KCCOM051.pdf
PDF 53 KB Posted
- Solicitation number
- NWWP4000-19-00072MWH
About this file
Mechanical prints for the two locations
View the file
Other files
| File | Type | Posted |
|---|---|---|
| CRP_WFO_Mech_dwgs.pdf | ||
| KCDME062.pdf | ||
| KCCOM041.pdf | ||
| KCDME042.pdf | ||
| KCDME032.pdf | ||
| KCCOM062.pdf | ||
| KCCOM031.pdf | ||
| KCDME051.pdf | ||
| BMX_WFO_Mech_dwgs.pdf | ||
| 19-00072_-_SF_18_Quote_Form.doc | DOC document | |
| 19-00072_-_SOW-CRP_HVAC_Controls_Replacement_Updated_Rev_4Mar19_-_FBO.pdf | ||
| 19-00072_-_SOW-BMX_HVAC_Controls_November_1,_2018_Rev_4Mar19_-_FBO.pdf | ||
| Calera_AL_SCLS.pdf | ||
| Corpus_Christi_TX_SCLS.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FD
SP
KANSAS CITY, MO.
U.S.A.
ARCHITECTS, P.A.
GOULD EVANS
SERVICES CONTRACTOR
PROGRAM MANAGEMENT
PROJECT NO.
WFO / NEXRAD PROGRAM
DESCRIPTION OF REVISIONFDI
APPROVED APPROVED
ACTR/COTR
BY
CHECKED
BY
PREPAREDDATENO.
SPECIAL ENGINEERING PROGRAM OFFICE (SEPO)
WEATHER FORECAST OFFICE
REV.CLIN.DWG. NO.SIZE
ACOTR./COTR.
ENGR/PROJ. MGR.
SUP'V. ENGR.
CHECKED
DRAWN
S P
EC
IA
L
EN
GIN
EERING PROGRAM
OFF
ICE
N A T
IO
N
AL
OC
EANIC
ND TMOSPH
ER
ICA
A
AD
M
IN
IS
T R A T
IO
N
HVAC
TEMPERATURE CONTROLS
BIRMINGHAM, ALABAMA
R L ANDREWS
L
L
IN CONDUITS (SEE ELECTRICAL DWG E06).
ALL 24 VOLT CONTROL WIRING UNDER THE FLOOR SHALL BE INSTALLED
L
EQUIPMENT SEQUENCE OF CONTROLS
SPACE TEMPERATURE CONTROLSHEATER
ELECTRIC DUCT
MS SD
MS SD
AIR FAN
SUPPLY
FILTER
VALVE
SOLENOID
STEAM
T
H
TEMPERATURE CONTROL LEGEND
MOTOR STARTER
INPUT OR OUTPUT
TEMPERATURE CONTROL PANEL
ROOM HUMIDITY SENSOR
ROOM TEMPERATURE SENSOR
T
SD
DP
MS
HL
L
CONTROL WIRING
H
D
FS
DUCT TEMPERATURE SENSOR
AIRFLOW SWITCH
DIFFERENTIAL PRESSURE SWITCH
DUCT SMOKE DETECTOR
HIGH LIMIT HUMIDISTAT
DUCT HUMIDITY SENSOR
MOTOR OPERATED DAMPER
5.
4.
3.
2.
1.
THE ALARM AND INDICATION LIGHTS PANEL SHALL BE PROVIDED WITH
SUPPLY
AIRAIR
OUTSIDE
AIR
RETURN
DP
B
(109)
ROOM
OPERATIONS
H 8
THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETAILING THE HVAC
CONTROL SYSTEM, POWER WIRING, LOW VOLTAGE CONTROL WIRING, AND
CONNECTIONS NECESSARY TO PROVIDE A COMPLETE AND OPERABLE
TEMPERATURE AND HUMIDITY CONTROL SYSTEM BASED ON THE SCHEMATIC
ALL 24 VOLT CONTROL WIRING SHALL BE FURNISHED AND INSTALLED BY
TEMPERATURE CONTROL CONTRACTOR AND SHALL BE SHIELDED CLASS 2
PLENUM RATED CABLE.
AND SEQUENCE OF OPERATION AS SHOWN ON THIS DRAWING.
SD
TEMPERATURE CONTROL NOTES
DTH
2 1 A 5
T
D A
3T
H 4
DP
C
T
(HU-1)
HUMIDIFIER
FS HLSUPPLY
AIR FAN
COOLING
COIL
F
E
SPACE HUMIDITY
FILTER DIFF PRESSURE
FAN DIFF PRESSURE
R/A HUMIDITY
M/A TEMPERATURE
O/A HUMIDITY
R/A TEMPERATURE
S/A TEMPERATURE
O/A TEMPERATURE
HUMIDIFIER
AHU START/STOP
COOLING
SUPPLY FAN STATUS
DIRTY FILTERS
O/A, R/A DAMPERS
F
E
D
C
B
A
INPUTS OUTPUTS
UNIT
CONDENSING
D
E
COIL
COOLING
T
C
DP
AD
T
3A1
T D
SD
FILTER
B
DP
RETURN
AIR
OUTSIDE
AIR AIR
SUPPLY
L L
L
D
CONDENSING
UNIT
AHU-1, AHU-2 CONTROLS
AHU-3 CONTROLS
OUTPUTSINPUTS
AHU-3 CONTROLS
A
B
C
D
E
O/A, R/A DAMPERS
DIRTY FILTERS
SUPPLY FAN STATUS
COOLING
AHU START/STOP
O/A TEMPERATURE
M/A TEMPERATURE
S/A TEMPERATURE
FAN DIFF PRESSURE
FILTER DIFF PRESSURE
AHU-1, AHU-2 CONTROLS
(EDH-10)
(EDH-1)
ELECTRIC DUCT HEATERSPACE TEMPERATURE
ELECTRIC DUCT HEATERJ
A
INPUTS OUTPUTS
T 1 A
SUPPLY
AIR AIR
SUPPLY
ALL 120 VOLT POWER WIRING TO CONTROL PANELS AND MOTOR OPERATED
DAMPERS SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL
CONTRACTOR (SEE ELECTRICAL DWG E05).
10 COMMERCIAL/GENERATOR
AUTOMATIC
SWITCH
(ATS)
POWER STATUS
TRANSFER
THE FOLLOWING IDENTIFICATION AND INDICATOR LIGHTS (FOR EACH AHU):
SUPPLY FAN OPERATING
SUPPLY FAN FAILURE
CONDENSING UNIT OPERATING
CONDENSING UNIT FAILURE
FILTER CHANGE REQUIRED
GREEN
RED
GREEN
RED
RED
6.
INDICATOR LIGHT (LOCATED IN
ALARM/INDICATION LIGHTS PANEL)
AIR HANDLING UNIT (AHU-1,2)
AIR HANDLING UNIT (AHU-3)
ELECTRIC DUCT HEATERS (EDH)
A SPACE TEMPERATURE SENSOR SHALL MODULATE THE ELECTRIC DUCT HEATER WHEN
HEATING IS REQUIRED.
PACKAGED AIR CONDITIONING UNITS (PAC-1,2)
THE PAC UNITS (PAC-1,2), CONDENSING UNITS (C-1,2) AND THE REMOTE CONTROL
BOX (RCB) ARE GOVERNMENT FURNISHED EQUIPMENT. BOTH PAC UNITS HAVE INTERNAL
CONTROLS AND ARE CONNECTED TO THE RCB. THE RCB CONTROLS THE LEAD/LAG
SEQUENCING OF THE UNITS TO MAINTAIN EQUAL RUN TIME. A HIGH TEMPERATURE
EXHAUST FAN (EF-1)
THE EXHAUST FAN SHALL RUN CONTINUOUSLY.
TRANSFER FAN (TF-2)
THE TRANSFER FAN SHALL RUN CONTINUOUSLY.
HUMIDIFIER (HU-1)
ELECTRIC CONVECTION HEATERS (EH-1, 2)
THE ELECTRIC CONVECTION HEATERS HAVE SELF CONTAINED CONTROLS. THE THERMOSTATS
SHALL BE SET TO MAINTAIN A SPACE TEMPERATURE OF 65°F.
THERMOSTAT IS ALSO CONNECTED TO THE RCB, TO ENERGIZE THE LAG PAC UNIT ON
A HIGH SPACE TEMPERATURE SIGNAL. BOTH PAC UNITS WILL BE ABLE TO RUN IN
THE NORMAL OPERATION MODE. UPON A SIGNAL FROM THE AUTOMATIC TRANSFER
SWITCH (ATS), THE RCB WILL ALLOW ONLY ONE PAC UNIT TO RUN IN THE
EMERGENCY OPERATION MODE.
SPACE TEMPERATURE
THE HUMIDIFIER SHALL NOT BE ALLOWED TO OPERATE UNLESS THE AIR HANDLING UNIT
SUPPLY AIR FAN IS IN OPERATION. AN AIR FLOW SWITCH SHALL DE-ENERGIZE THE
HUMIDIFIER UPON LOSS OF AIRFLOW. THE STEAM SOLENOID VALVES SHALL BE
INTERLOCKED TO OPEN WHEN THE CORRESPONDING AIR HANDLING UNIT IS IN OPERATION.
THE SPACE HUMIDITY SENSOR SHALL MODULATE THE HUMIDIFIER. WHEN THE HUMIDIFIER
IS ENERGIZED, THE SUPPLY AIR TEMPERATURE SHALL BE RESET TO 65°F. WHEN THE
HUMIDIFIER IS DE-ENERGIZED, SUPPLY AIR TEMPERATURE SHALL BE SET BACK TO 55°F.
A SIGNAL FROM THE HIGH-LIMIT HUMIDITY SENSOR SHALL DE-ENERGIZE THE HUMIDIFIER.
AIR HANDLING UNIT 3 (AHU-3) SERVES THE ADMINISTRATION AREA AND OPERATES ON
(1) ONE STAGE COOLING;
(2) OUTSIDE AIR ECONOMIZER CYCLE IS CONTROLLED BY OUTSIDE AIR TEMPERATURE;
(3) NO HUMIDITY CONTROL.
AHU-3, ACU-3 AND ASSOCIATED ELECTRIC DUCT HEATERS SHALL NOT OPERATE ON
EMERGENCY POWER. UPON RESTORATION OF COMMERCIAL POWER, AHU-3, ACU-3 AND
ASSOCIATED ELECTRIC DUCT HEATERS SHALL RETURN TO NORMAL OPERATING MODE.
AN 8-HOUR SCHEDULE. PROGRAM NIGHT SETBACK. THE OPERATION OF AHU-3 IS
SIMILAR TO AIR HANDLING UNITS 1 & 2 WITH THE FOLLOWING EXCEPTIONS:
AIR HANDLING UNITS 1 AND 2 (AHU-1, 2) SERVE THE OPERATIONS AREA AND ARE
OPERATED ON A 24-HOUR SCHEDULE. ONLY ONE AIR HANDLING UNIT SHALL OPERATE,
AND THE NON-OPERATING UNIT SHALL SERVE AS A BACK-UP. THE BACK-UP UNIT SHALL
BE STARTED AUTOMATICALLY UPON FAILURE OF THE OTHER UNIT. AHU-1 AND 2 SHALL BE
PROGRAMMED TO ALTERNATE TO MAINTAIN EQUAL RUN TIME. THE SUPPLY AIR FAN SHALL
RUN CONTINUOUSLY. A SUPPLY AIR TEMPERATURE SENSOR SHALL MODULATE THE AIR
TEMPERATURE SENSOR WITH THE MAXIMUM COOLING DEMAND. AN OUTSIDE AIR ECONOMIZER
CYCLE SHALL BE PROVIDED WITH ENTHALPY CONTROL. A MIXED AIR TEMPERATURE SENSOR
SHALL MODULATE THE OUTSIDE AND RETURN AIR DAMPERS DURING THE ECONOMIZER CYCLE.
MINIMUM OUTSIDE AIR SHALL BE PROVIDED WHEN THE UNIT IS NOT IN ECONOMIZER CYCLE.
HUMIDITY SHALL BE CONTROLLED BY A SPACE HUMIDITY SENSOR. HEATING WILL BE
PROVIDED BY INDIVIDUAL ELECTRIC DUCT HEATERS (EDH). SMOKE DETECTORS, IN THE
SUPPLY AND RETURN AIR DUCTWORK, SHALL DE-ENERGIZE THE SUPPLY AIR FAN UPON
COOLED CONDENSING UNIT (ACU) TO MAINTAIN 55°F DISCHARGE AIR TEMPERATURE. THE
COMPRESSOR SHALL BE EQUIPPED WITH A CYLINDER UNLOADER FOR TWO STAGES OF
COOLING. THE SUPPLY AIR TEMPERATURE SHALL BE RESET TO SATISFY THE ROOM
STM
G L
L
L
L F
T 7
R/A TEMPERATURE7
6 CONDENSING UNIT
CONTROL SAFETIES
CONDENSING UNIT
SAFETIESF
CONTROL SAFETIES
CONDENSING UNIT11
G STATUS
CONDENSING UNIT
E
SENSING SMOKE. UPON LOSS OF COMMERCIAL POWER, THE AIR HANDLING UNIT SHALL BE
PROGRAMMED FOR A TIMED DELAY RESTART. ELECTRIC DUCT HEATER EDH-2 SHALL NOT
OPERATE ON EMERGENCY POWER.
(NC - NORMALLY CLOSED)
(NO - NORMALLY OPEN)
(NC)
(NO)
(NC)
(NO)
SET ROOM TEMPERATURE AT 72°F FOR ALL AREAS SERVED BY AHU-1 AND
AHU-2, AND 78°F FOR ALL AREAS SERVED BY AHU-3. SET ROOM HUMIDITY
AT 50% RELATIVE HUMIDITY.
SET ALTERNATING TIME OF AHU-1 & 2, AND PAC-1 & 2 FOR 84
HOUR INTERVALS.
7.
CO01
449404- 5 M05 CO 1
S MINO
D FULCHER
BLR/TLS
JAB
1 10/7/94 SJL D FULCHER BLR/TLS JAB REVISED PER AS-BUILT CONDITIONS
9:
S
JL
2/
1= 1' K
C C O M