KCDME042.pdf
PDF 111 KB Posted
- Solicitation number
- NWWP4000-19-00072MWH
About this file
Mechanical prints for the two locations
View the file
Other files
| File | Type | Posted |
|---|---|---|
| CRP_WFO_Mech_dwgs.pdf | ||
| KCDME062.pdf | ||
| KCCOM041.pdf | ||
| KCCOM051.pdf | ||
| KCDME032.pdf | ||
| KCCOM062.pdf | ||
| KCCOM031.pdf | ||
| KCDME051.pdf | ||
| BMX_WFO_Mech_dwgs.pdf | ||
| 19-00072_-_SF_18_Quote_Form.doc | DOC document | |
| 19-00072_-_SOW-CRP_HVAC_Controls_Replacement_Updated_Rev_4Mar19_-_FBO.pdf | ||
| 19-00072_-_SOW-BMX_HVAC_Controls_November_1,_2018_Rev_4Mar19_-_FBO.pdf | ||
| Calera_AL_SCLS.pdf | ||
| Corpus_Christi_TX_SCLS.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCALE: 1"=20'
SCALE: 1"=20'
10' 60'40'20'0
ELECTRICAL SITE PLAN
NOTES
SEE DWG E10, DETAIL 5, FOR LIGHT POLE DETAIL.
3 SEE DWG E10, DETAIL 6, FOR PHOTOCELL MOUNTING DETAIL.
C
ORANGE
DETECTIVE TAPE
4" PVC (TYP)
FINISHED GRADE
6"
C
CONDUIT SPACERS, ON
APPROX 10' SPACING
CONDUIT TRENCHING
C = COMMUNICATION
TELCO
COMMUNICATIONS
C = COMMUNICATION
CONDUIT TRENCHING
APPROX 10' SPACING
CONDUIT SPACERS, ON
P
6"
FINISHED GRADE
4" PVC (TYP)
DETECTIVE TAPE
ORANGE
C
APPROX 10' SPACING
CONDUIT SPACERS, ON S
C = COMMUNICATION (RGS)
RDA FROM WFO
6"
FINISHED GRADE
3" CONDUIT
DETECTIVE TAPE
GUARD WIRE
ORANGE
#4/0 BARE CU
C
S = SPARE (PVC)
CONDUIT TRENCHING
ORANGE
DETECTIVE TAPE
FINISHED GRADE
P
CONDUIT SPACERS, ON
APPROX 10' SPACING
CONDUIT TRENCHING
P = POWER
SERVICE ENTRANCE
SCALE:
SECTION 1
-NONE
SCALE:
SECTION 2
-NONE
C
6"
SCALE:
SECTION 3
-NONE
U-1
SCALE:
SECTION 4
-NONE
GRANULAR BEDDING
MATERIAL (CLASS C
BEDDING)
MATERIAL (CLASS C
GRANULAR BEDDING
BEDDING)
GRANULAR BEDDING
MATERIAL (CLASS C
BEDDING)
GRANULAR BEDDING
MATERIAL (CLASS C
BEDDING)
SEE SPECIFICATION SECTION 02210 FOR EARTHWORK.
CONDUIT TRENCHING
UPPER AIR FROM WFO
SCALE:
SECTION 5
-NONE
BEDDING)
MATERIAL (CLASS C
GRANULAR BEDDING
C = COMMUNICATION
P
#4/0 BARE CU
ORANGE
GUARD WIRE
DETECTIVE TAPE
4" PVC
FINISHED GRADE
6"P = POWER
CCONDUIT SPACERS, ON
APPROX 10' SPACING
DP-14
7 SEE DWG E10, SECTION 8, FOR TRANSFORMER PAD
P = POWER
COIL 6 FEET OF COPPER GROUND AND/OR GUARD
WIRE AT RDA SITE. LEAVE COILED WIRE SIX INCHES BELOW
GRADE FOR FUTURE CONNECTIONS BY OTHERS.
4" CONDUIT
GROUNDING DETAIL.
CAP AND STAKE CONDUIT FOR FUTURE USE WITH 4"x4"
WOOD POST, 12" ABOVE FINISHED GRADE, PAINTED ORANGE.
OU DO
ASK
VERY
IRST WITH
LWAYS BE
AFETY SHOULD
Y T E F A S
N
OI
T A
R T
SI
NI
M
DA
A
A CIREHPSOMTDN
CI
NA
E
CO
LA
N
OI
T A N
EC
I
FF
O
MA
RGO
RPGNIREENIGNE
LAI
CE
P S
DRAWN
CHECKED
SUP'V. ENGR.
ENGR/PROJ. MGR.
ACOTR./COTR.
SIZE DWG. NO. CLIN. REV.
SPECIAL ENGINEERING PROGRAM OFFICE (SEPO)
NO. DATE PREPARED
BY
CHECKED
BY
ACTR/COTR
APPROVEDAPPROVED
FDI DESCRIPTION OF REVISION
WFO / NEXRAD PROGRAM
PROJECT NO.
PROGRAM MANAGEMENT
SERVICES CONTRACTOR
GOULD EVANS
ARCHITECTS, P.A.
U.S.A.
KANSAS CITY, MO.
FD
SP
K C D M E0
E04 DM 2
CORPUS CHRISTI, TEXAS
WEATHER FORECAST OFFICE
ELECTRICAL
SITE PLAN
L J FOSTER
L J FOSTER
T M SUPER
MJM/TLS
JTS
044131-
DM01
:3
A N J
F17
ROUTE GUARD WIRE AROUND HANDHOLES.
STUB-OUT CONDUIT 5'-0".
SEE DWG E10, DETAIL 1, FOR FLAGPOLE LIGHT DETAIL.
INSTALL LIGHTNING PROTECTION SYSTEM PER
SPECIFICATION SECTION 16000.
SEE DWGS E06, E07, E09 AND E11 FOR DETAILED CONDUIT
LOCATIONS IN THIS AREA.
JOHN PINSON DRIVE
E x x x x x
BUILDINGGRID
NORTH NORTH
8"W
E x x x x
UTILITY XFMR
BUILDING
DDG/STOR
8"W
WFO
FUTURE NEXRAD
RADAR TOWER
(NOT IN CONTRACT)
x x
INFLATION BUILDING
UPPER AIR
E
7 5
11'-0" 22'-0" 22'-0"
2'-0"
F10
F10
F10
F10
F16 F16 F16
4'-0" (TYP)
0"
0"
0"
0"
HANDHOLE #5
HANDHOLE #3
HANDHOLE #6
HANDHOLE #1
F10
HANDHOLE #4
PANEL "PS"
J-BOX (COMM)
SEE DWGS
E06 & E07
SEE DWG E07
DP-14,
PPA-12, SEE
DWG E08
U-1, SEE DWG E06
SEE DWG E07
3/4"C, SEE DWG E08
PPA-12, 2#10,1#12G,
DP-14
(2) 4"PVC (C0MM)
(2) 4"PVC (C0MM)
FUEL TANK
SEE DWG E06
(2) 4"PVC (C0MM)
C
SCALE:
SECTION
CONDUIT TRENCHING
UPPER AIR FROM WFO
C
#4/0 BARE CU
GUARD WIRE
4" PVC (TYP)
C = COMMUNICATION
CONDUIT SPACERS, ON
APPROX 10' SPACING
NONE
6"
C
2 8
ORANGE
DETECTIVE TAPE
MATERIAL (CLASS C
BEDDING)
GRANULAR BEDDING
FINISHED GRADE
DWG S14 (SEE
SEE DETAIL ON
ROHN TOWER #1
NOTE 3)
ROHN TOWER #2
DWG S14 (SEE
NOTE 3)
SEE DETAIL ON
DWG S14
DETAIL ON
SUPPORT SEE
DISH ANTENNA
SEE DETAIL ON
RAIN GAGE PAD
DWG S14
SCALE:
SECTION
NONE
CONDUIT TRENCHING
ROHN TOWER FROM WFO
FINISHED GRADE
GRANULAR BEDDING
MATERIAL (CLASS C
BEDDING)C = COMMUNICATION
APPROX 10' SPACING
CONDUIT SPACERS, ON
P = POWER
DETECTIVE TAPE
ORANGE
4" PVC (TYP)
6"
P C
HANDHOLE #2
4 (1) 4" PVC
(1) 3" RGS
5'-0"
TYPICAL 2 PLACES
SEE DWG E06SEE DWG E06
1 1/2"C, SEE DWG E07
12 13
12 13
#4/0 BARE CU GND WIRE
TO BLDG COUNTERPOISE,
SEE DWG E05
MATERIAL (CLASS C
GRANULAR BEDDING
RAIN GAGE FROM WFO
CONDUIT TRENCHING
SCALE:
SECTION
P = POWER
NONE
4" PVC (TYP)
CONDUIT SPACERS, ON
APPROX 10' SPACING
C = COMMUNICATION
BEDDING)
6"
P C
DETECTIVE TAPE
ORANGE
FINISHED GRADE
SEE DWGS
E06 & E07
SEE DWG E07
HANDHOLE #7
4'-0"Lx4'-0"Wx4'-0"H x x
(TYPICAL
5 PLACES)
INSTALL A 30"HX24"WX8"D J-BOX, HINGED,
NEMA 3R, MOUNTED 5'-6" ABOVE PAD, MOUNT
BOX WITHOUT DRILLING HOLES INTO TOWER.
CONTINUE CONDUITS TO J-BOX WITH FLEXIBLE CONDUITS.
CAP CONDUIT 6" ABOVE TOP OF CONCRETE PAD.
INSTALL 4" PVC CONDUIT 48" BELOW FINISHED GRADE,
FOR UTILITY SERVICE, USE LONG RADIUS ELBOWS FOR
ALL 90% BENDS, LEAVE 12" STUB-UP ABOVE GRADE
CAP AND STAKE.
1 08/16/94 ANJ ADDED UTILITY SERVICE CONDUITS
4"C15
HANDHOLE #8
30'-0"
TMS MJM/RRW FGR/JTS
FGR/JABERP/RRWTMS REVISED PER AS-BUILT CONDITIONSMCK6/6/962
OU DO
ASK
VERY
IRST WITH
LWAYS BE
AFETY SHOULD
Y T E F A S
N
OI
T A
R T
SI
NI
M
DA
A
A CIREHPSOMTDN
CI
NA
E
CO
LA
N
OI
T A N
EC
I
FF
O
MA
RGO
RPGNIREENIGNE
LAI
CE
P S
DRAWN
CHECKED
SUP'V. ENGR.
ENGR/PROJ. MGR.
ACOTR./COTR.
SIZE DWG. NO. CLIN. REV.
SPECIAL ENGINEERING PROGRAM OFFICE (SEPO)
NO. DATE PREPARED
BY
CHECKED
BY
ACTR/COTR
APPROVEDAPPROVED
FDI DESCRIPTION OF REVISION
WFO / NEXRAD PROGRAM
PROJECT NO.
PROGRAM MANAGEMENT
SERVICES CONTRACTOR
GOULD EVANS
ARCHITECTS, P.A.
U.S.A.
KANSAS CITY, MO.
FD
SP
K C D M E0
E04 DM 2
CORPUS CHRISTI, TEXAS
WEATHER FORECAST OFFICE
ELECTRICAL
SITE PLAN
L J FOSTER
L J FOSTER
T M SUPER
MJM/TLS
JTS
044131-
DM01
:3
A N J
E x x x x x x x
HANDHOLE #1HANDHOLE #2
4 (1) 4" PVC
(1) 3" RGS
5'-0" x x
30'-0"
PC NO.
BY
CHECKED
SITE
DATE
FD
SP
PC-07-DM-E04-0
05/18/95
CORPUS CHRISTI, TEXAS
| Model |
| Layout1 |
File details come from the government source that posted it.