Att_1_ECW-50_Specifications.docx
DOCX document 52 KB Posted
- Attached to
- Electronics Cooling Water (ECW-50) Federal contract opportunity
- Solicitation number
- N68335-19-R-0202
About this file
Attachment 1, Specification
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions_Round_5.pdf | ||
| Questions_round_4.pdf | ||
| Questions_round_3.pdf | ||
| Questions_round_2.pdf | ||
| Questions_and_answers_WE_9.14.19.pdf | ||
| Att_3_Cross_Reference_Matrix_Template.docx | DOCX document | |
| ATT_2_P1_Pricing_Spreadsheet_SSP.xlsx | XLSX spreadsheet | |
| N68335-19-R-0202_1.docx | DOCX document | |
| Exhibit_A_ECW-50_CDRLs__05.15.19.pdf | ||
| ATT_4_Data_Item_Transmittal_Acceptance_Rejection_Form_.doc | DOC document | |
| Exhibit_A_ECW-50_CDRLs__05.15.19.pdf | ||
| ATT_2_P1_Pricing_Spreadsheet_SSP.xlsx | XLSX spreadsheet | |
| Att_1_ECW-50_Specifications.docx | DOCX document | |
| N68335-19-R-0202.docx | DOCX document | |
| ATT_4_Data_Item_Transmittal_Acceptance_Rejection_Form_.doc | DOC document | |
| Att_3_Cross_Reference_Matrix_Template.docx | DOCX document |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ECW-50 system Requirement Report Author: MB Revision: 1.0 Document Number: 4K7_ECW50_001
| Distribution D: |
| Other requests for this document shall be referred to the Naval Air Warfare Center Aircraft Division, Code 4.11.7 Bldg. 8271, 17454 Webster Field Road, St. Inigoes MD 20684-4012. |
Date: January 29, 2019
REVISION HISTORY
| Revision |
| Date |
| Reason For Changes |
| Author |
| 0.1 |
| May 15, 2018 |
| <Initial draft> |
| Marta Bierria |
| 0.2 |
| January 16, 2019 |
| Technical updates & minor fixes |
| Trevor Smith |
| 0.3 |
| January 29, 2019 |
| -SPN-43 replacement requirements humidity range added to 2.6 |
-added Distribution D statement -Header removals with minor editing -Rational removals David Nelson
TABLE OF CONTENTS
| Introduction | 1 |
| Purpose | 1 |
| Scope | 1 |
| 1 Meet SPN-50 cooling needs | 2 |
| 1.1 Meet cooling needs of the SPN-50 SSTX | 2 |
| 1.1.1 Minimum water flow rate for SSTX | 2 |
| 1.1.2 SSTX input water pressure | 2 |
| 1.1.3 Temperature of the chilled water for SSTX | 2 |
| 1.1.4 SSTX heat transfer need | 2 |
| 1.1.5 SSTX Proof pressure | 2 |
| 1.2 Meet cooling needs of the SPN-50 SDU 1 | 3 |
| 1.2.1 Minimum Water flow rate for SDU 1 | 3 |
| 1.2.2 SDU 1 input water pressure | 3 |
| 1.2.3 Temperature of the chilled water for SDU 1 | 3 |
| 1.2.4 SDU 1 heat transfer need | 3 |
| 1.2.5 SDU 1 proof pressure | 3 |
| 1.3 Meet cooling needs of the SPN-50 SDU 2 | 4 |
| 1.3.1 Minimum Water flow rate for SDU 2 | 4 |
| 1.3.2 SDU 2 input water pressure | 4 |
| 1.3.3 Temperature of the chilled water for SDU 2 | 4 |
| 1.3.4 SDU 2 heat transfer need | 4 |
| 1.3.5 SDU 2 proof pressure | 4 |
| 2 Integrate into Shipboard Environment Constraints | 5 |
| 2.1 Meet shipboard power requirements | 5 |
| 2.2 Meet shock requirements | 5 |
| 2.3 Ship power characteristics | 5 |
| 2.4 Withstand ship ambient temperature | 5 |
| 2.5 Operate after storage temperatures | 5 |
| 2.6 Operate in ship humidity levels | 5 |
| 2.7 Operate in dusty conditions | 6 |
| 2.8 Resist effects of corrosion due to salt | 6 |
| 2.9 Shipboard Chilled Water Characteristics | 6 |
| 2.10 Shipboard Electromagnetic Environment Requirements | 6 |
| 2.11 Shipboard Accessibility | 7 |
| 2.12 Meet vibration requirements | 7 |
| 3 Human Engineering Design Criteria | 7 |
| 3.1 Warning of unsafe function | 7 |
| 3.2 Eliminate/cover up unsafe objects | 7 |
| 3.3 Safety marking - installation | 7 |
| 3.4 Safety marking - maintenance | 8 |
| 3.5 Safety marking - operation | 8 |
| 3.6 Safety marking - repair | 8 |
| 3.7 Safety marking - replacement | 8 |
| 3.8 Safety marking - points of access and barriers | 8 |
| 3.9 Safety marking - hazardous material | 8 |
| 3.10 Protect personnel from hazards | 8 |
| Appendix A: Requirements Table | 10 |
| Meet SPN-50 cooling needs Table | 10 |
TABLE OF FIGURES
Figure 1. Meet SPN-50 cooling needs Table 10
EXECUTIVE SUMMARY
This document captures high level system requirements for the SPN-50 Radar System Electronic Cooled Water (ECW-50) system.
ECW-50 system Date: January 29, 2019 Requirement Report Document Number: 4K7_ECW50_001
Use or disclosure of data contained on this sheet is subject to the restrictions on the title page i
Introduction Purpose This document provides ECW-50 system requirements with their properties including requirement ID, requirement name, requirement text, and requirement source where applicable. The numbering schema of the requirements ID shows the requirement traceability, meaning requirement with the ID 1.1 represent a child requirement of the requirement with the ID 1, requirement with the ID 1.1.1 is a child requirement of the requirement with the ID 1.1 The children requirements are also considered derived requirements and are intended to further refine the higher level requirement to facilitate the ECW-50 system design.
Scope The ECW-50 system is a liquid cooling system that will provide chilled liquid to the SPN-50 Radar System components that are designed to rely on the liquid cooling to dissipate the large amounts of heat generated by those components. The SPN-50 radar system components that require liquid cooling are Solid State Transmitter (SSTX), and two Signal Data Units (SDUs).
The ECW-50 system will be installed with the SPN-50 onboard the CVN and L-class ships and must integrated into existing shipboard environment with minimum impact.
The ECW-50 system has to meet the Grade A shock and vibration requirements as defined in the MIL-DTL-901E.
Use or disclosure of data contained on this sheet is subject to the restrictions on the title page
1 Meet SPN-50 cooling needs
1.1 Meet cooling needs of the SPN-50 SSTX
1.1.1 Minimum water flow rate for SSTX
The ECW-50 system shall provide, to the SPN-50 SSTX, chilled water with the minimum water flow rate of 9.7 Gallons per Minute (GPM).
1.1.2 SSTX input water pressure
The ECW-50 system shall provide, to the SPN-50 SSTX, chilled water at a minimum pressure of 26 psi, which is equal to the pressure drop through the SSTX at the 9.7 GPM minimum flowrate, and a maximum pressure of 108 psi.
1.1.3 Temperature of the chilled water for SSTX
The ECW-50 system shall provide, to the SPN-50 SSTX, water at the temperature of greater than or equal to 41 deg. F and less than or equal to 59 deg. F.
1.1.4 SSTX heat transfer need
The ECW-50 system shall support the estimated SPN-50 SSTX heat emission to cooling water of 11 kW (37,534 BTU/h).
1.1.5 SSTX Proof pressure
The ECW-50 system shall have provisions to ensure that the maximum pressure of the chilled water at the inlet of the SSTX will not exceed 150 psi.
1.1.6 SSTX coupling
The ECW-50 system shall connect to the AN/SPN-50 SSTX using 1.3125-12 UNJ connector.
1.2 Meet cooling needs of the SPN-50 SDU 1
1.2.1 Minimum Water flow rate for SDU 1
The ECW-50 system shall provide, to the SPN-50 SDU 1, chilled water with the minimum water flow rate of 1.6 Gallons per Minute (GPM).
1.2.2 SDU 1 input water pressure
The ECW-50 system shall provide, to the SPN-50 SDU 1, chilled water at a minimum pressure of 1.6 psi, which is equal to the pressure drop through the SDU at the 1.6 GPM minimum flowrate, and a maximum pressure of 58 psi.
1.2.3 Temperature of the chilled water for SDU 1
The ECW-50 system shall provide, to the SPN-50 SDU 1, water at the temperature of greater than or equal to 41 deg. F and less than or equal to 59 deg. F.
1.2.4 SDU 1 heat transfer need
The ECW-50 system shall support the SPN-50 SDU 1 heat emission to cooling water of 1.3 kW (4,306 BTU/h).
1.2.5 SDU 1 proof pressure
The ECW-50 system shall have provisions to ensure that the maximum pressure of the chilled water at the inlet of the SDU 1 will not exceed 80 psi.
1.2.6 SDU 1 coupling
The ECW-50 system shall connect to the AN/SPN-50 SDU1 using 0.8750-14 UNJF connector.
1.3 Meet cooling needs of the SPN-50 SDU 2
1.3.1 Minimum Water flow rate for SDU 2
The ECW-50 system shall provide, to the SPN-50 SDU 2, chilled water with the minimum water flow rate of 1.6 Gallons per Minute (GPM).
1.3.2 SDU 2 input water pressure
The ECW-50 system shall provide, to the SPN-50 SDU 2, chilled water at a minimum pressure of 1.6 psi, which is equal to the pressure drop through the SDU at the 1.6 GPM minimum flowrate, and a maximum pressure of 58 psi.
1.3.3 Temperature of the chilled water for SDU 2
The ECW-50 system shall provide, to the SPN-50 SDU 2, water at the temperature of greater than or equal to 41 deg. F and less than or equal to 59 deg. F.
1.3.4 SDU 2 heat transfer need
The ECW-50 system shall support the SPN-50 SDU 2 heat emission to cooling water of 1.3 kW (4,306 BTU/h).
1.3.5 SDU 2 proof pressure
The ECW-50 system shall have provisions to ensure that the maximum pressure of the chilled water at the inlet of the SDU 2 will not exceed 80 psi.
1.3.6 SDU 2 coupling
The ECW-50 system shall connect to the AN/SPN-50 SDU2 using 0.8750-14 UNJF connector.
2 Integrate into Shipboard Environment Constraints
2.1 Meet shipboard power requirements
The ECW-50 system shall use the ship AC power that conforms to the MIL-STD-1399-300.
2.2 Meet shock requirements
The ECW-50 system shall meet Grade A shock requirements specified in MIL-DTL-901E.
2.3 Ship power characteristics
The ECW-50 system shall use a type 1, 60 Hz, 440 VAC, 3 phase, Delta ship power.
2.4 Withstand ship ambient temperature
The ECW-50 system equipment mounted in conditioned areas shall operate during and after exposure to ambient air temperature extremes of a minimum of 0 deg. C (32 deg. F) to a maximum of +50 deg. C (+122 deg. F) in accordance with MIL-STD-810G method 501.5 (High Temperature) and 502.3 (Low Temperature).
2.5 Operate after storage temperatures
The ECW-50 system shall operate without any degradation in performance after exposure to storage temperatures of a minimum of -46 deg. C (-50 deg. F) to a maximum of +70 deg. C (+158 deg. F) in accordance with MIL-STD-810G Method 501.5 (High Temperature) and 502.5 (Low Temperature).
2.6 Operate in ship humidity levels
The ECW-50 system shall operate in the ship humidity of 0 – 95%
2.7 Operate in dusty conditions
The ECW-50 system shall operate during and after exposure to dust as described in MIL-STD-810G, Method 510.5
2.8 Resist effects of corrosion due to salt
The ECW-50 system shall resist the effects of corrosive environment due to salt spray/fog in accordance with MIL-STD-810G, Method 503.5
2.9 Shipboard Chilled Water Characteristics
The ECW-50 system shall connect to the ship’s chilled water system and interface with water that meets the purity specifications as defined in the DOD-STD-1399 Section 532 paragraph 5.2.1.
Chilled water that (1) has a maximum oxygen concentration of 0.5 parts per million by weight, (2) contains solids whose size will be less than or equal to 0.5 micrometers, and (3) has conductivity less than or equal to 2.0 mircosiemens per centimeter corrected to 25 deg. C (77 deg. F)
2.10 Shipboard Electromagnetic Environment Requirements
The ECW-50 system shall meet applicable MIL-STD-464C/461G requirements for shipboard equipment installed below decks. At a minimum, the following MIL-STD-461 requirements must be met:
· CE101: Conducted emissions, power leads, 30 Hz to 10 kHz (MIL-STD-461G, fig. CE101-2).
· CE102: Conducted emissions, power leads, 10 kHz to 10 MHz (MIL-STD-461G, fig. CE102-1).
· CS101: Conducted susceptibility, power leads, 30 Hz to 150 kHz (MIL-STD-461G, fig. CS101-1, Curve #1).
· CS114: Conducted susceptibility, 10 kHz to 200 MHz (MIL-STD-461G, fig. CS114-1, curve #2).
· CS116: Conducted susceptibility, 10 kHz to 100 MHz (MIL-STD-461G, fig. CS116-2).
· CS118: Conducted susceptibility, personnel borne electrostatic discharge.
· RE101: Radiated emissions, magnetic field, 30 Hz to 100 kHz (MIL-STD-461G, fig. RE101-2).
· RE102: Radiated emissions, electric field, 10 kHz to 10 times the highest internally-generated frequency produced by the EUT (MIL-STD-461G, fig. RE102-1, Below Decks limit).
· RS101: Radiated susceptibility, magnetic fields, 30 Hz to 100 kHz (MIL-STD-461G, fig RS101-1).
· RS103: Radiated susceptibility, electric fields, 2 MHz to 18 GHz at levels up 10V/m (MIL-STD-461G, Table XI).
2.11 Shipboard Accessibility
The ECW-50 system shall be hatchable for US Navy Carrier and Amphibious Assault ships.
2.12 Meet vibration requirements
The ECW-50 system shall meet Type I vibration requirements specified in MIL-STD-167-1A.
3 Human Engineering Design Criteria
3.1 Warning of unsafe function
In accordance with MIL-STD-1472G: the ECW-50 system shall provide visual, or audible, safety warnings, cautions, of unsafe functions and/or conditions that could contribute to a safety hazard to the system user.
3.2 Eliminate/cover up unsafe objects
In accordance with MIL-STD-1472G, the ECW-50 system hazards, such as sharp corners, projections, moving parts, electrical potential and any other elements that could cause injury, shall be eliminated or covered with protective shields or guards.
3.3 Safety marking - installation
In accordance with MIL-STD-1472G, the ECW-50 system shall be marked when safety hazards are present during the installation of system equipment or parts thereof.
3.4 Safety marking - maintenance
The ECW-50 system shall be marked when safety hazards are present during the maintenance of the system equipment or parts thereof.
3.5 Safety marking - operation
The ECW-50 system shall be marked when safety hazards are present during the operation of the system equipment or parts thereof.
3.6 Safety marking - repair
The ECW-50 system shall be marked when safety hazards are present during the repair of the system equipment or parts thereof.
3.7 Safety marking - replacement
The ECW-50 system shall be marked when safety hazards are present during the replacement of the system equipment or parts thereof.
3.8 Safety marking - points of access and barriers
The ECW-50 system guards, barriers, access doors, covers and plates shall be marked when they protect personnel from safety hazards.
3.9 Safety marking - hazardous material
The ECW-50 system parts containing hazardous material shall be marked with appropriate hazard warnings in accordance with MIL-STD-129R.
3.10 Protect personnel from hazards
The ECW-50 system shall protect personnel from conditions that create risk of death, injury, acute chronic illness throughout the system life-cycle in accordance with MIL-STD-1472G.
Appendix A: Requirements Table Meet SPN-50 cooling needs Table
Meet SPN-50 cooling needs Table
| ID |
| Name |
| Text |
| Requirement Type |
| Owner |
1.1.1
Minimum water flow rate for SSTX The ECW-50 system shall provide, to the SPN-50 SSTX, chilled water with the minimum water flow rate of 9.7 Gallons per Minute (GPM).
Requirement
Meet cooling needs of the SPN-50 SSTX [Meet SPN-50 cooling needs]
1.1.2
SSTX input water pressure The ECW-50 system shall provide, to the SPN-50 SSTX, chilled water at a minimum pressure of 26 psi, which is equal to the pressure drop through the SSTX at the 9.7 GPM minimum flowrate, and a maximum pressure of 108 psi.
Requirement
Meet cooling needs of the SPN-50 SSTX [Meet SPN-50 cooling needs]
1.1.3
Temperature of the chilled water for SSTX
| The ECW-50 system shall provide, to the SPN-50 SSTX, water at the temperature of greater than or equal to 41 deg. F and less than or equal to 59 deg. F. |
| Requirement |
Meet cooling needs of the SPN-50 SSTX [Meet SPN-50 cooling needs]
1.1.4
SSTX heat transfer need The ECW-50 system shall support the SPN-50 SSTX heat emission to cooling water of 11 kW (37,534 BTU/h).
Requirement
Meet cooling needs of the SPN-50 SSTX [Meet SPN-50 cooling needs]
1.1.5
SSTX Proof pressure
| The ECW-50 system shall have provisions to ensure that the maximum pressure of the chilled water at the inlet of the SSTX will not exceed 150 psi. |
| Requirement |
Meet cooling needs of the SPN-50 SSTX [Meet SPN-50 cooling needs]
1.1.6
SSTX coupling The ECW-50 system shall connect to the AN/SPN-50 SSTX using 1.3125-12 UNJ connector.
Requirement
Meet cooling needs of the SPN-50 SSTX [Meet SPN-50 cooling needs]
1.2
1.2.1
Minimum Water flow rate for SDU 1 The ECW-50 system shall provide, to the SPN-50 SDU 1, chilled water with the minimum water flow rate of 1.6 Gallons per Minute (GPM).
Requirement
Meet cooling needs of the SPN-50 SDU 1 [Meet SPN-50 cooling needs]
1.2.2
SDU 1 input water pressure The ECW-50 system shall provide, to the SPN-50 SDU 1, chilled water at a minimum pressure of 1.6 psi, which is equal to the pressure drop through the SDU at the 1.6 GPM minimum flowrate, and a maximum pressure of 58 psi.
Requirement
Meet cooling needs of the SPN-50 SDU 1 [Meet SPN-50 cooling needs]
1.2.3
Temperature of the chilled water for SDU 1
| The ECW-50 system shall provide, to the SPN-50 SDU 1, water at the temperature of greater than or equal to 41 deg. F and less than or equal to 59 deg. F. |
| Requirement |
Meet cooling needs of the SPN-50 SDU 1 [Meet SPN-50 cooling needs]
1.2.4
SDU 1 heat transfer need
| The ECW-50 system shall support the SPN-50 SDU 1 heat emission to cooling water of 1.3 KW (4,306 BTU/h). |
| Requirement |
Meet cooling needs of the SPN-50 SDU 1 [Meet SPN-50 cooling needs]
1.2.5
SDU 1 proof pressure
| The ECW-50 system shall have provisions to ensure that the maximum pressure of the chilled water at the inlet of the SDU 1 will not exceed 80 psi. |
| Requirement |
Meet cooling needs of the SPN-50 SDU 1 [Meet SPN-50 cooling needs]
1.2.6
SDU 1 coupling The ECW-50 system shall connect to the AN/SPN-50 SDU1 using 0.8750-14 UNJF connector.
Requirement
Meet cooling needs of the SPN-50 SDU 1
1.3
1.3.1
Minimum water flow rate for SDU 2 The ECW-50 system shall provide, to the SPN-50 SDU 2, chilled water with the minimum water flow rate of 1.6 Gallons per Minute (GPM).
Requirement
Meet cooling needs of the SPN-50 SDU 2 [Meet SPN-50 cooling needs]
1.3.2
SDU 2 input water pressure The ECW-50 system shall provide, to the SPN-50 SDU 2, chilled water at a minimum pressure of 1.6 psi, which is equal to the pressure drop through the SDU at the 1.6 GPM minimum flowrate, and a maximum pressure of 58 psi.
Requirement
Meet cooling needs of the SPN-50 SDU 2 [Meet SPN-50 cooling needs]
1.3.3
Temperature of the chilled water for SDU 2
| The ECW-50 system shall provide, to the SPN-50 SDU 2, water at the temperature of greater than or equal to 41 deg. F and less than or equal to 59 deg. F. |
| Requirement |
Meet cooling needs of the SPN-50 SDU 2 [Meet SPN-50 cooling needs]
1.3.4
SDU 2 heat transfer need
| The ECW-50 system shall support the SPN-50 SDU 2 heat emission to cooling water of 1.3 KW (4,306 BTU/h). |
| Requirement |
Meet cooling needs of the SPN-50 SDU 2 [Meet SPN-50 cooling needs]
1.3.5
SDU 2 proof pressure
| The ECW-50 system shall have provisions to ensure that the maximum pressure of the chilled water at the inlet of the SDU 2 will not exceed 80 psi. |
| Requirement |
Meet cooling needs of the SPN-50 SDU 2 [Meet SPN-50 cooling needs]
1.3.6
SDU 2 coupling The ECW-50 system shall connect to the AN/SPN-50 SDU2 using 0.8750-14 UNJF connector.
Requirement
Meet cooling needs of the SPN-50 SDU 2
2.1
Meet shipboard power requirements The ECW-50 system shall use the ship AC power that conforms to the MIL-STD-1399-300.
Requirement
Integrate into Shipboard Environment Constraints [Model]
2.2
Meet shock requirements The ECW-50 system shall meet Grade A shock requirements specified in MIL-DTL-901E.
Requirement
Integrate into Shipboard Environment Constraints [Model]
2.3
Ship power characteristics The ECW-50 system shall use a type 1, 60 Hz, 440 VAC, 3 phase, Delta ship power.
Requirement
Integrate into Shipboard Environment Constraints [Model]
2.4
Withstand ship ambient temperature
| The ECW-50 system equipment mounted in conditioned areas shall operate during and after exposure to ambient air temperature extremes of a minimum of 0 deg. C (32 deg. F) to a maximum of +50 deg. C (+122 deg. F) in accordance with MIL-STD-810G method 501.5 (High Temperature) and 502.3 (Low Temperature). |
| Requirement |
Integrate into Shipboard Environment Constraints [Model]
2.5
Operate after storage temperatures
| The ECW-50 system shall operate without any degradation in performance after exposure to storage temperatures of a minimum of -46 deg. C (-50 deg. F) to a maximum of +70 deg. C (+158 deg. F) in accordance with MIL-STD-810G Method 501.5 (High Temperature) and 502.5 (Low Temperature). |
| Requirement |
Integrate into Shipboard Environment Constraints [Model]
2.6
Operate in ship humidity levels
| The ECW-50 system shall operate in the ship humidity of –0-95%. |
| Requirement |
Integrate into Shipboard Environment Constraints [Model]
2.7
Operate in dusty conditions
| The ECW-50 system shall operate during and after exposure to dust as described n MIL-STD-810G, Method 510.5 |
| Requirement |
Integrate into Shipboard Environment Constraints [Model]
2.8
Resist effects of corrosion due to salt
| The ECW-50 system shall resist the effects of corrosive environment due to salt spray/fog in accordance with MIL-STD-810G, Method 503.5 |
| Requirement |
Integrate into Shipboard Environment Constraints [Model]
2.9
Shipboard Chilled Water Characteristics The ECW-50 system shall connect to the ship’s chilled water system and interface with water that meets the purity specifications as defined in the DOD-STD-1399 section 532 paragraph 5.2.1.
Requirement
Integrate into Shipboard Environment Constraints [Model]
2.10
Shipboard Electromagnetic Environment Requirements The ECW-50 system shall meet applicable MIL-STD-464C/461G requirements for shipboard equipment installed below decks. As a minimum, the following MIL-STD-461 requirements must be met:
· CE101: Conducted emissions, power leads, 30 Hz to 10 kHz (MIL-STD-461G, fig. CE101-2).
· CE102: Conducted emissions, power leads, 10 kHz to 10 MHz (MIL-STD-461G, fig. CE102-1).
· CS101: Conducted susceptibility, power leads, 30 Hz to 150 kHz (MIL-STD-461G, fig. CS101-1, Curve #1).
· CS114: Conducted susceptibility, 10 kHz to 200 MHz (MIL-STD-461G, fig. CS114-1, curve #2).
· CS116: Conducted susceptibility, 10 kHz to 100 MHz (MIL-STD-461G, fig. CS116-2).
· CS118: Conducted susceptibility, personnel borne electrostatic discharge.
· RE101: Radiated emissions, magnetic field, 30 Hz to 100 kHz (MIL-STD-461G, fig. RE101-2).
· RE102: Radiated emissions, electric field, 10 kHz to 10 times the highest internally-generated frequency produced by the EUT (MIL-STD-461G, fig. RE102-1, Below Decks limit).
· RS101: Radiated susceptibility, magnetic fields, 30 Hz to 100 kHz (MIL-STD-461G, fig RS101-1).
· RS103: Radiated susceptibility, electric fields, 2 MHz to 18 GHz at levels up 10V/m (MIL-STD-461G, Table XI).
Requirement
Integrate into Shipboard Environment Constraints [Model]
2.11
Shipboard Accessibility The ECW-50 system shall be hatchable for US Navy Carrier and Amphibious Assault ships.
Requirement
Integrate into Shipboard Environment Constraints [Model]
2.12
Meet Vibration Requirement
| The ECW-50 system shall meet Type I vibration requirements specified in MIL-STD-167-1A. |
| Requirement |
Integrate into Shipboard Environment Constraints [Model]
3.1
Warning of unsafe function
| In accordance with MIL-STD-1472G: the ECW-50 system shall provide visual, or audible, safety warnings, cautions, of unsafe functions and/or conditions that could contribute to a safety hazard to the system user. |
| Requirement |
Human Engineering Design Criteria [Model]
3.2
Eliminate/cover up unsafe objects
| In accordance with MIL-STD-1472G: the ECW-50 system hazards, such as sharp corners, projections, moving parts, electrical potential and any other elements that could cause injury, shall be eliminated or covered with protective shields or guards. |
| Requirement |
Human Engineering Design Criteria [Model]
3.3
Safety marking - installation
| In accordance with MIL-STD-1472G: the ECW-50 system shall be marked when safety hazards are present during the installation of system equipment or parts thereof. |
| Requirement |
Human Engineering Design Criteria [Model]
3.4
Safety marking - maintenance
| The ECW-50 system shall be marked when safety hazards are present during the maintenance of the system equipment or parts thereof. |
| Requirement |
Human Engineering Design Criteria [Model]
3.5
Safety marking - operation
| The ECW-50 system shall be marked when safety hazards are present during the operation of the system equipment or parts thereof. |
| Requirement |
Human Engineering Design Criteria [Model]
3.6
Safety marking - repair
| The ECW-50 system shall be marked when safety hazards are present during the repair of the system equipment or parts thereof. |
| Requirement |
Human Engineering Design Criteria [Model]
3.7
Safety marking - replacement
| The ECW-50 system shall be marked when safety hazards are present during the replacement of the system equipment or parts thereof. |
| Requirement |
Human Engineering Design Criteria [Model]
3.8
Safety marking - points of access and barriers
| The ECW-50 system guards, barriers, access doors, covers and plates shall be marked when they protect personnel from safety hazards. |
| Requirement |
Human Engineering Design Criteria [Model]
3.9
Safety marking - hazardous material
| The ECW-50 system parts containing hazardous material shall be marked with appropriate hazard warnings in accordance with MIL-STD-129R. |
| Requirement |
Human Engineering Design Criteria [Model]
3.10
Protect personnel from hazards
| The ECW-50 system shall protect personnel from conditions that create risk of death, injury, acute chronic illness throughout the system life-cycle in accordance with MIL-STD-1472G. |
| Requirement |
Human Engineering Design Criteria [Model] image2.jpeg image1.jpeg