This is an Indoor Environmental Quality (IEQ) survey report from the Industrial Hygienist at NMRTU Earle regarding mold inspection in Buildings C-10, C-11, C-12, and C-13 at Naval Weapons Station Earle, Colts Neck, NJ, dated April 14, 2023.

The survey found localized spots of white mold growth on rafters in the attic spaces of four two-story masonry buildings used for barracks/lodging. The buildings had attic ventilation issues with multiple inoperable fans, and temperature/humidity readings taken on April 12, 2023 showed attic conditions of 95.6-100.7°F with 19.6-29.9% relative humidity. Key recommendations include: consulting with NAVFAC PWD to repair attic ventilation systems, replacing missing insulation, cleaning mold from rafters using N95 masks and PPE, maintaining humidity below 60%, and following specific mold prevention practices like keeping windows closed during AC operation and quickly addressing water issues. Building C-10 (MWR Deer Run Lodging) showed the least mold presence, while Building C-13 recently underwent mold remediation on its lower floors. The report includes photos documenting the mold conditions in the attics.

View the file

Other files

File Type Posted
RFI LOG Mold Removal 6027730.xlsx XLSX spreadsheet
RFI LOG Mold Removal 6027730.xlsx XLSX spreadsheet
RFI LOG Mold Removal 6027730.xlsx XLSX spreadsheet
N4008525Q2505-0001 (Released).pdf PDF
FY25 SOW MOLD C10 C11 C12.pdf 2 signed edit.pdf PDF
N4008525Q2505 (Released).pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .