Attachment K_Design Revision 01.pdf

PDF 2 MB Posted

Attached to
X-132 Entrance at Northeast Loading Dock Renovations, NSN
Solicitation number
N4008526R0272
Issued by

About this file

This document is a Design Revision 1 package for a federal construction project at Naval Station Norfolk, dated September 22, 2026. The revision responds to design review comments for the X-132 Entrance at Northeast Loading Dock project (eProjects Work Order 1845266). The package includes updates to electrical, lighting, telecommunications, and security infrastructure drawings across multiple discipline areas.

The revision adds one new electrical details drawing (Sheet 63, EP501, NAVFAC Drawing 12,951,010) and revises 16 existing drawings across general, electrical, lighting, and telecommunications disciplines. Key revisions include edits to electrical symbols and legends; demolition and lighting plans incorporating quality control comments for clarity and correct terminology; updates to luminaire schedules and lighting control wiring diagrams; panel schedule modifications; and telecommunications symbol sheets, floor plans, and detail plates. Specific changes address clarification of demolition circuits, removal of unused symbols, editing of keynotes for accurate verbiage, updates to panel schedules, and correction of sheet border information. The work encompasses power distribution, lighting controls with emergency backup systems, data and voice telecommunications infrastructure, security systems roughing, and fire-rated penetration details. All drawings reference coordination requirements with architectural, mechanical, and fire protection disciplines, and include notes regarding secure boundary penetrations, dielectric breaks for conduit, and equipment grounding specifications consistent with NEC and UFC standards.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ROICC – Norfolk Form Version 2025.09.12 Page 1 of 3

Design Revision 1 eProjects Work Order Number: 1845266

Construction Contract Number: N/A

Building: X-132

Project Title: X-132 Entrance at Northeast Loading Dock

Date: 22 September 2026

Design Revision Purpose

1. Response to Design Review Comments.

Drawing Revisions

The following drawings, dated 9/22/2026, are added to the list of drawings and accompany this Design Revision:

SHEET NO.

NAVFAC DRAWING NO. SHEET TITLE NO. SHEET

ELECTRICAL

63 EP501 12,951,010 ELECTRICAL DETAILS

The following drawings are revised as of 9/22/2026, and accompany this Design Revision:

SHEET NO.

NAVFAC DRAWING NO. SHEET TITLE NO. SHEET

GENERAL

2 GI002 12,345,678 LIST OF SHEETS

ELECTRICAL

54 E-001 12,951,001 ELECTRICAL SYMBOLS, LEGEND, ABBREVIATIONS, AND NOTES

56 ED101 12,951,003 ENLARGED FIRST FLOOR PLAN - DEMOLITION

57 ED102 12,951,004 ENLARGED FIRST FLOOR PLANS - DEMOLITION

58 EL101 12,951,005 ENLARGED FIRST FLOOR PLAN - LIGHTING

59 EL501 12,951,006 LIGHTING DIAGRAMS AND DETAILS

60 EL601 12,951,007 LUMINAIRE SCHEDULE & LIGHTING PLATES

61 EP101 12,951,008 ENLARGED FLOOR PLAN - POWER

64 EP701 12,951,011 PANELBOARD SCHEDULES

TELECOMMUNICATIONS

65 T-001 12,951,012 TELECOMMUNICATIONS SYMBALS, LEGEND, ABBREVIATIONS, AND NOTES

66 T-002 12,951,013 OVERALL FIRST FLOOR PLAN

67 TT101 12,951,014 ENLARGED FLOOR PLAN - TELECOMMUNICATIONS

68 TT102 12,951,015 ENLARGED FIRST FLOOR PLAN - SECURITY

69 TT501 12,951,016 TELECOMMUNICATIONS DETAILS

70 TT502 12,951,017 TELECOMMUNICATIONS DETAILS

Form Version 2025.09.12 Page 2 of 3

On NAVFAC Drawing No. 12,951,001 (E-001)

ELECTRICAL LEGEND: Removed unused symbols.

On NAVFAC Drawing No. 12,950,949 (GI002)

ENLARGED FIRST FLOOR PLAN - DEMOLITION: Edited List of Sheets to incorporate information for added and revised sheets.

On NAVFAC Drawing No. 12,951,003 (ED101)

ENLARGED FIRST FLOOR PLAN - DEMOLITION: Edited to incorporate QC comments to indicate demo circuits and clarify demolition work.

KEYNOTES: Edited to incorporate QC comments to clarify and use correct verbiage.

On NAVFAC Drawing No. 12,951,003 (ED101)

KEYNOTES: Edited to incorporate QC comments to clarify and use correct verbiage.

On NAVFAC Drawing No. 12,951,005 (EL101)

ENLARGED FIRST FLOOR PLAN - DEMOLITION: Edited to incorporate QC comments and clarify work.

KEYNOTES: Edited to incorporate QC comments to clarify and use correct verbiage.

On NAVFAC Drawing No. 12,951,005 (EL101)

ENLARGED FIRST FLOOR PLAN - DEMOLITION: Edited to incorporate QC comments and clarify work.

KEYNOTES: Edited to incorporate QC comments to clarify and use correct verbiage.

On NAVFAC Drawing No. 12,951,006 (EL501)

LIGHTING AND RECEPTACLE CONTROLS WIRING DIAGRAM: Edited to remove receptacle controls from diagram.

On NAVFAC Drawing No. 12,951,006 (EL501)

LIGHTING CONTROLS WIRING DIAGRAM: Edited diagram.

On NAVFAC Drawing No. 12,951,007 (EL601)

LUMINAIRE SCHEDULE: Edited Luminaire schedule and notes.

On NAVFAC Drawing No. 12,951,007 (EL601)

LUMINAIRE SCHEDULE: Edited schedule.

On NAVFAC Drawing No. 12,951,008 (EP101)

ENLARGED FIRST FLOOR PLAN - DEMOLITION: Edited to incorporate QC comments and clarify work.

KEYNOTES: Edited to incorporate QC comments to clarify and use correct verbiage.

On NAVFAC Drawing No. 12,951,011 (EP701)

PANEL SCHEDULES: Updated Panel Schedules

KEYNOTES: Edited to incorporate QC comments to clarify and use correct verbiage.

Form Version 2025.09.12 Page 3 of 3

On NAVFAC Drawing No. 12,951,012 (T-001)

ELECTRICAL LEGEND: Removed unused symbols.

On NAVFAC Drawing No. 12,951,012 (T-002)

KEYNOTES: Edited to incorporate QC comments to clarify and use correct verbiage.

On NAVFAC Drawing No. 12,951,014 (TT101)

ENLARGED FIRST FLOOR PLAN - DEMOLITION: Edited to incorporate QC comments and clarify work.

KEYNOTES: Edited to incorporate QC comments to clarify and use correct verbiage.

On NAVFAC Drawing No. 12,951,015 (TT102)

ENLARGED FIRST FLOOR PLAN - DEMOLITION: Edited to incorporate QC comments and clarify work.

KEYNOTES: Edited to incorporate QC comments to clarify and use correct verbiage.

On NAVFAC Drawing No. 12,951,016 (TT501)

SHEET BORDER: Updated sheet number and NAVFAC Number

On NAVFAC Drawing No. 12,951,016 (TT502)

SHEET BORDER: Updated sheet number and NAVFAC Number

-End of Document-

WILLOUGHBY BAY

NAVAL SUPPORT

ACTIVITY

U.S. NAVAL STATION

SEWELLS POINT

NORFOLK

U.S. NAVAL

AIR STATION

CHESAPEAKE BAY

LITTLE CREEK

U.S. NAVAL

AMPHIBIOUS BASE

VA BEACH

OCEANA

NAVAL AIR

STATION

CHESAPEAKE

SOUTHERN BRANCH

EASTERN BRANCH

ST. JULIEN'S CREEK

U.S. NAVAL ANNEX

ELIZABETH RIVER

PORTSMOUTH

U.S. ARMY CRANEY

ISLAND DISPOSAL AREA

NANSEMOND RIVER

WESTERN BRANCH

CRANEY

ISLAND NAVY

DEPOT

PROJECT SITE

NORTH

GENERAL PROJECT SYMBOLS

A1

A-301

A-401 INTERIOR ELEVATION INDICATOR

INTERIOR ELEVATION NUMBER

SHEET WHERE DRAWN

EXTERIOR ELEVATION INDICATOR

ELEVATION NUMBER

DIRECTION OF VIEW

SHEET WHERE DRAWN

A1

A-301

WALL / PARTIAL BUILDING

SECTION INDICATOR

SECTION NUMBER

SHEET WHERE DRAWN

A1

A-301

BUILDING

SECTION

INDICATOR

A1

A-301

BUILDING

A1

A1

A1

A1

ROOM IDENTIFIER

DETAIL NUMBER

SHEET WHERE DRAWN

DETAIL INDICATOR

ROOM NAME

ROOM NUMBER

A-901 PHOTOGRAPH INDICATOR

PHOTOGRAPH NUMBER

SHEET WHERE SHOWN

A1

A-501

KEYNOTE INDICATOR

KEYNOTE NUMBER

PLAN NUMBER

A1

SCALE: 1/8" = 1'-0"

PLAN TITLE

A1

DETAILS / SECTIONS / ELEVS

SCALE: 1/8" = 1'-0"

A1

A-101

SECTION NUMBER

SHEET WHERE DRAWN

PLAN

NORTH

TRUE NORTH

VIEW NUMBER

SHEET BACK-REFERENCE

VIEW BACK-REFERENCE

REVISION NUMBER

REVISION TAG1

ROOM

PIER 11

PIER 10

PIER 9

PROJECT SITE

BUNKER HILL

DILLINGHAM BLVD

B U

N K

E R

H

IL

L

D E

C A

TU

R

A V

E

105TH ST

R O

D G

E R

S A

V E

HULL ST

PREBLE ST

V

IR

G

IN

IA

A

V E

M A

R Y

LA

N

D A

V E

DILLINGHAM BLVD

MASSEY

HUGHES DR

M A

R Y

LA

N

D A

V E

NORTH

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

GI002

L

IS

T O

F S

H E

E T

S G

E N

E R

A L P

R O

J E

C T

N O

T E

S A

N D

S Y

M B

O L S

DAS

12,950,949

SAR SAR

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

A. PILLO, RA

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

LIST OF SHEETS (CONT.)

SHEET NO.

NAVFAC DWG. NO. SHEET TITLENO. SHEET

GENERAL

1 GI001 12,950,948 COVER SHEET

2 GI002 12,950,949 LIST OF SHEETS, GENERAL PROJECT NOTES AND SYMBOLS

3 GI100 12,950,950 BUILDING CODE ANALYSIS AND LIFE SAFETY

4 GI101 12,950,951 FIRST FLOOR PLAN - LIFE SAFETY

CIVIL

5 C-001 12,950,952 CIVIL NOTES, ABBREVIATIONS, & SYMBOLS

6 CD101 12,950,953 CIVIL DEMOLITION PLAN

7 CS101 12,950,954 CIVIL SITE PLAN

8 C-501 12,950,955 PARKING LOT DETAILS

9 C-502 12,950,956 PAVEMENT DETAILS

VICINITY MAP

GENERAL PROJECT NOTES GOVERNING REGULATIONS

LOCATION MAP

A. WHERE EXISTING CONSTRUCTION IS DAMAGED BY CONSTRUCTION

REQUIRED BY THESE DOCUMENTS. REPAIR THE DAMAGED ITEM(S) WITH

MATERIALS TO MATCH THE ADJACENT MATERIAL, TEXTURE AND COLOR.

B. FIELD VERIFY EXISTING DIMENSIONS, PRIOR TO ORDERING MATERIALS OR

BEGINNING DEMOLITION.

C. ALL ITEMS NOT SHOWING AS "EXISTING" MUST BE PROVIDED AND

INSTALLED UNDER THE REQUIREMENTS OF THIS CONTRACT.

D. COORDINATE LAY DOWN AREA WITH THE CONTRACTING OFFICER PRIOR TO

THE PRECONSTRUCTION MEETING. THE ALLOWABLE AREA SIZE MUST BE

ESTABLISHED BY THE CONTRACTING OFFICER.

E. MANUFACTURER'S TRADE NAMES LISTED ARE NOT INTENDED TO BE

PROPRIETARY. PRODUCTS OF OTHER MANUFACTURERS WILL BE

ACCEPTABLE PROVIDED THEY MATCH THE COLOR, FINISHES, TEXTURES

AND PATTERNS OF THE MANUFACTURER LISTED, AND MEET THE TECHNICAL

REQUIREMENTS OF THE SPECIFICATIONS.

F. OBSERVE AND MAINTAIN BUILDING AND COMPOUND SECURITY

REQUIREMENTS AS DIRECTED BY THE CONTRACTING OFFICER.

G. CONSTRUCTION WILL BE ACCOMPLISHED IN AND AROUND AREAS WHICH

WILL REMAIN OPERATIONAL. AVOID INTERFERENCE WITH THE OPERATIONAL

WORK ROUTINE.

H. ALL SUBMITTALS REQUIRED BY THESE DRAWINGS OR SPECIFICATIONS

MUST BE SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL TO

COMMENCEMENT OF RELATED WORK.

I. STUDY AND COMPARE THE CONTRACT DOCUMENTS WITH EACH OTHER,

AND AT ONCE, REPORT TO THE CONTRACTING OFFICER ANY ERRORS,

INCONSISTENCIES, OR OMISSIONS DISCOVERED. ANY CONSTRUCTION

ACTIVITY PERFORMED KNOWING IT INVOLVES A RECOGNIZED ERROR,

INCONSISTENCY OR OMISSION IN THE CONTRACT DOCUMENTS WITHOUT

SUCH NOTICE TO THE CONTRACTING OFFICER, THE CONTRACTOR WILL

ASSUME RESPONSIBILITY FOR SUCH PERFORMANCE AND WILL BEAR THE

AMOUNT OF THE COST OF THE CONSTRUCTION.

J. REFER TO SPECIFICATION 01 14 00 - WORK RESTRICTIONS FOR SPECIAL

SCHEDULING REQUIREMENTS.

BUILDING CODES:

INTERNATIONAL BUILDING CODE (IBC) 2024

INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2024

UNIFIED FACILITIES CRITERIA (UFC) 1-200-01 DOD BUILDING CODE

(CHANGE 4, 17 DEC 2024)

ACCESSIBILITY CODE: (ABA)

ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS 2015

MECHANICAL CODE:

INTERNATIONAL MECHANICAL CODE (IMC) 2024

ELECTRICAL CODE:

NFPA 70, NATIONAL ELECTRIC CODE (NEC) 2023

PLUMBING CODE:

INTERNATIONAL PLUMBING CODE (IPC) 2024

FIRE PREVENTION & LIFE SAFETY CODE:

REFER TO SHEET GI100 FOR ADDITIONAL APPLICABLE CODES, STANDARDS

AND DESIGN CRITERIA.

LIST OF SHEETS

SHEET NO.

NAVFAC DWG. NO. SHEET TITLENO. SHEET

STRUCTURAL

10 S-001 12,950,957 STRUCTURAL SYMBOLS, LEGENDS, ABBREVIATIONS AND NOTES

11 S-002 12,950,958 STRUCTURAL NOTES

12 SD101 12,950,959 DEMOLITION FOUNDATION AND GROUND FLOOR PLAN

13 SD901 12,950,960 DEMOLITION STRUCTURAL PHOTOS

14 SB101 12,950,961 FOUNDATION AND GROUND FLOOR PLAN

15 SB401 12,950,962 RAMP - FOUNDATION PLAN, SECTIONS AND DETAILS

16 SB402 12,950,963 LOADING DOCK EXTENSION PLAN, AND SECTION

17 SB501 12,950,964 LOADING DOCK EXTENSION - DETAILS

18 SB502 12,950,965 INFILL DOCK LEVELER PLAN AND SECTION, TYPICAL FOOTING DETAILS

19 SB503 12,950,966 CONCRETE WALL INFILL SECTION, AND ELEVATION

20 SB504 12,950,967 MASONRY DETAILS

21 SB505 12,950,968 MASONRY DETAILS

22 SB506 12,950,969 DETAILS - MISCELLANEOUS

ARCHITECTURAL

23 A-001 12,950,970 ARCHITECTURAL ABBREVIATIONS, NOTES, SYMBOLS, AND OVERALL PLAN

24 AD101 12,950,971 ENLARGED FIRST FLOOR PLAN - DEMOLITION

25 AD102 12,950,972 ENLARGED FIRST FLOOR PLANS - DEMOLITION

26 AD103 12,950,973 ENLARGED FIRST FLOOR REFLECTED CEILING PLAN - DEMOLITION

27 AD201 12,950,974 PARTIAL ELEVATIONS - DEMOLITION

28 AE101 12,950,975 ENLARGED FIRST FLOOR PLAN - WORK

29 AE102 12,950,976 ENLARGED FIRST FLOOR PLANS - WORK

30 AE103 12,950,977 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN

31 AE201 12,950,978 ELEVATIONS - WORK

32 AE202 12,950,979 ELEVATIONS - WORK

33 AE501 12,950,980 DOOR SCHEDULE AND DETAILS

34 AE502 12,950,981 DOOR & WINDOW DETAILS

35 AE503 12,950,982 DETAILS

36 AE504 12,950,983 DETAILS

37 AE601 12,950,984 INTERIOR PARTITION TYPE SCHEDULE AND DETAILS

38 AF101 12,950,985 PARTIAL FIRST FLOOR FINISH AND SIGNAGE PLAN

39 AF601 12,950,986 INTERIOR FINISH SCHEDULE

40 AG601 12,950,987 TYPICAL SIGNAGE DETAILS, DOORWAY LOCATIONS, AND SCHEDULE

FIRE PROTECTION

41 FA001 12,950,988 FIRE ALARM AND MASS NOTIFICATION SYSTEM NOTES

42 FD101 12,950,989 PARTIAL FIRST FLOOR DEMOLITION PLAN - FIRE ALARM/ MASS NOTIFICATION

43 FA101 12,950,990 PARTIAL FIRST FLOOR WORK PLAN - FIRE ALARM/ MASS NOTIFICATION

44 FX101 12,950,991 FIRST FLOOR PLAN - FIRE SUPPRESSION

MECHANICAL

45 M-001 12,950,992 MECHANICAL LEGEND, ABBREVIATIONS AND NOTES

46 M-100 12,950,993 OVERALL FIRST FLOOR PLAN - MECHANICAL

47 MD401 12,950,994 FIRST FLOOR PLAN - DEMOLITION - MECHANICAL

48 MD402 12,950,995 ENLARGED FIRST FLOOR PLANS - DEMOLITION

49 M-401 12,950,996 ENLARGED FIRST FLOOR PLAN - MECHANICAL DUCTWORK

50 M-402 12,950,997 ENLARGE FIRST FLOOR PLAN - MECHANICAL PIPING

51 M-501 12,950,998 MECHANICAL DETAILS

52 M-601 12,950,999 MECHANICAL SCHEDULES

53 MI801 12,951,000 MECHANICAL CONTROLS

ELECTRICAL

54 E-001 12,951,001 ELECTRICAL SYMBOLS, LEGEND, ABBREVIATIONS, AND NOTES

55 E-002 12,951,002 OVERALL FIRST FLOOR PLAN

56 ED101 12,951,003 ENLARGED FIRST FLOOR PLAN - DEMOLITION

57 ED102 12,951,004 ENLARGED FIRST FLOOR PLANS - DEMOLITION

58 EL101 12,951,005 ENLARGED FIRST FLOOR PLAN - LIGHTING

59 EL501 12,951,006 LIGHTING DIAGRAMS AND DETAILS

60 EL601 12,951,007 LUMINAIRE SCHEDULE & LIGHTING PLATES

61 EP101 12,951,008 ENLARGED FLOOR PLAN - POWER

62 EP102 12,951,009 ENLARGED FLOOR PLANS - POWER

63 EP501 12,951,010 ELECTRICAL DETAILS

64 EP701 12,951,011 PANELBOARD SCHEDULES

TELECOMMUNICATIONS

65 T-001 12,951,012 TELECOMMUNICATIONS SYMBOLS, LEGEND, ABBREVIATIONS, AND NOTES

66 T-002 12,951,013 OVERALL FIRST FLOOR PLAN

67 TT101 12,951,014 ENLARGED FLOOR PLAN - TELECOMMUNICATIONS

68 TT102 12,951,015 FIRST FLOOR PLAN - SECURITY

69 TT501 12,951,016 TELECOMMUNICATIONS DETAILS

70 TT502 12,951,017 TELECOMMUNICATIONS DETAILS

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

D

E S

IG

N

R E

V

IS

IO

N

/2 2/

PANEL XXXXX

100A, 208Y/120V-30, 4W

FEEDS FROM PANEL MDP

INSTALLED 2019

DRAWING NO. ##,###,###

DEVICE ID

DEVICE RATING

POWER SOURCE

INSTALLATION DATE

NAVFAC DRAWING NUMBER

GENERAL

DEMOLITION AND NEW WORK NOTE - REFER TO "DEMOLITION

NOTES" AND "NEW WORK NOTES" FOR EACH SHEET

# SPECIALTY NOTE - REFER TO "SPECIALTY NOTES" FOR EACH SHEET

#. GENERAL NOTE - REFER TO "GENERAL NOTES" FOR EACH SHEET

OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS

NEW OR PROPOSED FOR CONSTRUCTION, UON.

OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS

EXISTING TO BE REMOVED-DEMOLISHED, UON.

OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS

EXISTING TO REMAIN, UON.

NEW TO EXISTING CONNECTION

REMOVE TO THIS POINT

LIGHTING

LED EXIT LUMINAIRE. ARROW, WHEN USED, INDICATES DIRECTION.

( INDICATES BRACKET, WALL MOUNTED.) FILLED IN QUADRANT(s)

OF SYMBOL INDICATES NUMBER AND ORIENTATION OF ILLUMINATED

FACES.

EMERGENCY BATTERY POWERED LED LIGHTING UNIT.

LED LUMINAIRE. ( INDICATES BRACKET, WALL MOUNTED.)

LED EMERGENCY LUMINAIRE. ( INDICATES BRACKET, WALL

MOUNTED.)

TOGGLE SWITCH, 20A, 120/277V. MOUNT 48" AFF UON. SUBSCRIPT "2"

= 2 WAY, "3" = 3 WAY, "4" = 4 WAY.

DIMMER SWITCH. (WATTAGE AS REQUIRED TO CONTROL THE

LUMINAIRE(S) CONNECTED UON.) MOUNT 48" AFF UON.

OCCUPANCY SENSOR, DUAL TECHNOLOGY. CEILING MOUNTED UON.OS

D

POWER PACK. SUBSCRIPT "E" INDICATES EMERGENCY BACKUP

POWER.

TS

HIGH INTENSITY DISCHARGE (H.I.D.) OR COMPACT FLUORESCENT

LUMINAIRE. ( INDICATES BRACKET, WALL MOUNTED.)

XX LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE, SHEET ELXXX.

OCCUPANCY SENSOR CONTROLLER, DUAL TECHNOLOGY. WALL

MOUNTED 48" AFF UON.

OS

POWER

20A, 120V DUPLEX CONVENIENCE RECEPTACLE. MOUNT 18" AFF

UON. 'GFI' DENOTES INTERNAL GROUND FAULT INTERRUPTER, 'WP'

DENOTES WEATHER PROOF ENCLOSURE AND 'C' DENOTES FLUSH

MOUNTED IN CEILING

QUADRUPLEX CONVENIENCE RECEPTACLE MOUNTED IN TWO-GANG

OUTLET BOX - EACH RATED 20A, 125 VOLTS WITH SINGLE COVER

PLATE, MOUNT 18" AFF, UON.

30A, 120V SINGLE OUTLET NEMA 6-30 WITH MATCHING PLUG.

JUNCTION BOX. MINIMUM 4" SQUARE X 2 1/8" SIZE PER NEC.J

20A, 120V DUPLEX CONVENIENCE RECEPTACLE UTILIZING GROUND

FAULT PROTECTION. MOUNT 6" ABOVE COUNTER UON. 'WP'

DENOTES WEATHER PROOF ENCLOSURE

20A, 120V FLUSH FLOOR DUPLEX RECEPTACLE

EQUIPMENT CONNECTIONS

MOTOR CONNECTION. HP AS INDICATED.

DISCONNECT SWITCH PROVIDED INTEGRAL WITH EQUIPMENT

M

E EQUIPMENT CONNECTION

MOTOR RATED SWITCH OR MANUAL MOTOR STARTER WITH

OVERLOADS.

M

DISCONNECT SWITCH. 3P = NO. OF POLES, 30 = SWITCH RATING, 20 =

FUSE RATING (NF = INDICATES NON-FUSED), 3R INDICATES NEMA

RATING.

3P

3R

WIRE, CONDUIT, AND RACEWAY

HOMERUN TO PANEL. PANEL & CIRCUIT DESIGNATIONS AS

INDICATED.

BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO TICK MARKS

INDICATE 2-#12 CONDUCTORS & 1-#12 GND. IN 1/2" CONDUIT UON.

CONDUIT LARGER THAN 1/2" & WIRE LARGER THAN #12 MUST BE

INDICATED.

LADDER RACK CABLE TRAY, SIZE AND TYPE AS INDICATED.

WIRE BASKET CABLE TRAY, SIZE AND TYPE AS INDICATED.

CONDUIT TURNED DOWN

CONDUIT TURNED UP

L2A-1,3

DISTRIBUTION

480Y/277V PANELBOARD.

208Y/120V PANELBOARD.

DRY-TYPE TRANSFORMER. 'T' DENOTES TRANSFORMER

IDENTIFICATION

T

240Y/120V PANELBOARD.

TELEPHONE/DATA

TELEPHONE OUTLET. MOUNT 18" AFF. UON.

COMBINATION VOICE/DATA OUTLET. MOUNT 18" AFF. UON.

DATA OUTLET. MOUNT 18" AFF. UON.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

E-001

E L E

C T

R

IC

A L S

Y M

B O

L S

L E

G E

N D

A

B B

R E

V

IA

T

IO

N S

A

N D

N O

T E

S

FVP

12,951,001

BMN BMN

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

CJM

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

GENERAL NOTES

GENERAL DEMOLITION NOTES

ELECTRICAL LEGEND

CONSTRUCTION NOTES

1/C ONE CONDUCTOR

A AMPERAGE OR AMPS

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ARF ABOVE RAISED FLOOR

BFG BELOW FINISHED GRADE

BH BASEBOARD HEATER

BKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

DWG DRAWING

EA EACH

EC EMPTY CONDUIT

ELEC ELECTRICAL

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

EXP EXPLOSION PROOF EQUIPMENT

FCU FAN COIL UNIT

FT FEET

GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED

GFE GOVERNMENT FURNISHED EQUIPMENT

GFGI GOVERNMENT FURNISHED GOVERNMENT INSTALLED

GFI GROUND FAULT INTERRUPTER

GND GROUND

HGT HEIGHT

HID HIGH INTENSITY DISCHARGE

HP HORSEPOWER

HUB COMPUTER DISTRIBUTION HUB

LED LIGHT EMITTING DIODE

LTS LUMINAIRE

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MLO MAIN LUGS ONLY

MTD MOUNTED

MTG HT MOUNTING HEIGHT

NEC NATIONAL ELECTRICAL CODE

NF NON FUSIBLE

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NTS NOT TO SCALE

OBI OUTLET BASE INFEED

OS OCCUPANCY SENSOR

PNL PANEL

PNLBD PANELBOARD

PVC POLYVINYL CHLORIDE CONDUIT

QU QUANTITY

REC RECEPTACLE

REQ'D REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

SHT SHEET

SUB SUBSTATION

SWBD SWITCHBOARD

T TELEPHONE

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLTAGE OR VOLTS

VRF VARIABLE REFRIGERANT FLOW UNIT

W WIRE

WP WEATHERPROOF

WW WIREWAY (TROUGH)

X IN SCHEDULES, ITEM NOT APPLICABLE

XFMR TRANSFORMER

Ø PHASE

ABBREVIATIONS

A EQUIPMENT SHOWN WITH DASHED LINE MUST BE REMOVED, UON.

B WIRING TO EQUIPMENT MUST BE REMOVED, UON.

C CONDUIT MUST BE REMOVED, UON.

D CONDUIT CONCEALED IN WALLS AND SLABS MUST BE BLANKED OFF AND

ABANDONED IN PLACE. PATCH WALLS AND SLABS AFTER DEMOLITION IS

COMPLETE.

E BOXES DISCONTINUED MUST BE BLANKED OFF OR REMOVED AND DEVICES

REMOVED.

F EXISTING ELECTRICAL EQUIPMENT NOT INDICATED ON DEMOLITION PLAN

MUST REMAIN CONNECTED FOR CONTINUED USE.

G RECONNECT EXISTING CIRCUIT(S) (INTERRUPTED BY REMOVAL OF

EXISTING DEVICE) TO THE REMAINING ELECTRICAL EQUIPMENT LOCATED

DOWNSTREAM FROM THE POINT OF INTERRUPTION.

1 ALL ELECTRICAL WORK AND MATERIAL IS NEW AND MUST BE PROVIDED BY

THE CONTRACTOR UON.

2 AN EQUIPMENT GROUND WIRE MUST BE RUN WITH FEEDERS AND BRANCH

CIRCUITS.

3 WIRING MUST BE AS PER NATIONAL ELECTRICAL CODE (NEC).

4 ELECTRICAL EQUIPMENT MUST BE IDENTIFIED AND LABELED.

5 FEEDERS/CIRCUITS MUST BE IDENTIFIED AT EACH END OF THE WIRE AND

AT EVERY SPLICE OR JUNCTION/PULL BOX.

6 PROVIDE NAMEPLATES ON THE EXTERIOR OF ELECTRICAL PANELS AND

ENCLOSURES AS FOLLOWS:

FOR DISCONNECT SWITCHES AND MOTOR STARTERS, THE TOP LINE SHALL

BE THE NAME/DESIGNATION OF EQUIPMENT BEING FED BY SAME.

7 PROVIDE NEW TYPED DIRECTORIES FOR PANELS (NEW OR EXISTING)

INCLUDED IN THIS PROJECT.

8 INTERIOR WIRING SYSTEMS MUST BE CONCEALED WITH FLUSH MOUNTED

BOXES/DEVICES, UON.

9 DRAWINGS ARE BASED ON EXISTING BUILDING PLANS AND FIELD

INVESTIGATIONS. CONTRACTOR MUST VISIT THE EXISTING BUILDING AND

ACQUAINT HIMSELF/HERSELF WITH THE EXISTING CONDITIONS.

CONTRACTOR MUST EXAMINE DRAWINGS TO AVOID CONFLICT.

10 COORDINATE LOCATION AND POWER REQUIREMENTS OF ELECTRICAL

DEVICES WITH MECHANICAL, PLUMBING, ARCHITECTURAL AND FIRE

PROTECTION DRAWINGS.

11 ELECTRICAL DEVICES SHOWN BUT NOT CIRCUITED MUST REMAIN ON

THEIR EXISTING CIRCUIT.

12 PROVIDE ARC-FLASH LABELS ON ALL PANELS/DISCONNECT SWITCHES AS

PER UFC 3-560-01 AND NFPA 70E. SEE DETAIL PLATE ON SHEET EP###.

13 SINGLE PHASE (120/208V) BRANCH CIRCUITS MUST CONSIST OF 2#12 & 1#12

GND. IN 1/2"C UON. THREE PHASE BRANCH CIRCUITS CONSIST OF 3#12 &

1#12 GND IN 1/2"C UON.

14 REFER TO PLANS FOR CONDUCTOR SIZING. COMPLY WITH THE FOLLOWING

GUIDELINES FOR CONDUCTOR RUN LENGTHS:

20A,120V CIRCUITS LONGER THAN 100' - USE #10 AWG TO LIMIT VOLTAGE

DROP ON BRANCH CIRCUITS TO 3%

20A, 120V CIRCUITS LONGER THAN 150' - USE #8 AWG TO LIMIT VOLTAGE

DROP ON BRANCH CIRCUITS TO 3%

20A, 277V CIRCUITS LONGER THAN 150' - USE #10 AWG TO LIMIT VOLTAGE

DROP ON BRANCH CIRCUITS TO 3%

15 COORDINATE ELECTRICAL WORK WITH ARCHITECTURAL, MECHANICAL AND

FIRE PROTECTION WORK PRIOR TO FABRICATION AND INSTALLATION TO

PREVENT CONFLICTS. NOTIFY CONTRACTING OFFICER WHERE CONFLICTS

ARE DISCOVERED PRIOR TO CONSTRUCTION AND BEFORE BEGINNING

WORK IN THOSE AREAS. ALL CONFLICTS THAT ARISE DUE TO LACK OF

COORDINATION MUST BE RECTIFIED BY THE CONTRACTOR AT NO COST TO

THE GOVERNMENT.

1 PROVIDE A MINIMUM OF 2 WEEKS NOTICE OF POWER OUTAGES TO

ACTIVITY AND GOVERNMENT OFFICIAL.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

D

E S

IG

N

R E

V

IS

IO

N

/2 2/

1 1

M

E

OS

OS

OS

OS

OS

PP

PP

PP

OS

PP

M M

1HB-13

FIRE PUMP

A-119

CORR

118A

JANITOR

A-120

STAIR #3

ST03

ELEVATOR LOBBY

MAIN ELECTRICAL

A-122

1HA-6

UH-5

B-109

OU-8U-2LA-11

NF

302P 3R

1HB-7

LEGEND

SYMBOL DESCRIPTION

AREA NOT IN CONTRACT.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

ED101

E N

L A

R G

E D

F

IR

S T

F L O

O R

P L A

N

D E

M O

L

IT

IO

N

FVP

12,951,003

BMN BMN

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

CJM

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

SCALE: 1/4" = 1'-0"

C1

E-002 B1

ENLARGED FIRST FLOOR PLAN - DEMOLITION

A REFER TO SHEET E-001 FOR GENERAL ELECTRICAL NOTES.

B PROVIDE ALL ELECTRICAL DEMOLITION WORK NECESSARY TO INSTALL

NEW WORK. REROUTE AND RECONNECT CIRCUITS (POWER AND

TELECOMMUNICATIONS) THAT WILL REMAIN IN USE, BUT INTERFERES WITH

NEW CONSTRUCTION. REMOVE ALL WIRING FROM ABANDONED CONDUITS

AND DISCONNECT FROM ALL POWER SOURCES.

C ALL EXISTING CONDUITS THAT WILL NOT BE REUSED MUST BE REMOVED.

ONLY CONDUITS IN WALLS THAT ARE TO REMAIN AND THAT DO NOT

INTERFERE WITH NEW WORK MAY BE ABANDONED IN PLACE.

D ALL MATERIALS REMOVED UNDER DEMOLITION SHALL BECOME THE

PROPERTY OF THE CONTRACTOR AND MUST BE REMOVED COMPLETELY

OFF SITE.

E CIRCUITS SHOWN ARE BASED ON FIELD AND DRAWING INVESTIGATIONS.

VERIFY ALL CIRCUITS PRIOR TO DEMOLITION.

F REFER TO ARCHITECTURAL SHEETS FOR EACH ROOM UNIT TYPE.

1 EXISTING POWER, LIGHTING, AND EQUIPMENT TO REMAIN. PRESERVE AND

EXTEND CIRCUITS FOR POWER, LIGHTING, AND EQUIPMENT IN THIS ROOM,

INCLUDING DEVICES NOT SHOWN, IMPACTED BY DEMOLITION TO REMAIN

ACTIVE.

2 DISCONNECT LIGHTS IN FIRE PUMP ROOM 119 AND EXTEND CIRCUIT TO

MAINTAIN DURING DEMOLITION WORK. PRESERVE LIGHT FIXTURES AND

CIRCUITS FOR RECONNECTION AS INDICATED ON WORK PLAN.

3 CIRCUIT FEEDS OTHER FIXTURES IN BUILDING NOT INDICATED ON PLAN.

EXTEND CKT TO MAINTAIN CONNECTION DURING DEMOLITION. PRESERVE

CKT FOR RECONNECTION AS INDICATED ON WORK PLAN.

4 EXISTING FIXTURE TO REMAIN. DEMOLISH WIRING BACK TO NEAREST

UPSTREAM JUNCTION BOX AND PRESERVE FIXTURE AND CONDUIT FOR

RECONNECTION IN NEW WORK.. EXTEND AND MAINTAIN EXISTING CIRCUIT

FEEDING FIXTURES TO REMAIN OUTSIDE OF SCOPE OF WORK. CKT IS

6-#12 AWG AND 1-#12 G IN 1/2" C.

5 DISCONNECT EXISTING FIXTURE AND PRESERVE FOR RECONNECTION IN

WORK. DEMOLISH WIRING AND CONDUIT BACK TO NEAREST UPSTREAM

JUNCTION BOX.

5 5 5 5

4 4

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

D

E S

IG

N

R E

V

IS

IO

N

/2 2/

1/4" = 1' - 0" 0 5' 10' 15'1'

GRAPHIC SCALE

KEY PLAN

DCA B E

PLAN

NORTH

AREA OF WORK

KEYNOTESGENERAL SHEET NOTES # (THIS SHEET ONLY)

G CONDUIT AND WIRING FEEDING DEVICES, LIGHTING FIXTURES, AND

EQUIPMENT CONNECTIONS LOCATED OUTSIDE OF SECURE BOUNDARY

MUST NOT BE RUN THROUGH SECURE BOUNDARY. ROUTE CONDUIT AND

CABLES AROUND SECURE BOUNDARY FROM SOURCE PANEL.

H SEE SHEET EP102 FOR PANEL LOCATIONS.

6 DEMOLISH EXISTING RECEPTACLE AND ASSOCIATED WIRING AND

CONDUIT BACK TO SOURCE. PRESERVE CIRCUIT BREAKER FOR REUSE.

7 EXISTING OCCUPANCY SENSOR TO REMAIN. PRESERVE FOR

RECONNECTION

8 EXISTING LIGHTING POWER PACK FOR LIGHTING CONTROLS AND

CONNECTION TO FIRE ALARM PANEL FOR EMERGENCY POWER TO

REMAIN. PRESERVE FOR RECONNECTION. SEE SHEET EL501 FOR

LIGHTING DETAILS.

9 DISCONNECT AND PRESERVE EXISTING OCCUPANCY SENSOR FOR

RECONNECTION.

10 DISCONNECT EXISTING DISCONNECT SWITCH AND PRESERVE FOR

RECONNECTION. DEMO CONDUIT AND WIRING BETWEEN DISCONNECT

SWITCH AND MECHANICAL UNIT. PRESERVE CKT FOR RECONNECTION.

11 EXISTING NIPR CABLE TRAY TO REMAIN. SEE SHEET TT101 FOR CABLE

TRAY WORK.

PLAN

NORTH

E E E E E

OU-1 OU-2 OU-3 OU-4

1LB-3,5 1LB-7,9 1LB-11,13 1LB-15,17

NF

302P 3RNF

302P 3RNF

302P 3RNF

302P 3R

OU-9

NF

302P 3R

U-2LB1-11,13

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

ED102

E N

L A

R G

E D

F

IR

S T

F L O

O R

P L A

N S

D

E M

O L

IT

IO

N

FVP

12,951,004

BMN BMN

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

CJM

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

SCALE: 1/4" = 1'-0"

C1

E-002 A1

ENLARGED FIRST FLOOR PLAN - DEMOLITION

SCALE: 1/4" = 1'-0"

C1

E-002 A3

ENLARGED FIRST FLOOR PLAN - DEMOLITION

1/4" = 1' - 0" 0 5' 10' 15'1'

GENERAL SHEET NOTES

GRAPHIC SCALE(S)

KEY PLAN

KEYNOTES# (THIS SHEET ONLY)

A EQUIPMENT SHOWN WITH DASHED LINE MUST BE REMOVED, UON.

B WIRING TO EQUIPMENT MUST BE REMOVED, UON.

C CONDUIT MUST BE REMOVED, UON.

D CONDUIT CONCEALED IN WALLS AND SLABS MUST BE BLANKED OFF AND

ABANDONED IN PLACE. PATCH WALLS AND SLABS AFTER DEMOLITION IS

COMPLETE.

E BOXES DISCONTINUED MUST BE BLANKED OFF OR REMOVED AND DEVICES

REMOVED.

F EXISTING ELECTRICAL EQUIPMENT NOT INDICATED ON DEMOLITION PLAN

MUST REMAIN CONNECTED FOR CONTINUED USE.

G RECONNECT EXISTING CIRCUIT(S) (INTERRUPTED BY REMOVAL OF

EXISTING DEVICE) TO THE REMAINING ELECTRICAL EQUIPMENT LOCATED

DOWNSTREAM FROM THE POINT OF INTERRUPTION.

1 DISCONNECT MECHANICAL UNIT FROM EXISTING DISCONNECT SWITCH

AND PRESERVE DISCONNECT SWITCH FOR RECONNECTION. DEMO

CONDUIT AND WIRING BETWEEN DISCONNECT SWITCH AND MECHANICAL

UNIT. PRESERVE CKT FOR RECONNECTION.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

D

E S

IG

N

R E

V

IS

IO

N

/2 2/

DCA B E

PLAN

NORTH

AREA OF WORK

PLAN

NORTH

PLAN

NORTH

OS

OS

OS

OS

PP

PP

PP

OS

PP

OS

OS

PP

OSOS

PP PP

PP

E

E

E

E

E

A

A

B

SECURITY BOOTH

117B

VESTIBULE

117A

LOCKERS

118B

FIRE PUMP

A-119

STAIR #3

ST03

CORR

118A

ELEVATOR LOBBY

MAIN ELECTRICAL

A-122

E-1H-18

B

X

LEGEND

SYMBOL DESCRIPTION

AREA NOT IN CONTRACT.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

EL101

E N

L A

R G

E D

F

IR

S T

F L O

O R

P L A

N

L

IG

H T

IN

G

FVP

12,951,005

BMN BMN

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

CJM

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

SCALE: 1/4" = 1'-0"

C1

E-002 B1

ENLARGED FIRST FLOOR PLAN - LIGHTING

1 RELOCATE EXISTING FIXTURE PRESERVED DURING DEMOLITION. PROVIDE

CIRCUIT INDICATED.

2 PROVIDE 4' LED LINEAR FIXTURE TO MATCH EXISTING FIXTURE TYPE

INDICATED.

3 EXISTING FIXTURE PRESERVED DURING DEMOLITION. PROVIDE WIRING

AND CONDUIT TO RECONNECT TO CIRCUIT INDICATED.

4 PROVIDE POWER PACK AND EMERGENCY POWER PACK FOR LIGHTING

CONTROLS. CONNECT EMERGENCY POWER PACK TO FIRE ALARM RELAY

PER MANUFACTURER'S REQUIREMENTS. SEE "EMERGENCY POWER PACK

WIRING DIAGRAM ON SHEET EL501 FOR ADDITIONAL DETAIL.

5 EXISTING LIGHTING CONTROLS PRESERVED DURING DEMOLITION.

RECONNECT AS INDICATED.

6 EXISTING FIXTURES, CONTROLS, AND CKT PRESERVED DURING

DEMOLITION. PROVIDE WIRE AND CONDUIT TO EXTEND CKT AS

NECESSARY TO ROUTE CKT FEED OUTSIDE OF SECURE AREA.

11 2

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

D

E S

IG

N

R E

V

IS

IO

N

/2 2/

1/4" = 1' - 0" 0 5' 10' 15'1'

GRAPHIC SCALE

KEY PLAN

DCA B E

PLAN

NORTH

AREA OF WORK

KEYNOTESGENERAL SHEET NOTES # (THIS SHEET ONLY)

7 NORMAL POWER FOR FIXTURES IN UNSECURED SPACE IS FED FROM

PANEL 1HB, CKT 7. EMERGENCY POWER FOR FIXTURES IN UNSECURED

SPACE IS FED FROM E-1H, CKT 10. PROVIDE CONDUIT AND WIRING TO

RECONNECT EXISTING FIXTURES SALVAGED DURING DEMOLITION.

PROVIDE WIRE AND CONDUIT TO RECONNECT LIGHTING CONTROLS.

FEEDERS FOR FIXTURES MUST NOT BE RUN IN SECURE AREA AND MUST

BE ROUTED OUTSIDE OF SECURE BOUNDARY.

8 NORMAL POWER FOR FIXTURES IN SECURE SPACES FED FROM PANEL

1HB, CKT 13. EMERGENCY POWER FOR FIXTURES IN SECURED AREA FED

FROM PANEL E-1H, CKT 26. PROVIDE CONDUIT AND WIRING TO

RECONNECT EXISTING FIXTURES PRESERVED DURING DEMOLITION.

PROVIDE WIRE AND CONDUIT TO RECONNECT LIGHTING CONTROLS.

FEEDERS PROVIDING POWER IN SECURE AREA MUST ONLY SERVE

SECURED AREA.

9 ROUTE ALL PENETRATIONS THROUGH SECURE BOUNDARY FOR POWER TO

LIGHTING IN THIS LOCATION. PROVIDE DIELECTRIC BREAK FOR CONDUIT

ON SECURE SIDE. SEE SHEET EP501 FOR ELECTRICAL DETAILS.

10 RELOCATE AND RECONNECT EXISTING FIXTURE SALVAGED DURING

DEMOLITION. PROVIDE WIRE AND CONDUIT TO EXTEND LIGHTING CKT

1HB-7 TO RECONNECT FIXTURE.

A REFER TO SHEET E-001 FOR GENERAL ELECTRICAL NOTES.

B PROVIDE ALL ELECTRICAL DEMOLITION WORK NECESSARY TO INSTALL

NEW WORK. REROUTE AND RECONNECT CIRCUITS (POWER AND

TELECOMMUNICATIONS) THAT WILL REMAIN IN USE, BUT INTERFERES WITH

NEW CONSTRUCTION. REMOVE ALL WIRING FROM ABANDONED CONDUITS

AND DISCONNECT FROM ALL POWER SOURCES.

C ALL EXISTING CONDUITS THAT WILL NOT BE REUSED MUST BE REMOVED.

ONLY CONDUITS IN WALLS THAT ARE TO REMAIN AND THAT DO NOT

INTERFERE WITH NEW WORK MAY BE ABANDONED IN PLACE.

D ALL MATERIALS REMOVED UNDER DEMOLITION SHALL BECOME THE

PROPERTY OF THE CONTRACTOR AND MUST BE REMOVED COMPLETELY

OFF SITE.

E CIRCUITS SHOWN ARE BASED ON FIELD AND DRAWING INVESTIGATIONS.

VERIFY ALL CIRCUITS PRIOR TO DEMOLITION.

F REFER TO ARCHITECTURAL SHEETS FOR EACH ROOM UNIT TYPE.

G CONDUIT AND WIRING FEEDING DEVICES, LIGHTING FIXTURES, AND

EQUIPMENT CONNECTIONS LOCATED OUTSIDE OF SECURE BOUNDARY

MUST NOT BE RUN THROUGH SECURE BOUNDARY. ROUTE CONDUIT AND

CABLES AROUND SECURE BOUNDARY FROM SOURCE PANEL.

H SEE SHEET EP102 FOR PANEL LOCATIONS.

PLAN

NORTH

EMERGENCY POWER

LIGHTING CIRCUIT

N H N H

POWER PACK

NOC

NORMAL

LIGHTING

LOAD

EMERGENCY

POWER PACK

NOC

LOW VOLTAGE CONTROL WIRING PER

MANUFACTURER'S REQUIREMENTS (TYP)

FIRE ALARM RELAY

(SEE FA DRAWINGS FOR LOCATIONS)

EMERGENCY

LIGHTING

LOAD

NCC

NOTE: MULTIPLE EMERGENCY POWER PACKS CAN BE CONNECTED TO A

SINGLE FIRE ALARM RELAY. CONSULT WITH MANUFACTURER FOR

MAXIMUM QUANTITY OF EMERGENCY POWER PACKS THAT CAN BE

WIRED TOGETHER.

DIGITAL POWER

PACK FOR

RECEPTACLES

LINE VOLTAGE FOR

RECEPTACLES

LINE VOLTAGE

FOR LIGHTING

H N

DIGITAL POWER

PACK FOR

LIGHTING

LIGHTING

LOAD

SWITCH LEG

LOW VOLTAGE CONTROL WIRING PER

MANUFACTURER'S REQUIREMENTS

LOW VOLTAGE SWITCH

OCCUPANCY SENSOR

DAYLIGHT SENSOR

H N

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

EL501

L

IG

H T

IN

G

D

IA

G R

A M

S A

N D

D E

T A

IL

S

FVP

12,951,006

BMN BMN

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

CJM

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

SCALE: NOT TO SCALE

C1

EMERGENCY POWER PACK WIRING DIAGRAM

SCALE: NOT TO SCALE

C3

LIGHTING CONTROLS WIRING DIAGRAM

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

D

E S

IG

N

R E

V

IS

IO

N

/2 2/

DIRECT/INDIRECT LED LUMINAIRE

REVISED: NOVEMBER 2020 NL-1LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - HEAVY GAUGE COLD ROLLED STEEL OR DIE CAST ALUMINUM. SIZE SHOWN

AS INDICATED IN LUMINAIRE SCHEDULE.

2. OPTICS - FROSTED ACRYLIC OR POLYCARBONATE LENS WITH DIE FORMED COLD

ROLLED SHEET STEEL REFLECTORS.

3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND

MINIMUM EFFICACY OF 100 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED

IN LUMINAIRE SCHEDULE.

4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH

MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND

< 20% THD. ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS

INDICATED IN LUMINAIRE SCHEDULE.

5. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION, ROHS COMPLIANT. DLC

QUALIFIED. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.

6. MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING.

7. OPTIONS - EMERGENCY BATTERY BACK-UP, INTEGRAL OCCUPANCY/VACANCY

SENSOR, VARIOUS SIZE AND OUTPUT OPTIONS, SURFACE-MOUNTING KIT.

NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE

THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

LED INDUSTRIAL LIGHT

REVISED: NOVEMBER 2020 NL-23LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - EXTRUDED ALUMINUM OR WELDED STEEL HOUSING WITH SNAP-ON END

CAPS. SIZE AS INDICATED IN LUMINAIRE SCHEDULE.

2. OPTICS - DIFFUSE ACRYLIC LENS.

3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND

MINIMUM EFFICACY OF 90 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED

IN LUMINAIRE SCHEDULE.

4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH

MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND

< 20% THD. ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS

INDICATED IN LUMINAIRE SCHEDULE.

5. CERTIFICATION - UL LISTED FOR DAMP OR WET LOCATION, ROHS COMPLIANT. DLC

QUALIFIED. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.

6. MOUNTING - PENDANT, STEM, OR SURFACE MOUNTED WITH STAINLESS STEEL

MOUNTING HARDWARE.

7. OPTIONS - INTEGRAL OCCUPANCY SENSOR, EMERGENCY BATTERY BACK-UP, VARIOUS

PROFILE DIMENSIONS AND RUN LENGTHS, AND VARIOUS CLEAR OR FROSTED

POLYCARBONATE LENSES.

NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE

THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

EDGE-LIT EXIT SIGN

REVISED: NOVEMBER 2020 NL-27LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - EXTRUDED ALUMINUM WITH CLEAR ACRYLIC EDGE-LIT PANEL.

2. LIGHT SOURCE - SOLID STATE LEDS.

3. DRIVER - INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF, OPERATING

VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD.

4. CERTIFICATION - NFPA 101, UL LISTED FOR DAMP OR WET LOCATION, AND ROHS

COMPLIANT.

5. MOUNTING - SURFACE MOUNTED ON CEILING AND/OR WALL.

6. OPTIONS - RED OR GREEN LETTERING, ONE- OR TWO-SIDED. BATTERY BACKUP.

NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE

THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

EL601

L U

M

IN

A

IR

E S

C H

E D

U L E

L

IG

H

T

IN

G P

L A

T E

S

FVP

12,951,007

BMN BMN

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

CJM

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

LUMINAIRE SCHEDULE

LUMINAIRE

TYPE DESCRIPTION PLATE LAMP TYPE WATTS LUMENS VOLTAGE MOUNTING NOTES

A 2'X2' RECESSED LED TROFFER NL-1 LED 33 W 3400 277 V RECESSED

B 4' LINEAR LED FIXTURE NL-2 LED 22 W 3300 277 V SURFACE 1

X EDGE-LIT LED EXIT SIGN NL-27 LED 0 W N/A 277 V SURFACE

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

D

E S

IG

N

R E

V

IS

IO

N

/2 2/

1. PROVIDE FIXTURE WITH POLYCARBONATE LENSE.

M M

E

U-2LA-11

OU-8

NF

302P 3R

1LB-27

1LB-25

1LB-8

1LB-21,23

302P 15

WSHP-1SECURITY BOOTH

117B

VESTIBULE

117A

LOCKERS

118B

FIRE PUMP

A-119

STAIR #3

ST03

JANITOR

A-120

CORR

118A

ELEVATOR LOBBY

MAIN ELECTRICAL

A-122

LEGEND

SYMBOL DESCRIPTION

AREA NOT IN CONTRACT.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

EP101

E N

L A

R G

E D

F L O

O R

P L A

N

P O

W E

R

FVP

12,951,008

BMN BMN

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

CJM

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

SCALE: 1/4" = 1'-0"

C1

E-002 B1

ENLARGED FIRST FLOOR PLAN - POWER

1 EXISTING DISCONNECT SWITCH PRESERVED DURING DEMOLITION.

PROVIDE 2-#10 AWG AND 1-#10 G IN 1/2" RIGID STEEL CONDUIT FROM

DISCONNECT SWITCH TO RELOCATED MECHANICAL UNIT ON INDICATED

CKT PRESERVED DURING DEMOLITION.

2 REROUTE CIRCUIT TO PENETRATE SECURE BOUNDARY AT INDICATED

LOCATION AND PROVIDE DIELECTRIC BREAK IN CONDUIT ON SECURE SIDE

OF BOUNDARY FOR MECHANICAL EQUIPMENT. RECONNECT TO EXISTING

CKT PRESERVED DURING DEMOLITION.

3 PROVIDE DISCONNECT SWITCH AND FEEDER FOR MECHANICAL UNIT AS

INDICATED. FEEDERS FOR UNIT MUST BE ROUTED OUTSIDE OF SECURE

BOUNDARY TO PANEL. SEE SHEET EP102 FOR ENLARGED ELECTRICAL

ROOM LAYOUT.

4 ROUTE FEEDERS FOR ELECTRICAL DEVICES OUTSIDE OF SECURE

BOUNDARY.

5 PROVIDE WIRE AND CONDUIT TO RECONNECT ALL DEVICES TO EXISTING

CIRCUIT AS INDICATED. PROVIDE DIELECTRIC BREAK ON SECURE SIDE OF

BOUNDARY AND ROUTE FEEDER THROUGH DESIGNATED PENETRATION

POINT INDICATED IN NOTE 6.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

D

E S

IG

N

R E

V

IS

IO

N

/2 2/

1/4" = 1' - 0" 0 5' 10' 15'1'

GRAPHIC SCALE

KEY PLAN

DCA B E

PLAN

NORTH

AREA OF WORK

KEYNOTESGENERAL SHEET NOTES # (THIS SHEET ONLY)

6 LOCATE PENETRATIONS INTO SECURE BOUNDARY WITHIN 96 SQ. INCH

AREA IN APPROXIMATELY THIS LOCATION. PROVIDE DIELECTRIC BREAKS

ON SECURE BOUNDARY SIDE IN ALL CONDUIT ENTERING SPACE..

7 PANEL FEEDING CKT LOCATED IN ROOM TELE 213B LOCATED ON THE

SECOND FLOOR.

A REFER TO SHEET E-001 FOR GENERAL ELECTRICAL NOTES.

B PROVIDE ALL ELECTRICAL DEMOLITION WORK NECESSARY TO INSTALL

NEW WORK. REROUTE AND RECONNECT CIRCUITS (POWER AND

TELECOMMUNICATIONS) THAT WILL REMAIN IN USE, BUT INTERFERES WITH

NEW CONSTRUCTION. REMOVE ALL WIRING FROM ABANDONED CONDUITS

AND DISCONNECT FROM ALL POWER SOURCES.

C ALL EXISTING CONDUITS THAT WILL NOT BE REUSED MUST BE REMOVED.

ONLY CONDUITS IN WALLS THAT ARE TO REMAIN AND THAT DO NOT

INTERFERE WITH NEW WORK MAY BE ABANDONED IN PLACE.

D ALL MATERIALS REMOVED UNDER DEMOLITION SHALL BECOME THE

PROPERTY OF THE CONTRACTOR AND MUST BE REMOVED COMPLETELY

OFF SITE.

E CIRCUITS SHOWN ARE BASED ON FIELD AND DRAWING INVESTIGATIONS.

VERIFY ALL CIRCUITS PRIOR TO DEMOLITION.

F REFER TO ARCHITECTURAL SHEETS FOR EACH ROOM UNIT TYPE.

G CONDUIT AND WIRING FEEDING DEVICES, LIGHTING FIXTURES, AND

EQUIPMENT CONNECTIONS LOCATED OUTSIDE OF SECURE BOUNDARY

MUST NOT BE RUN THROUGH SECURE BOUNDARY. ROUTE CONDUIT AND

CABLES AROUND SECURE BOUNDARY FROM SOURCE PANEL.

H SEE SHEET EP102 FOR PANEL LOCATIONS.

PLAN

NORTH

AF-1APRIL 2015

GENERAL ARC FLASH WARNING LABEL

SKETCH DATE STYLE

NOTES:

1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO WARN OF ARC

FLASH HAZARDS.

2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE.

3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE EQUIPMENT.

4. THE SIZE OF THE LABEL SHALL BE MINIMUM:

EQUIPMENT TYPE HEIGHT WIDTH

INDOOR 2" 3"

OUTDOOR 3" 4.5"

5. A DOWNLOADABLE WINDOWS METAFILE IS AVAILABLE ON THE WHOLE BUILDING DESIGN GUIDE

WEBSITE (WWW.WDBG.ORG) FOR USE IN A LABEL MAKING MACHINE.

A. THE FILE IS LOCATED ON THE "NAVFAC CADD DETAILS" PAGE. TO NAVIGATE TO THIS LOCATION, FOLLOW: HOME > DOCUMENTS & REFERENCES > CCB > CADD LIBRARY > NAVFAC CADD

RESOURCES > NAVFAC CADD DETAILS.

B. ALTERNATIVELY, TYPE IN THE FOLLOWING ADDRESS IN INTERNET EXPLORER:

HTTP://WWW.WBDG.ORG/CCB/BROWSE_CAT.PHP?C=23

WIDTH

HEIGHT

P O

W E

R

T E

LE

P

H O

N E

/D A

T A

T E

LE

P

H O

N E

ALIGN WITH CENTERLINE OF

DOOR FOR WALL MOUNTING

6"

48"

6" TYP

S W

IT

C

H /S

E N

S O

R

F A

P U

LL

S

T A

T

IO

N

P O

W E

R

C A

T V

18"

54"

W A

LL

M

T D

T E

LE

P

H O

N E

W A

LL

M

T D

S T

R O

B E

H O

R N

A N

D S

T R

O B

E

APPLIANCES SHALL BE MOUNTED

SUCH THAT THE ENTIRE LENS IS

NOT LESS THEN 80" AND NOT

GREATER THAN 96" ABOVE

FINISHED FLOOR.

48"

6" 3"

6"

D O

O R

SWITCH/SENSOR

6" TYP

6"

18"

MIN

4"

6" MAX

REFER TO PARTITION TYPE

FOR WALL ASSEMBLY

ULTRA NT RADIANT

BARRIER ADHERED

TO CONDUIT

SAFING BATT INSULATION

METALLIC CONDUIT

SEALANT AND

BACKER ROD

ACOUSTICAL

SEALANT

GROUNDING

CLAMP WITH

NO. 4 WIRE TO

SECURE AREA

GROUNDING

SYSTEM

THRU RF SHIELDING

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

EP501

E L E

C T

R

IC

A L D

E T

A

IL

S

FVP

12,951,010

BMN BMN

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

CJM

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

D

E S

IG

N

R E

V

IS

IO

N

/2 2/

SCALE: NOT TO SCALE

C2

TYPICAL MOUNTING HEIGHT AND DEVICE ALIGNMENT DETAIL

SCALE: NOT TO SCALE

A1

DIELECTRIC BREAK DETAIL

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

EP701

P A

N E

L B

O A

R D

S C

H E

D U

L E

S

FVP

12,951,011

BMN BMN

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

CJM

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

D

E S

IG

N

R E

V

IS

IO

N

/2 2/

TOTAL CONNECTED AMPS: A: 6.5 B: 4.8 C: 4.8

29 SPACE -- -- -- -- 0 A 20 -- -- HP-A-109 30

27 SPACE -- -- -- -- 0 A 20 -- -- HP-C-108 28

25 SPACE -- -- -- -- 0 A 20 -- -- SPARE 26

23 5 A 0 A 20 -- -- UH-18 24

21 5 A 0 A 20 -- -- UH-22 22

DOCK LEVELER 20

5 A 0 A 20 -- -- UH-10 20

17 HP-C-107 -- -- 20 0 A 0 A 20 -- -- UH-20 18

15 SPARE -- -- 20 0 A 0 A 20 -- -- UH-19 16

13 LTG SECURE AREA 1/2" #12 20 2 A 0 A 20 -- -- UH-16 14

11 LTG 106-115 -- -- 20 0 A 0 A 20 -- -- UH-12 12

9 LTG 128 -- -- 20 0 A 0 A 20 -- -- UH-21 10

7 LTG 101-105, 116-127 1/2" #12 20 0 A 0 A 20 -- -- UH-15 8

5 0 A 0 A 20 -- -- UH-14 6

3 0 A 0 A 20 -- -- UH-17 4

PANEL 1LA -- -- 20

0 A 0 A 20 -- -- UH-11 2

CKT

NO. LOAD DESCRIPTION

COND

SIZE

WIRE

SIZE

BKR

TRIP

A B C A B C

BKR

TRIP

WIRE

SIZE

COND

SIZE LOAD DESCRIPTION

CKT

NO.

150 AMP BUS 150 A MLO 480/277 Wye VOLTS 3PH, 4W, SN, 60HZ MIN. 35 KAIC SURFACE

PANEL 1HB SCHEDULE

TOTAL CONNECTED AMPS: A: 37.4 B: 43.6 C: 35.9

41 SPACE -- -- -- -- -- -- -- -- SPACE 42

39 SPACE -- -- -- -- -- -- -- -- SPACE 40

37 SPACE -- -- -- -- -- -- -- -- SPACE 38

35 SPACE -- -- -- -- -- -- -- -- SPACE 36

33 SPACE -- -- -- -- -- -- -- -- SPACE 34

31 SPACE -- -- -- -- -- -- -- -- SPACE 32

29 SPACE -- -- -- -- -- -- -- -- SPACE 30

27 RECEPT 117B 1/2" #12 20 6 A -- -- -- -- SPACE 28

25 REC 117A, 118B 1/2" #12 20 5 A -- -- -- -- SPACE 26

23 9 A 0 A 20 DOCK LEVELER CONTROLS 24

WSHP-1, RM 117A 1/2" #12 20

9 A 0 A 20 -- -- REC ELEV #4 PIT 22

19 ANNUNCIATOR PANEL -- -- 20 0 A 0 A 20 -- -- REC ELEV #3 PIT 20

17 10 A 0 A 20 -- -- REC 101, 102, 105 18

OU-4 1/2" #12 20

10 A 0 A 20 -- -- REC NSEC STORAGE 118 16

13 15 A 0 A 20 -- -- REC NSEC STORAGE 118 14

OU-3 1/2" #10 30

15 A 0 A 20 -- -- REC CORR 118, STOR 126 12

9 15 A 2 A 20 #12 1/2" REC FIRE PUMP 119 10

OU-2 1/2" #10 30

15 A 6 A 20 #12 1/2" RM 118A, 121 REC 8

5 7 A 0 A 20 -- -- REC ELEC 122 6

OU-1 1/2" #10 30

7 A 0 A 20 -- -- REC ELEC 123 4

1 EWC -- -- 20 0 A 0 A 20 -- -- REC ELEC 124 2

CKT

NO. LOAD DESCRIPTION

COND

SIZE

WIRE

SIZE

BKR

TRIP

A B C A B C

BKR

TRIP

WIRE

SIZE

COND

SIZE LOAD DESCRIPTION

CKT

NO.

100 AMP BUS 100 A MCB 208/120 Wye VOLTS 3PH, 4W, SN, 60HZ MIN. 10 KAIC SURFACE

PANEL 1LB SCHEDULE

TOTAL CONNECTED AMPS: A: 0.1 B: 0.0 C: 0.0

29 SPACE -- -- -- -- 0 A 20 -- -- SPARE 30

27 SPACE -- -- -- -- 0 A 20 -- -- SPARE 28

25 SPACE -- -- -- -- 0 A 20 LIGHTING 26

23 SPACE -- -- -- -- 0 A 20 -- -- LTG STAIR 6 24

21 SPACE -- -- -- -- 0 A 20 -- -- LTG STAIR 5 22

19 SPACE -- -- -- -- 0 A 20 -- -- LTG STAIR 4 AND ELEV CAB 20

17 0 A 0 A 20 #12 1/2" LTG STAIR 3 AND ELEV CAB 18

15 0 A 0 A 20 -- -- LTG STAIR 2 16

JOCKEY PUMP -- -- 20

0 A 0 A 20 -- -- LTG STAIR 1 AND ELEV CAB 14

11 0 A 0 A 20 -- -- EMERG LTG 106-115 12

9 0 A 0 A 20 -- -- EMERG LTG 101-105, 116-127 10

PANEL E-2HC -- -- 20

0 A 0 A 20 -- -- EMERG LTG 128 8

5 0 A 0 A 6

3 0 A 0 A 4

PANEL E-2HB -- -- 20

0 A 0 A

20 -- -- PANEL E-1L VIA XFMR E-1T

CKT

NO. LOAD DESCRIPTION

COND

SIZE

WIRE

SIZE

BKR

TRIP

A B C A B C

BKR

TRIP

WIRE

SIZE

COND

SIZE LOAD DESCRIPTION

CKT

NO.

125 AMP BUS 125 A MCB 480/277 Wye VOLTS 3PH, 4W, SN, 60HZ MIN. KAIC SURFACE

PANEL E-1H SCHEDULE

A REFER TO SHEET E-001 FOR GENERAL ELECTRICAL NOTES.

B PROVIDE ALL ELECTRICAL DEMOLITION WORK NECESSARY TO INSTALL

NEW WORK. REROUTE AND RECONNECT CIRCUITS (POWER AND

TELECOMMUNICATIONS) THAT WILL REMAIN IN USE, BUT INTERFERES WITH

NEW CONSTRUCTION. REMOVE ALL WIRING FROM ABANDONED CONDUITS

AND DISCONNECT FROM ALL POWER SOURCES.

C ALL EXISTING CONDUITS THAT WILL NOT BE REUSED MUST BE REMOVED.

ONLY CONDUITS IN WALLS THAT ARE TO REMAIN AND THAT DO NOT

INTERFERE WITH NEW WORK MAY BE ABANDONED IN PLACE.

D ALL MATERIALS REMOVED UNDER DEMOLITION SHALL BECOME THE

PROPERTY OF THE CONTRACTOR AND MUST BE REMOVED COMPLETELY

OFF SITE.

E CIRCUITS SHOWN ARE BASED ON FIELD AND DRAWING INVESTIGATIONS.

VERIFY ALL CIRCUITS PRIOR TO DEMOLITION.

F REFER TO ARCHITECTURAL SHEETS FOR EACH ROOM UNIT TYPE.

G CONDUIT AND WIRING FEEDING DEVICES, LIGHTING FIXTURES, AND

EQUIPMENT CONNECTIONS LOCATED OUTSIDE OF SECURE BOUNDARY

MUST NOT BE RUN THROUGH SECURE BOUNDARY. ROUTE CONDUIT AND

CABLES AROUND SECURE BOUNDARY FROM SOURCE PANEL.

H SEE SHEET EP102 FOR PANEL LOCATIONS.

1 CIRCUIT BREAKER PRESERVED DURING DEMOLITION AND RECONNECTED.

SEE DEMOLITION, LIGHTING, AND POWER PLANS FOR DETAILS. PROVIDE

CONDUIT AND WIRE TO MATCH EXISTING IN ACCORDANCE WITH NEC.

2 CIRCUIT DISCONNECTED DURING DEMOLITION AND RECONFIGURED. SEE

DEMOLITION, LIGHTING, AND POWER PLANS FOR DETAILS. PROVIDE

CONDUIT AND WIRE SIZED TO MATCH EXISTING IN ACCORDANCE WITH

NEC.

3 PROVIDE CIRCUIT FOR POWER/LIGHTING AS INDICATED. PROVIDE

CONDUIT AND WIRING AS INDICATED. SEE LIGHTING AND POWER PLANS

FOR DETAILS.

GENERAL SHEET NOTES

KEYNOTES# (THIS SHEET ONLY)

AUDIO/VISUAL

ICIC INTERCOMM

MICMIC MASTER INTERCOMM STATION

SECURITY

SECURITY CAMERA

CARD READERCR

BALANCE MAGNETIC SWITCHBMS

DOOR PROP ALARMA

DOOR STRIKEDS

MOTION SENSORMS

MAGNETIC LOCKML

JUNCTION BOX. MINIMUM 4" SQUARE X 2 1/8" SIZE PER NEC.J

TELEPHONE/DATA

TELEPHONE OUTLET. MOUNT 18" AFF. UON.

COMBINATION VOICE/DATA OUTLET. MOUNT 18" AFF. UON.

DATA OUTLET. MOUNT 18" AFF. UON.

CONDUIT, AND RACEWAY

LADDER RACK CABLE TRAY, SIZE AND TYPE AS INDICATED.

WIRE BASKET CABLE TRAY, SIZE AND TYPE AS INDICATED.

CONDUIT TURNED DOWN

CONDUIT TURNED UP

GENERAL

DEMOLITION AND NEW WORK NOTE - REFER TO "DEMOLITION

NOTES" AND "NEW WORK NOTES" FOR EACH SHEET

# SPECIALTY NOTE - REFER TO "SPECIALTY NOTES" FOR EACH SHEET

#. GENERAL NOTE - REFER TO "GENERAL NOTES" FOR EACH SHEET

OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS

NEW OR PROPOSED FOR CONSTRUCTION, UON.

OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS

EXISTING TO BE REMOVED-DEMOLISHED, UON.

OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS

EXISTING TO REMAIN, UON.

NEW TO EXISTING CONNECTION

REMOVE TO THIS POINT

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

N A

V A

L S

T A

T

IO

N

N O

R F

O L K

V

A

AS NOTED

T-001

T E

L E

C O

M M

U N

IC

A

T

IO

N S

S Y

M B

O L S

L E

G E

N D

A

B B

R E

V

IA

T

IO

N S

A

N D

N O

T E

S

FVP

12,951,012

BMN BMN

07/14/2026

E N

T R

A N

C E

A T

N O

R T

H E

A S

T L

O A

D

IN

G D

O C

K

DAS/SAR

1845266

N/A

N O

R F

O L K

V

IR

G

IN

IA

N A

V A

L S

T A

T

IO

N

J. MILLER, PE

CJM

M

ID

L A

N T

R

O

IC

C N

O R

F O

L K

B U

IL

D

IN

G

X -1

Approved by Ron Couture, Program Manager, with

MSC, via Email.

GENERAL NOTES

GENERAL DEMOLITION NOTES

TELECOMMUNICATIONS LEGEND

CONSTRUCTION NOTES

ABBREVIATIONS

AFF ABOVE FINISHED FLOOR

BFG BELOW FINISHED GRADE

C CONDUIT

EA EACH

EXIST EXISTING

GFCI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED

GFGI GOVERNMENT FURNISHED, GOVERNMENT INSTALLED

QU QUANTITY

REQ'D REQUIRED

RM ROOM

SHT SHEET

T TELEPHONE

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

1 PROVIDE A MINIMUM OF 2 WEEKS NOTICE OF POWER OUTAGES TO

ACTIVITY AND GOVERNMENT OFFICIAL.

A REFER TO SHEET T-001 FOR GENERAL NOTES.

B REFER TO SHEET T-501 FOR TELECOMMUNICATION DETAILS.

C ALL TELEPHONE/DATA WORK MUST BE COORDINATED WITH LOCAL IT

GROUP AND ACTIVITY VIA THE CONTRACTING OFFICER PRIOR TO

ORDERING MATERIALS. COORDINATE TELECOMMUNICATION OUTLET

NOMENCLATURE…