Attachment A 1733372 DWG.pdf
PDF 27 MB Posted
- Attached to
- B670 Load Bank Platform for DDGX Project
- Solicitation number
- N4008521R2653
About this file
This document appears to be Attachment A, a drawing related to Solicitation N4008521R2653 for a B670 Load Bank Platform for the DDGX Project issued by the Department of the Navy Naval Facilities Engineering Command.
The solicitation seeks a contractor to provide a B670 Load Bank Platform for the DDGX Project. The solicitation number is N4008521R2653 and the Federal Contract Opportunity ID is 5a058e5e28b54481b25b6859b76ab0f2. Interested parties can obtain more details by logging into the PIEE.eb.mil website and searching for the solicitation number. No other specifics about the required products or services, response/award dates, pricing terms, set asides, or incumbent information are provided in the available documentation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| GENERAL REQUIREMENTS FOR DDGX PROJECT.pdf | ||
| Attachment A 1733372_WP2_SPC.pdf | ||
| Attachment E SECNAV 5512 Form.pdf | ||
| Attachment C Pre-Proposal Inquiry (PPI) Form.xlsx | XLSX spreadsheet | |
| Attachment G PIEE Vendor Access Instructions.pdf | ||
| Attachment D Price Proposal Form.pdf | ||
| ATTACHMENT B WAGE DETERMINATION.pdf | ||
| Attachment F ODP Badge Access Request.xls | XLS spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FI
LE
N
AM
E:
N
:\8
-0
\C
AD
D\
W P2
\C
AD
D\
BL
DG
-1
-2
G0
.dw g
LA
YO
UT
N
AM
E:
La yo ut1 P
LO
TT
ED
: T hu rsd ay , A pr il 0
4, 7:5 5a m
US
ER
: s jac km an
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
N G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
-A
TL
AN
TI
C
AO
PS
NO
RT
H
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
EJA
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
DRAWFORM REVISION: 25 AUGUST 2020
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
D D
G (X
LB
TS
W
P 2:
E X
TE
R
IO
R
L O
A D
B A
N K
P
LA
TF
O
R M
A T
B
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
1733372
N40085-24-R-2653
3/26/2024
MRI/PJB
HPN
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY THAT THESE
DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED ENGINEER UNDER THE LAWS
OF THE STATE OF MARYLAND,
, EXPIRATION DATELICENSE No.
CGM
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
2G001
CO
VE
R
SH
EE
T
NONE
CMS SLJ JBS
12901635
29926 1/11/2026
SITE
DDG(X) LAND BASED TEST SITE (LBTS)
WP2: EXTERIOR LOAD BANK PLATFORM AT B670
VICINITY PLAN
95ARIVER
RT 76
E
H
RT
INTER
V I
R
P
R
BR
OA
D
ST
RE
ET
RT
R
W A
RT 130
ALE
ESTATE
RT 70
D
JERSEY
I L
E N
D
C
RT
M676 A
NEWINT
ER
ST
AT
E
INTER
STA
TE
INTERSTATE
RT 38
TURNPIKE
RT
JERSEY
NEW
PENNSYLVANIA
SCHUYLKILL
H
RT 1
P
E
L
I
D A
THE NAVY YARD
LOCATION PLAN
PROJECT
SITE
DR
Y D
OC
K 2
DR
Y D
OC
K 3
PIER 6A PIER 1
PIER 5 PIER 2PIER 4PIER 6
DR
Y D
OC
K 1
PIER F
BR
OA
D
ST
RE
ET
DR
Y D
OC
K 5
DR
Y D
OC
K 4
R T A
S T E 9 5
N T I
E
D E L A W A R E R I V E R
R E S E R V E B A S I N
MAIN GATE
WHARF N
ST
W
HA
RF
LIFT BRIDGE
PEARY WAY
BLDG 4
BLDG 77H
BLDG 77L
LEAGUE
ISLAND
BLVD
KITTY HAWK AVE
ADMIRAL
PHILADELPHIA NAVY YARD
PHILADELPHIA, PENNSYLVANIA
Approved for Public Release: Distribution is Unlimited Refer to PRA #NSWCPD-002656
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROT. ENG.
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
AO
PS
N
OR
TH
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
N
AV
A L
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
M
ID
-A
TL
AN
TI
C
N40085-24-R-2653
1733372
DD
G(
X)
LB
TS
W
P2 : E
XT
ER
IO
R
LO
AD
B
AN
K
PL
AT
FO
RM
A
T B6
NONE
DRAWFORM REVISION: 25 AUGUST 2020
EJA
MRI/PJB
HPN
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY
LICENSED ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 29926
EXPIRATION DATE 01/11/2026.
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
3/26/2024
C te m p Lo c a ls B
LD
G G B sj a c k m a n
( L o c a l) .r vt
CMS SLJ JBS
2G002
DR
AW
IN
G
IN
DE
X
12901636
CGM
DRAWING INDEX
SHEET NO. NAVFAC_NO DRAWING TITLE
8 - ARCHITECTURE
2A001 12901679 ARCHITECTURAL GENERAL NOTES AND ABBREVIATIONS
2AD121 12901680 FIRST FLOOR DEMOLITION PLAN
2AD122 12901681 ROOF DEMOLITION PLAN
2AD123 12901682 DEMOLITION INT ELEVATION & SECTION
2AD124 12901683 DEMOLITION DETAILS
2A101 12901684 FIRST FLOOR PLAN
2A102 12901685 ROOF PLAN
2A201 12901686 EXTERIOR ELEVATIONS
2A301 12901687 BUILDING SECTIONS
2A501 12901688 STAIR DETAILS
2A502 12901689 STAIR DETAILS
2A503 12901690 INTERIOR ELEVATION AND SECTION
2A504 12901691 DETAILS
2A505 12901692 DETAILS
11 - FIRE PROTECTION
2F001 12901693 ABBREVIATIONS, LEGEND, AND GENERAL NOTES
2FD101 12901694 FIRST FLOOR DEMOLITION PLAN
2F101 12901695 FIRST FLOOR PLAN
12 - FIRE ALARM
2FA001 12901696 ABBREVIATIONS, LEGEND, AND GENERAL NOTES
2FAD101 12901697 FIRST FLOOR DEMOLITION PLAN
2FA101 12901698 FIRST FLOOR PLAN
14 - MECHANICAL
2M001 12901699 MECHANICAL GENERAL NOTES, ABBREVIATIONS AND LEGEND
2MD101 12901700 FIRST FLOOR PLAN - DEMOLITION
2M101 12901701 FIRST FLOOR PLAN
2M501 12901702 MECHANICAL DETAILS
15 - ELECTRICAL
2E001 12901703 ELECTRICAL LEGEND AND DEFINITIONS
2E002 12901704 ELECTRICAL ABBREVIATIONS AND GENERAL NOTES
2ED101 12901705 FIRST FLOOR PLAN - DEMOLITION
2ED102 12901706 FIRST FLOOR PLAN - CONDUIT - DEMOLITION
2E101 12901707 FIRST FLOOR PLAN - LIGHITING
2E102 12901708 FIRST FLOOR PLAN - POWER
2E103 12901709 PLATFORM PLAN - LIGHTING
2E104 12901710 PLATFORM PLAN - POWER
2E105 12901711 GROUNDING PLAN
2E106 12901712 FIRST FLOOR PLAN - CONDUIT
2E501 12901713 ONE LINE DIAGRAM
2E601 12901714 ELECTRICAL DETAILS
2E701 12901715 SCHEDULES
DRAWING INDEX
SHEET NO. NAVFAC_NO DRAWING TITLE
1 - GENERAL
2G001 12901635 COVER SHEET
2G002 12901636 DRAWING INDEX
2G003 12901637 GENERAL PROJECT NOTES
2G004 12901638 PHILADELPHIA NAVY YARD ANNEX SITE MAP
2G005 12901639 OVERALL SITE PLAN - DDG(X) LBTS COORDINATION WITH BUILDING
77-87 COMPLEX PROJECTS NOT IN CONTRACT
2G006 12901640 SITE PLAN - DDG(X) LBTS COORDINATION WITH BUILDING 77-87
COMPLEX PROJECTS NOT IN CONTRACT
2G007 12901641 LIFE SAFETY PLANS
2G008 12901642 OVERALL SITE AND BUILDINGS 77H AND 670 ACCESS PLAN
2 - CIVIL
2C001 12901643 GENERAL CIVIL NOTES
2C002 12901644 CIVIL LEGEND AND ABBREVIATIONS
2C003 12901645 EROSION AND SEDIMENT CONTROL NOTES
2C101 12901646 EXISTING CONDITIONS AND DEMOLITION PLAN
2C102 12901647 SITE PLAN
2C103 12901648 EROSION AND SEDIMENT CONTROL PLAN
2C501 12901649 SITEWORK DETAILS
2C502 12901650 FENCE DETAILS
2C503 12901651 FENCE DETAILS
2C504 12901652 EROSION AND SEDIMENT CONTROL DETAILS
2C505 12901653 EROSION AND SEDIMENT CONTROL DETAILS
3 - HAZARDOUS MATERIALS
2H101 12901654 HAZARDOUS MATERIALS PLAN
6 -BUILDING GENERAL DEMOLITION
2XD101 12901655 FIRST FLOOR PLAN
2XD801 12901656 BUILDING GENERAL DEMOLITION - PHOTOGRAPHS
2XD802 12901657 BUILDING GENERAL DEMOLITION - PHOTOGRAPHS
7 - STRUCTURAL
2S001 12901658 GENERAL STRUCTURAL NOTES
2S002 12901659 GENERAL STRUCTURAL NOTES AND STRUCTURAL ABBREVIATIONS
2S003 12901660 TYPICAL STRUCTURAL DETAILS
2S004 12901661 TYPICAL STRUCTURAL DETAILS
2S005 12901662 TYPICAL STRUCTURAL DETAILS
2S006 12901663 TYPICAL STRUCTURAL DETAILS
2SD101 12901664 FLOOR PLAN - DEMOLITION
2SD102 12901665 ROOF FRAMING PLAN - DEMOLITION
2S101 12901666 FOUNDATION AND FLOOR PLAN
2S102 12901667 ROOF FRAMING PLAN
2S103 12901668 LOAD BANK PLATFORM TRUSS BOTTOM CHORD FRAMING PLAN
2S104 12901669 LOAD BANK PLATFORM TRUSS TOP CHORD FRAMING PLAN
2S201 12901670 TRUSS ELEVATIONS
2S202 12901671 TRUSS ELEVATIONS
2S203 12901672 BRACED FRAME ELEVATIONS
2S204 12901673 BRACED FRAME DETAILS
2S301 12901674 BUILDING CROSS SECTION
2S501 12901675 PILE AND PILE CAP DETAILS
2S502 12901676 SECTIONS AND DETAILS
2S601 12901677 GRAPHICAL COLUMN SCHEDULE AND DETAILS
2S602 12901678 PEDESTAL SCHEDULE AND DETAILS
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
SCALE:? ?
KEYNOTE INDICATOR
BUILDING GRID INDICATOR
BUILDING LEVEL INDICATOR
PLAN NORTH INDICATOR
TRUE NORTH
INDICATOR
SHEET CUT FROM
DETAIL NUMBER
ELEVATION INDICATOR
DETAIL INDICATOR
SECTION INDICATORSHEET WHERE SECTION IS DRAWN
SECTION NUMBER VIEW DIRECTION
SHEET WHERE ELEVATION IS DRAWN
ELEVATION NUMBER VIEW DIRECTION
SHEET WHERE DETAIL IS DRAWN
DETAIL NUMBER
VIEW TITLE INDICATOR
1SD502 DRAWING NUMBER INDICATOR
DISCIPLINE DESIGNATOR WITH OPTIONAL LEVEL 2 INDICATOR
SHEET TYPE INDICATOR
SHEET SEQUENCE INDICATOR
PLAN
NORTH
A3
XD801
PHOTO INDICATORSHEET WHERE PHOTO IS SHOWN
DETAIL NUMBER
APPROXIMATE LOCATION PHOTO WAS
TAKEN AND DIRECTION OF VIEW
WORK PACKAGE INDICATOR
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROT. ENG.
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
AO
PS
N
OR
TH
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
N
AV
A L
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
M
ID
-A
TL
AN
TI
C
N40085-24-R-2653
1733372
DD
G(
X)
LB
TS
W
P2 : E
XT
ER
IO
R
LO
AD
B
AN
K
PL
AT
FO
RM
A
T B6
NONE
DRAWFORM REVISION: 25 AUGUST 2020
EJA
MRI/PJB
HPN
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY
LICENSED ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 29926
EXPIRATION DATE 01/11/2026.
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
3/26/2024
C te m p Lo c a ls B
LD
G G B sj a c k m a n
( L o c a l) .r vt
CMS SLJ JBS
2G003
GE
NE
RA
L P
RO
JE
CT
N
OT
ES
12901637
CGM
GENERAL PROJECT NOTES
1. GENERAL NOTES APPLY TO THE ENTIRE PROJECT. GENERAL SHEET NOTES APPLY TO
THE ENTIRE SHEET ON WHICH THEY APPEAR. SHEET KEYNOTES APPLY TO THE
APPLICABLE SPECIFIC INSTANCE INDICATED.
2. THE PURPOSE OF THIS PROJECT IS TO PROVIDE A STEEL PLATFORM ABOVE BUILDING
670.
3. BUILDINGS 77H AND 670 ARE AN ACTIVE GOVERNMENT TEST FACILITY THAT WILL
REMAIN OCCUPIED DURING CONSTRUCTION. WORK MUST NOT INTERRUPT TESTING
ACTIVITIES.
4. DO NOT SCALE DRAWINGS. REFER TO DIMENSIONS INDICATED.
5. THE ENVELOPE OF BUILDINGS 77H AND 670 ARE SECURITY FEATURES AND MUST BE
MAINTAINED THROUGHOUT THE PROJECT TO ENSURE THAT UNAUTHORIZED
PERSONNEL CANNOT GAIN ACCESS INTO BUILDINGS 77H AND 670 AND THE OPERATING
SPACES. REPORT IMMEDIATELY TO THE CONTRACTING OFFICER ANY UNAUTHORIZED
OPENINGS OR INCORRECTLY SECURED OPENINGS IN THE BUILDING ENVELOPE.
6. BUILDING ENVELOPE (SIDING, ROOF, DOOR/WINDOW, ETC.) MODIFICATIONS,
TEMPORARY OR PERMANENT, MUST BE SCHEDULED AND COORDINATED WITH THE
CONTRACTING OFFICER. PROPOSED MODIFICATIONS TO THE BUILDING 77H OR BUILDING
670 ENVELOPE TO IMPLEMENT OR SUPPORT PHASING FOR THE DDG(X) PROJECT MUST
BE SUBMITTED FOR APPROVAL BY THE CONTRACTING OFFICER.
7. TAKE NECESSARY PRECAUTIONS TO ENSURE THAT ROOF OPENINGS AND OTHER
CRITICAL OPENINGS IN THE BUILDING ARE MONITORED CAREFULLY. TAKE IMMEDIATE
ACTIONS REQUIRED TO SEAL OFF SUCH OPENINGS WHEN RAIN OR OTHER
DETRIMENTAL WEATHER IS IMMINENT, AND AT THE END OF EACH WORKDAY. ENSURE
THAT THE OPENINGS ARE COMPLETELY SEALED OFF TO PROTECT MATERIALS AND
EQUIPMENT IN THE BUILDING FROM DAMAGE.
8. EXISTING DOORS IN THE BUILDING 77H OR BUILDING 670 ENVELOPE MUST BE KEPT
OPERATIONAL AND CLEAR OF OBSTRUCTIONS.
9. PHOTOGRAPHY AND AUDIO/VIDEO RECORDING IS NOT PERMITTED ON GOVERNMENT
PROPERTY AND GOVERNMENT PROPERTY MUST NOT BE PHOTOGRAPHED OR
RECORDED OTHERWISE. COORDINATE PHOTOGRAPHY REQUIREMENTS WITH THE
CONTRACTING OFFICER. REFER TO CONTRACT SPECIFICATIONS FOR ADDITIONAL
DETAILS.
10. VEHICLES ENTERING GOVERNMENT FENCELINE OR BUILDINGS MUST BE INSPECTED BY
SECURITY PRIOR TO ENTERING THE BUILDING AND MUST BE COMMERCIAL VEHICLES.
COORDINATE INSPECTIONS IN ADVANCE. REFER TO THE CONTRACT SPECIFICATIONS
FOR ADDITIONAL DETAILS.
11. PERIMETER GATES AND BUILDING DOORS MUST REMAIN CLOSED EXCEPT WHEN
PERSONNEL OR VEHICLES ARE ENTERING OR EXITING. GATES AND OVERHEAD DOORS
WILL BE OPENED BY THE GOVERNMENT AND MUST BE COORDINATED IN ADVANCE WITH
THE CONTRACTING OFFICER. PROPPING OF DOORS AND GATES IS PROHIBITED UNLESS
OTHERWISE APPROVED BY THE CONTRACTING OFFICER. REFER TO THE CONTRACT
SPECIFICATIONS FOR ADDITIONAL DETAILS.
STANDARD DRAWING SYMBOLS GENERAL DEMOLITION NOTES
1. FIELD VERIFY EXISTING DIMENSIONS.
2. WEATHERPROOF TEMPORARY OPENINGS IN THE BUILDING ENVELOPE TO PROTECT THE
INTERIOR OF BUILDING 670 FROM WEATHER FOR THE ENTIRE DURATION OF
CONSTRUCTION. DESIGN AND PROVIDE TEMPORARY WEATHERPROOFING MEASURES
FOR MINIMUM ENVIRONMENTAL LOADS IN ACCORDANCE WITH ASCE 37-14 "DESIGN
LOADS ON STRUCTURES DURING CONSTRUCTION."
3. THE CONTRACTOR IS RESPONSIBLE FOR THE MEANS AND METHODS OF DEMOLITION
AND THE INTEGRITY AND STABILITY OF THE EXISTING STRUCTURE DURING DEMOLITION
UNTIL THE WORK IS COMPLETED. DETERMINE LOCATIONS AND PROVIDE SHORING
WHERE EXISTING CONSTRUCTION TO REMAIN WILL BE AFFECTED BY DEMOLITION.
SHORING MUST BE DESIGNED, SIGNED AND SEALED BY A PROFESSIONAL ENGINEER
AND SUBMITTED TO THE CONTRACTING OFFICER FOR REVIEW AND APPROVAL.
4. THE CONTRACTOR IS RESPONSIBLE FOR MONITORING ALL COMPONENTS OF THE
EXISTING BUILDINGS IN THE VICINITY OF THE WORK DURING THE INSTALLATION OF
SHORING, DEMOLITION OF THE STRUCTURE AND THE REMOVAL OF SHORING. ANY
MOVEMENT OR DAMAGE OF THE BUILDING COMPONENTS NOTED RESULTING FROM THE
WORK MUST BE IMMEDIATELY REPORTED TO THE CONTRACTING OFFICER.
5. PROVIDE TEMPORARY WORK PLATFORMS AND DEMOLITION SHIELDS IN CLOSE
PROXIMITY TO THE UNDERSIDE OF THE ROOF TO PROTECT OCCUPANTS AND
EQUIPMENT, AND MAINTAIN BUILDING OPERATIONS DURING CONSTRUCTION.
6. PROTECT EXISTING EQUIPMENT TO REMAIN FROM DAMAGE, DEBRIS, DUST, ETC.
COORDINATE EQUIPMENT PROTECTION WITH THE CONTRACTING OFFICER.
7. CLEAN DEBRIS AND RUBBISH FROM ALL FLOORS, RAISED SURFACES, EQUIPMENT, AND
PIPING DUE TO ROOF DEMOLITION AND INSTALLATION. CLEANING MUST INCLUDE
EXTERIOR AREAS INCLUDING EXISTING GTG-A ASSEMBLY LOCATED EAST OF BUILDING
670 AND LOADBANK FARM LOCATED NORTH OF BUILDING 670.
8. THE EXISTING BUILDING 670 WOOD ROOF DECK SUPPORTS MANY EXISTING UTILITIES TO
REMAIN. TEMPORARILY SUPPORT EXISTING UTILITIES TO REMAIN PRIOR TO ROOF
DEMOLITION. PERMANENTLY SUPPORT UTILITIES DIRECTLY FROM EXISTING STEEL
ROOF FRAMING. DO NOT HANG ANY LOAD DIRECTLY FROM STEEL ROOF DECK WITHOUT
APPROVAL FROM THE MANUFACTURER AND THE CONTRACTING OFFICER.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
th
ST
RE
ET
th
ST
RE
ET
RESERVE BASIN
DELAWARE RIVER
BR
OA
D
ST
RE
ET
th
ST
RE
ET
BR
OA
D
ST
RE
ET
th
ST
RE
ET
CONSTITUTION AVENUE
th
ST
RE
ET
th
ST
RE
ET
CONSTITUTION AVENUE
FLAGSHIP AVENUE
INTREPID AVENUE
KITTY HAWK AVENUE
LE
AG
UE
IS
LA
ND
BO
UL
EV
AR
D
KITTY HAWK AVENUE
LIFT
BRIDGE
BLDG. 20
BLDG. 1029
BLDG.
BLDG.
BLDG. 643
BLDG. 20A
BLDG.
BLDG. 1
BLDG.
546BLDG.
LANGELY AVENUE
LEAGUE
ISLAND
BOULEVARD
TO PENROSE AVENUE (RTE. 291) TO INTERSTATE 95
TRUCK GATE
BLDG.
BLDG.
BL
DG
. 1
BL
DG
. 1
BL
DG
. 7
BL
DG
. 1
BL
DG
. 1
BLDG. 14
BLDG. 56
BLDG.
DiNIC'S
MERCER CAFE
BLDG.
BLDG.
BLDG.
BLDG.
77L
BLDG.
77H
BLDG. 1081
BLDG. 1082
ROUSE BOULEVARD
BLDG.
BLDG.
BL
DG
. 5
ADMIRAL PEARY WAY
OL
D
TH
S
TR
EE
T
TH
S
TR
EE
T
'S'
LOT
BLDG.
BLDG.
BLDG. 480
PHILADELPHIA NAVY YARD ANNEX SITE MAPA1
GENERAL SHEET NOTES
SHEET LEGEND
CJK CJK WCG
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
SI
TE
M
AP
AS NOTED
2G004
29926 1/11/2026
CONTRACTOR'S
HAUL ROUTE
PROPOSED CONTRACTOR'S HAUL ROUTE
FI
LE
N
AM
E:
N
:\8
-0
\C
AD
D\
W P2
\C
AD
D\
BL
DG
-1
-2
G0
.dw g
LA
YO
UT
N
AM
E:
La yo ut1 P
LO
TT
ED
: T hu rsd ay , A pr il 0
4, 9:3 5a m
US
ER
: c kid d
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
N G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
-A
TL
AN
TI
C
AO
PS
NO
RT
H
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
EJA
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
DRAWFORM REVISION: 25 AUGUST 2020
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
D D
G (X
LB
TS
W
P 2:
E X
TE
R
IO
R
L O
A D
B A
N K
P
LA
TF
O
R M
A T
B
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
1733372
N40085-24-R-2653
3/26/2024
MRI/PJB
HPN
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY THAT THESE
DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED ENGINEER UNDER THE LAWS
OF THE STATE OF MARYLAND,
, EXPIRATION DATELICENSE No.
CGM
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
PROJECT SITE
BUILDING 29 PASS OFFICE
1. REFER TO SHEET 2G003 FOR GENERAL PROJECT NOTES.
2. REFER TO SHEET 2G008 FOR LOCATION OF THE CONTRACTOR'S
CONSTRUCTION TRAILER(S) AND LAYDOWN SPACE.
3. REFER TO SHEET 2G008 FOR DESIGNATED CONTRACTOR'S BUILDING 77H
INGRESS AND EGRESS LOCATIONS.
4. CONTRACTOR MUST CLEAN HAUL VEHICLES AND TIRES OF SEDIMENT PRIOR
TO EXITING THE PROJECT SITE. ANY SEDIMENT DEPOSITED ON PUBLIC
ROADWAYS MUST BE REMOVED IMMEDIATELY AND RETURNED TO THE
CONSTRUCTION SITE. WASHING THE ROADWAY OR SWEEPING DEPOSITS
INTO ROADWAY DRAINAGE COURSES IS PROHIBITED.
5. VEHICLE INSPECTIONS BY THE NAVY POLICE WILL BE CARRIED OUT AT A
LOCATION IN THE PHILADELPHIA NAVY YARD ANNEX AND ARE REQUIRED FOR
ALL VEHICLES ENTERING A NAVY FENCE LINE OR NAVY BUILDING.
COORDINATE VEHICLE INSPECTIONS WITH THE CONTRACTING OFFICER
PRIOR TO MOBILIZATION.
NATIONAL REGISTER BOUNDARY
CONTRIBUTING STRUCTURE WITHIN
NATIONAL REGISTER BOUNDARY
NON-CONTRIBUTING STRUCTURE WITHIN
NATIONAL REGISTER BOUNDARY
PROPERTY LINE
BLDG 77L
KITTY HAWK AVENUE
ADMIRAL PEARY WAY
T
H S
TR
EE
T
W
AR
NO
CK
S
TR
EE
T
BLDG 77H
BLDG 87
BLDG
BLDG
BLDG 79
BLDG
BLDG 75
FLAGSHIP DRIVE
BLDG
D E L A W A R E R I V E R
OL
D
T
H S
TR
EE
T
LE
AG
UE
IS
LA
ND
B
OU
LE
VA
RD
BLDG 80 COOLING
TOWER
GTG's
A
B
BLDG
KITTY HAWK AVENUE
ADMIRAL PEARY WAYBLDG 776
487485
1 TYP.
1 TYP.
1 TYP.
3 4
FI
LE
N
AM
E:
N
:\8
-0
\C
AD
D\
W P2
\C
AD
D\
BL
DG
-1
-2
G0
.dw g
LA
YO
UT
N
AM
E:
La yo ut1 P
LO
TT
ED
: T hu rsd ay , A pr il 0
4, 7:5 6a m
US
ER
: s jac km an
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
N G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
-A
TL
AN
TI
C
AO
PS
NO
RT
H
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
EJA
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
DRAWFORM REVISION: 25 AUGUST 2020
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
D D
G (X
LB
TS
W
P 2:
E X
TE
R
IO
R
L O
A D
B A
N K
P
LA
TF
O
R M
A T
B
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
1733372
N40085-24-R-2653
3/26/2024
MRI/PJB
HPN
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY THAT THESE
DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED ENGINEER UNDER THE LAWS
OF THE STATE OF MARYLAND,
, EXPIRATION DATELICENSE No.
CGM
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
2G005
OV
ER
AL
L S
IT
E
PL
AN
DD
G( X)
LB
TS
C
OO
RD
IN
AT
IO
N W
IT
H
BU
ILD
IN
G
-8
7 C
OM
PL
EX
P
RO
JE
CT
S
NO
T
IN
C
ON
TR
AC
T
AS NOTED
CJK CJK WCG
12901639
29926 1/11/2026
GRAPHIC SCALE
BUILDING 77-87 COMPLEX PROJECTS NOT IN CONTRACT
OVERALL SITE PLAN - DDG(X) LBTS COORDINATION WITH
SCALE: 1" = 100'-0"A1
GENERAL SHEET NOTES
1. REFER TO SHEET 2G003 FOR GENERAL PROJECT NOTES.
2. REFER TO SHEET 2G004 FOR DESIGNATED HAUL ROUTE THROUGH THE NAVY
YARD.
3. REFER TO SHEET 2G004 FOR LOCATION OF THE CONTRACTOR'S
CONSTRUCTION TRAILER(S) AND LAYDOWN SPACE.
4. REFER TO SHEET 2G008 FOR DESIGNATED CONTRACTOR'S BUILDING 77H
AND BUILDING 670 INGRESS AND EGRESS LOCATIONS.
5. ITEMS THAT HAVE BEEN IDENTIFIED ON THIS PLAN AS 'NOT IN CONTRACT'
ARE OTHER PROJECTS PLANNED FOR THE BUILDING 77/87 COMPLEX. THESE
ITEMS ARE SHOWN IN AN APPROXIMATE WAY AND FOR COORDINATION
PURPOSES IN THE EVENT THAT CONSTRUCTION SCHEDULES/ACTIVITIES
SHOULD OVERLAP WITH THIS PROJECT. THE ITEMS SHOWN ARE BASED ON
DESIGN INFORMATION AND DO NOT REFLECT AS-BUILT CONDITIONS.
1. BUILDING 77H PERIMETER SECURITY IMPROVEMENTS (NOT IN CONTRACT).
2. PROJECT LOCATION.
3. APPROXIMATE LOCATION OF LARGE REPAIR PROJECT (NOT IN CONTRACT).
4. APPROXIMATE LOCATION OF SITE DEVELOPMENT FOR FUTURE PROJECT
(NOT IN CONTRACT).
5. MAIN SITE ACCESS EAST SIDE OF BUILDING 670 - CONTRACTOR PERSONNEL.
SHEET LEGEND
EXISTING NSWCPD PERIMETER FENCE
PROPERTY LINE
SHEET KEYNOTES
FENCE (NOT IN CONTRACT)
DROP ARM BARRIER (NOT IN CONTRACT)
0 100' 200'
SCALE: 1" = 100'-0"
50'
TURNSTILE (NOT IN CONTRACT)
BOLLARD / BOLLARD ARRAY (NOT IN CONTRACT)
SWING GATES (NOT IN CONTRACT)
AG
UE
IS
LA
ND
B
OU
LE
VA
RD
BLDG 77H
BLDG 670
GTG 'B'
SHED
BLDG 77L
FI
LE
N
AM
E:
N
:\8
-0
\C
AD
D\
W P2
\C
AD
D\
BL
DG
-1
-2
G0
.D wg
L
AY
OU
T
NA
ME
: L ay ou t1
P
LO
TT
ED
: T hu rsd ay
, A pr il 0 4, 9:1
5a m
US
ER
: c kid d
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
N G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
-A
TL
AN
TI
C
AO
PS
NO
RT
H
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
EJA
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
DRAWFORM REVISION: 25 AUGUST 2020
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
D D
G (X
LB
TS
W
P 2:
E X
TE
R
IO
R
L O
A D
B A
N K
P
LA
TF
O
R M
A T
B
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
1733372
N40085-24-R-2653
3/26/2024
MRI/PJB
HPN
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY THAT THESE
DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED ENGINEER UNDER THE LAWS
OF THE STATE OF MARYLAND,
, EXPIRATION DATELICENSE No.
CGM
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
GENERAL SHEET NOTES
GRAPHIC SCALE
1. ITEMS THAT HAVE BEEN IDENTIFIED ON THIS PLAN AS 'NOT IN CONTRACT'
ARE OTHER PROJECTS PLANNED FOR THE BUILDING 77/87 COMPLEX. THESE
ITEMS ARE SHOWN IN AN APPROXIMATE WAY AND FOR COORDINATION
PURPOSES IN THE EVENT THAT CONSTRUCTION SCHEDULES/ACTIVITIES
SHOULD OVERLAP WITH THIS PROJECT. THE ITEMS SHOWN ARE BASED ON
DESIGN INFORMATION AND DO NOT REFLECT AS-BUILT CONDITIONS.
0 20' 40'
SCALE: 1" = 20'-0"
10'
2G006
SI
TE
P
LA
N
- D
DG
(X
) L
BT
S
CO
OR
DI
NA
TI
ON
W
IT
H
BU
ILD
IN
G
-8
7 C
OM
PL
EX
P
RO
JE
CT
S
NO
T
IN
C
ON
TR
AC
T
AS NOTED
CJK CJK WCG
12901640
29926 1/11/2026
BUILDING 77-87 COMPLEX PROJECTS NOT IN CONTRACT
SITE PLAN - DDG(X) LBTS COORDINATION WITH
SCALE: 1" = 20'-0"A1
SHEET KEYNOTES
1. LOAD BANK PLATFORM. REFER TO STRUCTURAL DRAWINGS FOR
INFORMATION.
2. FUTURE PROJECT (NOT IN CONTRACT).
3. FENCE ENCLOSURE AND GATE FOR ACCESS CONTROL TO STAIRS.
4. BUILDING 77H PERIMETER SECURITY IMPROVEMENTS (NOT IN CONTRACT).
5. STAIRS FOR PLATFORM ACCESS. SEE SECTION A3/A-502.
6. FENCE AND GATE. SEE CIVIL DRAWINGS.
A
292827262524232221201918
A2
A1
A3
A4
21.4 22.5 23.5 24.6 25.5 26.4 27.5 28.6
A.2 X
*NOTE: OCCUPANT DISCHARGE LOAD INCLUDES
OCCUPANTS DISCHARGING FROM THE MAIN BUILDING
THROUGH BUILDING 670.
EXIT TRAVEL PATH (ARROWS
INDICATE DIRECTION OF TRAVEL)
COMMON PATH OF TRAVEL (ARROWS
INDICATE DIRECTION OF TRAVEL)
EGRESS START POINTX
LOAD
CAP
EGRESS CAPACITY
BUILDING EXIT LOCATION
STORAGE/UTILITY (300 GROSS SQFT/PERSON)(NO HATCH)
A
29282726252423222120
A2
A1
A3
A4
21.4 22.5 23.5 24.6 25.5 26.4 27.5 28.6
2 3 4
X196' TRAVEL DISTANCE
266' TRAVEL DISTANCE
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROT. ENG.
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
AO
PS
N
OR
TH
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
N
AV
A L
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
M
ID
-A
TL
AN
TI
C
N40085-24-R-2653
1733372
DD
G(
X)
LB
TS
W
P2 : E
XT
ER
IO
R
LO
AD
B
AN
K
PL
AT
FO
RM
A
T B6
AS NOTED
DRAWFORM REVISION: 25 AUGUST 2020
EJA
MRI/PJB
HPN
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY
THAT THESE DOCUMENTS WERE PREPARED OR
APPROVED BY ME, AND THAT I AM A DULY
LICENSED ARCHITECT UNDER THE LAWS OF THE
STATE OF MARYLAND, LICENSE NO. 17784
EXPIRATION DATE 07/23/2024.
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
3/26/2024
C te m p Lo c a ls B
LD
G A B s ja ck m a n
( L o c a l) .r vt
BTF AJM ML
2G007
LIF
E
SA
FE
TY
P
LA
NS
12901641
CGM
SCALE: 1/16" = 1'-0"B2 FIRST FLOOR LIFE SAFETY PLAN
1. EGRESS PATH THROUGH EXISTING BUILDING, 419' TO MAIN BUILDING EXIT.
2. EXISTING EGRESS ONTO HIGH ROOF.
3. EXISTING LADDER FROM 670 ROOF TO 77H ROOF.
4. METAL LADDER FROM PLATFORM DOWN TO 670 ROOF AS SECOND MEANS OF
EGRESS FROM PLATFORM PER NFPA 101 40.2.2.9.
OCCUPANCY/USE FACTOR LEGEND
CODE SUMMARY
SHEET LEGEND SHEET KEYNOTES GENERAL SHEET NOTES
CODE DATA: BLDG. 670
1) TYPE OF CONSTRUCTION:
IBC 2021: TYPE IIIB NFPA 220 2021: TYPE III(200)
2) OCCUPANCY CLASSIFICATION(S):
IBC: FACTORY (F-1) USE / BUSINESS (B) USE - NON-SEPARATED, MIXED USE (IBC SECTION 508.3)
NFPA 101: BUSINESS OCCUPANCY / INDUSTRIAL OCCUPANCY - MIXED OCCUPANCY (NFPA 101
SECTION 6.1.14.3)
NFPA 101: SPECIAL-PURPOSE INDUSTRIAL (NFPA 101, SECTION 40.1.2.1.2)
3) CLASSIFICATIONS OF HAZARDS:
NFPA 101 6.2.2.3: ORDINARY HAZARD
4) CATEGORIES OF WORK:
NFPA 101 43.2.2.1.4: MODIFICATION
IEBC 603: ALTERATION - LEVEL 3
BLDG. 670: 8,000 SF
5) BUILDING HEIGHT/AREA INFORMATION:
* BUILDING HEIGHT AND AREA ANALYSIS IS NOT REQUIRED FOR PROJECT AND IS INCLUDED HEREIN
FOR REFERENCE ONLY
BLDG. 77 COMPLEX:
BLDG. 77H IS PART OF MULTI-BUILDING COMPLEX; ANALYZED AS A SINGLE STRUCTURE IN
ACCORDANCE WITH IBC SECTION 503.1.2.
COMPLEX INCLUDES BLDGS. 77H, 77L, 87, 756, 771, 670 and 776
ALLOWABLE BLDG. AREA: (IBC SECTION 506.3)
ALLOWABLE AREA FACTOR - N/A (MEETS IBC SECTION 507.5, UNLIMITED AREA)
FRONTAGE INCREASE: NOT USED (IBC SECTION 506.3)
ALLOWABLE AREA: UNLIMITED (MEETS IBC SECTION 507.5)
BUILDING DIMENSIONS:
BLDG. 670 EX. AREA: 8,000 SF
OVERALL BLDG. 77 COMPLEX: 442,100 SF (MEETS ALLOWABLE AREA)
ALLOWABLE BLDG. HEIGHT: (IBC SECTION 504.3)
ALLOWABLE BLDG. HEIGHT: NOT LIMITED (IBC SECTION 503.1.1)
ACTUAL BLDG. HEIGHT: 80 FT (MEETS ALLOWABLE HEIGHT)
ALLOWABLE BLDG. STORIES: (IBC SECTION 504.4)
ALLOWABLE BLDG. STORIES: 3 (W/ SPRINKLER INCREASE)
UNLIMITED BLDG. AREA RESTRICTION: 2 STORIES (IBC SECTION 507.5)
ACTUAL BLDG. STORIES: 2 (MEETS ALLOWABLE STORIES)
6) OCCUPANT LOAD:
*OCCUPANCY ANALYZED FOR AFFECTED PORTIONS OF BLDG. 670 AND NEW PLATFORMS ONLY
OCCUPANT LOAD FACTORS: (NFPA 101 TABLE 7.3.1.2)
OCCUPANT LOAD: 27 PEOPLE
* OCCUPANT LOAD FACTOR NOT ASSIGNED PER NFPA 101 - USE NEEDS APPROVAL BY AHJ.
PLATFORM OCCUPANT LOAD: 3 PEOPLE
* OCCUPANT LOAD FACTOR NOT ASSIGNED PER NFPA 101 - USE NEEDS APPROVAL BY AHJ
7) EGRESS SUMMARY:
*MEANS OF EGRESS ANALYZED FOR AFFECTED PORTIONS OF BUILDIUNG 670 AND NEW
PLATFORM ONLY.
EGRESS DOOR WIDTH:
MINIMUM: NFPA 101 T7.3.3.1 = (0.2"/OCC) OR 32" AND NFPA 101 40.2.3.1 = 32"
PROVIDED: 32"
NUMBER OF EXITS:
MINIMUM: NFPA 101 40.2.4.1 = 2 EXITS
PROVIDED: 2 (ONE TO EXTERIOR, ONE TO 77H)
TRAVEL DISTANCE:
PERMITTED: NFPA 101 40.2.6.1 (SPECIAL PURPOSE INDUSTRIAL) = 400 FT, PROVIDED: 80 FT
DEAD END:
PERMITTED: NFPA 101 40.2.5.1 = 50 FT, PROVIDED: N/A
COMMON PATH
PERMITTED: NFPA 101 40.2.5.1 = 100 FT, PROVIDED: N/A
8) FIRE PROTECTION SYSTEM REQUIREMENTS:
REQUIRED CODE REFERENCE
AUTOMATIC SPRINKLERS: YES NFPA 13 & UFC 3-600-01 SECTION 9-7.2.1.1
FIRE EXTINGUISHERS: YES NFPA 101 SECTION 38.3.5
STANDPIPE SYSTEM: NO UFC 3-600-01 SECTION 9-10.2
FIRE ALARM SYSTEM: YES UFC 3-600-01 SECTION 9-18.1
SMOKE CONTROL SYSTEM: NO UFC 3-600-01 SECTION 9-20
0 32'16'8'
1/16" = 1'-0"SCALE:
PLAN
NORTH
1. SCOPE OF WORK FOR THIS PROJECT INCLUDES INSTALLATION OF METAL EQUIPMENT
PLATFORM ABOVE BUILDING WITH 4 STEEL COLUMNS COMING THROUGH BUILDING 670 AND
REPLACING EXISTING ROOF INCLUDING WOOD SHEATHING, INSULATION AND ROOF
MEMBRANE.
2. THIS PLAN IS PROVIDED TO SHOW LIFE SAFETY AND EGRESS COMPLIANCE FOR THE
OCCUPIED PORTION OF THE BUILDING.
APPLICABLE CODES AND STANDARDS
• INTERNATIONAL BUILDING CODE - 2021
• INTERNATIONAL EXISTING BUILDING CODE - 2021
• NFPA 101, LIFE SAFETY CODE - 2021
• NFPA 1, FIRE CODE - 2021
• UFC 1-200-01 DOD BUILDING CODE (GENERAL BUILDING
REQUIREMENTS), 01 SEPTEMBER 2022 CHANGE 2, 12 JUNE
• UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR
FACILITIES, WITH CHANGE 6, 6 MAY 2021
• UFC 4-010-01 DOD MINIMUM ANTITERRORISM STANDARDS
FOR BUILDINGS, 12 DEC. 2018 WITH CHANGE 1, 19 AUGUST
• UFC 4-010-06 CYBERSECURITY OF FACILITY-RELATED
CONTROL SYSTEMS, 12 JANUARY 2018
• NFPA 10, STANDARD FOR PORTABLE EXTINGUISHERS -
• NFPA 13, STANDARD FOR THE INSTALLATION OF
SPRINKLER SYSTEMS - 2022
• IMC INTERNATIONAL MECHANICAL CODE - 2021
• ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS - 2015
SCALE: 1/16" = 1'-0"C2 ROOF PLAN LIFE SAFETY PLAN
SY
M
DE
SC
RI
PT
IO
N
DA
TE
BLDG 77L
KITTY HAWK AVENUE
ADMIRAL PEARY WAY
T
H S
TR
EE
T
W
AR
NO
CK
S
TR
EE
T
BLDG 77H
BLDG 87
BLDG
BLDG
BLDG 79
BLDG
BLDG 75
FLAGSHIP DRIVE
BLDG
D E L A W A R E R I V E R
OL
D
T
H S
TR
EE
T
LE
AG
UE
IS
LA
ND
B
OU
LE
VA
RD
BLDG 80 COOLING
TOWER
GTG's
A
B
BLDG
KITTY HAWK AVENUE
ADMIRAL PEARY WAYBLDG 776
487485
5 TYP.
FUEL FARM
10,000 SF 1
TYP.
X
8 10
X
FI
LE
N
AM
E:
N
:\8
-0
\C
AD
D\
W P2
\C
AD
D\
BL
DG
-1
-2
G0
.dw g
LA
YO
UT
N
AM
E:
La yo ut1 P
LO
TT
ED
: T hu rsd ay , A pr il 0
4, 7:5 7a m
US
ER
: s jac km an
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
N G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
-A
TL
AN
TI
C
AO
PS
NO
RT
H
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
EJA
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
DRAWFORM REVISION: 25 AUGUST 2020
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
D D
G (X
LB
TS
W
P 2:
E X
TE
R
IO
R
L O
A D
B A
N K
P
LA
TF
O
R M
A T
B
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
1733372
N40085-24-R-2653
3/26/2024
MRI/PJB
HPN
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
PROFESSIONAL CERTIFICATION. I HEREBY CERTIFY THAT THESE
DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED ENGINEER UNDER THE LAWS
OF THE STATE OF MARYLAND,
, EXPIRATION DATELICENSE No.
CGM
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
OVERALL SITE AND BUILDINGS 77H AND 670 ACCESS PLAN
SCALE: 1" = 100'-0"A1
2G008
OV
ER
AL
L S
IT
E
AN
D
BU
ILD
IN
GS
H
AN
D
0 A
CC
ES
S
PL
AN
AS NOTED
CMS CMS JBS
12901642
29926 1/11/2026
GENERAL SHEET NOTES
GRAPHIC SCALE
0 100' 200'
SCALE: 1" = 100'-0"
50'
1. REFER TO SHEET 2G003 FOR GENERAL PROJECT NOTES.
2. THE NSWCPD PERIMETER FENCE IS A SECURITY FEATURE AND MUST BE
MAINTAINED AT ALL TIMES THROUGHOUT THE PROJECT TO ENSURE THAT
NEITHER PERSONNEL NOR VEHICLES CAN GAIN UNAUTHORIZED ACCESS
TO NSWCPD'S FACILITIES.
3. FENCE GATES IN THE NSWCPD PERIMETER FENCE MAY ONLY BE OPENED
BY GOVERNMENT PERSONNEL OR ACCESS CONTROL PERSONNEL (ACP).
THE ACP OR GOVERNMENT PERSONNEL MUST GUARD THE GATE DURING
THE ENTIRE TIME THE GATE IS UN-SECURED. THE GATE MUST BE
SECURED IMMEDIATELY FOLLOWING ITS USE, UNLESS OTHERWISE
PERMITTED BY THE COMMAND SECURITY DIRECTOR.
4. THE LOCATION OF THE CONTRACTOR'S CONSTRUCTION TRAILER(S) AND
LAYDOWN SPACE MUST BE COORDINATED WITH THE CONTRACTING
OFFICER.
5. REFER TO SHEET 2G004 FOR DESIGNATED HAUL ROUTE THROUGH THE
NAVY YARD.
6. CONTRACTOR IS RESPONSIBLE FOR PROTECTING AND SECURING ALL
MATERIAL IN LAYDOWN AREAS AND GOVERNMENT ASSUMES NO
RESPONSIBILITY FOR DAMAGED OR STOLEN MATERIAL BEING STORED.
7. ANY SEDIMENT DEPOSITED ON PUBLIC ROADWAYS MUST BE REMOVED
IMMEDIATELY AND RETURNED TO THE CONSTRUCTION SITE. WASHING
THE ROADWAY OR SWEEPING DEPOSITS INTO ROADWAY DRAINAGE
COURSES IS PROHIBITED.
8. EXCESS EXCAVATED SOIL, ROCK, EARTH MATERIALS, OR CONCRETE
RUBBLE MUST BE TEMPORARILY STOCKPILED ON-SITE. STOCKPILES MUST
BE NO GREATER THAN 20 FEET IN HEIGHT AND HAVE A SLOPE NO
GREATER THAN 2:1. PROVIDE COMPOST FILTER SOCKS TO COMPLETELY
SURROUND THE TEMPORARY STOCKPILE.
9. INSTALL ALL BMP'S IN ACCORDANCE WITH THE COMMONWEALTH OF
PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION EROSION
AND SEDIMENT CONTROL MANUAL, LATEST EDITION.
10. VEHICLE INSPECTIONS BY THE NAVY POLICE WILL BE CARRIED OUT AT A
LOCATION IN THE PHILADELPHIA NAVY YARD ANNEX AND ARE REQUIRED
FOR ALL VEHICLES ENTERING A NAVY FENCE LINE OR NAVY BUILDING.
COORDINATE VEHICLE INSPECTIONS WITH THE CONTRACTING OFFICER
PRIOR TO MOBILIZATION.
SHEET KEYNOTES
1. DESIGNATED AREA WITHIN S-LOT FOR CONTRACTOR'S CONSTRUCTION
TRAILER(S), AND MATERIAL STORAGE AND STAGING. COORDINATE EXACT
LOCATION AND AVAILABLE SQUARE FOOTAGE (SF) OF AREA WITH
CONTRACTING OFFICER.
2. APPROXIMATE BOUNDARY OF S-LOT (GOVERNMENT PROPERTY).
3. NSWCPD PERIMETER FENCE.
4. EXISTING EXIT ONLY TURNSTILE IN NSWCPD PERIMETER FENCE.
5. EXISTING VEHICLE GATE OPENING IN NSWCPD PERIMETER FENCE.
6. BUILDING 77H ACCESS - CONTRACTOR PERSONNEL.
7. BUILDING 670 AND 77H ACCESS - CONTRACTOR VEHICLE INGRESS AND
EGRESS (OVERHEAD DOOR, APPROXIMATELY 16 FEET WIDE BY 21 FEET
TALL).
8. VEHICLE ACCESS ROUTE TO BUILDING 670 THROUGH BUILDING 77H.
9. BUILDING 670 AND 77H EGRESS ONLY.
10. EMERGENCY EGRESS PATH THROUGH BUILDING 670. PROVIDE OVERHEAD
PROTECTION DURING ROOFING WORK FOR EMERGENCY EGRESS PATH.
11. BUILDING 670 ACCESS - CONTRACTOR VEHICLE INGRESS AND EGRESS.
SHEET LEGEND
NSWCPD PERIMETER FENCE
PROPERTY LINE
VEHICLE GATE OPENING IN PERIMETER FENCE
TURNSTILE IN PERIMETER FENCE
PERSONNEL ACCESS - EGRESS ONLY
PERSONNEL ACCESS - INGRESS AND EGRESS
X VEHICLE ACCESS - INGRESS AND EGRESS
APPROXIMATE LAYDOWN AREA BOUNDARY
N
AM
E:
N
:\8
-0
\C
AD
D\
W P2
\C
AD
D\
BL
DG
-1
-2
C0
.dw g
LA
YO
UT
N
AM
E:
La yo ut1 P
LO
TT
ED
: T hu rsd ay , A pr il 0
4, 7:5 7a m
US
ER
: s jac km an
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
N G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
-A
TL
AN
TI
C
AO
PS
NO
RT
H
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
EJA
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
DRAWFORM REVISION: 25 AUGUST 2020
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
D D
G (X
LB
TS
W
P 2:
E X
TE
R
IO
R
L O
A D
B A
N K
P
LA
TF
O
R M
A T
B
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
1733372
N40085-24-R-2653
3/26/2024
MRI/PJB
HPN
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
CGM
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
2C001
G
EN
ER
AL
C
IV
IL
N
O
TE
S
NONE
CJK CJK WCG
12901643
GENERAL CIVIL NOTES
PENNSYLVANIA ONE CALL SYSTEM
LOCATE ALL UNDERGROUND STRUCTURES AND UTILITIES, SUCH AS WATER MAINS, SEWERS,
TELEPHONE, GAS AND ELECTRIC CONDUITS, ETC. AND ABOVE GROUND UTILITIES, WHICH
MAY BE ENCOUNTERED DURING CONSTRUCTION OPERATIONS. TEST HOLES SHALL BE DUG
TO DETERMINE THE POSITION OF THE UNDERGROUND STRUCTURES AND UTILITIES, OR
ARRANGE WITH THE OWNERS OF SUCH UNDERGROUND STRUCTURES AND UTILITIES TO
ASSIGN A REPRESENTATIVE TO MARK THE LOCATIONS. PAY THE COST OF DIGGING TEST
HOLES AND LIKEWISE PAY THE COST OF THE SERVICE OF THE REPRESENTATIVES OF THE
OWNER OF SUCH UTILITIES FOR LOCATING THE SAID UTILITIES. THE COST OF DETERMINING
THE LOCATIONS IS TO BE INCLUDED IN THE PRICES BID. THE LOCATIONS AND DEPTH OF
EXISTING STRUCTURES AND UTILITIES AS SHOWN IN THE CONTRACT DOCUMENTS IS SIMPLY
FOR GUIDANCE AND HAVE NOT BEEN FIELD LOCATED. SINCE THE INFORMATION IS AS
FURNISHED BY THE RESPECTIVE UTILITIES, OR TAKEN FROM NON-AS-BUILT PLANS. THE
ENGINEER IS NOT RESPONSIBLE FOR THE ACCURACY OF THE PLANS IN THIS RESPECT. ALL
DESIGNERS AND CONTRACTORS UTILIZING THIS PLAN AND THE INFORMATION CONTAINED
THEREON ARE CAUTIONED TO COMPLY WITH THE REQUIREMENTS OF PENNSYLVANIA ACT
287 ENTITLED "UNDERGROUND UTILITY LINE PROTECTION."
PA ACT 287
1. A PORTION OF EXISTING TOPOGRAPHY, UTILITIES, AND PHYSICAL FEATURES SHOWN ARE BASED ON FIELD SURVEYS PERFORMED DECEMBER 2016
AND DECEMBER 2019 BY WHITMAN, REQUARDT AND ASSOCIATES, LLP., BALTIMORE, MARYLAND. VERTICAL CONTROL IS BASED ON THE NORTH AMERICAN VERTICAL DATUM 1988 (NAVD88). HORIZONTAL CONTROL IS BASED ON THE PENNSYLVANIA SOUTH COORDINATE SYSTEM, NORTH AMERICAN DATUM 1983 (NAD83) AND WAS ESTABLISHED FROM SURVEY CONTROL STATION NOS. JU2216 AND JU0704. THE REMAINDER OF EXISTING TOPOGRAPHY AND PHYSICAL FEATURES SHOWN SUPPLEMENTING THE FIELD SURVEYS WAS OBTAINED BY AERIAL PHOTOGRAMMETRY FLOWN IN FEBRUARY 2020. SUPPLEMENTAL UTILITY INFORMATION SHOWN WAS TAKEN FROM AVAILABLE RECORD DRAWINGS PROVIDED BY THE GOVERNMENT
AND UTILITY PROVIDERS.
2. FIELD VERIFY ACTUAL SITE CONDITIONS PRIOR TO THE START OF ANY WORK. THERE IS NO WARRANTY OR GUARANTEE ON THE COMPLETENESS OR CORRECTNESS OF THE EXISTING CONDITIONS INFORMATION. ANY DISCREPANCY FOUND MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
CONTRACTING OFFICER PRIOR TO THE START OF ANY WORK.
3. THE LOCATIONS OF UNDERGROUND UTILITIES SHOWN IN THESE DRAWINGS ARE APPROXIMATE. THE LOCATION AND EXTENT OF EXISTING UTILITY FACILITIES ARE SHOWN BASED UPON INFORMATION AVAILABLE AT THE TIME OF DESIGN. NEITHER THE GOVERNMENT NOR THE DESIGNER WARRANTS OR GUARANTEES THE ACCURACY OR COMPLETENESS OF INFORMATION PROVIDED BY THESE DRAWINGS.
4. CONTACT THE PUBLIC WORKS DIVISION AND PENNSYLVANIA ONE CALL (1-800-242-1776 OR AT 8-1-1) TO ALLOW MARKING OF EXISTING BURIED UTILITIES
AT LEAST 72 HOURS (THREE WORKING DAYS) PRIOR TO EXCAVATION.
5. EXISTING UNDERGROUND UTILITIES IN THE WORK AREA MUST BE POSITIVELY IDENTIFIED USING GROUND PENETRATING RADAR (GPR), ELECTROMAGNETIC, SONIC, OR OTHER TYPES OF EQUIPMENT BY A THIRD PARTY, INDEPENDENT, PRIVATE UTILITY LOCATING COMPANY, IN ADDITION TO ANY STATION LOCATING SERVICE SUCH AS PENNSYLVANIA ONE CALL AND COORDINATED WITH THE PUBLIC WORKS DIVISION. ANY MARKING MADE DURING THE UTILITY INVESTIGATION MUST BE MAINTAINED THROUGHOUT THE DURATION OF THE CONTRACT.
6. WHENEVER CONTRACT WORK INVOLVES CHIPPING, SAW CUTTING, OR CORE DRILLING THROUGH CONCRETE, BITUMINOUS ASPHALT OR OTHER IMPERVIOUS SURFACES, THE THIRD PARTY, INDEPENDENT, PRIVATE LOCATING COMPANY MUST LOCATE UTILITY DEPTH BY USE OF GROUND PENETRATING RADAR (GPR), X-RAY, BORE SCOPE OR ULTRASOUND PRIOR TO THE START OF DEMOLITION AND CONSTRUCTION. OUTAGES TO ISOLATE UTILITY SYSTEMS MUST BE USED IN CIRCUMSTANCES WHERE UTILITIES ARE UNABLE TO BE POSITIVELY IDENTIFIED. THE USE OF HISTORICAL
DRAWINGS DOES NOT ALLEVIATE THE CONTRACTOR FROM MEETING THIS REQUIREMENT.
7. TAKE NECESSARY PRECAUTIONS TO PROTECT EXISTING UTILITIES. AT CONTRACTOR'S EXPENSE, IMMEDIATELY REPAIR ANY DAMAGE TO UTILITIES.
THE CONTRACTOR WILL BE REQUIRED TO, AND AGREES TO, COMPLY WITH THE PROVISIONS OF THE GOVERNMENT, CITY, STATE, AND UTILITY PROVIDER FOR UNDERGROUND DAMAGE PREVENTION AND HEREBY AGREES TO HOLD THE GOVERNMENT HARMLESS AGAINST ANY LOSS, DAMAGES AND CLAIMS OF ANY NATURE WHATSOEVER ARISING OUT OF FAILURE TO COMPLY WITH SAID PROVISIONS.
8. VERIFY THE SIZE AND ELEVATION OF UNDERGROUND UTILITIES TO BE CROSSED PRIOR TO TRENCHING.
9. MAINTAIN ACCESS TO VALVES AND HYDRANTS FOR GOVERNMENT, PWD, AND EMERGENCY SERVICES PERSONNEL.
10. REPLACE VALVE BOXES, RISER OR LIDS LOST OR DAMAGED DURING CONSTRUCTION, WITH NO ADDITIONAL PAYMENT.
11. PERFORM WORK IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS, INCLUDING PENNSYLVANIA DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS (AS REFERENCED), LATEST EDITION; PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION; CITY OF PHILADELPHIA DEPARTMENT OF STREETS STANDARD CONSTRUCTION ITEMS DATED 1997; CITY OF PHILADELPHIA WATER DEPARTMENT STANDARD DETAILS AND SPECIFICATIONS FOR SEWERS DATED 1985; CITY OF PHILADELPHIA WATER DEPARTMENT WATER MAIN STANDARD DETAILS AND
CORROSION CONTROL SPECIFICATIONS DATED 1985 AS APPLICABLE.
12. VERIFY ALL EXISTING UTILITY INVERTS AND CLEARANCES FROM NEW WORK PRIOR TO START OF ANY WORK.
13. THESE DRAWINGS DO NOT INCLUDE THE NECESSARY COMPONENTS FOR CONSTRUCTION SAFETY. ALL CONSTRUCTION MUST BE DONE IN COMPLIANCE WITH THE US ARMY CORPS OF ENGINEERS EM 385, 2014 VERSION, AND THE MOST CURRENT VERSION OF OSHA STANDARDS AND/OR
REGULATIONS.
14. NOTIFY THE CONTRACTING OFFICER OF ANY DEVIATION TO THIS PLAN PRIOR TO ANY CHANGE BEING MADE. ANY CHANGE IN THIS PLAN WITHOUT THE WRITTEN AUTHORIZATION FOR SAID CHANGE FROM THE CONTRACTING OFFICER WILL BE THE RESPONSIBILITY OF THE CONTRACTOR OR
SUB-CONTRACTOR.
15. IN THE CASE OF A DISCREPANCY BETWEEN THE SCALED AND THE FIGURED DIMENSIONS SHOWN ON THESE PLANS, THE FIGURED DIMENSION WILL
GOVERN.
16. SAWCUT ALL JOINTS WHERE THE NEW CONSTRUCTION MEETS THE EXISTING PAVEMENT.
17. PIPE ELEVATIONS REFER TO INVERTS UNLESS NOTED OTHERWISE.
18. ALL STORM DRAIN APPURTENANCES MUST REMAIN FUNCTIONAL DURING CONSTRUCTION.
19. FINISHED GRADING/PAVEMENT MUST PROVIDE POSITIVE DRAINAGE TOWARDS STORM DRAINAGE FEATURES. GRADING MUST NOT RESULT IN LOW
SPOTS THAT HOLD WATER.
20. ALL POWER AND UTILITY OUTAGES MUST BE COORDINATED WITH THE CONTRACTING OFFICER AT LEAST FOUR (4) WEEKS IN ADVANCE. POWER AND UTILITY OUTAGES MAY NEED TO BE PLANNED TO OCCUR DURING SECOND AND/OR THIRD SHIFTS OR WEEKENDS TO MINIMIZE DISRUPTION TO
PRODUCTION.
21. ALL CONTRACTOR VEHICLES REQUIRING ACCESS TO THE NSWCPD COMPOUND ARE SUBJECT TO INSPECTIONS.
22. THE CONTRACTOR MUST REQUEST AND RECEIVE APPROVAL FROM NSWCPD FOR ALL DEMOLITION/CONSTRUCTION ACTIVITIES THAT IMPACT NSWCPD VEHICLE PATHS, PEDESTRIAN PATHWAYS AND ACCESS OR LAYDOWN AREA INSIDE THE NSWCPD FENCE LINE AND OUTSIDE DESIGNATED WORK ZONES. STEEL PLATE BRIDGING AND SHORING CAPABLE OF WITHSTANDING HS-20 TRAFFIC LOADING IS REQUIRED ON ALL OPEN EXCAVATIONS THAT IMPACT NSWCPD VEHICLE PATHS. ADEQUATE FALL PROTECTION SYSTEMS MUST BE PROVIDED AT ALL OPEN EXCAVATIONS THAT IMPACT PEDESTRIAN
PATHWAYS AND ACCESS.
23. ALL NSWCPD ITEMS WITHIN DESIGNATED WORK ZONES THAT ARE NOT TO BE DISPOSED OF BY THE CONTRACTOR AND NEED TO BE REMOVED FROM THE SITE MUST BE COORDINATED WITH THE CONTRACTING OFFICER A MINIMUM OF TEN (10) WORKING DAYS IN ADVANCE.
24. THE LOCATION OF THE CONTRACTOR'S CONSTRUCTION TRAILER(S) MUST BE COORDINATED WITH THE CONTRACTING OFFICER.
10.51MEAN HIGHER HIGH WATER (MHHW)
MEAN HIGH WATER (MHW)
MEAN SEA LEVEL (MSL)
NORTH AMERICAN
VERTICAL DATUM 1988 (NAVD'88)
MEAN LOW WATER (MLW)
MEAN LOWER LOW WATER (MLLW)
STATION DATUM
STATION
DATUMDESCRIPTION
10.11
7.31
6.92
4.01 3.82
0.00
NAVD'88
DATUM
3.59 3.19
0.39
0.00
-2.91 -3.10
-6.92
TIDAL DATUM ELEVATIONS
PNSY
DATUM
6.80
3.89
3.79
0.60 0.40
0.00
PHILADELPHIA NAVY
SHIPYARD DATUM (PNSY)
-1.75EXTREME LOW WATER (ELW)
NOTES:
1 ELEVATIONS SHOWN FOR STATION DATUM ARE DERIVED FROM NOAA TIDAL STATION
ID 8545240, PHILADELPHIA PA.
2 ELEVATIONS SHOWN FOR PHILADELPHIA NAVY YARD (PNSY) DATUM WERE RECEIVED
BY THE GOVERNMENT AND REPRESENTS THE VERTICAL DATUM HISTORICALLY USED
FOR CONSISTENCY IN REPORTING SCHEDULED UNDERWATER INSPECTIONS
PERFORMED AT THE NAVY YARD.
N
AM
E:
N
:\8
-0
\C
AD
D\
W P2
\C
AD
D\
BL
DG
-1
-2
C0
.dw g
LA
YO
UT
N
AM
E:
La yo ut1 P
LO
TT
ED
: T hu rsd ay , A pr il 0
4, 7:5 7a m
US
ER
: s jac km an
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
N G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
-A
TL
AN
TI
C
AO
PS
NO
RT
H
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
EJA
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
DRAWFORM REVISION: 25 AUGUST 2020
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
D D
G (X
LB
TS
W
P 2:
E X
TE
R
IO
R
L O
A D
B A
N K
P
LA
TF
O
R M
A T
B
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
1733372
N40085-24-R-2653
3/26/2024
MRI/PJB
HPN
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
CGM
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
2C002
C
IV
IL
L
EG
EN
D A
N D
A
BB
R
EV
IA
TI
O N
S
NONE
CJK CJK WCG
12901644
ABBREVIATIONS
EXISTING WATER LINE
EXISTING SANITARY SEWER
8.50
8"SS
EXISTING ELECTRIC DUCTBANK
8"W
EXISTING STORM DRAIN MANHOLE
EXISTING SANITARY SEWER MANHOLE
EXISTING ELECTRIC MANHOLE
EXISTING TELEPHONE MANHOLE
EXISTING STORM DRAIN INLET
EXISTING WATER VALVE
EXISTING FIRE HYDRANT
EXISTING STREET LIGHT
CIVIL SYMBOLS LEGEND
EXISTING GAS LINE
Wx Wx
SSx SSx
MH EXISTING UNKNOWN/UNIDENTIFIED MANHOLE
6" Gx Gx
EXISTING ELECTRIC JUNCTION BOX
EXISTING GAS METERGM
EXISTING SIGN
EXISTING SURVEY TRAVERSE STATION
EXISTING ABANDONED RIVER WATER LINEABAND 8" RW
TS
EXISTING GAS VALVE
EXISTING GAS TEST STATION
@ AT
A COMPRESSED AIR
ABAND ABANDONED
ADDL ADDITIONAL
ADJ ADJACENT
ABV ABOVE
APPROX APPROXIMATE
ATFP ANTI-TERRORISM/FORCE PROTECTION
AVB ACTIVE VEHICLE BARRIER
AVE AVENUE
AWG AMERICAN WIRE GAUGE
BLDG BUILDING
BC BOTTOM OF CURB
BM BENCHMARK
BMP'S BEST MANAGEMENT PRACTICES
CB CATCH BASIN
CBRE COLDWELL BANKER RICHARD ELLIS
CI CAST IRON
CIP CAST IRON PIPE
CL CENTERLINE
CLR CLEAR
CO CLEAN OUT
COL COLUMN
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CNDT CONDUIT
COMM TELECOMMUNICATIONS
COMP COMPACTED
CONC CONCRETE
COND CONDENSATE
CONT CONTINUED
D DRAIN PIPE
DEG DEGREE
DIA DIAMETER
DIP DUCTILE IRON PIPE
DNL DID NOT LOCATE
DOD DEPARTMENT OF DEFENSE
DOS DEPARTMENT OF STATE
DWG DRAWING
E EAST
EA EACH
EJB ELECTRIC JUNCTION BOX
ELEC ELECTRIC
EL ELEVATION
ELL ELBOW
EOI END OF INVESTIGATION
EX EXISTING
E&S EROSION AND SEDIMENT
CONTROL
EW EACH WAY
FDC FIRE DEPARTMENT CONNECTION
FF EL FINISH FLOOR ELEVATION
FH FIRE HYDRANT
FLG FLANGE
FNDN FOUNDATION
FO FUEL OIL
FOB FACE OF BUILDING
FOST FUEL OIL STORAGE TANK
FS FILTER SOCK
FT FEET/FOOT
G NATURAL GAS
GALV GALVANIZED
GM GAS METER
GPR GROUND PENETRATING RADAR
GTG GAS TURBINE GENERATOR
HB HORIZONTAL BEND
HDPE HIGH DENSITY POLYETHYLENE
HH HANDHOLE
HORIZ HORIZONTAL
HMA HOT MIX ASPHALT
I INLET
IP INLET PROTECTION
IN INLET
INV INVERT
LBES LAND BASED ENGINEERING TEST SITE
LOD LIMIT OF DISTURBANCE
LOW LIMIT OF WORK
LF LINEAR FOOT
MAC MACADAM
MAX MAXIMUM
MH MANHOLE
MIN MINIMUM
MJ MECHANICAL JOINT
MP MANAGEMENT PRACTICE
MVIT MOBILE VEHICLE INSPECTION TEAM
N NORTH
N/A NOT APPLICABLE
NFL NOT FIELD LOCATABLE
NMCI NAVY MARINE CORPS INTRANET
NSWCPD NAVAL SURFACE WARFARE CENTER -
PHILADELPHIA DIVISION
OC ON CENTER
OD OUTSIDE DIAMETER
OVHD OVERHEAD
PA PENNSYLVANIA
PE PLAIN END
PENNDOT PENNSYLVANIA DEPARTMENT OF
TRANSPORTATION
PGW PHILADELPHIA GAS WORKS
PIDC PHILADELPHIA INDUSTRIAL
DEVELOPMENT CORPORATION
PIV POST INDICATOR VALVE
PNSY PHILADELPHIA NAVAL SHIPYARD
POV PRIVATELY OWNED VEHICLE
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
PWD PHILADELPHIA WATER DEPARTMENT
R RADIUS
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
REQD REQUIRED
RW DELAWARE RIVER WATER
RWCS RIVER WATER COOLING SYSTEM
S SOUTH
SAN SANITARY SEWER
SCH SCHEDULE
SD STORM DRAIN MANHOLE
SF SQUARE FEET
SHT SHEET
SP STEEL PLATE
SQ SQUARE
SQ YD SQUARE YARD
SS STAINLESS STEEL
SSM SITE SECURITY MANAGER
ST STREET
STA STATION
STD STANDARD
STL STEEL
STM STEAM
SW ELECTRIC SWITCHGEAR
SWM STORMWATER MANAGEMENT
T&B TOP & BOTTOM
TC TOP OF CURB
TCP TERRA COTTA PIPE
TELE TELEPHONE
TELECOM TELECOMMUNICATIONS
THK THICK
T/D TOP OF DUCTBANK
T/G TOP OF GRATE
T/F TOP OF FRAME AND COVER
T/N TOP OF NUT ON VALVE
T/P TOP OF PIPE
T/PL TOP OF PLATFORM
T/S TOP OF CONCRETE SLAB/PAD
T/WALL TOP OF WALL
TRAV TRAVERSE
TYP TYPICAL
UGND UNDERGROUND
UNKN UNKNOWN
UON UNLESS OTHERWISE NOTED
UTP UNSHIELDED TWISTED PAIR
VB VERTICAL BEND
VERT VERTICAL
VOL VOLUME
W WATER / WEST / WITH
WM WATER METER
WP WORKING POINT
WQv WATER QUALITY VOLUME
WV WATER VALVE
XFMR TRANSFORMER
9 EXISTING CONTOUR (1 FOOT INTERVALS)
EXISTING ABANDONED PIPEABAND 8" PIPE
EXISTING GUARD POST
EXISTING STORM DRAIN12"SD
SDx SDx
EXISTING POST INDICATOR VALVE
EUX EUX
EXISTING COMMUNICATIONS DUCTBANKC X C X
E
S
T
D
EXISTING UTILITY POLE
EXISTING GUY WIRE
WV EXISTING WATER VALVE VAULT
EXISTING UNKNOWN UTILITYUK UK
EXISTING PWD-OWNED WATER LINE
EXISTING PWD-OWNED SANITARY SEWER8"SS (PWD)
8"W (PWD)
Wx Wx
SSx SSx
100 YEAR FLOOD PLAINFP FP
EXISTING CHAIN LINK FENCE LINEX X X X
EXISTING SIDEWALK/CONCRETE PAD
EXISTING BUILDING
EXISTING CONCRETE JERSEY BARRIERS
EXISTING STEEL PLATESP
EXISTING PEDESTRIAN TURNSTILE
EXISTING SPOT ELEVATION
EXISTING STEAM AND CONDENSATE LINES12"STM/4"COND
EXISTING ABANDONED WATER LINEABAND 8" W
EXISTING ABANDONED FUEL OIL PIPEABAND 2 1/2" FOIL
EXISTING PLUGGED/CAPPED PIPE
EXISTING FIRE PROTECTION WATER LINE (NAVY FIRE LOOP)8"W (FIRE)
Wx Wx
EXISTING ABANDONED STEAM AND CONDENSATE LINESABAND 12"STM/4"COND
EJB
NEW CHAIN LINK FENCEXXX
EXISTING FUEL OIL6" FOIL
FO EXISTING FUEL OIL MANHOLE
EXISTING FLAGPOLE
HORIZONTAL AND VERTICAL CONTROL LOCATIONS
KI
TT
Y H
AW
K
A
VE
NU
E
BLDG
77L
LEAGUE ISLAND BOULEVARD
BLDG 77H
BLDG 670
BLDG 87
BLDG
756 AD
MI
RA
L
PE
AR
Y
W
AY
PLAN
NOT TO SCALE
VERTICAL BM 'A'
' ' CUT ON CONC.
LIGHT POLE BASE
EL:11.21'
VERTICAL BM 'C'
' ' CUT ON CONC.
LIGHT POLE BASE
EL:11.12'
VERTICAL BM 'B'
' ' CUT ON CONC.
LIGHT POLE BASE
EL:11.45'
ENLARGED PLANS
NOT TO SCALE
NOTE:
VERTICAL CONTROL IS BASED ON THE NORTH AMERICAN VERTICAL DATUM 1988 (NAVD88). HORIZONTAL CONTROL IS BASED ON THE PENNSYLVANIA SOUTH COORDINATE SYSTEM, NORTH AMERICAN DATUM 1983 (NAD83) AND WAS ESTABLISHED FROM SURVEY CONTROL STATION NOS. JU2216 AND JU0704.
POINT NORTHING EASTING ELEV.
JU2216 204022.6839 2656022.7611 16.9882
JU0704 215958.2940 2719845.8443 50.6003
24.82'
24.
73'
STORM
DRAIN
INLET
CURB &
GUTTER
3.9 1'
LEAGUE ISLAND BLVD
STORM
DRAIN
INLET
WRA311
37.60'
20.10'
STREET
LIGHT
CO
NC
W
AL
K
19.32'
KI
TT
Y
HA
W K
AV
E
CU
RB
G
UT
TE
R
LIGHT
POLE
BM 'A'
FIRE
HYDRANT
VERTICAL BM 'A'
12.60'
42.13'
.75
LEAGUE ISLAND BLVD
CURB & GUTTER
ELEC
BOX
LIGHT POLE
BM 'B'
VERTICAL BM 'B' VERTICAL BM 'C'
5.0 0' 28.70'
.25
' LIGHT POLE
BM 'C'
CURB & GUTTER
CHAIN LINK FENCE
PARKING LOT
CONC. WALK
WRA311
MAGNETIC NAIL
N:212846.4562 E:2693484.6398
EL:7.60'
PARKING LOT
STREET
LIGHT
WRA702
MAGNETIC NAIL
N:212378.4780 E:2692975.1140
EL:7.34'
WRA701
REBAR AND CAP
N:212427.2980 E:2693251.0430
EL:7.74'
WRA702
X X X X
E
ADMIRAL PEARY WAY
CURB & GUTTER
5.70' 8.42'
CONC.
WALK
ELEC
MH STREET
LIGHT
SEAWALL
ORNAMENTAL RAILING
DELAWARE RIVER
.42
WRA701
X X X X
E
ADMIRAL PEARY WAY
CURB & GUTTER
19.60'
59.25'CONC.
WALK
ELEC MH STREET
LIGHT
SEAWALL
ORNAMENTAL
RAILING
DELAWARE RIVER
.25
X X FENCE
TURNSTILE
BUILDING 77H PERIMETER SECURITY IMPROVEMENTS (NOT IN CONTRACT):
VERTICAL BM 'D'
TOP OF NW BOLT
ON COLUMN B8
EL:9.57'
NEW EXTERIOR LOAD BANK PLATFORM
NEW CHAIN LINK SWING GATE
N
AM
E:
N
:\8
-0
\C
AD
D\
W P2
\C
AD
D\
BL
DG
-1
-2
C0
.dw g
LA
YO
UT
N
AM
E:
La yo ut1 P
LO
TT
ED
: T hu rsd ay , A pr il 0
4, 7:5 7a m
US
ER
: s jac km an
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
RI
N G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
-A
TL
AN
TI
C
AO
PS
NO
RT
H
NO
RF
OL
K
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V
IR
GI
NI
A
EJA
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
DRAWFORM REVISION: 25 AUGUST 2020
CHK
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
OF
EPROJECT NO.:
Whitman, Requardt & Associates, LLP 801 South Caroline Street, Baltimore, Maryland 21231
D D
G (X
LB
TS
W
P 2:
E X
TE
R
IO
R
L O
A D
B A
N K
P
LA
TF
O
R M
A T
B
PH
ILA
DE
LP
HI
A
NA
VY
Y
AR
D
AN
NE
X
PH
ILA
DE
LP
HI
A, P
EN
NS
YL
VA
NI
A
1733372
N40085-24-R-2653
3/26/2024
MRI/PJB
HPN
DE
PA
RT
ME
NT
O
F
TH
E
NA
VY
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
CGM
APPROVED BY: CARLOS HERNANDEZ ALICEA, PDC
BRANCH HEAD, PWD PENNSLYVANIA PER EMAIL
STANDARD EROSION AND SEDIMENT CONTROL NOTES
1. ALL EARTH DISTURBANCES, INCLUDING CLEARING AND GRUBBING AS WELL AS CUTS AND FILLS SHALL BE DONE IN ACCORDANCE WITH
THE APPROVED E&S PLAN. A COPY OF THE APPROVED DRAWINGS (STAMPED, SIGNED AND DATED BY THE REVIEWING AGENCY) MUST BE AVAILABLE AT THE PROJECT SITE AT ALL TIMES. THE PHILADELPHIA WATER DEPARTMENT (PWD) STORMWATER PLAN REVIEW SHALL BE NOTIFIED OF ANY CHANGES TO THE APPROVED PLAN PRIOR TO IMPLEMENTATION OF THOSE CHANGES. THE PWD STORMWATER PLAN REVIEW MAY REQUIRE A WRITTEN SUBMITTAL OF THOSE CHANGES FOR REVIEW AND APPROVAL AT ITS DISCRETION.
2. AT LEAST 7 DAYS PRIOR TO STARTING ANY EARTH DISTURBANCE ACTIVITIES, INCLUDING CLEARING AND GRUBBING, THE OWNER AND/OR OPERATOR SHALL INVITE ALL CONTRACTORS, APPROPRIATE MUNICIPAL OFFICIALS, THE E&S PLAN PREPARER, AND A PWD STORMWATER PLAN REVIEW INSPECTOR (MR. JOSEPH WHITFIELD 215-516-9674) TO AN ON-SITE PRECONSTRUCTION MEETING.
3. AT LEAST 3 DAYS PRIOR TO STARTING ANY EARTH DISTURBANCE ACTIVITIES, OR EXPANDING INTO AN AREA PREVIOUSLY UNMARKED, THE PENNSYLVANIA ONE CALL SYSTEM INC. SHALL BE NOTIFIED AT 1-800-242-1776 FOR THE LOCATION OF EXISTING UNDERGROUND
UTILITIES.
4. ALL EARTH DISTURBANCE ACTIVITIES SHALL PROCEED IN ACCORDANCE WITH THE SEQUENCE PROVIDED ON THE PLAN DRAWINGS.
DEVIATION FROM THAT SEQUENCE MUST BE APPROVED IN WRITING BY PWD AND PA DEP PRIOR TO IMPLEMENTATION.
5. AREAS TO BE FILLED ARE TO BE CLEARED, GRUBBED, AND STRIPPED OF TOPSOIL TO REMOVE TREES, VEGETATION, ROOTS AND OTHER
OBJECTIONABLE MATERIAL.
6. CLEARING, GRUBBING, AND TOPSOIL STRIPPING SHALL BE LIMITED TO THOSE AREAS DESCRIBED IN EACH STAGE OF THE CONSTRUCTION SEQUENCE.