FY14 CoF Repair Aircraft Hangar Fire Protection Systems EDM1719 Primary Scope
SECTION 09 51 00
ACOUSTICAL CEILINGS
08/10
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A489 (2012) Standard Specification for Carbon Steel Lifting Eyes
ASTM A641/A641M (2009a) Standard Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM C423 (2009a) Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method
ASTM C635/C635M (2013) Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-In Panel Ceilings
ASTM C636/C636M (2013) Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels
ASTM C834 (2010) Latex Sealants
ASTM E119 (2012a) Standard Test Methods for Fire Tests of Building Construction and Materials
ASTM E1264 (2008; E 2010) Acoustical Ceiling Products
ASTM E1414/E1414M (2011a) Airborne Sound Attenuation Between Rooms Sharing a Common Ceiling Plenum
ASTM E1477 (1998a; R 2013) Luminous Reflectance Factor of Acoustical Materials by Use of Integrating-Sphere Reflectometers
ASTM E580/E580M (2011b) Application of Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels in Areas Requiring Moderate Seismic Restraint
ASTM E795 (2005; R 2012) Mounting Test Specimens During Sound Absorption Tests
ASTM E84 (2012c) Standard Test Method for Surface
SECTION 09 51 00 Page 1
Burning Characteristics of Building Materials
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-310-04 (2012) Seismic Design for Buildings
UNDERWRITERS LABORATORIES (UL)
UL Fire Resistance (2012) Fire Resistance Directory
1.2 SYSTEM DESCRIPTION
Provide sound controlling units mechanically mounted on a ceiling suspension system for acoustical treatment. The unit size, texture, finish, and color must be as specified. The location and extent of acoustical treatment shall be as shown on the approved detail drawings.
Submit drawings showing suspension system, method of anchoring and fastening, details, and reflected ceiling plan. Coordinate with paragraph RECLAMATION PROCEDURES for reclamation of mineral fiber acoustical ceiling panels to be removed from the job site.
1.2.1 Fire Resistive Ceilings
Rate acoustical ceiling systems, indicated as fire resistant, for fire endurance as specified when tested in accordance with ASTM E119. Provide ceiling assembly rating for 1 hour as shown on drawings. Provide acoustical units with a flame spread of 25 or less and smoke development of 50 or less when tested in accordance with ASTM E84.
1.2.2 Ceiling Attenuation Class and Test
Provide a ceiling system with an attenuation class (CAC) of 40 minimum when determined in accordance with ASTM E1414/E1414M. Provide fixture attenuators over light fixtures and other ceiling penetrations, and provide acoustical blanket insulation adjacent to partitions, as required to achieve the specified CAC. Provide test ceiling continuous at the partition and assembled in the suspension system in the same manner that the ceiling will be installed on the project.
1.2.3 Ceiling Sound Absorption
Determine the Noise Reduction Coefficient (NRC) in accordance with ASTM C423 Test Method.
1.2.4 Light Reflectance
Determine light reflectance factor in accordance with ASTM E1477 Test Method.
1.2.5 Other Submittals Requirements
The following shall be submitted:
a. Manufacturer's data indicating percentage of recycle material in acoustic ceiling tiles to verify affirmative procurement compliance.
b. Total weight and volume quantities of acoustic ceiling tiles with recycle material.
SECTION 09 51 00 Page 2
c. Manufacturer's catalog showing UL classification of fire-rated ceilings giving materials, construction details, types of floor and roof constructions to be protected, and UL design number and fire protection time rating for each required floor or roof construction and acoustic ceiling assembly.
d. Reports by an independent testing laboratory attesting that acoustical ceiling systems meet specified fire endurance and sound transmission requirements. Data attesting to conformance of the proposed system to Underwriters Laboratories requirements for the fire endurance rating listed in UL Fire Resistance may be submitted in lieu of test reports.
e. Certificate attesting that the mineral based acoustical units furnished for the project contain recycled material and showing an estimated percent of such material.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Approved Detail Drawings
SD-03 Product Data
Acoustical Ceiling Systems
SD-04 Samples
Acoustical Units Acoustic Ceiling Tiles
SD-06 Test Reports
Fire Resistive Ceilings Ceiling Attenuation Class and Test
SD-07 Certificates
Acoustical Units Acoustic Ceiling Tiles
1.4 DELIVERY, STORAGE. AND HANDLING
Deliver materials to the site in the manufacturer's original unopened containers with brand name and type clearly marked. Carefully handle and store materials in dry, watertight enclosures. Immediately before installation, store acoustical units for not less than 24 hours at the same temperature and relative humidity as the space where they will be installed in order to assure proper temperature and moisture acclimation.
SECTION 09 51 00 Page 3
1.5 ENVIRONMENTAL REQUIREMENTS
Maintain a uniform temperature of not less than 60 degrees F nor more than 85 degrees F and a relative humidity of not more than 70 percent for 24 hours before, during, and 24 hours after installation of acoustical units.
1.6 SCHEDULING
Complete and dry interior finish work such as plastering, concrete and terrazzo work before ceiling installation. Complete mechanical, electrical, and other work above the ceiling line; install and start operating heating, ventilating, and air conditioning systems in order to maintain temperature and humidity requirements.
1.7 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a one year period. Include an agreement to repair or replace acoustical panels that fail within the warranty period in the standard performance guarantee or warranty. Failures include, but are not limited to, sagging and warping of panels; rusting and manufacturers defects of grid system.
1.8 EXTRA MATERIALS
Furnish spare tiles, from the same lot as those installed, of each color at the rate of 20 tiles for each 1000 tiles installed.
PART 2 PRODUCTS
2.1 ACOUSTICAL UNITS
Comply with EPA requirements in accordance with Section 01 62 35 RECYCLED/RECOVERED/BIOBASED MATERIALS. Submit two samples of each type of acoustical unit and each type of suspension grid tee section showing texture, finish, and color. Conform acoustical units to ASTM E1264, Class A, and the following requirements:
2.1.1 Affirmative Procurement
Mineral Wool, Cellulose, and Laminated Paperboard used in acoustic ceiling tiles are materials listed in the EPA's Comprehensive Procurement Guidelines (CPG) (http://www.epa.gov/cpg/). EPA's recommended Recovered Materials Content Levels for Mineral Wool, Cellulose, Structural Fiberboard and Laminated Paperboard are:
Product Material Percent of Post Consumer Materials
Percent of Total Recovered Materials
Laminate Paperboard
Post Consumer Paper
100 100
Rock Wool Slag 75
Cellulose Post Consumer Paper
75 75
a. The recommended recovered materials content levels are based on the weight (not volume) of materials in the insulating core only.
SECTION 09 51 00 Page 4
b. Submit recycled material content data for acoustic ceiling tiles indicating compliance with affirmative procurement.
c. Submit total weight and volume quantities of acoustic ceiling tiles with recycle material.
2.1.2 Units for Exposed-Grid System
a. Type: I (cellulose composition).
b. Flame Spread: Class A, 25 or less
c. Pattern: A .
d. Minimum NRC: 0.75 in open office areas; 0.60 in conference rooms, executive offices, teleconferencing rooms, and other rooms as designated; 0.50 in all other rooms and areas when tested on mounting Type E-400 of ASTM E795.
e. Minimum Light Reflectance Coefficient: LR-1, 0.75 or greater.
f. Nominal size: 24 by 48 inch.
g. Edge detail: Reveal .
h. Finish: Factory-applied standard finish .
i. Minimum CAC: 40.
2.1.3 Unit Acoustical Absorbers
Absorbers shall be individually mounted sound absorbing plaques composed of glass fibers or non-asbestos mineral fibers and having a NRC range of not less than 0.60 - 0.70 when tested in accordance with ASTM C423 and reported as a 4 frequency average.
2.2 SUSPENSION SYSTEM
Provide standard exposed-gridwidth flange suspension system conforming to ASTM C635/C635M. Provide surfaces exposed to view of aluminum or steel with a factory-applied white baked-enamel finish. Provide wall molding having a flange of not less than 15/16 inch. Provide inside and outside corner caps . Suspended ceiling framing system must have the capability to support the finished ceiling, light fixtures, air diffusers, and accessories, as shown. Provide a suspension system with a maximum deflection of 1/360 of the span length. Conform seismic details to the guidance in UFC 3-310-04 and ASTM E580/E580M.
2.3 HANGERS
Provide hangers and attachment capable of supporting a minimum 300 pound ultimate vertical load without failure of supporting material or attachment.
2.3.1 Wires
Conform wires to ASTM A641/A641M, Class 1, 0.08 inch (12 gauge).
SECTION 09 51 00 Page 5
2.3.2 Rods
Provide 3/16 inch diameter threaded steel rods, zinc or cadmium coated.
2.3.3 Eyebolts
Provide eyebolts of weldless, forged-carbon-steel, with a straight-shank in accordance with ASTM A489. Eyebolt size must be a minimum 1/4 inch, zinc coated.
2.3.4 Masonry Anchorage Devices
Comply with ASTM C636/C636M for anchorage devices .
2.4 ADHESIVE
Use adhesive as recommended by tile manufacturer.
2.5 FINISHES
Use manufacturer's standard textures, patterns and finishes as specified for acoustical units and suspension system members. Treat ceiling suspension system components to inhibit corrosion.
2.6 COLORS AND PATTERNS
Use colors and patterns for acoustical units and suspension system components in Conference Rooms 113A & B; Armstrong Ultima and tegular Lay-In and Second Floor Conference Room 230; Armstrong Cloud Cirrus Second Look, Scored Tegular, Medium Texture Linear Tile or approved equal.
2.7 ACOUSTICAL SEALANT
Conform acoustical sealant to ASTM C834, nonstaining.
PART 3 EXECUTION
3.1 INSTALLATION
Examine surfaces to receive directly attached acoustical units for unevenness, irregularities, and dampness that would affect quality and execution of the work. Rid areas, where acoustical units will be cemented, of oils, form residue, or other materials that reduce bonding capabilities of the adhesive. Complete and dry interior finish work such as plastering, concrete, and terrazzo work before installation. Complete and approve mechanical, electrical, and other work above the ceiling line prior to the start of acoustical ceiling installation. Provide acoustical work complete with necessary fastenings, clips, and other accessories required for a complete installation. Do not expose mechanical fastenings in the finished work. Lay out hangers for each individual room or space. Provide hangers to support framing around beams, ducts, columns, grilles, and other penetrations through ceilings. Keep main runners and carrying channels clear of abutting walls and partitions. Provide at least two main runners for each ceiling span. Wherever required to bypass an object with the hanger wires, install a subsuspension system so that all hanger wires will be plumb.
SECTION 09 51 00 Page 6
3.1.1 Suspension System
Install suspension system in accordance with ASTM C636/C636M and as specified herein. Do not suspend hanger wires or other loads from underside of steel decking.
3.1.1.1 Plumb Hangers
Install hangers plumb and not pressing against insulation covering ducts and pipes. Where lighting fixtures are supported from the suspended ceiling system, provide hangers at a minimum of four hangers per fixture and located not more than 6 inch from each corner of each fixture.
3.1.1.2 Splayed Hangers
Where hangers must be splayed (sloped or slanted) around obstructions, offset the resulting horizontal force by bracing, countersplaying, or other acceptable means.
3.1.2 Wall Molding
Provide wall molding where ceilings abut vertical surfaces. Miter corners where wall moldings intersect or install corner caps. Secure wall molding not more than 3 inch from ends of each length and not more than 16 inch on centers between end fastenings. Provide wall molding springs at each acoustical unit in semi-exposed or concealed systems.
3.1.3 Acoustical Units
Install acoustical units in accordance with the approved installation instructions of the manufacturer. Ensure that edges of acoustical units are in close contact with metal supports, with each other, and in true alignment. Arrange acoustical units so that units less than one-half width are minimized. Hold units in exposed-grid system in place with manufacturer's standard hold-down clips, if units weigh less than 1 psf or if required for fire resistance rating.
3.1.4 Caulking
Seal all joints around pipes, ducts or electrical outlets penetrating the ceiling. Apply a continuous ribbon of acoustical sealant on vertical web of wall or edge moldings.
3.1.5 Adhesive Application
Wipe back of tile to remove accumulated dust. Daub acoustical units on back side with four equal daubs of adhesive. Apply daubs near corners of tiles. Ensure that contact area of each daub is at least 2 inch diameter in final position. Press units into place, aligning joints and abutting units tight and uniform without differences in joint widths.
3.2 CEILING ACCESS PANELS
Locate ceiling access panels directly under the items which require access.
3.3 CLEANING
Following installation, clean dirty or discolored surfaces of acoustical units and leave them free from defects. Remove units that are damaged or
SECTION 09 51 00 Page 7 improperly installed and provide new units as directed.
3.4 RECLAMATION PROCEDURES
Neatly stack ceiling tile, designated for recycling by the Contracting Officer, on 4 by 4 foot pallets not higher than 4 foot. Panels must be completely dry. Shrink wrap and symmetrically stack pallets on top of each other without falling over.
-- End of Section --