This is a Statement of Work for the rental of emergency diesel generator equipment and associated services at Norfolk Naval Shipyard (NNSY) in Portsmouth, Virginia.
NNSY requires the rental of three trailer-mounted Emergency Diesel Generators (EDGs) and three Automatic Transfer Switches (ATS) to provide standby electrical power during utility outages at Berth 20 and Slab 36. The equipment will support project trailers and a living barge. The rental package includes one 500 kW standby-rated diesel generator and two 350 kW standby-rated diesel generators, each delivering 480 Volts, 3-Phase power. All generators must be equipped with auxiliary block heaters, battery charging circuits, output circuit breakers with overcurrent protection, and weatherproof operating instructions. Each unit requires a footprint not exceeding 20' L x 8' W and total weight not exceeding 45,000 lbs. Fuel systems must support minimum 24-hour runtime at full load, with external tanks not exceeding 1,240 gallons. All three Automatic Transfer Switches must be 800 Amps, 480 Volts, 3-Phase, 3-Pole, Service Entrance-rated units in NEMA 3 or above enclosures.
The Contractor bears full responsibility for all routine, preventative, and emergency maintenance at no additional charge, including parts and labor. 24/7/365 repair coverage is required with on-site technician arrival within four hours of notification and unit replacement within eight hours if on-site repairs are not possible. All service personnel must be U.S. citizens compliant with NNSY security requirements, including DBIDS cards and NAVSEA green badges. The Contractor must provide weather and saltwater-corrosion protection coverings, comprehensive technical documentation upon delivery, and on-site technical support during initial cable installation and Hazardous Energy Control coordination. Equipment delivery to NNSY Building 298 in Portsmouth, Virginia must include load-bank certification testing completed within two weeks prior to delivery. NNSY reserves the right to return equipment with 48 hours' written notice, with rental costs prorated based on actual calendar days in use.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions. Amend 003.pdf | ||
| Combo S-S.EDG Rental.Amend 002.pdf | ||
| Questions. Amend 002.pdf | ||
| Attachment 2 - Quote Sheet.Amend 001.xlsx | XLSX spreadsheet | |
| Combo S-S.EDG Rental.FINAL.pdf | ||
| Attachment 3 - DD Form 254.pdf | ||
| Attachment 2 - Quote Sheet.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Statement of Work
Berth 20 & Slab 36 Emergency Diesel Generator Rental
1.0 Scope
• 1.1 Objective: Norfolk Naval Shipyard (NNSY) requires the rental of three (3) trailer-mounted Emergency Diesel Generators (EDGs) to provide standby emergency electrical power during unplanned power outages and the rental of an Automatic Transfer Switch (ATS) to automatically supply power for each of the generators.
• 1.2 Background: The EDGs will serve as standby equipment to maintain operations for project trailers and a living barge at Berth 20 and Slab 36 during utility outages. The ATS will allow the automatic transfer of power from the generator to the living barge.
2.0 Applicable Documents
The Contractor shall comply with the latest revisions of the following documents:
• 2.1 Federal Regulations:
o 29 CFR 1915.89 – Control of Hazardous Energy (Lockout/Tags-Plus) o Occupational Safety and Health Administration (OSHA) standards
• 2.2 Department of the Navy & Shipyard-Specific Requirements:
o Norfolk Naval Shipyard OSHE Program Manual, NAVSHIPYDNORINST P5090.2 o NAVSEA Occupational Safety, Health, and Environment Corporate Manual (OSHECM), Chapter 250
(Hazardous Energy Control) o NAVSEA 04 Ser 04/281 – Implementation Plan for Portable Electronic Devices (PEDs) o NAVSEAINST 2200.1A – Portable Electronic Devices Policy o SECPROMAN Vol 1 5510.36 Rev E – Security Program Manual
3.0 Requirements
• 3.1 Equipment Specifications:
• 3.1.1 500 kW Standby Power Diesel Generator (Quantity: 1)
• Output & Capacity: 480 Volts, 3-Phase, 3-wire grounded, with a minimum Standby Rating of 500 kW.
• Auxiliary Systems: Equipped with an auxiliary block heater and battery charging circuit.
Auxiliary power connections must utilize standard commercial configurations (e.g., standard NEMA plugs).
• Safety Devices: Equipped with an output circuit breaker with overcurrent protection.
• Physical Limitations: Footprint shall not exceed 20' L x 8' W. Total unit weight shall not exceed
45,000 lbs.
• Fuel System: Onboard or external fuel tank capable of a minimum twenty-four (24) hour run time at full continuous load prior to refueling. External fuel tank, if utilized, shall not exceed 1,240 gallons in volume, 10' L x 8' W in footprint, and 15,000 lbs fully fueled weight (or dual tanks not exceeding 5'-5 3/8" x 7'-8 5/8" and 6,200 lbs each). Fuel tank lifting points must have current weight capacity certifications. The fuel system must allow safe refueling while the generator is operating.
• Enclosure: Self-contained, outdoor, rain-tight, sound-attenuated enclosure with a self-contained cooling system.
• Connection Interface: Equipped with mechanical terminal lugs or standard connections compatible with standard 500MCM power cables (supporting up to 4 conductors per phase).
• Certification: The unit must be clean, well-maintained, and have undergone a load-bank test within two (2) weeks prior to delivery. Certified test data must be provided upon delivery.
Winding insulation resistance shall meet commercial standards (minimum 5MΩ above ground with neutral disconnected).
• Operating Instructions: Legible, weatherproof operating instructions (start, stop, parallel synchronization, and breaker operation) must be permanently posted near the control panel.
• 3.1.2 350 kW Standby Power Diesel Generator (Quantity: 2)
• Output & Capacity: 480 Volts, 3-Phase, 3-wire grounded, with a minimum Standby Rating of
350 kW.
• Auxiliary Systems: Equipped with an auxiliary block heater and battery charging circuit.
Auxiliary power connections must utilize standard commercial configurations (e.g., standard NEMA plugs).
• Safety Devices: Equipped with an output circuit breaker with overcurrent protection.
• Physical Limitations: Footprint shall not exceed 20' L x 8' W. Total unit weight shall not exceed
45,000 lbs.
• Fuel System, Enclosure, Connection Interface, Certification, and Instructions: Must meet the identical performance, size, safety, and certification requirements outlined in Section 3.1.1.
• 3.1.3 Automatic Transfer Switch (Quantity: 3)
• 800 Amps, 480 Volts, 3-Phase, 3-Pole
• Service Entrance-Rated
• Enclosure: NEMA 3 and above
• 3.2 Contractor Responsibilities:
• 3.2.1 Maintenance & Repair: Provide all routine, preventative, and emergency maintenance (including parts and wear-and-tear replacement) at no additional charge during the rental term. All associated travel and labor costs shall be borne by the Contractor.
• 3.2.2 Service Response: Provide 24/7/365 repair coverage. The Contractor shall dispatch a qualified service technician to arrive on-site within four (4) hours of notification by NNSY. If repairs cannot be completed on-site, the Contractor must replace the unit within eight (8) hours of initial notification, at no additional cost.
• 3.2.3 Emergency Contacts: Legible, weatherproof emergency contact information for 24/7 service must be permanently affixed to each generator unit.
• 3.2.4 Badging & Security: Ensure all service technicians and drivers are U.S. citizens and comply with NNSY security requirements, including obtaining DBIDS cards, NAVSEA green badges, and adhering to Controlled Industrial Area (CIA) access policies.
• 3.2.5 Protective Coverings: Provide adequate weather and saltwater-corrosion protection coverings for all rental equipment.
• 3.2.6 Documentation: Provide comprehensive technical manuals, fuel consumption curves, allowable operating hours at various ratings, and technical parameters upon delivery.
• 3.2.7 On-Site Support: Provide a technical representative to assist NNSY personnel during initial cable installation, perform voltage and phase rotation checks, and participate in initial Hazardous Energy Control (HEC) lock coordination.