N4008523B0031 Dwgs.pdf
PDF 1 MB Posted
- Attached to
- Replacement Dining Area Lighting at WC100
- Solicitation number
- N4008526R9061
About this file
This is a set of electrical design drawings and specifications for replacement dining area lighting at MCB Camp Lejeune, North Carolina, specifically for work area WC100.
The project requires removal of existing recessed downlights, troffers, and occupancy sensors, with installation of new recessed downlights and direct/indirect LED luminaires to replace the existing fixtures. The contractor must provide new standalone switching and motion sensor control for troffers and downlights, locating new switches in existing switch locations while maintaining matching switching functionality. Additional occupancy sensor locations must be provided where required and recommended by the manufacturer. New acoustical ceiling tiles are required to complete the work, matching existing materials. The lighting circuit work involves providing conduit with 10 recessed downlight luminaires connected to three-way switches with a homerun to a new 20-amp breaker in the existing panelboard in the electrical room. All work must comply with North Carolina electrical codes, OSHA requirements, and NEC standards. The contractor is responsible for coordinating with other trades, verifying equipment ratings, protecting existing power and communications systems, and obtaining site familiarization prior to proposal submission. Work includes all necessary incidental materials such as conductors, conduit, backboxes, mounting brackets, and related components required for fully functional and code-compliant installation. The drawings include electrical legends, general notes, device mounting height details, luminaire schedules, control diagrams, and new work plans showing fixture and switch locations throughout the dining facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend0004 26R9061.pdf | ||
| Amend0003 26R9061.pdf | ||
| Amend0002 26R9061.pdf | ||
| 01 35 26.pdf | ||
| Amend0001 26R9061.pdf | ||
| 23-0031 SOW.pdf | ||
| Revised Contractor_Environmental_Guide.pdf | ||
| submittal register.pdf | ||
| RFP 23-0031.pdf | ||
| N4008523B0031 Specs.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T - 1
CONTRACT # DRAWING # SHEET # TITLE
23-0031 T-1
WAKE
DURHAM
PERSON
GRANVILLE
FRANKLIN
WARREN
COLUMBUS
BLADEN
HARNETT
WAYNE
JOHNSTON
WILSON
NASH
EDGECOMBE
SAMPSON
DUPLIN
JONES
GREENE
LENOIR
PITT
HERTFORD
GATES
CARTERET
CRAVEN
ONSLOW
PENDER
NEW
HANOVER
BRUNSWICK
PAMLICO
BEAUFORT
HYDE
DARE
C A
M D
E N
P A
S Q
U O
TAN K
TYRRELL
P E
R Q
U I M
A N
S
C H O W
A N
MARTIN WASHINGTON
NORTHAMPTON
CU
R
I U
K
T R
C
BERTIE
VANCE
CUMBERLAND
HALIFAX
ATLANTIC OCEAN
N S
T
STONE ST
O S
T
A ST
F ST
L
ST
H ST
G ST
C ST
G U
M
ST
D ST
M
IC
H
AEL R
D
I S T
BIRCH ST
MCHUGH BLVD
GIB
B R
D
JULIAN C SMITH
M S
T
W A
L L
A C
E C
R E
E K
R D
CROSS ST
P O
S T
L N
S
ET
H W
ILLIAM
S BLVD
LOU
IS
R D
G O
N Z
AL
E
Z
BL
VD
ASH
ST
D
UN
CAN S
T
E D
E N
ST
CUTLER ST
O
LD
SN
E
AD
S FERRY R
D
B
EV
IN
ST
W
EST R
D
C
ED
AR
ST
RAIL
RO
AD
R
D
F17 R
ANGE RD
CAR W
ASH R
D
CENTE
R R
D
P E
N D
E R
S T
BARKER ST
M O
L L
Y P
ITC
H
E R
EN
D
U R
AN
CE DR
L U
C Y
B R
E W
E R
AV
E
ET A3
RANGE R
D
HM S
MITH BLV
D
PA
R
AC
H
U
TE
TO
W
ER
R
D
COOPER ST
M A
IN
T
E N
A N
C E
R D
O N
S
LO
W D
R
HAM
M
OND R
D
SAN
GIN
R D
VIRGINIA DARE DR
TIM
M
ER
M
AN AVE
C O
N N
E C
TO
R
R D
O L
I V E
ST
F IR
ST
ISMT RD
EAST R
D
D O
G W
O O
D
ST
W
ILSON BLVD RAMP
ELM
ST
D A
L Y
R D
FRANKLI
N S
T
C
ON
E W
AY
TIMMERMAN PLZ
BLACKWOOD RD
BST LOOP R
D
H
IC
KO
R
Y ST
F6 RANGE RD
IN
C
ID
E
N T
A L
L O
O P
R D
M U
LBE
R
RY ST
SURGEONS ROW
W
IL
S O
N B
L V
D R
A M
P
SERVICE RD
O S T
B
ST
J O
N E
S S
T
G R
E E
N W
A Y
T
RA
IL
RT34
GREENWAY TRAIL
G R
E E
N W
A Y
TR
AIL
G R
E E
N W
A Y
T R
A
IL
G R
E E
N W
A Y
T R
AIL
G
RE
ENW
AY
TRAIL
ALZ11
FC67
FC69
PT3
S241
S44
WC144
FC39
S635
S180
FC199
S580
S1229
H85
S943
S1761
S1060
FC292
SWC1J
S1450K
SFC62D
SHP576A
S1861
S1847C
S1255
UN910
S1684
S1498
S747
S212
SF C66M
SWC113
SWC143
SF C64C
S1312A
SF C66N
CONT 160
F11
S956
S562
S775
S120
S563
S625
S208 S932
S124
SHP562
T P460
SF C299
H1
FC286
W C1
W C161
W C310
S FC66A
W C165
W C145
W C508
W C300
FC280
HP250
FC285
HP237
W C200
FC115
W C500
FC332
FC300
FC66
24E
W C506
W C504
FC100
H14
HP104
FC65
W C178
W C177
HP131
W C100
D29
FC356
HP413
FC230
HP259
FC51
H17
FC255
FC64
FC62
FC63
FC375
H13
HP500
FC504
FC507
W C160
W C159
W C124
W C125
FC303
HP55
FC45
HP513
HP504
HP512
HP465
H23
H21
FC270
HP455
W C148
H24
HP117
HP118
HP119
HP301
HP53
H17N
FC304
HP57
HP51
HP308
HP306
HP99
FC309
HP307
HP285
FC310
HP550
HP505
HP405
HP225
HP435
W C501
HP275
FC200
HP508
HP507
HP510
HP255
HP560
HP445
HP485
HP514
HP509
HP425
HP415
HP495
HP295
HP475
HP503
HP245
HP195
HP165
FC292
HP235
HP265
H20
FC263
HP215
W C140
HP100
HP115
HP155
FC291
HP135
HP175
HP125
HP145
HP105
W C146
HP185
123A
223A
423A
F C57
1880A
F C130
F C127
F C301
F C128
F C129
F C281 F C131
HP112
H22
F C298
F C143
S806
S870
HP5
F C173
S872
S965
S25A
F C134
F C253
CONT1
F C56
722A
T P448
ES101
F C190
1775E
1775F
1775A
1775B
1450A
1450B
F C355
1775C
1775D
S1053
1829A
1829B
1450C
1775H
1829C
1775G
S1752
S1753
F C307
T P457
F C174
F C250
F C50
F C206
F C207
S1124
F C211
3B
T P440
43C
976A
WC99
CONT5
H33
F C67
F C112
F C58
HP1016
S90
PT4
F C138
F C136
CONT
SF C221
F C137
16A
WC301
F C298A
58J
58K58L
F C140
ST P467
F C141
T P468
F C195
F C139
S894
HP89
HP121
58F
58M
PT 3C
58E
S871
PT5
H62
58H
PT6
58G
H84
H67
H66
H65
T P454
CT R365
H50
H63
H57
H52
H55
H54
H51
H59
H53
H58
H60
H56
H23A
T P456
SF C223
F C510
H61
1250F
518A
H49
236A
S204
1250M
S17C
F C101
F C201
SF C309A
1250J
F C102
1250L
S770
S214A
1250E
1250B
1250A
1250K
1250P
1250D
1250C
1250H
1250R
1250N
S746
1250AC
1250G
1250Q
S677
SHP505B
HP52
H21A
S730A
T P453
S1220B
S893
HP305
1250AJ
1250AL 1250AF
1250AB
1250AA
1250AE1250AK
751B
HP502
1250AH
1250AD
1250AN
425C
1250AG
HP56
1250AM
F C292F
HP515
HP511
F C240
S1967
SF C355A
SHP99A
WC503
S1231F
S1026A
PVWC1A
SPT 16
WC320
S125B
S125C
37A
HP88
S 869
H32
FC251
W C135
W C130
HP 1017
W C115
W C110
FC120
S 1854A
W C120
W C105
TP464
W C320
FC40
HP576
TP466
HP232
S 1743
FC294
HP416
HP206
FC241
FC362
FC293
FC354
FC230A
FC120A
FC375P
FC132
FC375N
HP328
S FC143B
S FC143A
RNGD30
S FC255B
S FC211C
S FC211D
S FC263B
S FC255C
S 1854B
FC302
S 1854C
WC204
CT R103
1450E
1742A
S1231L
1742B
1742C
SWC305
CT R363
S892
S718
WC200A
S1765B
F C250A F C250B
S1765A
F C250C
S1806
SWC165A
SWC145B
HP210
F C382
SHP117A
SHP88A
SWC165B
S1692
SWC145C
S1042A
SF C66B
SF C66H
S67
ALZ-5
ALZ-4
ALZ-6
ALZ-2
ALZ-33
60044569
BASE MAPLOCATION MAP
CAMP LEJEUNE
WC100
DRAWING INDEX
23-0031
23-0031
23-0031
60044570
60044571
60044572
E-1
E-2
E-3
GENERAL NOTESELECTRICAL LEGEND
LIGHTING PANEL, LIGHT POLE
LIGHTING
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTOR
MAIN DISTRIBUTION PANEL
MANUFACTURER
MANHOLE
MAIN LUGS ONLY
MOUNTED
MOUNTING
MANUAL TRANSFER SWITCH
MEDIUM VOLTAGE
NEUTRAL
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE
PUBLIC ADDRESS
PULL BOX, PUSH-BUTTON
POWER FACTOR
PHASE
PROGRAMMABLE LOGIC CONTROLLER
PANEL
POWER PANEL, POWER POLE
PORTABLE POWER EQUIPMENT CABLE
POTENTIAL TRANSFORMER
POWER
RECEPTACLE
REQUIRED
RIGID GALVANIZED STEEL CONDUIT
ROOM
REMOTE TELEMETRY UNIT
DC MOTOR DRIVE
SHEET
SURGE PROTECTION DEVICE
SPECIFICATION
SELECTOR SWITCH
STAINLESS STEEL
SWITCH
SWITCHBOARD
SWITCH GEAR
TELEPHONE
TWISTED PAIR SHIELDED
TRANSIENT VOLTAGE SURGE SUPPRESSER
TYPICAL
UNDERGROUND
UNIT HEATER
UNLESS OTHERWISE NOTED
UTILITY
VOLTS
VARIABLE FREQUENCY DRIVE
WIRE, WATT
WATT-HOUR
WEATHERPROOF
WEATHERPROOF TELEPHONE ENCLOSURE
TRANSFORMER
EXISTING RELOCATED
A, AMP
AFF
AFG
AHU
AIC
ATS
AWG
BOF
BRKR
C, CND
CAB
CAT
CL
CB
CCTV
CKT
CLG
CP
CR
CS
CV
CT
CU
EF
EMER
EMT
ENCL
EQUIP
EWC
EWH
EPRF
FA
FAAP
FACP
FBO
FLA
FLUOR
FLR
FWE
GEN
G, GND
GFCI
HH
HID
HOA
HP
HPF
HPS
HTR
HV
Hz
IMC
INCAND
JB
K
KCMIL
KVA
KW
KWH
AMPERE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAUGE
BOTTOM OF FIXTURE
BREAKER
CONDUIT
CABINET
CATALOG
CHLORINE
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CEILING
CONTROL PANEL
CONTROL RELAY, CORROSION RESISTANT
CONTROL SWITCH
CONTROL VALVE
CURRENT TRANSFORMER
COPPER
EXHAUST FAN
EMERGENCY
ELECTRICAL METALLIC TUBING
ENCLOSURE
EQUIPMENT
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXPLOSION PROOF
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FURNISHED BY OTHERS
FULL LOAD AMPS
FLUORESCENT
FLOOR
FURNISHED WITH EQUIPMENT
GENERATOR
GROUND
GROUND FAULT CURRENT INTERRUPTER
HANDHOLE
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTO
HORSE POWER
HIGH POWER FACTOR
HIGH PRESSURE SODIUM
HEATER
HIGH VOLTAGE
HERTZ
INTERMEDIATE METALLIC CONDUIT
INCANDESCENT
JUNCTION BOX
THOUSAND
THOUSAND CIRCULAR MILLS
KILOVOLT AMPERE
KILOWATTS
KILOWATT-HOURS
LP
LTG
MCB
MCC
MCP
MDP
MFR
MH
MLO
MTD
MTG
MTS
MV
N / NEUT
NA
NC
NEC
NIC
NL
NO
NTS
P
PA
PB
PF
PH
PLC
PNL
P
PPE
PT
PWR
RECPT, RCP
REQ'D
RGS
RM
RTU
DCM
SH
SPD
SPEC
SS
SST
SW
SWBD
SWGR
TEL
TPS
TVSS
TYP
UGND
UH
UON
UTIL
V
VFD
W
WH
WP
WTE
XFMR
X/R
1. ALL ELECTRICAL WORK MUST BE IN FULL COMPLIANCE WITH NFPA 70 THE NORTH CAROLINA
STATE BUILDING CODE, ALL LOCAL CODES AND ORDINANCES AND IN ACCORDANCE WITH THE
REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION.
2. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR MUST BE LISTED AND LABELED BY A
NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING
JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL MATERIAL, EQUIPMENT AND
DEVICES MUST BE NEW CURRENT PRODUCTS OF MANUFACTURERS REGULARLY ENGAGED IN
THE PRODUCTION OF SUCH PRODUCTS. EQUIPMENT MUST BE SUITABLE FOR ITS
APPLICATION (E.G. WHEN INSTALLED OUTDOORS, IT MUST BE WEATHERPROOF, ETC.)
3. THE CONTRACTOR MUST REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR WORK
REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL EQUIPMENT, AND
LAYOUT HIS WORK IN A COMPATIBLE AND FUNCTIONAL MANNER.
4. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED BY THE
CONTRACTOR MUST BE COMPLETE AND FULLY-FUNCTIONING AFTER INSTALLATION.
INCIDENTAL COMPONENTS MAY NOT BE SHOWN, AND ALL WORK WHICH MAY BE REASONABLY
IMPLIED AS BEING INCIDENTAL TO THIS WORK, BUT REQUIRED FOR THE PROPER OPERATION
OF THE EQUIPMENT OR SYSTEM MUST BE PROVIDED BY THE CONTRACTOR AND INCLUDED IN
THE BID. ADDITIONAL CIRCUITS MUST BE INSTALLED WHEREVER NEEDED TO CONFORM TO
THE SPECIFIC REQUIREMENTS OF EQUIPMENT.
5. TEMPORARY POWER CONNECTIONS AS REQUIRED MUST BE PROVIDED BY THE CONTRACTOR
AND INCLUDED IN THE BID. ALL TEMPORARY EQUIPMENT WIRING MUST BE IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE. THE CONTRACTOR MUST PROVIDE DETAILS,
METHODS, MATERIALS, ETC. FOR REVIEW PRIOR TO MAKING TEMPORARY CONNECTIONS.
FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS INCLUDING CONTROL EQUIPMENT,
MOTOR STARTERS, BRANCH AND FEEDER CIRCUIT BREAKERS, PANELBOARDS,
TRANSFORMERS, ETC. FOR TEMPORARY POWER. COORDINATE WITH THE UTILITY PROVIDER
AS REQUIRED.
6. THE WORK MUST INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING AT THE
COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR ADJUSTMENTS
NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM AND EQUIPMENT.
7. ALL ELECTRICAL EQUIPMENT MUST, AT ALL TIMES DURING CONSTRUCTION, BE ADEQUATELY
PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER AND/OR THE ELEMENTS.
ELECTRICAL EQUIPMENT MUST NOT BE STORED OUT OF DOORS, BUT MUST BE STORED IN
DRY PERMANENT SHELTERS. IF AN APPARATUS HAS BEEN DAMAGED, OR HAS BEEN SUBJECT
TO POSSIBLE INJURY BY WATER OR THE ELEMENTS, SUCH DAMAGE MUST BE REPLACED AT
NO ADDITIONAL COST.
8. DO NOT SCALE ELECTRICAL DRAWINGS. CONTRACTOR MUST FIELD VERIFY ALL DIMENSIONS.
9. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR OTHER
INSTALLATION DETAILS. UNLESS NOTED OTHERWISE, THE EXACT ROUTING OF FEEDER AND
BRANCH CIRCUIT RACEWAYS AND CABLES IS THE RESPONSIBILITY OF THE CONTRACTOR.
RISER AND GENERAL CIRCUIT ARRANGEMENTS ARE SHOWN
SCHEMATICALLY/DIAGRAMMATICALLY ONLY. THE CONTRACTOR MUST ROUTE CONDUITS AS
REQUIRED BY THE CONDITIONS OF THE INSTALLATION.
10. DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE. ADJUST EXACT
LOCATIONS AS REQUIRED TO SERVE THE INTENDED PURPOSE AND TO AVOID CONFLICTS AND
INTERFERENCES WITH OTHER TRADES. IF NOT SHOWN ON THE ARCHITECTURAL DRAWINGS
OR DIMENSIONED ON THE ELECTRICAL DRAWINGS, VERIFY EXACT LOCATION WITH THE
GOVERNMENT PRIOR TO ROUGH-IN.
11. CONDUIT TERMINATING IN PRESSED STEEL BOXES MUST HAVE DOUBLE LOCKNUTS AND
INSULATED BUSHINGS. CONDUITS TERMINATING IN GASKETED ENCLOSURES MUST BE
TERMINATED WITH GROUNDING TYPE CONDUIT HUBS.
12. BRANCH CIRCUIT HOMERUNS SHOWN ON DRAWINGS INDICATE PHASE CONDUCTORS,
NEUTRAL, EQUIPMENT GROUND CONDUCTORS AS REQUIRED. ADDITIONAL CONDUCTORS
REQUIRED FOR CONTROL MUST BE INCLUDED EVEN IF NOT EXPLICITLY SHOWN.
13. SEAL ALL CONDUIT OPENINGS THROUGH EXTERIOR BUILDING WALLS AND ROOF WATERTIGHT.
14. IN WET LOCATIONS AND EXTERIOR, ALL WIRING DEVICES MUST BE WEATHER-RESISTANT
LISTED WITH WEATHERPROOF WHILE IN USE COVER.
15. RACEWAYS PENETRATING FLOORS, CEILINGS OR WALLS MUST BE PROPERLY SEALED
SMOKETIGHT.
16. ALL RACEWAYS MUST BE CONCEALED WHERE POSSIBLE.
17. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY SURFACES OR
STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS AS MUCH AS POSSIBLE. NO
DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS MUST BE RUN STRAIGHT WITH QUALITY
WORKMANSHIP-LIKE MANNER. RUN PARALLEL OR BANKED RACEWAYS TOGETHER ON
COMMON SUPPORTS WHERE PRACTICAL. MAKE BENDS IN PARALLEL OR BANKED RUNS FROM
SAME CENTERLINE TO MAKE BENDS PARALLEL.
18. PATCHING OF WATERPROOFED SURFACES MUST RENDER THE AREA OF THE PATCHING
COMPLETELY WATERPROOF.
19. ALL MOTORS AND OTHER VIBRATING EQUIPMENT MUST BE CONNECTED TO THE CONDUIT
SYSTEM BY MEANS OF A SHORT SECTION (18 INCH MINIMUM) OF FLEXIBLE CONDUIT UNLESS
OTHERWISE INDICATED. AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
INSIDE THE FLEXIBLE CONDUIT AND TERMINATE AT THE LOAD END WITH AN APPROVED
GROUNDING CLAMP OR LUG.
20. SURFACE MOUNTED PANELBOARDS, JUNCTION, OUTLET AND PULL BOXES, RACEWAYS, ETC., INSTALLED ON EXTERIOR SURFACES OR INSIDE ON EXTERIOR WALLS MUST BE SUPPORTED
BY SPACERS TO PROVIDE A MINIMUM 1/4" MINIMUM CLEARANCE BETWEEN THE WALL AND
EQUIPMENT.
21. TYPED PANELBOARD DIRECTORIES INSTALLED IN THE PANELBOARD DOOR POCKET MUST
REFLECT FINAL CONDITIONS AND ACTUAL ROOM NAMES AND NUMBERS IN ADDITION TO THE
GENERAL DESCRIPTION SHOWN ON THE PANEL SCHEDULES ON THE DRAWINGS.
22. THE CONTRACTOR MUST VERIFY, PRIOR TO INSTALLATION OF CONDUCTORS OR CONDUIT
FEEDING ANY EQUIPMENT, THE ELECTRICAL EQUIPMENT IS RATED FOR USE WITH 75 DEGREE
C. WIRING. IF ANY EQUIPMENT IS RATED FOR USE WITH LESS THAN 75 DEGREE C.
CONDUCTORS, THE CONTRACTOR MUST NOTIFY THE GOVERNMENT IMMEDIATELY FOR
EVALUATION/CORRECTION.
23. DO NOT PULL CONDUCTORS UNTIL THE CONDUIT SYSTEM IS COMPLETE IN EVERY DETAIL. IN
THE CASE OF CONCEALED WORK, "COMPLETE" MEANS UNTIL ALL ROUGH PLASTERING OR
MASONRY HAS BEEN COMPLETED.
24. WHERE SIZE IS NOT SHOWN ON THE DRAWINGS, BRANCH CIRCUITS MUST CONSIST OF #12 OR
#10 AWG MINIMUM PHASE, NEUTRAL AND EQUIPMENT GROUND CONDUCTORS IN 3/4” MINIMUM
RACEWAY.
25. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS WITH A TOTAL
INSTALLED LENGTH GREATER THAN 75 FEET AND/OR BRANCH CIRCUIT HOMERUNS LONGER
THAN 50 FEET, I.E.; #12 AWG INCREASED TO #10 AWG FOR RECEPTACLE BRANCH CIRCUITS
OVER 75 FEET TOTAL LENGTH (INCLUDING THE HOMERUN SEGMENT) AND HOMERUNS OVER
50 FEET. IF 277 VOLT CIRCUITS ARE SHOWN, USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277
VOLT BRANCH CIRCUITS WITH TOTAL INSTALLED LENGTH GREATER THAN 200 FEET AND/OR
BRANCH CIRCUIT HOMERUNS LONGER THAN 125 FEET, I.E.; #12 AWG INCREASED TO #10 AWG
FOR RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH (INCLUDING THE
HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET.
26. KEEP CONDUCTOR SPLICES TO A MINIMUM. INSTALL SPLICES AND TAPES THAT POSSESS
EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION RATINGS THAN
CONDUCTORS BEING SPLICED. USE SPLICE AND TAP CONNECTORS COMPATIBLE WITH
CONDUCTOR MATERIAL. INSTALL CONDUCTORS AT EACH OUTLET WITH AT LEAST 6 INCHES
OF SLACK. CONNECT OUTLETS AND COMPONENTS TO WIRING AND TO GROUND AS INDICATED
AND INSTRUCTED BY THE MANUFACTURER.
27. DO NOT SPLICE BRANCH CIRCUIT HOMERUNS WITHOUT THE PERMISSION OF THE
GOVERNMENT. HOMERUNS MUST BE CONTINUOUS FROM THE LAST OUTLET BOX TO THE
SERVING PANELBOARD.
28. DO NOT COMBINE BRANCH CIRCUIT HOMERUNS UNLESS SPECIFICALLY INDICATED ON THE
DRAWINGS.
29. INSTALL WIRING DEVICES AT HEIGHTS AS SHOWN ON THE DRAWINGS.
30. PROTECT ALL EXISTING POWER, COMMUNICATIONS, DATA, LIFE SAFETY SYSTEMS, FIRE
ALARM AND PUBLIC ADDRESS SYSTEMS AND MAINTAIN THEM IN OPERATION THROUGHOUT
THE PROGRESS OF THE WORK. NOTIFY THE GOVERNMENT IF SHUTDOWNS ARE REQUIRED
PRIOR TO ANY OUTAGE OF SERVICE. WHERE THE DURATION OF A PROPOSED OUTAGE
CANNOT BE TOLERATED BY THE GOVERNMENT, PROVIDE TEMPORARY CONNECTIONS AS
REQUIRED TO MAINTAIN SERVICE.
31. PROVIDE GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL IN
ACCORDANCE WITH THE NEC INCLUDING EXTERIOR RECEPTACLES AND RECEPTACLES IN
AREAS SUBJECT TO POSSIBLE WET CONDITIONS.
32. COORDINATE LOCATIONS OF MECHANICAL EQUIPMENT WITH THE RESPECTIVE CONTRACTOR,
VENDORS AND THE GOVERNMENT BEFORE ROUGH-IN. ADJUST LIGHTING FIXTURES,
RECEPTACLES AND ELECTRICAL EQUIPMENT TO ACCOMMODATE THIS EQUIPMENT. ADVISE
THE GOVERNMENT OF CONFLICTS BEFORE ROUGH-IN.
33. BEFORE COMMENCING WORK OR ORDERING MATERIALS, THE CONTRACTOR MUST
COORDINATE WITH OTHER TRADES AND VERIFY THE NAMEPLATE RATINGS OF ALL EQUIPMENT
(MOTORS, HEATERS, COMPRESSORS, ETC.) AND ADJUST THE RATINGS OF THE ELECTRICAL
EQUIPMENT (SWITCHES, FUSES, CIRCUIT BREAKERS, FEEDERS, ETC.) AS APPROPRIATE TO
SERVE THIS EQUIPMENT.
34. ENERGIZE EQUIPMENT ONLY AFTER OBTAINING PERMISSION FROM THE CONTRACTOR
PROVIDING THE EQUIPMENT.
35. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR MUST MAKE FINAL
CONNECTIONS TO ALL UTILIZATION EQUIPMENT SHOWN ON THE DRAWINGS. VERIFY THE
TYPE OF FINAL CONNECTION AND PROVIDE APPROPRIATE WIRING METHOD. THE
CONTRACTOR MUST COORDINATE WITH THE MECHANICAL TRADE, PRIOR TO ORDERING OR
INSTALLATION OF ANY EQUIPMENT, TO VERIFY MECHANICAL EQUIPMENT REQUIREMENTS ARE
PROVIDED IN THE ELECTRICAL DESIGN. THE CONTRACTOR WILL NOT BE COMPENSATED FOR
COSTS ASSOCIATED WITH CHANGING THE ELECTRICAL SYSTEMS TO MATCH UTILIZATION
EQUIPMENT, EVEN IF THE ELECTRICAL WORK IS INSTALLED PER THE ELECTRICAL DRAWINGS.
36. THE CONTRACTOR MUST COORDINATE ALL EQUIPMENT TERMINATIONS, PLUGS AND
CORDSETS WITH VENDOR EQUIPMENT AND VERIFY ALL DEVICE LOCATIONS FOR SPECIALITY
EQUIPMENT WITH CASEWORK PRIOR TO ROUGH-IN.
37. INSTALLATION INFORMATION PACKED WITH DEVICES AND EQUIPMENT MUST BE RETAINED
FOR INCLUSION IN THE OPERATIONS AND MAINTENANCE MANUALS.
38. THE CONTRACTOR MUST VISIT THE SITE AND BECOME FAMILIAR WITH THE EXISTING
ELECTRICAL SYSTEMS AND THE EXISTING BUILDING. THE SUBMISSION OF THE PROPOSAL BY
THE CONTRACTOR SHALL BE CONSIDERED EVIDENCE THAT HE OR HIS REPRESENTATIVE HAS
VISITED THE SITE AND BUILDINGS AND NOTED THE LOCATION AND CONDITIONS UNDER WHICH
THE WORK WILL BE PERFORMED AND THAT HE TAKES FULL RESPONSIBILITY OF ALL FACTORS
GOVERNING HIS WORK. NO EXTRAS WILL BE CONSIDERED BECAUSE OF ADDITIONAL WORK
NECESSITATED BY EXISTING JOB CONDITIONS THAT ARE NOT INDICATED ON THE DRAWINGS.
39. ELECTRICAL DEVICES OR COMPONENTS INDICATED MUST BE PROVIDED WITH CONDUCTORS,
CONDUIT, BACKBOXES, MOUNTING BRACKETS, AND ALL RELATED INCIDENTAL MATERIALS
REQUIRED FOR FULLY FUNCTIONAL AND CODE COMPLIANT INSTALLATION.
40. SAFETY
A. COMPLY WITH OSHA AND NEC ARC FLASH PROTECTION REQUIREMENTS.
B. FOR EQUIPMENT BEING REMOVED AND REPLACED, THE CONTRACTOR SHALL
DE-ENERGIZE THE EQUIPMENT AND MAKE IT SAFE PRIOR TO REMOVAL AND COMPLY WITH
OSHA REQUIREMENTS FOR LOCKING-OUT AND TAGGING EQUIPMENT TO PREVENT
INADVERTENT RE-ENERGIZING.
ABBREVIATIONS
PANELBOARD
LUMINAIRE; TYPE AS INDICATED (2X4)
CIRCUIT CONNECTION. CONDUCTORS IN CONDUIT.
(MINIMUM 2-#12,1-#12 EGC IN 1/2 C.)
WALL SWITCH, LOW VOLTAGE, SEE OCC. SENSOR
DIAGRAM.
46" AFF UNLESS OTHERWISE NOTED. ASSOCIATED LOW
VOLTAGE WIRING IS NOT SHOWN ON DRAWINGS FOR
CLARITY.
X = TYPE:
3 = 3 WAY SWITCH
EMERGENCY LIGHTING UNIT
EMERGENCY EXIT LIGHTING
CEILING MOUNTED, LOW VOLTAGE, DUAL TECH,
OCCUPANCY SENSOR, WITH POWER/RELAY PACK
MOUNTED ABOVE DROP CEILING, DIMMABLE AS
INDICATED. PROVIDE ACCESS PANELS FOR ANY
MOUNTING ABOVE DRYWALL CEILINGS.
LIGHTING CONTROL PANEL
AREA OF WORK
FINISHED CEILING
FLOOR
DOOR
ABOVE
COUNTER
RECEPTACLE/DATA
3"
NOTE:
DETAIL SHOWN FOR REFERENCE ONLY, NOT ALL DEVICES ARE INDICATED
ON PLANS.
BACK SPLASHSTRIKE
SIDE
HINGE
SIDE
COUNTER TOP
LIGHT SWITCH
/DIMMER
CABLE, VOICE/DATA,
DUPLEX & QUADRAPLEX
RECEPTACLES
GANG
SWITCHING
MECHANICAL
CASETTE
CLOCK HANGER
RECEPTACLE
WALL MOUNTED EXIT
SIGN ABOVE DOOR (MAX.
MT. HT. OF 80" ABOVE
TOP OF DOOR)
ELECTRICAL DEVICES MOUNTING HEIGHT
CABLE TV
OUTLET
TV RECEPTACLE
A/V
OUTLET
(HDMI)
LCP
x
RECESSED DOWNLIGHT; TYPE AS INDICATED
A = FIXTURE TYPE B = SWITCH DESIGNATOR
S
E - 1 christopher.maas Stamp
WORK NOTES
1. REMOVE EXISTING RECESSED DOWNLIGHTS, TROFFERS, AND OCCUPANY SENSORS IN THE WORK AREA. DISCONNECT
LUMINAIRES FROM THE EXISTING LIGHTING CONTROL SYSTEM. STAND ALONE EMERGENCY AND EXIT LIGHTING IS TO REMAIN
WITH EXISTING FUNTIONALITY.
2. PROVIDE NEW RECESSED DOWNLIGHTS AND DIRECT/INDIRECTION LED LUMNAIRES TO REPLACE EXISTING FIXTURES IN THE WORK AREA. SEE LUMINAIRE SCHEDULE FOR FIXTURE DETAILS. CONNECT NEW LUMINAIRES TO EXISTING POWER CIRCUITS IN CONDUIT. PROVIDE ALL NECESSARY INCIDENTAL WORK AS REQUIRED FOR FULLY FUNCTIONAL LIGHTING SYSTEM.
3. PROVIDE NEW STANDALONE SWITCHING AND MOTION SENSOR CONTROL FOR TROFFERS AND DOWNLIGHTS IN THE WORK AREA. SEE OCCUPANY CONTROLS DIAGRAM. LOCATE NEW SWITCHES IN EXISTING SWITCH LOCATIONS WITH MATCHING SWITCHING AREA FUNCTIONALITY. PROVIDE ADDITIONAL OCCUPANCY SENSOR LOCATIONS WHERE REQUIRED AND
RECOMMENDED BY MANUFACTURER.
4. PROVIDE NEW ACOUSTICAL CEILING TILES AS NEEDED TO COMPLETE WORK. MATCH EXISTING A.C.T.
EXISTING ELECTRICAL
PANELS TO REMAIN
NEW WORK PLAN
KEYED WORK NOTES
1 PROVIDE LIGHTING CIRCUIT IN CONDUIT WITH (10) RECESSED DOWNLIGHT LUMINAIRES. (MIN 2 - #12, 1 - #12 EGC IN 1/2"C.) TO
THREE WAY SWITCHES. PROVIDE HOMERUN TO NEW 20A/1 BREAKER TO EXISTING PANELBOARD IN ELECTRICAL ROOM.
AREA OF
WORK
E - 2
LUMINAIRE SCHEDULE CEILING OCCUPANCY/VACANCY SENSOR DIMMING DIAGRAM
OPERATION SEQUENCE
E - 3
| E-LIGHTING PLAN Model (1) |
| E-LIGHTING PLAN Model (1) 2 |
| E-LIGHTING PLAN Model (1) 3 |
| E-LIGHTING PLAN Model (1) 4 |
| 2026-06-30T16:38:06-0400 | |
| MAAS.CHRISTOPHER.JETT.1588040727 |
File details come from the government source that posted it. Updated .