Section 09 22 00.pdf
PDF 18 KB Posted
- Attached to
- DESIGN-BUILD (DB), G/ATOR SUPPORT FACILITIES, NAS OCEANA, DAM NECK ANNEX, VIRGINIA BEACH, VA
- Solicitation number
- N4008524R2504
About this file
This document provides specifications for metal support systems for plaster and gypsum board. Key details include requirements for steel materials to have galvanized, aluminum, or aluminum-zinc coatings. Support systems must comply with seismic standards for zones with seismic activity. Metal support systems must contain a minimum of 20% recycled content, and data identifying the recycled content percentage is required. Installation must follow various ASTM standards and provide framing at 16 inches or 24 inches on center as specified. Erection tolerances are outlined for surfaces to be covered by various finish materials.
The related federal contract opportunity is a solicitation from the Department of the Navy Naval Facilities Engineering Command for design-build of G/ATOR support facilities at NAS Oceana Dam Neck Annex in Virginia Beach, Virginia. The solicitation number and deadline are provided.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 09 22 00
SUPPORTS FOR PLASTER AND GYPSUM BOARD
02/10, CHG 2: 08/18
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 341 (2016) Seismic Provisions for Structural Steel Buildings
ASTM INTERNATIONAL (ASTM)
ASTM A463/A463M (2015; R 2020; E 2020) Standard Specification for Steel Sheet, Aluminum-Coated, by the Hot-Dip Process
ASTM A653/A653M (2020) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM C645 (2014; E 2015) Nonstructural Steel Framing Members
ASTM C754 (2020) Standard Specification for Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products
ASTM C841 (2003; R 2013) Installation of Interior Lathing and Furring
ASTM C847 (2014a) Standard Specification for Metal Lath
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM EMLA 920 (2009) Guide Specifications for Metal Lathing and Furring
UNDERWRITERS LABORATORIES (UL)
UL Fire Resistance (2014) Fire Resistance Directory
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for
Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Metal Support Systems; G
Submit for the erection of metal framing, furring, and ceiling suspension systems. Indicate materials, sizes, thicknesses, and fastenings.
SD-03 Product Data
Metal Support Systems
Recycled Content for Metal Support Systems; S
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the job site and store in ventilated dry locations permitting easy access for inspection and handling. If materials are stored outdoors, stack materials off the ground, supported on a level platform, and fully protected from the weather. Handle materials carefully to prevent damage. Remove damaged items and provide new items.
PART 2 PRODUCTS
2.1 MATERIALS
Provide steel materials for metal support systems with galvanized coating ASTM A653/A653M, G-60; aluminum coating ASTM A463/A463M, T1-25; or a 55-percent aluminum-zinc coating. Provide support systems and attachments per UFC 3-301-01, "Structural Engineering" in seismic zones.
Provide metal support systems containing a minimum of 20 percent recycled content. Provide data identifying percentage of recycled content for metal support systems.
2.1.1 Materials for Attachment of Lath
2.1.1.1 Suspended and Furred Ceiling Systems and Wall Furring
ASTM C841, and ASTM C847.
2.1.1.2 Non-load Bearing Wall Framing
NAAMM EMLA 920.
2.1.2 Materials for Attachment of Gypsum Wallboard
2.1.2.1 Suspended and Furred Ceiling Systems
ASTM C645.
2.1.2.2 Non-load Bearing Wall Framing and Furring
ASTM C645, but not thinner than 0.0179 inch thickness, with 0.0329 inch minimum thickness supporting wall hung items such as cabinetwork, equipment and fixtures.
2.1.2.3 Furring Structural Steel Columns
ASTM C645. Steel (furring) clips and support angles listed in UL Fire Resistance may be provided in lieu of steel studs for erection of gypsum wallboard around structural steel columns.
2.1.2.4 Z-Furring Channels with Wall Insulation
Not lighter than 26 gage galvanized steel, Z-shaped, with 1-1/4 inch and 3/4 inch flanges and depth as required by the insulation thickness provided.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Systems for Attachment of Lath
3.1.1.1 Suspended and Furred Ceiling Systems and Wall Furring
ASTM C841, except as indicated otherwise.
3.1.1.2 Non-load Bearing Wall Framing
NAAMM EMLA 920, except provide framing members 16 inches o.c. unless indicated otherwise.
3.1.2 Systems for Attachment of Gypsum Wallboard
3.1.2.1 Suspended and Furred Ceiling Systems
ASTM C754, except provide framing members 16 inches o.c. unless indicated otherwise.
3.1.2.2 Non-load Bearing Wall Framing and Furring
ASTM C754, except as indicated otherwise.
3.1.2.3 Furring Structural Steel Columns
Install studs or galvanized steel clips and support angles for erection of gypsum wallboard around structural steel columns in accordance with the UL Fire Resistance, design number(s) indicated and of the fire resistance rating indicated.
3.1.2.4 Z-Furring Channels with Wall Insulation
Install Z-furring channels vertically spaced not more than 24 inches o.c.
Locate Z-furring channels at interior and exterior corners in accordance with manufacturer's printed erection instructions. Fasten furring channels to masonry and concrete walls with powder-driven fasteners or hardened concrete steel nails through narrow flange of channel. Space fasteners not more than 24 inches o.c.
3.2 ERECTION TOLERANCES
Provide framing members which will be covered by finish materials such as wallboard, plaster, or ceramic tile set in a mortar setting bed, within the following limits:
a. Layout of walls and partitions: 1/4 inch from intended position;
b. Plates and runners: 1/4 inch in 8 feet from a straight line;
c. Studs: 1/4 inch in 8 feet out of plumb, not cumulative; and
d. Face of framing members: 1/4 inch in 8 feet from a true plane.
Provide framing members which will be covered by ceramic tile set in dry-set mortar, latex-portland cement mortar, or organic adhesive within the following limits:
a. Layout of walls and partitions: 1/4 inch from intended position;
b. Plates and runners: 1/8 inch in 8 feet from a straight line;
c. Studs: 1/8 inch in 8 feet out of plumb, not cumulative; and
d. Face of framing members: 1/8 inch in 8 feet from a true plane.
-- End of Section --
File details come from the government source that posted it. Updated .