AMEND 0005 AMENDMENT TO SOW B355 DNA Renovate Rooms 216-218.pdf
PDF 332 KB Posted
- Solicitation number
- N4008525R0019
About this file
This document is Amendment 0001 for a renovation project at NAS Oceana, Dam Neck Annex in Virginia Beach, VA, dated 10 July 2025. The amendment modifies multiple sections of the original solicitation for Building 355, specifically focusing on Rooms 216-218. Key changes include:
- Flooring specifications: Replacing slip-resistant epoxy floor coating requirements with standard epoxy paint matching existing corridor colors, reducing the wall base from 12 to 8 inches. 2. Interior door specifications: Upgrading from "maximum duty" to "Level 4" hollow metal interior doors with a 40 STC (Sound Transmission Class) requirement. 3. Demolition and concept plans: Deleting the existing document in Part 6 and replacing it with a new version. These modifications suggest refinements to the original renovation plan for the SOCOM Compound, maintaining slip resistance and sound insulation standards while adjusting specific material and finish details.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 355 – RENOVATE ROOMS 216-218
NAS Oceana, Dam Neck Annex, Virginia Beach VA
Amendment 0001
10 JULY 2025
1) In PART 3, 5.0 Room Requirements, Existing Corridor, Page 6:
Remove the following:
o Paint existing corridor floors with a slip resistant epoxy floor coating o Paint existing 12 inch ceramic tile base on existing CMU wall with a slip resistant epoxy floor coating
Replace with:
o Paint existing corridor floors with an epoxy paint, match existing epoxy paint in color o Paint existing 8 inch CMU base on existing CMU wall with an epoxy paint, match existing corridor floor epoxy paint in color
2) In PART 3, 6.0 Engineering Systems Requirements (ESR), C30 Interior Finishes, C3020 Floor Finishes, b. Resinous Flooring Systems, Page 9:
b. Resinous Flooring System: Provide a resinous epoxy floor coating system 3/16” thick with a slip-resistant, seamless finish in the existing corridor to include the existing 12 inch CMU wall base. Provide flooring systems smooth enough to meet the minimum requirements of this RFP or the manufacturer’s smoothness requirements, whichever is most restrictive. Maintain slip resistance with a dynamic coefficient of friction of 0.42, according to ANSI 137.1-2012.
b. Resinous Flooring System: Provide an epoxy paint floor coating system with a slip-resistant, seamless finish in the existing corridor to include the existing 8 inch CMU wall base. Epoxy paint to match existing epoxy paint in corridor. Provide flooring systems smooth enough to meet the minimum requirements of this RFP or the manufacturer’s smoothness requirements, whichever is most restrictive. Maintain slip resistance with a dynamic coefficient of friction of 0.42, according to ANSI 137.1-2012.
BUILDING 355 – RENOVATE ROOMS 216-218
NAS Oceana, Dam Neck Annex, Virginia Beach VA
Amendment 0001
10 JULY 2025
3) In PART 3, C1020 INTERIOR DOORS, Paragraph 1:
Provide flush hollow metal interior doors (maximum duty).
Provide flush hollow metal interior doors (Level 4). Doors must meet 40 STC requirements.
4) In PART 6, 2ND FLOOR DEMOLITION AND CONCEPT PLANS (A-101):
Delete the following:
The document in its entirety.
The new document in its entirety.
**End of Amendment 0001**