P947_RFP_Part_3_5_Room_Requirements_Air_Compressor_Room.pdf

PDF 93 KB Posted

Attached to
P947 Welding and Body Repair Shop Facility, Marine Corps Logistics Base, Albany, Georgia.
Solicitation number
N4008519R9000
Issued by

About this file

P947_RFP_Part_3_5_Room_Requirements_Air_Compressor_Room.pdf

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Welding & Body Shop Facility Work Order: 1365028 Marine Corps Logistics Base, Albany, GA

Air Compressor Room Space Characteristics

Function/adjacencies: House air compressor equipment.

Special Dimensions:

Ideal Plan Dimensions: 150 SF; Sized for equipment and service space.

Minimum Ceiling Height: Maximum height for required equipment and service.

Acoustics: Provide a room enclosure with a minimum STC 56. Provide room construction per UFC 3‐450‐01, Noise and Vibration Control.

Number of Occupants: N/A Other/Special Requirements: Locate this room next to the Mechanical Room.

Uniformat Section

Description Qty Size Specific Requirements

A103001 Slab on Grade SF SF

B203001 Solid Double Exterior Doors

Minimum 6’‐0” x 7’‐0”

Galvanized metal insulated door and galvanized metal frame with removable mullions. Size door opening to be large enough allow removal of equipment from the room with little difficulty. Egress per fire code.

B203008 Exterior Door Hardware Stainless steel finish, grade one series 1000, mortise‐ type.

C302010 Floor Finishes Sealed Concrete with caulk sealer between slab and wall. No base required.

C301001 Concrete Wall Finish CMU.

C303090 Ceiling Finishes Painted exposed structure.

C304001 Interior Coatings SF SF Painted CMU / Painted GWB where indicated. Paint suitable in accordance with Master Painter Institute (MPI) standards for the interior architectural surface being finished.

D20 Plumbing AR AR

D202002 Valves & Hydrants 1 AR Provided wall mounted hose bib in this room in accordance with ESR D202002.

D203003 Floor Drains AR AR Provide floor drains in this room in accordance with

ESR D203003.

D209005 Compressed Air System 1 Provide compressed air system in accordance with

ESR D209005.

D30 HVAC AR AR Provide heating and ventilation only in accordance with UFC 3‐410‐01 and ESR D30.

Welding & Body Shop Facility Work Order: 1365028 Marine Corps Logistics Base, Albany, GA

Air Compressor Room Space Characteristics

Function/adjacencies: House air compressor equipment.

Special Dimensions:

Ideal Plan Dimensions: 150 SF; Sized for equipment and service space.

Minimum Ceiling Height: Maximum height for required equipment and service.

Acoustics: Provide a room enclosure with a minimum STC 56. Provide room construction per UFC 3‐450‐01, Noise and Vibration Control.

Number of Occupants: N/A Other/Special Requirements: Locate this room next to the Mechanical Room.

Uniformat Section

Description Qty Size Specific Requirements

D304007 Exhaust Systems AR AR Provide an exhaust system in accordance with ESR D304007.

D305002 Unit Heaters AR AR Provide unit heaters in accordance with ESR D305002.

D40 Fire Protection Provide per section D40.

D50 Electrical Distribution

Provide per section D50.

Provide GFI electrical outlets, minimum one (1) per wall and within 25 feet of equipment, lighting and other electrical devices.

D5020 Lighting and Branch Wiring

Provide dedicated 480V 3 phase power circuit for compressor. Provide dedicated power circuit for HVAC, exhaust, unit heaters, and other required equipment, if provided.

D503001 Telecommunication Systems

Provide one telecommunication drop, where required for any system in the room, including DDC system.