N40085-09-D-5027-0005-SOF Canopy.pdf
PDF 4 MB Posted
- Attached to
- REPLACE ECP CANOPY, BLDG 380, DAM NECK ANNEX
- Solicitation number
- N4008525R0131
About this file
This set of architectural and engineering documents details the design for a Special Operations Forces (SOF) Perimeter Security and Main Entry Improvements project at NAS Oceana Dam Neck Annex in Virginia Beach, VA. The project involves constructing a gate canopy with a complex structural design featuring space frame roof framing, concrete columns and foundations, and integrated electrical and storm piping systems. The canopy has a distinctive L-shaped configuration spanning approximately 126 linear feet, supported by multiple concrete columns with 8'x8' and 7'x7' footings.
Key technical specifications include a space frame roof structure with specific design loads, steel deck roofing, multiple roof drains, lightning protection, and comprehensive lighting infrastructure. The design incorporates 14 canopy light fixtures, traffic controller areas, electrical switchbanks, and green/red light signaling systems. Structural elements are designed with precise engineering requirements, including seismic considerations, wind load calculations, and compliance with building codes. The project appears to be a comprehensive security and entry control infrastructure improvement for a military installation, with detailed attention to structural integrity, electrical systems, and functional design.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
S Y M
D A T E
A P P R
D E S C R
IP
T
IO
N
AS NOTED
N40085-12-R-4515
SEAL
A/E INFO
D E P A R T M E N T O F T H E N A V Y
N A V A L F A C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D
V
IR
G
IN
IA
B E A C H , V A
N A S O C E A N A
N A V A L
FA
C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D M
ID
-A
TL
A N
TI
C
V
IR
G
IN
IA
B E A C H , V A
D A M N E C K A N N E X
A
B
C
D
PHONE: (757) 474-0612 FAX: (757) 474-0919
VIRGINIA BEACH, VIRGINIA, 23464
748 LORD DUNMORE DRIVE, SUITE 101
NRW
CONSULTING STRUCTURAL ENGINEERS
C :\A L O C A L R E V
IT
F
IL
E S \1 S O F V
IS
IT
O R C E N T E R N R W S tru ct ur al _c om pu te r2 5.
rv t
/1 7/ :2 0:
P M
S001G
P S O F P E R
IM
E T E R S E C U R
IT
Y
M A
IN
E N T R Y I M P R O V E M E N T S S O F
G E N E R A L N O T E S
MLM KBF KBF
1174158
Dec. 20, 2013
12655869
GENERAL:
1. ALL WORK SHALL COMPLY WITH THE CODES LISTED
BELOW AND IN THE SPECIFICATIONS.
2. THE CONTRACTOR SHALL VERIFY ALL DRAWINGS FOR
COORDINATION BETWEEN TRADES, LOCATE SLOTS, SLEEVES
AND TRENCHES AS REQUIRED FOR MECHANICAL TRADES.
PROVIDE AND INSTALL ANCHORS, INSERTS, HANGERS, ETC. AS
REQUIRED FOR VARIOUS TRADES.
3. SUBMIT SHOP DRAWINGS OF REINFORCEMENT DETAILS,
STRUCTURAL STEEL, ETC. FOR APPROVAL BEFORE
PROCEEDING WITH THE WORK. THE CONTRACTOR SHALL
CHECK ALL DIMENSIONS AND ACCEPT FULL RESPONSIBILITY
FOR DIMENSIONAL CORRECTNESS.
4. UNDER NO CIRCUMSTANCES SHALL REPRODUCTION OF
CONTRACT DRAWINGS BE USED AS SHOP DRAWINGS.
5. PROVIDE ALL TEMPORARY GUYING AND BRACING
REQUIRED TO ERECT AND HOLD THE STRUCTURE IN PROPER
ALIGNMENT UNTIL ALL STRUCTURAL WORK AND
CONNECTIONS HAVE BEEN COMPLETED.
6. LOADING APPLIED TO THE STRUCTURE DURING THE
PROCESS OF CONSTRUCTION SHALL NOT EXCEED THE SAFE
LOAD-CARRYING CAPACITY OF THE STRUCTURAL MEMBERS.
THE LIVE LOADINGS USED IN THE DESIGN OF THIS STRUCTURE
ARE INDICATED IN THE “DESIGN CRITERIA NOTES”. DO NOT
APPLY ANY CONSTRUCTION LOADS UNTIL ALL STRUCTURAL
FRAMING IS PROPERLY CONNECTED TOGETHER AND UNTIL
ALL TEMPORARY BRACING IS IN PLACE.
7. TYPICAL DETAILS AND GENERAL NOTES APPLY TO ALL
PARTS OF THE JOB EXCEPT WHERE SPECIFICALLY DETAILED
OR NOTED OTHERWISE.
8. STRUCTURAL DRAWINGS SHOW ONLY THE BASIC
STRUCTURAL FRAMING. REFER TO ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DRAWINGS FOR NON-
STRUCTURAL ITEMS WHICH REQUIRE SPECIAL PROVISIONS
DURING THE CONSTRUCTION OF THE STRUCTURAL FRAME.
9. INFORM THE CONTRACTING OFFICER IN WRITING OF
ANY DEVIATION FROM THE CONTRACT DOCUMENTS. THE
CONTRACTOR SHALL NOT BE RELIEVED OF THE
RESPONSIBILITY OF SUCH DEVIATION BY THE CONTRACTING
OFFICER REVIEW OF SHOP DRAWINGS, PRODUCT DATA, ETC.
UNLESS THE CONTRACTOR HAS SPECIFICALLY INFORMED THE
CONTRACTING OFFICER OF SUCH DEVIATION AT THE TIME OF
SUBMISSION, AND THE CONTRACTING OFFICER HAS GIVEN
WRITTEN APPROVAL TO THE SPECIFIC DEVIATION.
FOUNDATION:
1. FOUNDATIONS FOR THIS STRUCTURE HAVE BEEN
DESIGNED IN ACCORDANCE WITH THE RECOMMENDATIONS IN
THE GEOTECHNICAL EXPLORATION REPORT, PREPARED BY
ECS MID-ATLANTIC, LLC AND DATED MARCH 5, 2013
2. THE ENTIRE STRUCTURE SHALL BE FOUNDED ON VERY
WELL COMPACTED STRUCTURAL FILL OR UNDISTURBED SOIL.
DESIGN BEARING PRESSURE = 1500 P.S.F.
3. NO FOUNDATION WORK SHALL BE INSTALLED UNTIL ALL
FOOTING WORK HAS BEEN COORDINATED WITH ADJACENT
UNDERGROUND UTILITIES, ETC. FOOTINGS SHALL BE
LOWERED WHERE REQUIRED.
4. NO UNBALANCED BACKFILLING SHALL BE DONE AGAINST
FOUNDATION WALLS UNLESS WALLS ARE SECURELY BRACED
AGAINST OVERTURNING.
5. BOTTOM OF EXTERIOR FOOTINGS SHALL BEAR A
MINIMUM OF 18 INCHES BELOW FINAL GRADE. LOWER
FOOTINGS AS REQUIRED TO MAINTAIN COVERAGE.
6. ALL EARTHWORK SHALL BE PERFORMED IN
ACCORDANCE WITH THE RECOMMENDATIONS INDICATED IN
THE GEOTECHNICAL ENGINEERING REPORT PREPARED BY
ECS MID-ATLANTIC, LLC AND DATED MARCH 5, 2013.
DESIGN LOADS
1. DESIGN LIVE LOADS USED IN THE DESIGN OF THESE STRUCTURES ARE AS
FOLLOWS:
2. UNIFORM LIVE LOADS:
SOF - CANOPY:
SLAB ON GRADE: 4" SLAB: 100 PSF
ROOF LIVE LOAD: 20 PSF
SOF - FIRING POSITION:
SLAB ON GRADE: 4" SLAB: 100 PSF
SECOND FLOOR: 50 PSF
ROOF LIVE LOAD: 20 PSF
SOF - GUARD HOUSE:
SLAB ON GRADE: 4" SLAB: 100 PSF
ROOF LIVE LOAD: 20 PSF
SOF - SENTRY BOOTH:
SLAB ON GRADE: 4" SLAB: 100 PSF
ROOF LIVE LOAD: 20 PSF
SOF - NORTH GATE SENTRY BOOTH:
SLAB ON GRADE: 4" SLAB: 100 PSF
ROOF LIVE LOAD: 20 PSF
SOF - VISITOR CENTER:
SLAB ON GRADE: 4” SLAB: 100 PSF
SLAB ON GRADE: WAREHOUSE (6" SLAB): 250 PSF
ROOF LIVE LOAD: 20 PSF
3. ROOF SNOW LOADS:
GROUND SNOW LOAD Pg = 10 PSF SNOW EXPOSURE FACTOR Ce = 1.0
SNOW LOAD IMPORTANCE FACTOR I =1.0
THERMAL FACTOR Ct=1.0 ROOF LOAD: Pf = 10.0 PSF
4. WIND LOADS:
WIND VELOCITY (3 SEC GUST) 115 MPH
IMPORTANCE FACTOR I = 1.0, BUILDING CATEGORY II
WIND EXPOSURE CATEGORY (MAIN WINDFORCE-RESISTING SYSTEM): C
WIND EXPOSURE CATEGORY (COMPONENTS AND CLADDING): C
INTERNAL PRESSURE COEFFICIENT: +/- 0.18 (ENCLOSED)
(CANOPIES: OPEN STRUCTURES)
5. SEISMIC LOADS:
SEISMIC OCCUPANCY CATEGORY II, SEISMIC USE GROUP I
IMPORTANCE FACTOR I = 1.0
Ss = .11g S1 = .05g
SOIL SITE CLASS E
SEISMIC DESIGN CATEGORY B
BASIC SEISMIC FORCE RESISTING SYSTEM:
VISITOR CENTER: INTERMEDIATE PRECAST SHEAR WALLS, R=5, Cs=0.037
CANOPY: ORDINARY REINFORCED CONCRETE MOMENT FRAMES,
R=1, Cs=.103 ALL OTHER BUILDINGS: REINF MASONRY SHEAR WALLS, R=2, Cs=0.092
ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE ANALYSIS
6. ATFP DESIGN LOADS (VISITOR CENTER):
INHABITED BUILDING - VERY LOW LEVEL OF PROTECTION
EXPLOSIVE WEIGHT 1 (UFC 4-010-02)
STANDOFF DISTANCE:
INTERIOR BLAST WALL: 81'
EXTERIOR PERIMETER WALL ( LOW ROOF): 115' @ 32 DEG INCIDENCE
EXTERIOR PERIMETER WALL ( HIGH ROOF): 125' @ 32 DEG INCIDENCE
EXTERIOR PERIMETER WALLS: 135' PERPENDICULAR TO WALL
GENERAL NOTES:
CONCRETE WORK:
1. UNLESS OTHERWISE NOTED OR DETAILED ALL CONCRETE
WORK SHALL BE IN ACCORDANCE WITH THE AMERICAN
CONCRETE CODE (A.C.I. 318) AND ITS LATEST AMENDMENTS AND
THE SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR
BUILDINGS (ACI 301).
2. ALL CONCRETE SHALL BE NORMAL WEIGHT AGGREGATE
CONCRETE HAVING A MINIMUM 28 DAY COMPRESSIVE STRENGTH
AS FOLLOWS:
WAREHOUSE SLAB: 4,000 PSI
ALL OTHER CONCRETE: 3,000 P.S.I.
CONCRETE EXPOSED TO WEATHER SHALL BE AIR ENTRAINED.
3. ALL REINFORCING SHALL CONFORM TO ASTM A-615, GRADE
60.
4. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185 AND
PROVIDED IN FLAT SHEETS. WELDED WIRE FABRIC SHALL BE
PROPERLY SUPPORTED PRIOR TO PLACING CONCRETE.
HOOKING OF MESH IS NOT PERMITTED.
5. UNLESS OTHERWISE NOTED, REINFORCING STEEL MARKED
CONTINUOUS (CONT.) SHALL BE LAPPED 48 X BAR DIAMETER AT
SPLICES. FOR LAPS AT CORNERS, REFER TO TYPICAL DETAIL.
6. ALL REINFORCING STEEL SHALL BE HELD SECURELY IN
PLACE TO PREVENT DISLOCATION DURING THE POURING
OPERATION. SLAB REINFORCING BARS SHALL BE SUPPORTED ON
HIGH CHAIRS AND BAR SPACERS OF SUITABLE DESIGN, OR
CONCRETE BLOCKS HAVING THE SAME MINIMUM COMPRESSIVE
STRENGTH OF THE CONCRETE SLAB.
7. DETAILING OF ALL CONCRETE STEEL REINFORCEMENT
SHALL BE IN ACCORDANCE WITH THE MANUAL OF STANDARD
PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES
(A.C.I. 315).
8. NO CONCRETE SHALL BE PLACED UNTIL ALL EMBEDDED
WORK HAS BEEN INSTALLED, TESTED AND INSPECTED.
9. EXCEPT AS OTHERWISE SHOWN MINIMUM PROTECTION
(CONCRETE COVER) FOR REINFORCING STEEL SHALL BE AS
FOLLOWS:
CONCRETE SURFACES CAST AGAINST SOIL: 3"
CONCRETE SURFACES EXPOSED TO EARTH OR WEATHER:1-1/2"
INTERIOR CONCRETE SURFACES: 3/4" FOR SLABS; 1-1/2” FOR
BEAMS & COLUMNS
STRUCTURAL STEEL:
1. ALL STRUCTURAL STEEL SHALL BE NEW, CLEAN AND
STRAIGHT. STEEL WIDE FLANGE SHAPES SHALL CONFORM TO
ASTM A-992, GRADE 50. ALL OTHER STEEL SHAPES SHALL
CONFORM TO ASTM 36 UNLESS OTHERWISE NOTED.
STRUCTURAL TUBES ( HSS ) SHALL CONFORM TO ASTM A-500,
GRADE B.
2. STRUCTURAL STEEL FABRICATION AND ERECTION SHALL
COMPLY WITH THE SPECIFICATIONS, THE VIRGINIA STATEWIDE
BUILDING CODE AND THE "SPECIFICATION FOR STRUCTURAL
STEEL BUILDINGS," ANSI/AISC 360-05, WITH ITS LATEST
AMENDMENTS.
3. UNLESS OTHERWISE NOTED, ALL CONNECTIONS SHALL BE
AISC TYPE 2, STANDARD FRAMED BEAM CONNECTIONS. THE
FABRICATOR IS RESPONSIBLE FOR DESIGNING ALL
CONNECTIONS. WHERE REACTIONS ARE NOT INDICATED ON PLAN,
CONNECTIONS SHALL BE DESIGNED FOR ½ OF THE TOTAL
ALLOWABLE UNIFORM LOAD FOR LATERALLY SUPPORTED BEAMS
GIVEN IN PART 3 OF THE “STEEL CONSTRUCTION MANUAL”, 13TH
EDITION. CONNECTION DETAILS SHALL BE IN ACCORDANCE WITH
AISC STANDARDS.
4. UNLESS OTHERWISE NOTED ALL SHOP CONNECTIONS
SHALL BE WELDED AND ALL FIELD CONNECTIONS SHALL BE
BOLTED. THE FABRICATOR IS RESPONSIBLE FOR THE DESIGN OF
ALL CONNECTIONS. REFER TO SPECIFICATIONS.
5. ALL HOLES REQUIRED IN STRUCTURAL STEEL MEMBERS
FOR PIPING SHALL BE SHOWN ON THE SHOP DRAWINGS AND BE
MADE IN THE SHOP. NO HOLES SHALL BE CUT IN THE FIELD
WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER OF
RECORD, AND NOTIFICATION OF THE CONTRACTING OFFICER.
6. WELDING SHALL COMPLY WITH THE "STRUCTURAL WELDING
CODE" PREPARED BY THE A.W.S., MINIMUM WELD SIZE SHALL BE
3/16" FILLET WELD, ELECTRODES SHALL BE E70XX. FOR ANGLE
CONNECTIONS WHERE WELDS ARE NOT NOTED, PROVIDE A
MININUM OF 2" OF 3/16" ON 2 SIDES OF ANGLE (4" TOTAL WELD).
7. UNLESS OTHERWISE NOTED HIGH STRENGTH BOLTS
SHALL COMPLY WITH ASTM A-325 AND ANCHOR BOLTS SHALL
COMPLY WITH ASTM A-1554 GRADE 36.
8. ALL EXPOSED LINTELS IN EXTERIOR WALLS SHALL BE
GALVANIZED.
STEEL DECK NOTES:
1. STEEL DECK SHALL CONFORM TO THE LATEST EDITION OF THE AISI
SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL
STEEL MEMBERS AND THE STEEL DECK INSTITUTE DESIGN MANUAL FOR
COMPOSITE DECKS, FORM DECKS AND ROOF DECKS.
2. ATTACH ROOF DECK TO SUPPORTS WITH 5/8” DIAMETER PUDDLE
WELDS IN ALL RIBS WHERE SIDELAPS OCCUR AND AT 12 INCHES ON
CENTER ALONG SUPPORTS. FASTEN SIDELAPS WITH #10 SELF TAPPING
SCREWS AT A MAXIMUM SPACING OF 18 INCHES.
3. WELDING SHALL BE IN ACCORDANCE WITH AWS D1.3, “STRUCTURAL
WELDING CODE - SHEET STEEL.
4. DO NOT HANG OR SUPPORT ANY LOADS FROM METAL ROOF DECK.
5. DECK SHALL BE CONTINUOUS OVER A MINIMUM OF THREE SPANS.
LIGHTGAGE FRAMING
1. ALL LIGHT GAGE FRAMING SHALL CONFORM TO THE AMERICAN IRON
AND STEEL INSTITUTE (AISI) “SPECIFICATION FOR THE DESIGN OF COLD-
FORMED STEEL STRUCTURAL MEMBERS” LATEST EDITION.
2. UNLESS OTHERWISE NOTED, ALL STUDS SHALL BE GALVANIZED.
3. ALL GALVANIZED STUDS 16 GAGE AND HEAVIER SHALL BE FORMED
FROM STEEL THAT CORRESPONDS TO THE REQUIREMENTS OF ASTM A653,
GRADE 50, WITH MINIMUM YIELD OF 50,000 P.S.I.
3. ALL GALVANIZED STUDS LIGHTER THAN 16 GAGE, TRACK, BRIDGING,
AND ACCESSORIES SHALL BE FORMED FROM STEEL CORRESPONDING TO
THE REQUIREMENTS OF ASTM A653, GRADE 33, WITH A MINIMUM YIELD OF
33,000 P.S.I.
4. FOR EXTERIOR STUD SIZES, REFER TO PLANS AND SECTIONS.
MASONRY:
1. MASONRY CONSTRUCTION SHALL CONFORM TO ACI 530 AND ACI
530.1, BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR
MASONRY STRUCTURES.
2. MASONRY BLOCK SHALL CONFORM TO ASTM C90. MASONRY
MORTAR SHALL CONFORM TO ASTM C270, TYPE S. MASONRY HAS BEEN
DESIGNED FOR A COMPRESSIVE STRENGTH OF 1500 PSI.
3. GROUT SHALL CONFORM TO ASTM C476. GROUT SHALL HAVE A
MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 2000 PSI. SLUMP AT POINT
OF PLACEMENT SHALL BE BETWEEN 8 AND 10 INCHES.
4. ALL REINFORCING BARS SHALL CONFORM TO ASTM A615, GRADE 60.
BARS SHALL BE LAPPED PER MASONRY LAP SPLICE SCHEDULE. PROVIDE
BAR POSITIONERS FOR VERTICAL REINFORCING AT A MAXIMUM SPACING
OF 8 FEET ON CENTER.
6. GROUTING SHALL BE STOPPED 1-1/2” BELOW THE TOP OF A COURSE
SO AS TO FORM A KEY AT THE POUR JOINT.
7. ALL BOLTS, ANCHORS, ETC. PLACED IN THE WALL, SHALL BE
GROUTED SOLID INTO POSITION.
SAFETY:
1. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION
PRACTICES, CONTRACTOR WILL BE SOLELY AND COMPLETELY
RESPONSIBLE FOR CONDITION OF JOB SITE INCLUDING SAFETY OF ALL
PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK.
2. THE DUTY OF THE CONTRACTING OFFICER IN CONDUCTING
CONSTRUCTION REVIEW OF CONTRACTOR'S PERFORMANCE IS NOT
INTENDED TO INCLUDE REVIEW OF ADEQUACY OF CONTRACTOR'S
SAFETY MEASURES IN, ON, OR NEAR THE CONSTRUCTION SITE.
STRUCTURAL ABBREVIATIONS
ARCH. ARCHITECT, ARCHITECTURAL
BLDG. BUILDING
BOTT. BOTTOM
C.M.U. CONCRETE MASONRY UNIT
C.J. CONTROL JOINT
C.L. CENTERLINE
COL. COLUMN
CONC CONCRETE
CONT. CONTINUOUS
DIA. DIAMETER
DWG. DRAWING
ELEV. ELEVATION
EXP. EXPANSION
FNDN. FOUNDATION
F.O. FACE OF
F.O.B. FACE OF BRICK
FTG. FOOTING
GALV. GALVANIZED
HORIZ. HORIZONTAL
H.S. HIGH STRENGTH
INSUL. INSULATION
JT. JOINT
L ANGLE
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MASMASONRY
MECH. MECHANICAL
MIN MINIMUM
O.C. ON CENTER
OPP. OPPOSITE
PAF POWDER ACTUATED FASTENER
P.J.F. PREMOLDED JOINT FILLER
PL. PLATE
P.S.I. POUNDS PER SQUARE INCH
P.S.F. POUNDS PER SQUARE FOOT
REINF. REINFORCE,REINFORCING
REQ'D. REQUIRED
SCHED. SCHEDULE
SECT. SECTION
SHT. SHEET
SPECS. SPECIFICATIONS
STL. STEEL
T.O. TOP OF
TYP. TYPICAL
U.O.N. UNLESS OTHERWISE NOTED
VERT. VERTICAL
W.W.F. WELDED WIRE FABRIC
W/ WITH
W/O WITHOUT
Ø DIAMETER
° DEGREES
± PLUS OR MINUS
PRECAST CONCRETE:
1. PRECAST CONCRETE WALL PANELS SHALL BE SOLID PANELS,
DESIGNED AND FABRICATED BY THE PRECAST CONCRETE
MANUFACTURER CERTIFED UNDER THE PCI PLANT CERTIFICATION
PROGRAM.
2. PANELS SHALL BE DESIGNED FOR THE WIND AND SEISMIC LOADS
NOTED BELOW, AND SHEAR LOADS AS INDICATED ON SHEET S-201,
REFER TO SPECIFICATIONS FOR SUBMITTAL REQUIREMENTS.
3. PRECAST CONCRETE UNITS SHALL HAVE A 28-DAY COMPRESSIVE
STRENGTH OF 5000 PSI MINIMUM.
4. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60.
5. PRECAST UNITS SHALL CONFORM TO ACI 318 AND PCI MNL-122.
6. ALL CONNECTIONS OF PRECAST TO PRECAST, OR PRECAST TO
ADJACENT MEMBERS SHALL BE DESIGNED AND PROVIDED BY THE
PRECAST MANUFACTURER, AND INSTALLED BY THE CONTRACTOR.
OPEN WEB STEEL JOIST:
1. OPEN-WEB STEEL JOIST SHALL COMPLY WITH THE STANDARD
SPECIFICATION FOR OPEN WEB JOISTS OF THE STEEL JOIST INSTITUTE,
LATEST EDITION.
2. OPEN-WEB STEEL JOIST SHALL HAVE A MINIMUM BEARING ON STEEL
OF= 2 ½”
3. ALL STEEL JOIST SHALL BE WELDED WHEREVER THEY BEAR ON
STRUCTURAL STEEL MEMBERS, IN ACCORDANCE WITH THE S.J.I AND THE
A.I.S.C SPECIFICATIONS
4. FOR JOIST BRIDGING REQUIREMENTS SEE STANDARD S.J.I. AND
A.I.S.C. SPECIFICATIONS.
5. ROOF JOISTS SHALL BE DESIGNED FOR A NET UPLIFT LOAD OF 25
PSF. A SINGLE LINE OF BOTTOM CHORD BRIDGING SHALL BE PROVIDED
NEAR THE FIRST BOTTOM CHORD PANEL POINTS WHENEVER UPLIFT LOADS
OCCUR.
6. JOIST BRIDGING AND CONNECTIONS SHALL BE COMPLETELY
INSTALLED PRIOR TO PLACING ANY CONSTRUCTION LOADS ON THE JOISTS.
CONSTRUCTION LOADING SHALL NOT EXCEED THE JOIST DESIGN LOAD.
DESIGN CRITERIA:
1. INTERNATIONAL BUILDING CODE – 2009 EDITION .
UFC 1-200-01 GENERAL BUILDING REQUIREMENTS
UFC 3-301-01 STRUCTURAL ENGINEERING WITH
CHANGE 3
UFC 3-310-04 SEISMIC DESIGN FOR BUILDINGS
UFC 4-010-01 DOD MINIMUM ANTITERRORISM
STANDARDS( FEB 2012)
2. REFERENCED CODES: ACI 318 & COMMENTARY,
BUILDING CODE FOR REINF. CONCRETE; ANSI/AISC
360-05, “SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS.
NOTE: WHERE THREE BARS OCCUR, CENTER BAR
SHALL BE TREATED SAME AS INNER FACE BAR.
TYPICAL DETAIL SHOWING CONTINUOUS
REINFORCEMENT AT CORNERS AND
INTERSECTIONS
NOT TO SCALE
INTERSECTION
DIA.
16xBAR
DIA.
16xBAR
CORNER
36 x BAR DIA.
T Y P
O
T Y P
O
DIA.
16xBAR
D
IA
x B A R
TYPICAL WALL FOOTING DETAIL
AT PLUMBING / WATER LINES
WALL, REFER
TO PLANS
BOTTOM OF
FOOTING
INDICATED ON
FOUNDATION
PLUMBING/ WATER
LINE, REFER TO
PLUMBING DWGS.
FOR LOCATION
'X' DISTANCE
FROM TOP OF
PIPE TO
BOTTOM OF
FOOTING
FOOTING
SLEEVE IN WALL,
REFER TO PLUMBING
DWGS.
STEP BOTTOM OF FOOTING
BELOW PLUMBING LINE.
REFER TO TYPICAL
STEPPED FOOTING DETAIL
BACKFILL EXCAVATION WITH CONCRETE
TO LIMITS OF FOOTING PLUS 18" MIN.,
EACH SIDE OF FOOTING
NOTE: WHERE 'X' EXCEEDS 2 FEET
EXCAVATION MAY BE BACKFILLED WITH
COMPACTED STRUCTURAL FILL.
FOOTING ELEVATION
WHERE 'X' IS LESS THAN 3 INCHES
FOOTING ELEVATION
WHERE 'X' IS GREATER THAN 3 INCHES
SECTION TYPICAL
AT CONTRACTORS
OPTION, FOOTING
MAY BE LOWERED
BELOW PIPE.
NOT TO SCALE
M
IN
WHERE PLUMBING LINE INTERFERES
WITH FOOTING REINF., STOP REINF
AND ADD BARS AS SHOWN
3 - #5 BARS
2' - 0"
NOTE: THIS DETAIL IS ONLY APPLICABLE TO CASES WHERE
THE PIPE IS INSTALLED PRIOR TO CASTING THE FOOTING.
TYPICAL COLUMN ISOLATION
JOINT DETAIL
COLUMN
ELEVATION
PLAN
FOR COL. BASE
PLATE DETAILS. REFER
TO RELEVANT SECTIONS
SLAB ON GRADE
SLAB
ON
GRADE
NOTE: PAINT ALL STEEL
BELOW FLOOR WITH 2
COATS OF ASPHALTIC PAINT
COLUMN
REFER TO PLAN
OUTLINE OF COL.
BASE PLATE
C.L. COLUMN & CONST.
JOINT OR SAW JOINT,
REFER TO PLAN
ISOLATION JOINT
2" M
IN
FE
LT
BL
D G
R E
FE
R T O P
LA
N
IS
O
LA
TI
O N J O
IN
T
NOT TO SCALE
FOOTING (ELEV.)
CONST. JT.
SLAB (ELEVATION)
CONST. JT.
SLAB REINF.
TOP OF SLAB
ADD 3/4"Ø x 1'-6" PLAIN BAR
@ 12" O.C. MIDDLE OF SLAB
(GREASE ONE END)
CONST. JT.
(WOODEN BULK HEAD)
TYPICAL JOINT DETAILS
SAW JOINT
SLAB (ELEVATION)
1/8" WIDE SAWED JOINT (S.J.)
FILL WITH ELASTOMERIC
SEALANT PER SPECS.
1/4 DEPTH OF SLAB
NOT TO SCALE
D E P T H
FOOTING REINF. ADD #5 x 5'-0"
@ 12" O.C. (MIN.
2 BARS)
3"
(D
D E P T H
..D /3
TYPICAL SILL DETAIL
TOP OF FOOTING
ELEV. REFER TO
PLAN
FOR PAVING REFER
TO CIVIL DWGS.
1- #4CORNER BAR
FOR FOOTING SIZE AND
REINF. REFER TO PLAN
PROVIDE TWO
LAYERS OF 15 #
BLDG. PAPER
FOR SLAB SIZE AND
REINF. REFER TO PLAN
#4 @ 12" O.C. TOP
W/ 2 - #3 SUPPORT BARS
NOT TO SCALE
3' - 0"
WALL BEYOND
TYPICAL DETAIL SHOWING SLAB
REINFORCING @ EXT. DOORS &
CORNERS
#4 TOP
#4 @ 12" O.C. TOP
#3 SUPPORT.
#3 SUPPORT.
DETAIL @ EXT. DOOR
2- #4 x 3'-0"
MIDDLE OF
SLAB
SLAB CORNER
NOT TO SCALE
TYPICAL STEPPED FOOTING DETAIL
TOP OF FOOTING
FOR ELEV. REFER
TO PLAN
CONTINUOUS REINF.
NOTE: THIS DETAIL APPLIES TO ELEVATION CHANGES SHOWN ON PLAN
AND AT LOCATIONS NOT SHOWN BUT REQUIRED BY JOB CONDITIONS.
NOT TO SCALE
STEP LOCATIONS INDICATED
ON PLAN ARE APPROXIMATE
LOCATIONS AND SHOULD BE
LOCATED AS REQUIRED BY
PLUMBING, SOIL CONDITIONS,
GRADES, ETC.
36 x BAR Ø
36 x BAR Ø
36 x
BA
R Ø
MIN.
2' - 0"
M A X
MIN.
8"
TYPICAL ADDED REINF. @ JOIST SUPPORTING
LOADS BETWEEN PANEL POINTS
L-2x2x1/4 WELD
TO JOIST EACH SIDE
FOR JOIST,
REFER TO PLAN
NOT TO SCALE
LOAD
LOAD
JOIST ON BEAM
TYPICAL 'SP' JOIST CONNECTION DETAIL
TOP OF STEEL ELEV.
REFER TO PLAN
STEEL
BEAM
3/8" STABILIZER PLATE
EXTEND JOIST BOTTOM
CHORD AS SHOWN, @
'SP' JOIST
STIFFENER PLATES
AFTER ALL ROOF DEAD
LOADS ARE IN PLACE
NOT TO SCALE
O" 3/16 3/8" STIFF. PLATE
EACH SIDE
3/4" PLATE, WIDTH =
COL. + 2" (1" EA. SIDE
MIN.) LENGTH = COL. + 6"
(3" EA. SIDE) TYPICAL
UNLESS NOTED OTHERWISE
PLATE LENGTH
4 - 3/4" DIA.,
H.S. BOLTS
REFER TO PLAN
C.L. COLUMN
2 SIDED DOUBLE ANGLE
SHEAR CONNECTION
DETAIL AS PER
AISC TABLES
1/4
TYPICAL DETAIL SHOWING
BEAM BEARING ON COLUMN
NOT TO SCALE
TYPICAL BEAM TO COLUMN TAB PLATE
CONNECTION DETAIL
C.L. COLUMN
FOR BEAM SIZE,
REFER TO PLAN
1/2" MIN.
CAP PLATE TOP OF STEEL
ELEV. REFER
TO PLAN
3/8" MIN. TAB
PLATE
NOT TO SCALE
TYPICAL JOIST BRIDGING ANCHORAGE DETAILS
STEEL BEAM
BRIDGING, WELD
TO BM. FLANGES
AS SHOWN
JOIST
JOIST @ CMU WALL BEAM PARALLEL TO JOIST
NOT TO SCALE
2- 1/2"Ø ANCHOR BOLTS WITH 6"
EMBED. OR DRILLED-IN
ADHESIVE
BOLTS (AT EA. BRIDGING. LINE)
GROUT
SOLID WITH CONC.
JOIST, REFER TO PLAN
JOIST BRIDGING, WELD
TO BRIDGING
ANCHOR ANGLE L3x3x1/4
@ EA. BRIDGING LINE
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
S Y M
D A T E
A P P R
D E S C R
IP
T
IO
N
AS NOTED
N40085-12-R-4515
SEAL
A/E INFO
D E P A R T M E N T O F T H E N A V Y
N A V A L F A C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D
V
IR
G
IN
IA
B E A C H , V A
N A S O C E A N A
N A V A L
FA
C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D M
ID
-A
TL
A N
TI
C
V
IR
G
IN
IA
B E A C H , V A
D A M N E C K A N N E X
A
B
C
D
PHONE: (757) 474-0612 FAX: (757) 474-0919
VIRGINIA BEACH, VIRGINIA, 23464
748 LORD DUNMORE DRIVE, SUITE 101
NRW
CONSULTING STRUCTURAL ENGINEERS
C :\A L O C A L R E V
IT
F
IL
E S \1 S O F V
IS
IT
O R C E N T E R N R W S tru ct ur al _c om pu te r2 5.
rv t
/1 7/ :2 0:
P M
S002G
P S O F P E R
IM
E T E R S E C U R
IT
Y
M A
IN
E N T R Y I M P R O V E M E N T S S O F
T Y P
IC
A L D E T A
IL
S
MLM KBF KBF
1174158
Dec. 20, 2013
12655870
MASONRY LAP SPLICE SCHEDULE
BAR SIZE
REINF.
CENTERED
8", 10", 12"
MAS.
#3 16
1. SMALLER BAR LAP LENGTH SHALL BE USED WHEN SPLICING
DIFFERENT SIZED BARS.
2. LAP LENGTHS SPECIFICALLY DETAILED ON DRAWINGS SHALL
GOVERN INSTEAD OF SCHEDULED LAP LENGTHS.
3. MECHANICAL COUPLERS MAY BE USED IN LIEU OF ANY LAP LENGTH
SHOWN.
4. WHEN LOW LIFT GROUTING IS USED, AND THE LAP LENGTH
EXCEEDS THE GROUT LIFT HEIGHT, A MECHANICAL COUPLER IS
REQUIRED IN LIEU OF LAPPED REINF.
NOTES:
#4
#5
#6
60#7
REINF.
CENTERED
6" MAS.
REINF.
FACE
2" CLR.
TYPICAL LINTEL DETAILS
LINTEL DEPTH
REFER TO
SCHED.
MASONRY
F.O.B.
C.L. EXP. BOLT
(FOR SPANS
OVER 6'-0")
FOR ANGLE
REFER TO NOTES
FOR REINF.
REFER TO
SCHED.
CMU WALL
WIDTH OF
ATTACHED STEEL BRICK SUPPORT
FOR
REINF.
REFER TO
SCHED.
MIN.
4"
NOT TO SCALE
F.O.B.
LOOSE STEEL BRICK SUPPORT
5/16"
MASONRY AND PRECAST
CONCRETE LINTEL SCHED.
FOR C.M.U. PARTITIONS
WALL
WIDTH 4' SPAN &
LESS CLEAR
SPAN
TOP AND BOTTOM REINFORCING
OVER 4' TO
6' CLEAR
SPAN
OVER 6' TO
8' CLEAR
SPAN
6" 1 - # 5 1 - # 5 1 - # 6
2 - # 4 2 - # 4 2 - # 5
2 - # 4 2 - # 5 2 - # 6
2 - # 5 2 - # 6 2 - # 7
1. FOR SIZE AND LOCATION OF OPENINGS REFER TO ARCH.
DRAWINGS.
2. BEARING SHALL BE 8" MINIMUM EACH END.
3. LINTELS UP TO 6'-0" SPAN SHALL BE 7 5/8" DEEP.
LINTELS OVER 6'-0" SPAN SHALL BE 15 5/8" DEEP.
4. FOR HEAD DETAILS REFER TO ARCHITECTURAL DRAWINGS.
5. IN ADDITION TO MASONRY LINTELS AND AS REQUIRED BY
ARCHITECTURAL DETAILS PROVIDE 4" x 6" x 5/16" LOOSE LINTELS AND 4" x 6" x 5/16" ATTACHED LINTELS FOR VENEER SUPPORT. WHERE VENEER
IS PRECAST, CONTRACTOR HAS OPTION TO HAVE PRECAST VENEER
DESIGNED TO SPAN OPENINGS.
6. FOR SPANS OVER 6'-0" LINTEL ANGLE SHALL BE ATTACHED TO
MASONRY OR PRECAST LINTEL WITH 5/8" ROUND EXPANSION BOLTS AT
3'-0" O.C. (MIN. 3 PER ANGLE).
7. STEEL LINTEL ANGLES SHALL BE GALVANIZED.
8. REINFORCING STEEL SHALL BE A.S.T.M. GRADE 60.
9. CONTRACTOR SHALL SUBMIT FOR APPROVAL SHOP DRAWINGS AND
SCHEDULES SHOWING SIZE, DETAILS, LOCATION, ETC. FOR ALL LINTELS
IN C.M.U. WALLS.
NOTES:
8"
10"
12"
LINTEL SHALL HAVE SOLID BOTTOM
AND BE 2" WIDER THAN WALL ABOVE
(TYP)
NOT TO SCALE
TYPICAL DETAILS SHOWING VERTICAL
REINFORCING IN MASONRY WALLS
PLAN DETAIL SECTION
FOR BAR SIZE AND MAX.
SPACING REFER TO
RELEVANT
FOUNDATION SECTION
CONTROL JOINT,
REFER TO ARCH.
DWGS.
PLACE VERTICAL BAR @
CORNERS AND ENDS OF WALLS
AND @ EACH SIDE OF ALL
WALL OPENINGS AND CONTROL
JOINTS
FOR EXACT SIZE AND
LOCATION OF WALL
OPENINGS REFER TO
ARCH. AND MECH. DWGS.
STANDARD 90° HOOK
FOR FOUNDATION REFER TO
FOUNDATION PLAN AND
DETAILS
DOWELS SAME SIZE AND LOCATION
AS VERT. WALL REINF.
SPLICES AND DOWEL LAPS PER MASONRY
BAR SPLICE SCHEDULE, PROVIDE SPLICES
WHERE INDICATED ON PLAN & AS REQ'D BY
FABRICATOR SHOP DRAWINGS.
VERTICAL WALL REINF. (REFER TO
SCHED.) FULL HEIGHT OF WALL. FILL
BLOCK VOIDS SOLID WITH GROUT AT
EACH BAR (REFER TO SPECS.)
FLOOR
(U.O.N.)
EQUAL
(U.O.N.)
EQUAL
TYPICAL JOIST BEARING ON CMU DETAILS
2 -1/2"Ø x 4"
HEADED STUDS
FOR BOND BEAM
REFER TO
RELEVANT SECTION,
TYPICAL
JOIST BEARING ELEVATION
= TOP OF BOND BEAM,
TYP.
NOT TO SCALE
1/2" TYP.
EDGE OF BOND
BEAM
BRG. PLATE1/2"x6"*x 0'-10"
RELEVANT SECTIONS, (TYP.)
CMU BEARING WALL
FOR WIDE REFER TO
TYP.
WHERE WALL CONTINUES,
BLOCK SOLID AROUND BEAM
AFTER INSTALLATION
BEAM, REFER TO PLAN
PROVIDE SOLID BLOCK OR FILL
VOIDS SOLID WITH CONC. 3'-0"
MINIMUM EACH SIDE OF BEAM
ABOVE. (MORTAR JOINTS SHALL
BE FULL WIDTH OF CMU)
6'-0" LONG MASONRY JOINT
REINFORCING, EACH COURSE, 3
COURSES BELOW BEAM
BEARING
BEARING PLATE, 1/2" X
6" X 1'-0", UNLESS
OTHERWISE NOTED.
NON-METALIC, NON-
SHRINK GROUT
SETTING BED (3/4" MIN.)
2 - 3/4" DIA. x 12"
HEADED ANCHOR
BOLTS (A307)
TYPICAL DETAIL SHOWING STEEL
BEAM BEARING ON CMU
NOT TO SCALE
ATFP OPENING SUPPORTS AND BRACING
NOT TO SCALE
ELEVATION
CHANNEL @ EACH JAMB OF
OPENING
C6x8.2 FOR SPANS UP TO 15' C8x11.5 FOR SPANS OVER 15'
C6x8.2 @ HEAD & SILL OF
OPENING, ATTACH TO
VERTICAL CHANNEL WITH
L-4x4x1/4 x 0'-4" (SAME AS
TOP CLIP)
FIRST FLOOR
SLAB
ATFP BRACING ONLY OCCURS TO OCCUPIED
PORTION OF THE VISITOR CENTER, REFER
TO SHEET S001G FOR LOCATION.
SECTION
FOR BEAM REFER
TO PLAN
CLIP L-6x3 1/2 x 5/16 (LLH) x 0'-4", W/ (2) 1/2"Ø EXP.
BOLT (3" GAGE)
CLIP L-4x4x1/4 x 0'-4" WELD TO
BEAM AND CHANNEL WITH
MINIMUM OF 4" OF 3/16"
FILLET WELD (2 EACH SIDE)
OPENING
C6x8.2 @ HEAD &
SILL OF OPENING
CHANNEL @ EACH JAMB
OF OPENING
C6x8.2 FOR SPANS UP TO 15' C8x11.5 FOR SPANS
OVER 15'
FOR BEAM
REFER TO PLAN
8"
16 GAGE STUD
(LAID FLAT)+ 14
GAGE TRACK,
HANG FROM BEAM
ABOVE WITH
STUDS.
8"
C6x8.2, BLOCK SOLID @
ATFP WINDOWS,
PROVIDE LIGHTGAGE
TRACK T&B OF CHANNEL
WHERE PC PANEL
DOES NOT SPAN
ACROSS OPENING,
PROVIDE L-6x4x5/16, (LLV)GALV, BEAR
8" MIN, EACH END.
LINTELS/FRAMING @ EXTERIOR
LIGHTGAGE WALL FRAMING.
BLOCKING,
REFER TO
ARCH.
DRAWINGS
PC PANEL
(WHERE
APPLICABLE)
PC PANEL
(WHERE
APPLICABLE)
NOT TO SCALE
WHERE WINDOW DOES
NOT ALIGN WITH CHANNEL,
PROVIDE 1/4" PLATE,
WELDED TO CHANNEL FOR
WINDOW CONNECTION,
COORDINATE WITH
WINDOW MANUFACTURER
FOR PLATE WIDTH.
TYPICAL LINTEL DETAIL TYPICAL LINTEL @ ATFP OPENING
PC PANEL DESIGNED
TO SPAN OVER
OPENING (BY
PRECAST
MANUFACTURER).WHERE PC PANEL
DOES NOT SPAN
ACROSS OPENING,
PROVIDE L-6x4x5/16, (LLV)GALV, BEAR
8" MIN, EACH END.
LINTELS @ EXTERIOR PRECAST WALL
BLOCKING,
REFER TO
ARCH.
DRAWINGS
PC FASCIA
PANEL
NOT TO SCALE
TYPICAL LINTEL DETAIL TYPICAL LINTEL @ ROLL-UP DOOR
1' - 2"
PLATE 6"X6"X1/4" W/ (2)
1/2"Ø HEADED STUDS,
SPACE @ 4'-0" O.C. MAX
@ LINTELS (MAXIMUM
1'-0" FROM FACE OF
OPENING)
1'-1" X 1/4" CONT. PLATE
(GALV)
L-4x3x5/16 (LLV), WELD
TO PLATES WITH 2" OF
1/4" FILLET WELDS @
12" O.C.
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
S Y M
D A T E
A P P R
D E S C R
IP
T
IO
N
AS NOTED
N40085-12-R-4515
SEAL
A/E INFO
D E P A R T M E N T O F T H E N A V Y
N A V A L F A C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D
V
IR
G
IN
IA
B E A C H , V A
N A S O C E A N A
N A V A L
FA
C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D M
ID
-A
TL
A N
TI
C
V
IR
G
IN
IA
B E A C H , V A
D A M N E C K A N N E X
A
B
C
D
PHONE: (757) 474-0612 FAX: (757) 474-0919
VIRGINIA BEACH, VIRGINIA, 23464
748 LORD DUNMORE DRIVE, SUITE 101
NRW
CONSULTING STRUCTURAL ENGINEERS
C :\A L O C A L R E V
IT
F
IL
E S \1 S O F V
IS
IT
O R C E N T E R N R W S tru ct ur al _c om pu te r2 5.
rv t
/1 7/ :2 0:
P M
S003G
P S O F P E R
IM
E T E R S E C U R
IT
Y
M A
IN
E N T R Y I M P R O V E M E N T S S O F
T Y P
IC
A L D E T A
IL
S
MLM KBF KBF
1174158
Dec. 20, 2013
12655871
DAVID P. ISBELL AI
NI
G
RI
VFOHTLAEWNO
M
M O
C
No.
ARCH TI ECT
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
SY
M
DA
TE
AP
PR
DE
SC
RI
PT
IO
N
AS NOTED
N40085-09-D-5027-0005
SEAL
A/E INFO
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
VI
RG
IN
IA
B
EA
CH
, V
A
NA
S
OC
EA
NA
NA
VA
L F
AC
ILI
TIE
S E
NG
IN
EE
RI
NG
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
VI
RG
IN
IA
B
EA
CH
, V A
DA
M
NE
CK
A
NN
EX
A
B
C
D
C:
\U se rs\ ds an for d\D oc um en ts\
SO
F Ca no pie s - A
RC
H
- C en tra l_d sa nfo rd .rv t
/19 /20
9:
:53
A M
G001C
P
S
O F
P E
R
IM
E
TE
R S
E C
U R
IT
Y
M
A
IN
E N
TR
Y
IM
P
R O
V E
M E
N T
- S O
F
SO
F
GA
TE
C
AN
OP
Y
- C
OV
ER
S
HE
ET
DPR DLS DPR
1174158
14993
Dec. 20, 2013
12655959
P527 SOF PERIMETER SECURITY & MAIN ENTRY
IMPROVEMENTS - SOF GATE CANOPY
NAS OCEANA DAM NECK ANNEX VIRGINIA BEACH, VA
/1
A1
S301C
A D
/1
1C1 24"x24" CONC. COL W/ 8-#8 VERT.
SPACED EQUALLY AROUND COL.
PERIMETER AND #5 TIES AT 12" O.C.
(U.O.N. IN SECTION) (TYP.)
F8.0
F8.0 8'-0" x 8'-0" x 2'-0" COLUMN
FOOTING W/ 9-#6 TOP AND
BOTT. EACH WAY (TYP)
C1 C1
F7.0 F7.0
F8.0
C1
C1 C1
F7.0 7'-0" x 7'-0" x 2'-0" COLUMN
FOOTING W/ 8-#6 TOP AND
BOTT. EACH WAY (TYP)
F7.0
8' - 0"
8' - 0"
CB
54' - 2 9/16" 42' - 2" 30' - 1 7/16"
C1
C1 C1
F8.0
F8.0
F7.0
C1
1. UNLESS OTHERWISE NOTED THUS (-_____) ON PLAN,
TOP OF ALL COLUMN FOOTINGS @ SOF GATE CANOPIES
SHALL BE AT ELEVATION 6.55, INDICATING ACTUAL
ELEVATION.
3. NO FOUNDATION WORK SHALL BE INSTALLED UNTIL ALL
UNDERGROUND UTILITIES, ETC. HAVE BEEN COORDINATED
WITH FOUNDATION LOCATIONS AND ELEVATIONS.
4. FOR GENERAL NOTES AND TYPICAL DETAILS, REFER TO
SHEETS S001G, S002G AND S003G.
SHEET KEY NOTES #
1. OUTLINE OF CANOPY ABOVE.
THE FOUNDATIONS AND COLUMNS HAVE BEEN DESIGNED BASED
UPON PRELIMINARY LOADING AND FRAME SUPPORT/COLUMN
LOCATIONS. SPACE FRAME SHOP DRAWINGS SHALL BE SUBMITTED
INCLUDING ALL SUPPORT/COLUMN LOCATIONS, AND REACTIONS.
STRUCTURAL ENGINEER OF RECORD SHALL REVIEW SHOP
DRAWINGS INCLUDING SPACE FRAME SUPPORT/COLUMN
REACTIONS/LOCATIONS AND ISSUE REVISED DRAWINGS, AS
REQUIRED TO SUPPORT ANY CHANGES, PRIOR TO ANY
FOUNDATION WORK. FOR LOADING REQUIREMENTS REFER TO
SHEET S102C.
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
S Y M
D A T E
A P P R
D E S C R
IP
T
IO
N
AS NOTED
N40085-12-R-4515
SEAL
A/E INFO
D E P A R T M E N T O F T H E N A V Y
N A V A L F A C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D
V
IR
G
IN
IA
B E A C H , V A
N A S O C E A N A
N A V A L
FA
C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D M
ID
-A
TL
A N
TI
C
V
IR
G
IN
IA
B E A C H , V A
D A M N E C K A N N E X
A
B
C
D
PHONE: (757) 474-0612 FAX: (757) 474-0919
VIRGINIA BEACH, VIRGINIA, 23464
748 LORD DUNMORE DRIVE, SUITE 101
NRW
CONSULTING STRUCTURAL ENGINEERS
C :\A L O C A L R E V
IT
F
IL
E S \1 S O F C an op y S T R U C T U R A L
- C en tr al _c om pu te r2 5.
rv t
/1 7/ :3 3:
P M
S101C
P S O F P E R
IM
E T E R S E C U R
IT
Y
M A
IN
E N T R Y I M P R O V E M E N T S O F
S O F G A T E C A N O P Y F O U N D A T
IO
N P
LA
N S
KEM MLM MLM
1174158
14994
DEC. 20, 2013
1265596104'0 8' 16'
SCALE: 1/8"=1'-0"
1/8" = 1'-0"
SOF GATE CANOPY FOUNDATION PLAN
FOUNDATION PLAN NOTES
SPACE FRAME DESIGN CRITERIA
A1
S301C
A D
/1
/1
1 1
CB
54' - 2 9/16" 42' - 2" 30' - 1 7/16"
1. DATUM FOR ALL ELEVATIONS GIVEN ON THIS PLAN IS TOP OF
PAVEMENT @ HIGH POINT ELEV. 8.55 = 0'-0".
2. ROOF CONSTRUCTION SHALL BE A 1 1/2" DEEP 20 GAGE
GALVANIZED ROOF DECK SUPPORTED ON A PRE-ENGINEERED
SPACE FRAME ROOF STRUCTURE BEARING ON CONCRETE COLUMNS.
UNDERSIDE OF SPACE FRAMES SHALL BE A MINIMUM OF 17'-6"
ABOVE THE HIGHEST PAVEMENT ELEV. (PAVEMENT @ SOF ELEV. 8.55)
3. PRE-ENGINEERED SPACE FRAME SHALL BE DESIGNED FOR THE
FOLLOWING LOADS IN ADDITION TO SELF-WEIGHT:
COLLATERAL DEAD LOAD: 10 PSF
ROOF LIVE LOAD: 20 PSF (REDUCIBLE)
WIND, SEISMIC, SNOW LOADS: REFER TO SHEET S001G.
4. FOR COLUMN SIZE SEE FOUNDATION PLAN.
5. FOR GENERAL NOTES AND TYPICAL DETAILS REFER TO SHEET
S001G, S002G AND S003G.
1. EXTENT OF CANOPY ROOF.
SHEET KEY NOTES #
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
S Y M
D A T E
A P P R
D E S C R
IP
T
IO
N
AS NOTED
N40085-12-R-4515
SEAL
A/E INFO
D E P A R T M E N T O F T H E N A V Y
N A V A L F A C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D
V
IR
G
IN
IA
B E A C H , V A
N A S O C E A N A
N A V A L
FA
C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D M
ID
-A
TL
A N
TI
C
V
IR
G
IN
IA
B E A C H , V A
D A M N E C K A N N E X
A
B
C
D
PHONE: (757) 474-0612 FAX: (757) 474-0919
VIRGINIA BEACH, VIRGINIA, 23464
748 LORD DUNMORE DRIVE, SUITE 101
NRW
CONSULTING STRUCTURAL ENGINEERS
C :\A L O C A L R E V
IT
F
IL
E S \1 S O F C an op y S T R U C T U R A L
- C en tr al _c om pu te r2 5.
rv t
/1 7/ :3 3:
P M
S102C
P S O F P E R
IM
E T E R S E C U R
IT
Y
M A
IN
E N T R Y I M P R O V E M E N T S O F
S O F G A T E C A N O P Y R O O F F R A M
IN
G P
LA
N S
KEM MLM MLM
1174158
14995
DEC. 20, 2013
12655961
1/8" = 1'-0"
SOF CANOPY ROOF FRAMING PLAN
ROOF FRAMING PLAN NOTES
4'0 8' 16'
SCALE: 1/8"=1'-0"
PERIMETER MEMBER OF
SPACE FRAME SHALL BE
FLAT SIDED TO
ACCOMMODATE FASCIA
ATTACHMENT.
(TYP @ PERIMETER OF
CANOPY/SPACE FRAME)
L-4x4x1/4 CONT
(GALV)
FOR FASCIA
FRAMING, REFER
TO ARCH.
DRAWINGS
STEEL ROOF DECK
RAIN LEADER (WHERE APPLICABLE),
ENCASE IN CONCRETE COLUMN.
FOR COL. SIZE AND REINF. REFER TO PLAN
BOTTOM OF TRUSS, 17'-6"
CLEAR MINIMUM FROM TOP
OF PAVEMENT BELOW (TYPICAL)
GRID/CENTERLINE OF
COLUMN & FOOTING
T Y P
FOR FOOTING SIZE
AND REINF. REFER
TO PLAN
FOR PAVING REFER
TO CIVIL DWGS.
COL. TIES, REFER TO PLAN
TOP OF COLUMN ELEVATION SHALL BE
COORDINATED WITH SPACE FRAME
MANUFACTURER
DOWELS TO MATCH
VERT. REINF.
U .O .N x B A R D
IA
C L R
3/4" CHAMFER @ CORNERS
12" X 12" X 3/4" TOP PLATE
W/ (4) 3/4"Ø X 1'-6" LONG HEADED
STUDS, WELDED TO PLATE
(GALV)., SUPPORT ON 4" GROUT
BED.
1 1/2"
SPACE COLUMN TIES AS SHOWN
AT TOP OF COLUMN
16' - 8"
TOP OF
COLUMN
17' - 9"
2"
S301C
B3
2"
362S162-54 STUDS
@ 16" O.C.
12 GAGE BENT PLATES W/
(4) #12 SCREWS @ STUD,
AND (4) PAF FASTENERS
@ ANGLE.
362S162-54 STUD
SUPPORT @ EACH
VERTICAL STUD, ATTACH
TO STUD & CLIP WITH (4)
#12 SCREWS
L-4x4x1/4 CONT. , PROVIDE 1" WIDE X 2" LONG
SLOTS IN HORIZONTAL LEG @ 2'-0" O.C. TO
WELD ANGLE TO THE TOP TUBE. WITH 1/4"
FILLET WELDS.
3" STEEL DECK, REFER
TO PLAN
TOP CHORD OF TRUSS
(TUBE) BY SPACE FRAME
MANUFACTURER
FOR FASCIA, ROOFING & INSULATION,
REFER TO ARCHITECTURAL
DRAWINGS.
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
S Y M
D A T E
A P P R
D E S C R
IP
T
IO
N
AS NOTED
N40085-12-R-4515
SEAL
A/E INFO
D E P A R T M E N T O F T H E N A V Y
N A V A L F A C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D
V
IR
G
IN
IA
B E A C H , V A
N A S O C E A N A
N A V A L
FA
C
IL
IT
IE
S E N G
IN
E E R
IN
G C O M M A N D M
ID
-A
TL
A N
TI
C
V
IR
G
IN
IA
B E A C H , V A
D A M N E C K A N N E X
A
B
C
D
PHONE: (757) 474-0612 FAX: (757) 474-0919
VIRGINIA BEACH, VIRGINIA, 23464
748 LORD DUNMORE DRIVE, SUITE 101
NRW
CONSULTING STRUCTURAL ENGINEERS
C :\A L O C A L R E V
IT
F
IL
E S \1 S O F C an op y S T R U C T U R A L
- C en tr al _c om pu te r2 5.
rv t
/1 7/ :3 3:
P M
S301C
P S O F P E R
IM
E T E R S E C U R
IT
Y
M A
IN
E N T R Y I M P R O V E M E N T S O F
S O F G A T E C A N O P Y S T R U C T U R A L S E C T
IO
N S
KEM MLM MLM
1174158
14996
DEC. 20, 2013
12655962
SECTION
1/2" = 1'-0"S101C
A1
S-102C
0 1' 2' 4'
SCALE: 1/2"=1'-0"
DETAIL
3" = 1'-0"S301C
B3
0 6" 1'
SCALE: 3"=1'-0"
3"
A201CB1
A201C
A201C
A201C
A1
B3
C1
TYP
A B C
54'-2 9/16" 42'-2" 30'-1 7/16"
'-2
'-1 5/
B1 A501C
'-2
'-3 1/
2"
96'-4" 36'-4 1/2"
'-5
1/ 2"
132'-8 1/2"
D
1/2" / 12"
1/2
1/2
1/2" / 12"
1/2
1/2" / 12"
HIP
ROOF PLAN LEGEND
DIRECTION OF ROOF SLOPE
ROOF DRAIN
LIGHTNING PROTECTION (GROUND ROD),
REFER TO ELECTRICAL DRAWINGS
DAVID P. ISBELL AI
NI
G
RI
VFOHTLAEWNO
M
M O
C
No.
ARCH TI ECT
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
SY
M
DA
TE
AP
PR
DE
SC
RI
PT
IO
N
AS NOTED
N40085-09-D-5027-0005
SEAL
A/E INFO
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
VI
RG
IN
IA
B
EA
CH
, V
A
NA
S
OC
EA
NA
NA
VA
L F
AC
ILI
TIE
S E
NG
IN
EE
RI
NG
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
VI
RG
IN
IA
B
EA
CH
, V A
DA
M
NE
CK
A
NN
EX
A
B
C
D
C:
\U se rs\ ds an for d\D oc um en ts\
SO
F Ca no pie s - A
RC
H
- C en tra l_d sa nfo rd .rv t
/19 /20
9:
:26
A M
A101C
P
S
O F
P E
R
IM
E
TE
R S
E C
U R
IT
Y
M
A
IN
E N
TR
Y
IM
P
R O
V E
M E
N T
- S O
F
SO
F
GA
TE
C
AN
OP
Y
- R
OO
F
PL
AN
DRP DLS DPI
1174158
14997
Dec. 20, 2013
12655963
1/8" = 1'-0"
SOF CANOPY ROOF PLAN
KEYNOTES
1 2 PLY MODIFIED BITUMEN ROOF
2 ROOF DRAIN
3 TAPERED INSULATION
4 LIGHTNING PROTECTION SYSTEM, REFER
TO ELECTRICAL DRAWINGS
24'16'8'4'0 1/8"=1'-0"
T.O. DECK - SOF
CANOPY
22'-7 1/2"
FIN FL
0'-0"
4 4 4
T.O. DECK - SOF
CANOPY
22'-7 1/2"
FIN FL
0'-0"
A B C
D
T.O. DECK - SOF
CANOPY
22'-7 1/2"
FIN FL
0'-0"
1 2 3
4 4
T.O. DECK - SOF
CANOPY
22'-7 1/2"
FIN FL
0'-0"
ABC
D
DAVID P. ISBELL AI
NI
G
RI
VFOHTLAEWNO
M
M O
C
No.
ARCH TI ECT
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
SY
M
DA
TE
AP
PR
DE
SC
RI
PT
IO
N
AS NOTED
N40085-09-D-5027-0005
SEAL
A/E INFO
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
VI
RG
IN
IA
B
EA
CH
, V
A
NA
S
OC
EA
NA
NA
VA
L F
AC
ILI
TIE
S E
NG
IN
EE
RI
NG
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
VI
RG
IN
IA
B
EA
CH
, V A
DA
M
NE
CK
A
NN
EX
A
B
C
D
C:
\U se rs\ ds an for d\D oc um en ts\
SO
F Ca no pie s - A
RC
H
- C en tra l_d sa nfo rd .rv t
/19 /20
9:
:29
A M
A201C
P
S
O F
P E
R
IM
E
TE
R S
E C
U R
IT
Y
M
A
IN
E N
TR
Y
IM
P
R O
V E
M E
N T
- S O
F
SO
F
GA
TE
C
AN
OP
Y
- E
LE
VA
TI
ON
S
DRP DLS DPI
1174158
14998
Dec. 20, 2013
12655964
1/8" = 1'-0"A101C
CANOPY ELEVATIONB1
1/8" = 1'-0"A101C
CANOPY ELEVATIONC1
1/8" = 1'-0"A101C
CANOPY ELEVATIONB3
KEYNOTES
1 REINFORCED CONCRETE COLUMN,
REFER TO STRUCTURAL DRAWINGS
2 ALUMINUM COMPOSITE PANEL SYSTEM
3 STEEL TRUSS, SEE STRUCTURAL
DRAWINGS
4 LAMBS TONGUE, REFER TO DETAIL ON
SHEET A501C
1/8" = 1'-0"A101C
CANOPY ELEVATIONA1
24'16'8'4'0 1/8"=1'-0"
2'- 2"
4"
9 5/8"
1/2" / 12"
3"
141423
8" MINIMUM, TYP.
" A
BO
VE
G
RA
DE
DAVID P. ISBELL AI
NI
G
RI
VFOHTLAEWNO
M
M O
C
No.
ARCH TI ECT
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
SY
M
DA
TE
AP
PR
DE
SC
RI
PT
IO
N
AS NOTED
N40085-09-D-5027-0005
SEAL
A/E INFO
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
VI
RG
IN
IA
B
EA
CH
, V
A
NA
S
OC
EA
NA
NA
VA
L F
AC
ILI
TIE
S E
NG
IN
EE
RI
NG
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
VI
RG
IN
IA
B
EA
CH
, V A
DA
M
NE
CK
A
NN
EX
A
B
C
D
C:
\U se rs\ ds an for d\D oc um en ts\
SO
F Ca no pie s - A
RC
H
- C en tra l_d sa nfo rd .rv t
/19 /20
9:
:31
A M
A501C
P
S
O F
P E
R
IM
E
TE
R S
E C
U R
IT
Y
M
A
IN
E N
TR
Y
IM
P
R O
V E
M E
N T
- S O
F
SO
F
GA
TE
C
AN
OP
Y
- R
OO
F
DE
TA
ILS
DRP DLS DPI
1174158
14999
Dec. 20, 2013
12655965
KEYNOTES
1 ALUMINUM COMPOSITE PANEL SYSTEM
2 CONTINUOUS SEALANT
3 3-5/8" METAL STUD FRAMING @ 16" O.C., AT BULK HEADS
4 1/2" GLASS MAT SHEATHING
5 STEEL ANGLE, SEE STRUCTURAL DRAWINGS
6 CONTINUOUS BACKER ROD AND SEALANT
7 TREATED WOOD BLOCKING
8 ALUMINUM COMPOSITE COPING
9 WRAP BITUMEN SHEET OVER WOOD BLOCKING
10 ALUMINUM COMPOSITE PANEL TERMINATION CLIP, PROVIDE
FASTENERS TO SECURE TO BLOCKING
11 (3) ROWS, 1/8" DIAMETER WEEP/VENT AT 1" O.C. CONTINUOUS
12 METAL COUNTER-FLASHING RECIEVER
13 2-PIECE METAL COUNTER-FLASHING
14 MODIFIED BITUMEN FLASHING
15 ROOF MEMBRANE SYSTEM MANUF APPROVED CUT-OFF
MASTIC
16 MODIFIED BITUMEN CAP SHEET
17 MODIFIED BITUMEN BASE SHEET
18 1/2" PROTECTION BOARD
19 2" RIGID INSULATION
20 STEEL TUBE, SEE STRUCTURAL DRAWINGS
21 METAL ROOF DECK, SEE STRUCTURAL DRAWINGS
22 36" X 36" 4 LB. LEAD FLASHING SET IN ASPHALT CEMENT
23 ROOF DRAIN
24 ROOF DRAIN PIPE
25 REINFORCED CONCRETE COLUMN, REFER TO STRUCTURAL
DRAWINGS
26 CAST BRONZE WALL FLANGE
27 CAST BRONZE NOZZLE
28 BIRD SCREEN
29 RAIN LEADER, REFER TO PLUMBING DRAWINGS
30 SEE STRUCTURAL DRAWINGS FOR CANOPY ROOF FRAMING
DETAILS AND CONNECTIONS
31 1/2" DIA. ANCHOR BOLTS W/NUT AND WASHERS STAGGERED
AT 24" O.C.
32 TAPERED RIGID INSULATION
3" = 1'-0"A101C
ROOF DETAILB1
3" = 1'-0"
TYPICAL ROOF DRAIN DETAIL
0 1" 6" 9"2" 3" 4" 5" 1' 3"=1'-0"
3" = 1'-0"
TYPICAL LAMBS TONGUE DETAIL
A
C
O P R
E R
E
GE N
I N
ANO
E S S I
F
L
Lic. No. 048052
SORIN C. NICU
NW
O O M M
HT O
RG
IV
I
AE
N I
L F
J
J J JJ J J
J
J J
J
FINISHED GRADE
GUARD HOUSE
IN/OUT IN/OUT IN/OUT IN/OUT
TRAFFIC CONTROLLER (TYPICAL)
IN/OUT
IN/OUT
TWO 4-GANG SWITCHBANKS
PANEL 'LG1'LIGHTING
CONTACTOR
SECURITY
BACKBOARD
CANOPY LIGHT FIXTURE (TYPICAL OF 14)
DETERENT SYSTEM SWITCH
ELECTRONIC BIRD
ALL FIXTURES IN THIS AREA
ARE TYPE " " U.O.NS
ALL FIXTURES IN THIS AREA
ARE TYPE " " U.O.NS
G R G R
G R
OUT OUT
G R G R ININ G R IN
OUT
2 2
G R OUT
G R IN
12 12 12
1213 LG1-3
101010
1/8" = 1'-0" 0' 5' 10' 20' 30'
GRAPHIC SCALE
29 N. Kings Way
Hampton,Virginia 23669-3503 Phone: (757) 722-7074 Fax: (757) 722-9092
A
OF
1909 CYPRESS AVENUE
VIRGINIA BEACH, VA 23451
(757) 417 - 0140
SHEET
B
C
1 2 3 4 5
D
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
1 2 3 4 5
<<XX>>
CHIEF ENG/ARCH
BRANCH MANAGER
<<PM/DM>>
DES DRW CHK
SATISFACTORY TO DATE
DES
APPROVED
FOR COMMANDER NAVFAC
SY
M
DA
TE
AP
PR
DE
SC
RI
PT
IO
N
AS NOTED
N40085-12-R-4515
SEAL
A/E INFO
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
C
OM
MA
ND
VI
RG
IN
IA
B
EA
CH
, V
A
NA
S
OC
EA
NA
NA
VA
L F
AC
ILI
TIE
S E
NG
IN
EE
RI
NG
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
VI
RG
IN
IA
B
EA
CH
, V A
DA
M
NE
CK
A
NN
EX
A
B
C
D
C:
\U se rs\ av au gh n\D oc um en ts\
RE
VI
T\
SO
F
Ca no pie s -
E
LE
C
- C en tra l_a va ug hn
.rv t
/18
/20
2:
:42 P
M
E101C
P
S
O F
P E
R
IM
E
TE
R S
E C
U R
IT
Y
M
A
IN
E N
TR
Y
IM
P
R O
V
O V
E R
W A
TC
H
SO
F
SO
UT
H
GA
TE
C
AN
OP
Y
- L
IG
HT
IN
G
RJP RJP SCN
149101
2013 DEC 20
12655967
SCALE: 1/8" = 1'-0"
SOF SOUTH GATE CANOPY - LIGHTING
SHEET KEYNOTES
1. TO CIRCUIT HU-1 VIA LIGHTING CONTACTOR IN ELECTRICAL ROOM 107 IN
VISITOR CENTER. PROVIDE ONE 1" CONDUIT WITH 2#10 AND 1#10 GND FROM
POWER HANDHOLE. SEE SHEET ES102S IN SOF PACKAGE FOR LOCATION OF
POWER HANDHOLE.
2. CONNECT TO SWITCHBANK IN GUARD HOUSE. GREEN/RED LIGHT CANOPY
DETAIL THIS SHEET.
GENERAL NOTES
A. FOR DETAILS AND LIGHT FIXTURE SCHEDULE SEE SHEETS E501D THROUGH
E505D IN SOF PACKAGE.
B. FOR PANELBOARD SCHEDULES SEE SHEETS E601S AND E602S IN SOF
PACKAGE.
SCALE: NOT TO SCALE
SOF CANOPY GREEN/RED LIGHT ELEVATION
3. PROVIDE ONE 1" CONDUIT, EACH WITH 3#12 AND 1#12 GROUND FROM
SWITCHBANK IN GUARD HOUSE TO JUNCTION BOX, ENCASE CONDUIT IN
CONCRETE COLUMN.
4. RUN CONDUITS PARALLEL TO CANOPY SUPPORT STRUCTURE FOR
CONCEALMENT.
5. GREEN/RED LIGHT, FOUR FOR INCOMING AND FOUR FOR OUTGOING TRAFFIC.
SUPPORT TO CANOPY STRUCTURE AS REQUIRED. CENTER LIGHT FIXTURE OVER
ASSOCIATED LANE.
5 TYPICAL
6. PROVIDE FOUR 1/2" CONDUITS FROM INCOMING TRAFFIC JB AND FOUR 1/2"
CONDUITS FROM OUTGOING JB, EACH WITH 3#12 AND 1#12 GROUND TO
TRAFFIC CONTROLLER'S OF ASSOCIATED GREEN/RED LIGHT.
7. PROVIDE ONE 3/4" CONDUIT TO JUNCTION BOX, ENCASED IN CONCRETE
COLUMN, FOR CANOPY LIGHTING CIRCUIT.
8. CONNECT TO METAL HALIDE FIXTURES. SEE CANOPY LIGHTING PLAN THIS
SHEET.
9. POWER JUNCTION BOX FOR CCTV POWER.
10. CCTV SECURITY CAMERA. PROVIDED AND INSTALLED BY SECURITY
CONTRACTOR.
11. CONNECT TO POWER JUNCTION BOX.
12. CONNECT TO SECURITY JUNCTION BOX.
12121212 11 11 11 11
13. CCTV SECURITY JUNCTION BOX.
14. MOUNT LIGHT FIXTURES SO THAT THE BOTTOM OF THE LIGHT FIXTURE IS
FLUSH WITH THE BOTTOM OF THE CANOPY CHORD.
15. PROVIDE ONE 1" CONDUIT TO ELECTRONIC BIRD DETERENT SYSTEM. PROVIDE
WIRING PER MANUFACTURER'S REQUIREMENTS.
14 TYPICAL
File details come from the government source that posted it. Updated .