Ambient Temperature Range –4…140° F (–20…60° C) Storage Temperature Range –40…176° F (–40…80° C) Humidity 0…85%, non-condensing
Configuration Via optional keypad or configuration software; software available on USB drive or download
Units - Programable
Velocity feet/second, meters/second Volumetric total US Gallons, Million Gallons, Imperial Gallons, Million Imperial Gallons, Acre-Feet, Liters, Hectoliters, Cubic Meters, Cubic Feet, Oil Barrels (42 gallons), Fluid Barrels (31.5 gallons), Imperial Fluid Barrels (36 imperial gallons), Pounds (Kilograms) and custom units
Flow rate Acre Feet/Day, Liters/Second, Liters/Minute, Liters/Hour, Cubic Meters/Second, Cubic Meters/Minute, Cubic Meters/Hour, Cubic Feet/Minute, Cubic Feet/Minute, Cubic Feet/Hour, Gallons/Second, Gallons/Minute, Gallons/Hour, Million Gallons/Day, Imperial Gallons/Second, Imperial Gallons/Minute, Imperial Gallons/Hour, Million Imperial Gallons/Day, Oil Barrels/Day, Fluid Barrels/Day, Imperial Fluid Barrels/Day and custom units
Energy total (energy meters)
British Thermal Unit (Btu), Thousand Btu, Millions Btu, Kilocalories, Mega calories, Kilowatt-hour, Megawatt hour, Kilojoules, Mega joules, Ton-hour (Refrigeration)
Heat/cooling rate (energy meters)
Btu/hour, Thousand Btu/hour, Millions Btu/hour, Ton (Refrigeration), Watts, Kilowatts, Megawatts, Kilojoules/hour, Mega joules/hour, Kilocalories/hour, Mega calories/hour
Temperature (energy meters)
Fahrenheit, Celsius, Kelvin
MS-1
Flow Meter
Energy Meter
Inputs and Outputs
0/4…20 mA output One 16-bit, isolated, max 800 Ohms, internal or external power
Two 16-bit, isolated, max 800 Ohms, internal or external power
Digital input One 5…30V DC, isolated, externally or internally sourced, reset totalizer or alarm output
Digital output
Two selectable pulse, alarm, flow direction, sink isolated open collector, 5…30V DC, max.
50 mA externally or internally sourced
Three selectable pulse, frequency, alarm, flow direction, isolated open collector, 5…30V DC, externally or internally sourced
RTD (energy only) None Two 2-wire, 3-wire or 4-wire Pt100/Pt1000 RTD 12-bit inputs; Range of –40…200° C; Clamp-on resistor kits available
Ports
Programming USB 2.0 mini B connector for connection to a device with configuration software EIA-485 Modbus RTU command set or BACnet MS/TP; Baud rates 9600, 14400,19200, 38400, 57600, 76800, 115k; terminating resistor selectable Ethernet Optional 10/100 Base T RJ45, communication via Modbus TCP/IP or BACnet/IP with webserver
Data Logging
Number of points Up to 8 parameters per record. Selectable 1 second to 1 day Transfer logs via memory card
Real Time Clock Backed up with a super capacitor, minimum of 32 days of data retention without power; Requires no servicing
MicroSD card slot 8 GB card, included with transmitter Alarms Records 150 previous alarms, warnings or errors Languages English, French, German, Italian, Spanish Security Four levels: Read-only, Operator, Service and Admin; 6-digit passcode number; selectable auto logout
Transducers
Model Construction Pipe/Tubing Sizes Protection
CA-CT *
fixed small pipe
CPVC, Ultem®, Nylon cord grip, PVC cable jacket; –40…194° F (–40…90° C) 0.5…2 in. (12…50 mm) NEMA 6 / IP67
UZ
adjustable small pipe
CPVC, Ultem, and anodized aluminum track system; Nickel-plated brass connector with Teflon insulation; PVC cable jacket, –40…194° F (–40…90° C)
0.5…2 in. (12…50 mm) NEMA 12
NZ
standard pipe
PVC, Ultem®, Nylon cord grip, PVC cable jacket;
–40…250° F (–40…121° C)
2…36 in (DN50…DN900) NEMA 6 /IP67
RZ
standard pipe
PBT glass filled, Ultem®, Nylon cord grip; PVC cable jacket; , –40…250° F (– 40…121° C)
2…36 in (DN50…DN900) NEMA 6 /IP67
JZ, KZ
standard pipe, integrated rail
PBT glass filled, Ultem, Nylon cord grip; PVC cable jacket; –40…250° F (– 40…121° C)
2.5…6 in.
(DN65…DN150)
2.5…12 in.
(DN65…DN300)
NEMA 6 /IP67
WZ
standard pipe, submersible
CPVC, Ultem, Nylon cord grip; Polyethylene cable jacket; –40…194° F (– 40…90° C)
2…36 in (DN50…DN900) NEMA 6P /IP68
HZ
high temperature
PTFE, Vespel, Nickel-plated brass cord grip;
FEP cable jacket; –40…350° F (–40…176° C)
2…36 in (DN50…DN900) NEMA 6 /IP67
LZ
large pipe
CPVC, Ultem, Nylon cord grip PVC cable jacket; –40…194° F (–40…90° C)
8…100 in NEMA 6 / IP67
YZ
large pipe submersible
CPVC, Ultem, Nylon cord grip; Polyethylene cable jacket; –40…194° F (– 40…90° C)
8…100 in NEMA 6P /IP68
+ CA-CT fixed small pipe transducers are pipe size, pipe material specific. Not adjustable.
RTD Kits
Part Number Description Temp Range RTD-3B-20 Pair of 3 wire RTD 1000 Ohm RTD with mounting kit and 20 ft of cable. 32…212° F (0…100° C) RTD-3B-50 Pair of 3 wire RTD 1000 Ohm RTD with mounting kit and 50 ft of cable. 32…212° F (0…100° C) RTD-3B-100 Pair of 3 wire RTD 1000 Ohm RTD with mounting kit and 100 ft of cable. 32…212° F (0…100° C)
MS-1; WATER MONITORING STATION
Transducers Fixed Small Pipe
Pipes and Tubing 1/2…2 in. (12…50 mm)
Fixed Small Pipe U-Bolt Connections CF, CL
ANSI/DN and Copper 2 in. (50 mm) Models
RZ
Pipes 2 in. (50 mm) and Larger
NZ, WZ, HZ, LZ, YZ
Pipes 2 in. (50 mm) and Larger
C (Min Clearance) A
B
TOP VIEW
OF PIPE
UZ
Adjustable Small Pipe ½ in to 2 in
Easy Rail (JZ, KZ) Adjustable 2.5 in to 6 in /12in
RZ NZ, WZ HZ LZ, YZ UZ JZ KZ
A 3.75 in. (95 mm) 2.95 in. (74.9 mm) 2.95 in. (74.9 mm) 3.40 in. (86.4 mm) 7 in. (178 mm) 13.62 in. (345.95 mm) 19.92 in. (505.97 mm) B 2.35 in. (60 mm) 2.75 in. (69.8 mm) 2.75 in. (69.8 mm) 2.94 in. (74.7 mm) 1.6 in. (42 mm) 11.73 in. (297.94 mm) 18.03 in. (457.96 mm) C — 3.00 in. (76.2 mm) 3.00 in. (76.2 mm) 3.20 in. (81.3 mm) 1.5 in. (39 mm) 0.75 in. (19.05 mm) 0.75 in. (19.05 mm) D 2.19 in. (56 mm) 1.70 in. (43.2 mm) 1.71 in. (43.4 mm) 2.50 in. (63.5 mm) — 0.79 in. (20.06 mm) 0.79 in. (20.06 mm) E — — — — — 2.76 in. (70.10 mm) 2.76 in. (70.10 mm) F — — — — — 2.36 in. (59.94 mm) 2.36 in. (59.94 mm)
B D
A C
D
D mm i n c h
MS-1
TRANSMITTER ONLY
Ultrasonic Clamp-on Meter Flow NCMB2-F - - - Certification
CE C
Hazardous Location, Division 1/Zone 2 B Transmitter Type 110/220 VAC Remote Mounted R 24 VDC/VAC Remote Mounted B Hardware 1/2 in. NPT Threads, Poly Cable Glands S Communication/Output Standard Output (Modbus RTU/BACnet MS/TP) S Standard Output, Modbus TCP Ethernet T Standard Output, BACnet/IP Ethernet V Standard Output, Aux Output 9 Testing & Tagging Factory Calibrated F Factory Calibrated/Stainless Steel Tag S
Ultrasonic Clamp-on Energy / Flow Meter NCMB2-E - C - - Certification
CE C
Transmitter Type 110/220 VAC Remote Mounted R 24 VDC/AC Remote Mounted B Hardware 1/2 in. NPT Threads, Poly Cable Glands S Communication/Output Standard Output S Standard Output, Modbus TCP Ethernet T Standard Output, BACnet/IP Ethernet V Standard Output, Aux Output 9 Testing & Tagging Factory Calibrated F Factory Calibrated/Stainless Steel Tag S
Note: Energy meter requires a 3 wire RTD.
RTD-3B-20 : Pair of 3 wire RTD 1000 Ohm , 20 ft of cable RTD-3B-50 : Pair of 3 wire RTD 1000 Ohm , 50 ft of cable RTD-3B-100 : Pair of 3 wire RTD 1000 Ohm , 100 ft of cable
TRANSDUCERS ONLY
Ultrasonic Clamp-on Transducers NCMTX - - - - Certification -CE (Standard) C Small pipe, ½ to 2 in, (13 to 50mm) UZ Medium pipe, 2 to 36 in, (50 to 915mm) – (Standard) RZ Medium pipe Submersible, 2 to 36 in, (50 to 915mm) WZ Medium pipe High Temperature, 2 to 36 in, (50 to 915mm) HZ Large pipe, 8 to 100 in, (203 to 2,540 mm) LZ Large pipe Submersible, 8 to 100 in, (203 to 2,540 mm) YZ Hazardous Location, Class 1, Division 2 B Medium pipe, 2 to 36 in, (50 to 915mm) RZ Medium pipe Submersible, 2 to 36 in, (50 to 915mm) WZ Large pipe, 8 to 100 in, (203 to 2,540 mm) LZ Large pipe Submersible, 8 to 100 in, (203 to 2,540 mm) YZ
Remote Cable Length (Required) 15 Feet AC 30 Feet AF 50 Feet AK 75 Feet AR 100 Feet BW 150 Feet BK 200 Feet DW Flex Conduit Length (Optional) None WW 5 Feet AA 15 Feet AC 30 Feet AF 50 feet AK 75 Feet AR 100 Feet BW 150 Feet BK 200 Feet DW
Note: Energy meter requires strap on RTDs.
Pair of 3 wire RTD 1000 Ohm, 20 ft of cable RTD-3B-20 Pair of 3 wire RTD 1000 Ohm, 50 ft of cable RTD-3B-50 Pair of 3 wire RTD 1000 Ohm, 100 ft of cable RTD-3B-100
755 Ash St, Canton GA 30114, USA – (770)516-3999 – sales@noncontactmeters.com www.noncontactmeters.com
Product Data sheet NCMB2. rev 8.14.20
Trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Noncontact Meters Inc reserves the right to change product or system specifications without notice. ©2020 Noncontact Meters, Inc. All rights reserved.
Job Name_______________________________________ Contractor_______________________________________
Job Location_____________________________________ Approval_________________________________________
Engineer_________________________________________ Contractor’s P.O. No._ ____________________________
Approval_________________________________________ Representative_ __________________________________
Engineering Specification
Series LFUSG-B Under Sink Guardian®
The LFUSG-B M3 Under Sink Guardian® 3⁄8" compression and Quick-Connect fitting thermostatic mixing valves maintain and limit hot water to desired selectable temperature between 80°F and 120°F (27°C and 49°C) with flow rates as low as 0.25 gpm (1.0 lpm) and as high as 2.25 gpm (8.5 lpm). The mixing valve is listed to ASSE Standard 1070 for single fixture applications and IAPMO cUPC. The LFUSG-B M3 features Lead Free* construction to comply with Lead Free* installation requirements. The superior flow characteristics of these valves provide temperature control with low pressure drop. As an added feature, the LFUSG-B M3 incorporates dual check valves to protect against cross-flow and integral screens to filter out debris. This product meets the reduced Q test statistic criteria of 0.5 ppb for lead per Section 9.5.1.1 of NSF/ANSI/CAN 61.
Features
• �Lead Free* Brass body construction
• Installs easily between the stop valves and faucet
• �Includes tamper resistant locking nut to prevent accidental mis-adjustment
• �Built-in check valves prevent migration of hot water to cold and cold water to hot water piping
• Provided with cap for three port application
• �Integral strainer with 40 mesh stainless steel screens to filter out debris
Applications The unit is intended for under sink installation to control the hot water temperature and minimize the occurrence of accidental scald ing. The water temperature must be adjusted by the installer using a thermometer to measure the hot water temperature at the faucet outlet. Maximum temperature of 105°F (41°C) is recommended.
Specifications A Thermostatic Mixing Valve shall be installed on the hot water supply to the fixture. The valve shall be ASSE Standard 1070 and IAPMO cUPC listed and control the temperature of the hot water.
It shall have a Lead Free* brass 4-port, “H” pattern body. Lead Free* under counter thermostatic valves shall comply with state codes and standards, where applicable, requiring reduced lead content. The valve shall include integral check valves, integral screens and an adjustment nut with locking feature. The valve shall be provided with 3⁄8" (10mm) male compression or Quick-connect fittings. The valve shall be Watts® Series LFUSG-B.
For satin chrome finish specify – SC.
ASSE 1070 & IAPMO cUPC Listed
Materials Body: Lead Free* Brass
Rubber Disc: Buna-N
O-rings: Buna-N
Spring: Stainless steel
Piston: Noryl®
Thermostat: Copper
Approval
This product meets the reduced Q test statistic criteria of 0.5 ppb for lead per Section 9.5.1.1 of NSF/ANSI/CAN 61.
Pressure – Temperature Minimum supply pressure: 30psi (207 kPa) Hot inlet temperature: 120°F-180°F (49°C-82°C) Cold inlet temperature: 39°F-80°F (3.8°C-27°C) Minimum inlet temperature differential: 5°F (2.8°C) Temperature range: 80°F-120°F (27°C-49°C) Maximum pressure: 150psi (10.3 bar) Minimum Flow: 0.25 gpm (1.0 l/m) Maximum Pressure Differential between Hot & Cold Water Supplies: 20%
ES-LFUSG-B M3
*The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
Noryl® is a registered trademark of SABIC Innovative Plastics®.
LEAD FREE*
ASSE 1070
LFUSG-B M3 LFUSG-B-QC M3
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Certified to
NSF/ANSI/CAN 61-9 & 372
MV-1; THERMOSTATIC
MIXING VALVE
Basic Construction
Typical Installations
Dimensions – Weights
| kPa | psi |
| 620 | 90 |
| 551 | 80 |
| 482 | 70 |
| 413 | 60 |
| 345 | 50 |
| 276 | 40 |
| 207 | 30 |
| 138 | 20 |
| 69 | 10 |
| 0 | 0 |
Flow Capacity
| 0 | 1.00 | 2.00 | 3.00 | 4.00 | gpm |
| 0 | 3.8 | 7.8 | 11.4 | 15.2 | lpm |
Two Handle Faucet Sensor Faucet
Check Module
Ferrule
Plunger
Body
Thermostat
Temperature Adjustment Screw
Screen
Compression Nut
Spring
Locking Nut
A
B
C
D
MODEL SIZE DIMENSIONS WEIGHT
A B C D
in. mm in. mm in. mm in. mm lbs. kgs.
LFUSG-B M3 3⁄8" Comp. 33⁄16 81 33⁄8 85 113⁄16 47 11⁄2 38 .82 .37 LFUSG-B-SC M3 3⁄8" Comp. 33⁄16 81 33⁄8 85 113⁄16 47 11⁄2 38 .82 .37 LFUSG-B-QC M3 3⁄8" Quick Connect 31⁄4 83 4 102 21⁄4 57 11⁄2 38 1.05 .48 LFUSG-B-QC-SC M3 3⁄8" Quick Connect 31⁄4 83 4 102 21⁄4 57 11⁄2 38 1.05 .48
Watts
LFUSG-B M3
This information is not intended to replace the full product installa-tion and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product.
NOTICE
ES-LFUSG-B M3 2302 © 2023 Watts
USA: T: (978) 689-6066 • Watts.com Canada: T: (888) 208-8927 • Watts.ca
Latin America: T: (52) 55-4122-0138 • Watts.com
LFUSG-B M3
MV-1; THERMOSTATIC
MIXING VALVE
33 © 2023 AS America Inc.
spec_0355-0356 Lucerne WallHung Lavs Rev. 3 9/23
To Be Specified:
❏ Color: ❏ White ❏ Faucet:
❏ Faucet Finish:
❏ Supplies:
❏ 1-1/4" Trap:
❏ Bracket Support (by others):
❏ Concealed Arms Support (by others):
Lucerne™
Wall-Hung Lavatory
VITREOUS CHINA
Lucerne™ Wall-Hung Lavatory
| • | Wall-hung sink |
| • | Vitreous china |
| • | Front overflow |
| • | D-shaped bowl |
| • | � Self-draining deck area with contoured back and side |
splash shields
| • | Faucet ledge |
| • | � Compliant with Texas Accessibility Standard (TAS) |
for children age group 13 and up
Faucet holes on 203 mm (8") centers:
| ❏ | 0356.028 For exposed bracket support (by others) |
| ❏ | � 0356.015 For wall hanger (included) or concealed |
arms support (by others) ❏ � 0356.915 For wall hanger (included) or concealed arms support (by others) less overflow ❏ � 0356.037 For wall hanger (included) or concealed arms support (by others) with extra 35 mm (1-3/8") hole for soap/lotion dispenser (by others) on right-hand side
Faucet holes on 102 mm (4") centers:
| ❏ | 0355.027 For exposed bracket support (by others) |
| ❏ | � 0355.012 For wall hanger (included) or concealed |
arms support (by others) ❏ � 0355.912 For wall hanger (included) or concealed arms support (by others) less overflow ❏ � 0355.056 For wall hanger (included) or concealed arms support (by others) with extra 35 mm (1-3/8") hole for soap/lotion dispenser (by others) on left-hand side
❏ � 0355.034 For wall hanger (included) or concealed arms support (by others) with extra 35 mm (1-3/8") hole for soap/lotion dispenser (by others) on right-hand side
❏ � 0355.041 With two holes spaced 343 mm (13-1/2") in back splash for 10 mm (3/8") bolts (by others)
Single center faucet hole:
| ❏ | 0356.041 For exposed bracket support (by others) |
| ❏ | 0356.421 For wall hanger (included) or |
| concealed arms support (by others) | |
| ❏ | 0356.921 For wall hanger (included) or |
| concealed arms support (by others) less overflow | |
| ❏ | � 0356.439 For wall hanger (included) or concealed |
arms support (by others) with single faucet hole on right ❏ � 0356.066 For exposed bracket support (by others) with single faucet hole on right ❏ � 0356.115 For wall hanger (included) or concealed arms support (by others) with extra 35 mm (1-3/8") hole for soap/lotion dispenser (by others) on left-hand side
❏ � 0356.137 For wall hanger (included) or concealed arms support (by others) with extra 35 mm (1-3/8") hole for soap/lotion dispenser (by others) on right-hand side
SEE FOLLOWING PAGES FOR ROUGHING-IN DIMENSIONS
0355.012
0356.041
BARRIER FREE
Compliance Certifications - Meets or Exceeds the Following Specifications:
| • | ASME A112.19.2 / CSA B45.1 for Vitreous |
| China Fixtures |
Nominal Dimensions:
540 x 464 mm (21-1/4" x 18-1/4")
Bowl sizes:
379 mm (14-7/8") wide 254 mm (10") front to back 165 mm (6-1/2") deep
P-102; WALL
MOUNT LAVATORY
34 © 2023 AS America Inc.
spec_0355-0356 Lucerne WallHung Lavs Rev. 3 9/23
Lucerne™
Wall-Hung Lavatory
VITREOUS CHINABARRIER FREE
8" CENTER CONFIGURATIONS
All Wall Hanger (included) or Concealed Arm Configurations
SIDE VIEW - ALL CONFIGURATIONS
102mm (4")
152mm (6")
152mm (6")
102mm (4")
86mm (3-3/8")
197mm (7-3/4")
8mm (5/16")
464mm (18-1/4")
540mm (21-1/4")
13mm (1/2")
FINISHED
WALL
FINISHED
WALL
(6) 25mm
(1") DIA.
ACCESS
HOLES
FOR
CONC.
ARMS
102mm (4") 27.4mm
(1-1/16")
87mm (3-3/8")
267mm (10-1/2")
425mm (16-3/4")
122mm (4-3/4")
44mm (1-3/4")
38mm (1-1/2") 10mm
(3/8")
DIA. ANCHOR
SCREW HOLES
203mm
(8")
SUPPLIES AS REQUIRED
1-1/4" O.D. WASTE
OUTLET FOR
DRAIN PLUG
1-1/4" O.D. WASTE
OUTLET FOR
POP-UP DRAIN
27mm x 8mm (1 x 1/4") SLOTS
S-9 HANGER
3m m (8
*26 0m m (1
0- 1/
4"
8m m (1
1- 3/
4"
2m m
(1 3-
7/ 8"
7m m
4m m
FINISHED
FLOOR
58mm (2-1/4") DIA.
HOLES FOR
CONCEALED ARMS
34" (864mm)
27" MIN.
(686mm)
18-1/4" (464mm)
8" MIN.
(203mm)
FINISHED
WALL
6" MAX.
(152mm)
9" MIN.
(229mm)BARRIER FREE
CLEARANCE
11" (279mm)
102mm (4")
152mm (6")
152 mm (6")
86mm (3-3/8")
197mm (7-3/4")
8mm (5/16")
464mm (18-1/4")
540mm (21-1/4")
13mm (1/2")
FINISHED
WALL
(6) 25mm
(1") DIA.
ACCESS
HOLES FOR
CONC. ARMS
102mm (4")
27.4mm (1-1/16")
87mm (3-3/8")
267mm (10-1/2")
425mm (16-3/4")
122mm (4-3/4")
44mm (1-3/4")
38mm (1-1/2")
10mm (3/8")
DIA. ANCHOR
SCREW HOLES
203mm
(8")
SUPPLIES
AS REQUIRED
1-1/4" O.D. WASTE
OUTLET FOR
DRAIN PLUG
1-1/4" O.D. WASTE
OUTLET FOR
POP-UP DRAIN
27mm x 8mm (1" x 1/4") SLOTS
S-9 HANGER
203mm (8")
*286mm (11-3/4")
298mm (11-3/8")*
352mm (13-7/8")*
787mm (31") 864mm (34")
FINISHED
FLOOR
58mm (2-1/4") DIA.
HOLES FOR
CONCEALED ARMS
203mm (8")
34" (864mm)
27" MIN.
(686mm)
18-1/4" (464mm)
8" MIN.
(203mm)
FINISHED
WALL
6" MAX.
(152mm)
9" MIN.
(229mm)
11" (279mm)
BARRIER FREE
CLEARANCE
FINISHED
WALL
FINISHED
WALL
BARRIER FREE
CLEARANCE
8" MIN.
(203mm)
6" MAX.
(152mm)
34" (864mm)
27" MIN.
(686mm)
9" MIN.
(229mm)
18-1/4" (464mm)
11" (279mm)
17" (432mm)
4" CENTER CONFIGURATIONS
All Wall Hanger (included) or Concealed Arm Configurations
NOTES:
* �DIMENSIONS SHOWN FOR LOCATION OF SUPPLIES AND “P”
TRAP ARE SUGGESTED. PROVIDE SUITABLE REINFORCEMENT
FOR ALL WALL SUPPORTS. FITTINGS NOT INCLUDED AND MUST
BE ORDERED SEPARATELY. CONCEALED ARM SUPPORT AS
REQUIRED TO BE FURNISHED BY OTHERS.
IMPORTANT: Dimensions of fixtures are nominal and may vary within the range of tolerances established by ANSI Standard A112.19.2. These measurements are subject to change or cancellation. No responsibility is assumed for use of superseded or voided pages.
MEETS THE AMERICANS WITH DISABILITIES ACT GUIDE-
LINES AND ANSI A117.1 ACCESSIBLE AND USABLE
BUILDINGS AND FACILITIES - CHECK LOCAL CODES.
Top of front rim mounted 864mm (34") from finished floor.
35 © 2023 AS America Inc.
SINGLE CENTER HOLE CONFIGURATIONS
All Wall Hanger (included) or Concealed Arm Configurations
SINGLE CENTER HOLE ON RIGHT CONFIGURATIONS
All Wall Hanger (included) or Concealed Arm Configurations
NOTES:
* �DIMENSIONS SHOWN FOR LOCATION OF SUPPLIES AND “P” TRAP ARE SUGGESTED. PROVIDE SUITABLE REINFORCEMENT
FOR ALL WALL SUPPORTS. FITTINGS NOT INCLUDED AND MUST BE ORDERED SEPARATELY. CONCEALED ARM SUPPORT
AS REQUIRED TO BE FURNISHED BY OTHERS.
IMPORTANT: Dimensions of fixtures are nominal and may vary within the range of tolerances established by ANSI Standard A112.19.2.
These measurements are subject to change or cancellation. No responsibility is assumed for use of superseded or voided pages.
spec_0355-0356 Lucerne WallHung Lavs Rev. 3 9/23
Lucerne™
Wall-Hung Lavatory
VITREOUS CHINA
BARRIER FREE
102mm (4")
152mm (6")
152mm (6")
86mm (3-3/8")
197mm (7-3/4")
8mm (5/16")
464mm (18-1/4")
FINISHED
WALL
(6) 25mm (1") DIA.
ACCESS HOLES
FOR CONC. ARMS
25mm (1-3/8") DIA.
PUNCHING
540mm (21-1/4")
13mm (1/2")
44mm (1-3/4") DIA.
STD. OUTLET
102mm (4")
87mm (3-3/8")
425mm (16-3/4")
44mm (1-3/4")
38mm (1-1/2")
10mm (3/8")
DIA. ANCHOR
SCREW HOLES
203mm (8")
787mm (31") 864mm (34")
FINISHED
FLOOR
58mm (2-1/4") DIA.
HOLES FOR
CONCEALED ARMS27.4mm (1-1/16")
267mm (10-1/2")
122mm (4-3/4")
27mm x 8mm (1" x 1/4") SLOTS
S-9 HANGER
114mm (4-1/2")
86mm (3-3/8")
197mm (7-3/4")
8mm (5/16")
464mm (18-1/4")
540mm (21-1/4")
13mm (1/2")
FINISHED
WALL
425mm (16-3/4")
102mm (4")
13mm x 51mm BRACKET (1/2" x 2") SLOTS
349mm (13-3/4")
57mm (2-1/4")
44mm (1-3/4") DIA.
STD. OUTLET
25mm (1") DIA.
HOLES
35mm (1-3/8") DIA.
PUNCHING
102mm (4")
87mm (3-3/8")
425mm (16-3/4")
44mm (1-3/4")
38mm (1-1/2")
10mm (3/8")
DIA. ANCHOR
SCREW HOLES
203mm (8")
787mm (31") 864mm (34")
FINISHED
FLOOR
58mm (2-1/4") DIA.
HOLES FOR
CONCEALED ARMS
27.4mm (1-1/16")
267mm (10-1/2")
122mm (4-3/4")
27mm x 8mm (1" x 1/4") SLOTS
S-9 HANGER
MEETS THE AMERICANS WITH DISABILITIES ACT GUIDE-
LINES AND ANSI A117.1 ACCESSIBLE AND USABLE
BUILDINGS AND FACILITIES - CHECK LOCAL CODES.
Top of front rim mounted 864mm (34") from finished floor.
Job Name ________________________________________________
Item Number _____________________________________________
Section/Tag ______________________________________________
Model Specified ___________________________________________
Architect _________________________________________________
Engineer _________________________________________________
Contractor ________________________________________________
[ ] Submitted as Shown [ ] Submitted with Variations
Date _____________________________________________________
2100 South Clearwater Drive Des Plaines, IL
P: 847/803-5000 F: 847/803-5454
Technical: 800/TEC-TRUE www.chicagofaucets.com
Manual Sink Faucets
895-GN6AE36XK317AB
Product Type
Deck-mounted manual faucet with 4" centers
Features & Specifications
Handles include color-coded index 4" fixed centers 6" rigid/swing gooseneck spout Pressure compensating laminar flow non-aerating outlet 1.5 GPM Vandal Proof 4" wristblade handle Ceramic 1/4-turn operating cartridge, right-hand Ceramic 1/4-turn operating cartridge, left-hand ECAST® design provides durable cast brass construction with total lead content equal to or less than 0.25% by weighted average CFNow! Item Ships in 3 Days
Performance Specification
Rated Operating Pressure: 20-125 PSI Rated Operating Temperature: 40-140°F
Warranty
5-Year Limited Cartridge Warranty Lifetime Limited Faucet Warranty 1-Year Limited Finish Warranty
Codes & Standards
ASME A112.18.1/CSA B125.1
ADA ANSI/ICC A117.1
Complies with CALGreen requirements
NSF/ANSI/CAN 61: Q ≤ 1
NSF/ANSI/CAN 372 Low Lead Content Certified to WaterSense by ICC-ES
ECAST products are intended for installation where state laws and local codes mandate lead content levels or in any location where lead content is a concern.
Last Revision: 10/21/2024 • Product specifications subject to change without notice
P-102, P-103; WRIST
BLADE FAUCETS
2100 South Clearwater Drive Des Plaines, IL
P: 847/803-5000 F: 847/803-5454
Technical: 800/TEC-TRUE www.chicagofaucets.com
895-GN6AE36XK317AB
Architect/Engineer Specification Chicago Faucets No. 895-GN6AE36XK317AB, Sink Faucet for hot and cold water, deck-mounted with 4" fixed centers, chrome plated.
Rigid/swing gooseneck spout, 6" center-to-center. 1.5 GPM (5.7 L/min) pressure compensating, non-aerating, laminar outlet. 4" metal, vandal-proof, wristblade handles with sixteen-point, tapered broach and secured blue and red index buttons. Quaturn™ rebuildable compression cartridge, opens and closes 90°, closes with water pressure, features square, tapered stem. 1/2" NPSM supply inlets and coupling nut for 3/8" or 1/2" flexible riser. ECAST® construction with less than 0.25% lead content by weighted average. CALGreen compliant.