This document outlines a pre-solicitation notice for architectural and engineering services. The Veterans Health Administration Program Contracting Activity Central is seeking statements of qualifications from firms interested in providing design services for the development of construction documents including drawings, specifications, and reports, as well as construction period services for Project #607-397 to expand specialty care at the VA Medical Care Center in Madison, Wisconsin. The anticipated firm fixed price contract will be awarded in accordance with the Selection of Architects and Engineers statute, FAR subpart 36.6, VAAR 836.6, and VAAM M836.6. Construction contracts will not be awarded to the designing firm or its affiliates per FAR 36.209. Interested parties should submit SF330 forms to the Department of Veterans Affairs Technology Acquisition Center Austin by the anticipated response date.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. VISIT THE PROJECT SITE PRIOR TO BID AND BECOME FAMILIAR WITH EXISTING CONDITIONS AFFECTING THE
WORK.
2. INSTALL WORK SUBSTANTIALLY AS SHOWN ON THE DRAWINGS. DEVIATIONS FROM LOCATIONS SHOWN MAY HAVE TO BE MADE AT NO ADDITIONAL COST TO THE OWNER IN ORDER TO CLEAR THE WORK OF THE OTHER TRADES. ALL SUCH DEVIATIONS SHALL BE PREVIOUSLY APPROVED BY THE OWNER'S REPRESENTATIVE.
3. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR EXACT LOCATION OF DRAINS AND PLUMBING
FIXTURES. VERIFY CEILING HEIGHT AND MATERIALS.
4. IT IS THE INTENT OF THESE DRAWINGS THAT A COMPLETE WORKING SYSTEM PROPERLY TESTED WILL BE
OPERATIONAL UPON COMPLETION OF INSTALLATION.
5. WHERE EXISTING PIPING IS REMOVED AND NOT RE-CONNECTED, CAP EXISTING SERVICES SO THAT DEAD END
PIPE RUNS ARE NOT CREATED.
6. PLUMBING CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING OF OPENINGS REQUIRED FOR
PLUMBING WORK.
6. PLUMBING CONTRACTOR IS RESPONSIBLE FOR REMOVING EXISTING VACUUM AND GAS SYSTEMS IN A CLEAN WORKING MANNER AND RECONNECT TO NEW WORK WITH LITTLE DISTURBANCE AS POSSIBLE TO CURRENT NOT IN CONTRACT ROOMS. ALL WELDS AND FITTINGS SHALL BE JOINED FOLLOWING ALL NFPA CODES BY A LICENSED CONTRACTOR TO WORK ON SAID SYSTEMS. INCORRECT INSTALLATIONS THAT DO NOT PASS INSPECTIONS AND CERTIFICATIONS SHALL BE TAKEN CARE OF BY CONTRACTOR AT NO COST TO THE GOVERNMENT.
GENERAL NOTES: PLUMBING
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
VITREOUS CHINAC_TOILETSKINGSTONK-4330
K-2031GREENWICHLAVATORYVITREOUS CHINA VITREOUS CHINAC_TOILETSKINGSTONK-4330
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-4915BARDONC_URINALSVITREOUS CHINA
VITREOUS CHINAC_TOILETSKINGSTONK-4330
VITREOUS CHINAC_TOILETSKINGSTONK-4330
VITREOUS CHINAC_TOILETSKINGSTONK-4330
1-1/4" HWR
2-1/2" HW
3" CW
1-1/4" HCW
3/4" CWR
2-1/2" HW
3" CW
3/4" HCW
3/4" CW
1-1/4" HW
2" SAN
DROP
2" SAN DN.
2" V UP
2" SAN UP/DN.
2" V UP/DN.
2" CW UP/DN.
4" HW UP/DN.
4" SAN UP/DN.
2" V UP/DN.
2" CW UP/DN.
4" HW UP/DN.
2" CW UP/DN.
4" HW UP/DN.
2" CW UP/DN.
2" HW UP/DN.
4" HW UP/DN.
2" CW UP/DN.
2" V UP/DN.
4" SAN UP/DN.
4" SAN UP/DN.
2" V UP/DN.
2" CW UP/DN.
4" HW UP/DN.
4" W UP/DN.
1" HW UP/DN.
2" CW UP/DN.
2" SAN UP/DN.
2" V UP/DN.
1" HW UP/ DN.
2" CW UP/DN.
2" SAN UP/DN.
" V UP/DN.
" HW UP/ DN.
" CW UP/DN.
4" SAN UP/DN.
2" V UP/DN.
2" HW UP/DN.
4" CW UP/DN.
4" HW UP/DN.
4" CW UP/DN.
2" SAN UP/DN.
2" V UP/DN.
4" HW UP/DN.
1" CW UP/DN.
2" SAN UP/DN.
2" V UP/DN.
" HW UP/DN.
" CW UP/DN.
2" SAN UP/DN.
" V UP/DN.
4" SAN UP/DN.
4" SAN UP/DN.
2" V UP/DN.
2" SAN DROP
2"
4"
1 1/2"
4" CW
4" HW
5" S UP/DN
'A' WING RISER: 4" CW, 3" HW,
2" HWR, 3 4" CWR, UP & DN.
2"
2"
(2) 2 GPM EACH
3" CW
3" HW
1" HWR
4" CWR
2" 68 CWFU
2" 48 HWFU
2" CW DN.
1" HW DN.
(2) 2 GPM
EACH
1" CW
1" HW
FD-W
FD-W
FD-W
FD-W
FD-W
FD-W
CW-42
4" CWR
4" HWR
2" V
1-1/4" HW
2" CW
FD
1-1/4" HW2-1/2" CW
1-1/4" HW, CW
4"
1 1/2"
3/4" HW, CW
2" HW 37 HWFU
3" CW 123 CWFU
4" HWR
4" CWR
FD
FD
FD
FD
FD
FD
FD
FD
4" HW
4" CW
FD
FD
1" HW
1" CW
2" HW
1-1/2" HW
SANITARY
UP TO
SCRUB SINKS
UP
2" SAN
VENT
2" CW
1-1/2" UP
VENT
SAN UP IN WALL?
1-1/2" CW
4"
2" SAN
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
VITREOUS CHINAC_TOILETSKINGSTONK-4330
K-2031GREENWICHLAVATORYVITREOUS CHINA VITREOUS CHINAC_TOILETSKINGSTONK-4330
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-4915BARDONC_URINALSVITREOUS CHINA
VITREOUS CHINAC_TOILETSKINGSTONK-4330
VITREOUS CHINAC_TOILETSKINGSTONK-4330
VITREOUS CHINAC_TOILETSKINGSTONK-4330
1-1/4" HWR
2-1/2" HW
3" CW
1-1/4" HCW
3/4" CWR
2-1/2" HW
3" CW
3/4" HCW
3/4" CW
1-1/4" HW
2" SAN
DROP
2" SAN DN.
2" V UP
2" SAN UP/DN.
2" V UP/DN.
2" CW UP/DN.
4" HW UP/DN.
4" SAN UP/DN.
2" V UP/DN.
2" CW UP/DN.
4" HW UP/DN.
2" CW UP/DN.
4" HW UP/DN.
2" CW UP/DN.
2" HW UP/DN.
4" HW UP/DN.
2" CW UP/DN.
2" V UP/DN.
4" SAN UP/DN.
4" SAN UP/DN.
2" V UP/DN.
2" CW UP/DN.
4" HW UP/DN.
4" W UP/DN.
1" HW UP/DN.
2" CW UP/DN.
2" SAN UP/DN.
2" V UP/DN.
1" HW UP/ DN.
2" CW UP/DN.
2" SAN UP/DN.
" V UP/DN.
" HW UP/ DN.
" CW UP/DN.
4" SAN UP/DN.
2" V UP/DN.
2" HW UP/DN.
4" CW UP/DN.
4" HW UP/DN.
4" CW UP/DN.
2" SAN UP/DN.
2" V UP/DN.
4" HW UP/DN.
1" CW UP/DN.
2" SAN UP/DN.
2" V UP/DN.
" HW UP/DN.
" CW UP/DN.
2" SAN UP/DN.
" V UP/DN.
4" SAN UP/DN.
4" SAN UP/DN.
2" V UP/DN.
2" SAN DROP
2"
4"
1 1/2"
4" CW
4" HW
5" S UP/DN
'A' WING RISER: 4" CW, 3" HW,
2" HWR, 3 4" CWR, UP & DN.
2"
2"
(2) 2 GPM EACH
3" CW
3" HW
1" HWR
4" CWR
2" 68 CWFU
2" 48 HWFU
2" CW DN.
1" HW DN.
(2) 2 GPM
EACH
1" CW
1" HW
FD-W
FD-W
FD-W
FD-W
FD-W
FD-W
CW-42
4" CWR
4" HWR
2" V
1-1/4" HW
2" CW
FD
1-1/4" HW2-1/2" CW
1-1/4" HW, CW
4"
1 1/2"
3/4" HW, CW
2" HW 37 HWFU
3" CW 123 CWFU
4" HWR
4" CWR
FD
FD
FD
FD
FD
FD
FD
FD
4" HW
4" CW
FD
FD
1" HW
1" CW
2" HW
1-1/2" HW
SANITARY
UP TO
SCRUB SINKS
UP
2" SAN
VENT
2" CW
1-1/2" UP
VENT
SAN UP IN WALL?
1-1/2" CW
4"
2" SAN
12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
THIRD FLOOR PLAN - PLUMBING DEMOLITION1
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
THIRD FLOOR PLAN - PLUMBING NEW WORK2
GENERAL NOTES
DEMOLITION NOTES
NEW WORK NOTES
3/4" CW
1-1/2" HW
2" CW
1-1/4" HW
1-1/2" CW
PLUMB
DRAIN
BOP = 111"
1-1/4" HW
S
S
S
S L
BOP = 101"
1-1/4" HW
1" CW
2" CW
S
NIC
NIC NIC
NIC
S
NIC
NIC
S
NIC
3/4" CW
1-1/2" HW
2" CW
CSS
S
1-1/4" HW
BOP = 116"
12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
FOURTH FLOOR PLAN - PLUMBING DEMOLITION1
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023
DEMOLITION NOTES
CLEAN
UTILITY
B4060
105SF
BR
TOILET
B4062A
74SF
CLEAN
UTILITY
B4060
105SF
BR
TOILET
B4062A
74SF
B4059B4059
CATH
LAB
C4109
CONTROL
ROOM
C4110SCRUB
ANTE-ROOM
C4111
EQUIPMENT
ROOM
C1409A
CLEAN
UTILITY
C4112
SOILED
UTILITY
C4151
AO
CR
OFFICE
B4147
RECOVERY 1
C4159B
RECOVERY 2
C4159C
RECOVERY
AREA
C4159
TLT
C4159A
STRESS
ROOM
C4150A
MEDS
NOURISH
C4159E
NURSE
STATION
C4159D
IT ROOM
C4109B
BREAK
ROOM
A4042
DSPECT
C4150C
CR
CR
VITREOUS CHINA
C_SINKSCAMERTON
K-12867
OA V S
CR
AO
FEC
PP
PP
CR
CR
OA V S
O
AO
AO
1-1/4" HW
1-1/2" CW
1-1/4" HW
1" CW
NIC
NIC NIC
NIC
NICNIC
NIC
NIC
4"
1 1/2"
2" SAN DN.
2" V UP
2" SAN UP/DN.
2" V UP/DN.
2" CW UP/DN.
4" HW UP/DN.
4" SAN UP/DN.
2" V UP/DN.
2" CW UP/DN.
4" HW UP/DN.
2" CW UP/DN.
4" HW UP/DN.
4" SAN UP/DN.
2" V UP/DN.
2" CW UP/DN.
4" HW UP/DN.
4" W UP/DN.
1" HW UP/DN.
2" CW UP/DN.
4" SAN UP/DN.
2" V UP/DN.
5" S UP/DN
2" 4"
1 1/2"
EXISTING
3/4" CW
1-1/2" HW
2" CW
1-1/4" HW
1-1/2" CW
1-1/4" HW
S
S
1-1/4" HW
1" CW
2" CW
NIC
NIC NIC
NIC
NIC
NIC
S
NIC
3/4" CW
1-1/2" HW
2" CW
1-1/4" HW
EXTEND TO ICE MAKER
SEE 6/PL500
1-1/2" HW
2" CW
1-1/2" HW
2" CW
12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
FOURTH FLOOR PLAN - PLUMBING NEW WORK1
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
GENERAL NOTES
NEW WORK NOTES
4th Floor
P-528
1-1/2" CIRCUIT VENT
(4 DFU)
2" PVC
FIELD LOCATE NEW CORED HOLE
WITHIN CABINET SPACE
2" SAN (4 DFU)
2" SAN
ACCESS PANEL BY ARCH
1/2" COPPER FROM ICE MAKER TO VISIBLE AIR
GAP CONNECTION AT FUNNEL DRAIN, INSTALL
TRAP PRIMER DOWNSTREAM OF LAV CW
FIXTURE STOP
8"
4"
8"
6"
4"
16" X 3 4" SLOT
8"
2'-0"
6"
2"
3'-0" 4"
Ø 716 HOLE 1-1/2" OD
4"
2"
MIXER BRACKET
1/2" IPS
SUPPLIES
THROUGH
WALL
FROM
FOOT
VALVE
24" FROM
FLOOR
(SUGGESTED)
1'-8"
1'-17 8"
16"
8"
16"
8"
2"7
16"
16" 4-716"
3-7 8"
1'-71 2"1'-4"
1'-10" 2'-1"
2"
Ø11 2"
2'-7"
ASSE 1070 TMV
FOOT CONTROL/FAUCET
COMPONENTS
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023
ALARM
PANEL
TO REMAIN,
MA O2 VAC
N2, N20
1/2" N2 3/4" N2O
2" VAC
FLOOR BOX:
MA,O2, VAC,
N2, S TO BE
REMOVED
NITROGEN GAS
CONTROL PANEL
TO BE REMOVED
3/4" VAC
3/4" VAC
WAGD
1/2" O2
1/2" AIR
1/2" N2O
2 -ZONE
VALVES TO
REMAIN
1-MA,O2,VAC
1-WAGD
3/4" WAGD
OUTLETS:
2"MA,12" O2, 2- 34"VAC,
2" N2O, 34" WAG
OUTLETS CEILING:
2"MA,12" O2, 2- 34"VAC,
2" N2O, 34" WAG TO
BE REMOVED
WALL OUTLETS:
O2 , MA, VAC, S,
,TO BE REMOVED
1 1/4" 02
3/4" MA
N2 FROM 3RD FLOOR
2-ZONE
VALVES TO
REMAIN
1-MA,02,VAC
1-WAGD
WALL OUTLETS:
VAC, S, MA, O2
TO BE
REMOVED
WALL OUTLETS:
O2 , MA, VAC, S,
,TO REMAIN
WALL OUTLETS:
O2 , MA, VAC, S,
,TO BE REMOVED
WALL OUTLETS:
O2 , MA, VAC, S,
,TO REMAIN
N20 AND N2
ZONE VALVE TO
REMAIN
OUTLETS:
2"MA,12" O2, 2- 34"VAC,
2" N2O, 12" N2, 34" WAG
2"MA,12" O2, 2- 34"VAC,
2" N2O, 34" WAG
NITROGEN GAS
CONTROL PANEL
OUTLETS WALL :
2"O2, 34"VAC,AND
SLIDE TO BE
REMOVED
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
VITREOUS CHINAC_TOILETSKINGSTONK-4330
K-2031GREENWICHLAVATORYVITREOUS CHINA VITREOUS CHINAC_TOILETSKINGSTONK-4330
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-4915BARDONC_URINALSVITREOUS CHINA
VITREOUS CHINAC_TOILETSKINGSTONK-4330
VITREOUS CHINAC_TOILETSKINGSTONK-4330
VITREOUS CHINAC_TOILETSKINGSTONK-4330
OUTLETS UP:
2"MA,12" O2, 1- 34"VAC,
2" N2, 2" N2 UP TO
NITROGEN GAS
CONTROL PANEL
OUTLETS UP:
2"MA,12" O2, 34"VAC,
2" N2, 12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
FOURTH FLOOR PLAN - MEDICAL GAS DEMOLITION2
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
GENERAL NOTES
DEMOLITION NOTES
12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
THIRD FLOOR PLAN - MEDICAL GAS DEMOLITION1
CATH
LAB
C4109
CONTROL
ROOM
C4110
SCRUB
ANTE-ROOM
C4111
EQUIPMENT
ROOM
C1409A
CLEAN
UTILITY
C4112
SOILED
UTILITY
C4151
OFFICE
B4147
RECOVERY 1
C4159B
RECOVERY 2
C4159C
RECOVERY
AREA
C4159
TLT
C4159A
STRESS
ROOM
C4150A
MEDS
NOURISH
C4159E
NURSE
STATION
C4159D
IT ROOM
C4109B
BREAK
ROOM
A4042
DSPECT
C4150C
FEC
O
A V
OA V S
WAGN2O
TYP.
O V
A
N2O
WAG
OA V S
O
A O V
WAG
N2O
ALARM
PANEL
TO REMAIN,
MA O2 VAC
N2, N20
1/2" N2 3/4" N2O
2" VAC
2 -ZONE
VALVES TO
REMAIN
1-MA,O2,VAC
1-WAGD
3/4" WAGD
OUTLETS:
2"MA,12" O2, 2- 34"VAC,
2" N2O, 34" WAG
1 1/4" 02
3/4" MA
N2 FROM 3RD FLOOR
2-ZONE
VALVES TO
REMAIN
1-MA,02,VAC
1-WAGD
WALL OUTLETS:
O2 , MA, VAC, S,
,TO REMAIN
WALL OUTLETS:
O2 , MA, VAC, S,
,TO REMAIN
N20 AND N2
ZONE VALVE TO
REMAIN
OUTLETS:
2"MA,12" O2, 2- 34"VAC,
2" N2O, 12" N2, 34" WAG
2"MA,12" O2, 2- 34"VAC,
2" N2O, 34" WAG
NITROGEN GAS
CONTROL PANEL
GO-1GO-1
GO-2
GO-3
ALP-1
NCP-1
3/4" MA, 3/4" O2, 1" MV
1/2" MA, 1/2" O2, 1" MV,
1" WAG, 1/2" N20
1/2" MA, 1/2" O2, 3/4" MV
GO-4
1/2" O2
1/2" MA, 1/2" O2, 3/4" MV
TO OUTLETS
AVOID PIPES IN
THIS AREA
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA VITREOUS CHINAC_TOILETSKINGSTONK-4330
K-2031GREENWICHLAVATORYVITREOUS CHINA VITREOUS CHINAC_TOILETSKINGSTONK-4330
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-2031GREENWICHLAVATORYVITREOUS CHINA
K-4915BARDONC_URINALSVITREOUS CHINA
VITREOUS CHINAC_TOILETSKINGSTONK-4330
VITREOUS CHINAC_TOILETSKINGSTONK-4330
VITREOUS CHINAC_TOILETSKINGSTONK-4330
OUTLETS UP:
2"MA,12" O2, 1- 34"VAC,
2" N2, 2" N2 UP TO
NITROGEN GAS
CONTROL PANEL
OUTLETS UP:
2"MA,12" O2, 34"VAC,
2" N2, GO-3
12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
FOURTH FLOOR PLAN - MEDICAL GAS NEW WORK2
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
GENERAL NOTES
NEW WORK PLAN NOTED
1 1
2 2
12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
THIRD FLOOR PLAN - MEDICAL GAS NEW WORK1
1 3
1/2" N2
1-1/4" O2
3/4" AIR
2" VAC
1/2" 02
3/4" VAC
1/2" AIR
1/2" N20
1/2" AIR
1/2" 02
3/4" WAGD
O2
AIR
VAC
1/2" 02
3/4" VAC
1/2" O2
1/2" AIR
3/4" VAC1/2" N2
1/2" O2
1/2" AIR
3/4" VAC
1/2" 02
3/4" VAC
3/4" O2
3/4" AIR
1" VAC
3/4" WAGD
3/4" O2
3/4" VAC
3/4" AIR
CONTROL ROOM
C4158
WAGD
C4159
FUTURE
5TH FLOOR LEVEL
4TH FLOOR LEVEL
8TH FLOOR LEVEL
6TH FLOOR LEVEL
7TH FLOOR LEVEL
3TH FLOOR LEVEL
CORRIDOR
C4161
CATH LAB 1
C4159
1/2" N2O
O2
VAC
A
N2O
N2
N2
3/4" AIR
3/4" VAC
3/4" O2
EXAM
ROOM
C4150A
CARDIOLOGY
ROOM
C4109
1/2" O2
1/2" AIR
3/4" VAC
CARDIOLOGY
ROOM
C4109
1/2" 02
AIR
AIR
WAGD N2O A A O2VAC
CATH LAB 1
C4159- WALL OUTLETS
CEILING OUTLETS
FLOOR OUTLETS
WALL OUTLETS
WALL OUTLETS
ZONE VALVE BOX
ZONE VALVE BOX
C4159
ZONE VALVE
BOX 3/4" VAC
FLOOR OUTLET -ETR
CATH LAB 2
C4156
CEILING
NITROGEN CONTROL
PANEL TO BE
RELOCATED
ZONE VALVE BOX
FUTURE
ZONE VALVE BOX
C4156
CATH LAB 2
C4156
WALL
WAGD
C4156
EXISTING OUT OF
SCOPE
GENERAL NEW PLAN NOTES P701 DEMO NOTES
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023
1" VAC
1/2" O2
1/2" AIR
3/4" VAC1/2" N2
1/2" O2
1/2" AIR
3/4" VAC
3/4" O2
3/4" A
1" VAC
3/4" WAGD
3/4" O2
3/4" VAC
3/4" AIR
CONTROL ROOM
C4158
WAGD
FUTURE
5TH FLOOR LEVEL
4TH FLOOR LEVEL
8TH FLOOR LEVEL
6TH FLOOR LEVEL
7TH FLOOR LEVEL
3TH FLOOR LEVEL
CORRIDOR
C4161
CATH LAB NEW
C4109
1/2" N2O
O2
VAC
AIR
N2O
N2
N2
3/4" AIR
3/4" VAC
3/4" O2
1/2" N2
1/2" O2
1/2" AIR
1/2" 02
3/4" VAC
1/2" AIR
1/2" N20
1/2" AIR
1/2" 02
3/4" WAGD
1/2" 02
3/4" VAC
DSPECT
C4150A
1/2" N2O
3/4" WAGD
1/2" 02
AIR
1/2" O2
1/2" AIR
3/4" VAC
1/2" N2
AIR
CEILING OUTLETS
FLOOR OUTLETS FLOOR OUTLET ETRRECOVERY ROOMS
NEW
C4159
1/2" O2
1/2" AIR
3/4" VAC
1/2" O2
1/2" AIR
3/4" VAC
RECOVERY ROOMS
NEW
C4159
WALL OUTLETS
CATH LAB 2
C4156
CEILING
1/2" N2
RELOCATED
CATH LAB 2
C4156
WALL
O2
AIR
ZONE VALVE BOX
ZONE VALVE BOX
WAGD
FUTURE
EXISTING OUT OF
SCOPE
GENERAL NEW PLAN NOTES P702 NEW PLAN NOTES
CONTROL ROOM
C4110
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023
1/
'-1
1 1/2 2'-0
1 1/2 10'-0
2 1 /2 x 4 '-7
1/
7'-2 1/2
2'
-1
1/
3'-5 1/2
1/
5'
-0
'-8
/2
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6 1 x
0' -6
1'
-5
/2
1/
8' -6
1 6' -7
1.5"76'-2"
1" 11'-2"
1" 11'-2" 1"11'-2"
1"19'-7"
1"12'-6"
1"12'-8"
1.5" 42'-2"
1"23'-10"
1"3'-9"
2"15'-10"1"1'-3" 1"9'-1"
1"2'-0" 1"5'-10"
2"9'-3"
1"3'-2"
2"37'-0"
1"4'-7" 1"5'-5"
2"45'-4"
1"12'-1"
1"0'-6"
1"2'-9"
1"6'-10"
1.5"20'-4"
1.5"3'-4"
2"19'-2"
1"1'-7"
1"1'-7"
1"10'-8"
1"2'-5"
1"1'-7"
1"8'-0"
1"1'-9"
1"9'-10"
1"5'-3"
1"9'-6"
1.25"4'-9"
1"1'-5" 1"1'-5"
2"19'-9"
1.5"4'-0"
1.25" 30'-0"1.25" 3'-6"1" 3'-0"
1.25"12'-0"1.5"3'-0"
1.5"12'-0"
2"3'-0"
1.25" 5'-6"1.5" 5'-6"
1"1'-6"
1" 2'-0"
1" AUX. DRAIN
3" 28'-5"
1" AUX. DRAIN
1"12'-6" 1.25"4'-3"
14'-0"
2.5"3'-0"
2"36'-8"
1" DRAIN
1"1'-3"1.25"6'-1"1"8'-7"
1"3'-3"
C4159
2 1/2 1'-7 1/2
2 1/2
2'-8 1/2
2 1/2" FLOOR CONTROL ASSEMBLY
SEE STANDPIPE DRAWINGS
CUT EXIST.
BRANCHLINE TO
CORRIDOR
CROSSMAINS- NEW
LINES NEED AVOID
PHILIPS CEILING
MOUNTED EQUIPMENT
FOURTH FLOOR CORE
FLOOR CONTROL ASSEMBLY
- 2 1/2" CONTROL VALVE
- FLOW SWITCH
- TEST & DRAIN VALVE
ELEVATOR
NO A.S.
ELEVATOR
NO A.S.
ELEVATOR
NO A.S.
ELEVATOR
NO A.S.
ELEVATOR
NO A.S.
1"12'-6" 1.25"1'-3"
1"12'-6" 1.25"1'-3"
1"11'-2" 1"11'-2"
1"11'-2"
1.5"42'-1"
7' -0
1"4'-7"
1"4'-7"
1"4'-7"
1"6'-11"
1"5'-4"
1"4'-2" 1" 4'-1"
1"1'-7"
1"1'-0"
1.5"12'-0"
1.25" 2'-0"1.25"6'-0"1.5"7'-0"2"3'-0"
1"12'-0"1"3'-0"
2.5" 22'-11"
2"3'-0"
1" 3'-3"1" 3'-3"
2"3'-0" 1.5"15'-9"
1" 1'-0" 1" 1'-8"
1" 1'-0" 1" 1'-8"
1" AUX. DRAIN
1" AUX. DRAIN
1 x 1'
-6
1 x 1'
-6
1 x 1'
-0
7'-4
2 7' -1
2 1' -3
2 2' -2
1 1/2 5'-2
1 1/2 1'-8
1 1/2 14'-7 1/2
1 1/2 13'-8 1/2
1 1/2 9'-9 1/2
1 1/2 13'-4
1 1/2 10'-1 1/2
1 1/2 9'-5
1 1/2 9'-9
1 1/2 12'-6
1 1/2 9'-6
3'-6
0'-9
1'-6
1/
2'
-2
1'-3 1 2'
-2
5' -1
3'-0 1/2
3'-0
1/
1'
-9 1 1' -9
'-0
/2 1 1' -9
'-0
/2 1 1' -9
'-0
/2
1' -9
1 8' -2
7'
-2
/2
7'-10
1 1/4
3'-4
1'-3
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6 1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1 x 0'
-6
1' -3
1/
3'
-1
/2
'-2
/2
'-4
/2
1 1/2 8'-8 1/2
1/
5'
-1
1/
3' -1
/2
1 1/2 12'-7 1/2
1 1' -1 1 1' -1 1 1' -1 1 1' -1 1 1' -1
4'-0 1/2
9'
-1
1/
0'
-1
9'
-2
/2
1/
5'
-8
/2
EXISTING FIRE HOSE CABINET. REMOVE 2 1/2"
VALVE AND ALL PIPING POSSIBLE. CAP AND
ABANDON PIPING NOT REMOVABLE.
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
DEMO PLAN NOTES
GENERAL DEMOLITION NOTES
1/
'-1
1 1/2 2'-0
1 1/2 10'-0
2 1 /2 x 4 '-7
1/
7'-2 1/2
2'
-1
1/
1 x 0'
-6 1 x
0' -6
6#3
1"
23'-10"
2"
37'-0"
1"
1'-7"
1"
5'-3"
FS
B4149
C4109
C4159
C4110 C4158
B4106
C4156A
C4158A
C4159A
B4148
B4147A
C4111
C4112
C4157
2 1/2 1'-7 1/2
2 1/2
2'-8 1/2
CONNECT TOEXIST.
BRANCHLINE TO
EXISTING C WING
CROSSMAIN. INSTALL
NEW PIPE AND
SPINKLER HEADS
AVOIDING NEW CATH
LAB PHILIPS
EQUIPMENT AND
CEILING NO FLY
ZONES
ELEVATOR
NO A.S.
ELEVATOR
NO A.S.
ELEVATOR
NO A.S.
ELEVATOR
NO A.S.
ELEVATOR
NO A.S.
1.5"
2"
14'-2" 1"
4'-1"
1"
1'-7"
1"
1'-0"
1 1/2 1'-8
1 1/4 2'-11 1/2
1/
5'
-1FLOOR CONTROL ASSEMBLY
- 2 1/2" CONTROL VALVE
- FLOW SWITCH
- TEST & DRAIN VALVE
CATH
LAB
C4109
CONTROL
ROOM
C4110SCRUB
ANTE-ROOM
C4111
EQUIPMENT
ROOM
C1409A
CLEAN
UTILITY
C4112
AO
CR
OFFICE
B4147
RECOVERY 1
C4159B
RECOVERY 2
C4159C
RECOVERY
AREA
C4159
TLT
C4159A
MEDS
NOURISH
C4159E
NURSE
STATION
C4159D
IT ROOM
C4109B
CR
OA V S
CR
AO
FEC
PP
PP
CR
CR
OA V S
AO
AO
1.5"
20'-4"
1"
8'-0"
1"
9'-10"
1"
5'-3"
1"
9'-6"
1.25"
4'-9"
1.5"
4'-0"
1"
1'-7"
2"
15'-10"
2"
9'-3"
STAIR
A4042 B4049A
1.5"
42'-1"
BREAK
ROOM
A4042
CR
2"
36'-8"
C4150
C4151
C4150A
C4150B
C4150C
2"
45'-4"
SOILED
UTILITY
C4151
STRESS
ROOM
C4150A
DSPECT
C4150C
VITREOUS CHINA
C_SINKSCAMERTON
K-12867
O
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
NEW PLAN NOTES
EQUIPMENT NOTES
NOTES
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023
16/8 SA
/1
8"Ø
10/10
16/6 10/6 10/10
/6
/1
/1
/6
16/6
8/10
14/
/6
8/10
/6
12/6
/1
SA
20/10 10 /6
18/10
18/10
14/14
14/14
18/8
/1
RA
/1
/8
/1
/1
T
T
T
T
T
T
T
T
T
T
/1
10/6
/6
/1
0 10"Ø x1
TT
T
T
T
T
50/20
UP TO
ROOF
T
TT
/1
SA
T
EX 230
EA
8/8
785 EA
EX 60
SA
EX 65
SA
EX 60
SA
EX 60
SA
EX 60
SA
EX 60
SA
EX 60
EA EX 60
EA
EX 160
SA
EX 60
EA
EX 65
EA
EX 60
EA
/1
EA
13/13
EA
12/13
EA
EX 65
SA
EX 60
SA
EX 65
EA
EX 120
EA
EX 60
EA
EX 60
EA
13/13
EA
EX 60
SA
EX 60
EA
24/10
EA
SD
28/12
SA
LOCATED IN
PENTHOUSE
EX 60
SA
EX 60
EA T
FSD
TFSD
EX 135
SAEX 75
SA
EX 365
SA
EX 250
SA
EX 250
SA
EX 250
SA
EX 250
SA
EX 250
SA
EX 365
SA
EX 365
SA
EX 325
SA
EX 475
RA
EX 415
RA
EX 415
RA
EX 155
SAEX 158
EA
EX 750
RA
EX 750
RA
24/8
16/6
EX 300
RA EX 150
SA
EX 150
SA EX 78
EAEX 400
RAEX 68
EA
16/8
EX 550
SA
EX 560
RA
EX 560
RA
EX 560
RA
EX 103
EA
EX 100
SA
EX 415
RA
10/6
EX 200
SA EX 230
SA
EX 350
SA
EX 200
SA
EX 650
SA
EX 650
SA
50/20
UP TO
ROOF
EX 530
RA
EX 265
SA
EX 265
SA
EX 180
SA
EX 190
SA
26/22
UP TO
ROOF
EX 700
RA
22/16
EX 200
SA
EX 360
SA
EX 360
RA
EX 350
SA
EX 200
RA
EX 230
RA
14/6
EX 200
SA
EX 240
SA
EX 240
EA
EX 420
EX 415
RA
EX 415
RA
EX 415
SA
EX 415
SA
EX 190
SA
EX 380
RA
20/14 RA
18/12 SA
1-1/2" HW
12/12
UP TO
ROOF
12/12
UP TO
ROOF
EX 155
FCU
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
DEMO PLAN NOTES
GENERAL DEMOLITION NOTES
FOURTH FLOOR PLAN - HVAC DUCTWORK DEMOLITION
12" 0 1' 5' 10'
SCALE: 1/8" = 1'-0"
2"LPS
21/2"MPR UP
31/2"MPR DN
5"MPS
UP/DN
5"LPS UP
5"LPS
5"
LP
S 5"
LP
S
6"HPS UP/DN
T
T
T
T
T
T
T
T
T
T
3"LPR UP/DN
NEW
2" RHW
S
& RHW
R UP
2"
RH
W R 2"
RH
W S
6"CHS/CHR
UP/DN
4"M
PR UP/DN
3"LPR UP
5"LPS UP
3/4" HWS/HWR
UP
1-1/2"MPS UPMPR UP
5"HWS & HWR DN 2"HWS
& HWR UP TO ROOF
NEW
1-1/2" HW
S & HW
R UP
2" R
HW
S2
" R
HW
R 2"
R
HW
S2" R
HW
R
HW
R
HW
SHW
R
HW
S
5"LPS UP
MPR
STERILIZERGLASS
WASHER
T
T
1"CHS/CHR DN
1-1/2"LPS DN
T
T
1-1/4"
1-1/4"
1-1/2"
1"
3/4"
T
T
T
CH
SCH
R
RS
RL
FCU
2" HWS, HWR, CHS,
CHR
2"
2" C
HS2"
C
HR
T
FCU
3/4"
1"
3/4"
T
TT
T
785 EA
EX-FCU
T
CHS
HWSCHR
HWR
1-1/4"
HW
R
HW
S
T
EX-FCU EX-FCU
6"LPS UP
6"LPS UP
3/4"
1" 3/4"
3/4"
EX-CONV
RH-4C-02
RH-4C-06
RH-4C-01
RH-4C-07
RH-4C-08
RH-4C-11
RH-4C-09A
RH-4C-10
RH-4C-14
RH-4C-13
RH-4C-12
RH-4C-09B
RH-4C-01
RH-4C-04
RH-4C-03
1"
1-1/2" HW
6"LPS
CAPPED
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV EX-CONV
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
DEMO PLAN NOTES
GENERAL DEMOLITION NOTES
FOURTH FLOOR PLAN - HVAC PIPING DEMOLITION
12" 0 1' 5' 10'
SCALE: 1/8" = 1'-0"
CATH
LAB
C4109
CONTROL
ROOM
C4110
SCRUB
ANTE-ROOM
C4111
EQUIPMENT
ROOM
C1409A
CLEAN
UTILITY
C4112
SOILED
UTILITY
C4151
OFFICE
B4147
RECOVERY 1
C4159B
RECOVERY 2
C4159C
RECOVERY
AREA
C4159
TLT
C4159A
STRESS
ROOM
C4150A
MEDS
NOURISH
C4159E
NURSE
STATION
C4159D
IT ROOM
C4109B
BREAK
ROOM
A4042
DSPECT
C4150C
CLEAN
UTILITY
B4060
105SF
BR
TOILET
B4062A
74SF BARIATRIC
ROOM
B4062
249SF
PATIENT
ROOM
B4064
242SF
CLEAN
UTILITY
B4060
105SF
BR
TOILET
B4062A
74SF BARIATRIC
PATIENT ROOM
B4062
249SF
PATIENT
ROOM
B4064
242SF
BARIATRIC
ROOM
B4063
23SF
BR
TOILET
B4063A
54SF
NURSE
ALCOVE
B4193
35SF
NURSE
MANAGER
B4061
95SF
B4059B4059
BARIATRIC
ROOM
B4063
23SF
BR
TOILET
B4063A
54SF
NURSE
ALCOVE
B4193
35SF
NURSE
MANAGER
B4061
95SF
AO
CR
CR
CR
VITREOUS CHINA
C_SINKSCAMERTON
K-12867
OA V S
CR
AO
FEC
PP
PP
CR
CR
OA V S
O
AO
AO
/1
/1
/6
16/6
8/10
14/
/6
8/10
/6
12/6
/1
SA
20/10 10 /6
18/10
18/10
14/14
14/14
18/8
/1
RA
/1
/8
/1
/1
T
T
T
T
T
/6
TT
T
T
T
T
50/20
UP TO
ROOF
T
EX 230
EA
8/8
785 EA
EX 60
SA
EX 65
SA
EX 60
SA
EX 60
SA
EX 60
SA
EX 60
SA
EX 60
EA EX 60
EA
EX 160
SA
EX 60
EA
EX 65
EA
EX 60
EA
/1
EA
13/13
EA
12/13
EA
EX 65
SA
EX 60
SA
EX 65
EA
EX 120
EA
EX 60
EA
EX 60
EA
13/13
EA
EX 60
SA
EX 60
EA
24/10
EA
SD
28/12
SA
LOCATED IN
PENTHOUSE
EX 60
SA
EX 60
EA T
FSD
TFSD
EX 475
RA
EX 155
SA
16/8
EX 550
SA
EX 560
RA
EX 560
RA
EX 560
RA
EX 103
EA
10/6
EX 230
SA
EX 350
SA
EX 650
SA
EX 650
SA
50/20
UP TO
ROOF
EX 530
RA
EX 265
SA
EX 265
SA
EX 180
SA
EX 190
SA
26/22
UP TO
ROOF
EX 700
RA
22/16
EX 200
SA
EX 360
SA
EX 360
RA
EX 350
SA
EX 200
RA
EX 230
RA
14/6
EX 200
SA
EX 240
SA
EX 240
EA
EX 420
20/14 RA
1-1/2" HW
12/12
UP TO
ROOF
12/12
UP TO
ROOF
EX 155
FCU
VAV-4150.2
VAV-4150.1
RHC-4159.2
VAV-4159.3
VAV-4147RHC-4159.1
RHC-4109
VAV-4110
LOW
RETURN
RHC-4112
F 819
RA
1 251
SA
B 251
RA
2 320
SAC 280
EA
2 357
SA
C 311
RA
F 166
EA
2 365
SAD 635
RA
F 135
EA
B 162
RA
1 162
SA
1 104
SA
1 104
SA
A 90
RA
3 535
SA
C 715
RA
1 155
SA
5 75
SA
B 75
RA
6 900
SA
48x8 8/6
E A
28/12
SA
16/12
/10
/12
5 615
SA
36x8
A 50
RA
A 50
TG
24/8 DN
LOW
RETURN
F 819
RA24/8
DN
/12
RA
/12
R A
5 615
SA
36x8
/14
R A
VAV-4111
6/6
4TH FLOOR C-WING
ROOF
'-8
9'- 8"
8'- 6"
10/6
/8
16/8
/8
4Ø
10/8
10/8 EA
/12
20/12
/6
10/6
A 90
RA
6"Ø 6"Ø
/10
/8
10/6 16/10
/10
/6
6" Ø
AC-1
2 365
SA
8/6 E
A
16/12 16/12
8/6 E
A
(2-WAY THROW)
/6
D4109-SAAFMS
9'-
1/ 4"
7/
8"
VAV-4150.3
D 190
RA
20/12
C 375
RA2 375
SA
CATH
LAB
C4109
CONTROL
ROOM
SCRUB
ANTE-ROOM
EQUIPMENT
ROOM
C1409A
C4109B
AO
CR
PP
CR
CR
AO
AO 16
/6
EX 475
RA
16/8
1-1/2" HW
12/12
UP TO
ROOF
RHC-4109
TT
T
LOW
RETURN
F 819
RA
1 251
SA
B 251
RA
2 320
SAC 280
EA
6 900
SA
48x8 8/6
E A
28/12
SA
16/12
/10
/12
5 615
SA
36x8
A 50
RA
A 50
TG
24/8 DN
LOW
RETURN
F 819
RA24/8
DN
/12
RA
/12 R
A
5 615
SA
36x8
/14
R A
6/6
4TH FLOOR C-WING
10/6
/8
4Ø
AC-1
D4109-SAAFMS
20/12
T RT
OFFICE
B4147
RECOVERY 1
C4159B
RECOVERY 2
C4159C
RECOVERY
AREA
C4159
TLT
C4159A
MEDS
NOURISH
C4159E
NURSE
STATION
C4159D
CR
OA V S
AO
FEC
PP
CR
OA V S
12/6 24 /8
/1
8/8
EA
EX 475
RA
EX 155
SA
EX 103
EA
1-1/2" HW
RHC-4159.2
VAV-4159.3
VAV-4147RHC-4159.1
T T
T
T
F 135
EA
B 162
RA
1 162
SA
1 104
SA
1 104
SA
A 90
RA
3 535
SA
C 715
RA
1 155
SA
5 75
SA
B 75
RA
8/6 E
A
/10
/12
20/12
/6
10/6
A 90
RA
6"Ø 6"Ø
/10
/8
10/6 16/10
/10
/6
6" Ø
8/6 E
A
16/12 16/12
(2-WAY THROW)
/6
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
NEW PLAN NOTES
GENERAL NEW PLAN NOTES
FOURTH FLOOR PLAN - HVAC PIPING NEW WORK
12" 0 1' 5' 10'
SCALE: 1/8" = 1'-0"
FOURTH FLOOR PLAN - HVAC DUCTWORK ENLARGED CATH LAB NEW WORK
12" 0 1' 5' 10'
SCALE: 1/4" = 1'-0"
FOURTH FLOOR PLAN - HVAC DUCTWORK ENLARGED RECOVERY AREA
12" 0 1' 5' 10'
SCALE: 1/4" = 1'-0"
CATH
LAB
C4109
CONTROL
ROOM
C4110
SCRUB
ANTE-ROOM
C4111
EQUIPMENT
ROOM
C1409A
CLEAN
UTILITY
C4112
SOILED
UTILITY
C4151
OFFICE
B4147
RECOVERY 1
C4159B
RECOVERY 2
C4159C
RECOVERY
AREA
C4159
TLT
C4159A
STRESS
ROOM
C4150A
MEDS
NOURISH
C4159E
NURSE
STATION
C4159D
IT ROOM
C4109B
BREAK
ROOM
A4042
DSPECT
C4150C
CLEAN
UTILITY
B4060
105SF
BR
TOILET
B4062A
74SF BARIATRIC
ROOM
B4062
CLEAN
UTILITY
B4060
105SF
BR
TOILET
B4062A
74SF
NURSE
MANAGER
B4061
95SF
B4059B4059
NURSE
MANAGER
B4061
95SF
AO
CR
CR
CR
VITREOUS CHINA
C_SINKSCAMERTON
K-12867
OA V S
CR
AO
FEC
PP
PP
CR
CR
OA V S
O
AO
AO
2"LPS
21/2"MPR UP
31/2"MPR DN
5"MPS
UP/DN
5"LPS UP
5"LPS
5"
LP
S 5"
LP
S
6"HPS UP/DN
T
T
T
T
T
3"LPR UP/DN
2"
RH
W R 2"
RH
W S
5"HWS & HWR DN 2"HWS
& HWR UP TO ROOF
2" R
HW
S2
" R
HW
R 2"
R
HW
S2" R
HW
R
HW
R
HW
SHW
R
HW
S
STERILIZERGLASS
WASHER
T
1"CHS/CHR DN
1-1/2"LPS DN
T
1-1/4"
1"
3/4"
T
T
T
CH
SCH
R
2" HWS, HWR, CHS,
CHR
2"
2" C
HS2"
C
HR
T
FCU
1"
3/4"
T
785 EA
EX-FCU
T
CHS
HWSCHR
HWR
1-1/4"
HW
R
HW
S
T
EX-FCU EX-FCU
6"LPS UP
6"LPS UP
3/4"
1"
3/4"
EX-CONV
RH-4C-07
RH-4C-08
RH-4C-11
RH-4C-09A
RH-4C-10
RH-4C-14
RH-4C-12
RH-4C-09B
RH-4C-01
1"
1-1/2" HW
6"LPS
CAPPED
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
EX-CONV
T
RHC-4150.1
RHC-4150.2
RHC-4109
RHC-4112
T
TT
T
T T
T
T
AC-1
MOUNT IN
CEILING GRID
4TH FLOOR C-WING
ROOF
'-8
9'- 8"
8'- 6"
VAV-4110VAV-4111
RHC-4159.1
RHC-4159.2
9'-
1/ 4"
7/
8"
VAV-4147
VAV-4159.3
T
T RT
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
FOURTH FLOOR PLAN - HVAC PIPING NEW WORK1
NEW PLAN NOTES
GENERAL NEW PLAN NOTES
AHU-124
LP
S
CH
S
CH
R
LP
R
ACCUACCU
ACCU
44/24
REMOVE EXISTING CONDENSING UNIT
AND ASSOCIATED REFRIGERATION
PIPING SERVING FAN COIL UNIT IN
ROOM B4-147. EXISTING ACCU & PIPING
CURBS TO REMAIN.
EXISTING RETURN DUCT
TO BE LOWERED FOR
NEW STAIR ACCESS.
SEE NEW WORK PLAN
M103
SEE PHOTO
M103
SEE PHOTO
EF-2 CFM
EF-1 (EF-124)
407 CFMREMOVE EXISTING EF-2. EXISTING
CURBS TO REMAIN OR PROVIDED NEW
WITH SAME SIZE OPENING.
REMOVE EXISTING EF-1. EXISTING
CURBS TO REMAIN OR PROVIDED NEW
WITH SAME SIZE OPENING.
FOR 1/2" RHG AND 1/4" RL SEE M102
FOR CONTINUATION
PROVIDE DRAIN AS NECESSARY PER
MANUFACTURER'S REQUIREMENT.
DIRECT DRAIN PIPING TO NEAREST
ROOF DRAIN.
AHU-124
LP
S
CH
S
CH
R
LP
R
ACCU
ACCU
DN
UP
44/24
LOWERED RETURN DUCT
FOR NEW STAIR ACCESS.
REVISE EXISTING DUCT
SUPPORTS AND REINSULATE
DUCTWORK AS REQUIRED.
M103
NEW STAIRWAY OVER
LOWERED DUCT
NEW ACCU-1
EF-2
450 CFM
EF-1 (EF-124)
600 CFM
FOR 1/2" RHG AND 1/4" RL SEE M102
FOR CONTINUATION
PROVIDE DRAIN AS NECESSARY PER
MANUFACTURER'S REQUIREMENT.
DIRECT DRAIN PIPING TO NEAREST
ROOF DRAIN.
NEW STAIRWAY
ROOF
MODIFY EXISTING
DUCT SUPPORTS FOR
LOWERED DUCT
LOWER PORTION OF
EXISTING RETURN DUCT
TO 12" ABOVE ROOF
12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
FIFTH FLOOR PLAN - HVAC DEMOLITION1
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
B A
C
B-Core
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
12" 0 1' 5' 10' 20'
SCALE: 1/8" = 1'-0"
FIFTH FLOOR PLAN - HVAC NEW WORK2
NO SCALE
FIFTH FLOOR C-WING ROOF PHOTO5
12" 0 1' 5' 10'
SCALE: 1/4" = 1'-0"
SECTION AT NEW ACCESS STAIRWAY3
NO SCALE
FIFTH FLOOR C-WING ROOF PHOTO4
NO SCALE
FIFTH FLOOR EXHAUST FAN EF-1 AND EF-2 PHOTO6
SCALE: NTS
RECTANGULAR AND ROUND FLEXIBLE CONNECTION DETAILS
MH-500
SCALE: NTS
RH-VAV BOX AIR TERMINAL UNIT INSTALLATION DETAIL
MH-500
SCALE: NTS
PIPING HIGH AND LOW POINT DETAILS
MH-500
MH-500
MH-501
MH-501
MH-501
SCALE: NTS
GYPSUMBOARD WALL MOUNTED RETURN GRILLS 3
MH-500
SCALE: NTS
HOT WATER HEATING COIL (RHC-#) & VAV (VAV-#) PIPING CONNECTIONS
MH-500
MH-500
MH500
MH-501
MH-501
MH-500
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
SCALE: NTS
GYPSUM BOARD CEILING MOUNTED SUPPLY AIR
MH-500
MH-500
SCALE: NTS
DUCTWORK TRANSITIONS (WITH EQUIPMENT MOUNTED IN DUCT) 9
MH-500
SCALE: NTS
ROOF DUCT AND PIPING SUPPORTS 7
MH-500
MH501
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
SCALE: NTS
DUCTWORK BRANCH CONNECTION 2
MH-501
SCALE: NTS
DUCTWORK SQUARE VANED ELBOWS 3
MH-501
SCALE: NTS
FLEXIBLE DUCT WORK SUPPORT 4
MH-501
SCALE: NTS
DUCTWORK RADIUS ELBOWS 5
MH-501
SCALE: NTS
DUCT WORK HANGER SUPPORTS 7
MH-501
SCALE: NTS
VOLUME DAMPER DETAIL (VD) 8
MH-501
MH-500
MH-501
MH-500
MH-500 5
MH-500
MH-500
MH-500
SCALE: NTS
DUCT CROSSOVER DETAIL 9
MH-501
SCALE: NTS
EXHAUST FAN DETAIL 6
MH-501
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
REGISTER - GRILLE - DIFFUSER SCHEDULE
MARK FUNCTION TYPE CFM
MAX SIZE BORDER MATERIAL
FINISH
MANUFACTURER
REMARKS
N.C.
(INCHES) OR FRAME STEEL & MODEL NO.
REMARKS:
1. PROVIDE SPECIFIC NOISE CRITERIA (NC) DATA FOR EACH LINE ITEM WITH SHOP DRAWINGS. NOT TO EXCEED 35
2. COORDINATE BORDER OR FRAME TYPE WITH CEILING OR WALL TYPE. SEE A201 AND A702.
3. COORDINATE FINISH WITH ARCHITECT/ENGINEER.
4. DIFFUSER / GRILLE TO BE CEILING RECESSED. SEE PLANS
5. DIFFUSER / GRILLE TO HAVE VOLUME DAMPER IN BRANCH DUCTWORK. SEE PLANS
RETURN X STND.
WHITE 1, 2, 3, 4, 5
164-545 10" Ø
NECK
RA-D
X 1, 2, 3, 4, 5EA-G STND.
WHITE
16-20
DESIGN
SA-1
SA-2
1, 2, 3, 4, 5
SQUARE FACE
NOMINAL PNL.
24 X 24
X STND.
WHITE
SUPPLY 24 x 24
LAY-IN
1, 2, 3, 4, 5
SQUARE FACE
NOMINAL PNL.
24 X 24
X STND.
WHITE NAILOR RNSSUPPLY
12" Ø
NECK
19-22315-785
24 x 24
LAY-IN
NAILOR RNS
NAILOR 4360
NAILOR 4360
14-19
24 x 24
LAY-IN
105-349PERF. PANEL
12 x 12
8" Ø
NECK
EXHAUST 10-16 X STND.
WHITE 1, 2, 3, 4, 5164-275
12 x 12
LAY-IN
EA-H PERF. PANEL
24 x 24
NAILOR 4360
10" Ø
NECK
19-24 24 x 24
LAY-IN
236-
PERF. PANEL
24 x 24
12" Ø
NECK
RETURN X STND.
WHITE 1, 2, 3, 4, 5RA-E NAILOR 436015-21 24 x 24
LAY-IN321-855PERF. PANEL
24 x 24
14" Ø
NECK
SA-3
140-420 8" Ø
NECK
14-19 1, 2, 3, 4, 5
SQUARE FACE
NOMINAL PNL.
24 X 24
X STND.
WHITE NAILOR RNSSUPPLY 24 x 24
LAY-IN
SPLIT SYSTEM UNIT SCHEDULE
INDOOR OUTDOOR CFM COOLING DATA (MBH) MANUFACTURER
INDOOR-BASIS
OF DESIGN
INDOOR UNIT OUTDOOR UNIT
UNIT MARK UNIT MARK CAPACITY
RANGE
NOMINAL MODEL NO. MODEL NO.
AC-1 ACCU-1 4-22 18 SAMSUNG
SERIES CEILING
MOUNTED
CASSETTE OR
APPROVED
EQUAL
AC018BN4DCH/AA
REMARKS:
1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE ON E002 FOR ELECTRICAL DATA.
2. COOLING DATA BASED ON 95°F OUTDOOR TEMPERATURE, INDOOR 80.6°F DB/ 66.2°F WB.
3.
4.
CONDENSATE PUMP TO BE SHIPPED LOOSE FOR FIELD INSTALLATION AND BE POWERED OFF THE INDOOR UNIT. PUMP OPTION BD-BLUE230
5.
PROVIDE OUTDOOR UNIT WITH SUPPORTING STAND
6. DISCONNECT PROVIDED BY MC/EC AND FIELD INSTALLED.
7. PROVIDE LOW AMBIENT WIND BAFFLES FOR COOLING TO -40F.
8.
PROVIDE THERMOSTAT CONTROLLERS.
CFM
636-848 1413
L-H
REFRIGERANT PIPE SIZED AND LENGTHS TO BE COORDINATED WITH MANUFACTURER FOR A COMPLETE
PACKAGE. NOT TO EXCEED 164 LINEAR FT WITH 96 VERTICAL SEPARATION.
9.
MANUFACTURER
OUTDOOR-BASIS
OF DESIGN
SAMSUNG
OUTDOOR
CONDENSER OR
APPROVED
EQUAL
PROVIDE BACNET INTERFACE BOARD FOR SYSTEM TO TIE INTO BAS SYSTEM.
10. INDOOR UNIT COMES WITH WASHABLE FILTER MEDIA.
AC018BXSCCC/AA
REFERENCE CONTROL DIAGRAMS FOR TEMPERATURE CONTROL AND PROVIDE ROOM SENSOR CONNECTED TO BMS FOR
FAILURE/ALARM NOTIFICATIONS
11.
1, 2, 3, 4, 5
SQUARE FACE
NOMINAL PNL.
24 X 24
X STND.
WHITE
SUPPLY 24 x 24
LAY-IN
6" Ø
NECK
13-1780-315 NAILOR RNSSA-4
X 1, 2, 3, 4, 5RA-A STND.
WHITE NAILOR 4360
10-1559-275PERF. PANEL
24 x 24
RETURN 24 x 24
LAY-IN
6" Ø
NECK
RETURN X STND.
WHITE 1, 2, 3, 4, 5RA-B NAILOR 436014-19 24 x 24
LAY-IN105-489PERF. PANEL
24 x 24
8" Ø
NECK
RETURN X STND.
WHITE 1, 2, 3, 4, 5RA-C NAILOR 436010-16 24 x 24
LAY-IN164-545PERF. PANEL
24 x 24
10" Ø
NECK
RA-F 890WALL PANEL
24 x8
24X8"RETURN
EXHAUST
SUPPLY
SUPPLYSA-5
SA-6 WALL PANEL.
48 X 8
36x8"
48x8"
CNH184DB CXC18SCB
13-19
13-20
36 x 8
LAY-IN
48 x 8
LAY-IN
TITUS 300
TITUS 350
1, 2, 3, 4, 5
1, 2, 3, 4, 5
TITUS 300
X
X
STND.
WHITE
STND.
WHITE
X
WALL PANEL.
36 X 8
12-20 24 x 8
LAY-IN
STND.
WHITE 1, 2, 3, 4, 5
FAN SCHEDULE
MARK SERVES TYPE CFM EXT. FAN DRIVE CONTROL
MANUFACTURER
REMARKSS.P. RPM BASIS OF DESIGN
EF-2 C-4111
ROOF MOUNTED
POWER
EXHAUSTER 450 .5'' 1800 DIRECT UNIT
MOUNTED 1,2,3
REMARKS:
1. PROVIDE 18" HIGH ROOF CURB OR REUTILIZE EXISTING WHEREVER NECESSARY. VERIFY SIZE IN FIELD
MOTOR
GENERAL NOTES:
A. CONTRACTOR SHALL VERIFY/COORDINATE ALL RATINGS FOR EQUIPMENT SUPPLIED BY THE SELECTED MANUFACTURER. WHERE RATINGS ARE OTHER THAN AS NOTED ON MECHANICAL/ELECTRICAL COORDINATION SCHEDULE, DISCONNECTS, MOTOR STARTERS, OVERCURRENT DEVICES AND RELATED REVISIONS SHALL BE PROVIDED ACCORDINGLY. THE CONTRACTOR THAT FURNISHES EQUIPMENT WITH RATINGS OTHER THAN AS NOTED SHALL BE RESPONSIBLE FOR ALL COORDINATION AND COSTS FOR REVISIONS TO ACCOMMODATE SELECTED EQUIPMENT.
B. ALL FRACTIONAL HORSEPOWER MOTORS SHALL BE PROVIDED WITH INTEGRAL OVERLOAD PROTECTION.
C. HORSEPOWER RATED TOGGLE SWITCHES (SH): FOR 120 V MOTORS LESS THAN 1/2 HP, REUTILIZE EXISTING 15 OR 20 AMP BREAKER IN EXISTING
PANEL.
VOLTS/
PHASE
120V/1P
1/6 HP-
ECODP
2. PROVIDE EXTERNALLY MOUNTED DISCONNECT/ HP RATED TOGGLE SWITCH
& MODEL NO.
EF-1
(EF 124)
ROOF MOUNTED
POWER
EXHAUSTER 600 1" DIRECT UNIT
MOUNTED 1,2,3120V/1P
TWIN CITY MODEL VC
112 OR APPROVED
EQUAL
1/6 HP-
ECODP
3. PROVIDE FACTORY SPEED CONTROLLER OR CONSTANT VOLUME
TWIN CITY MODEL VC
098 OR APPROVED
EQUAL
TG 35-87PERF. PANEL
12 x12
4" ØTRANSFER NAILOR RNS &
ARNSX11-19 12 x 12
LAY-IN
STND.
WHITE 1, 2, 3, 4, 5
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
CATH LAB C4109
Output Input Virtual Local Controller BAS Full BAS
IntegrationDigital Analog Digital Analog Digital Analog Visible Adjustable Overridable Visible Adjustable Overridable SA Damper Command (V-1) X X X X X SA Damper Feedback (V-1) X X
X
XX
X X
X X X
X X X X X
X X X X X X X X X
REHEAT COUNT SCHEDULE
X
X X
FCU
(EX)
ACCU
NEW
(4C)
ACCUs
(EX)
FCU
(EX)
JACE-002
(C4144)
RS485
BACnet
OTHERS
General CV Points List - C WING- See schedule for related boxes Output Input Virtual Local Controller BAS Full BAS
IntegrationDigital Analog Digital Analog Digital Analog Visible Adjustable Overridable Visible Adjustable Overridable
(RHCV TERMINAL UNIT TYPICAL
FOR 3 GROUPS)
RHCV TERMINAL UNIT RH-N FLOW
RHCV TERMINAL UNIT RH-N SA TEMP
V-1 RE-HEAT VALVE
V-2 RE-HEAT VALVE
V-3 RE-HEAT VALVE
FAN EF-1(EF124) STATUS/ALARM
FAN EF-1(EF124) SPEED
FAN EF-1(EF124) START/STOP
FAN EF-2 STATUS/ALARM
FAN EF-2 SPEED
FAN EF-2 START/STOP
RM SIDE PRESSURE SENSOR-NEW
X X X
X XX X
X X X
X X X
X X
X X XXX
X X XXX
X X X
X X X X X X X X X
X X X X X X X X X
X X X
X X X X X
PRESSURE MONITOR-NEW STATUS/ALARM X X X XX
Reheat Feedback
Reheat Command
Discharge Flow
AFMS Unocc Discharge Flow SP Discharge Temp Discharge Pressure
Zone Temperature SP Zone Temperature
AFMS Occ Discharge Flow SP
X X
X X X
D-4109 SA Unocc Hi SP X X X X X X D-4109 SA Unocc Lo SP X X X X X X
4C Zone Occupancy X X X X
FCU (RADIATOR) COMMAND
FCU (RADIATOR) COMMAND
X X
X X
X
4C Zone Unocc High SP 4C Zone Unocc Low SP 4C Zone Occ HiLimit SP
4C Zone Occ LoLimit SP 4C Zone Occupancy
X X X X X
X X X X X
X X X X X
X X X X X
C-WING 4TH FLOOR BALANCING NOTES
1. CONTRACTOR SHALL TEST FOR EACH ROOM IN PROJECT A FULL RANGE OF AIR FLOW RATES AND PRESSURES.
2. CONTRACTOR TO REFER TO MECHANICAL DRAWINGS, SCHEDULES AND CONTROL DRAWINGS FOR SPECIFIC EQUIPMENT REFERENCE
AND DETAILS
3. CONTRACTOR TO MAINTAIN REQUIREMENTS FOR ROOM PRESSURE RELATIONSHIPS WITH ADJOINING AREAS AS INDICATED BELOW.
WORK HVAC TAB AIR CHANGES WITH REQUIREMENTS BELOW:
3.1. C4109
PRESSURE= POSITIVE WITH RESPECT TO ADJOINING CORRIDOR C4161
4. ADJUST RETURN/EXHAUST VALUES TO MAINTAIN POSITIVE AND NEGATIVE PRESSURES.
5. ADJUST SUPPLY VALUES TO MAINTAIN POSITIVE AND NEGATIVE PRESSURES.
6. PROVIDE ADJUSTED VALUES OF FLOW RATES TO VA FOR REVIEW TO MINIMIZE IMPACT ON NON-PROJECT AREAS. SEE M101 FOR
LOCATIONS.
7. THE CONTRACTOR SHALL PROVIDE A FULLY FUNCTIONAL SYSTEM. ADDITIONAL EQUIPMENT AND COMPONENTS NOT SIZED HERE NEED TO BE PROVIDED PER MANUFACTURER RECOMMENDATIONS AND SUGGESTED INSTALLATION FOR THIS APPLICATION.
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
BALANCE AIRFLOWS BACK TO CFMS RECORDED PRIOR TO DEMOLITION.
DUCTWORK ARRANGEMENT OR DIFFUSER LOCATIONS AS WELL AS AIR BALANCE IN
THIS AREA NOT TESTED NOR CONFIRMED. CONTRACTOR TO TAKE AIR FLOW
READINGS ON SUPPLY AND RETURN AIR AND RE-BALANCE AGAINST AHU-124.
TYPICAL REHEAT CONTROL DIAGRAM2A
NO SCALE
TYPICAL VAV W/REHEAT CONTROL DIAGRAM2B
M
NO SCALE
CATH LAB VAV W/REHEAT CONTROL DIAGRAM2C
4C THERMOSTAT CONTROL SEQUENCE
GENERAL
SYSTEM CONSISTS OF A THERMOSTAT AND HOT WATER CONTROL VALVE(S): REHEAT AND/OR RADIATOR. SYSTEM HAS OCCUPANCY CONTROL. ZONE POINTS ARE LINKED AND CONTROLLED BY THE SUPERVISORY CONTROLLER.
2-WAY VALVE CONTROL
1. IF ZONE IS UNOCCUPIED, MODULATE 2-WAY HW CONTROL VALVE(S) TO MAINTAIN ROOM TEMPERATURE TO ZONE
UNOCC LOW SP (ADJ, INITIALLY 60 F).
2. IF ZONE IS OCCUPIED, MODULATE 2-WAY HW CONTROL VALVE(S) TO MAINTAIN ROOM TEMPERATURE TO ZONE
UNOCC LOW SP (ADJ, INITIALLY 70 F).
LOCAL TEMP SP
1. THERMOSTAT WILL ALLOW USER TO LOCALLY ADJUST ROOM TEMP SP BETWEEN THE BOUNDARIES OF ZONE OCC
HILIMT SP (ADJ, INITIALLY 74 F) AND ZONE OCC LOLIMIT SP (ADJ, INITIALLY 68 F)
LOSS OF POWER
1. CONTROL VALVES WILL REMAIN AT THEIR CURRENT SETTING DURING A LOSS OF ELECTRICAL POWER
2. THE C-WING PROJECT 607-19-106 PROVIDED CAPABILITY TO HAVE THE PERIMETER HEAT PIPING LOOP AND THE
REHEAT PIPING LOOP AS TWO SEPARATE CONTROLLED SYSTEMS, ADDITIONALLY THE PERIMETER LOCAL HEATER(S) CAN BE OFF (WHEN OA TEMP IS HIGHER) OR CAN BE CONTROLLED IN SEQUENCE WITH SINGLE SMART
THERMOSTAT.
CATH LAB C4109 CONTROL SEQUENCE
OCCUPIED/UNOCCUPIED MODE + FLOW
THESE UNITS HAVE OCCUPANCY CONTROL THAT IS CONTROLLED BY THE AHU-124 PRIMARY CONTROLLER'S
OCCUPIED/UNOCCUPIED MODE POINT.
DAMPER CONTROL + FLOW CONTROL OF D-4109-SA
1. DURING OCCUPIED MODE, DAMPER WILL MODULATED TO MAINTAIN 100% DISCHARGE FLOW TO OCC
DISCHARGE FLOW SP.
2. DURING UNOCCUPIED MODE, DAMPER WILL MODULATED TO MAINTAIN 50% DISCHARGE FLOW TO
UNOCC DISCHARGE FLOW SP.
3. VAV 4111 ALONG WITH EF -02 VAV-4110 TO OPERATE SO THAT AIR FLOW INTO, AND OUT OF THE CATH
LAB 4109 VIA DAMPER D-4109 - SA ARE REDUCED TO ABOUT 50% CAPACITY DURING OFF HOURS AND
SHOULD BE COMMANDED ON A TIME SCHEDULE BASIS.
TEMPERATURE CONTROL
1. MODULATE REHEAT COMMAND TO MAINTAIN ZONE TEMPERATURE TO ZONE TEMPERATURE SETPOINT.
TEST AND BALANCING NOTE
THE TAB CONTRACTOR WILL USE THE INDICTED FLOW RATES FOR INITIAL BALANCE. IN CASE THERE IS A
DEFICIENCY OF AIR FLOW RATES, THE MORE CRITICAL AREAS SHALL HAVE THE PRIORITY IN
COMPARISON WITH THE LESS-CRITICAL AREAS. THE FOLLOWING AREAS ARE DESIGNATE AS
LESS-CRITICAL AREAS.
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023
C-WING 4TH FLOOR BALANCING NOTES
1. CONTRACTOR SHALL TEST FOR EACH ROOM IN PROJECT A FULL RANGE OF AIR FLOW RATES AND PRESSURES.
2. CONTRACTOR TO REFER TO MECHANICAL DRAWINGS, SCHEDULES AND CONTROL DRAWINGS FOR SPECIFIC EQUIPMENT REFERENCE
AND DETAILS
3. CONTRACTOR TO MAINTAIN REQUIREMENTS FOR ROOM PRESSURE RELATIONSHIPS WITH ADJOINING AREAS AS INDICATED BELOW.
WORK HVAC TAB AIR CHANGES WITH REQUIREMENTS BELOW:
3.1. C4109
PRESSURE= POSITIVE WITH RESPECT TO ADJOINING CORRIDOR C4161
4. ADJUST RETURN/EXHAUST VALUES TO MAINTAIN POSITIVE AND NEGATIVE PRESSURES.
5. ADJUST SUPPLY VALUES TO MAINTAIN POSITIVE AND NEGATIVE PRESSURES.
6. PROVIDE ADJUSTED VALUES OF FLOW RATES TO VA FOR REVIEW TO MINIMIZE IMPACT ON NON-PROJECT AREAS. SEE M101 FOR
LOCATIONS.
7. THE CONTRACTOR SHALL PROVIDE A FULLY FUNCTIONAL SYSTEM. ADDITIONAL EQUIPMENT AND COMPONENTS NOT SIZED HERE NEED TO BE PROVIDED PER MANUFACTURER RECOMMENDATIONS AND SUGGESTED INSTALLATION FOR THIS APPLICATION.
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
BALANCE AIRFLOWS BACK TO CFMS RECORDED PRIOR TO DEMOLITION.
DUCTWORK ARRANGEMENT OR DIFFUSER LOCATIONS AS WELL AS AIR BALANCE IN
THIS AREA NOT TESTED NOR CONFIRMED. CONTRACTOR TO TAKE AIR FLOW
READINGS ON SUPPLY AND RETURN AIR AND RE-BALANCE AGAINST AHU-124.
TYPICAL REHEAT CONTROL DIAGRAM2A
NO SCALE
TYPICAL VAV W/REHEAT CONTROL DIAGRAM2B
4C THERMOSTAT CONTROL SEQUENCE
GENERAL
SYSTEM CONSISTS OF A THERMOSTAT AND HOT WATER CONTROL VALVE(S): REHEAT AND/OR RADIATOR. SYSTEM HAS OCCUPANCY CONTROL. ZONE POINTS ARE LINKED AND CONTROLLED BY THE SUPERVISORY CONTROLLER.
2-WAY VALVE CONTROL
1. IF ZONE IS UNOCCUPIED, MODULATE 2-WAY HW CONTROL VALVE(S) TO MAINTAIN ROOM TEMPERATURE TO ZONE
UNOCC LOW SP (ADJ, INITIALLY 60 F).
2. IF ZONE IS OCCUPIED, MODULATE 2-WAY HW CONTROL VALVE(S) TO MAINTAIN ROOM TEMPERATURE TO ZONE
UNOCC LOW SP (ADJ, INITIALLY 70 F).
LOCAL TEMP SP
1. THERMOSTAT WILL ALLOW USER TO LOCALLY ADJUST ROOM TEMP SP BETWEEN THE BOUNDARIES OF ZONE OCC
HILIMT SP (ADJ, INITIALLY 74 F) AND ZONE OCC LOLIMIT SP (ADJ, INITIALLY 68 F)
LOSS OF POWER
1. CONTROL VALVES WILL REMAIN AT THEIR CURRENT SETTING DURING A LOSS OF ELECTRICAL POWER
2. THE C-WING PROJECT 607-19-106 PROVIDED CAPABILITY TO HAVE THE PERIMETER HEAT PIPING LOOP AND THE
REHEAT PIPING LOOP AS TWO SEPARATE CONTROLLED SYSTEMS, ADDITIONALLY THE PERIMETER LOCAL HEATER(S) CAN BE OFF (WHEN OA TEMP IS HIGHER) OR CAN BE CONTROLLED IN SEQUENCE WITH SINGLE SMART
THERMOSTAT.
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023
DS
ELECTRICAL SYMBOLS - NEW
JS
MOUNTING HEIGHT SCHEDULE
DEVICE MOUNTING HEIGHT
SWITCHES 48-INCH TOP
RECEPTACLE AND TELECOMMUNICATION:
48-INCH TOP
IN JANITOR CLOSETS, EQUIPMENT
ROOM, STORAGE ROOM, SHOP
TOILETS AND UNFINISHED AREAS
RECEPTACLE AND TELECOMMUNICATION:
24-INCH BOTTOM
WEATHERPROOF (EXTERIOR)
RECEPTACLE AND TELECOMMUNICATION:
16-INCH BOTTOM
OTHER LOCATIONS
RECEPTACLE AND TELECOMMUNICATION:
BOTTOM 2-INCHES ABOVE BACKSPLASH
AT COUNTERS AND DESK
FIRE ALARM, HORNS AND VISUALS UNITS BOTTOM OF UNIT 80-INCHES ABOVE FINISHED
FLOOR
CLOCKS, SPEAKERS, ETC. TOP OF UNIT 2-INCHES BELOW CEILING OR
96-INCHES (WHICHEVER IS LOWER)
THERMOSTATS, STARTERS, SPEAKER
48-INCH TOPCONTROLS, FIRE ALARM MANUAL STATIONS,
WALL PHONES, ETC.
NOTES:
THE MOUNTING HEIGHT SCHEDULE IS INCLUDED TO ASSIST THE CONTRACTOR IN
ESTIMATING. HEIGHTS LISTED ARE ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED.
ALL DEVICE LOCATIONS SHALL BE COORDINATED WITH ARCHITECTURAL DETAILS AND
ELEVATIONS. EXACT HEIGHTS SHALL BE OBTAINED FROM THE VA COR.
RENOVATE FOR CATH LAB
POC: Aslam Husain
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
25% Schematic Design 06.29.2022 6.9.23
Project Number
Building Number
607-CSI-106
33 North LaSalle Street, Suite 3600 Chicago, IL 60602 Phone: 312.376.3100 POC: Thomas C. Jeziorski
50% Design Development 10.14.2022 65% Construction Documents 1.27.2023 95% Construction Documents 5.5.2023 100% Construction Documents 6.9.2023
COMMUNICATION SYMBOLS-NEW
SWITCHES
RECEPTACLES
FIRE ALARM SYSTEM -NEW
SECURITY SYSTEMS - NEW
LIGHTING -NEW
POWER
EXISTING ELECTRICAL SYMBOLS AND ABBR.
SHOWN ED100 SEE ET101 FOR ADDITIONAL
NURSE CALL SYSTEM
NOTE:
1. SEE SPECIFICATION SECTIONS 26 51 00 FOR ADDITIONAL INFORMATION REGARDING LIGHTING FIXTURE AND INSTALLATION REQUIREMENTS. PROVIDE OPTIONS AND ACCESSORIES REFERENCED BY THE COLUMN TITLED
"OPTIONS".
2. MANUFACTURERS AS SHOWN AS BASIS OF DESIGN , DESCRIPTIVE AND QUALITY STANDARD ONLY. NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION APPROVAL.CONTRACTOR SHALL MEET ALL REQUIREMENTS AND FEATURES INDICATED AND PROVIDE FOR APPROVAL BY ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED, INACCURATE OR DISCONTINUED PART NUMBERS. ACCEPTABLE MANUFACTURERS MUST MEET THE PHOTOMETRIC PERFORMANCE OF THE LISTE.CONTRACTOR TO PROVIDE PRODUCT OR UNIT.
3. FIXTURE TO BE PROVIDED WITH FAIL-SAFE SEALED RATED FOR WET LOCATIONS
4. NOT USED.
5. FOR ALL LIGHT FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION WILL RETURN TO THE SWITCHED/COMTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
6. CLEAN TROFFER AND LENS
7. XRAY ON SIGN TO BE PROVIDED WITH RELAYS FOR CONNECTION WITH PHILIPS EQUIPMENT REQUIREMENTS. SEE CANON DRAWINGS FOR MORE INFORMATION.
ABBREVIATIONS:
AR = AS REQUIRED EM = END MOUNT LD = LED DIMMING R = RECESS
CAB = CABINET
ES = EXPOSED STRUCTURE
OT = OTHER
RM = REMOTE
CL = CLEAR
ET = ELECTRONIC
P = PENDANT/CHAIN
S = SURFACE
DM = LED DIMMING 0-10V
F = FLUORESCENT
PL = PLASTER
ST = STANDARD
DR = LED DRIVER
LG = LAY-IN GRID
PS = PULSE START V = VARIES
DW = DRYWALL
Q = QUARTZ W = WALL MOUNTED
UNV = UNIVERSAL VARIES (120V/277V)
M = METAL
C = CONCRETE BEAM/SLAB
JUNO LIGHTING 2A-841-N-U-WH
B = BRICK/MASONRY
LED 4 IN UNIT 17 4000 80 120 R
PRIOR APPROVED EQUAL
4.125"F9 RECESSED ADJUSTABLE LED
DOWN LIGHT
LG COOPER LIGHTING HALO
NURSES CALL SCHEDULE
LIGHT FIXTURE SCHEDULE
FIXTURE LAMPS VOLT MOUNTCEILING FIXTURE FIXTURE SPECIFICATION AND ACCEPTABLE MANUFACTURERS
ID DESCRIPTION TYPE NO. DESCRIPTION WATTS K CRI TYPE DEPTH MANUFACTURER
F1-1
2' X 4' LED CEILING LIGHT
COOPER LIGHTING
LED 8 IN UNIT 48.6 3500 80 120-277 R 3.25"
F1-2
F1-3 LED 1 IN UNIT 55.4 80 120-277 3.25"
PRIOR APPROVED EQUAL
24FCZ2-50-UNV-L835-CP125-CD1-U
PRIOR…