Omega_Park_100P_Plans.pdf
PDF 5 MB Posted
- Attached to
- Omega Park CCUA Connection State and local contract opportunity
- Solicitation number
- 25/26-007
- Issued by
- Clay County, Miramar Beach CDP, Florida
About this file
This document is a comprehensive set of design and construction documents for the Omega Park CCUA (Clay County Utility Authority) Connection project located at 4317 County Road 218 in Middleburg, Florida. The project involves installing a new utility infrastructure system, including water and sewer connections, a private grinder lift station, electrical services, and associated site improvements at the Omega Park recreational facility. The 100% submittal package is dated 06/20/2025 and includes multiple technical disciplines such as civil, electrical, landscape, and utility plans, with detailed specifications and drawings covering everything from site conditions to utility details, electrical site plans, and landscape requirements.
The project is being undertaken by Clay County Parks and Recreation, with Chen Moore and Associates serving as the engineering design firm. The total project area involves utility connections across multiple baseball and softball fields, with specific work including the installation of approximately 190 linear feet of 8" PVC gravity main, 484 linear feet of 2" force main, a new 2,000-gallon grease trap, and associated electrical and site infrastructure. The documents indicate careful consideration of existing site conditions, tree preservation, utility separations, and coordination with local utility providers like Clay County Utility Authority, Clay Electric, and AT&T. The project appears to be fully funded and is part of a planned infrastructure improvement for the county park system, with detailed technical specifications ensuring compliance with local, state, and federal regulations.
View the file
Other files for this state and local contract opportunity
Show all 41
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCATION MAP
N.T.S
INDEX OF DRAWINGS
SHT # DWG # SHEET TITLE
01 C1.01 COVER
02 -03 C2.01 TO C2.02 GENERAL NOTES
04 C3.01 EXISTING CONDITIONS PLAN
05 C4.01 DEMOLITION PLAN
06 C5.01 UTILITY PLAN
07 - 08 C6.01 TO C6.02 UTILITY DETAILS
09 C7.01 PRIVATE GRINDER STATION DETAILS
10 E1.00 SITE PLAN
11 - 15 E1.01 TO E1.05 ELECTRICAL SPECIFICATIONS
16 E1.06 ELECTRICAL DETAILS
17 E1.07 PANEL SCHEDULES
18 L1.01 LANDSCAPE PLAN
19 L2.01 LANDSCAPE SCHEDULE & DETAILS
20 L3.01 LANDSCAPE SPECIFICATIONS
N
OMEGA PARK CCUA CONNECTION
OMEGA PARK, 4317 COUNTY ROAD 218 MIDDLEBURG, FL.
100% SUBMITTAL
DATE OF ISSUE: 06/20/2025
24-0543.00006
C1.01 01 20
DRAWING NUMBER
CLIENT PROJECT NUMBER
PROJECT NUMBER
Pl ot D at e:
/2 0/
:5 9:
A M
U se rn am e:
jh ub ba rd
L ay ou t N am e:
C
1.
Fo ld er P at h:
V Pr oj ec ts \2
4\
-0
3.
- o m eg a pa rk c cu a co nn ec tio n\ De sig n\
CA
D\ Sh ee ts
F ile na m e:
4-
.0
C ov er S he et .d w g
OF
501 Riverside Avenue, Suite 501 Jacksonville, FL 32202
904.398.8636 www.chenmoore.com
REGISTRATION
CLAY COUNTY PARKS AND RECREATION
477 HOUSTON STREET
GREEN COVE SPRINGS, FL 32043
Phone: (904)-284-2102
CLAY COUNTY COUNCIL
JOHN SGROMOLO DISTRICT 1
ALEXANDRA COMPERE DISTRICT 2
JIM RENNINGER DISTRICT 3
BETSY CONDON, CHAIR DISTRICT 4
KRISTEN BURKE, VICE-CHAIR DISTRICT 5
JUSTIN PIERCE DIRECTOR OF PARKS AND
RECREATION
PROJECT
LOCATION
COUNTY
CLAY
COUNTY
CLAY
DOCTORS LAKE
COUNTY
CLAY
COUNTY
CLAY
W A
LL
A
BY
A
VE
SECTION 31, TOWNSHIP 04S, RANGE 26E
JENNIFER L. SMITH, PE
LICENSE NO. 72232
DATE: __________
THIS SEAL IS ONLY VALID ON PRINTED
COPIES THAT ARE DATED WITH THE
LICENSEE'S ORIGINAL HAND SIGNATURE.
SCANNED OR ELECTRONIC COPIES ARE NOT
CONSIDERED SIGNED AND SEALED.
JEN
NIFER L. SMITH
No. 72232
L I C E NS E
F L O R I DA
P R O F E S S I O N A L E N G I N E
E RSTATE OF
02/06/25
OMEGA PARK
CCUA
CONNECTION
OMEGA PARK, 4317
COUNTY ROAD 218
MIDDLEBURG, FL.
06/20/2025
MB
JH
JS
GENERAL NOTES
C2.01
02 20100% SUBMITTAL
ABBREVIATIONS
(00.0) SOFT ELEVATION
(00.00) HARD ELEVATION
ARV AIR RELEASE VALVE
(C) CALCULATED
CMA CHEN MOORE AND ASSOCIATES
CONC. CONCRETE
(D) DEED
DI DUCTILE IRON
DIP DUCTILE IRON PIPE
DIPS DUCTILE IRON PIPE SIZE
EOP EDGE OF PAVEMENT
EX. EXISTING
EXIST. EXISTING
ERCP ELLIPTICAL REINFORCED CONCRETE PIPE
F.A.C. FLORIDA ADMINISTRATIVE CODE
FDEP FLORIDA DEPARTMENT OF ENVIRONMENTAL PROTECTION
FDOT FLORIDA DEPARTMENT OF TRANSPORTATION
FPS FEET PER SECOND
G.V. GATE VALVE
HDPE HIGH DENSITY POLYETHYLENE
ID. IDENTIFICATION
INV INVERT
I.P. IRON PIPE
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
OSY OUTSIDE STEM AND YOKE
(M) MEASURED
O.R.B. OFFICIAL RECORDS BOOK
(P) PLAT
P.B. PLAT BOOK
PSI POUNDS PER SQUARE INCH
PG PAGE
PVC POLYVINYL CHLORIDE
(R) RECORD
RCP REINFORCED CONCRETE PIPE
RCWM REUSE WATER MAIN
RE# REAL ESTATE NUMBER
RPZ REDUCED PRESSURE ZONE
R/W RIGHT OF WAY
SJRWMD ST. JOHNS RIVER WATER MANAGEMENT DISTRICT
SS STAINLESS STEEL
STA. STATION
UNK UNKNOWN
W/ WITH
LEGEND
PROPOSED CONCRETE
PROPOSED ASPHALT
REMOVE MATERIAL FROM AREA
REMOVE ITEM
DRAWING NUMBER
DRAWING TITLE
CHECKED BY
DRAWN BY
DESIGNED BY
DATE OF ISSUE
REVISIONS
VERIFY SCALES
CLIENT PROJECT NUMBER
PROJECT NUMBER
PROJECT INFORMATION
CLIENT
REGISTRATION
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY
1"0
Pl ot
D at e:
/2 0/
0:
:2
AM
U se rn am e:
jh ub ba rd
L ay ou t N am e:
C
2.
Fo ld er P at h:
V
Pr oj ec ts
\2
4\
-0
3.
- o m eg a pa rk c cu a co nn ec tio n\
De sig n\
CA
D\ Sh ee ts
F ile na m e:
4-
.0
G en er al N ot es
.d w g
OF
501 Riverside Avenue, Suite 501 Jacksonville, FL 32207
904.398.8636 www.chenmoore.com
JENNIFER L. SMITH, PE
LICENSE NO. 72232
DATE: __________
THIS SEAL IS ONLY VALID ON PRINTED
COPIES THAT ARE DATED WITH THE
LICENSEE'S ORIGINAL HAND SIGNATURE.
SCANNED OR ELECTRONIC COPIES ARE NOT
CONSIDERED SIGNED AND SEALED.
JEN
NIFER L. SMITH
No. 72232
L I C E NS E
F L O R I DA
P R O F E S S I O N A L E N G I N E
E RSTATE OF
06/20/2025
RIGHT-OF-WAY LINE
CENTER LINE
EXISTING TOP OF BANK
EXISTING FORCE MAIN
EXISTING ASPHALT
EXISTING CONCRETE
EXISTING OVERHEAD ELECTRIC
EXISTING CHAIN-LINK FENCE
W
EXISTING ELEVATION
EXISTING UTILITY POLE
EXISTING GUY WIRE
EXISTING GOAL POST
EXISTING SINGLE POST SIGN
EXISTING WATER METER
EXISTING TREES
EXISTING WATER MAIN
EXISTING STORM DRAIN
EXISTING FLAG POLE
EXISTING LIGHT POLE
EXISTING BURIED ELECTRIC
EXISTING GAS
PROPOSED WATER METER
PROPOSED BACKFLOW PREVENTOR
W
PROPOSED 2" WATER SERVICE
PROPOSED SANITARY SEWER
PROPOSED 2" FORCE MAIN
PROPOSED CLEANOUT
S
FM
W
90.0
EXISTING CLEANOUTCO
GENERAL NOTES
1. GENERAL NOTES ON THE PROJECT PLANS AND DRAWINGS ARE SOLELY TO AID AND ASSIST THE
CONTRACTOR WITH THE FIELD OPERATIONS FOR THE PROJECT. SAID GENERAL NOTES MAY NOT
FULLY DESCRIBE ALL OF THE REQUIREMENTS FOR AN ITEM. THEREFORE, THE CONTRACTOR SHALL
READ AND VERIFY THE CONTRACT DOCUMENTS, INCLUDING BUT NOT LIMITED TO THE PLANS,
SPECIFICATIONS, GENERAL TERMS AND CONDITIONS, AND THE SUPPLEMENTAL TERMS AND
CONDITIONS, TO FULLY UNDERSTAND AND COMPLY WITH ALL THE REQUIREMENTS THEREIN.
2. THE INFORMATION PROVIDED ON THE PLANS ARE BASED ON THE BEST AVAILABLE INFORMATION
AND SHOULD BE CONSIDERED APPROXIMATE. CONTRACTOR SHALL BE RESPONSIBLE FOR
FAMILIARIZING HIMSELF WITH CURRENT SITE CONDITIONS, AND SHALL REPORT DISCREPANCIES TO
THE ENGINEER PRIOR TO STARTING WORK.
3. CONTRACTOR WILL SECURE WORK SITE TO PROTECT THE PUBLIC HEALTH AND WELFARE.
4. ALL WORK WILL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE FDOT DESIGN STANDARDS, MUTCD AND CLAY COUNTY.
5. CONTRACTOR TO REPAIR ALL DAMAGES INCURRED AS A RESULT OF CONSTRUCTION ACTIVITIES SUCH AS BUT NOT LIMITED TO SIDEWALK, PAVEMENT, LANDSCAPING, FENCING, ETC. NO ADDITIONAL
COMPENSATION WILL BE GIVEN.
6. CONTRACTOR SHALL CONTROL/REMOVE DUST WITH A STREET SWEEPER USING WATER OR OTHER
EQUIPMENT CAPABLE OF CONTROLLING DUST.
7. ALL PUBLIC LAND CORNERS AND MONUMENTS WITHIN THE LIMITS OF CONSTRUCTION SHALL BE PROTECTED BY THE CONTRACTOR AS FOLLOWS: CORNERS AND MONUMENTS IN CONFLICT WITH THE
WORK AND IN DANGER OF BEING DAMAGED, DESTROYED OR COVERED SHALL BE PROPERLY
REFERENCED BY A FLORIDA PROFESSIONAL SURVEYOR AND MAPPER IN ACCORDANCE WITH THE
MINIMUM TECHNICAL STANDARDS OF THE FLORIDA BOARD OF PROFESSIONAL SURVEYORS AND
MAPPERS. PRIOR TO BEGINNING WORK AT THE SITE, THE CONTRACTOR SHALL RETAIN THE
SURVEYOR TO REFERENCE, AND RESTORE UPON COMPLETION OF THE WORK, ALL SUCH CORNERS
AND MONUMENTS AND SHALL FURNISH THE ENGINEER A SIGNED AND SEALED COPY OF THE
SURVEYOR'S REFERENCE DRAWING. COST OF THIS WORK SHALL BE DEEMED INCIDENTAL TO THE
TOTAL PROJECT COST.
8. THE CONTRACTOR SHALL NOTIFY THE OWNER IN WRITING AT LEAST 48 HOURS PRIOR TO
COMMENCEMENT OF CONSTRUCTION.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A PROPER STAGING AREA.
10.THE CONTRACTOR SHALL BE RESPONSIBLE TO SATISFY ALL REQUIREMENTS OF ANY REGULATORY AGENCY PERMITS IN REGARDS TO CONSTRUCTION ACTIVITIES AND RELATED CONDITIONS PRIOR TO
THE START OF CONSTRUCTION.
11.THE CONTRACTOR SHALL MAINTAIN PEDESTRIAN AND VEHICULAR ACCESS TO ALL ADJACENT
PROPERTIES AT ALL TIMES UNLESS OTHERWISE APPROVED BY THE COUNTY.
12.THE CONTRACTOR SHALL NOT ENCROACH INTO PRIVATE PROPERTY WITH PERSONNEL, MATERIAL OR
EQUIPMENT.
13.THE CONTRACTOR SHALL DISPOSE OF ALL EXCESS EXCAVATED MATERIAL AND DEBRIS TO AN
APPROVED SITE IN A LEGAL MANNER AT NO ADDITIONAL COST TO THE PROJECT.
14.THE CONTRACTOR SHALL VERIFY, PHOTOGRAPH AND INVENTORY THE EXACT LOCATION OF ALL
EXISTING TREES, STRUCTURES, PAVEMENT OR OTHER FEATURES. ANY EXISTING STRUCTURE,
PAVEMENT, TREE OR OTHER EXISTING FEATURE, WHICH IS IN CONFLICT OR DAMAGED, EXPOSED OR
IN ANY WAY DISTURBED BY CONSTRUCTION PERFORMED UNDER THE CONTRACT, SHALL BE
RESTORED PROMPTLY TO IT'S ORIGINAL CONDITION AT NO ADDITIONAL COST TO THE PROJECT.
15.THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING IMMEDIATELY OF ANY CONFLICT
ARISING DURING CONSTRUCTION FOR ANY IMPROVEMENTS SHOWN ON THESE DRAWINGS.
16.ALL CONSTRUCTION LAYOUT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
17.ALL EXISTING MANHOLE TOPS, CATCH BASIN GRATES, VALVE BOX TOPS, WATER METER TOPS CLEANOUTS, AND OTHER UTILITY TOPS WITHIN THE PROJECT AREA SHALL BE MODIFIED TO MATCH
FINISHED GRADE BY CONTRACTOR. THE COST OF ADJUSTMENT SHALL BE IDENTICAL TO THE
ASSOCIATED PAY ITEM AT NO ADDITIONAL COST TO THE PROJECT. PLANS MAY NOT SHOW ALL
LOCATIONS NECESSARY FOR ADJUSTMENTS. CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL
NECESSARY UTILITY TOPS TO BE ADJUSTED.
18.CONTRACTOR TO RESTORE ALL SODDED AREAS OF THE PROJECT WHICH ARE DISTURBED DUE TO
CONSTRUCTION ACTIVITIES. RESTORED SOD SHALL MATCH EXISTING SOD UNLESS OTHERWISE
INDICATED.
19.ALL PROPOSED WORK SHALL BE PERFORMED WITHIN THE PROJECT PROPERTY LIMITS AND THE
LIMITS OF THE EXISTING STATE/LOCAL RIGHT-OF-WAY, AND ALL IMPROVEMENTS SHALL BE
CONSTRUCTED AND INSTALLED WITHIN SAID LIMITS.
20.THE CONTRACTOR SHALL ASSIST THE COUNTY WITH THE HANDLING OF PUBLIC INFORMATION MATERIALS, INCLUDING CITIZEN NOTIFICATION LETTERS AND PROJECT CONSTRUCTION SIGNS, PRIOR TO THE START OF EACH SIGNIFICANT PHASE OF CONSTRUCTION. COST OF THIS WORK SHALL BE
INCLUDED IN THE MAINTENANCE OF TRAFFIC BID ITEM.
ENVIRONMENTAL NOTES:
1. THE PROPOSED PROJECT IMPROVEMENTS ARE NOT LOCATED WITHIN CLAY COUNTY DELINEATED ARCHAEOLOGICAL CONSERVATION AREAS. NO IMPACTS TO EXISTING HISTORICAL AND CULTURAL RESOURCES ARE EXPECTED AS A RESULT OF THE PROPOSED PROJECT. IF ANY HISTORICAL AND
CULTURAL RESOURCES ARE FOUND DURING CONSTRUCTION, CONTRACTOR SHALL IMMEDIATELY
NOTIFY THE COUNTY.
2. ANY MATERIAL TO BE STOCKPILED FOR PERIODS GREATER THAN 24 HOURS SHALL BE PROTECTED
BY APPROPRIATE EROSION CONTROL DEVICES.
3. NO STAGING OR OTHER ACTIVITIES FOR THIS PROJECT SHOULD OCCUR WITHIN THE DRIPLINE OF
EXISTING TREES.
4. A CERTIFIED ARBORIST CERTIFIED BY THE INTERNATIONAL SOCIETY OF ARBORICULTURE SHALL BE
PRESENT ON SITE TO DIRECT ALL ROOT PRUNING AND/OR CANOPY TRIMMING ACTIVITIES IF
NECESSARY.
5. TREE PROTECTION SHOULD BE INSTALLED AROUND TREES TO REMAIN LOCATED ADJACENT TO
CONSTRUCTION ACTIVITIES.
6. THE CONTRACTOR SHALL NOT REMOVE, RELOCATE OR PRUNE ANY TREES WITHOUT PRIOR
APPROVAL FROM THE COUNTY. THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS FROM
CLAY COUNTY PRIOR TO ANY TREE REMOVAL/RELOCATION.
7. CONTRACTOR SHALL KEEP NEW AND EXISTING INLETS CLEAN OF MILLING MATERIALS AND DEBRIS.
INLETS LOCATED NEAR CONSTRUCTION ACTIVITIES SHOULD BE PROTECTED BY APPROPRIATE
EROSION CONTROL DEVICES.
8. ALL CONSTRUCTION AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH THE LATEST
REQUIREMENTS OF CLAY COUNTY, FDOT, AND ALL OTHER APPLICABLE LOCAL, STATE AND NATIONAL
CODES.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT ALL CONSTRUCTION SHALL BE DONE IN A SAFE MANNER AND IN STRICT COMPLIANCE WITH ALL THE REQUIREMENTS OF FEDERAL OCCUPATIONAL SAFETY AND HEALTH ACT OF 1970, AND ALL STATE AND LOCAL SAFETY AND HEALTH
REGULATIONS.
PRE-CONSTRUCTION RESPONSIBILITIES:
1. PRIOR TO THE COMMENCEMENT OF THE CONSTRUCTION AND THE RECEIPT OF THE "NOTICE TO
PROCEED", THE CONTRACTOR SHALL CONTACT THE OWNER AND ARRANGE A PRE-CONSTRUCTION
CONFERENCE TO INCLUDE THE ENGINEER OF RECORD. THE CONTRACTOR SHALL SUBMIT A
CONSTRUCTION SCHEDULE AND BE PREPARED TO DISCUSS ANY CONCERNS OR COORDINATION
EFFORTS AND REQUIREMENTS WITH THE PARTIES INVOLVED.
2. THE CONTRACTOR SHALL OBTAIN A SUNSHINE 811 LOCATE TICKET, AT LEAST TWO (2) FULL BUSINESS DAYS PRIOR TO BEGINNING ANY EXCAVATION. CONTACT 811, WWW.SUNSHINE811.COM
3. CONTRACTOR SHALL PREPARE A STORM WATER POLLUTION PREVENTION PLAN ACCORDING TO THE LATEST FDOT SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION, SECTION 104, AND CLAY
COUNTY. CONTRACTOR SHALL IMPLEMENT THE PLAN PRIOR AND DURING CONSTRUCTION AT NO
ADDITIONAL COST TO THE OWNER.
PROJECT RECORD DOCUMENTS:
1. DURING THE DAILY PROGRESS OF THE JOB THE CONTRACTOR SHALL RECORD THE EXACT LOCATION, LENGTH, AND ELEVATION OF ALL PROPOSED IMPROVEMENTS ON HIS SET OF CONSTRUCTION
DRAWINGS.
2. UPON COMPLETION OF CONSTRUCTION AND PRIOR TO FINAL PAYMENT, THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER ONE COMPLETE SET OF ALL "AS BUILT" CONSTRUCTION CHANGES AND DIMENSIONS, LOCATIONS AND ELEVATIONS OF ALL IMPROVEMENTS AND IN ACCORDANCE WITH THE
"SURVEY WORK" SECTION OF THE "SPECIFICATIONS AND CONTRACT DOCUMENTS" FOR THIS
PROJECT.
3. ALL "AS-BUILT" INFORMATION AND ELEVATIONS SHALL BE CERTIFIED BY A FLORIDA PROFESSIONAL
SURVEYOR AND MAPPER AND SHALL BE PROVIDED IN AUTOCAD AND PDF FORMAT.
UTILITIES:
1. LOCATION AND SIZES OF EXISTING UTILITIES ARE INDICATED IN THE PLANS BASED ON THE INFORMATION AVAILABLE AT THE TIME INCLUDING SURVEYED INFORMATION AND UTILITY RECORDS OBTAINED FROM UTILITY PROVIDERS; HOWEVER, THIS INFORMATION IS NOT GUARANTEED. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE LOCATION, CHARACTER, AND DEPTH OF
ALL EXISTING UTILITIES.
2. A MINIMUM OF TWO (2) TWO FULL BUSINESS DAYS PRIOR TO DIGGING, THE CONTRACTOR SHALL CALL
“SUNSHINE STATE ONE” AT 811 TO REQUEST UTILITY LOCATIONS BEFORE BEGINNING ANY
CONSTRUCTION ACTIVITIES.
3. EXISTING UTILITIES SHALL BE MAINTAINED IN SERVICE DURING CONSTRUCTION UNLESS OTHERWISE APPROVED BY THE UTILITY OWNER. ALL EXISTING UTILITIES ARE TO REMAIN UNLESS OTHERWISE
NOTED.
4. IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY TO VERTICALLY AND HORIZONTALLY PROTECT ANY AND ALL EXISTING UTILITIES ON THIS PROJECT. ANY DAMAGE TO SUCH UTILITIES SHOWN OR NOT SHOWN ON THE PLANS SHALL BE IMMEDIATELY REPORTED TO THE UTILITY OWNER.
THE OWNER RESERVES THE RIGHT TO REMEDY SUCH DAMAGE BY ORDERING OUTSIDE PARTIES TO
MAKE SUCH REPAIRS AT THE EXPENSE TO THE CONTRACTOR.
5. CONTRACTOR IS RESPONSIBLE FOR REMOVING ALL UTILITY MARKINGS ONCE THE WORK IS
COMPLETED. CONTRACTOR SHALL USE SPECIAL CARE WHEN REMOVING THE UTILITY MARKINGS. THE REMOVAL METHOD NEEDS TO BE SUCH THAT IT DOES NOT DAMAGE THE SURFACES OF THE EXISTING WORK ALREADY IN PLACE. IF WATER-BLASTING OLDER ASPHALT PAVEMENT, CARE NEEDS TO BE TAKEN TO NOT DISCOLOR THE ASPHALT OR POLISH THE AGGREGATE. IF THE REMOVALS ARE ON
OLDER CONCRETE SURFACES, THE ENTIRE SURFACE OF A PANEL OR SECTION NEEDS TO BE
BLASTED TO SHOW UNIFORM COLOR THROUGHOUT THAT SAME PANEL OR SECTION. IN ANY CASE
(ASPHALT OR CONCRETE SURFACE), THE METHOD NEEDS TO BE SUCH THAT A SLICK SURFACE IS NOT LEFT BEHIND. FINAL PAYMENT TO THE CONTRACTOR MAY BE WITHHELD UNTIL THE UTILITY
MARKS ARE PROPERLY REMOVED.
6. UTILITY OWNERS
AT&T (561) 683-2729
CLAY COUNTY UTILITY AUTHORITY (904) 272-5999
CLAY ELECTRIC ORANGE PARK DISTRICT (800) 778-9140
COMCAST CABLE COMMUNICATIONS (800) 778-9140
SUNSHINE ONE CALL TICKET NUMBER 136302904
ADDITIONAL GENERAL NOTES
1. THE CONTRACTOR SHALL NOTIFY THE COUNTY IN ADVANCE OF MAKING ANY CONNECTION TO AN
ACTIVE PIPELINE OR UTILITY SYSTEM.
2. ALL ELEVATIONS SHOWN ON THE CONSTRUCTION DRAWINGS ARE BASED ON THE NORTH AMERICAN
VERTICAL DATUM ( NAVD 88).
3. ALL DEVIATIONS FROM PLANS ARE TO BE APPROVED IN WRITING PRIOR TO CONSTRUCTION AND FOR
ALL INSPECTIONS AND TESTING.
4. THE COUNTY AND ENGINEER MUST BE GIVEN A MINIMUM 48 HOURS NOTICE FOR ALL INSPECTIONS
UNLESS OTHERWISE AGREED UPON.
5. THE EXISTING ELEVATIONS SHOWN HEREIN ARE FOR THE PURPOSE OF INDICATING THE GROUND ELEVATION ONLY AT THE POSITION SHOWN AND IN NO WAY SHOULD INDICATE ELEVATION AT ANY
OTHER POINT OTHER THAN THAT SHOWN.
6. BOUNDARY AND TOPOGRAPHIC INFORMATION SHOWN ON THE PLANS ARE TAKEN FROM SURVEY
INFORMATION PREPARED BY SAM SURVEYORS, DATED 5/03/23.
7. ALL WATER BOX, COMMUNICATION BOX, CABLE TV BOX, UTILITY BOX/COVER ETC, DAMAGED DURING CONSTRUCTION OF PROPOSED IMPROVEMENTS SHALL BE REPLACED WITH IDENTICAL OR BETTER TO
UTILITY OWNER SATISFACTION AT NO ADDITIONAL COST.
8. THE WORDS 'NEW', 'PROPOSED', 'INSTALL', 'PROVIDE', OR WORDS WITH SIMILAR MEANING, ON ANY
PART OF THESE CONSTRUCTION DOCUMENTS, SHALL BE INTERPRETED, UNLESS OTHERWISE
SPECIFICALLY STATED, TO MEAN 'FURNISHING AND INSTALL COMPLETE IN PLACE AND READY FOR
SERVICE'.
9. THESE CONSTRUCTION DOCUMENTS ARE COMPLEMENTARY. WORK DEPICTED UNDER A PARTICULAR DISCIPLINE MAY TRIGGER WORK UNDER A DIFFERENT DISCIPLINE. SUCH WORK REQUIRED FOR THE INTENDED AND PROPER FUNCTION OF THE IMPROVEMENTS, SHALL BE CONSIDERED INCIDENTAL AND PART OF THE CONTRACTOR'S BID PRICE. NO ADDITIONAL PAYMENT WILL BE MADE FOR SUCH ITEMS.
10.THE LOCATION AND SIZE OF ALL EXISTING UTILITIES SHOWN ON THESE DRAWINGS ARE
APPROXIMATE, ADDITIONAL UTILITIES MAY EXIST WHICH ARE NOT SHOWN ON THESE DRAWINGS. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR THE LOCATION OF ALL EXISTING UTILITIES. THE
CONTRACTOR SHALL VERIFY ALL UTILITIES BY ELECTRONIC METHODS AND BY HAND EXCAVATION IN
COORDINATION WITH ALL UTILITY COMPANIES, PRIOR TO BEGINNING ANY CONSTRUCTION
OPERATION, ANY AND ALL CONFLICTS OF EXISTING UTILITIES WITH PROPOSED IMPROVEMENTS MUST
BE RESOLVED BY THE ENGINEER AND THE OWNER. THIS WORK BY THE CONTRACTOR SHALL BE
CONSIDERED INCIDENTAL TO THE CONTRACT AND NO ADDITIONAL COMPENSATION SHALL BE
ALLOWED.
11.EXISTING GRADES WERE TAKEN FROM THE BEST AVAILABLE DATA AND MAY NOT ACCURATELY
REFLECT PRESENT CONDITIONS. CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING
THEMSELVES WITH CURRENT SITE CONDITIONS, AND SHALL REPORT ANY DISCREPANCIES TO THE
ENGINEER PRIOR TO STARTING WORK.
12.THE CONTRACTOR SHALL PREPARE AND SUBMIT SHOP DRAWINGS FOR ALL ITEMS LISTED IN
PROJECT SPECIFICATION.
13.UNDER NO CIRCUMSTANCES SHALL THE CONTRACTOR LEAVE EXCAVATED TRENCHES, OR PORTIONS OF WORK, EXPOSED OR OPEN AT THE END OF THE WORKING DAY, WEEKENDS, HOLIDAYS OR OTHER TIMES. WHEN THE CONTRACTOR IS NOT WORKING, UNLESS OTHERWISE DETERMINED, ANY TRENCH
SHALL BE COVERED, FIRMLY SECURED AND MARKED ACCORDINGLY FOR PEDESTRIAN TRAFFIC.
14.CAST IRON PRODUCTS: HEAVY DUTY CLASSIFICATION SUITABLE FOR HIGHWAY TRAFFIC LOADS, OR
16,000 LB. WHEEL LOADS.
15.STEEL GRATING AND COVERS: TRAFFIC CLASSIFICATION H-20 AASHTO H20: 16,000 LBS OVER 8" X 20"
AREA.
16.ALL STRUCTURES MUST BE CAPABLE OF SUSTAINING HEAVY TRAFFIC LOADS.
17.EXCAVATED OR OTHER MATERIAL STORED ADJACENT TO OR PARTIALLY UPON A ROADWAY
PAVEMENT SHALL BE ADEQUATELY MARKED FOR TRAFFIC SAFETY AT ALL TIMES.
18.TEMPORARY PATCH MATERIAL MUST BE ON THE JOB SITE WHENEVER PAVEMENT IS CUT, OR THE
INSPECTOR WILL SHUT THE JOB DOWN.
19.CONTRACTOR SHALL NOTIFY LAW ENFORCEMENT AND FIRE PROTECTION SERVICES TWENTY-FOUR
(24) HOURS IN ADVANCE OF THE DETOUR IN ACCORDANCE WITH SECTION 336.048 OF FLORIDA
STATUTES.
DEMOLITION NOTES
1. CONDUCT DEMOLITION OPERATIONS AND REMOVE DEBRIS TO ENSURE MINIMUM INTERFERENCE WITH
ROADS, STREETS, WALKS, AND OTHER ADJACENT OCCUPIED AND USED FACILITIES.
2. DO NOT CLOSE OR OBSTRUCT STREETS, WALKS, OR OTHER ADJACENT OCCUPIED OR IN-USE
FACILITIES WITHOUT PERMISSION FROM OWNER, AND AUTHORITIES HAVING JURISDICTION. PROVIDE
ALTERNATE ROUTES AROUND CLOSED OR OBSTRUCTED TRAFFIC WAYS AS REQUIRED BY
GOVERNING REGULATIONS.
3. CONDUCT DEMOLITION OPERATIONS TO PREVENT INJURY TO PEOPLE AND DAMAGE TO ADJACENT BUILDINGS AND FACILITIES TO REMAIN. ENSURE SAFE PASSAGE OF PEOPLE AROUND DEMOLITION
AREA.
4. ERECT TEMPORARY PROTECTION, SUCH AS WALKS, FENCES, BARRIERS, RAILINGS, ETC. WHERE
REQUIRED BY AUTHORITIES HAVING JURISDICTION.
5. PROTECT EXISTING SITE IMPROVEMENTS, APPURTENANCES, AND LANDSCAPING TO REMAIN.
6. ADJACENT IMPROVEMENTS SHALL BE CLEANED OF DUST, DIRT, AND DEBRIS CAUSED BY DEMOLITION OPERATIONS. RETURN ADJACENT AREAS TO CONDITION EXISTING BEFORE START OF DEMOLITION.
7. FOR SELECTIVE DEMOLITION, USE CUTTING METHODS LEAST LIKELY TO DAMAGE CONSTRUCTION TO REMAIN OR ADJOINING CONSTRUCTION. TO MINIMIZE DISTURBANCE OF ADJACENT SURFACES, USE
HAND OR SMALL POWER TOOLS DESIGNED FOR SAWING OR GRINDING, NOT HAMMERING OR
CHOPPING. TEMPORARILY COVER OPENINGS TO REMAIN.
8. DEMOLISH CONCRETE IN SMALL SECTIONS. CUT CONCRETE AT JUNCTURES WITH CONSTRUCTION TO
REMAIN, USING POWER-DRIVEN MASONRY SAW OR HAND TOOLS; DO NOT USE POWER-DRIVEN
IMPACT TOOLS.
9. INFORMATION SHOWN ON THE DRAWINGS AS TO THE LOCATION OF EXISTING UTILITIES HAS BEEN
PREPARED FROM THE MOST RELIABLE DATA AVAILABLE TO THE ENGINEER; HOWEVER, THIS
INFORMATION IS NOT GUARANTEED. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
DETERMINE THE LOCATION, CHARACTER, AND DEPTH OF ALL EXISTING UTILITIES. THE CONTRACTOR
SHALL ASSIST THE UTILITY COMPANIES, BY EVERY MEANS POSSIBLE, TO DETERMINE SAID
LOCATIONS AND THE LOCATIONS OF RECENT ADDITIONS TO THE SYSTEMS NOT SHOWN.
10.REMOVAL, DEMOLITION, HAULING, AND DISPOSAL SHALL COMPLY WITH REGULATIONS BY F.D.E.P., E.P.A., AND ANY OTHER AUTHORITY HAVING JURISDICTION.
11.ALL EXISTING UTILITY MH COVERS, ELECTRICAL BOXES, METER BOXES, METERS, DRAINAGE STRUCTURES, ETC. WITHIN PROPOSED AREAS OF IMPROVEMENTS SHALL BE ADJUSTED TO GRADE
ELEVATION, UNLESS OTHERWISE NOTED.
12.ALL EXISTING STREET LIGHTING WILL REMAIN IN PLACE AND REMAIN IN SERVICE DURING
CONSTRUCTION OPERATIONS. CONTRACTOR SHALL USE CARE TO ENSURE EXISTING CONDUIT,
PULLBOXES, AND CONTROL ARE NOT DAMAGED DURING DEMOLITION OPERATIONS.
EARTHWORK NOTES
1. THE CONTRACTOR'S BID FOR EARTHWORK SHALL INCLUDE THE EXCAVATION, REMOVAL AND
DISPOSAL OF ALL MATERIALS, OF WHATEVER CHARACTER, WITHIN THE LIMITS OF CONSTRUCTION.
2. ALL TOPSOIL THAT IS SUITABLE FOR LANDSCAPING OR SODDING OPERATIONS MAY BE STOCKPILED
NEARBY FOR SUCH USE IF APPROVED BY THE COUNTY.
3. WHERE MUCK, ROCK, CLAY, OR OTHER MATERIAL WITHIN THE LIMITS OF CONSTRUCTION IS UNSUITABLE IN ITS ORIGINAL POSITION THE CONTRACTOR SHALL EXCAVATE SUCH MATERIAL IN ITS ENTIRETY AND BACKFILL WITH SUITABLE MATERIAL WHICH SHALL BE COMPACTED IN PLACE TO
CONFORM TO THE REQUIRED GRADES AND SECTIONS AS SHOWN ON THE PLANS.
4. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE UNSUITABLE MATERIAL PRESENT ON-SITE
AND INCLUDE THE REMOVAL AND REPLACEMENT OF SAME IN HIS BID PRICE.
5. THE CONTRACTOR SHALL MAKE HIS OWN ESTIMATE ON THE VOLUME OF MATERIAL ACTUALLY
REQUIRED TO OBTAIN THE CROSS SECTIONS OR GRADES AS SHOWN ON THE PLANS.
6. THE CONTRACTOR SHALL REMOVE ALL MUCK, YIELDING MATERIAL ROOTS, VEGETATION AND OTHER
DEGRADABLE MATERIAL IN ITS ENTIRETY, WITHIN THE PAVEMENT UNITS AND BELOW ALL
STRUCTURES AND UTILITIES TO FULL EXCAVATED TRENCH WIDTH. SAID MATERIAL SHALL BE
REPLACED WITH CLEAN ORGANIC FREE MATERIAL WITH ROCKS SMALLER THAN ONE INCH IN
DIAMETER COMPACTED TO NOT LESS THAN 98% MAXIMUM DENSITY AT OPTIMUM MOISTURE. AASHTO
T-180 METHOD "D" WITH MAXIMUM LIFTS OF TWELVE INCHES COMPACTED THICKNESS.
7. TRENCH BACKFILL AND COMPACTION SHALL FOLLOW THE CONTRACT SPECIFICATIONS.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING APPROPRIATE SAFETY PRECAUTIONS DURING EXCAVATION AND TRENCHING OPERATIONS AS REQUIRED BY THE "TRENCH SAFETY ACT".
9. THIS WORK SHALL INCLUDE THE EXCAVATION OF WHATEVER SUBSTANCES THAT SHALL BE
ENCOUNTERED TO THE DEPTHS AS SHOWN ON THE PLANS. EXCAVATED MATERIALS NOT REQUIRED FOR FILL OR BACKFILL SHALL BE REMOVED FROM THE WORK SITE AS DIRECTED BY THE ENGINEER AND SHALL BE CONSIDERED TO BE A PART OF THE BID PRICE OF THE UTILITY PIPE FOR WHICH
EXCAVATION AND BACKFILL IS REQUIRED.
10.WATER SHALL NOT BE PERMITTED TO ACCUMULATE IN THE EXCAVATED AREA. IT SHALL BE
REMOVED BY PUMPING OR OTHER MEANS AS APPROVED BY THE ENGINEER. THE REMOVAL OF
WATER SHALL BE CONSIDERED TO BE A PART OF THE BID PRICE OF THE UTILITY PIPE FOR WHICH EXCAVATION AND BACKFILL IS REQUIRED. CONTRACTOR TO OBTAIN DEWATERING PERMITS FROM
APPLICABLE JURISDICTIONAL AGENCIES (SJRWMD, ETC.) IF REQUIRED.
11.IF THE BOTTOM OF THE TRENCH IS ROCK, THE EXCAVATION SHALL BE CARRIED EIGHT INCHES BELOW THE INVERT OF THE PIPE AND BACKFILLED WITH THOROUGHLY COMPACTED SAND, GRAVEL, OR OTHER SUITABLE MATERIAL APPROVED BY THE ENGINEER.
12.ROCK EXCAVATION SHALL INCLUDE ANY ROCK ENCOUNTERED WHICH CANNOT BE REMOVED WITH A
3/4 YARD BACKHOE UNDER NORMAL OPERATING CONDITIONS. ROCK EXCAVATION SHALL BE
INCIDENTAL TO CONSTRUCTION OF ALL PIPING SYSTEMS AND NO SEPARATE PAYMENT WILL BE
MADE.
13.WHENEVER IT IS NECESSARY, IN THE INTEREST OF SAFETY, TO BRACE OR SHORE THE SIDES OF THE TRENCH, SUCH BRACING OR SHORING SHALL BE CONSIDERED TO BE PART OF THE BID PRICE OF
UTILITY PIPE FOR WHICH EXCAVATION AND BACKFILL IS REQUIRED.
14.THE CONTRACTOR SHALL FURNISH, PUT IN PLACE AND MAINTAIN SUCH SHEETING, BRACING, AS MAY BE REQUIRED TO SUPPORT THE SIDE OF THE EXCAVATION, AND TO PREVENT ANY MOVEMENT WHICH
CAN IN ANY WAY DAMAGE THE WORK OR ENDANGER ADJACENT STRUCTURES.
15.IF FIELD CONDITIONS, TYPE OF SHEETING OR CONSTRUCTION METHODS MAKE REMOVAL OF
SHEETING IMPRACTICABLE, AT NO ADDITIONAL COST TO THE OWNER, THE CONTRACTOR MAY LEAVE ALL SHEETING IN PLACE. THE ENGINEER MAY REQUIRE SHEETING TO BE CUT OFF AT ANY SPECIFIED ELEVATION BUT IN NO CASE WILL ANY SHEETING BE LEFT CLOSER THAN TWO (2) FEET BELOW THE
NATURAL SURFACE, NOR CUT OFF BELOW THE ELEVATION OF THE TOP OF THE PIPE.
16.AFTER PIPES, STRUCTURES, AND OTHER APPURTENANCES HAVE BEEN INSTALLED, THE TRENCH OR
OPENING SHALL BE BACKFILLED WITH MATERIAL IN CONFORMANCE WITH THE SPECIFICATION.
17.IN AREAS WHERE PAVEMENTS ARE TO BE CONSTRUCTED OVER THE PIPE. THE REMAINDER OF THE
TRENCH SHALL BE PLACED IN SIX INCH LAYERS (COMPACTED THICKNESS) AND SHALL BE
COMPACTED TO 100 PERCENT OF MAXIMUM DENSITY AS DETERMINED BY AASHTO T-180.
CONTRACTOR WILL BE RESPONSIBLE FOR CORRECTING DAMAGE FROM SETTLEMENT IN THE
BACKFILLED AREAS WHETHER UNDER THE PAVEMENT OR OTHERWISE.
18.IN AREAS WHERE NO PAVEMENT IS TO BE CONSTRUCTED, THE BACKFILL ABOVE THE TWELVE INCH LINE ABOVE THE PIPE SHALL BE COMPACTED TO A FIRMNESS APPROXIMATELY EQUAL TO THAT OF
THE SOIL ADJACENT TO THE PIPE TRENCH.
19.CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING REQUIRED SAFETY BARRIER AND
PROTECTIVE STEEL PLATE COVERINGS FOR OPEN TRENCHES.
20.SEE SOILS EVALUATION OF THE PROJECT AREA ON GEOTECHNICAL INVESTIGATION REPORT
PERFORMED BY MESKEL AND ASSOCIATES ENGINEERING, FILE NUMBER 0020-0018B, DATED JUNE 20, 2023.
PAVING AND GRADING NOTES
1. UNDERGROUND UTILITIES SHALL BE COMPLETED OR SLEEVING PROVIDED BEFORE ANY PAVEMENT
CONSTRUCTION BEGINS.
2. ALL PAVEMENT SUBGRADE MATERIAL SHALL BE COMPACTED TO 98% MAXIMUM DENSITY AT
OPTIMUM MOISTURE, AASHTO T-180, METHOD "D" AND SHALL CONFORM TO THE REQUIREMENTS OF F.D.O.T. SPECIFICATIONS, SECTION 120. THE TEST RESULTS SHALL BE ACCEPTED BY THE COUNTY
PRIOR TO PLACEMENT OF BASE MATERIAL.
3. IF THE PLANS INDICATE A LIMEROCK BASE, THE CONSTRUCTION AND THE MATERIAL FOR THE SHELLROCK BASE SHALL CONFORM TO THE REQUIREMENTS OF F.D.O.T. SPECIFICATIONS, SECTION
230. THE SHELLROCK BASE SHALL BE COMPACTED TO 98% MAXIMUM DENSITY AT OPTIMUM
MOISTURE. AASHTO T-180, METHOD "D", THE ENGINEER SHALL SPECIFY THE LOCATION AND NUMBER
OF DENSITY TESTS REQUIRED. THE TEST RESULTS SHALL BE ACCEPTED BY THE COUNTY AND
ENGINEER PRIOR TO APPLICATION OF THE PRIME AND TACK COATS.
4. THE PRIME AND TACK COAT CONSTRUCTION AND MATERIALS FOR THE PRIME AND TACK COATS SHALL CONFORM TO THE REQUIREMENTS OF F.D.O.T. STANDARD SPECIFICATIONS, SECTION 300. THE PRIME AND TACK COATS SHALL BE APPLIED PRIOR TO CONSTRUCTION OF THE ASPHALT SURFACE COURSE AND SHALL BE SANDED AND ROLLED IN ACCORDANCE WITH SECTION 300. APPLICATION
RATES SHALL BE 0.15 GAL/SY FOR LIMEROCK BASE AND 0.25 GAL/SY FOR SHELLROCK BASE.
5. ASPHALTIC CONCRETE SURFACE COURSE SHALL BE AS SHOWN ON THE PLANS. THE MATERIALS FOR THE ASPHALT CONCRETE SURFACE COURSE SHALL CONFORM TO THE REQUIREMENTS OF F.D.O.T.
STANDARD SPECIFICATIONS, SECTION 334.
6. THE MATERIAL TO BE USED AS A STABILIZER SHALL BE SOIL OF HIGH BEARING VALUE SUCH AS, SAND-CLAY, GROUND LIMESTONE, CRUSHED LIMEROCK, OYSTER SHELL, COQUINA SHELL, ROCK
SCREENINGS, OR ANY OTHER MATERIAL WHICH IS SUITABLE FOR STABILIZATION. MUCK SHALL NOT
BE USED AS STABILIZING MATERIAL.
7. ALL GRADES SHOWN REFER TO FINISHED ASPHALT PAVEMENT UNLESS OTHERWISE NOTED.
8. MATERIAL HAVING A PLASTICITY INDEX AT MORE THAN 10 OR A LIQUID LIMIT GREATER THAN 40 SHALL NOT BE USED. ALL MATERIAL USED FOR STABILIZING THE ROADBED SHALL PASS A 3-1/2 INCH
RING.
9. WHERE THE BEARING VALUE OF THE EXISTING SUBGRADE IS ADEQUATE WITHOUT ADDITION OF STABILIZING MATERIAL, THE SUBGRADE SHALL BE SCARIFIED AND DICED, HARROWED, BLADED, OR TILLED FOR REMOVAL OF BOULDERS, ROOTS, ETC. TO ASSURE UNIFORMITY AND THOROUGH MIXING
OF MATERIAL TO THE FULL WIDTH AND DEPTH OF REQUIRED STABILIZATION. THE COMPACTED
SUBGRADE SHALL CONFORM TO THE LINES, GRADES AND CROSS-SECTION SHOWN ON THE PLANS.
10.CONTRACTOR SHALL SAW CUT EXISTING PAVEMENT AT THE LIMITS OF REMOVAL OF EXISTING
PAVEMENT AND WHEN NEW PAVEMENT CONSTRUCTION MEETS EXISTING PAVEMENT. MEET AND
MATCH SHALL ALSO MEAN SAW CUT AND MATCH.
11.THE SUBGRADE TO BE STABILIZED MAY BE PROCESSED IN ONE COURSE, UNLESS THE EQUIPMENT
AND METHODS BEING USED DO NOT PROVIDE THE REQUIRED UNIFORMITY, PARTICLE SIZE
LIMITATION, COMPACTION AND OTHER DESIGNED RESULTS IN WHICH CASE, THE COUNTY WILL
DIRECT THAT THE PROCESSING BE DONE IN MORE THAN ONE COURSE.
12.PRIOR TO THE BEGINNING OF STABILIZING OPERATIONS, THE AREA TO BE STABILIZED SHALL HAVE
BEEN CONSTRUCTED TO AN ELEVATION SUCH THAT UPON COMPLETION OF STABILIZING
OPERATIONS, THE COMPLETED STABILIZED SUBGRADE SHALL CONFORM TO THE LINES, GRADES
AND CROSS-SECTION SHOWN IN THE PLANS, PRIOR TO THE SPREADING OF ANY ADDITIVE
STABILIZING MATERIAL THE SURFACE OF THE ROADBED SHALL BE BROUGHT TO A PLACE
APPROXIMATELY PARALLEL TO THE PLANE OF THE PROPOSED FINISHED SURFACE.
13.THE STABILIZING MATERIAL SHALL BE APPLIED IN SUCH QUANTITY AS IS NECESSARY TO PRODUCE THE REQUIRED BEARING VALUE. IT SHALL BE INCORPORATED WITH THE SUBGRADE BY FLOWING, DICING, HARROWING, BLADING OR MIXING WITH ROTARY TILLERS UNTIL THE MIXED MATERIALS ARE
OF A UNIFORM BEARING VALUE FOR THE FULL WIDTH AND DEPTH OF THE COURSE BEFORE
COMPACTION, REGARDLESS OF THE CHARACTER OR BEARING VALUE. ALL MATERIALS IN THE
STABILIZING COURSE THAT WILL NOT PASS A 3-1/2" RING SHALL BE REMOVED OR BROKEN DOWN TO
A SIZE NOT LARGER THAN 3-1/2 INCHES.
14.COMPACTION SHALL BE ACCOMPLISHED BY ROLLING WITH ANY TYPE OF EQUIPMENT WHICH WILL PRODUCE THE REQUIRED DENSITY. COMPACTION SHALL CONTINUE UNTIL THE ENTIRE DEPTH TO BE
STABILIZED HAS A DENSITY OF NOT LESS THAN 98 PERCENT OF THE MAXIMUM DENSITY IN
ACCORDANCE WITH AASHTO T-180, FIELD DENSITY TESTS SHALL BE MADE AT INTERVALS NOT
GREATER THAN 50 FEET IN EACH COURSE OR LAYER.
15.THE LIMEROCK SHALL BE TRANSPORTED TO THE POINT WHERE IT IS TO BE USED OVER BASE PREVIOUSLY PLACED, IF PRACTICABLE, AND DUMPED ON THE END OF THE PROCEEDING SPREAD, HAULING OVER THE SUBGRADE AND DUMPING ON THE SUB GRADE WILL BE PERMITTED ONLY WHEN
IN THE COUNTY'S OPINION THESE OPERATIONS WILL NOT BE DETRIMENTAL TO THE BASE.
16.THE LIMEROCK SHALL BE SPREAD UNIFORMLY, WITH EQUIPMENT ACCEPTABLE TO THE ENGINEER, ALL SEGREGATED OR OTHERWISE UNACCEPTABLE AREAS SHALL BE REMOVED AND REPLACED WITH
PROPERLY GRADED ROCK, AFTER SPREADING IS COMPLETED, THE ENTIRE SURFACE SHALL BE
SCARIFIED AND THEN SHAPED SO AS TO PRODUCE THE REQUIRED GRADE, THICKNESS AND
CROSS-SECTION AFTER COMPACTION. LIFTS SHALL HAVE A MAXIMUM COMPACTED THICKNESS OF
SIX INCHES.
17.COMPACTION SHALL BE ACCOMPLISHED AT OPTIMUM MOISTURE. WHEN THE MATERIAL DOES NOT HAVE THE PROPER MOISTURE CONTENT TO ENSURE THE REQUIRED DENSITY, WETTING OR DRYING
WILL BE REQUIRED. ADDED WATER SHALL BE UNIFORMLY MIXED TO THE FULL DEPTH OF THE
COURSE WHICH IS BEING COMPACTED.
18.BEFORE ANY BITUMINOUS MATERIAL IS APPLIED, ALL LOOSE MATERIAL, DUST, DIRT, CAKED SLAY AND FOREIGN MATERIAL WHICH MIGHT PREVENT PROPER BOND WITH EXISTING SURFACE SHALL BE
REMOVED FOR THE FULL WIDTH OF THE APPLICATION. PARTICULAR CARE SHALL BE TAKEN TO
CLEAN THE OUTER EDGE OF THE STRIP TO BE TREATED IN ORDER TO ENSURE THAT THE PRIMER WILL ADHERE. WHERE THE PRIMER IS APPLIED ADJACENT TO CURB & GUTTER OR VALLEY GUTTER, SUCH CONCRETE SURFACES ARE TO BE PROTECTED AND KEPT FREE OF BITUMINOUS MATERIAL.
19.NO BITUMINOUS MATERIAL SHALL BE APPLIED WHEN THE TEMPERATURE OF THE AIR IS LESS THAN
40 DEGREES F IN THE SHADE AND FALLING, OR WHEN IN THE OPINION OF THE COUNTY, THE
WEATHER CONDITIONS OR THE CONDITION OF THE EXISTING SURFACE IS UNSUITABLE.
20.THE SURFACE TO BE PRIMED SHALL BE CLEAN AND DRY FOR LIMEROCK BASES. THE GLAZED FINISH
SHALL BE REMOVED BEFORE THE APPLICATION OF PRIME COAT.
21.WHERE NEW PAVEMENT MEETS EXISTING, CONNECTION SHALL BE MADE IN A NEAT STRAIGHT LINE
AND FLUSH WITH EXISTING PAVEMENT.
WATER AND SEWER NOTES:
1. CONTRACTOR SHALL COORDINATE WITH OWNER BEFORE ANY WATER OR SEWER DEMOLITION,
SHUT-DOWN OR TIE-IN.
2. CONTRACTOR SHALL FIELD VERIFY EXISTING WATERMAIN, DOMESTIC AND FIRE SERVICE LINE SIZE
AND LOCATION PRIOR TO ANY NEW WATERMAIN INSTALLATION.
3. ALL NEW WATERMAIN SHALL BE HIGH DENSITY POLYETHYLENE (HDPE) DR-18 PIPE OR PVC IN
ACCORDANCE WITH CCUA MATERIALS LIST.
4. CONTRACTOR SHALL PERFORM APPROPRIATE FLUSHING, PRESSURE TESTS AND CHLORINATION OF
NEW WATERMAIN AS REQUIRED BY AUTHORITIES HAVING JURISDICTION IN THE AREA.
5. WATER MAINS SHALL BE LAID TO PROVIDE A HORIZONTAL DISTANCE OF AT LEAST THREE FEET BETWEEN THE OUTSIDE OF THE WATER MAIN AND THE OUTSIDE OF ANY EXISTING OR PROPOSED
STORM SEWER, STORMWATER FORCE MAIN, OR PIPELINE CONVEYING RECLAIMED WATER
REGULATED UNDER PART III OF CHAPTER 62-610, F.A.C.
A. WATER MAINS SHALL BE LAID TO PROVIDE A HORIZONTAL DISTANCE OF AT LEAST THREE FEET, AND PREFERABLY TEN FEET, BETWEEN THE OUTSIDE OF THE WATER MAIN AND THE OUTSIDE OF
ANY EXISTING OR PROPOSED VACUUM-TYPE SANITARY SEWER.
B. WATER MAINS SHALL BE LAID TO PROVIDE A HORIZONTAL DISTANCE OF AT LEAST SIX FEET, AND PREFERABLY TEN FEET, BETWEEN THE OUTSIDE OF THE WATER MAIN AND THE OUTSIDE OF ANY
EXISTING OR PROPOSED GRAVITY- OR PRESSURE-TYPE SANITARY SEWER, WASTEWATER FORCE
MAIN, OR PIPELINE CONVEYING RECLAIMED WATER NOT REGULATED UNDER PART III OF CHAPTER 62-610, F.A.C. THE MINIMUM HORIZONTAL SEPARATION DISTANCE BETWEEN WATER MAINS AND
GRAVITY-TYPE SANITARY SEWERS SHALL BE REDUCED TO THREE FEET WHERE THE BOTTOM OF
THE WATER MAIN IS LAID AT LEAST SIX INCHES ABOVE THE TOP OF THE SEWER.
C. WATER MAINS CROSSING ANY EXISTING OR PROPOSED GRAVITY- OR VACUUM-TYPE SANITARY SEWER OR STORM SEWER SHALL BE LAID SO THE OUTSIDE OF THE WATER MAIN IS AT LEAST SIX INCHES, AND PREFERABLY 12 INCHES, ABOVE OR AT LEAST 12 INCHES BELOW THE OUTSIDE OF THE OTHER PIPELINE. HOWEVER, IT IS PREFERABLE TO LAY THE WATER MAIN ABOVE THE OTHER
PIPELINE.
D. WATER MAINS CROSSING ANY EXISTING OR PROPOSED PRESSURE-TYPE SANITARY SEWER,
WASTEWATER OR STORMWATER FORCE MAIN, OR PIPELINE CONVEYING RECLAIMED WATER
SHALL BE LAID SO THE OUTSIDE OF THE WATER MAIN IS AT LEAST 12 INCHES ABOVE OR BELOW THE OUTSIDE OF THE OTHER PIPELINE. HOWEVER, IT IS PREFERABLE TO LAY THE WATER MAIN
ABOVE THE OTHER PIPELINE.
6. WATERMAIN INSTALLATION AND TRENCH BACKFILL SHALL BE IN ACCORDANCE WITH THE PLANS
AND CLAY COUNTY UTILITY AUTHORITY STANDARD DETAILS.
EXISTING EASEMENT
OMEGA PARK
CCUA
CONNECTION
OMEGA PARK, 4317
COUNTY ROAD 218
JH
JS
GENERAL NOTES
C2.02
03 20100% SUBMITTAL
DRAWING NUMBER
DRAWING TITLE
CHECKED BY
DRAWN BY
DESIGNED BY
DATE OF ISSUE
REVISIONS
VERIFY SCALES
CLIENT PROJECT NUMBER
PROJECT NUMBER
PROJECT INFORMATION
CLIENT
REGISTRATION
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY
1"0
Pl ot
D at e:
/2 0/
0:
:3 rn am e:
jh ub ou t N am e:
C
2.
Fo ld er P at h:
V
Pr oj ec ts
\2
4\
-0
3.
- o m eg a pa rk c cu a co nn ec tio n\
De sig n\
CA
D\ Sh na m e:
4-
.0
G en er al N ot es
.d w g
OF
501 Riverside Avenue, Suite 501 Jacksonville, FL 32207
904.398.8636 www.chenmoore.com
JENNIFER L. SMITH, PE
LICENSE NO. 72232
DATE: __________
THIS SEAL IS ONLY VALID ON PRINTED
COPIES THAT ARE DATED WITH THE
LICENSEE'S ORIGINAL HAND SIGNATURE.
SCANNED OR ELECTRONIC COPIES ARE NOT
CONSIDERED SIGNED AND SEALED.
JEN
NIFER L. SMITH
No. 72232
L I C E NS E
F L O R I DA
P R O F E S S I O N A L E N G I N E
E RSTATE OF
06/20/2025
SPECIFICATIONS FOR CONSTRUCTION OF WATER DISTRIBUTION SYSTEM
01. MANHOLES. Manhole bases, sections, and cones shall conform to the requirements of ASTM C478, Specifications for Precast Reinforced Concrete Manhole Sections. Cement shall meet the requirements of ASTM C150, Specifications for Portland Cement, Type II. Concrete shall meet the minimum requirements for Class "A" Concrete Work. Minimum wall thickness shall be 1/12 the inside diameter in inches plus one (1) inch. Bases for manholes shall be cast integrally with the bottom manhole section. Joint contact surfaces shall be formed with machined castings; they shall be exactly parallel with a 2 degree slope and nominal 1/16 inch clearance with the tongue equipped with a proper recess for the installation of an O-ring rubber gasket, conforming to ASTM C443, Joints for circular Concrete sewer and Culvert pipe using Rubber gasket, or RAM-NEK premolded Plastic Joint Sealer to joints.
Manhole adjustment materials shall be sound, hard, and pre-primed. Precast concrete adjustment rings may be utilized. Precast manhole walls shall not be coated unless otherwise noted. Cement grout for manhole bottoms shall be a stiff rich mix of Type II Portland Cement and sharp plaster sand. Calcium chloride may be added (maximum of 2%) to aid in obtaining a faster set. At permanent pump station locations, the first upstream manhole from the station shall be lined with a polyethylene liner as manufactured and installed by AGRU America, Inc., or approved equal.
01.1 CAST IRON MANHOLE FRAMES AND COVERS. Cast iron manhole frames and covers shall be as detailed on drawings.
Castings shall meet the requirements of ASTM A48, Specifications for Gray Iron Castings, Class No.30, or Grade 65-45-12, Ductile Iron meeting the requirements of ASTM A536, Standard Specification for Ductile Iron Castings. In either case, manhole frame and cover shall be designed to withstand an HS20-44 loading defined in the AASHTO specifications. Frames and covers shall be machined or ground at touching surfaces so as to seat firmly and prevent rocking.
01.2 FLEXIBLE MANHOLE CONNECTOR. All connections between sewer pipe and pre-cast concrete manholes shall be accomplished by a Flexible Connector, "Kor-N-Seal", as manufactured by National Pollution Control Systems, Inc., or approved equal.
01.3 FLOW CHANNELS. Flow channels in manhole base shall be formed of D.O.T. Class I Type II cement grout with brick and trowel to a smooth surface finish. Grout surface shall be 1" min. thickness over brick. While the precast manholes are being installed, cut off pipes 4 inches inside face of the manhole and construct the invert to the shape and sizes of pipe indicated. All inverts shall provide a constant gradient from influent pipe to effluent pipe through manhole. Changes in direction of the sewer and entering branch or branches shall be laid out in smooth curves of the longest possible radius which is tangent to the center lines of adjoining pipelines.
01.4 DROP INLETS. Where shown on the drawings, drop inlets to the manholes shall be constructed as shown on the approved drawings and specified herein.
02. POLYVINYL CHLORIDE PIPE. Polyvinyl Chloride Sewer Pipe shall conform to the requirements of ASTM D-3034, SDR 26. The PVC compound conforming to ASTM D-1784. Pipe shall be manufacturers-marked in 5 ft. intervals or less, indicating manufacturers name, nominal size, cell classification and legend. Joints shall be push-on rubber gasketed, conforming to ASTM 3212. Pipe and fittings shall be installed in accordance with recommended practice ASTM D-2321. All pipe and sewer fittings shall be SDR-26 heavy wall, installed up to a depth of 13 feet from finish grade to invert of pipe. Maximum depth of gravity sewer without prior approval shall be 13 feet.
03. PIPE BETWEEN MANHOLES. All piping installed between manholes shall be the same material and class. No dissimilar pipe material will be allowed anywhere within a single run of pipe.
04. SANITARY SERVICE LATERALS. Sanitary service laterals shall be Polyvinyl Chloride Pipe conforming to the requirements of ASTM D-3034, SDR 26 where cover over top of pipe is 36 inches or greater. Where cover over top of pipe is less than 36 inches, specific construction conditions shall be directed by the Clay County Utility Authority (CCUA). All sanitary service laterals shall be a minimum of 4'-0" deep at the right-of-way line to top of pipe. Any sanitary service lateral which must be more than 6'-0" deep at the right-of-way line and shall not be installed prior to obtaining permission from the CCUA field inspector or CCUA Engineering Department. All sanitary service laterals shall be 6-inch diameter from the main to the right-of-way line with a minimum slope of 0.60% (0.6 feet per hundred feet). In single family residential developments, services shall reduce to 4" in size at the property line utilizing the proper fittings for the type of pipe specified. All sewer service laterals over 13' deep shall be constructed of DR18 PVC pipe, and DR18 pipe fittings, per CCUA standard sewer system details.
05. PUMP STATIONS (TEMPORARY OR PERMANENT). All pump stations shall be constructed in accordance with CCUA standards, rules and regulations and be approved by CCUA. All work and materials shall meet the requirements of CCUA Standard Pump Station Details and Specifications or the plans, details and specifications for that specific pump station.
06. FORCE MAINS. Force mains shall be C900 DR18 PVC and conform to the requirements of ASTM D-1784, D-2241, D-3139 and F-477. Pipe shall be color coded and manufacturers-marked "FORCE MAIN" at every 12" along the barrel of the pipe. Ductile iron pipe for force main service shall be polylined. Ductile iron pipe is not to be used without prior approval of the Clay County Utility Authority.
Fittings shall be C110 gray iron and shall be epoxy coated and lined. All force mains shall be installed with minimum tracer wire per CCUA standard location wire details. All force mains should be installed with minimum 5 feet cover from finish grade, unless approved by CCUA.
07. LIFT STATION VALVES. See CCUA Approved Lift Station Details and Materials Manual for acceptable gate valves and check valves.
08. FORCE MAIN VALVE. Gate valve, resilient seated, same as specified in Water Distribution System Specifications Section 11.
Except valve bodies shall be grey iron. Valve box shall have the word "SEWER" cast into the cover.
01. JOINT RESTRAINT. All fittings shall be properly and adequately restrained against lateral movement at all water main tees, crosses, valves, bends, and fire hydrants. See CCUA Approved Materials Manual for acceptable restraints.and refer to joint restraint tableon detail sheet WAT 02.
02. DUCTILE IRON PIPE. Ductile iron pipe shall conform to ANSI Specification A21.50 (AWWA C150) latest, "Thickness Design of Ductile Iron Pipe", Table 50.5, laying condition Type 2, internal operating pressure of 250 p.s.i. for an 8-foot depth of cover, Class 51 minimum and shall be ANSI A21.51 (AWWA C151), latest centrifugally cast pipe. Laying lengths shall be 20 feet or less in length, and shall be clearly marked with pressure rating, thickness, class, height of pipe without lining, length, and manufacturer. Ductile iron pipe for water service shall be furnished with cement lining per AWWA C110, C115 and C151. The pipe shall have design values of 60,000 p.s.i. minimum tensile strength, and 42,000 p.s.i. minimum yield strength.
Ductile iron pipe for water or service lines shall be used in any easement, right-of-way, between lots, or any instance where a building foundation or other permanent appurtenance is within 10' of the water or service line.
03. DUCTILE IRON FITTINGS Ductile iron fittings shall be C153 cement lined and suitable for the type and class of pipe to which connected. Gaskets shall be suitable for potable, domestic water service. Minimum working pressure shall be 150 p.s.i.
04. POLYVINYL CHLORIDE PIPE. Polyvinyl chloride pipe for water mains 4 inch through 24 inches in diameter, shall be DR18 (C900) Pressure Class 235 psi PVC 1120; water distribution mains above 24 inches in diameter shall be DR25 (C900) Pressure Class 165 PVC 1120, conforming to ASTM D-1784, D-2241, D-3139 and F-477, latest, and shall bear the seal of the National Sanitation Foundation. Pipe shall be color coded and marked on at least 1 (one) side with the word "WATER" at every 12" along the barrel of the pipe, with the lettering facing up. Couplings shall be rubber gasketed, push-on type conforming to ASTM D-2122.
All water pipe shall be blue in color.
05. STEEL CASING PIPE. Steel casing pipe shall be of size indicated on the Drawings and shall conform to ASTM A139, with a minimum yield strength of 35,000 p.s.i.
06. POLYVINYL CHLORIDE (PVC 1120, SCHEDULE 80) PIPE Polyvinyl Chloride Pipe shall conform to the requirements of ASTM D 1785. Fittings shall be suitable for type of installation required. All piping smaller than 4" shall be Schedule 80 PVC.
07. GATE VALVES AND BOXES. Gate valves shall be non-rising stem type and shall be suitable for a 200 p.s.i. non-shock working pressure. Gate valves shall be mechanical joint, flanged or screwed. Gate valves shall have a 2" operating nut and open left. Gate valves shall have joints suitable for the type of main on which installed. Valves shall be as described in the CCUA Material Manual.
08. WATER METER BOXES. See CCUA Approved Materials Manual for acceptable water meter boxes.
Developer shall be responsible for installation of meter boxes on all water services as part of the water main installation as per standards for water meter service details. All curb stops shall be adjusted to the proper elevation and shall be accessible for the installation of the water meter. The Contractor shall be required to open all boxes for the CCUA inspector at the final inspection. A treated 6'-6" fence post marker shall be painted blue for identification. Meter boxes shall not be placed in any sidewalk or driveway without approval of CCUA.
09. CURB STOPS. Curb stops shall be cast bronze, inverted key stop, roundway, with check, lock wing type, for locking in the closed position. See CCUA Approved Materials Manual for acceptable curb stops.
10. FIRE HYDRANTS. Fire hydrants shall be traffic type, 150 pound working pressure, AWWA Standard C502, latest revisions, with two 2 1/2" nozzles, one 4 1/2" nozzle and one 5 1/4" main valve. Fire hydrant shall be compression type with breakable coupling and bolts. Pipe connection shall be mechanical joint. Fire hydrants shall be painted silver, BLP Mobile Paints, Liquid Aluminum, 1151 alkyd weight 56.6% x volume 41.2% VOC 3.76 lb. per gallon with 1 1/2" penta nuts, opening left. See CCUA Approved Materials Manual for acceptable fire hydrants.
11. NEW CONNECTION TO EXISTING MAIN. New connection to existing main in service shall be accomplished by the "wet tap" method utilizing full circle stainless steel tapping sleeve and mechanical joint tapping valve. Tapping sleeve shall be rated at 200 p.s.i., non-shock working pressure conforming to AWWA Standard C110, latest revision. Stainless steel tapping sleeves shall be from those listed in CCUA approved material manual. Tapping valve shall be mechanical joint on one end and standard flanged joint on other end. Valve shall conform of these specifications.
12. FIRE LINES/MAINS. All fire lines or mains connecting to CCUA owned potable water main shall be installed by a State of Florida Licensed Fire Installation Contractor, and shall meet all requirements of the local Authority, State Fire Marshal, County Fire Marshal, and the National Fire Protection Association.
Work performed must meet all requirements of NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances.
12.1 The Fire Marshal shall have the right to deny acceptance or use of any fire line, installed and connected to a CCUA owned and maintained water main until such time that the Contractor installing the fire line can produce proof to the Fire Marshal that all paperwork, fees due, or close out documents have been satisfactorily prepared and approved by CCUA.
13. INSTALLATION. The minimum cover over top of potable water main shall be 36". All water lines and appurtenances shall be thoroughly cleaned of all foreign matter before being lowered into the trench and shall be kept clean during laying operations by means of plugs or other approved methods. All pipe shall be checked for defects before being lowered into the trench. Defective pipe shall not be used. Pipe found to be defective, after installation shall be removed and replaced with sound pipe at no additional expense to the Owner. The full length of each section of pipe shall rest solidly upon the pipe bed, with recesses excavated to accommodate the bells and joints. All pipe that has the grade or joint disturbed after laying shall be taken up and reinstalled. The pipe shall not be laid in water or when trench or weather conditions are unsuitable for the work. All joints shall be cleaned of all foreign matter before making the joint. Fittings at bends in the pipe shall be properly restrained with joint restrainers adequately sized to prevent movement and dislocating or blowing off when the line is under pressure. Service laterals shall terminate at the point as shown in the CCUA Standard Detail drawing.
14. STERILIZATION. After completion of construction and testing, the water system shall be sterilized with chlorine in accordance with AWWA Standard C651, latest, and State of Florida Department of Environmental Protection requirements before acceptance for domestic operation. The amount of chlorine applied shall be sufficient to provide a dosage of 50 parts per million or more. The chlorine solution shall remain in the new pipe system for a period of at least 24 hours, during which time every valve in the new pipe system shall be opened and closed several times to assure contact with every surface of the system.
After completion of sterilization procedures, the system shall be flushed using chlorinated water from a domestic water source having a chlorine residual of at least 1 part per million. The Contractor shall obtain all bacteriological clearances as required by the Florida Department of Environmental Protection. After bacteriological clearances, the pressure in the main shall not drop below 20 p.s.i. Clearance report to be submitted to the Engineer and CCUA Inspector. The Contractor should be aware that there is a timing maximum related to bacteriological clearance of the main, completion of as-built drawings and Engineer / CCUA completion of Certificate of Completion. In any project where the bacteriological clearances are greater than 60 days old at the time of submittal of Certificate of Completion to FDEP, the Contractor may be required to pull more samples and obtain more bacteriological clearances. Prior to introducing the chlorine solution, the lines shall be thoroughly flushed with clean water utilizing full pipe diameter flushing for pipe up to and including 8" diameter.