ATTACHMENT C PPIs Building 362 - NAVFAC Responses.pdf
PDF 96 KB Posted
- Solicitation number
- N4008522R2727
View the file
Other files
| File | Type | Posted |
|---|---|---|
| TST Fire Alarm PPIs Building 362 Response.pdf | ||
| 1690856_Misc. Bldg. Renovations_AMENDMENT 1.docx | DOCX document | |
| ATTACHMENT C - PPI Tazewell-BGI - NAVFAC Responses.pdf | ||
| 22R2727_AMENDMENT 0001.pdf | ||
| BASE ACCESS INSTRUCTION.pdf | ||
| SecNav 5512.pdf | ||
| 1690856_362 Misc Reno_FINAL DB-RFP PACKAGE_SIGNED.pdf | ||
| ATTACHMENT C PPIs Building 362.xlsx | XLSX spreadsheet | |
| ATTACH. G BLANK Sponsor Verification Spreadsheet.xls | XLS spreadsheet | |
| va62.txt | TXT text file | |
| General Requirements BLDG 362.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REFERENCE
Page, Section, Drawing #
Part 3, Page 8, D2010 Plumbing Fixtures
Water Closets states, "Provide mounted flush valve type water closets in Toilet room 107." The existing water closet is floor mounted and clear chase spase is not available for wall mounting. Is it the intent of the RFP to provide a floor mounted water closet?
Floor mounted.
Part 3, Page 3, 5.0 Room Requirements
Entry (RM 101) - Item 3 states to replace water-damaged gypsum board. At site visit on 7/5 no water-damaged gypsum board was seen in this space. Confirm if this repair is still required.
This item has been repaired and is no longer required in the Scope of Work.
Part 3, Page 4, 5.0 Room Requirements
Shower and Drying Area (RM 111 & 112) - Item 3 states to replace existing grab bars. There are no existing grab bars in this space per site visit on 7/5. Confirm if new grab bars are required.
Provide grab bars at southwest corner shower.
Part 3, Page 4, 5.0 Room Requirements
Stairwell (Rm 106, 206, & 306) - Item 6 states to provide surface mounted LED lighting fixtures. Confirm if the new fixture quantity must meet lighting code calcualitons or to directly replace the existing quantity of 6 existing fixtures.
Per RFP light must meet uniform lighting levels per IES standards throughout the space.The lighting must meet lighting code calculations.
Part 6, Attachments, Drawing A-401
TOILET ROOM 107 - New Work Key Note #13 indicates to prep, prime, and paint metal trim and doors. Existing door 107 is a wood door in a hollow metal frame. Confirm the intent is not to paint the existing wood door.
The intent is not to paint the door.
Part 6, Attachments, Drawing A-401
TOILET ROOM 107 - New Work Key Note #9 indicates to provide grab bars. Confirm the intent for this space is to be an ADA compliant toilet room. The current toilet configuration does not appear to meet ADA requirements.
The intent is to provide an ADA compliant toilet room as much as possible without increasing the size of the bathroom. Please provide the grab bars.
ATTACHMENT A
Project Title: Miscellaneous Building Renovations
Solicitation / RFP#: N40085-22-R-2727 PPI Cut Off Date: 7/12/2022 Proposal Due: 7/22/2022
PPI No.
CONTRACTOR QUESTIONS GOVERNMENT RESPONSES
Part 3 Section D4010
The scope of work asks to replace a conventional fire alarm control panel with an addressable fire alarm control panel and provide compatible smoke detectors, duct smoke detectors, and monitor modules. The existing devices (manual pull stations, etc.) throughout the building are not addressable and will not be compatible with an addressable fire alarm control panel. Please clarify if new monitor modules are to be provided to monitor each existing zone at the new addressable fire alarm control panel, or if new monitor modules are to be provided at each existing device throughout the building to report to the new FACP. Please clarify if all smoke detectors (including elevator recall detectors and all building duct smoke detectors) are to be replaced with new compatible smoke detectors.
Provide new addressable smoke detectors and duct smoke detectors compatible with the new fire alarm control panel throughout. Provide monitor modules for each zone.