This notice is a pre-solicitation for architect-engineering services related to Project #607-397 to expand specialty care at the VA Medical Care Center in Madison, Wisconsin. The Veterans Health Administration Program Contracting Activity Central intends to award a firm fixed price design contract for complete construction documents, working drawings, specifications, reports, and construction period services. Responses are sought in the form of Standard Form 330 statements of qualifications, with the anticipated award being made in accordance with the Selection of Architects and Engineers statute, FAR subpart 36.6, VAAR 836.6, and VAAM M836.6. Construction contracts for the resulting project design will not be awarded to the designing firm or its affiliates per FAR 36.209, with the exception of approval from the agency head.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMERICAN SOCIETY FOR TESTING
AMERICAN PLYWOOD ASSOCIATION
AMERICAN CONCRETE INSTITUTE
INTERNATIONAL CONFERENCE OF
STRUCTURAL ABBREVIATIONS:
JB JOIST BRACE
JST JOIST
JT JOINT
K KIP (1,000 LB.)
KSI KIPS PER SQUARE INCH
L LENGTH, ANGLE
LAB LABORATORY
LB POUND
LF LINEAL FOOT
LIN LINEAL, LINEAR
LL LIVE LOAD
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LN LINE
LOC LOCATION, LOCATE
LONGIT LONGITUDINAL
LP LOW POINT
LTWT LIGHTWEIGHT
LVL LAMINATED VENEER LUMBER
LWR LOWER
MANUF MANUFACTURER
MATL MATERIAL
MAX MAXIMUM
MC MOMENT CONNECTION
MECH MECHANICAL
MED MEDIUM
MEP MECHANICAL, ELECTRICAL,
PLUMBING DRAWINGS
MF MOMENT FRAME
MFR MANUFACTURE,
MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
ML MATCH LINE
MO MASONRY OPENING
MTD MOUNTED
MTG MOUNTING HEIGHT
MTL METAL
NIC NOT IN CONTRACT
NO(#) NUMBER
NOM NOMINAL
NS NEAR SIDE
N-S NORTH-SOUTH
NTS NOT TO SCALE
NW NORMAL WEIGHT
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OPHD OPPOSITE HAND
OPNG OPENING
OPT OPTION, OPTIONAL
P/C PRECAST
P/S PRESTRESSED
P/T POST TENSIONED
PART PARTITION
PCF POUNDS PER CUBIC FOOT
PCY POUNDS PER CUBIC YARD
PEN PENETRATION
PERP PERPENDICULAR
PJF PREMOLDED JOINT FILLER
PL PLATE
PLC PLACE
PP PARTIAL PENETRATION
PREFAB PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT, POST-TENSION
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT, REINFORCE
REQD REQUIRED
REV REVISE, REVISION
RFG ROOFING
RH RIGHT HAND
RO ROUGH OPENING
SC SOLID CORE, SLIP CRITICAL
SCHED SCHEDULE
SECT SECTION
SEOR STRUCTURAL ENGINEER
OF RECORD
SEQ SEQUENCE
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SLBB SHORT LEG BACK TO BACK
SOG SLAB ON GRADE
SPEC SPECIFICATION
SS STAINLESS STEEL
SSL SHORT SLOTTED (HOLES)
STD STANDARD
STG STRONG
STL STEEL
STRUCT STRUCTURAL, STRUCTURE
SUPT SUPPORT
SUSP SUSPEND, SUSPENDED
SW SHORT WAY, SHEAR WALL
SYM SYMMETRICAL
T TOP
T&B TOP AND BOTTOM
T&G TONGUE & GROOVE
TEMP TEMPERATURE, TEMPORARY
THK THICK, THICKNESS
THRU THROUGH
TOF TOP OF FOOTING
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSVERSE
TS TUBULAR STEEL
TYP TYPICAL
UC ANC UNDERCUT ANCHOR
UL UNDERWRITERS'
LABORATORIES
UNO UNLESS NOTED OTHERWISE
UT ULTRASONIC TEST
VB VAPOR BARRIER
VERT VERTICAL
VIF VERIFY IN FIELD
W/ WITH
W WIDE
W/O WITHOUT
WD WOOD
WP WORK POINT
WT WEIGHT
WWF WELDED WIRE FABRIC
X-STG EXTRA STRONG
XX-STG DOUBLE EXTRA STRONG
YD YARD
& AND
@ AT
°, DEG DEGREE
#, LB NUMBER, POUND
Ø, DIA DIAMETER
AB ANCHOR BOLT
ACI
ACOUST ACOUSTICAL
ADDL ADDITIONAL
ADH ADHESIVE
ADJ ADJACENT
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
AGG AGGREGATE
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE
ALUM ALUMINUM
ANC ANCHOR, ANCHORAGE
ANG ANGLE
ANOD ANODIZED
APA
APPD APPROVED
APPROX APPROXIMATE
ARCH ARCHITECT/ ARCHITECTURAL
ASTM
AND MATERIALS
AVG AVERAGE
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BAL BALANCE
BF BOTH FACES
BLDG BUILDING
BLK BLOCK
BM BEAM
BOT BOTTOM
BP BASE PLATE
BR BRACE, BRACED FRAME
BRG BEARING
BRKT BRACKET
BSMT BASEMENT
BW BOTH WAYS
C CAMBER
CANT CANTILEVER
C/C CENTER TO CENTER
CEM CEMENT
CIP CAST IN PLACE
CJ CONTROL JOINT
CL, C CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
COORD COORDINATE, COORDINATION
CP COMPLETE PENETRATION
WELD-ULTRASONIC TEST
CTR CENTER
D DEEP, DEPTH
DB BAR DIAMETERS
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION, DEMOLISH
DEP DEPRESSION OR DEPRESS
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DL DEAD LOAD
DN DOWN
DO DITTO
DWG DRAWING
DWL DOWEL
EA EACH
EC EPOXY COATED
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR
EQ EQUAL
EQMT EQUIPMENT
ES EACH SIDE
EW EACH WAY
E-W EAST-WEST
EXIST EXISTING
EXP EXPANSION
EXP ANC (WEDGE) EXPANSION ANCHOR
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FF FINISHED FLOOR
FIN FINISH
FLEX FLEXIBLE
FLG FLANGE
FLR FLOOR
FOS FACE OF STUD
FP FIREPROOF
FRM FRAME
FS FAR SIDE
FT (') FEET, FOOT
FTG FOOTING
FURN FURNISH
GA GAGE, GAUGE
GALV GALVANIZED
GB GRADE BEAM
GEN GENERAL
GIR GIRDER
GL GLUE LAMINATED (BEAM)
GRND GROUND
GYP GYPSUM, GYPSUM DRYWALL
HC HOLLOW CORE
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
HS HIGH STRENGTH
HSA HEADED STUD ANCHOR
HSS HOLLOW STEEL SHAPE
HT (H) HEIGHT
ICBO
BUILDING OFFICIALS
ID INSIDE DIAMETER
IN (") INCH
INCL INCLUDE
INFO INFORMATION
INSUL INSULATE, INSULATION
INT INTERIOR
IT SCREW ANC INTERNALLY THREADED SCREW
ANCHOR
GENERAL:
1. APPLICABLE CODE: IBC 2012
2. FIRE RATING: SEE ARCHITECTURAL DRAWINGS.
3. CONTRACTOR TO VERIFY ALL DIMENSIONS AT JOB SITE BEFORE FABRICATION.
4. EL 0'-0" = 904'-6"
5. SPECIFICATIONS ARE AN INTEGRAL PART OF CONTRACT DOCUMENTS. IN CASE OF
DISCREPANCIES BETWEEN SPECIFICATIONS AND DRAWINGS THE CONTRACTOR SHALL
REQUEST CLARIFICATION FROM THE ENGINEER BEFORE PROCEEDING WITH THE WORK.
6. ALL DETAILS, SECTIONS AND NOTES ON STRUCTURAL DRAWINGS ARE INTENDED TO BE
TYPICAL FOR SIMILAR SITUATIONS, UNLESS NOTED OTHERWISE.
7. DO NOT SCALE DRAWINGS.
8. STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT FINISHED STRUCTURE AND,
UNLESS NOTED OTHERWISE, DO NOT INDICATE METHOD OF CONSTRUCTION.
9. EXISTING CONDITIONS AND RELATED DIMENSIONS INDICATED ON THE DRAWINGS ARE
PROVIDED FOR INFORMATION ONLY AND SHALL BE FIELD VERIFIED PRIOR TO
COMMENCING WORK. SUBMIT CONDITIONS THAT DIFFER FROM THAT INDICATED ON
DRAWINGS TO ARCHITECT FOR REVIEW PRIOR TO COMMENCING WORK.
GENERAL NOTES:
L
COORDINATION BY CONTRACTOR:
1. SEE ARCHITECTURAL, CIVIL, MECHANICAL, ELECTRICAL, PLUMBING AND OTHER DESIGN
DRAWINGS FOR SCOPE OF WORK AND COORDINATION OF TRADES.
2. SEE CIVIL OR ARCHITECTURAL DRAWINGS FOR LOCATION OF BENCHMARK WITH RESPECT
TO BUILDING GRID LINES.
3. PRINCIPAL OPENINGS ARE INDICATED ON THE DRAWINGS. SEE ARCHITECTURAL,
MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR ADDITIONAL OPENINGS,
BLOCKOUTS AND SLEEVES. CONTRACTOR SHALL SUBMIT A COORDINATED PLAN SHOWING
ALL SLAB AND WALL OPENINGS, BLOCKOUTS, AND SLEEVES TO ARCHITECT FOR REVIEW
AND APPROVAL WITH EACH FLOOR AND WALL REINFORCING STEEL SHOP DRAWING
PROVIDE OPENINGS, BLOCKOUTS AND SLEEVES BASED ON SUBMITTAL RESPONSES
ALLOWING PENETRATION ONLY.
4. SEE ARCHITECTURAL DRAWINGS FOR LINTELS, SHELF ANGLES, HANDRAILS,
GUARDRAILS, VANITY SUPPORT, PARTITION SUPPORT, COLUMN COVERS, EMBEDMENTS,
EXPANSION JOINT ASSEMBLIES, DOORJAMBS, AND SIMILAR
COMPONENTS. SEE ARCHITECTURAL DRAWINGS FOR STEEL PAN STAIRS AND STEEL PAN
STAIR SUPPORT.
5. SEE ARCHITECTURAL DRAWINGS FOR PARTITION ATTACHMENTS AND CURBS.
6. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COMPLY WITH ALL APPLICABLE
FEDERAL LAWS, INCLUDING THE OCCUPATIONAL SAFETY AND HEALTH
ACT (OSHA) AND REGULATIONS ADOPTED PURSUANT THERETO.
7. THE BUILDING IS DESIGNED FOR PERMANENT LOADS APPLIED TO THE STRUCTURE IN ITS
FINAL CONFIGURATIONCONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO
PROTECT STRUCTURE, WORKMEN OR OTHER PERSONS DURING CONSTRUCTION. SUCH
MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR
CONSTRUCTION EQUIPMENT, SHORING FOR BUILDING, SHORING FOR EARTH BANKS, FORMS,
SCAFFOLDING, PLANKING, SAFETY NETS, SUPPORT, BRACING FOR CRANES AND GIN
POLES, AND SIMILAR MEANS-AND-METHODS ELEMENTS.
8. CONTRACTOR SHALL SUPERVISE AND DIRECT WORK AND SHALL BE SOLELY RESPONSIBLE
FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES.
CONTRACTOR AT HIS OWN EXPENSE SHALL ENGAGE PROPERLY QUALIFIED PERSONS TO
DESIGN AND DETERMINE WHERE AND HOW TEMPORARY PRECAUTIONARY MEASURES
SHALL BE USED AND TO INSPECT THE SAME IN FIELD.
9. SITE OBSERVATION BY FIELD REPRESENTATIVE OF ARCHITECT DOES NOT CONSTITUTE
INSPECTION OF WORK ITEMS.
HANGING ARCHITECTURAL/MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION LOADS:
1.
2.
3. LOADS HANGING DIRECTLY FROM ROOF DECK ARE NOT PERMITTED.
4.
5.
6. DOUBLE SIDED CLIP CONNECTIONS TO BEAM BOTTOM FLANGE SHALL BE LIMITED TO
500 LBS.
DEMOLITION AND SHORING:
1. INFORMATION PROVIDED ON THE EXISTING STRUCTURE IS PROVIDED FOR
INFORMATION ONLY. EXISTING CONSTRUCTION INFORMATION SHALL BE CHECKED
AGAINST CONDITIONS FOUND IN THE FIELD PRIOR TO FABRICATION AND ERECTION
OF ALL NEW CONSTRUCTION.
4.
5.
TOP OF SLAB ELEVATIONS:
1. SEE STRUCTURAL PLANS FOR TOP OF STRUCTURAL SLAB ELEVATIONS. FINISH
STRUCTURAL SLABS LEVEL WITHIN SPECIFIED TOLERANCES EXCEPT WHERE INDICATED
AS SLOPED.
2. SEE STRUCTURAL DRAWINGS FOR SLAB ON GRADE AND STRUCTURAL SLAB ELEVATION
CHANGES AT RAMPS AND FLOOR DEPRESSIONS. SEE ARCHITECTURAL DRAWINGS FOR
PLAN DIMENSIONS AT FLOOR DEPRESSIONS.
3. SEE ARCHITECTURAL DRAWINGS FOR FINISHED ELEVATIONS OF FILL SLABS, WEAR
SLABS AND TOPPING.
GRIDLINES:
1. GRIDLINES INDICATE COLUMN CENTERLINES OR FACE OF COLUMN/WALL/FOUNDATION
UNLESS SPECIFIC DIMENSIONS ARE PROVIDED LOCATING CENTERLINES OR FACE OF
ELEMENTS WITH RESPECT TO PROVIDED GRIDLINES.
SPECIAL INSPECTIONS:
1. SPECIAL INSPECTIONS ARE REQUIRED IN ACCORDANCE WITH SECTION 17 OF THE
REFERENCED EDITION OF IBC. REFER TO SHEET S-002 FOR THE STATEMENT OF SPECIAL
INSPECTIONS.
CONCRETE ACCESSORIES:
1. MISCELLANEOUS STEEL SHAPES, PLATES, AND BARS, ASTM A36.
2. EXCEPT AS DETAILED ON STRUCTURAL DRAWINGS, NO CONCRETE ELEMENTS
SHALL BE SLEEVED FOR PIPING OR DUCTS, UNLESS APPROVED BY THE ENGINEER.
3. NON-SHRINK GROUT FOR BASE PLATES, SLEEVES AND EMBEDDED STEEL:
GROUT SHALL BE AN APPROVED NON-SHRINK CEMENTITIOUS GROUT
CONTAINING NATURAL AGGREGATES DELIVERED TO THE JOB SITE IN FACTORY
PRE-PACKAGED CONTAINERS REQUIRING ONLY THE ADDITION OF WATER. THE
MINIMUM 28-DAY COMPRESSIVE STRENGTH SHALL BE AT LEAST 1,000 PSI
HIGHER THAN THE SUPPORTING CONCRETE STRENGTH, UNLESS NOTED
OTHERWISE. GROUT SHALL BE MIXED, APPLIED AND CURED IN STRICT
ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTRUCTIONS. FOR
GROUTING UNDER BASE PLATES, GROUT SHALL BE PROPORTIONED AS A
FLOWABLE MIX.
POST-INSTALLED CONCRETE ANCHORS:
1. POST-INSTALLED MECHANICAL ANCHORS INSTALLED INTO CONCRETE SHALL BE ICC-
ES APPROVED FOR USE IN CRACKED CONCRETE AND SHALL BE TESTED IN
ACCORDANCE WITH ICC-ES AC-193. REFER TO SPECIFICATIONS FOR APPROVED LIST
OF MECHANICAL ANCHORS.
2. POST-INSTALLED ADHESIVE ANCHORS INSTALLED INTO CONCRETE SHALL BE ICC-ES
APPROVED FOR USE IN CRACKED CONCRETE AND SHALL BE TESTED IN ACCORDANCE
WITH ICC-ES AC-308. REFER TO SPECIFICATIONS FOR LIST OF APPROVED ADHESIVE
ANCHORS.
3. ADHESIVE ANCHORS SHALL NOT BE INSTALLED UNTIL CONCRETE AGE HAS REACHED
21 DAYS.
4. ANCHORS SHALL BE INSTALLED BY QUALIFIED PERSONNEL IN STRICT ACCORDANCE
WITH THE CONTRACT DOCUMENTS, APPROVED ICC-ES REPORT, AND
MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS.
5. NO REINFORCEMENT SHALL BE CUT TO INSTALL ANCHORS. DEFECTIVE HOLES SHALL
BE GROUTED WITH CEMENTITIOUS GROUT.
6. REFER TO STATEMENT OF SPECIAL INSPECTIONS FOR SPECIFIC ANCHOR INSPECTION
REQUIREMENTS.
7. POST-INSTALLED CONCRETE ANCHOR CALL-OUTS AND MINIMUM EMBEDMENTS:
MECHANICAL ANCHORS ARE INDICATED ON THE DRAWINGS AS FOLLOWS:
A. WEDGE EXPANSION ANCHORS - DESIGNATED AS EXP ANC
B. UNDERCUT ANCHORS - DESIGNATED AS UC ANC
C. SCREW ANCHORS - DESIGNATED AS SCREW ANC
D. INTERNALLY THREADED SCREW ANCHOR - DESIGNATED AS IT SCREW ANC
ADHESIVE ANCHORS ARE INDICATED ON THE DRAWINGS AS FOLLOWS:
A. ADHESIVE ANCHORS - ADH ANC
MINIMUM EMBEDMENT DEPTH SHALL BE AS FOLLOWS:
A. MECHANICAL ANCHORS - 6 BOLT DIAMETERS UNLESS NOTED OTHERWISE ON
DRAWINGS OR MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS.
B. ADHESIVE ANCHORS - 12 BOLT DIAMETERS UNLESS NOTED OTHERWISE ON
DRAWINGS OR MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS.
STRUCTURAL STEEL:
1. THE STEEL FRAMING IS A "NON SELF SUPPORTING STEEL FRAME" AS DEFINED IN THE AISC
CODE OF STANDARD PRACTICE. TEMPORARY SUPPORTS AND BRACINGS MUST NOT BE
REMOVED UNTIL THE CONCRETE SLAB OR ROOF DECK IS FULLY INSTALLED AND ALL
CONNECTIONS COMPLETED. CONTRACTOR SHALL FABRICATE AND ERECT STEEL IN
CONFORMANCE WITH OSHA'S SAFETY REQUIREMENTS INCLUDING 29 CFR PART 1926
SAFETY STANDARDS FOR STEEL ERECTION.
2. STRUCTURAL STEEL DETAILING, FABRICATION, AND ERECTION SHALL COMPLY WITH ALL
APPLICABLE PROVISIONS OF AISC SPECIFICATION 360 AND AISC CODE OF STANDARD
PRACTICE.
3. SUBMIT DETAILED, ENGINEERED, AND COORDINATED SHOP DRAWINGS FOR ALL
STRUCTURAL STEEL INDICATING COMPLIANCE WITH THE DESIGN INTENT FOR REVIEW
PRIOR TO FABRICATION.
4. STEEL SHAPES:
CHANNELS, ANGLES, PLATES, BARS, THREADED RODS - ASTM A36
W SHAPES - ASTM A992
HSS ROUND AND RECTANGULAR SHAPES - ASTM A 500 GRADE B
PIPE - ASTM A53 TYPE E OR S GRADE B STD. WT., UNO
ANCHOR RODS - ASTM F1554 GRADE 36
HIGH STRENGTH BOLTS - ASTM A325N OR F1852 (UNO)
COMPOSITE STUDS - ASTM A108
5. SHEAR STUDS SHALL BE 3/4"Ø. TOP OF STUDS SHALL BE 1 1/2" MIN. ABOVE TOP OF
STEEL DECK AFTER INSTALLATION. REFER TO TYPICAL DETAILS FOR STUD PLACEMENT
AND SPACING. SUBMIT SHOP DRAWINGS INDICATING STUD LAYOUT FOR REVIEW PRIOR
TO ERECTION.
6. WELDING SHALL CONFORM TO STANDARDS OF AWS D1.1. ELECTRODES FOR FIELD AND
SHOP WELDING SHALL BE E70XX AND SHALL CONFORM TO AWS RECOMMENDATIONS.
WELDS NOT INDICATED SHALL BE AWS MINIMUM. FOLLOW PREHEAT REQUIREMENTS OF
AWS. LOW HYDROGEN ELECTRODES MAY BE UTILIZED TO MINIMIZE THE USE OF PREHEAT.
USE LOW HYDROGEN ELECTODES FOR WELDING TO CONCRETE EMBEDMENT PLATES OR
OTHER STRUCTURAL STEEL ELEMENT IN CONTACT WITH CONCRETE OR MASONRY.
7. FABRICATE BEAMS SO THAT ANY NATURAL CAMBER IS UPWARD AFTER ERECTION.
8. BEARING SURFACES OF ALL COLUMNS SHALL BE FINISHED FOR FULL BEARING CONTACT
OR WELDS SHALL BE DESIGNED TO TRANSMIT ALL AXIAL COMPRESSION.
9. ALL CUTS, HOLES, ETC. REQUIRED IN STRUCTURAL STEEL MEMBERS FOR THE WORK OF
OTHER TRADES SHALL BE SHOWN ON THE SHOP DRAWINGS. BURNING OF HOLES OR
CUTS IN STRUCTURAL MEMBERS IN THE FIELD IS NOT ALLOWED WITHOUT PRIOR WRITTEN
APPROVAL BY THE STRUCTURAL ENGINEER.
10. CONTRACTOR SHALL COORDINATE ROOF OPENINGS FOR NUMBER, SIZE AND LOCATION.
11. REFER TO ARCH. DRAWINGS FOR FIREPROOFING REQUIREMENTS.
12. SPLICING STRUCTURAL MEMBERS WHERE NOT DETAILED ON STRUCTURAL DRAWINGS IS
PROHIBITED WITHOUT PRIOR ACCEPTANCE BY STRUCTURAL ENGINEER.
13. STEEL BEAMS AND STEEL DECK HAVE BEEN DESIGNED FOR UN-SHORED CONDITIONS
ASSUMING 20 PSF CONSTRUCTION LIVE LOADS. DO NOT SHORE STEEL BEAMS AND/OR
STEEL DECK WITHOUT PRIOR REVIEW AND ACCEPTANCE BY STRUCTURAL ENGINEER.
SUPPORT FORMWORK FOR FLAT SOFFIT SLABS FROM STEEL BEAMS THAT DIRECTLY
SUPPORT SLAB BEING FORMED. DESIGN AND DETAIL FORMWORK FOR FLAT SLABS FROM
STEEL BEAMS THAT DIRECTLY SUPPORT SLAB BEING FORMED. DESIGN AND DETAIL
FORMWORK FOR FLAT SLABS TO CONTINUOUSLY BRACE TOP FLANGE OF STEEL BEAMS
FROM LATERAL MOVEMENT DURING CONSTRUCTION OF SLAB. FLOOR SLABS SHALL BE
CONSTRUCTED TO THE ELEVATIONS SPECIFIED.
14. AT ELEVATED CONCRETE FLOORS ON STEEL DECK THE CONCRETE FLOORS SHALL BE
PLACED TO THE INDICATED ELEVATION WITHIN THE SPECIFIED TOLERANCES. THE STEEL
BEAMS SUPPORTING CONCRETE FLOORS HAVE BEEN CAMBERED WHERE INDICATED FOR
THE EXPECTED DEAD LOAD DEFLECTION HOWEVER SOME VARIABILITY IN THE BEAM
DEFLECTION WILL BE EXPECTED RESULTING IN UP TO A MAXIMUM 1" DEFLECTION
BEYOND LEVEL AT THE CENTER OF TYPICAL BAYS. THE STRUCTURAL MEMBERS HAVE
BEEN DESIGNED TO ACCOMMODATE THIS ADDITIONAL WEIGHT. THE CONTRACTOR SHALL
CONSIDER THAT THIS SITUATION MAY INCREASE THE AS-PLACED CONCRETE VOLUME BY
10% ABOVE THE THEORETICAL VOLUME DUE TO PONDING AND INCLUDE THIS VOLUME IN
THE BASE CONCRETE BID.
STRUCTURAL STEEL CONNECTIONS:
1. WHERE CONNECTION DETAILS ARE COMPLETELY DETAILED ON THE DRAWINGS THEY
SHALL BE INCORPORATED INTO THE FABRICATOR'S DESIGN. CONNECTIONS SHOWN ON
THE DRAWINGS BUT NOT FULLY DETAILED ARE SCHEMATIC AND ARE ONLY INTENDED
TO SHOW THE GENERAL RELATIONSHIP OF MEMBERS BEING CONNECTED. WHERE
FULLY DETAILED CONNECTION INFORMATION IS NOT PROVIDED ON THE DRAWINGS THE
STEEL FABRICATOR IS RESPONSIBLE FOR THE DESIGN OF ALL CONNECTIONS AND
SHALL DESIGN CONNECTIONS FOR BEAMS FOR THE REACTION FORCE INDICATED ON
THE DRAWINGS.
SUBMIT FOR RECORD CONNECTION CALCULATIONS PREPARED IN ACCORDANCE WITH
AISC 360 - LRFD THAT HAVE BEEN SIGNED AND SEALED BY A STRUCTURAL ENGINEER
LICENSED IN THE STATE OF THE PROJECT LOCATION.
BOLTED CONNECTIONS - BOLTED CONNECTIONS SHALL USE HIGH-STRENGTH BOLTS IN
ACCORDANCE WITH AISC "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325
OR A490 BOLTS." BOLTS SHALL BE INSTALLED TO THE SNUG TIGHT CONDITION UNLESS
INDICATED BELOW OR ON THE DRAWINGS.
BOLTS IN THE FOLLOWING CONNECTIONS SHALL BE INSTALLED TO THE FULLY
PRETENSIONED CONDITION:
a. JOINTS THAT ARE SUBJECT TO SIGNIFICANT LOAD REVERSAL SUCH AS CONNECTIONS
IN BRACED FRAMES AND CONNECTIONS FOR MEMBERS WITH SPECIFIED REVERSIBLE
AXIAL FORCES.
h. ASTM A490 BOLTS THAT ARE SUBJECT TO TENSION OR COMBINED SHEAR AND
TENSION
BOLTS IN THE FOLLOWING CONNECTIONS AND AS INDICATED ON THE DRAWINGS SHALL
BE INSTALLED TO THE SLIP CRITICAL CONDITION WITH CLASS A FAYING SURFACE
PREPARATION USING DIRECT TENSION INDICATORS CONFORMING TO ASTM F959 OR
TENSION CONTROL THREADED FASTENERS MEETING ASTM F1852 OR F2280:
a. JOINTS IN WHICH SLIP WILL BE DETRIMENTAL TO THE PERFORMANCE OF THE
STRUCTURE SUCH AS WEB AND/OR FLANGE BOLTS AT MOMENT CONNECTIONS
b. JOINTS WITH OVERSIZE HOLES
c. JOINTS THAT UTILIZE SLOTTED HOLES WHERE THE DIRECTION OF THE LOAD IS
PARALLEL TO THE DIRECTION OF THE APPLIED LOAD
SINGLE SIDED CLIP CONNECTIONS TO BEAM BOTTOM FLANGE SHALL BE LIMITED TO
300 LBS PER LOCATION. SINGLE SIDED CLIP CONNECTIONS TO BEAM TOP FLANGE
SHALL BE LIMITED TO 500 LBS PER LOCATION.
LIMIT LOADS HANGING FROM COMPOSITE SLABS AND CONCRETE SLABS TO 100 LBS
PER LOCATION FOR ATTACHMENT TO EMBEDMENTS OR TO ANCHORS.
DISTRIBUTE HANGING LOADS AS REQUIRED TO LIMIT THE AVERAGE DISTRIBUTION
TO THE SUPPLEMENTAL DEAD LOAD INDICATED ON LOAD MAPS AT EACH BUILDING
BAY. WITHIN THE LISTED LIMITATION FOR AVERAGE DISTRIBUTION, LIMIT INDIVIDUAL
HANGER LOADS TO VALUES LISTED IN THIS SECTION.
CONNECTIONS OF ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE
PROTECTION ITEMS TO THE STRUCTURE SHALL BE DESIGNED AND DETAILED BY THE
CONTRACTOR RESPONSIBLE FOR THAT WORK. SUBMIT FOR ACTION, DETAILS OF
HANGER CONNECTIONS. INDICATE LOCATIONS OF CONNECTIONS AND LOADS
IMPARTED ON THE STRUCTURE. REVISE HANGER LOCATIONS AND FREQUENCIES
WHERE NECESSARY TO MEET STRUCTURAL REQUIREMENTS.
ALL CONCRETE TO BE REMOVED SHALL BE SAW CUT A MINIMUM OF 1" DEEP PRIOR
TO FINAL BREAK OUT. PROVIDE A CLEAN, GRADUAL TRANSITION BETWEEN WORK
WHICH IS TO REMAIN AND WORK TO BE REMOVED.
DIMENSIONS ON THE DRAWINGS SHALL BE FIELD VERIFIED PRIOR TO THE START
OF THE WORK. CONTACT THE ENGINEER IMMEDIATELY IF SIGNIFICANT DEVIATIONS
ARE ENCOUNTERED.
3. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO THE START OF WORK AND SHALL
BECOME FAMILIAR WITH THE EXISTING CONDITIONS, LIMITATIONS AND ANY
FEATURES WHICH MAY AFFECT THE PROPOSED DEMOLITION. THE CONTRACTOR
SHALL BEAR THE FULL RESPONSIBILITY FOR THE DESIGN AND INSTALLATION OF ALL
TEMPORARY SHORING TO BE USED.
2. DEMOLITION WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE
SPECIFICATIONS AND SHALL BE STRICTLY LIMITED TO THE AREAS AND ITEMS CLEARLY
DEFINED ON THE DRAWINGS. ALL DEMOLITION SHALL BE CONDUCTED IN A CLEAN,
WORKMANLIKE MANNER AND SHALL MINIMIZE DISRUPTION TO ADJACENT BUILDING
ITEMS AND FEATURES BEYOND THE CURRENT WORK.
7. AT THE TIME OF CONSTRUCTION, LOADS ON ROOF SHALL
NOT EXCEED THE LIVE LOAD SPECIFIED ABOVE.
8. IF CONSTRUCTION LOADS EXCEED THE SPECIFIED LOADS,
PROPERLY SHORE THE INFLUENCED AREA OF FLOOR.
DESIGN LOADS:
1. DESIGN BASED UPON 2012 INTERNATIONAL BUILDING CODE
(IBC), IN CONJUNCTION WITH ASCE7-10
2. WIND LOAD: N/A
3. SNOW LOAD:
GROUND SNOW LOAD, Pg = 30 PSF
IMPORTANCE FACTOR, I = 1.2 (RISK CATEGORY IV)
SNOW EXPOSURE FACTOR, Ce = 1.0
THERMAL FACTOR Ct = 1.0
FLAT ROOF SNOW LOAD, Pf = 26 PSF
4. SEISMIC LOAD:
RISK CATEGORY = IV
SEISMIC DESIGN CATEGORY = C
IMPORTANCE FACTOR, I = 1.5 (RISK CATEGORY IV)
Ss
S1
SDS
SD1
SITE CLASS = D
5. LIVE LOADS:
TYP FLOOR LIVE LOAD
PARTITIONS
MIN ROOF LIVE LOAD
SNOW LOAD
6. DEAD LOADS:
COLLATERAL AT TYP FLOOR
ROOF COLLATERAL
= 0.104
= 0.044
= 0.112
= 0.070
= 22.5 PSF
= 8.5 PSF
= 60 PSF
= 15 PSF
= 20 PSF
= 26 PSF PLUS DRIFT
1. STRUCTURAL COMPONENTS ARE NOT DESIGNED FOR VIBRATORY EQUIPMENT. PLACE
VIBRATORY EQUIPMENT ON VIBRATION ISOLATORS.
2. LOADING OF MECHANICAL ROOMS ARE BASED ON WEIGHTS OF ASSUMED EQUIPMENT, AS
INDICATED ON MECHANICAL DRAWINGS, INCLUDING WEIGHTS OF CONCRETE PADS, WHERE
INDICATED. REPORT ANY PLANNED CHANGE IN TYPE, SIZE, LOCATION OR NUMBER OF
EQUIPMENT TO ARCHITECT PRIOR TO ANY ACTION.
3. ELEVATOR GUIDERAIL SUPPORTS, MACHINE ROOMS, PITS, AND PENTHOUSES ARE BASED ON
ELEVATOR TYPES INDICATED ON ARCHITECTURAL DRAWINGS OR SPECIFICATIONS. REPORT
ANY PLANNED CHANGE TO ELEVATORS TO ARCHITECT PRIOR TO ANY ACTION.
EQUIPMENT LOADS:
EXISTING STRUCTURE DEAD LOADS CALCULATED USING
HOLABIRD AND ROOT CONSTRUCTION DRAWINGS FOR
MAIN BUILDING UNIT B DATED JANUARY 14, 1949.
INSPECTION TASK
REFERENCE FOR
INSPECTION CRITERIA
1.
2.
3.
4.
5.
6.
INSPECTION TASK
REFERENCE FOR
INSPECTION CRITERIA
2.
1.
3.
INSPECTION TASK
REFERENCE FOR
INSPECTION CRITERIA
1.
4.
5.
6.
3.
2.
1.
2.
3.
4.
5.
6.
INSPECTION TASK
REFERENCE FOR
INSPECTION CRITERIA
INTERNATIONAL BUILDING CODE (IBC) 2012
1705 SPECIAL INSPECTIONS
1. SPECIAL INSPECTIONS SHALL BE PERFORMED IN ACCORDANCE WITH IBC
SECTION 1705.
2. SPECIAL INSPECTIONS SHALL CONSIST OF THE INSPECTION OF THE
MATERIALS, FABRICATION, ERECTION OR PLACEMENT OF COMPONENTS REQUIRING
SPECIAL EXPERTISE TO ENSURE COMPLIANCE WITH THE APPROVED CONSTRUCTION
DOCUMENTS AND REFERENCED STANDARDS.
3. CONTINUOUS SPECIAL INSPECTIONS SHALL BE PERFORMED BY A SPECIAL
INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED.
4. PERIODIC SPECIAL INSPECTIONS SHALL BE THE PART-TIME OR INTERMITTANT
OBSERVATION BY A SPECIAL INSPECTOR OF WORK REQUIRING SPECIAL INSPECTION
WHO IS PRESENT IN THE AREA WHERE THE WORK HAS BEEN OR IS BEING
PERFORMED AND AT THE COMPLETION OF THE WORK.
SCHEDULE OF SPECIAL INSPECTION SERVICES
1704.2.5 INSPECTION OF FABRICATORS
1705.2.1 REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION
MATERIAL VERIFICATION OF HIGH
STRENGTH BOLTS, NUTS AND
FREQUENCY
Y
N
INSPECTION
WASHERS:
A. IDENTIFICATION MARKINGS TO
CONFORM TO ASTM STANDARDS
SPECIFIED IN THE APPROVED
CONSTRUCTION DOCUMENTS
B. MANUFACTURER'S CERTIFICATE OF
COMPLIANCE REQUIRED
APPLICABLE ASTM
MATERAIL
STANDARDS, AISC 360
SECT. A3.3
Y
PERIODIC
INSPECTION OF HIGH STRENGTH
BOLTING:
A. SNUG TIGHT JOINTS AISC 360 SECT. M2.5
IBC SECT. 1704.3.3
Y
PERIODIC
Y
PERIODIC
B. PRETENTIONED AND SLIP CRITICAL
JOINTS USING TURN-OF-NUT WITH
MATCHMARKING, TWIST-OFF BOLT
OR DIRECT TENSION INDICATOR
Y
PERIODIC
AISC 360 SECT. M2.5
IBC SECT. 1704.3.3
METHODS OF INSTALLATION
C. PRETENTIONED AND SLIP CRITICAL
JOINTS USING TURN-OF-NUT
WITHOUT MATCHMARKING OR
CALIBRATED WRENCH METHODS OF
Y
PERIODIC
AISC 360 SECT. M2.5
IBC SECT. 1704.3.3
INSTALLATION
MATERIAL VERIFICATION OF
STRUCTURAL STEEL AND COLD-
FORMED STEEL DECK:
A. FOR CONSTRUCTION STEEL,
IDENTIFICATION MARKINGS TO
CONFORM TO AISC 360
FOR OTHER STEEL, IDENTIFICATION
MARKINGS TO CONFORM TO ASTM
STANDARDS SPECIFIED IN THE
APPROVED CONSTRUCTION
DOCUMENTS
B.
C. MANUFACTURER'S CERTIFIED TEST
REPORTS
MATERIAL VERIFICATION OF WELD
FILLER MATERIALS:
A. IDENTIFICATION MARKINGS TO
CONFORM TO AWS SPECIFICATION
IN THE APPROVED CONSTRUCTION
DOCUMENTS
B. MANUFACTURER'S CERTIFICATE OF
COMPLIANCE REQUIRED
INSPECTION OF WELDING -
STRUCTURAL STEEL AND COLD-
FORMED STEEL DECK:
A. COMPLETE AND PARTIAL JOINT
PENETRATION GROOVE WELDS
B. MULTIPASS FILLET WELDS
C. SINGLE PASS FILLET WELDS > 5/16"
D. PLUG AND SLOT WELDS
E.
F. FLOOR AND ROOF DECK WELDS
SINGLE PASS FILLET WELDS <= 5/16"
INSPECTION OF STEEL FRAME
JOINT DETAILS FOR COMPLIANCE:
A. DETAILS SUCH AS BRACING AND
STIFFENING
B. MEMBER LOCATIONS
C. APPLICATION OF JOINT DETAILS AT
EACH CONNECTION
Y
PERIODICIBC SECT. 1704.3.2
Y
PERIODICIBC SECT. 1704.3.2
Y
PERIODICIBC SECT. 1704.3.2
Y
PERIODICAWS D1.3
Y
PERIODIC
IBC SECT. 1704.3.1
AWS D1.1
Y
CONTINUOUS
IBC SECT. 1704.3.1
AWS D1.1
Y
CONTINUOUS
IBC SECT. 1704.3.1
AWS D1.1
Y
CONTINUOUS
IBC SECT. 1704.3.1
AWS D1.1
Y
CONTINUOUS
IBC SECT. 1704.3.1
AWS D1.1
Y
PERIODIC
A5 DOCUMENTS
AND APPLICABLE AWS
AISC 360 SECT. A3.5
Y
PERIODICAISC 360 SECT. M5.5
Y
PERIODIC
APPLICABLE ASTM
STANDARDS
Y
1705.11 SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE -
SEISMIC FORCE RESISTING SYSTEM - SDC C, D, E, F
THE SEISMIC FORCE RESISTING SYSTEM CONSISTS OF THE FOLLOWING ELEMENTS:
[PROVIDE DESCRIPTION OF THE ELEMENTS OF THE SFRS]
FREQUENCY
Y
N
INSPECTION
STRUCTURAL STEEL (EXCEPT R=3)
N
CONTINUOUSAISC 341
A.
STRUCTURAL WOOD:
FIELD GLUING OF ELEMENTS OF
SFRS
N
CONTINUOUS
NAILING, BOLTING ANCHORING AND
OTHER FASTENING OF COMPONENTS
OF SFRS
N
PERIODIC
B.
COLD FORMED STEEL FRAMING:
A. WELDING OF ELEMENTS SFRS
N
PERIODIC
SCREWING, BOLTING, ANCHORING
AND OTHER FASTENING OF
COMPONENTS OF SFRS
N
PERIODIC
B.
1705.11.5 SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE - ARCHITECTURAL COMPONENTS
RESISTANCE CONSISTS OF THE FOLLOWING:
THE DESIGNATED SEISMIC SYSTEMS REQUIRING SPECIAL INSPECTIONS FOR SEISMIC
[PROVIDE DESCRIPTION OF THE DESIGNATED SEISMIC SYSTEMS]
FREQUENCY
Y
N
INSPECTION
ARCH COMPONENTS IN SDC C-F
IDENTIFIED AS "DESIGNATED SEISMIC
SYSTEM" IAW ASCE 7 CH 13 (LIST
COMPONENTS HERE)
YY
PERIODICIBC SECT. 1705.11.4
ANCHORAGE OF STORAGE RACKS
8' OR GREATER IN HEIGHT IN SDC
D, E, F
N
PERIODIC
N
PERIODIC
ANCHORAGE OF ACCESS FLOORS
IN SDC D, E, F
ERECTION AND FASTENING OF
NON-BEARING EXTERIOR WALLS IN
STRUCTURES > 30 FEET IN HEIGHT
N
PERIODIC
IN SDC D, E, F
ERECTION AND FASTENING OF
NON-BEARING INTERIOR WALLS
WEIGHING MORE THAN 15 PSF IN
STRUCTURES IN SDC D, E, F
N
PERIODIC
ERECTION AND FASTENING OF
EXTERIOR CLADDING, INTERIOR
AND EXTERIOR VENEER WEIGHING
MORE THAN 5 PSF IN STRUCTURES
> 30 FEET IN HEIGHT IN SDC D, E, F
N
PERIODIC
1705.11.5 SPECIAL INSPECTIONS FOR SEISMIC RESISTEANCE - MECHANICAL AND ELECTRICAL
RESISTANCE CONSISTS OF THE FOLLOWING:
THE DESIGNATED SEISMIC SYSTEMS REQUIRING SPECIAL INSPECTIONS FOR SEISMIC
[PROVIDE DESCRIPTION OF THE DESIGNATED SEISMIC SYSTEMS]
COMPONENTS (REQUIRED IN SDC C, D, E, F)
MECHANICAL AND ELECTRICAL
Y
PERIODIC
ANCHORAGE OF ELECTRICAL
EQUIPMENT FOR EMERGENCY OR
STAND BY POWER SYSTEMS IN SDC
Y
PERIODIC
C, D, E, F
ANCHORAGE OF OTHER ELECTRICAL
EQUIPMENT IN SDC E AND F
N
PERIODIC
INSTALLATION OF PIPING SYSTEMS
CARRYING HAZARDOUS MATERIALS
AND ASSSOCIATED MECHANICAL UNITS
N
PERIODIC
IN SDC SDC C, D, E, F
INSTALLATION OF HVAC DUCTWORK
THAT WILL CONTAIN HAZARDOUS
MATERIALS IN SDC C, D, E, F
N
PERIODIC
INSTALLATION OF VIBRATION
ISOLATION SYSTEMS IN SDC C-F
WHERE 0.25" OR LESS CLEARANCE
IS SPECIFIED BETWEEN THE
EQUIPMENT SUPPORT FRAME AND
RESTRAINT
IBC SECT. 1705.11.4
N
CONTINUOUS
FREQUENCY
Y
N
INSPECTION
STATEMENT OF SPECIAL INSPECTIONS:
THE FOLLOWING TABLES TOGETHER WITH THE SPECIFIC MATERIAL TESTS DESCRIBED IN THE PROJECT
SPECIFICATIONS SHALL CONSTITUTE THE STATEMENT OF SPECIAL INSPECTIONS IN ACCORDANCE WITH
IBC SECTION 1704. WHERE THE LOCAL JURISDICTION REQUIRES A GREATER LEVEL OF INSPECTION THAN
LISTED IN THE FOLLOWING TABLES THOSE REQUIREMENTS SHALL BE FOLLOWED.
(REQUIRED IN SDC C, D, E, F)
IDENTIFIED AS "DESIGNATED SEISMIC
SYSTEM" IAW ASCE 7 CH 13 (LIST
COMPONENTS HERE)
IBC SECT. 1705.11.2
IBC SECT. 1705.11.2
IBC SECT. 1705.11.3
IBC SECT. 1705.11.3
INSPECTION TASK
REFERENCE FOR
INSPECTION CRITERIA
1.
2.
3.
4.
5.
1705.13 SPRAY APPLIED FIRE-RESISTANT MATERIALS
FREQUENCY
Y
N
INSPECTION
STRUCTURAL MEMBER SURFACE
CONDITIONS PREPARATION
Y
PERIODIC
AVERAGE THICKNESS
Y
PERIODIC
MANUFACTURER'S
INSTRUCTIONS
DENSITY
Y
PERIODIC
APPROVED DESIGN
ASTM E605
BOND STRENGTH
Y
PERIODIC
IBC SECT. 1705.13.6
ASTM E 736
CONDITION OF FINISHED APPLICATION
Y
PERIODIC
APPROVED DESIGN
ASTM E605
IBC SECT 1705.13.4
IBC SECT 1705.13.5
INSPECTION TASK
REFERENCE FOR
INSPECTION CRITERIA
1.
2.
1705.16 FIRE-RESISTANT PENETRATIONS AND JOINTS
(HIGH-RISE BUILDINGS AND RISK CATEGORY III OR IV BUILDINGS)
FREQUENCY
Y
N
INSPECTION
PENETRATION FIRESTOPS
Y
PERIODIC
FIRE -RESISTANT JOINT SYSTEMS
Y
PERIODIC
APPROVED DESIGN
ASTM E2393
IBC SECT 1705.16.2
APPROVED DESIGN
ASTM E2393
IBC SECT 1705.16.2
Y
Y
DETAIL NUMBER
FIRE PROTECTION EQUIPMENT ITEM NUMBER
POINT OF CONNECTION
FLUSH MOUNTED HEAD
GEN. GENERAL
GALLON PER MINUTEGPM
FIRE DEPARTMENT CONNECTION
GALLONGAL
FURNISHED BY OTHERSFBO
FDC
FP
EXISTINGEXIST
DN DOWN
CONTRACTOR
BUILDINGBLDG
CONTR.
PD
PRV
NIC
BELOW FINISHED FLOOR
BACKFLOW PREVENTER
ABOVE FINISHED FLOORAFF
BFF
BFP
ACCESS PANELAP
PRESSURE REDUCING VALVE
PUMP DISCHARGE
NOT IN CONTRACT
SQUARE FEET
TYPICAL
SP SPRINKLER PIPE
CW COLD WATER
FIRE PROTECTION LEGEND AND ABBREVIATIONS
HP
SYMBOL
HORSE POWER
DESCRIPTION
TYP.
S/F
SYMBOL DESCRIPTION
SEMI-RECESSED HEAD
PENDENT HEAD
UPRIGHT HEAD
SIDEWALL SPRINKLER HEAD
E FIRE EXTINGUISHER
FIRE PUMP
PRE-ACTION VALVEP
FIRE HOSE CABINETFHC
NOTES
IF THE OWNER WITH CONSULTATION OF THE ARCHITECT DECIDES TO
ACCEPT A LESSER QUANTITY OR LOWER QUALITY OF PRODUCTS AND WORK, THE
CONTRACTOR SHALL REMIT TO THE OWNER THE DIFFERENCE BETWEEN THE COST OF THE
WORK THAT THE OWNER ACCEPTS AND THE COST OF THE GREATER QUANTITY OR BETTER
QUALITY OF PRODUCTS AND WORK.