This document is a Standard Form 30 (SF-30) Amendment 0007 for Solicitation Number N4008525R2511, a Design-Build (DB) project to replace backup power generation systems at Naval Support Activity Hampton Roads in Norfolk, Virginia. The amendment provides clarifications and responses to pre-proposal inquiries for contractors, addressing technical specifications for electrical, fire protection, and mechanical systems across multiple rooms including UPS rooms, generator areas, and a Quonset hut.

Key details include scope modifications for fire protection systems, sprinkler installations in specific rooms, dry pipe sprinkler requirements, and clarifications on electrical equipment upgrades. The amendment specifies that contractors must provide design and installation for UPS systems, generators, switchboards, and associated infrastructure, with particular attention to security constraints within a controlled area. The proposal due date remains 15 July 2025 at 2:00 PM EDT, and the government indicates flexibility on some technical specifications, such as UPS configuration and equipment placement, while maintaining core project requirements.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

1. CONTRACT ID CODE

3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 10-83)

Prescribed by GSA

FAR (48 CFR) 53.243

FACILITY CODE

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

15C. DATE SIGNED 16C. DATE SIGNED

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

Previous edition unusable

15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

NAVFACSYSCOM MID-ATLANTIC

CONTRACTING CORE

9324 VIRGINIA AVENUE

NORFOLK VA 23511-3095

TEL: EMAIL:

BY

See Item 6

N40085

PAGE OF PAGES

1 17

2. AMENDMENT/MODIFICATION NUMBER

0007 07/07/2025

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

N40085-25-R-2511 - DESIGN-BUILD (DB), P-1401 REPLACE BACKUP POWER GENERATION UPS, PLC’S, NAVAL

SUPPORT ACTIVITY HAMPTON ROADS NORFOLK, VIRGINIA

POC: Jonathan Castillo, jonathan.y.castillo.civ@us.navy.mil

Please see continuation pages.

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as hereto fore changed, remains unchanged and in full force and effect.

9A. AMENDMENT OF SOLICITATION NUMBER

N40085-25-R-2511

9B. DATED (SEE ITEM 11)

04/23/2025

N4008525R2511

Section SF 30 – Block 14 continuation page (SF 30)

The following have been added by full text:

AMENDMENT 0006

This amendment is issued to incorporate the following:

1. Provide Continuation Sheet for Contract Specifications

2. Provide responses to Pre-Proposal Inquiries

Note: The proposal due date remains 15 July 2025 at 2:00PM EDT.

1. Continuation Sheet

RFP PART 2, SECTION 01 45 35, SPECIAL INSPECTIONS. PARAGRAPH 1.3.12 STATEMENT OF SPECIAL

INSPECTIONS (SSI):

Delete the following:

This schedule is included at the end of this specification.

RFP PART 3, SECTION 1.0 PROJECT DESCRIPTION:

Add the following paragraph to this section:

This facility that this project supports is a secure “controlled area” with a security perimeter wall/boundary. The areas of this project scope such as the UPS room, the UPS battery room, the generator control switchgear room, substation 1 room, generator 1 and generator 2 room, the Quonset Hut associated with generator 3 and substation 2, and mechanical room 159 are outside this perimeter boundary. The Contractor must not add a new penetration through this existing perimeter security wall without the explicit permission from the Activity and NAVFAC. The Contractor and their DORs must design the scope of this project in such a way as to leave this perimeter secure wall intact and coordinate all existing penetrations in a manner to maintain their security integrity and characteristics. Provide all necessary shielding, grounding, power filters, dielectric fittings, signal filters to maintain the necessary and applicable security features of UFC 4-010-05. Any fire protection water may be procured from mechanical room 159 and the fire alarm and wet pipe sprinkler lines must not penetrate the secure boundary when routed to the areas under this project scope. Any work or investigation associated from this project must be arranged in advance. The Contractor and their DORs/designers must be always escorted within the secure controlled area of the facility. Contractor must coordinate all work inside and outside the controlled area with the site security manager.

2. Pre-Proposal Inquiries

PPI # Page Section Paragraph Question Responses

PDF 31,

39, 60, 61, 73, 83, 203, 210, 237, 239, 245, 261, 309, 359, 367, 381 of

RFP:

Part Two - General Requirements Part Three - Project Program

Section 01 33 10.05 20 Design Submittal Procedures, Part 1 General, sub-part

1.12 Record

Drawings, par. 1.12.1 DD for 1354, d.

Interim DD form 1354, pg 13.

Section 01 78 00 Closeout Submittals, "These sections state that the projected is to be designed and construction in accordance with UFC 1- 200-02 High Performance and Sustainable Building (HPSB) Requirements and the checklist(s) to be submitted and Third Party Certification be provided, if applicable .

Please bid per the RFP.

sub-part 1.4 Submittals, SD-11,

pg. 5., Part 3 Execution, sub-part

3.5 Real Property

Records, par. 3.5.2 Completed DD form 1354, pg. 12.

2.0 Project

Objectives, 2.3 Project Specific Priorities, 2.3.1 Sustainable Design and Construction

UFC 1-200-02 Table 1-1 Building Compliance Requirements and Thresholds states that for Guiding Principles Compliance Tracking and Reporting the following conditions are to be met.

for a comprehensive replacement in an existing building that is ≥10,000 GSF, with total cost >$3M and 50% or more Estimated Replacement Cost (ERC).

Is the project area greater than or equal to 10,000

SF?

Is the estimated construction cost greater than $ 3.0M?

Is the estimated construction cost 50% or more than the Estimated Replacement Cost (ERC) [of the building/facility]?

Is Third Party Certification required?

N/A

N/A N/A The RFP makes no mention of UFC 3-201-01 Civil Engineering.

Chapter 2 Site Design 2-

1.2 Flood Hazard Planning

and throughout has criteria for determining the flood hazard and risk reduction.

Can the government provided the flood hazard data for the site and what if any flood mitigation measures are required of this project?

This information is unable to be provided. Please bid per the RFP.

PDF 305

of 448

Part 3, Chapter 6 ESR, D40 Fire Protection, D4010 Fire alarm and Detection Systems the RFP indicates to “Survey the existing system and provide calculations for the capacity of notification and audio signals.”

Does the government have full fire alarm system as-builts to support this investigation of the existing system and determine what current capacity of system is?

No additional files are able to be provided.

PDF 306

of 448

Part 3, Chapter 6 ESR, D40 Fire Protection, D4040 Sprinkler systems the RFP indicates to provide dry pipe sprinkler

Does the government have any proposed locations to provide the nitrogen generators and dry pipe

UPS Room 199A will have space available following removal of proposed equipment.

protection within unheated areas and nitrogen generation system(s) for the associated new dry systems.

risers outside of the areas concerned of freezing planned?

Part 2, Section 01 31

19.05 20

(6) (b) Building Floor Plans

Please verify life safety code analysis and floor plans must be provided for only the three spaces identified under Part 3, section 5.0 Room Requirements as having sprinkler and FA/MNS system scope. If not, please identify extent of life safety code analysis and drawings scope.

Life Safety Code work must be provided for areas 199A, 199B, Engine gen set Controls Switchgear Room, Room 158, Gen Set 3 per the

RFP.

274, 275, 278 (of 448)

Part 3, Chapter 5.0 Room Requirements

D40 Please confirm fire alarm and sprinkler system scope is associated only with rooms 199A, 199B, and Engine Generator Set Controls Switchgear Room as indicated in the RFP. If not, please identify all spaces requiring Fire Protection scope.

Fire protection scope must be provided for rooms 199A, 199B, Engine gen set Controls Switchgear Room, Room 158, Gen Set 3, per the RFP.

Part 3, Chapter 6.0, Section D50

2 Paragraph indicates, "The purpose of this project is to update the existing UPS #1 with Batteries, UPS #2 with Batteries, Switchboard with three Generator protections and PLCs (Programmable Logic Controllers) located in PLC room…."

Where is the PLC Room?

Is it currently sprinklered?

Please identify its location on one of the drawings provided.

Location of PLC Room (Generator control switchgear) is below the second floor exit stair, immediately adjacent to RM 168, accessed only from the exterior. PLC Room is not sprinklered.

Are the equipment pads for the UPS systems in room 199A and 199B to be housekeeping pads? Should the existing floor be assumed to be a slab on grade that can adequately support the weight of the equipment and pad? If not, are structural as-builts of building available showing the floor construction so

Existing equipment pads may be reused if deemed adequate for the new equipment.

that the existing floor capacity can be determined?

B20 – Exterior Closure Quonset Hut, yet B20 is “Not Used” Page 289. Are Quonset Hut as-built drawings? Can interior and exterior photos of structure be provided that show the construction of the structure? Can the removal of the equipment be assumed to be through the end wall of the Quonset hut, or is it anticipated that the side walls (assumed bearing walls) will need to be modified for removal?

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

Attachment F “Transformer pads to be 12-inch minimum above grade.” Is it acceptable to assume that all exterior equipment pads must meet this elevation requirement? If not, please provide the required top of pad elevations in relation to adjacent existing grades.

Division 01 Please confirm NAVFAC will provide the Division 01 files shown in the RFP in a native .SEC file for inclusion into the contract documents.

Confirmed. Division 01 files will be provided to the successful awardee post award.

N/A N/A

Electrical Please Provided photos of the following:

- UPS’s o UPS #1, nameplate, batteries, overall picture o UPS #2, nameplate, batteries, overall picture o Batteries in UPS Room 199A o Batteries in UPS Room 199B

- Switchboard o Existing 3000A, 208/120V Switchboard “Main 1” in Room 158A o Overall picture, nameplate(s), main breaker(s), tie breaker(s), o UPS breakers § UPS #1 Input CB and UPS #2 Input CB (2000A

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

each, spare right now) § UPS #1 bypass CB (1200A) and UPS #2 bypass CB (1600A)

- Panelboard o Existing 2000A, 208/120V panelboard “MDP-2” in Room A115 o Overall picture, nameplate(s), main breaker(s), tie breaker(s) o Breaker feeding ATS in Generator #3 room (Quonset Hut)

N/A N/A

Electrical Please Provided photos of the following:

Generators o Generator #1 nameplate, overall picture o Generator #2 nameplate, overall picture o Generator #3 nameplate, overall picture

- Quonset Hut (Generator #3 Room) o Overall interior and exterior pictures o Transformer § T2, 750kVA, 34.5kV- 208/120V in Quonset Hut o Panels § All panels in the Quonset hut, inc. panel schedule cards, nameplates, breakers § This includes panelboard

“DU”

o Lights § Pictures of light fixtures, switches, emergency lights o ATS

§ 2000A ATS

o Duct Bank § Existing two-way 5” duct bank which will feed the Secondary Unit Substation from Generator #3 room (Quonset Hut) existing floor box.

§ Existing floor box in Generator #3 room (Quonset Hut) which will be used for splicing existing 35 kV cable from demolished transformer “T2”

Photos are unable to be provided at this time. If requested, photos can be

N/A N/A

Mechanical Please Provided photos of the following (see also attached drawing mark-up):

General Interior and Exterior photos as indicated by the arrows on eh attached drawing.

Roof Top Mechanical Equipment and Name Plate Data Louvers and Generator Set Exhaust on the Quonset Hut.

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

All 01 45 25

N/A Please confirm the spec is relevant and required.

SOW appears that quality and integrity could be accomplished through testing and inspection managed by the QCM.

Spec Section 01 45 25 is not found. Bid per the RFP.

Att. F modified the Part 3, chapter 6 ESR D50 states:

“Provide a selective coordination study, Fault current analysis, and Arc Flash Hazard report for all new equipment to include each subpanel directly connected to this new work…” This would exclude any motor contributions that are not connected to new equipment or existing equipment directly connected to new equipment. Please confirm that studies will not include fault current contributions from large motor loads. Please clarify study requirements.

The DOR needs to perform the calculations in accordance with UFC 3-501- 01, "Electrical Engineering" paragraph 3-2.2 and all applicable subparagraphs.

The DOR will need to examine the site and any available drawings to a degree to support the calculations.

Att. F Part 3, chapter 6 ESR D509002 states:

“Provide a new circuit breaker in the refurbished paralleling gear for a connection point for a portable load bank.” Load banks are typically provided for systems where required periodic load testing cannot be achieved with the connected building load.

The benefit of multiple

Provide the work as described in the RFP.

paralleled generators is that you can have 1 (of the

3) units very loaded up, to satisfy the 50% and 75% minimum load, without needing to supplement with a load bank. Please confirm the requirement to provide the likely unnecessary load bank connection. If still deemed necessary, please provide desired size for connection box (e.g. 2000A, 5000A).

42 Att. F Part 3, chapter 6 ESR D509002: There is no mention of replacing the existing draw-out breakers in the switchboard. They are over 20 years old, shows signs of rust and no evidence of preventative maintenance being performed recently. Please confirm existing switchboard breakers are to be reused as-is.

Refurbished generator switchgear circuit breakers must be cleaned and conditioned per ATT F.

Existing switchboard circuit breakers of sub 1 are to be reused per the

RFP.

43 The drawings in part six clearly don’t accurately reflect the current electrical distribution system. (e.g. they don’t show the connection of all 3 generators and utility to the generator paralleling switchboard). We assume the DOR who prepared the RFP must have developed an accurate one-line of the facility in order to write an accurate RFP. Please provide that information.

The Contractor must have their DOR develop a design that complies with requirements provided in this RFP.

274-275, RFP Part 3, “Room Requirements”, specifies fire protection system modifications in rooms 199A and 199B, and in the Engine Generator Set Controls Switchgear Room. Fire protection system modifications are not specified for the Generator #3 room, Room 158, or Room 158B.

Please specify any fire protection system scope outside rooms 199A, Provide Sprinkler/fire alarm within rooms 199A, 199B, Engine gen set Controls Switchgear Room, Room 158, 158B, Gen Set 3.

Extend sprinkler Riser in rm

159. Provide Dry pipe valve w/nitrogen charging system within rm 159 off of Sprinkler main. Provide dry pipe sprinkler coverage for other unheated areas.

Provide auxiliary drains as required to route dry piping on bldg. exterior.

199B, and the Engine Generator Set Controls Switchgear Room.

RFP requires project to modify existing fire protection systems. Are as-built drawings of existing fire alarm and sprinkler systems available?

As-built drawings are not available for this facility for Fire alarm or Sprinkler systems, all available drawings are provided in

RFP.

RFP Part 3 §D50 describes Base Bid, Bid Option i, and Bid Option ii scope for Electrical work. Please delineate Fire Protection system scope for Base Bid and each Bid Option.

Bid option work follows area of work of other disciplines.

RFP Part 3 §D4010 requires Contractor to survey existing fire alarm system “and provide calculations for capacity of notification and audio signals.” Please specify minimum spare capacity that must be maintained for existing fire alarm notification circuits and batteries.

Provide minimum 10% spare capacity of existing circuits.

RFP Part 3 §D4010 requires modification of “existing addressable fire alarm/mass notification system”. Drawings in RFP Part 6 refer to horn/strobes (i.e., not mass notification). Please clarify whether project includes providing or modifying mass notification system components.

Existing Fire alarm system is EST and horn based fire alarm only. There is no mass notification component connected to the fire alarm system within the building at this time.

RFP Part 3 §D509001 requires firestopping of penetrations at fire-rated walls, partitions, and floors. To provide a basis for firestopping cost estimate, please identify fire-rated construction within areas of work.

Bid per the RFP.

01 45 35 Is the Qualified Fire Protection Engineer (QFPE), Fire Protection Designer of Record (FPDOR), and/or the Registered Fire Protection Engineer (FPQC) also allowed to serve as the

Permitted if qualified.

firestop Special Inspector required by spec 01 45 35?

01 45 35 RFP Part 2 Specification 01 45 35 states that a Schedule of Special Inspections (SSI), which lists required Special Inspections, “is included as an attachment to” the spec.

The SSI doesn’t appear to have been included in the RFP; please clarify extent of Contractor’s responsibility for developing SSI.

Please see Continuation Sheet provided with Amendment 0007.

The Government anticipates a structural inspection with work associated with structural modifications to the Quonst Hut for demolition and new work according to your DOR and design.

13526 1.8.5 Please verify that a 40-hour contract safety awareness course for this project will not be required. If the 40 hour safety awareness course is required, please provide a list of required attendees (i.e. only supervisors and foremen, etc.). This is to ensure compliance with the specification.

This will be addressed with the successful awardee post award.

6 A10 Please note that the bid options for the foundations under the engineering systems requirements do not appear to match the bid form provided. The bid form bid option item No 1 states to replace emergency generator #3.

Bid option I on page 281 of the design requirements has the contractor designing/installing foundations for the generator controls switchgear; bid option II has the contractor designing/installing foundations for the switchboard main 2, transformer and medium voltage switch gear primary disconnect. Please provide a revised design requirement matching the bid form.

The only new pads would be for equipment provided under this contract, including the generator in bid option (i) and the LFMV Transformer in bid option (ii). Pads for the switchboard in bid option

(ii) would be up to the Contractor's DOR design.

Existing pads may be reused if feasible. The Government does not anticipate new pads for the UPS equipment, UPS battery cabinets, or generator control switchgear. The Contractor must provide required pads for all equipment per the design. The Government also anticipates a pad for the generator control switchgear load bank connection box, but the exact arrangement would be up to the equipment the DOR selects and the equipment the Contractor procures.

6 D50 Please describe the software that the

Bid per the RFP.

contractor is to include with the new UPS or a basis of design so the contractor may provide the proper software for the UPS units.

6 D50 Please verify that the new network connection from the first floor to the large penthouse communication link, as required per page 307 of the design documents, is to be included in bid option 2. If not, please specify where the cost for this item should be included.

Bid per the RFP.

6 D50 Please verify that the contractor will not be required to provide the temporary generator until the two UPS are to be removed by the contractor.

Bid per the RFP.

6 D50 If the owner requires the temporary generator before the contractor has the replacement equipment on-site, please provide a date that the contractor is to include for the start of the rental period for the temporary generator.

Bid per the RFP.

6 D50 Please provide the standards for the new lighting that will be required for this project. If this cannot be provided, please verify that the contractor will match existing only update to new LED.

Bid per the RFP.

6 D40 Please define the area of work as the contractor is to include wet and dry pipe automatic sprinkler protection and fire alarm modifications in the area of work. Please verify that the contractor will be required to include modifications to the entire building, or only the areas in which work is being performed (i.e. Rooms 199A, 199B, 158, 158 B and the Quonset hut).

Sprinkler system work is limited to the exterior accessed rooms within the scope of work and supply connection within room 159.

6 D50 Please provide make/model & S/N of existing equipment that is to be removed or modified.

This information is unable to be provided, please bid per the RFP.

6 D50 Please verify that the new UPS are to be top-fed.

That is not a requirement of the RFP. Any usable conduits below the slab may be reused if proven.

6 D50 For custom UPS systems such as this manufacturing in the US is limited. Please advise on Buy America Requirements and if they can be waived for the UPS equipment as it is proprietary.

The Government cannot waive the procurement policy, but equivalent UPS configurations will be accepted during the design based upon availability. The Government can accept an N+1 configuration where N is 150-160 kVA output using at least 2 modules in a capacity of 225kVA to 240kVA. Contractor takes all responsibility to make all circuit connection using a minimum of 2 feeders per module + external maintenance bypass.

Part 2, Section 01 31

19.05 20

(6) (b) Building Floor Plans

Please verify life safety code analysis and floor plans must be provided for only the three spaces identified under Part 3, section 5.0 Room Requirements as having sprinkler and FA/MNS system scope. If not, please identify extent of life safety code analysis and drawings scope.

Confirmed. Provide LS code analysis for area of work.

274, 275, 278 (of 448)

Part 3, Chapter 5.0 Room Requirements

D40 Please confirm fire alarm and sprinkler system scope is associated only with rooms 199A, 199B, and Engine Generator Set Controls Switchgear Room as indicated in the RFP. If not, please identify all spaces requiring Fire Protection scope.

Sprinkler system work is limited to the exterior accessed rooms within the scope of work and supply connection within the building, rooms 199A, 199B, Engine gen set Controls Switchgear Room, Room 158, Gen Set 3, Sprinkler Riser is located in room 159, see drawing F- 102 and C-2 for water service entry.

Part 3, Chapter 6.0, Section D50

2 Paragraph indicates, "The purpose of this project is to update the existing UPS #1 with Batteries, UPS #2 with Batteries, Switchboard with three Generator protections and

UPS sprinkler work is part of the Scope of Work. The UPS room is currently a non-sprinklered space.

PLCs (Programmable Logic Controllers) located in PLC room…." Please verify if the UPS room is currently sprinklered. If it is, please provide the type of the current fire protection located in the UPS room.

Part 3, Chapter 6.0, Section D50

2 Please verify if the new sprinkler system required for the UPS room will need to be a dry-type system. If not, please specify what system will be required.

The contractor is to provide Dry Sprinkler protection in UPS room 199A and 199B even though it is heated.

Part 3 - Chapter 6 / ESR D50

D50 System Description

There is a requirement to provide reconditioned breakers for switchboard "Main 1" should the breakers fail and not be able to be closed after opening. Please refurbished breakers available for this gear. If not, please provide the make/model of the existing breakers that require reconditioning.

Bid per the RFP.

Part 3 - Chapter 6 / ESR D50

D50 System Description

If "Main 1" is old equipment in poor condition or with problems finding spare parts, please verify that the contractor will not be required to replace "Main 1". It may be in the best interest to replace "Main 1", but the documents do not state that this is a requirement.

Bid per the RFP.

Part 3, Chapter 6.0, Section D50

Construction - Base Bid

Please verify that the existing Generator #3 winding pitch matches the winding pitch for Generators #1 and #2. If not, please provide the winding pitch for all generators.

This information is unable to be provided, please bid per the RFP.

6 D50 Please provide the runtime requirement for the new UPS system.

The RFP requires each 250 kVA module to have its own independent 15-minute battery system.

274, 275, 278 (of 448)

Part 3, Chapter 5.0 Room Requirements

D40 Please provide the existing fire alarm panel make and model.

The existing fire alarm system is an EST system with horns and strobes for notification. See Appendix A drawings for location.

274, 275, 278 (of 448)

Part 3, Chapter 5.0 Room Requirements

D40 Please provide the existing fire alarm panel location of where the contractor will need to tie into the system.

If this cannot be provided, please provide the approximate length of conduit/wire that will be required to reach the existing fire alarm panel location.

The addressable fire alarm circuit and notification circuit is available in UPS room 199B. FACP location shown on Appendix A drawings.

274, 275, 278 (of 448)

Part 3, Chapter 5.0 Room Requirements

D40 Please provide ceilings types that the contractor will be required to remove and replace.

Bid per the RFP.

274, 275, 278 (of 448)

Part 3, Chapter 5.0 Room Requirements

D40 Please provide the access requirements if the contractor will be required to enter the SCIF building.

Please verify that the contractor will not need to pay for any escorts, extra passes, background checks, etc. if the contractor will need to enter the SCIF building for access for any tie-ins required.

A free escort will be provided; however, the contractor must provide an access request 10 working days before the access is needed.

121 Please provide exterior photographs of the north, south, and west sides of the Quonset hut.

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

122 Please provide exterior photos of north, south, and west side of generator paralleling control & Switchboard room.

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

123 Please provide exterior photos of north, south, and west side of room 158 & 158B. (Main 1 Room)

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

124 Please provide interior photos of room 158 & 158B. (Main 1 Room)

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

125 Please provide exterior photos of north, south, and west side of UPS room.

(Room 199A & 199B)

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

126 Please provide interior photos of Quonset hut.

Photos are unable to be provided at this time. If requested, photos can be

127 Please provide interior photos of generator paralleling control & switchboard room.

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

128 Please provide interior photos of UPS room (Room 199A& 199B)

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

129 Please provide interior photos of room A115.

(MDP-2 Room)

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

130 Please provide photos of all equipment name plates, panel schedules, breaker name plates and Panel ID.

(Generator 3, T2 sub-station, Main 2, MDP -2, Generator paralleling control switchboard, Sw- 233, T1 sub-station, Main 1 Panel EM, MDP 1978, DP-2, UPS 1 & 2, UPS 1

& 2 battery cabinets, Panel PU, Panel UDP, any UPS bypass switches and disconnects etc.)

Photos are unable to be provided at this time. If requested, photos can be provided post award to the successful awardee.

131 What is the fire alarm manufacturer in building

NH139?

The existing fire alarm system is an EST system with horns and strobes for notification. See Appendix A drawings for location.

132 Please confirm that NH139 & NH-94, there is existing copper or fiber optic cable to connect the remote UPS monitoring systems.

Bid per the RFP.

133 Can you please provide As-builts for Generator paralleling control switchboards? This does not appear in the RFP drawings?

This information is unable to be provided, please bid per the RFP.

134 Please confirm 1 concrete pad will be utilized for both 250KVA UPS cabinets?

Bid per the RFP.

135 Is an environmental permit need for option 1, removal install new generator 3?

Yes.

136 Does the temporary generator require auto or manual controls?

Please bid per the RFP. See Attachment F.

137 Do we need a temporary generator for removal and reinstallation of UPS system?

Please bid per the RFP. See Attachment F.

138 The RFP appears to not have any requirements for communications systems.

However, inside the existing generator paralleling control and switchboard room, located under the steps there is a communications network cabinet. Please confirm that this is not needed.

Bid per the RFP.

139 Inside the existing generator paralleling control and switchboard, there is a small standalone UPS, we assume this is for the communication in the paralleling gear. Please confirm this is not required.

The equipment is supporting PLCs that currently do not work correctly and would need to be removed upon the refurbishment process.

140 2 Part 3, Chapter 6, ESR D50 & D509002

1 Attachment F RFP states to “Provide a new circuit breaker in the refurbished paralleling gear for a connection point for a portable load bank”. There is not room in the existing line-up to provide this circuit breaker. Because of this, a new section would have to be provided at 22” width. There are concerns that the new switchgear section will not fit in the existing room and space needs to be confirmed by others. Please advise on the allowable space.

The circuit breaker would not need to be draw-out for the load test if that saves room. Alternate means and methods like tapping the bus and putting the circuit breaker in the adjacent outdoor connection box would be acceptable.

141 We are requesting clarification regarding the specified 250kVA Uninterruptible Power Supply (UPS) at 208 Volts. After reaching out to major UPS manufacturers, we have confirmed that no standard, native 208V UPS systems are available at

480V is not available in the building. Equivalent UPS configurations will be accepted during the design based upon availability.

The Government can accept an N+1 configuration where N is 150-160 kVA output using at least 2 modules in a capacity of 225kVA to 240kVA. Contractor takes this kVA rating. At 250kVA, the industry standard offering is typically 480 Volts.

all responsibility to make all circuit connection using a minimum of 2 feeders per module + external maintenance bypass.

142 Currently there is no room for the Load bank breaker they have asked for in the existing Paralleling Switchgear. Could we use an outdoor tap box in its place? Would this need a dedicated breaker to feed it or could it be tapped on the bus?

Please see PPI Response #140.

143 The existing units have a different pitch from what the new unit will have due to the age, in order to, correct this we need to install a DPNL and associated equipment to do so we need to know the existing load between the phase to neutral. Please advise.

Bid per the RFP. The voltage is known, but the unbalanced load phase to neutral may vary. The Contractor's equipment vendor and DOR can verify additional information during the design phase.