Questions. Amend 003.pdf
PDF 126 KB Posted
- Solicitation number
- N4215827QS001
About this file
This is a Questions and Answers document addressing clarifications for a generator and Automatic Transfer Switch (ATS) rental solicitation issued by NAVFAC at the Norfolk Naval Shipyard (NNSY). The quote deadline is October 23, 2026, at 10:00 AM EDT, with an anticipated delivery date of November 2, 2026, at Building 298.
The solicitation requires rental of three generators: one 500 kW unit and two 350 kW units (with 320 kW as an acceptable alternative). Associated ATS panels must be 480V, 3-Pole, Service Entrance-Rated with NEMA 3 or better enclosures; the 500 kW generator requires an 800A ATS while each 350 kW generator requires a 400A ATS. Generators may exceed the stated footprint by up to 2 feet. The Government will provide diesel fuel, ongoing refueling, and fuel delivery through NAVFAC's refueling team, while NNSY's Shop 99 will provide auxiliary electrical power for support equipment and will furnish cables and perform all ATS and generator connections/installations. Contractors must perform voltage and phase rotation checks and participate in initial lockout coordination. Monthly invoicing through WAWF is required upon rendering of service, with the Contracting Officer's Representative reviewing for acceptance. No DD Form 254 or security clearances beyond U.S. citizenship, DBIDS registration, NAVSEA green badges, and site access requirements are needed for subcontractor drivers and service technicians. Amendment 001 updated the quote sheet to reflect CLIN 1003 for the ATS option and added a TOTAL column for each CLIN.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Combo S-S.EDG Rental.Amend 002.pdf | ||
| Questions. Amend 002.pdf | ||
| Attachment 2 - Quote Sheet.Amend 001.xlsx | XLSX spreadsheet | |
| Combo S-S.EDG Rental.FINAL.pdf | ||
| Attachment 1 - Statement of Work.pdf | ||
| Attachment 3 - DD Form 254.pdf | ||
| Attachment 2 - Quote Sheet.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. Is diesel fuel, ongoing refueling, and fuel delivery provided by the Government, or must the contractor include these costs? Who provides auxiliary electrical power for block heaters and battery chargers?
NAVFAC’s refueling team will provide fuel and ongoing refueling. NNSY’s Shop 99 will provide auxiliary electrical power for block heaters and battery chargers.
2. Are electrical power cables and physical connection/installation of the ATS and generators furnished/performed by NNSY? Please confirm the contractor’s responsibility beyond on-site technical assistance, phase/voltage verification, and lockout coordination.
NNSY’s Shop 99 will provide cables and perform connection/installation of the ATSs and generators.
3. Are all three ATS panels required to be service-entrance-rated, 800A, 480V, 3-pole, NEMA 3 or better, and is the ATS configuration approved for each generator?
The ATS for the 500 kW generator is required to be 800 A, and the two ATSs for the 350 kW generators are required to be 400 A. All three ATSs are required to be 480 V, 3-Pole, Service Entrance-Rated, and with an enclosure of NEMA 3 or above.
4. Is the anticipated delivery/start date November 2, 2026, and what are the access, staging, and acceptance requirements at Building 298?
Yes, the anticipated delivery is November 2nd, 2026. The contractor shall perform voltage and phase rotation checks and participate in initial lockout coordination at Building 298.
5. Please confirm the required DD Form 254/security clearance obligations for this rental and whether subcontractor drivers and service technicians require any clearances beyond the stated U.S. citizenship, DBIDS, NAVSEA green badges, and site access requirements.
No other clearances beyond what you have stated are needed.
6. The SAM.gov posting identifies October 23, 2026, 10:00 AM EDT as the quote deadline, while page 2 of the solicitation states October 23, 2027. Please confirm the controlling deadline.
The deadline is October 23, 2026 at 10:00 AM EDT.
7. The solicitation uses CLIN 1003 for the ATS option; please confirm how the option ATS line should be entered if the supplied quote sheet is inconsistent.
For Amendment 001, the quote sheet has been updated to reflect CLIN 1003 for the ATS option.
In addition, a column for TOTAL for each CLIN has been added.
8. Please confirm whether the Government expects monthly invoicing for accepted rental services through WAWF and whether there are any specific acceptance or payment milestones.
Upon rendering of monthly service, please submit monthly invoicing through WAWF. Upon receipt, the Contracting Officer’s Representative (COR) will review for acceptance.
9. Would it be acceptable to be over by 2ft on footprint stated in the statement of work? Also, is a 320KW generator an acceptable alternative for the 350KW requested ?
Yes, it is acceptable for the generators to be over by 2 ft on footprint, and a 320 kW generator is an acceptable alternative for the 350 kW generator.