GDS_100pct DRAFT_Site 14_Vol. 14.7.pdf

PDF 16 MB Posted

Attached to
DRAFT RFP – PDI: GUAM DEFENSE SYSTEM, COMMAND CENTER, JOINT REGION MARIANAS, GUAM
Solicitation number
N62742GDSCC
Issued by

About this file

This document is a Draft Request for Proposal (RFP) for the construction (design-bid-build) of a command center, 9 MW (N+2) mission power generation facility, switchgear building, and associated equipment for the Guam Defense System at Joint Region Marianas, Guam. The estimated cost range is $250,000,000 to $500,000,000.

The Draft RFP is being released for industry review and comment to improve understanding of the government's requirements and industry capabilities prior to issuing the final RFP. The government is requesting industry feedback through an Industry Feedback Questionnaire and/or questions and comments via email by 2:00 PM HST on 15 August 2024. Proprietary information will not be accepted. The government intends to use Navy personnel and possibly an architect-engineering firm to review and evaluate the responses. Responding to this draft does not preclude participation in any future solicitation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V F

A C

P A

C

IF

IC

M

A K

A L A

P A

H

A W

A

II

AS NOTED

P R

O J E

C T

S

IT

E

C O

M M

A N

D C

E N

T E

R

N A

V F

A C

P A

C

IF

IC

1812861

KYM

JC

Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813

A/E Task Order No. N6274223F0324

FOR REVIEW

ONLY

Name

Registration Number #

These documents are for Design Review and not intended for

Construction Bidding or Permit Purposes. They were prepared by, or under the supervision of:

Date

SEAL

24 JUN 2024

A N

D E

R S

E N

A

IR

F O

R C

E B

A S

E

KYM

AWK/DMK

/2

/2

:3 :0

A

M

C U s e rs

\l a r6

\D o c u m e n ts

\P

G L a re s

.r v t

14GI-G-013

C O

V E

R S

H E

E T

DCT

EL EL

G U

A M

G

I- G

-0

FINAL DESIGN SUBMITTAL

100% DESIGN SUBMITTAL

VICINITY MAP PROJECT LOCATION MAP

VOLUME 14.7 - POWER PLANT (GENERAL, MECHANICAL,

ELECTRICAL, TELECOMMUNICATIONS & SECURITY

PRIME CONSULTANT

CONSULTANTS

GENERAL NOTES AND REQUIREMENTS

VOLUME DESCRIPTION

VOL 14.1 GENERAL & SITE

VOL 14.2

VOL 14.4

COMMAND CENTER (GENERAL & STRUCTURAL)

VOL 14.5 COMMAND CENTER ( GENERAL, TELECOMMUNICATIONS, AUDIO VISUAL & SECURITY)

COMMAND CENTER ( GENERAL & ELECTRICAL)

VOL 14.3 COMMAND CENTER (GENERAL, ARCH, INTERIOR, FIRE PROTECTION, PLUMBING & MECHANICAL )

VOL 14.6 POWER PLANT (GENERAL, STRUCT, ARCH, INTERIOR, FIRE PROTECTION & PLUMBING

VOL 14.7 POWER PLANT (GENERAL, MECHANICAL, ELECTRICAL, TELECOMMUNICATIONS & SECURITY

VOL 14.8 ACCESS CONTROL

PROJECT 693

SITE 14 COMMAND CENTER

ANDERSEN AIR FORCE BASE, GUAM

PLAN NORTH PLAN NORTH

Jacobs/B&V, a Joint Venture (Federal Services)

BLACK & VEATCH

SHEET REFERENCES WITHOUT SITE NUMBER AND BUILDING ID (I.E. FRIST FOUR

CHARACTERS) ARE INDICATING SHEETS WITHIN THE SAME SERIES OF DRAWINGS

OR TO GENERAL SHEETS, AS APPLICABLE.

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V F

A C

P A

C

IF

IC

M

A K

A L A

P A

H

A W

A

II

AS NOTED

F Y

P

R O

J E

C T

G D

S C

O M

M A

N D

C E

N T

E R

N A

V F

A C

P A

C

IF

IC

1764210

KYM

JC

Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813

A/E Task Order No. N6274223F0324

FOR REVIEW

ONLY

Name

Registration Number #

These documents are for Design Review and not intended for

Construction Bidding or Permit Purposes. They were prepared by, or under the supervision of:

Date

SEAL

24 JUN 2024

A N

D E

R S

E N

A

IR

F O

R C

E B

A S

E

KYM

AWK/DMK

/2

/2

:2

:5

P

M

C R e v it \l o c a l_

\P

G

T a rr D

C b v .c o m

.r v t

14GI-G-014

S H

E E

T

IN

D E

X

ELDCT DCT

G U

A M

G I-

G -0

100% DESIGN SUBMITTAL

SITE 14 - MECHANICAL SHEET INDEX - VOL. 14.7

SHEET.

NO

NAVFAC

DWG. NO. SHEET NUMBER SHEET NAME

MECHANICAL

0 14GI-M-001 MECHANICAL LEGENDS AND ABBREVIATIONS

0 14GI-M-002 MECHANICAL LEGENDS AND ABBREVIATIONS

0 14GI-M-003 MECHANICAL GENERAL NOTES

0 14GI-M-004 MECHANICAL PIPING LEGENDS

0 14GI-M-005 MECHANICAL HVAC LEGENDS

0 14GI-M-006 MECHANICAL EQUIPMENT LEGENDS

0 14GI-M-007 MECHANICAL INSTRUMENTATION LEGENDS

0 14GI-M-008 POINT SCHEDULE INSTRUCTIONS

MECHANICAL

0 14PP-M-501 POWER PLANT - MECHANICAL DETAILS

0 14PP-M-502 POWER PLANT - MECHANICAL DETAILS

0 14PP-M-503 POWER PLANT - MECHANICAL DETAILS

0 14PP-M-504 POWER PLANT - MECHANICAL DETAILS

0 14PP-M-601 POWER PLANT - MECHANICAL SCHEMATICS

0 14PP-M-611 POWER PLANT - MECHANICAL SCHEMATICS

0 14PP-M-701 POWER PLANT - MECHANICAL SCHEDULES

0 14PP-M-702 POWER PLANT - MECHANICAL SCHEDULES

0 14PP-M-703 POWER PLANT - MECHANICAL SCHEDULES

0 14PP-M-704 POWER PLANT - MECHANICAL SCHEDULES

0 14PP-M-801 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-802 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-803 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-804 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-805 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-806 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-807 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-808 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-809 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-810 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-811 POWER PLANT - MECHANICAL CONTROLS

0 14PP-M-901 POWER PLANT - FUEL OIL RISER DIAGRAM - OVERALL

0 14PP-MH111 POWER PLANT - HVAC PLAN - OVERALL

0 14PP-MH112 POWER PLANT - HVAC PLAN - AREA A

0 14PP-MP111 POWER PLANT - MECHANICAL PIPING PLAN - OVERALL

0 14PP-MP113 POWER PLANT - MECHANICAL PIPING PLAN - AREA B

0 14PP-MP114 POWER PLANT - MECHANICAL PIPING PLAN - AREA C

SITE 14 - ELECTRICAL SHEET INDEX - VOL. 14.7

SHEET.

NO

NAVFAC

DWG. NO. SHEET NUMBER SHEET NAME

ELECTRICAL

0 14GI-E-001 ELECTRICAL ABBREVIATIONS

0 14GI-E-002 ELECTRICAL LEGEND AND NOTES

0 14GI-E-003 GENERAL - ELECTRICAL LEGEND AND NOTES

0 14GI-E-004 ELECTRICAL CIRCUIT AND RACEWAY LEGEND

0 14GI-E-005 CIRCUIT & RACEWAY TYPES

0 14GI-E-006 INSTRUMENTATION I/O LIST LEGEND

ELECTRICAL - POWER

0 14PP-EP101 POWER PLANT - UNDERFLOOR RACEWAY PLAN - OVERALL

0 14PP-EP102 POWER PLANT - UNDERFLOOR RACEWAY PLAN - AREA A

0 14PP-EP103 POWER PLANT - UNDERFLOOR RACEWAY PLAN - AREA B

0 14PP-EP104 POWER PLANT - UNDERFLOOR RACEWAY PLAN - AREA C

0 14PP-EP111 POWER PLANT - POWER PLAN - OVERALL

0 14PP-EP112 POWER PLANT - POWER PLAN - AREA A

0 14PP-EP113 POWER PLANT - POWER PLAN - AREA B

0 14PP-EP114 POWER PLANT - POWER PLAN - AREA C

0 14PP-EP201 POWER PLANT - EQUIPMENT ELEVATIONS - GENERATOR

SWITCHGEAR

0 14PP-EP202 POWER PLANT - EQUIPMENT ELEVATIONS - MV SWITCHGEAR

0 14PP-EP203 POWER PLANT - EQUIPMENT ELEVATIONS - LV SWITCHGEAR

0 14PP-EP501 POWER PLANT - DUCTBANK SECTION DETAILS

0 14PP-EP511 POWER PLANT - ELECTRICAL MANHOLE BUTTERFLY DETAILS

0 14PP-EP518 POWER PLANT - ELECTRICAL MANHOLE DETAILS

0 14PP-EP521 POWER PLANT - GENSET ENCLOSURE DETAIL

0 14PP-EP601 POWER PLANT - ONE-LINE DIAGRAM

0 14PP-EP602 POWER PLANT - ONE-LINE DIAGRAM

0 14PP-EP603 POWER PLANT - ONE-LINE DIAGRAM

0 14PP-EP604 POWER PLANT - ONE-LINE DIAGRAM - 125 VDC

0 14PP-EP605 POWER PLANT - ONE-LINE DIAGRAM INVERTER

0 14PP-EP611 POWER PLANT - ONE-LINE DIAGRAM - ZONES OF PROTECTION

0 14PP-EP612 POWER PLANT - ONE-LINE DIAGRAM - ZONES OF PROTECTION

0 14PP-EP613 POWER PLANT - MVS SCHEMATICS SYNC CHECK

INTERCONNECTIONS

0 14PP-EP616 POWER PLANT - BREAKER CONTROL INTERCONNECTION BLOCK

DIAGRAM

0 14PP-EP617 POWER PLANT - DIESEL GENERATOR OVERALL CONTROL

DIAGRAM

0 14PP-EP651 POWER PLANT - ONE-LINE DIAGRAM - TYP MVS BREAKERS -

GENERATOR SWGR

0 14PP-EP652 POWER PLANT - ONE-LINE DIAGRAM - TYP MVS BREAKERS -

GENERATOR SWGR

0 14PP-EP653 POWER PLANT - ONE-LINE DIAGRAM - MVS BREAKERS - SWGR A

0 14PP-EP654 POWER PLANT - ONE-LINE DIAGRAM - MVS BREAKERS - SWGR A

0 14PP-EP655 POWER PLANT - ONE-LINE DIAGRAM - MVS BREAKERS - SWGR B

0 14PP-EP656 POWER PLANT - ONE-LINE DIAGRAM - MVS BREAKERS - SWGR B

0 14PP-EP661 POWER PLANT - THREE LINE DIAGRAM 13.8kV BREAKER

0 14PP-EP671 POWER PLANT - MVS SCHEMATICS TYPICAL GENERATOR

BREAKER DC

0 14PP-EP672 POWER PLANT - MVS SCHEMATICS GENERATOR SYNC CONTROL

DC

0 14PP-EP673 POWER PLANT - MVS SCHEMATICS TYPICAL UTILITY BREAKER DC

0 14PP-EP674 POWER PLANT - MVS SCHEMATICS UTILITY SYNC CONTROL DC

0 14PP-EP675 POWER PLANT - MVS SCHEMATICS MAIN BUS DIFFERENTIAL DC

0 14PP-EP676 POWER PLANT - MVS SCHEMATICS GENERATOR DIFFERENTIAL

DC

0 14PP-EP677 POWER PLANT - MVS SCHEMATICS GENERATOR TIE BREAKER DC

0 14PP-EP678 POWER PLANT - MVS SCHEMATICS TYPICAL FEEDER BREAKER

DC

0 14PP-EP679 POWER PLANT - MVS SCHEMATICS BUS TIE BREAKER DC

0 14PP-EP680 POWER PLANT - MVS SCHEMATICS BUS TIE SYNC CONTROL DC

0 14PP-EP681 POWER PLANT - MVS SCHEMATICS LVS FEEDER BREAKER DC

0 14PP-EP682 POWER PLANT - MVS SCHEMATICS LOAD BANK BREAKER DC

0 14PP-EP683 POWER PLANT - MVS SCHEMATICS ASSET FEEDER BREAKER DC

0 14PP-EP684 POWER PLANT - COMMUNICATIONS PROCESSOR RELAYING

INTERCONNECTIONS

0 14PP-EP685 POWER PLANT - LVS SCHEMATICS BUS A

0 14PP-EP686 POWER PLANT - LVS SCHEMATICS BUS B

0 14PP-EP687 POWER PLANT - LVS SCHEMATICS BUS A AND B

0 14PP-EP688 POWER PLANT - INVERTER PANELBOARD SYNC CHECK RELAY

0 14PP-EP701 POWER PLANT - PANEL SCHEDULES

0 14PP-EP702 POWER PLANT - PANEL SCHEDULES

0 14PP-EP703 POWER PLANT - PANEL SCHEDULES

0 14PP-EP751 POWER PLANT - CIRCUIT SCHEDULES

0 14PP-EP752 POWER PLANT - CIRCUIT SCHEDULES

0 14PP-EP771 POWER PLANT - RACEWAY SCHEDULES

0 14PP-EP772 POWER PLANT - RACEWAY SCHEDULES

0 14PP-EP773 POWER PLANT - RACEWAY SCHEDULES

0 14PP-EP774 POWER PLANT - RACEWAY SCHEDULES

0 14PP-EP775 POWER PLANT - RACEWAY SCHEDULES

0 14PP-EP901 POWER PLANT - SEQUENCE OF OPERATION

0 14PP-EP902 POWER PLANT - SEQUENCE OF OPERATION

ELECTRICAL - LIGHTING

0 14PP-EL111 POWER PLANT - LIGHTING PLAN - OVERALL

0 14PP-EL112 POWER PLANT - LIGHTING PLAN - AREA A

0 14PP-EL113 POWER PLANT - LIGHTING PLAN - AREA B

0 14PP-EL114 POWER PLANT - LIGHTING PLAN - AREA C

0 14PP-EL501 POWER PLANT - LIGHTING CONTROL DIAGRAM

0 14PP-EL502 POWER PLANT - LIGHTING DETAILS

0 14PP-EL701 POWER PLANT - LUMINAIRE SCHEDULE

ELECTRICAL - GROUNDING & LIGHTNING PROTECTION

0 14PP-EG111 POWER PLANT - GROUNDING PLAN - OVERALL

0 14PP-EG112 POWER PLANT - GROUNDING PLAN - AREA A

0 14PP-EG113 POWER PLANT - GROUNDING PLAN - AREA B

0 14PP-EG114 POWER PLANT - GROUNDING PLAN - AREA C

0 14PP-EG121 POWER PLANT - LIGHTNING PROTECTION PLAN - OVERALL

0 14PP-EG122 POWER PLANT - LIGHTNING PROTECTION PLAN - AREA A

0 14PP-EG123 POWER PLANT - LIGHTNING PROTECTION PLAN - AREA B

0 14PP-EG124 POWER PLANT - LIGHTNING PROTECTION PLAN - AREA C

0 14PP-EG501 POWER PLANT - GROUNDING DETAILS

0 14PP-EG502 POWER PLANT - GROUNDING DETAILS

0 14PP-EG503 POWER PLANT - LIGHTNING PROTECTION DETAILS

0 14PP-EG601 POWER PLANT - GROUNDING RISER

ELECTRICAL - INSTRUMENTATION & CONTROL

0 14PP-EI111 POWER PLANT - INSTRUMENTATION & CONTROL PLAN - OVERALL

0 14PP-EI112 POWER PLANT - BUILDING CONTROL SYSTEM PLAN - AREA A

0 14PP-EI113 POWER PLANT - INSTRUMENTATION & CONTROL PLAN - AREA B

0 14PP-EI114 POWER PLANT - INSTRUMENTATION & CONTROL PLAN - AREA C

0 14PP-EI601 POWER PLANT - FACILITY CONTROL SYSTEMS BLOCK DIAGRAM

0 14PP-EI602 POWER PLANT - PCMS COMMUNICATIONS RACK ELEVATIONS

0 14PP-EI603 POWER PLANT - PCMS-14PP69111 - ENCLOSURE BLOCK DIAGRAM

0 14PP-EI604 POWER PLANT - PCMS-14PP69112 - ENCLOSURE BLOCK DIAGRAM

0 14PP-EI605 POWER PLANT - PCMS-14PP69113 - ENCLOSURE BLOCK DIAGRAM

0 14PP-EI606 POWER PLANT - PCMS-14PP69114 - ENCLOSURE BLOCK DIAGRAM

0 14PP-EI607 POWER PLANT - PCMS-14PP69201A - ENCLOSURE BLOCK

DIAGRAM

0 14PP-EI608 POWER PLANT - PCMS-14PP69201B - ENCLOSURE BLOCK

DIAGRAM

0 14PP-EI609 POWER PLANT - PCMS-14PP69301A - ENCLOSURE BLOCK

DIAGRAM

0 14PP-EI610 POWER PLANT - PCMS-14PP69301B - ENCLOSURE BLOCK

DIAGRAM

0 14PP-EI611 POWER PLANT - PCMS-14PP-69101A - ENCLOSURE BLOCK

DIAGRAM

0 14PP-EI612 POWER PLANT - PCMS-14PP69101B - ENCLOSURE BLOCK

DIAGRAM

0 14PP-EI630 POWER PLANT - PCMS-14PP69101A & PCMS-14PP69101B FUEL

CONTROL BLOCK DIAGRAM

0 14PP-EI750 POWER PLANT - PCMS CONDUIT SCHEDULE

0 14PP-EI760 POWER PLANT - PCMS CIRCUIT SCHEDULE

0 14PP-EI761 POWER PLANT - PCMS CIRCUIT SCHEDULE

0 14PP-EI762 POWER PLANT - PCMS CIRCUIT SCHEDULE

0 14PP-EI901 POWER PLANT - PCMS I/O LIST - SHEET 1

0 14PP-EI902 POWER PLANT - PCMS I/O LIST - SHEET 2

0 14PP-EI903 POWER PLANT - PCMS I/O LIST - SHEET 3

0 14PP-EI904 POWER PLANT - PCMS I/O LIST - SHEET 4

0 14PP-EI905 POWER PLANT - PCMS I/O LIST - SHEET 5

0 14PP-EI906 POWER PLANT - PCMS I/O LIST - SHEET 6

0 14PP-EI907 POWER PLANT - PCMS I/O LIST - SHEET 7

0 14PP-EI908 POWER PLANT - PCMS I/O LIST - SHEET 8

0 14PP-EI909 POWER PLANT - PCMS I/O LIST - SHEET 9

0 14PP-EI910 POWER PLANT - PCMS I/O LIST - SHEET 10

0 14PP-EI911 POWER PLANT - PCMS I/O LIST - SHEET 11

0 14PP-EI912 POWER PLANT - PCMS I/O LIST - SHEET 12

0 14PP-EI913 POWER PLANT - PCMS I/O LIST - SHEET 13

0 14PP-EI914 POWER PLANT - PCMS I/O LIST - SHEET 14

0 14PP-EI915 POWER PLANT - PCMS I/O LIST - SHEET 15

0 14PP-EI916 POWER PLANT - PCMS I/O LIST - SHEET 16

0 14PP-EI917 POWER PLANT - PCMS I/O LIST - SHEET 17

0 14PP-EI918 POWER PLANT - PCMS I/O LIST - SHEET 18

0 14PP-EI919 POWER PLANT - PCMS I/O LIST - SHEET 19

0 14PP-EI920 POWER PLANT - PCMS I/O LIST - SHEET 20

0 14PP-EI921 POWER PLANT - PCMS I/O LIST - SHEET 21

0 14PP-EI922 POWER PLANT - PCMS I/O LIST - SHEET 22

0 14PP-EI923 POWER PLANT - PCMS I/O LIST - SHEET 23

0 14PP-EI924 POWER PLANT - PCMS I/O LIST - SHEET 24

0 14PP-EI925 POWER PLANT - PCMS I/O LIST - SHEET 25

0 14PP-EI926 POWER PLANT - PCMS I/O LIST - SHEET 26

0 14PP-EI927 POWER PLANT - PCMS I/O LIST - SHEET 27

0 14PP-EI928 POWER PLANT - PCMS I/O LIST - SHEET 28

0 14PP-EI929 POWER PLANT - PCMS I/O LIST - SHEET 29

0 14PP-EI930 POWER PLANT - PCMS I/O LIST - SHEET 30

0 14PP-EI931 POWER PLANT - PCMS I/O LIST - SHEET 31

0 14PP-EI932 POWER PLANT - PCMS I/O LIST - SHEET 32

0 14PP-EI933 POWER PLANT - PCMS I/O LIST - SHEET 33

0 14PP-EI934 POWER PLANT - PCMS I/O LIST - SHEET 34

0 14PP-EI935 POWER PLANT - PCMS I/O LIST - SHEET 35

0 14PP-EI936 POWER PLANT - PCMS I/O LIST - SHEET 36

0 14PP-EI937 POWER PLANT - PCMS I/O LIST - SHEET 37

0 14PP-EI938 POWER PLANT - PCMS I/O LIST - SHEET 38

0 14PP-EI939 POWER PLANT - PCMS I/O LIST - SHEET 389

0 14PP-EI940 POWER PLANT - PCMS I/O LIST - SHEET 40

SITE 14 - TELECOMMUNICATIONS SHEET - VOL. 14.7

SHEET.

NO

NAVFAC

DWG. NO. SHEET NUMBER SHEET NAME

GENERAL

0 14GI-T-001 TELECOMMUNICATIONS LEGEND

TELECOMMUNICATIONS

0 14PP-T-111 POWER PLANT - TELECOMMUNICATIONS PLAN - OVERALL

0 14PP-T-112 POWER PLANT - TELECOMMUNICATIONS PLAN - AREA A

0 14PP-T-113 POWER PLANT - TELECOMMUNICATIONS PLAN - AREA B

0 14PP-T-114 POWER PLANT - TELECOMMUNICATIONS PLAN - AREA C

0 14PP-T-201 POWER PLANT - TELECOMMUNICATIONS ELEVATIONS

0 14PP-T-501 POWER PLANT - TELECOMMUNICATIONS - STANDARD DETAILS

0 14PP-T-601 TELECOMMUNICATIONS GROUNDING DETAILS

0 14PP-T-603 TELECOMMUNICATIONS GROUNDING ONE-LINE

SITE 14 - GENERAL SHEET INDEX - VOL. 14.7

SHEET

NO.

NAVFAC

DWG. NO. SHEET NUMBER SHEET NAME

GENERAL

0 14GI-G-013 COVER SHEET

0 14GI-G-014 SHEET INDEX

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

P R

O J E

C T

S

IT

E

C O

M M

A N

D C

E N

T E

R

A N

D E

R S

E N

A

IR

F O

R C

E B

A S

E G

U A

M

GENERAL ABBREVIATIONS GENERAL ABBREVIATIONS

(CONTINUED)

@ AT

& AND

˪ ANGLE

AAV AUTOMATIC AIR VENT

AC ALTERNATING CURRENT OR AIR CONDITIONING

AD ACCESS DOOR

ADA AMERICANS WITH DISABILITIES ACT (STANDARDS)

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

ALM ALARM

AMP AMPERE

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

APD AIR PRESSURE DROP

APPROX APPROXIMATE

ARCH ARCHITECT

ASSY ASSEMBLY

ATMOS ATMOSPHERE

AUTO AUTOMATIC

AUX AUXILIARY

AVG AVERAGE

BAS BUILDING AUTOMATION SYSTEM

BD MANUAL BALANCING (VOLUME) DAMPER

BLDG BUILDING

BLW BELOW

BMS BUILDING MANAGEMENT SYSTEM

BOD BOTTOM OF DUCT

BOI BOTTOM OF INSULATION

BOP BOTTOM OF PIPE

BOS BOTTOM OF STEEL

BOT BOTTOM

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNITS PER HOUR

C CHANNEL, CELSIUS

CAP CAPACITY

CBN COMMON BONDING NETWORK

CCW COUNTERCLOCKWISE

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CHEM CHEMICAL

CI CAST IRON OR CONTRACTOR INSTALLED

CL CENTERLINE

CLG COOLING

CLR CLEAR, CLEARANCE

CNDS CONDENSATE

CNTRL CONTROL

CMD COMMAND

CMU CONCRETE MASONRY UNIT

CNTRL CONTROL

CO2 CARBON DIOXIDE

COL COLUMN

CONC CONCRETE

CONN CONNECTION

CONT CONTINUATION, CONTINUE

CP CONTROL PANEL

CTR CENTER

CU COPPER

CV VALVE FLOW COEFFICIENT

DB DECIBEL, DRY BULB

DC DIRECT CURRENT

DD DUCT DETECTOR

DDC DIRECT DIGITAL CONTROL

DEF DIESEL EXHAUST FLUID

DEG OR ° DEGREE

DIA OR ø DIAMETER

DIFF DIFFERENTIAL

DIM DIMENSION

DISCH DISCHARGE

DN DOWN

DP DEW POINT, DIFFERENTIAL PRESSURE

DS DISCONNECT SWITCH

DSC DESICCANT

DSW DESICCANT WHEEL

DWG DRAWING

EA EACH

EAT ENTERING AIR TEMP

ECC ECCENTRIC

ECM ELECTRONICALLY COMMUNICATED MOTOR

EDB ENTERING DRY BULB

EFF EFFICIENCY

ELEC ELECTRIC

EL, ELEV ELEVATION

EMCS EMERGENCY MONITORING CONTROL STATION

EPO EMERGENCY POWER OFF (SWITCH)

ESP EXTERNAL STATIC PRESSURE

EQUIP EQUIPMENT

EWB ENTERING WET BULB

EXIST EXISTING

EXT EXTERIOR

F FAHRENHEIT

FA FREE AREA

FBO FURNISHED BY OTHERS (OR OWNER)

FC FAIL CLOSED

FH FILTER HOUSING, FLEXIBLE HOSE

FIG FIGURE

FLA FULL LOAD AMPS

FLG FLANGE

FLR FLOOR

FM FACTORY MUTUAL

FO FAIL OPEN, FLAT OVAL, OR FIBER OPTIC

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FPM FEET PER MINUTE

FT FEET OR FOOT

G GAUGE, GAGE

GA GAUGE

GAL GALLON

GALV GALVANIZED

GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED

GFGI GOVERNMENT FURNISHED GOVERNMENT INSTALLED

GND GROUND

GPH GALLON PER HOUR

GPM GALLON PER MINUTE

GWB GYPSUM WALLBOARD

GYP GYPSUM

H HEIGHT

HDPE HIGH DENSITY POLYETHYLENE

HOR HORIZONTAL

HR HOUR

HRV HEAT RECOVERY VENTILATOR

HP HORSEPOWER

HT HEIGHT

HTG HEATING

HZ HERTZ

IBC INTERNATIONAL BUILDING CODE

ID INSIDE DIAMETER

IE INVERT ELEVATION

IN INCHES

INCL INCLUDED

INWC INCHES OF WATER COLUMN

INST INSTRUMENTATION, INSTANTANEOUS

INSUL INSULATION

IPS IRON PIPE SIZE

IR INFRARED

kV KILOVOLT kVA KILOVOLT AMPERES kW KILOWATT kWh KILOWATT-HOUR

KW KILOWATT

L LENGTH

LAT LEAVING AIR TEMP

LB POUND

LDP LEAVING DEWPOINT

LED LIGHT EMITTING DIODE

LP LOW PRESSURE

LR LONG RADIUS

M METER, MOTOR

MATL MATERIAL

MAX MAXIMUM

MBH ONE THOUSAND BRITISH THERMAL UNITS PER HOUR

MFG MANUFACTURING

MFR MANUFACTURER

MIN MINIMUM, MINUTE

MNOA MINIMUM OUTSIDE AIR

MOCP MAXIMUM OVER CURRENT PROTECTION

MPT MALE PIPE THREAD

MS MOTOR SWITCH, MOTOR STARTER

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NEG NEGATIVE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER, NORMALLY OPEN

NOM NOMINAL

NPT NATIONAL PIPE THREAD

NTS NOT TO SCALE

OCC OCCUPIED

OD OUTSIDE DIAMETER

OF/CI OWNER FURNISHED / CONTRACTOR INSTALLED

(THE FOLLOWING ARE ALL ENCOMPASSING AND MAY

OR MAY NOT BE UTILIZED HERE-IN)

DETAIL IDENTIFICATION

DETAIL NUMBER

SHEET NUMBER ON WHICH

DETAIL IS SHOWN

SECTION IDENTIFICATION

SECTION LETTER

SHEET NUMBER ON WHICH

DETAIL IS SHOWN

DETAIL, SECTIONS & PLAN TITLE

DETAIL, SECTION OR PLAN TITLE

M-501

M-30

A

M-101

DETAIL, SECTION OR PLAN TITLE

DETAIL OR PLAN NUMBER,

OR SECTION LETTER

APPROPRIATE ARCHITECTURAL OR

ENGINEERING SCALE, OTHERWISE

"NOT TO SCALE".

SCALE

SHEET NUMBER OR WHICH DETAIL,

SECTION OR PLAN IS SHOWN

GENERAL LEGEND

(LEGEND: BVF - GENERAL LEGEND)

DUCTWORK ABBREVIATIONS

EA EXHAUST AIR

OA OUTSIDE AIR

MA MIXED AIR

MUA MAKEUP AIR

RA RETURN AIR

RFA RELIEF AIR

SA SUPPLY AIR

TA TRANSFER AIR

MECHANICAL PIPING ABBREVIATIONS

ATV ATMOSPHERIC (STEAM) VENT

ATF AUTOMATIC TRANSMISSION FLUID

BBD BOILER BLOWDOWN

BFW BOILER FEEDWATER

CBR CHILLED BEAM RETURN

CBS CHILLED BEAM SUPPLY

CD CONDENSATE DRAIN

CG CHASSIS GREASE

CHWS CHILLED WATER SUPPLY

CHWR CHILLED WATER RETURN

CST CLEAN STEAM

CSC CLEAN STEAM CONDENSATE

CS CONDENSER WATER SUPPLY

CR CONDENSER WATER RETURN

DEFF DIESEL EXHAUST FLUID OFFLOADING

DEFP DIESEL EXHAUST FLUID PIPE

DEFS DIESEL EXHAUST FLUID SUPPLY

DEFR DIESEL EXHAUST FLUID RETURN

EC ENGINE COOLANT

EEV ENGINE EXHAUST VENT

EO ENGINE OIL

FOF FUEL OIL OFFLOADING

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

GO GEAR OIL

GV ATMOSPHERIC COMBUSTION GAS VENT

GWS GLYCOL CHILLED WATER SUPPLY

GWR GLYCOL CHILLED WATER RETURN

HWS HEATING HOT WATER SUPPLY

HWR HEATING HOT WATER RETURN

MTWS MEDIUM TEMPERATURE HEATING WATER SUPPLY

MTWR MEDIUM TEMPERATURE HEATING WATER RETURN

HTWS HIGH TEMPERATURE HEATING WATER SUPPLY

HTWR HIGH TEMPERATURE HEATING WATER RETURN

IA INSTRUMENT AIR

LPS LOW PRESSURE STEAM

LPC LOW PRESSURE CONDENSATE

PGV PRESSURIZED COMBUSTION GAS VENT

RD REFRIGERANT DISCHARGE

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

VAC VACUUM

(THE FOLLOWING ARE ALL ENCOMPASSING AND MAY OR MAY NOT BE UTILIZED HERE-IN)

(THE FOLLOWING ARE ALL ENCOMPASSING AND MAY OR MAY NOT BE UTILIZED HERE-IN)

PIPING SYSTEM IDENTIFICATION

PIPE SIZE

SYSTEM (SEE SYSTEM ABBREVIATIONS)

2" XX

GENERAL ABBREVIATIONS

(CONTINUED)

% PERCENT

PH OR ø PHASE

PL PLATE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PT POINT

QTY QUANTITY

R RADIUS

RAF RAISED ACCESS FLOOR

RECIRC RECIRCULATION

RED REDUCER

REF REFERENCE

REQ'D REQUIRED

RH RELATIVE HUMIDITY

RM ROOM

RPM REVOLUTIONS PER MINUTE

RST RESET

RT RATE

S SECOND

SCH SCHEDULE

SCRD SCREWED

SEC SECOND

SHT SHEET

SPEC SPECIFICATION SECTION

STD STANDARD

STL STEEL

SYS SYSTEM

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE OR TEMPORARY

TOC TOP OF CONCRETE

TOD TOP OF DUCT

TOS TOP OF STEEL

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UNG UNDERGROUND

UNO UNLESS NOTED OTHERWISE

UNOCC UNOCCUPIED

V VENT, VOLT, VOLTAGE

VAC VOLTS ALTERNATING CURRENT, VACUUM

VEL VELOCITY

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WIDTH, WATT

W/ WITH

W/O WITHOUT

WB WET BULB

WC WATER PRESSURE DROP

WT WEIGHT

ZN ZONE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VF

AC

P

AC

IF

IC

M

A K

AL

A

PA

, H

AW

AI

I

AS NOTED

FY

P R

O

JE

C T

G D

S C

O M

M

AN

D C

EN

TE

R

N A

VF

AC

P A

C

IF

IC

1764210

KYM

JC

Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813

A/E Task Order No. N6274223F0324

FOR REVIEW

ONLY

Name

Registration Number #

These documents are for Design Review and not intended for

Construction Bidding or Permit Purposes. They were prepared by, or under the supervision of:

Date

SEAL

24 JUN 2024

AN

DE

RS

EN

A

IR

F O

RC

E

BA

SE

LJE

AWK/DMK

6/

/2

6:

:0

PM

P6

_1

_1 4_

G _d et ac he d.

rv t

14GI-M-001

ME

CH

AN

IC

AL

LE

GE

ND

S

AN

D

AB

BR

EV

IA

TI

ON

S

MAMMGP JTW

G

UA

M

G

I-M -0

100% DESIGN SUBMITTAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

P R

O J E

C T

S

IT

E

C O

M M

A N

D C

E N

T E

R

A N

D E

R S

E N

A

IR

F O

R C

E B

A S

E G

U

INTERFACE SYMBOLS

ITEMS THIS SIDE OF SYMBOL NEW

ITEMS THIS SIDE SYMBOL

EXISTING (OR MUST REMAIN)

ITEMS THIS SIDE OF SYMBOL

MUST BE REMOVED

ITEMS THIS SIDE OF SYMBOL

EXISTING (OR MUST REMAIN)

ITEMS THIS SIDE OF SYMBOL

TO BE INSTALLED IN THIS CONTRACT

ITEMS THIS SIDE OF SYMBOL

TO BE INSTALLED IN FUTURE CONTRACT

ITEMS THIS SIDE OF SYMBOL

ARE INCLUDED IN THE SYSTEM

INDICATED.

ITEMS THIS SIDE OF SYMBOL

ARE INCLUDED IN THE SYSTEM

INDICATED.

ITEMS THIS SIDE OF SYMBOL

ARE INCLUDED IN THE SYSTEM

INDICATED.

EXISTING, DEMOLITION, AND NEW

CONTRACT LIMITS

YY-ZZZ##

DRAWING -TO-DRAWING INTERFACE CONTINUATION FLAGS

FLOW "FROM" DRAWING

"TO" DRAWING NUMBER

SEQUENTIAL FLAG ID NUMBER

(EACH FLAG LEAVING FROM

DRAWING HAS A UNIQUE

FLAG ID NUMBER)

YY-ZZZ##

FLOW "TO" DRAWING

"FROM" DRAWING NUMBER

FLAG ID NUMBER CORRESPONDS

TO SEQUENTIAL ID ON

"FROM" DRAWING

X

"FROM" FLOW CONTINUATION

ON SAME DRAWING

SEQUENTIAL FLAG ID NUMBER

(EACH "FROM" FLAG LEAVING FROM

DRAWING HAS A UNIQUE

FLAG ID NUMBER)

"TO" FLOW CONTINUATION

ON SAME DRAWING

FLAG ID NUMBER

(EACH "TO" FLAG ID NUMBER

CORRESPONDS TO ID NUMBER

ON "FROM" FLAG)

X

MECHANICAL SYSTEM LIMITS

SAME DRAWING -TO-DRAWING INTERFACE CONTINUATION FLAGS

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VF

AC

P

AC

IF

IC

M

A K

AL

A

PA

, H

AW

AI

I

AS NOTED

FY

P R

O

JE

C T

G D

S C

O M

M

AN

D C

EN

TE

R

N A

VF

AC

P A

C

IF

IC

1764210

KYM

JC

Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813

A/E Task Order No. N6274223F0324

FOR REVIEW

ONLY

Name

Registration Number #

These documents are for Design Review and not intended for

Construction Bidding or Permit Purposes. They were prepared by, or under the supervision of:

Date

SEAL

24 JUN 2024

AN

DE

RS

EN

A

IR

F O

RC

E

BA

SE

LJE

AWK/DMK

6/

/2

6:

:2

PM

P6

_1

_1 4_

G _d et ac he d.

rv t

14GI-M-002

ME

CH

AN

IC

AL

LE

GE

ND

S

AN

D

AB

BR

EV

IA

TI

ON

S

MAMMGP JTW

G

UA

M

G

I-M -0

100% DESIGN SUBMITTAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

P R

O J E

C T

S

IT

E

C O

M M

A N

D C

E N

T E

R

A N

D E

R S

E N

A

IR

F O

R C

E B

A S

E G

U

GENERAL MECHANICAL NOTES

(CONTINUED)

GENERAL DUCT SUPPORT NOTES

1. ENTIRE SCOPE OF SUPPORT LOCATION, DESIGN, FABRICATION, AND INSTALLATION

OF HVAC DUCTS MUST BE CONTRACTOR'S RESPONSIBILITY. HVAC DUCTS MUST BE

IN ACCORDANCE WITH THE LATEST SMACNA PUBLICATION "SEISMIC RESTRAINT

MANUAL" AND SPECIFICATIONS.

GENERAL HVAC NOTES

1. ALL HVAC PENETRATIONS IN FIRE WALLS MUST HAVE FIRE DAMPERS. ALL FIRE

DAMPERS, SMOKE DAMPERS, AND FIRE/SMOKE DAMPERS MUST BE INSTALLED IN

ACCORDANCE WITH SHEET METAL AND AIR CONDITIONING NATIONAL

ASSOCIATION (SMACNA) SMOKE, AND RADIATION DAMPER INSTALLATION GUIDE

FOR HVAC SYSTEMS, UL, IBC, AND DAMPER MANUFACTURER'S

RECOMMENDATIONS

2. ALL RECTANGULAR DUCT ELBOWS MUST HAVE TURNING VANES UNLESS NOTED

OTHERWISE. ALL UNEQUAL TURNING VANES MUST HAVE SINGLE-THICKNESS

TURNING VANES WITH TRAILING EDGE. NOT ALL TURNING VANES ARE INDICATED

ON THE DRAWINGS.

3. ALL DUCT SIZE DIMENSIONS INDICATED ON THE DRAWINGS ARE CLEAR INSIDE

DIMENSIONS.

4. ALL HVAC PENETRATIONS EQUAL OR GREATER THAN 96 SQ IN AND ALONG THE

SECURE BOUNDARY MUST HAVE MANBARS.

5. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL FIRE

RATED WALLS AND ASSEMBLIES. PROVIDE APPROVED FIRE DAMPERS IN ALL

REQUIRED PENETRATIONS FOR DUCTWORK, GRILLES, REGISTERS, AND

DIFFUSERS.

6. COORDINATE THE LOCATION OF ALL DIFFUSERS, GRILLES, REGISTERS, ACCESS

DOORS, ETC. WITH ARCHITECTURAL REFLECTED CEILING PLANS.

7. CONTRACTOR MUST COORDINATE ALL DUCTWORK WITH PIPING, STRUCTURAL,

AND ELECTRICAL SYSTEMS AND MUST PROVIDE NECESSARY OFFSETS TO AVOID

CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.

8. PIPING SUPPORTS, ELECTRICAL TRAY AND CONDUIT SUPPORTS, OR CEILING

SUPPORTS, MUST NOT BE SUSPENDED FROM DUCTWORK.

9. DUCT MOUNTED ACCESS DOORS MUST BE PROVIDED AT EACH CONTROL DAMPER,

FIRE DAMPER, CONTROL INSTRUMENTS, AND OTHER EQUIPMENT THAT REQUIRES

SERVICE OR INSPECTION AND AT LOCATIONS SPECIFIED. THE ACCESS DOOR

MUST BE INSTALLED IN AN ACCESSIBLE LOCATION (PREFERABLY BOTTOM OF

DUCT) AND MUST OPEN AGAINST PRESSURE. CONTRACTOR MUST INSTALL

ACCESS DOORS AFTER SUCH LOCATIONS ARE APPROVED BY THE OWNER.

10. MANUAL VOLUME DAMPERS MUST BE PROVIDED WHERE INDICATED OR AS

REQUIRED FOR SYSTEM BALANCING.

11. PROVIDE TRANSITION FITTINGS WHEN CHANGING DUCT DIMENSIONS. ALL

OFFSETS IN THE DUCTWORK MUST BE OF THE SMACNA TYPE 3 (RADIUSED OR

OGEE) UNLESS OTHERWISE NOTED.

GENERAL INSTRUMENTATION NOTES

1. INSTRUMENT CONNECTIONS ARE NOT DIMENSIONED ON THE DRAWINGS. THE

CONNECTION LOCATIONS SHOWN ARE INTENDED TO SERVE AS A GENERAL GUIDE

ONLY TO ILLUSTRATE THE DESIRED LOCATIONS OF THE CONNECTIONS. FOR

INSTRUMENT CONNECTIONS NOT IDENTIFIED ON PLAN DRAWING(S) REFER TO HVAC

AIRFLOW AND INSTRUMENTATION DIAGRAMS FOR RELATIVE LOCATIONS. THE

CONTRACTOR MUST AVOID INTERFERENCE WITH OTHER INSTRUMENT

CONNECTIONS, PIPING, EQUIPMENT, AND THE WORK OF OTHER DISCIPLINES.

WHERE PRESSURE AND TEMPERATURE CONNECTIONS ARE SHOWN ADJACENT TO

EACH OTHER, A MINIMUM DISTANCE OF 12 IN MUST BE MAINTAINED BETWEEN

INSTRUMENT CONNECTIONS WHERE POSSIBLE.

2. INSTRUMENTATION (FOR EXAMPLE, PI, TI, PDI) IS NOT ALL SHOWN ON PLAN

DRAWINGS. CONTRACTOR MUST PROVIDE INSTRUMENTATION AS INDICATED ON

CONTROL DIAGRAMS AND MUST LOCATE DEVICES SUCH THAT A PERSON CAN

EASILY READ GAUGE WHILE STANDING ON FLOOR.

3. THERMOSTATS AND ROOM TEMPERATURE TRANSMITTERS MUST BE MOUNTED 4 FT

ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE.

4. ALL PRESSURE INSTRUMENTATION MUST BE FOR 0.75 IN DIA PIPING.

TEMPERATURE TAPS MUST BE SUITABLE FOR THERMOWELL, IN NO CASE LESS

THAN 0.75 IN. ALL PRESSURE INSTRUMENTATION MUST BE PROVIDED WITH A 0.75

IN ISOLATION BALL VALVE.

5. CONTRACTOR MUST AFFIX PERMANENT TAGS/LABELS TO ALL DEVICES AS

SPECIFIED.

6. CONTRACTOR MUST LABEL ALL DDC I/O SIGNAL LINES: 4-20 mA, VDC, OR SNVT.

7. CONTRACTOR MUST SHOW A UNIQUE IDENTIFIER FOR EACH DEVICE. WHERE

MULTIPLE IDENTICAL DEVICES ARE SHOWN (FOR EXAMPLE; DDC CONTROLLER, OA

SENSOR, OR EP TRANSDUCER) EACH MUST BE SEQUENTIALLY NUMBERED. WHERE

SEPARATE DDC CONTROLLER BUBBLES ARE USED TO REPRESENT/SHOW

A COMMON (OR SINGLE) CONTROLLER EACH BUBBLE MUST USE THE SAME

IDENTIFIER AND NUMBER. DEVICE AND SIGNAL IDENTIFIERS MUST BE CONSISTENT

BETWEEN DRAWINGS.

8. CONTRACTOR MUST UNIQUELY NUMBER ALL ANSI 709.1 DEVICES. THIS NUMBERING

MUST BE CONSISTENT BETWEEN ALL DRAWINGS.

GENERAL PIPE SUPPORT NOTES

1. ALL PIPE SUPPORTS MUST CONFORM TO THE REQUIREMENTS OF MSS-SP-58 AND

MSS-SP-69 AND AS SPECIFIED.

2. SUPPORTS MUST BE CAPABLE OF RESISTING HORIZONTAL AND VERTICAL FORCES

INDUCED BY EARTHQUAKE IN ADDITION TO NORMAL LOADS DUE TO WEIGHT OF

PIPE, FITTINGS, WEIGHT OF FLUID, INSULATION, AND LOADS DUE TO THERMAL

EXPANSION OR CONTRACTION. DESIGN OF SEISMIC BRACING MUST CONFORM TO

SPECIFICATIONS. SUPPORTS ON OUTSIDE PIPING EXPOSED TO WIND MUST BE

CAPABLE TO WITHSTAND 105 MPH WIND LOAD.

3. CONTRACTOR MUST BE RESPONSIBLE FOR THE DESIGN, FABRICATION, AND

INSTALLATION OF ALL PIPE SUPPORTS AND SEISMIC BRACING. SHOP DRAWINGS

THAT INDICATE TYPE AND LOCATION MUST BE PROVIDED FOR GOVERNMENT

APPROVAL.

4. CONTRACTOR MUST BE RESPONSIBLE FOR ALL SUPPLEMENTARY STEEL REQUIRED

FOR PIPE SUPPORT INSTALLATION.

5. CONTROL VALVE AND MOTOR OPERATED VALVE OPERATORS MUST BE BRACED

FOR SEISMIC LOADS IN ACCORDANCE WITH THE SPECIFICATIONS.

GENERAL PIPING NOTES

1. REFER TO LEGENDS AND SYMBOLS SHEETS FOR ADDITIONAL INFORMATION.

2. PIPING IS SHOWN FOR INFORMATION AND GENERAL ROUTING. THE CONTRACTOR

MUST PROVIDE FINAL ROUTING FOR ALL PIPING AND MUST PROVIDE SHOP

DRAWINGS THAT INCLUDE: EXACT DIMENSIONED ROUTING OF ALL PIPE, PIPE SIZE,

DIMENSIONED TIE-IN LOCATIONS, AND FIRE WALL PENETRATION DETAILS. THE

CONTRACTOR MUST AVOID INTERFERENCES WITH OTHER PIPING, EQUIPMENT,

CODE REQUIRED CLEARANCES, AND THE WORK OF OTHER DISCIPLINES.

3. ALL THREADED PIPING (VALVES, EQUIPMENT, AND FITTINGS) SHOWN ON THE

DRAWING AS FITTING TO FITTING AND NOT DIMENSIONED MUST BE INSTALLED

USING 3 IN LONG PIPE NIPPLES BETWEEN EACH ITEM UNLESS NOTED OTHERWISE.

4. PIPING AND SUPPORTS MUST NOT INTERFERE WITH EQUIPMENT MAINTENANCE

ACCESS OR PULL SPACE. PIPE SUPPORTS MUST BE FURNISHED AND INSTALLED IN

ACCORDANCE WITH THE SPECIFICATIONS.

5. ROUTE PIPING AS HIGH AS POSSIBLE. COORDINATE WITH ALL TRADES FOR

SPATIAL REQUIREMENTS PRIOR TO ROUGH-IN.

6. EQUIPMENT PIPING CONNECTION SIZES AND CONFIGURATION SHOWN ON

DRAWINGS ARE ESTIMATED AND MUST BE ADJUSTED FOR THE ACTUAL

EQUIPMENT FURNISHED.

7. CONTRACTOR MUST PROVIDE ALL PIPING WITH VALVED AND CAPPED HIGH POINT

VENTS AND LOW POINT DRAINS TO ALLOW VENTING, FILLING, AND DRAINING ALL

PIPE SECTIONS. UNLESS OTHERWISE INDICATED, SIZE MUST BE 1 IN FOR PIPE 6"

DIA AND LARGER, 0.75 IN FOR PIPE 0.75 IN THROUGH 4 IN DIA, AND LINE SIZE FOR

PIPE SMALLER THAN 0.75 IN DIAMETER. DRAWINGS DO NOT INDICATE ALL

REQUIRED VENTS AND DRAINS.

8. ISOLATION VALVES MUST BE PROVIDED WHERE INDICATED AND AS REQUIRED FOR

EQUIPMENT ISOLATION. EVERY VALVE MUST BE INSTALLED IN AN ACCESSIBLE

LOCATION. IF INSTALLED ABOVE A HARD CEILING, CONTRACTOR MUST PROVIDE

AN ACCESS PANEL FOR ACCESSIBILITY. REFER TO ARCHITECTURAL RCP FOR

ADDITIONAL INFORMATION.

9. ALL VALVE OPERATORS INCLUDING CONTROL VALVE AND MOTOR OPERATED

VALVE OPERATORS MUST BE ORIENTED PER MANUFACTURER'S INSTRUCTIONS

AND TO AVOID INTERFERENCE WITH OTHER PIPING AND EQUIPMENT.

GENERAL WATER RISER DIAGRAM NOTES

1. REFER TO LEGENDS AND SYMBOLS SHEETS FOR ADDITIONAL INFORMATION.

2. PROVIDE CHAINWHEEL OPERATORS FOR ALL VALVES IN EQUIPMENT ROOMS

MOUNTED GREATER THAN 7'-0" ABOVE FLOOR LEVEL. CHAIN MUST EXTEND DOWN

TO 7'-0" ABOVE FLOOR LEVEL.

3. ALL VALVES (EXCEPT MODULATING CONTROL VALVES) AND STRAINERS MUST BE

FULL SIZE OF PIPE BEFORE REDUCING SIZE TO MAKE CONNECTIONS TO

EQUIPMENT AND CONTROLS.

4. PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN THE HYDRONIC

PIPING SYSTEM. ALL PIPING MUST GRADE TO LOW POINTS. PROVIDE HOSE END

DRAIN VALVES EQUAL TO PIPE (MAX OF 3/4") AT THE BOTTOM OF ALL RISERS AND

LOW POINTS.

5. UNIONS AND/OR FLANGES MUST BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN

BYPASSES, AND IN LONG PIPING RUNS (100 FEET OR MORE) TO PERMIT

DISASSEMBLY FOR ALTERATION AND REPAIRS.

GENERAL PIPING NOTES

(CONTINUED)

1. CONTRACTOR MUST REVIEW ALL DRAWINGS AND SPECIFICATIONS PRIOR TO BID TO

ALLOW FOR A COMPLETE UNDERSTANDING OF THE SCOPE OF WORK REQUIRED.

2. THE PLANS ARE TO A GREAT EXTENT SCHEMATIC IN NATURE. DRAWING SCALES SHOULD

BE VERIFIED FROM DIMENSIONS ON ARCHITECTURAL PLANS. THE INFORMATION

PRESENTED IS AS EXACT AS COULD BE SECURED. THE CONTRACTOR MUST OBTAIN

EXACT LOCATION, MEASUREMENTS, LEVELS, ETC. AT THE SITE AND MUST

SATISFACTORILY ADAPT THE WORK TO THE ACTUAL CONDITIONS AT THE PROJECT SITE.

ALL UNDERGROUND UTILITIES MUST BE VERIFIED AND LOCATED TO AVOID DAMAGE AND

DISRUPTION OF SERVICES.

3. ALL ELEVATIONS SHOWN ARE ABOVE FINISHED FLOOR, UNLESS NOTED OTHERWISE.

4. THE CONTRACT DRAWINGS DO NOT SHOW EVERY FITTING AND APPURTENANCE FOR

EACH UTILITY BECAUSE OF THE SCALE OF THE DRAWINGS. EACH CONTRACTOR MUST

HAVE INCLUDED IN HIS BID SUFFICIENT FITTINGS, MATERIAL AND LABOR TO ALLOW FOR

ADJUSTMENT IN ROUTING OF UTILITIES MADE NECESSARY BY THE COORDINATION

PROCESS.

5. CONTRACTOR MUST COORDINATE WITH ALL TRADES PRIOR TO STARTING INSTALLATION.

COORDINATION INCLUDES, BUT NOT LIMITED TO, UTILITIES REQUIRED, SPACIAL

REQUIREMENTS AND ANY ADDITIONAL INSTALLATION REQUIREMENTS.

6. CONTRACTOR MUST PROVIDE COMPLETE AND FUNCTIONAL SYSTEMS FOR ITEMS

DETAILED IN THE CONTRACT DOCUMENTS. THIS INCLUDES, BUT IS NOT LIMITED TO,

VALVES, DAMPERS AND ACCESSORIES REQUIRED.

7. IF A DISCREPANCY EXISTS BETWEEN THE DRAWINGS AND THE SPECIFICATIONS,

CONTACT THE ENGINEER FOR RESOLUTION BEFORE PROCEEDING. IF CONTRACTOR

DOES NOT RECEIVE CLARIFICATION PRIOR TO BID, THEY MUST ASSUME THE MOST

EXPENSIVE OPTION FOR BID.

8. CONSTRUCTION OF SECURE AREAS, AND SECURE AREA MATERIALS AND COMPONENTS,

SHALL COMPLY WITH UFC 4-010-015 AND IC TECH SPECS FOR ICD/ICS 705, AND FULLY

MEET AND PASS ALL ACCREDITATION.

GENERAL MECHANICAL NOTES

9. SUPPORTS - EQUIPMENT, PIPING, DUCTWORK, OR ANY OTHER ACCESSORY MUST NOT BE

SUPPORTED FROM OTHER PIPING, DUCTWORK, METAL ROOF DECK, LATERAL BRACING

BRIDGING, OR CONDUIT. ITEMS MUST ONLY BE SUPPORTED FROM BUILDING STRUCTURE.

10. ALL EQUIPMENT MUST BE SELECTED FOR SITE CONDITIONS.

11. PLAN AND SECTION DRAWINGS ARE BASED ON SPECIFIC BASIS-OF-DESIGN EQUIPMENT

MODELS. LAYOUT OF EQUIPMENT, CONCRETE PADS, DUCT CONNECTIONS AND PIPING

EQUIPMENT MUST BE VERIFIED AND ADJUSTED BY CONTRACTOR TO MATCH ACTUAL

EQUIPMENT FURNISHED. PHYSICAL CONSTRAINTS MAY PRECLUDE PURCHASE OF

CERTAIN EQUIPMENT MODELS. PLACEMENT OF ACTUAL EQUIPMENT FURNISHED MUST

NOT VIOLATE CODE RELATED SPACE REQUIREMENTS AND MANUFACTURER-

RECOMMENDED MAINTENANCE SPACE. UNLESS INDICATED OTHERWISE, CONCRETE

HOUSEKEEPING PAD, AS DETAILED ON THE STRUCTURAL DRAWINGS, MUST BE PROVIDED

FOR ALL FLOOR MOUNTED MECHANICAL EQUIPMENT. THE MECHANICAL CONTRACTOR

MUST COORDINATE THE PAD DIMENSIONAL REQUIREMENTS WITH THE STRUCTURAL

CONTRACTOR.

12. BEFORE INSTALLATION OF EQUIPMENT CONTRACTOR MUST VERIFY THAT COILS, TUBES,

AND OTHER MAINTENANCE ITEMS FOR EQUIPMENT CAN BE REMOVED WITHOUT

INTERFERENCE. CONTRACTOR MUST PROVIDE ADEQUATE ACCESS TO ALL EQUIPMENT

AND RECOMMENDED MAINTENANCE CLEARANCES.

13. ALL PENETRATIONS OF FIRE RESISTANCE-RATED CONSTRUCTION RATED ASSEMBLIES

ARE TO BE PROTECTED BY AN APPROVED THROUGH-PENETRATION SYSTEM THAT HAS

BEEN TESTED IN ACCORDANCE WITH DIVISION 7 SPECIFICATIONS. REFER

ARCHITECTURAL PLANS FOR FIRE RESISTANCE-RATED CONSTRUCTION LOCATIONS.

14. ALL HVAC PENETRATIONS IN FIRE RESISTANCE-RATED CONSTRUCTION MUST HAVE AN

APPROVED LIFE SAFETY DAMPER AND IN COMPLIANCE WITH NFPA. ALL LIFE SAFETY

DAMPERS (FIRE, SMOKE, AND FIRE/SMOKE) MUST BE INSTALLED IN ACCORDANCE WITH

SHEET METAL AND AIR CONDITIONING NATIONAL ASSOCIATION (SMACNA), SMOKE AND

RADIATION DAMPER INSTALLATION GUIDE FOR HVAC SYSTEMS, UL, IBC, AND DAMPER

MANUFACTURER'S RECOMMENDATIONS. FIRE DAMPERS MUST BE INSTALLED IN ALL FIRE

RESISTANCE RATED WALLS, PARTITIONS AND FLOORS. FIRE/SMOKE DAMPERS ARE

REQUIRED IN FIRE/SMOKE RATED CONSTRUCTION. SMOKE DAMPERS ARE REQUIRED IN

SMOKE RATED CONSTRUCTION. RADIATION DAMPERS ARE REQUIRED IN CEILING RATED

CONSTRUCTION. REFER ARCHITECTURAL PLANS FOR FIRE RESISTANCE-RATED

CONSTRUCTION LOCATIONS.

15. DUCT MOUNTED ACCESS DOORS MUST BE PROVIDED AT EACH CONTROL DAMPER, FIRE

DAMPER, CONTROL INSTRUMENTS, AND OTHER EQUIPMENT THAT REQUIRES SERVICE OR

INSPECTION AND AT LOCATIONS SPECIFIED. THE ACCESS DOOR MUST BE INSTALLED IN

AN ACCESSIBLE LOCATION (PREFERABLY BOTTOM OF DUCT) AND MUST OPEN AGAINST

PRESSURE. CONTRACTOR MUST INSTALL ACCESS DOORS AFTER SUCH LOCATIONS ARE

APPROVED BY THE OWNER.

16. CONTRACTOR TO PROVIDE DUCT TRANSITIONS AS REQUIRED FOR CONNECTION OF

DUCTS TO THE MECHANICAL UNITS. VERIFY SIZES FOR FINAL CONNECTION TO THE

PURCHASED EQUIPMENT.

17. PROVIDE TRANSITION FITTINGS WHEN CHANGING DUCT DIMENSIONS. ALL OFFSETS IN

THE DUCTWORK MUST BE OF THE SMACNA TYPE 3 (RADIUSED OR OGEE) UNLESS

OTHERWISE NOTED.

18. ALL RECTANGULAR SUPPLY, RETURN, AND EXHAUST AIR ELBOWS MUST BE SQUARE WITH

TURNING VANES OR RADIUS ELBOWS. ALL UNEQUAL TURNING VANES MUST HAVE

SINGLE-THICKNESS TURNING VANES WITH TRAILING EDGE. NOT ALL TURNING VANES ARE

INDICATED ON THE DRAWINGS.

19. ALL DUCT SIZE DIMENSIONS INDICATED ON THE DRAWINGS ARE CLEAR INSIDE

DIMENSIONS.

20. COORDINATE THE LOCATION OF ALL DIFFUSERS, GRILLES, REGISTERS, ACCESS DOORS,

ETC. WITH ARCHITECTURAL REFLECTED CEILING PLANS, FIRE PROTECTION SHOP

DRAWINGS AND ELECTRICAL SPECIAL SYSTEM PLANS.

21. CONTRACTOR MUST COORDINATE ALL DUCTWORK WITH PIPING, STRUCTURAL, AND

ELECTRICAL SYSTEMS AND MUST PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS

AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.

10. ALL BUTTERFLY VALVES MUST HAVE SPOOL PIECES UPSTREAM AND

DOWNSTREAM SO THAT THE DISK WILL NOT ENTER ADJACENT FITTINGS.

WHERE STEEL FLANGES CONNECT WITH CAST IRON FLANGES, THEY MUST

BE PROVIDED WITH FLAT FACES AND FULL FACE GASKETS.

11. UNLESS DIRECTED OTHERWISE, DO NOT ROUTE PIPING ABOVE ELECTRICAL

PANELS AND GEAR. ANY PIPING THAT IS ROUTED OVER SUCH EQUIPMENT

MUST BE PROVIDED WITH A DRIP PAN.

12. PIPING INSULATION IS NOT SHOWN ON PLANS FOR DRAWING CLARITY.

13. PIPING PLANS DO NOT SHOW ALL REQUIRED DEVICES, VALVES AND

APPURTANANCES. SEE DIAGRAMS AND DETAILS FOR ITEMS NOT SHOWN ON

PIPING PLANS.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VF

AC

P

AC

IF

IC

M

A K

AL

A

PA

, H

AW

AI

I

AS NOTED

FY

P R

O

JE

C T

G D

S C

O M

M

AN

D C

EN

TE

R

N A

VF

AC

P A

C

IF

IC

1764210

KYM

JC

Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813

A/E Task Order No. N6274223F0324

FOR REVIEW

ONLY

Name

Registration Number #

These documents are for Design Review and not intended for

Construction Bidding or Permit Purposes. They were prepared by, or under the supervision of:

Date

SEAL

24 JUN 2024

AN

DE

RS

EN

A

IR

F O

RC

E

BA

SE

LJE

AWK/DMK

6/

/2

6:

:0

PM

P6

_1

_1 4_

G _d et ac he d.

rv t

14GI-M-003

ME

CH

AN

IC

AL

G

EN

ER

AL

N

OT

ES

MAMMGP JTW

G

UA

M

G

I-M -0

100% DESIGN SUBMITTAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

P R

O J E

C T

S

IT

E

C O

M M

A N

D C

E N

T E

R

A N

D E

R S

E N

A

IR

F O

R C

E B

A S

E G

U

S

S

S

S

S

S

M

M

M

M

F

F

LS

L

T

S

S S

S

MF

A

D

VFD

MS

P

VB

V/A

PSD

AS

P

T

EDUCATOR, AIR INJECTOR

STRAINER, Y-TYPE

POST INDICATOR GATE VALVE

STRAINER, SIMPLEX BASKET TYPE

STRAINER, DUPLEX BASKET TYPE

STRAINER, CONE OR PLATE TYPE

RUPTURE DISC

MUFFLER

FLEXIBLE HOSE

EXPANSION JOINT

SIGHT GLASS, INLINE

FLOW INDICATOR, INLINE

SOLENOID OPERATED VALVE

SOLENOID OPERATED VALVE 3-WAY

SOLENOID OPERATED VALVE 4-WAY

SOLENOID OPERATED VALVE,

WITH MANUAL OVERRIDE

OIL MIST ELIMINATOR

FILTER IN-LINE

INLET FILTER SILENCER

PRESSURE REDUCING REGULATOR

PRESSURE REDUCING REGULATOR,

WITH FILTER

PRESSURE REDUCING REGULATOR,

WITH FILTER AND PRESSURE INDICATOR

PRESSURE REDUCING REGULATOR,

WITH PRESSURE INDICATORS

PRESSURE REGULATING VALVE,

WITH INTERNAL SENSING TAP

PRESSURE REGULATING VALVE,

WITH INTERNAL SENSING TAP

AND PRESSURE INDICATOR

PRESSURE REGULATING VALVE,

WITH EXTERNAL SENSING TAP

PRESSURE REGULATING VALVE,

WITH EXTERNAL SENSING TAP

AND PRESSURE INDICATOR

BACK PRESSURE REGULATING VALVE,

WITH INTERNAL SENSING TAP

BACK PRESSURE REGULATING VALVE,

WITH INTERNAL SENSING TAP

AND PRESSURE INDICATOR

BACK PRESSURE REGULATING VALVE,

WITH EXTERNAL SENSING TAP

BACK PRESSURE REGULATING VALVE,

WITH EXTERNAL SENSING TAP AND

PRESSURE INDICATOR

BACK PRESSURE REGULATING VALVE,

WITH INTERNAL AND EXTERNAL

SENSING TAP

TEMPERATURE REGULATING VALVE,

WITH EXTERNAL SENSING TAP

AUTOMATIC RECIRCULATION

CONTROL

FLOW ELEMENT (ORIFICE)

VENTURI

ANGLE RELIEF VALVE,

SAFETY RELIEF VALVE

ANGLE/SAFETY RELIEF VALVE,

WITH DRIP PAN ELBOW

RELIEF VALVE, IN-LINE

HYDROSTATIC RELIEF VALVE

RELIEF VALVE, WITH FLAME

ARRESTOR COMBINATION

FLAME ARRESTOR

AUTOMATIC AIR VENT

VENT SEAL

HEAD CHAMBER

SEPARATION CHAMBER

PRESSURE BREAKDOWN

ISOLATED DIAPHRAGM

STRAIGHTENING VANES

QUICK DISCONNECT

BUG SCREEN

SPRAY NOZZLE

CIRCUIT BALANCING VALVE

GAUGE CONNECTIONS

PRESSURE/TEMPERATURE (P/T) PLUG

SIPHON LOOP

SAMPLE COIL

EXHAUST HEAD

SOLENOID OPERATED VALVE,

WITH DOUBLE COIL

MOTOR OPERATED VALVE

MOTOR OPERATED VALVE 3-WAY

MOTOR OPERATED VALVE,

WITH MANUAL OVERRIDE

MOTOR OPERATED VALVE 4-WAY

GATE/ISOLATION VALVE

GATE VALVE, SLIDE

PLUG VALVE

PLUG VALVE, 3-WAY

GLOBE VALVE

GLOBE VALVE, 3-WAY

CHECK VALVE

CHECK VALVE, STOP

CHECK VALVE, ANGLE STOP

CHECK VALVE, AIR OPERATED

CHECK VALVE, AIR OPERATED

WITH CLOSING HANDWHEEL

BALL VALVE

BALL VALVE, 3-WAY

BALL VALVE, WITH VENT

BALL VALVE, 3-WAY

WITH FUSIBLE LINK

BUTTERFLY VALVE

NEEDLE VALVE

PET COCK

ANGLE VALVE

3-WAY VALVE

4-WAY VALVE

DIAPHRAGM VALVE

FLOAT VALVE

FLUSH VALVE

FOOT VALVE

INTERLOCK VALVE

PINCH VALVE

UNIT TANDEM BLOWDOWN VALVE

BALL VALVE,

WITH FUSIBLE LINK

PRESSURE REDUCING REGULATOR,

WITH PRESSURE INDICATOR

TRIPLE DUTY VALVE

ANTI-SYPHON VALVE

MECHANICAL PIPING SYMBOLS

PUMP SUCTION DIFFUSER

FLEXIBLE PIPE CONNECTION

LIQUID SEPARATOR

LUBRICATOR

VACUUM BREAKER

TRAP (STEAM)

THERMOSTATIC RADIATOR

VALVE WITH REMOTE SENSOR

ANNUBAR

PRESSURE VACUUM VENT

COMPRESSED AIR, BREATHING

AIR, OR INSTRUMENT AIR, DROP

VACUUM BREAKER/AIR VENT

(THE FOLLOWING ARE ALL ENCOMPASSING AND MAY OR MAY NOT BE UTILIZED HERE-IN)

STRAINER WITH BLOWDOWN

VALVE AND HOSE CONNECTION

CONTROL VALVE

PRESSURE REDUCING VALVE

INLINE CONCENTRIC REDUCER

THERMOMETER

INLINE ECCENTRIC REDUCER

AQUASTAT

FIN TUBE RADIATOR

FLOW MEASURING

AND BALANCING

DEVICE

MOTOR STARTER

VARIABLE FREQUENCY DRIVE

THERMOMETER

BALL VALVE WITH VENT

EXPANSION VALVE

PRESSURE DIFFERENTIAL SENSOR

UNION PURGE VALVE

BALANCING VALVE

FLOW INDICATOR

SIGHT GLASS

3-WAY CONTROL VALVE

LIQUID FLOW SWITCH

FLOW SWITCH

ELBOW DOWN

ELBOW UP

TEE DOWN

TEE UP

SLOPE

PIPE LINE CONCENTRIC REDUCTION

FLOW LINE WITH DIRECTION OF

FLOW

DIRECTION OF SLOPE

(TOWARD LOW POINT)

HEAT TRACED PIPE

HEAT TRACED PIPE INDICATING

ORIGIN OR TERMINATION POINT

PIPE BREAK

CLOSURE, FLANGED

CLOSURE, WELDED CAP

CLOSURE, SCREWED CAP

HOSE CONNECTION

CONNECTION, PLUGGED

INSULATING FLANGE OR

BUSHING

UNION

CLAMP COUPLING

ELBOW

45º ELBOW

45º ELBOW DOWN

45º ELBOW UP

TEE

ELBOW DOWN TO TEE

TEE DOWN TO ELBOW

TEE DOWN TO TEE

ELBOW DOWN LEFT

ELBOW DOWN RIGHT

END CAP

PIPE UP

FLANGES

PIPE ANCHOR

PIPE GUIDE

DUAL DIRECTION OF FLOW

MECHANICAL PIPE AND FITTING LEGEND

(THE FOLLOWING ARE ALL ENCOMPASSING AND MAY OR MAY NOT BE UTILIZED HERE-IN)

PIPE LINE ECCENTRIC REDUCTION

MANUAL AIR VENTM

PRESSURE INDICATOR

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VF

AC

P

AC

IF

IC

M

A K

AL

A

PA

, H

AW

AI

I

AS NOTED

FY

P R

O

JE

C T

G D

S C

O M

M

AN

D C

EN

TE

R

N A

VF

AC

P A

C

IF

IC

1764210

KYM

JC

Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813

A/E Task Order No. N6274223F0324

FOR REVIEW

ONLY

Name

Registration Number #

These documents are for Design Review and not intended for

Construction Bidding or Permit Purposes. They were prepared by, or under the supervision of:

Date

SEAL

24 JUN 2024

AN

DE

RS

EN

A

IR

F O

RC

E

BA

SE

LJE

AWK/DMK

6/

/2

6:

:0

PM

P6

_1

_1 4_

G _d et ac he d.

rv t

14GI-M-004

ME

CH

AN

IC

AL

P

IP

IN

G

LE

GE

ND

S

MAMMGP JTW

G

UA

M

G

I-M -0

100% DESIGN SUBMITTAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

P R

O J E

C T

S

IT

E

C O

M M

A N

D C

E N

T E

R

A N

D E

R S

E N

A

IR

F O

R C

E B

A S

E G

U

C

C

T

H

F

VS

TT

C

P

SD

PI

SDT

MT

PDG

PDT

TG

E

ES

TE

FOB OR FOT

HS

FAN, CENTRIFUGAL

FAN, PROPELLER

OR VANEAXIAL

PLUG FAN. DUAL

ROOF OR WALL HOOD

SUPPLY AIR

ROOF OR WALL HOOD

EXHAUST AIR

UNIT HEATER

HORIZONTAL DISCHARGE

CONVECTOR

LOUVER

DOOR LOUVER

DAMPER, SHUT-OFF

DAMPER, CONTROL

DAMPER, OPPOSED BLADE

DAMPER,

(SINGLE LINE DUCTWORK)

BACKDRAFT DAMPER

MOTORIZED OPERATOR

AIR MONITOR STATION

WATER COIL

THERMOSTAT

HUMIDISTAT

FREEZESTAT

VAPOR SENSOR

DIRECTION OF FLOW

FLOW ARROW

DISCHARGE/DIRECT

FLOW ARROW

INLET/INDIRECT

STRAIGHTENING VANES

TEMPERATURE TRANSMITTER

CO2 SENSOR

STATIC PRESSURE SENSOR

EMERGENCY AIR DISTRIBUTION SHUTOFF

HVAC LEGEND

FLAT PLATE

ENERGY

RECOVERY

ENTHALPY WHEEL

(THE FOLLOWING ARE ALL ENCOMPASSING AND MAY OR MAY NOT BE UTILIZED HERE-IN)

SMOKE DETECTOR

PRESSURE INDICATOR

SPEED DIFFERENTIAL TRANSMITTER

MOISTURE TRANSMITTER

PRESSURE DIFFERENTIAL GAUGE

PRESSURE DIFFERENTIAL TRANSMITTER

TEMPERATURE SENSOR

TEMPERATURE GAUGE

COIL (ELECTRIC / REFRIGERANT)

FILTER, DISPOSABLE

FILTER, HIGH EFFICIENCY

ON CONTROLS NO DEFINITION

AIR OUTLET AND INLET IDENTIFICATION

DEVICE TYPE: S-SUPPLY, E-EXHAUST, R-RETURN, T-TRANSFER

DEVICE GROUP: R-REGISTER, G-GRILLE, D-DIFFUSER

DEVICE DESIGNATION

CFM THRU DEVICE

NUMBER OF SLOTS (OPTIONAL)

S R-1-750-1

24X10-6Ø-2

NUMBER OF THROWS (OPTIONAL)

DUCT SIZE (IN) OR DIAMETER (Ø) (OPTIONAL)

SIZE - WIDTH BY LENGTH (IN)

FLEXIBLE CONNECTION

TURNING VANES

SPLITTER DAMPER

FLEXIBLE DUCT

REGISTER OR GRILLE IN

DUCTWORK

EXTRACTOR

SUPPLY DIFFUSER

MANUAL VOLUME DAMPER OR

BALANCING DAMPER

SUPPLY DIFFUSER

WITH DIRECTION OF

THROW INDICATED

RETURN INLET,

GRILLE OR REGISTER

EXHAUST INLET,

GRILLE OR REGISTER

24"X12"

8" Ø

30"X20"

30"X20"

12"X24"

DUCT TRANSITION FLAT ON

BOTTOM OR TOP

DUCT SIZE TRANSITION

FLAT ON ONE SIDE

DUCT SIZE TRANSITION

CONCENTRIC

DUCT SIZE TRANSITION

RECTANGULAR TO ROUND

SUPPLY AIR DUCT OR AIR UNDER POSITIVE

PRESSURE (CONDITIONED AIR) TURNING

TOWARD/AWAY RESPECTIVELY

RECTANGULAR

ROUND

OVAL

RETURN AIR/OUTSIDE AIR DUCT, AIR UNDER

NEGATIVE PRESSURE (UNCONDITIONED AIR)

TURNING TOWARD/AWAY RESPECTIVELY

EXHAUST AIR DUCT, AIR UNDER NEGATIVE

PRESSURE (UNCONDITIONED AIR) TURNING

TOWARD/AWAY RESPECTIVELY

RECTANGULAR DUCT SIZE FIRST

NUMBER IS SIDE SHOWN

ROUND DUCT DIMENSION

OVAL DUCT DIMENSION

FIRST DIMENSION IS SIDE SEEN

RECTANGULAR DUCT IN SECTION.

FIRST NUMBER IS ARROW SIDE

OVAL DUCT IN SECTION FIRST

NUMBER IS ARROW SIDE

SUPPLY OUTLET, REGISTER OR

GRILLE IN DUCTWORK (SIDE OR

BOTTOM)

INTERNALLY LINED DUCT

RECTANGULAR

ROUND

OVAL

RECTANGULAR

ROUND

OVAL

RETURN INLET, REGISTER OR

GRILLE IN DUCTWORK (SIDE

OR BOTTOM)

EXHAUST INLET, REGISTER

OR GRILLE IN DUCTWORK

(SIDE OR BOTTOM)

HVAC LEGEND

D DROP IN DUCT, AIR

FLOW DIRECTION

SHOWN

R RISE IN DUCT, AIR

FLOW DIRECTION

SHOWN

D

R

D

R

(THE FOLLOWING ARE ALL ENCOMPASSING AND MAY OR MAY NOT BE UTILIZED HERE-IN)

PLUG FAN, SINGLE

HYDROGEN SENSOR

TERMINAL UNIT

FIRE DAMPER (2 HOUR)

MOTOR OPERATED DAMPER

(MOD) HORIZONTAL DUCT

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VF

AC

P

AC

IF

IC

M

A K

AL

A

PA

, H

AW

AI

I

AS NOTED

FY

P R

O

JE

C T

G D

S C

O M

M

AN

D C

EN

TE

R

N A

VF

AC

P A

C

IF

IC

1764210

KYM

JC

Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813

A/E Task Order No. N6274223F0324

FOR REVIEW

ONLY

Name

Registration Number #

These documents are for Design Review and not intended for

Construction Bidding or Permit Purposes. They were prepared by, or under the supervision of:

Date

SEAL

24 JUN 2024

AN

DE

RS

EN

A

IR

F O

RC

E

BA

SE

LJE

AWK/DMK

6/

/2

6:

:1

PM

P6

_1

_1 4_

G _d et ac he d.

rv t

14GI-M-005

ME

CH

AN

IC

AL

H

VA

C

LE

GE

ND

S

MAMMGP JTW

G

UA

M

G

I-M -0

100% DESIGN SUBMITTAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

P R

O J E

C T

S

IT

E

C O

M M

A N

D C

E N

T E

R

A N

D E

R S

E N

A

IR

F O

R C

E B

A S

E G

U

S

C

HX-xxxHX-xxx

HX-XXX

CSF-XXX

CH-XXX

XX-YYY

AIR SEPARATOR

EXPANSION TANK

CHEMICAL SHOT FEEDER

AIR COOLED CHILLER

PUMP,

POSITIVE DISPLACEMENT

PUMP

PUMP, DIAPHRAGM

CHEMICAL FEED PUMP

HEATER,

IMMERSION TANK TYPE

MOTOR

METER

CYCLONIC SEPARATOR

MECHANICAL EQUIPMENT LEGEND

XX-EQUIPMENT TYPE (SEE LEGEND)

YYY- EQUIPMENT NUMBER

(THE FOLLOWING ARE ALL ENCOMPASSING AND MAY OR MAY NOT BE UTILIZED HERE-IN)

HEAT EXCHANGER (BRAZED PLATE OR PLATE & FRAME)

HEAT EXCHANGER (SHELL AND TUBE)

RECIRCULATING PUMP OR SUBMERSIBLE PUMP

EQUIPMENT TAG IDENTIFICATIONEQUIPMENT TAG DESIGNATOR

XXXX-XXXXXXXXX

EXAMPLE: FCU-14PP41101

EQUIPMENT TAG NUMBER

SYSTEM ID

BUILDING ID

SITE

EQUIPMENT TAG

T TANK

TCV TEMPERATURE CONTROL VALVE

TG TRANSFER GRILLE

TO TRANSFER OPENING

UH UNIT HEATER

VAV VARIABLE AIR VOLUME TERMINAL UNIT

VF VENTILATION FAN

WB WATER BOILER

WH WATER HEATER

WAHP WATER TO AIR HEAT PUMP

WWHP WATER TO WATER HEAT PUMP

WSHP WATER SOURCE HEAT PUMP

BUILDING IDENTIFIER

YY BUILDING (OR LOCATION) NAME

(CONTINUED)

EQUIPMENT TAG DESIGNATOR

AC AIR COMPRESSOR

ACC ACCUMULATOR

ACCU AIR COOLED CONDENSING UNIT

ACU AIR CONDITIONING UNIT

AD AIR DRYER

AFC AFTER COOLER

AFMA AIR FLOW MEASUREMENT ARRAY

AHU AIR HANDLING UNIT

AR AIR RECEIVER

AS AIR SEPARATOR

BFP BACKFLOW PREVENTER

BLR BOILER

C CONDENSER

CC COOLING COIL

CH CHILLER

CHWP CHILLED WATER PUMP

CMP COMPRESSOR

COND CONDENSER UNIT

CRAC COMPUTER ROOM AIR CONDITIONING UNIT

CRAH COMPUTER ROOM AIR HANDLER

CSF CHEMICAL SUPPLY FEEDER

CT COOLING TOWER

CUH CABINET UNIT HEATER

CV CONTROL VALVE

CWP CONDENSER WATER PUMP

DA DEAERATOR

DDT DIESEL EXHAUST FLUID DAY TANK

DEFP DIESEL EXHAUST FLUID PUMP

DEFT DIESEL EXHAUST FLUID BULK TANK

DHC DUCT HEATING COIL

DHP DOMESTIC HOT WATER PUMP

D DAMPER

DOAS DEDICATED OUTDOOR AIR SYSTEM

DSP DUPLEX SUMP PUMP

ECON ECONOMIZER

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EG EXHAUST GRILLE

ER EXHAUST REGISTER

ET EXPANSION TANK

EUH ELECTRIC UNIT HEATER

EVAP EVAPORATOR

EWU ENERGY WHEEL UNIT

FBT FUEL BULK TANK

FCU FAN COIL UNIT

FD FIRE DAMPER

FF FUEL FILTER

FLT FILTER

FOP FUEL OIL PUMP

FP FUEL POLISHER

FSD FIRE/SMOKE DAMPER

FPB FAN POWERED TERMINAL BOX

HC HEATING COIL

HX HEAT EXCHANGER

HP HEAT PUMP

HUM HUMIDIFIER

HWP HEATING WATER PUMP

IH INFRARED HEATER

L LOUVER

LOC LUBE OIL COOLER

LOH LUBE OIL HEATER

LOP LUBE OIL PUMP

MAU MAKEUP AIR UNIT

MOD MOTOR OPERATED DAMPER

MOV MOTOR OPERATED VALVE

PVR POWER ROOF VENTILATOR

PRV PRESSURE REDUCING VALVE OR

PRESSURE RELIEF VALVE

RAH RECIRCULATING AIR HANDLER

RCV RECEIVER

RD RELIEF DAMPER

RF RETURN FAN

RG RETURN GRILLE

RH ROOF HOOD

RHC REHEAT COIL

RLF RELIEF FAN

RR RETURN REGISTER

RTU ROOF TOP UNIT

SD SUPPLY DIFFUSER

SF SUPPLY FAN

SFH SPRAY FOG HUMIDIFIER

SP SUMP PUMP

(THE FOLLOWING ARE ALL ENCOMPASSING AND MAY OR MAY NOT BE UTILIZED HERE-IN)

PUMP, SUBMERSIBLE SYSTEM IDENTIFIER

03 FUEL OIL SYSTEM

12 POTABLE WATER SYSTEM (PW, DCW, & DHW)

16 NON-POTABLE WATER SYSTEM

17 BUILDING WASTE SYSTEMS

(SANITARY, OIL WASTE, ROOF DRAINS, ETC.)

18 HAZARDOUS FLUID CONTAINMENT

31 CHILLED WATER SYSTEMS

33 REFRIGERATION (DX) SYSTEMS

41 AIR SUPPLY, EXHAUST, AND VENTILATION SYSTEMS

51 MONITORING SYSTEMS (02, CO, N2 PURGE, ETC.)

52 FIRE PROTECTION SYSTEMS

65 BMS

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P

AR

TM

E

N T