This is an Amendment to Solicitation (Amendment 0001) issued by NAVPAC Mid-Atlantic for contract N40085-26-R-9061, effective July 20, 2026, for replacement dining area lighting at WC100. The amendment addresses 12 clarifications to the original solicitation through a Questions and Answers format.
Key clarifications include: fire alarm interface is not required for ceiling occupancy/vacancy sensor dimming; luminaire tie wires for humid spaces apply to the project; lighting control system commissioning by a factory-trained technician and end-user training are not required; no photosensors are included and photosensor testing is not required; maintenance and operations manuals for the lighting control system are not required; metal-clad cable is acceptable only for replacement of existing metal-clad cable; electrical work must be performed by a licensed electrical company supervised by the contractor's qualified individual, with no specific Master/Journeyman Electrician designation required for North Carolina; and on/off dimmers must be provided at all S3 switch locations as shown on the drawings. Additionally, Section 01 35 26 has been added and incorporated into the project specifications. The time and date for receipt of proposals remains unchanged, and the amendment must be acknowledged when proposals are submitted.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend0004 26R9061.pdf | ||
| Amend0003 26R9061.pdf | ||
| Amend0002 26R9061.pdf | ||
| 01 35 26.pdf | ||
| N4008523B0031 Dwgs.pdf | ||
| 23-0031 SOW.pdf | ||
| N4008523B0031 Specs.pdf | ||
| Revised Contractor_Environmental_Guide.pdf | ||
| submittal register.pdf | ||
| RFP 23-0031.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N40085-26-R-9061 Amendment 0001
CONTINUATION SHEET
1. QUESTION: Drawing E-3, ceiling occupancy/vacancy sensor dimming diagram shows an auxiliary interface device to a fire alarm module. The diagram says "where required for fire alarm interface". Is fire alarm interface required? If so, please provide more details and specifications for this work.
ANSWER: Fire alarm interface is not required.
2. QUESTION: Specification section 26 51 00 Interior Lighting - 2.5.3 references luminaire tie wires as a standard wire and a wire for humid spaces. Which one applies to this project?
ANSWER: Ties for humid spaces.
3. QUESTION: Specification section 26 51 00 Interior Lighting - 3.2.1.1 Lighting Control Verification Tests states to verify operation/test lights and sensors per the approved sequence of operations. Please provide direction for the sequence of operations as there does not appear to be a sequence specified.
ANSWER: Verify proper operation of complete lighting system. No sequence of operation test is required.
4. QUESTION: Specification section 26 51 00 Interior Lighting - 3.3 Closeout Activities calls for commissioning of the lighting system by a factory trained field service technician. There is not a lighting control system being installed. Can this requirement be removed?
ANSWER: Commission the lighting system delivered under the contract. A factory trained field service technician is not required.
5. QUESTION: Specification section 26 51 00 Interior Lighting - 3.3 Closeout Activities calls for maintenance staff and end user training for a lighting control system. There is not a lighting control system being installed. Can these requirements be removed?
ANSWER: End user training under this section is not required.
6. QUESTION: Specification section 26 51 00 Interior Lighting - has section 3.1.4.3 Photosensors along with a photosensors tests sequence further down in the specifications. We cannot locate any photosensors on the prints. Please provide direction.
ANSWER: No photosensors are included. No photosensor tests are required.
7. QUESTION: Specification section 26 51 00 Interior Lighting - 1.7.1 Lighting System under operation and maintenance manuals. There is not a lighting control system being installed. Can this requirement be removed?
ANSWER: Maintenance and operations manuals under this section are not required.
8. QUESTION: Specification section 26 20 00 Interior Distribution - 2.6.6 Metal-Clad cable is listed as a product. Is MC cable acceptable for use on this project?
ANSWER: Metal-clad cable is only acceptable where being employed for the replacement of existing metal-clad cable.
9. QUESTION: Specifications section 26 20 00 Interior Distribution - 1.5.1 Electrician Qualifications under 1.5 Quality Assurance states "Electrical work must be performed by qualified persons with verifiable credentials who are familiar with applicable code requirements. Verifiable credentials consist of State, National and] Local Certifications or Licenses that a Master or Journeyman Electrician may hold, depending on work being performed".
• The state of North Carolina does not qualify electrical license holders as Master or Journeyman. Please provide clarification.
• Is it the intent to have a licensed electrical company perform the work or each individual laborer be a license holder?
• Is the intent to have the onsite electrician provide quality assurance on themselves or are we to provide a stand-alone QC for this work?
ANSWER: The intent is for a licensed electrical company to perform the work. Work should be supervised by the contractor’s qualified individual.
10. QUESTION: Drawing E-2 work notes #3 states to provide new stand alone switching and motion sensor control. The switches are identified as S3 on the new work plan. The legend on drawing E-1 shows that an S3 is a Low voltage wall switch and to see the occ sensor diagram. The Occ Sensor diagram on E-3 shows a picture of what appears to be an on/off switch with dimming buttons.
• No specifications are provided to identify the switch requirements
• Some smaller rooms have the S3 symbols but do not have occupancy detection in place (No room numbers identified on prints). Is the same on/off dimmer required at each S3 location?
ANSWER: Yes, provide the same on/off dimmer at each location.
11. See attached SECTION 01 35 26 added and incorporated into the project.
12. All other terms and conditions remain unchanged.