Oil_Analysis_T61_20260105_(1).pdf

PDF 1 MB Posted

Attached to
Life Extension for Deerhaven Unit 1 Transformers
Solicitation number
2026-093
Issued by
Alachua County, Graceville City, Florida

About this file

This is a TOA (Transformer Oil Analysis) technical report for transformer DHT61, a 138 kV OA/FA model Westinghouse (ABB) unit manufactured in 1970 and located at the Deerhaven substation in Gainesville, Florida, operated by GRU (Gainesville Regional Utilities). The report documents comprehensive oil analysis results from samples collected on January 5, 2026, with historical data spanning from 2006 through January 2026. The analysis includes dissolved gas analysis (DGA), breathing status assessment, moisture content evaluation, fluid quality testing, furan analysis, and PCB contamination screening. Key findings indicate that all gases remain at acceptable concentrations with no recent production of fault gases (gassing status 2), moisture content is acceptable at 6 mg/kg with 16% relative saturation, fluid quality shows no oil degradation problems with an acid number of 0.010 mg KOH/g and dielectric breakdown of 50 kV, and PCB levels are non-detectable at 5.0 mg/kg. The transformer's oil preservation system operates as an N2-blanketed unit with positive pressure and low oxygen levels, and the equipment has been in service continuously since at least 2006.

The analysis reveals a historical gassing event related to carbon monoxide production beginning in April 2016, indicating a potential hotspot affecting winding insulation paper, though recent accumulated failure rates remain low at 6.31% for liquid and 0.18% for paper. All test results are classified as acceptable (result code 1), with recommended retesting scheduled annually on January 5, 2027. The transformer's estimated safe handling limit is currently 10.2%, representing adequate operational margin, and the equipment demonstrates stable operating conditions with no anomalies detected across all analytical parameters. This technical documentation serves as the foundation for GRU's planned life extension project for Unit 1 transformers at Deerhaven, specifically supporting the procurement and replacement specifications for transformer T-61 along with radiators, wiring, and comprehensive testing requirements outlined in the related contract opportunity.

View the file

Other files

File Type Posted
Life_Extension_for_Deerhaven_Unit_1_Transformers.pdf PDF
T62_.JPEG JPEG file
T65.JPEG JPEG file
T61.JPEG JPEG file
T61_.JPEG JPEG file
T61___.JPEG JPEG file
T62.JPEG JPEG file
T62_Nameplate.JPG JPG image
T61_Nameplate.JPG JPG image
T62___.JPEG JPEG file
T65_.JPEG JPEG file
T65_Nameplate.JPEG JPEG file
T61_T62_Cabinet_Wiring_Diagram_(1).pdf PDF
Oil_Analysis_T62_20260105_(1).pdf PDF
T61_T62_Outline_Drawing.pdf PDF
Power_Transformer_Maintenance_Checklist_Unit_1_(2).pdf PDF
DH_Unit_1_Transformers_Life_Extension_Specification_2026-093.docx DOCX document
Power_Transformer_Maintenance_Checklist_Unit_1.pdf PDF
T61_T62_Cabinet_Wiring_Diagram.pdf PDF
Oil_Analysis_T61_20260105.pdf PDF
Oil_Analysis_T62_20260105.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TOA™ Analysis Report TRN DHT61

1 Report generated from GRU at 20260127T020049Z

Equipment DHT61 MVAR Actual 52.267

Serial No. 7001632 In service True

Apparatus type TRN Spare False

Owner GAINESVILLE Tank MAIN

Region GAINESVILLE Norms used TRN_IEEE_INC_69_288KV

Substation Deerhaven Gassing status 2

Norms TRN_IEEE_INC_69_288KV DGA result 1→1

Fluid type OIL Breathing result 2→2

Description Transformer Moisture result 1→1

Manufacturer Westinghouse (ABB) FQ result 1→1

Year manufactured 1970 Trace elements result 0→0

Model OA/FA Particle analysis result 0→0 kV ratings 138 PCB result 1→1

Max rated voltage 138000 Furan result 1→1

Fluid volume 4440 Oil test status UNREVIEWED

Last Analysis Done On 2026-01-26

Last sample date 2026-01-05

Tank last modified date 2026-01-26

Equipment last modified date 2020-07-17

Norms last modified date 2021-06-05

Last analysis date 2026-01-26

Read-only samples 6

Excluded samples 0

Total samples 91

Sample Remarks

Sampled Container Lab remarks

2026-01-05 AC595 A50 All gases at acceptable concentrations

2025-07-02 GW432 A50 All gases at acceptable concentrations

2024-12-10 GK996 A50 All gases at acceptable concentrations

2024-04-10 DB894 A50 All gases at acceptable concentrations

2023-09-18 AT333 A50 All gases at acceptable concentrations

2 Report generated from GRU at 20260127T020049Z

Reliability-based DGA Summary

DGA last date 2026-01-05 Cumulative sev liquid % 6.31

DGA samples 59 Cumulative sev paper % 0.18

Gassing events 6 Gassing status 2

Event fault type N/A Normalized HF ratio 0.00

HF %/yr combined 0.00

Accumulated NEI-HC

Fa ilu re r at e

6.31 %

Accumulated NEI-CO

Fa ilu re r at e

0.18 % Grey area represents cumulative gassing event severity.

Red arrow represents event severity growth rate.

Reliability-based DGA Diagnosis

No recent production of fault gas (gassing status 2). An extreme increase in CO/CO2 suggests a hotspot affecting winding insulation paper, rather than general overheating of the paper or a hotspot outside the winding.

Dissolved Gas Analysis

Lab report number 250565-003 247423-005 244280-020 240105-003 237213-003

Sample date 2026-01-05 2025-07-02 2024-12-10 2024-04-10 2023-09-18

Sample temp 11 26 20 21 27 °C

Hydrogen (H2) 2 2 4 5 10 µL/L

Methane (CH4) 13.0 13.0 14.0 13.0 14.0 µL/L

Ethane (C2H6) 7.0 6.0 7.0 6.0 7.0 µL/L

Ethylene (C2H4) 3.0 4.0 4.0 3.0 4.0 µL/L

Acetylene (C2H2) 0.0 0.0 0.0 0.0 0.0 µL/L

Carbon Monoxide (CO) 68~ 74~ 90 92 118 µL/L

Carbon Dioxide (CO2) 1180 1150 1175 1190 1201 µL/L

Oxygen (O2) 1436 1482 2092 1310 1738 µL/L

Nitrogen (N2) 82123 78595 76345 83040 81857 µL/L

Total heat gas 23 23 25 22 25 µL/L

TDCG 93 99 119 119 153 µL/L

Equivalent TCG 0.065 0.076 0.097 0.093 0.128 %

Total partial press 100.7 89.2 89.6 96.4 92.6 % atm

3 Report generated from GRU at 20260127T020049Z

Lab report number 250565-003 247423-005 244280-020 240105-003 237213-003

Est. safe handling limit 10.2 10.3 9.8 9.6 8.9 %

Predicted composite fault gas 14 15 20 22 31 µL/L

Acetylene/Hydrogen (C2H2/H2) 0.0 0.0 0.0 0.0 0.0

CO2/CO 17.353 15.541 13.056 12.935 10.178

CO/CO2 0.058 0.064 0.077 0.077 0.098

Oxygen/Nitrogen (O2/N2) 0.017 0.019 0.027 0.016 0.021

ETCG/ESHL 0.006 0.007 0.010 0.010 0.014

NEI-HC 0.09 0.09 0.10 0.08 0.10 kJ/kL

NEI-CO 1.90 1.88 1.99 2.02 2.15 kJ/kL

DGA retest days 365 365 365 365 365 days

DGA retest date 2027-01-05 2026-07-02 2025-12-10 2025-04-10 2024-09-17

DGA reference days 187.0 204.0 244.0 205.0 221.0 days

DGA result 1 1 1 1 1

Gassing status 2 2 2 2 2

HF %/yr combined 0.00 0.00 0.00 0.00 0.00

Symbol legend: ~: below min interpretation level

Dissolved Gas Analysis Remarks

No anomalies.

Dissolved Gas Analysis Summary

Variable name Value Units Description

Carbon Monoxide (CO) 68~ µL/L co~

Gassing Events

Date

NE

I-H

C [k

J/k L]

2: D1

Accumulated Hydrocarbon Gas NEI

NEI-HC

Cumulative NEI-HC Gassing Event

4 Report generated from GRU at 20260127T020049Z

Date

NE

I-C

O [k

J/k L]

6: PD

Accumulated Carbon Oxide Gas NEI

NEI-CO

Cumulative NEI-CO Gassing Event

Date

0.0

0.1

0.2

0.3

CO

/C

O2

Carbon Monoxide to Carbon Dioxide Ratio

CO/CO2

Smoothed CO/CO2 Gassing Event

ID Event Event start Start value Inc Days Samples FT RCOR % Sev % HF %/yr

1 C2H2 2005-10-12 0.000 1220.000 70 2 D1

2 HC 2003-10-27 0.496 15.167 786 6 D1 6.16 2.44

3 R 2007-10-15 0.034 0.040 771 5 119

4 R 2013-01-15 0.067 0.115 323 3 172

5 R 2019-03-25 0.043 0.084 400 2 194

6 CO 2016-04-19 9.066 2.283 1863 10 PD 0.08 0.01

Breathing Status Analysis

Sample date 2026-01-05 2025-07-02 2024-12-10 2024-04-10 2023-09-18

Oxygen (O2) 1436 1482 2092 1310 1738 µL/L

Nitrogen (N2) 82123 78595 76345 83040 81857 µL/L

Total partial press 100.7 89.2 89.6 96.4 92.6 % atm

Median O2 1482 1738 1865 1738 1738

Median N2 81857 81857 81857 83040 85632

Max deviation O2 782 782 782 428 436

Max deviation N2 6695 6695 8149 10117 10117

Predicted preservation class

N2-BLANKET N2-BLANKET N2-BLANKET N2-BLANKET N2-BLANKET

Breathing status result 2 2 2 2 2

5 Report generated from GRU at 20260127T020049Z

Breathing Status Remarks

Oil preservation type is not defined on the equipment properties. A value is required to check if it is consistent with the data. Appears to be an N2-blanketed system with positive pressure and low O2.

O2 & N2 Diagram

O2/N2 = 0.5

Supersaturated

0 5000 10000 15000 20000 25000 30000 35000 Oxygen (O2) [µL/L]

20000

40000

60000

80000

100000

Ni to rg en

(N 2)

[µ L/

L]

Oil Preservation System as a Function of O2 and N2

Air

Cons-Sealed

N2-blanket Sealed

Super-atmospheric (Pressurized) Atmospheric (Air) Sub-atmospheric (Sealed) Illogical Previous sample(s) Latest sample Time Progression

Moisture Analysis

Lab report number 250565-003 247423-005 244280-020 240105-003 237213-003

Sample date 2026-01-05 2025-07-02 2024-12-10 2024-04-10 2023-09-18

Sample temp 11 26 20 21 27 °C

Moisture (H2O) 6 12 11 10 8 mg/kg

Relative saturation 16 17 20 17 11 %

Dew point -23 -11 -13 -14 -18 °C

Moisture result 1 1 1 1 1

Moisture Remarks

The water content of the oil is acceptable.

6 Report generated from GRU at 20260127T020049Z

Fluid Quality

Lab report number 237213-003 220686-003 219034-003 204367-009 150203-018

Sample date 2023-09-18 2020-12-07 2020-08-26 2018-03-06 2008-10-29

Sample temp 27 14 36 30 20 °C

Diel breakdown D877 50.0 49.0 47.0 50.0 kV

Acid number 0.010 0.010 0.010 0.010 mg KOH/g

Interfacial tension 36.3 36.3 34.2 37.2 mN/m

Specific Gravity 0.8800 0.8790 0.8790 0.8800

Color 2.0 2.0 1.5 2.0

Oil quality index 0.3 0.3 0.3 0.3

Visual CLEAR OK OK OK

Corrosive Sulfur D1275B Noncorrosive

Fluid quality retest days 365 365 365 365 days

Fluid quality retest date 2024-09-17 2021-12-07 2019-03-06 2009-10-29

FQ result 1 1 1 1

Fluid Quality Analysis Remarks

No oil quality problems were detected.

Furans / Alcohols

Lab report number 150203-018 136966-005

Sample date 2008-10-29 2006-05-01

Sample temp 20 40 °C

2-furfural (2FAL) 0 0 µg/L

Furan result 1 1

Furan Analysis Remarks

Furan levels are within acceptable limits.

7 Report generated from GRU at 20260127T020049Z

PCB Analysis

Lab report number 192008-003 152796-003 150203-018 136966-005

Sample date 2016-01-19 2009-05-12 2008-10-29 2006-05-01

Sample temp 40 45 20 40 °C

Total PCB 5.0 5.0 5.0 4.0 mg/kg

PCB result 1 1 1 1

PCB Remarks

Not PCB contaminated. For a report of the last PCB sample, see the PCB in Oil Report.

History Graphs and Diagnostic Charts µL /L

Hydrocarbon gases and hydrogen

H2

CH4

C2H6 C2H4 C2H2 µL /L

Atmospheric gases and carbon monoxide

N2 O2

CO2

CO

https://www.toa4online.com/toa/redirect?page=pcb_report&db=GRU&equipnum=DHT61&serialnum=7001632&apprtype=TRN&tank=MAIN

8 Report generated from GRU at 20260127T020049Z

1999 2004 2009 2014 2019 2024 2029

NEI-HC

kJ /k

L

1999 2004 2009 2014 2019 2024 2029

NEI-CO

kJ /k

L 1999 2004 2009 2014 2019 2024 2029

Hydrogen (H2) µL /L

1999 2004 2009 2014 2019 2024 2029

Methane (CH4) µL /L

1999 2004 2009 2014 2019 2024 2029

Ethane (C2H6) µL /L

1999 2004 2009 2014 2019 2024 2029

Ethylene (C2H4) µL /L

1999 2004 2009 2014 2019 2024 2029

Acetylene (C2H2) µL /L

1999 2004 2009 2014 2019 2024 2029

Carbon Monoxide (CO) µL /L

9 Report generated from GRU at 20260127T020049Z

1999 2004 2009 2014 2019 2024 2029

Carbon Dioxide (CO2) µL /L

1999 2004 2009 2014 2019 2024 2029

10000

15000

20000 Oxygen (O2) µL /L

1999 2004 2009 2014 2019 2024 2029

20000

40000

60000

80000

100000

Nitrogen (N2) µL /L

1999 2004 2009 2014 2019 2024 2029

Total heat gas µL /L

1999 2004 2009 2014 2019 2024 2029

TDCG

µL /L

1999 2004 2009 2014 2019 2024 2029 0.0

0.5

1.0

1.5

2.0 Equivalent TCG

1999 2004 2009 2014 2019 2024 2029

Total partial press a tm

1999 2004 2009 2014 2019 2024 2029

Est. safe handling limit

10 Report generated from GRU at 20260127T020049Z

1999 2004 2009 2014 2019 2024 2029

Predicted composite fault gas µL /L

1999 2004 2009 2014 2019 2024 2029

Acetylene/Hydrogen (C2H2/H2)

1999 2004 2009 2014 2019 2024 2029

CO2/CO

1999 2004 2009 2014 2019 2024 2029 0.00

0.10

0.20

0.30

CO/CO2

1999 2004 2009 2014 2019 2024 2029 0.00

0.05

0.10

0.15

0.20 Oxygen/Nitrogen (O2/N2)

1999 2004 2009 2014 2019 2024 2029 0.0

0.1

0.2

0.3

0.4

ETCG/ESHL

2006 2011 2016 2021 2026

Diel breakdown D877 kV

2006 2011 2016 2021 2026 0.00

0.05

0.10

0.15

0.20

Acid number m g

KO

H

/g

11 Report generated from GRU at 20260127T020049Z

2006 2011 2016 2021 2026

Interfacial tension m N

/m

2006 2011 2016 2021 2026 0.0

0.2

0.4

0.6

0.8

Specific Gravity

2006 2011 2016 2021 2026 0.0

0.5

1.0

1.5

2.0 Color

2006 2011 2016 2021 2026 0.00 0.05 0.10 0.15 0.20 0.25

Oil quality index

2001 2006 2011 2016 2021 2026 2031

Moisture (H2O) m g/ kg

2001 2006 2011 2016 2021 2026 2031

Relative saturation

2006 2007 2008 2009

2-furfural (2FAL) µg /L

1999 2004 2009 2014 2019 2024 2029

Sample temp

°C

12 Report generated from GRU at 20260127T020049Z

2015 2017 2019 2021 2023 2025 2027 0.00

0.01

0.02

0.03

0.04 HF %/yr combined

Raw Data Upper alert limit Lower alert limit