G m

CCCCCCCCCCCCC

ROOF HATCH

C C C

PC E7

E8

M3-31

EF-4

M3-33

29610

NO

RT

H CAROL INA

PR

OFESS I ONA L

SEAL

E

N G I N E E

R

R O

B E

R T S C O T T P E R

K I

N S

320-C Midland Parkway, Summerville, SC, 29485

ENGINEERING | ARCHITECTURE

CEMS Project No: Project Manager: R. Alvar

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY

MARINE CORPS BASE

CAMP LEJEUNE, NORTH CAROLINA

NAVAL FACILITIES ENGINEERING COMMAND

SIZE CODE IDENT NO. NAVFAC DRAWING NO.

SCALE: SPEC. SHEET OF

E1 80091

300 N. 3rd St., Suite 110, Wilmington, NC, 28401 843.875.3637 910.363.1640

CONSTR. CONTR. NO.:

ISSUE DATE:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF

THE CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICE HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME

CONTRACTOR TO THE CONTRACTING OFFICER.

DISCLOSURE OF INFORMATION

AS NOTED

C. COOPER

N. HEBEL

S. PERKINS

INTERIOR & EXTERIOR REPAIRS AT BEQ

M440

ATTIC ELECTRICAL NEW WORK PLAN

E-102

133 14528 JULY 2017

60020346

15153G

N40085-17-B-0019

05-17-0019

NEW WORK KEYNOTES:

NO. DESCRIPTION

E7 CONNECT NEW RECEPTACLE TO UNSWITCHED LEG OF ATTIC LIGHTING CIRCUIT.

E8 PROVIDE PHOTOCELL MOUNTED ON ROOF PEAK AND CONNECT TO EXTERIOR

LIGHTING CONTROL PANEL. SEE DETAIL ON E-501.

1. SEE SHEET E-001 FOR GENERAL NOTES AND LEGEND.

2. SEE SHEET E-501 FOR LIGHTING FIXTURE SCHEDULE.

GENERAL NOTES:

SCALE: 3/32" = 1'-0"1 ATTIC ELECTRICAL NEW WORK PLAN

PLAN NORTH

SCALE: 3/32"=1'-0"

816 16

GRAPHIC SCALE

,W

V

V

CH-1

MECHANICAL

BUILDING

A501

H1-(1,3,5)

EXISTING

PANEL 'BB'

E12

HEAT TRACE

BB-(28,30)

HHWP-1

BB-(11,13,15)

HHWP-1

BB-(17,19,21)

PANEL 'H1'

T1

STEP-DOWN TRANSFORMER

G

MECHANICAL

BUILDING

A501

EXISTING

PANEL 'BB'

E13

EXISTING

PANEL 'BB'

MECHANICAL

BUILDING

A501

29610

NO

RT

H CAROL INA

PR

OFESS I ONA L

SEAL

E

N G I N E E

R

R O

B E

R T S C O T T P E R

K I

N S

320-C Midland Parkway, Summerville, SC, 29485

ENGINEERING | ARCHITECTURE

CEMS Project No: Project Manager: R. Alvar

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY

MARINE CORPS BASE

CAMP LEJEUNE, NORTH CAROLINA

NAVAL FACILITIES ENGINEERING COMMAND

SIZE CODE IDENT NO. NAVFAC DRAWING NO.

SCALE: SPEC. SHEET OF

E1 80091

300 N. 3rd St., Suite 110, Wilmington, NC, 28401 843.875.3637 910.363.1640

CONSTR. CONTR. NO.:

ISSUE DATE:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF

THE CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICE HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME

CONTRACTOR TO THE CONTRACTING OFFICER.

DISCLOSURE OF INFORMATION

AS NOTED

C. COOPER

N. HEBEL

S. PERKINS

INTERIOR & EXTERIOR REPAIRS AT BEQ

M440

ENLARGED ELECTRICAL NEW WORK PLANS

E-103

134 14528 JULY 2017

60020347

15153G

N40085-17-B-0019

15-17-0019

SCALE: 1/4" = 1'-0"2

ENLARGED MECHANICAL BUILDING/CHILLER

YARD NEW WORK POWER PLAN

NEW WORK KEYNOTES:

NO. DESCRIPTION

E12 PROVIDE NEW RECEPTACLE AND CONNECT TO EXISTING 120V

RECEPTACLE CIRCUIT INSIDE MECHANICAL BUILDING.

E13 PROVIDE NEW LIGHT FIXTURE WITH INTEGRAL PHOTOCELL AND

CONNECT TO EXISTING EXTERIOR LIGHITNG CIRCUIT.

SCALE: 1/4" = 1'-0"3

ENLARGED MECHANICAL BUILDING/CHILLER

YARD NEW WORK LIGHTING PLAN

GENERAL NOTES:

1. SEE SHEET E-001 FOR GENERAL NOTES AND LEGEND.

2. SEE SHEET E-501 FOR LIGHTING FIXTURE SCHEDULE.

3. SEE E-001 FOR COMMUNICATIONS AND CATV NOTES.

PLAN NORTH

04 8268 02 4 8134

SCALE: 1/4"=1'-0"

GRAPHIC SCALE

SCALE: 1/4" = 1'-0"1

ENLARGED MECHANICAL BUILDING

DEMOLITION PLAN

O S

O S3

G G

G

Gm m

OS

OS

V

J

OS

O S

O S

O S

G

G G

G m m m

OS

OS

V

J

OS

O S

O S3

O S

3 G

G G G

G G m m

G m

OSOS

V

J

OS

E-402

Y

F2

F1

Y

Y

Y

Y Y

Y

PANEL 'K'

LOUNGE

CORRIDOR

COMM ROOM

LAUNDRY

CENTRAL STAIR

EF-2

UH-2

C

C

C

D

LGT

BB

B B

BB

B B

G

G

AHU-2C

K-1 K-23

K-(38,40,42)

HAND

DRYER K-3

A

A

A

X1

X1

UP

DOWN

K-1

K-1

K-1

K-26

K-24 K-23

K-23

K-(8,10)

K-(12,14)

K-(16,18)

K-(20,22)

K-2

K-4

K-6

K-23 K-7

K-23

K-9

K-23

K-7

K-7

K-5

X1

Y

F2

F1

Y

Y

Y

Y

Y

PANEL 'Q'

LOUNGE

CORRIDOR

STORAGE

LAUNDRY

CENTRAL STAIR

EF-3

UH-3

FPB3B-21

D

C

G

G

AHU-3C

Q-1 Q-13

Q-(38,40,42)

HAND

DRYER Q-3

B B

B B

BB

B B

A

X1

A

A

X1

C

C

C

C

Y

DOWN

Q-1

Q-1

Q-1

Q-7 Q-13

Q-13

Q-13

Q-13

Q-13

Q-13

Q-7

Q-7

Q-5

Q-(28,30)

Q-11

Q-9

Q-2

Q-4

Q-6

Q-(8,10)

Q-(12,14)

Q-(16,18)

Q-(20,22)

Q-26

Q-24

X1

E-402

F2

Y

Y Y

Y

Y

Y

PANEL 'C'

PANEL 'D'

CORRIDOR

DUTY

NEW LAUNDRY ROOM

LAUNDRY

CENTRAL STAIR

120119

EF-1

UH-1

FPB1B-01

C

C

G

G

AHU-1C

C-1

C-19

C-(38,40,42) C-26C-1

C-(8,10)

C-(12,14)

C-(16,18)

C-(20,22)

C-2

C-4

C-6 C-1C-24

C-19

C

B

B

FACP

XTMR

B B

B B

D

HAND

DRYER C-3

BB

B

B

A

A

A

C

C

X1

X1

UP

C-1

C-1

C-5

C-7

C-7

C-15

C-13C-11C-9

C-17

C-17

C-19

C-19

C-19

C-19

C-19

C-21

C-(28,30)

C-23 C-25

C-19

C-19

C-7

29610

NO

RT

H CAROL INA

PR

OFESS I ONA L

SEAL

E

N G I N E E

R

R O

B E

R T S C O T T P E R

K I

N S

320-C Midland Parkway, Summerville, SC, 29485

ENGINEERING | ARCHITECTURE

CEMS Project No: Project Manager: R. Alvar

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY

MARINE CORPS BASE

CAMP LEJEUNE, NORTH CAROLINA

NAVAL FACILITIES ENGINEERING COMMAND

SIZE CODE IDENT NO. NAVFAC DRAWING NO.

SCALE: SPEC. SHEET OF

E1 80091

300 N. 3rd St., Suite 110, Wilmington, NC, 28401 843.875.3637 910.363.1640

CONSTR. CONTR. NO.:

ISSUE DATE:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF

THE CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICE HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME

CONTRACTOR TO THE CONTRACTING OFFICER.

DISCLOSURE OF INFORMATION

AS NOTED

C. COOPER

N. HEBEL

S. PERKINS

INTERIOR & EXTERIOR REPAIRS AT BEQ

M440

ENLARGED ELECTRICAL NEW WORK PLANS

E-401

135 14528 JULY 2017

60020348

15153G

N40085-17-B-0019

05-17-0019

SCALE: 1/4" = 1'-0"

E-101

ENLARGED SECOND FLOOR ELECTRICAL NEW

WORK PLAN

SCALE: 1/4" = 1'-0"

E-101

ENLARGED THIRD FLOOR ELECTRICAL NEW

WORK PLAN

1. SEE SHEET E-501 FOR LIGHTING FIXTURE SCHEDULE.

2. ALL 'X1' AND 'Y' TYPE FIXTURES ARE TO BE FED FROM UNSWITCHED LEG OF NEAREST LIGHTING

CIRCUIT. MOUNT 'X1' TYPE FIXTURES LOCATED IN CORRIDOR TO WALL ABOVE DOOR.

3. PROVIDE ALL COMMUNICATIONS CABLING, EQUIPMENT, AND JACK SET ASSEMBLIES

ASSOCIATED WITH OFFICE AREAS AND AREAS SERVICED BY BASE TELEPHONE SYSTEM PER

CAMP LEJEUNE COMMUNICATIONS SPECIFICATION 27 10 00. ALL WORK SHALL BE DONE BY A

QUALIFIED COMMUNICATIONS SUBCONTRACTOR. CONTACT CONSTRUCTION MANAGER

REGARDING ANY COMMUNICATIONS QUESTIONS.

4. ALL AHU UNITS SHALL BE PROVIDED WITH DEDICATED CONTROLS CIRCUIT, CONDUITM AND

WIRING. SEE PANEL SCHEDULES ON SHEETS E-601 AND E-602 FOR CIRCUITING. COORDINATE

FINAL CONNECTION WITH MANUFACTURER'S REQUIREMENTS.

5. FACP TO HAVE TWO GREEN CAT 6 CABLES TO COMM ROOM.

6. DRYER CIRCUIT TO BE 2#10, #10N, #10G 3/4"C.

GENERAL NOTES:

SCALE: 1/4" = 1'-0"

E-101

ENLARGED FIRST FLOOR ELECTRICAL NEW

WORK PLAN

PLAN NORTH

04 8268 02 4 8134

SCALE: 1/4"=1'-0"

m

O S

G G m

C

D D

VFPB

SLEEPING ROOM

208V

42"42"

CKT-B

CKT-A

CKT-A

E9

NEW LAUNDRY ROOM

D-(29,31)D-(1,3)

D-(5,7)

D-(9,11)

D-(13,15)

D-(17,19)

D-(21,23)

D-(25,27)

D-(33,35)

D-(37,39)

D-(2,4)

D-(6,8)

D-(10,12)

D-(14,16)

D-(18,20)

D-22

D-24

D-26

D-28

D-30

D-32

D-34

D-36

D-38

D-40

TGB

C

C C

COMM ROOM

FCU-1

TELEPHONE

BACKBOARD

K-11

K-13

K-15

K-21

K-19

K-17

K-23

E10

29610

NO

RT

H CAROL INA

PR

OFESS I ONA L

SEAL

E

N G I N E E

R

R O

B E

R T S C O T T P E R

K I

N S

320-C Midland Parkway, Summerville, SC, 29485

ENGINEERING | ARCHITECTURE

CEMS Project No: Project Manager: R. Alvar

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY

MARINE CORPS BASE

CAMP LEJEUNE, NORTH CAROLINA

NAVAL FACILITIES ENGINEERING COMMAND

SIZE CODE IDENT NO. NAVFAC DRAWING NO.

SCALE: SPEC. SHEET OF

E1 80091

300 N. 3rd St., Suite 110, Wilmington, NC, 28401 843.875.3637 910.363.1640

CONSTR. CONTR. NO.:

ISSUE DATE:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF

THE CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICE HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME

CONTRACTOR TO THE CONTRACTING OFFICER.

DISCLOSURE OF INFORMATION

AS NOTED

C. COOPER

N. HEBEL

S. PERKINS

INTERIOR & EXTERIOR REPAIRS AT BEQ

M440

ENLARGED ELECTRICAL NEW WORK PLANS

E-402

136 14528 JULY 2017

60020349

15153G

N40085-17-B-0019

05-17-0019

SCALE: 1/4" = 1'-0"

E-101

TYPICAL ENLARGED SLEEPING

ROOM NEW WORK PLAN

GENERAL NOTES:

1. SEE SHEET E-501 FOR LIGHTING FIXTURE SCHEDULE.

2. ALL 'Y' AND 'X1' TYPE FIXTURES ARE TO BE FED FROM UNSWITCHED LEG OF NEAREST

LIGHTING CIRCUIT. MOUNT 'X1' TYPE FIXTURES LOCATED IN COORIDOR TO WALL ABOVE

DOOR.

3. PROVIDE ALL COMMUNICATIONS CABLING, EQUIPMENT, AND JACK SET ASSEMBLIES

ASSOCIATED WITH OFFICE AREAS ADN AREAS SERVICED BY BASE TELEPHONE SYSTEM

PER CAMP LEJEUNE COMMUNICATIONS SPECIFICATION 27 10 00. ALL WORK SHALL BE

DONE BY A QUALIFIED COMMUNICATIONS SUBCONTRACTOR. CONTACT CONSTRUCTION

MANAGER REGARDING ANY COMMUNICATIONS QUESTIONS.

4. HORIZONAL CATV COAX FROM BEQ ROOMS TO THE CHASE WAY ARE TO BE REMOVED

AND REPLACED WITH NEW.

5. ALL AHU UNITS SHALL BE PROVIDED WITH DEDICATED CONTROLS CIRCUIT, CONDUIT,

AND WIRING. SEE PANEL SCHEDULES ON SHEETS E-601 AND E-602 FOR CIRCUITING.

COORDINATE FINAL CONNECTION WITH MANUFACTURER'S REQUIREMENTS.

6. DRYER CIRCUIT TO BE 2#10, #10N, #10G 3/4"C.

SCALE: 1/4" = 1'-0"

E-401

ENLARGED LAUNDRY POWER

NEW WORK PLAN

SCALE: 1/2" = 1'-0"

E-401

ENLARGED COMMUNICATIONS

ROOM NEW WORK PLAN

04 8268 02 4 8134

SCALE: 1/4"=1'-0"

PLAN NORTH

1 2 42

SCALE: 1/2"=1'-0"

GRAPHIC SCALES

NOTES:

CKT 'A' - RECEPTACLES - ROOM/GFCI

CKT 'B' - LIGHTING

SEE PANEL SCHEDULES FOR SPECIFIC ROOM

CIRCUITS.

NEW WORK KEYNOTES:

NO. DESCRIPTION

E9 SEE PANEL SCHEDULE FOR SPECIFIC MECHANICAL EQUIPMENT CIRCUIT.

E10 PROVIDE 1" CONDUIT WITH PULLSTRING TO CU-1. COORDINATE WITH

MECHANICAL REFRIGERANT LINE ROUTING TO BE USED FOR CONDUIT.

G G

G m

V m

G

G m

G

V m

G

G m

G

V m

GG

m

G

V m

3 G G m

G

V m

V

V

3 G G m

G

V m

V

V

C

C

C

C

PANEL 'MDP'

PANEL 'A'

Y

PANEL 'B'

PANEL 'M1'

'B-AAC-AHU-1A'

PANEL

'B-BC-AC'

PANEL

AHU-1A

MECHANICAL

DHU-1A

M1-17

M1-(11,13,15)

Y

VAVOA-1A

M1-19

M1-7

M1-9

M1-3

M1-1

M1-1

M1-1

C

C

PANEL 'F'

Y

PANEL 'G'

MECHANICAL

DHU-1B

C

C

'B-AAC-AHU-1B'

PANEL

'B-BC-B' PANEL

AHU-1B

M1-18

M1-(12,14,16)

Y

VAVOA-1B

M1-19

M1-2

M1-2

M1-8

M1-10M1-2

M1-4

C

C

Y

PANEL 'H'

PANEL 'J'

PANEL 'M2'

MECHANICAL

DHU-2A

C

C

'B-AAC-AHU-2A'

PANEL

AHU-2A

Y

VAVOA-2A

M2-7

M1-(11,13,15)

M2-17

M2-9

M2-3

M2-1

M2-1M2-1

C

C

PANEL 'L'

YPANEL 'N'

MECHANICAL

DHU-2B

C

C

AHU-2B

Y

VAVOA-2B

'B-AAC-AHU-2B'

PANEL

M2-18

M2-(12,14,16)

M2-19

M2-2 M2-2

M2-10

M2-2

M2-4

C

C

PANEL 'O'

PANEL 'P'

PANEL 'M3'

ERV-A

MECHANICAL

DHU-3A

C

C

'B-AAC-AHU-3A'

PANEL

AHU-3A

M3-(11,13,15)

VAVOA-3A

M3-32

M3-7

Y

ERV-A

'B-AAC-ERV-A'

PANEL

Y

M3-3

M3-1

M3-9

M3-1

M3-(19,21,23)

M3-(26,28,30)M3-17

M3-1

MECHANICAL

C

C

PANEL 'R'

'B-AAC-ERV-B'

PANEL

ERV-B

C

C

'B-AAC-AHU-3A'

PANEL

AHU-3B

M3-(12,14,16)

VAVOA-3B

M3-32

M3-8

ERV-B

PANEL 'S'

DHU-3B

Y

M3-2

M3-2

M3-2

M3-10

M3-(20,22,24)

M3-(26,28,30)

M3-18

M3-4

29610

NO

RT

H CAROL INA

PR

OFESS I ONA L

SEAL

E

N G I N E E

R

R O

B E

R T S C O T T P E R

K I

N S

320-C Midland Parkway, Summerville, SC, 29485

ENGINEERING | ARCHITECTURE

CEMS Project No: Project Manager: R. Alvar

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY

MARINE CORPS BASE

CAMP LEJEUNE, NORTH CAROLINA

NAVAL FACILITIES ENGINEERING COMMAND

SIZE CODE IDENT NO. NAVFAC DRAWING NO.

SCALE: SPEC. SHEET OF

E1 80091

300 N. 3rd St., Suite 110, Wilmington, NC, 28401 843.875.3637 910.363.1640

CONSTR. CONTR. NO.:

ISSUE DATE:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF

THE CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICE HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME

CONTRACTOR TO THE CONTRACTING OFFICER.

DISCLOSURE OF INFORMATION

AS NOTED

C. COOPER

N. HEBEL

S. PERKINS

INTERIOR & EXTERIOR REPAIRS AT BEQ

M440

ENLARGED ELECTRICAL NEW WORK PLANS

E-403

137 14528 JULY 2017

60020350

15153G

N40085-17-B-0019

05-17-0019

SCALE: 1/4" = 1'-0"

E-101

ENLARGED ELECTRICAL

NEW WORK PLAN

SCALE: 1/4" = 1'-0"

E-101

ENLARGED ELECTRICAL

NEW WORK PLAN

GENERAL NOTES:

1. SEE SHEET E-501 FOR LIGHTING FIXTURE SCHEDULE.

2. SEE E-001 FOR COMMUNICATIONS AND CATV NOTES.

3. COORDINATE PANELBOARD AND LIGHTING LOCATIONS WITH ALL OTHER

DISCIPLINES PRIOR TO ROUGH IN.

4. ALL AHU AND ERV UNITS SHALL BE PROVIDED WITH DEDICATED CONTROLS

CIRCUIT, CONDUIT, AND WIRING. SEE PANEL SHCEDULES ON SHEETS E-601

AND E-602 FOR CIRCUITING. COORDINATE FINAL CONNECTION WITH

MANUFACTURER'S RREQUIREMENTS.

5. MECHANICAL EQUIPMENT DDC PANELS TO HAVE TWO GREEN CAT 6 CABLES

TO COMM ROOM.

SCALE: 1/4" = 1'-0"

E-101

ENLARGED ELECTRICAL

NEW WORK PLAN

SCALE: 1/4" = 1'-0"

E-101

ENLARGED ELECTRICAL

NEW WORK PLAN

SCALE: 1/4" = 1'-0"

E-101

ENLARGED ELECTRICAL

NEW WORK PLAN

SCALE: 1/4" = 1'-0"

E-101

ENLARGED ELECTRICAL

NEW WORK PLAN

PLAN NORTH

04 8268 02 4 8134

PRISMATIC LENS FLUORESCENT TROFFER

REVISED: APRIL 2016 NL-4LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL. EXTRUDED ALUMINUM DOOR WITH

SPRING-LOADED CAM LATCHES. OPTIONAL SIZES OF 1FT x 4FT, 2FT x 2FT, AND 2FT x 4FT AVAILABLE.

2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH

HIGH-REFLECTANCE, BAKED WHITE ENAMEL OR POLYESTER POWDER COAT; PAINTED

AFTER FABRICATION.

3. LENS - 100% VIRGIN ACRYLIC, CLEAR PRISMATIC PATTERN A12 WITH MINIMUM 0.125

IN. THICKNESS.

4. LIGHT SOURCE - LINEAR T8, T5, OR COMPACT TT5 FLUORESCENT WITH QUANTITY AND

CHARACTERISTICS AS INDICATED IN LUMINAIRE SCHEDULE.

5. BALLAST - PROGRAMMED-START, CLASS P, THERMALLY-PROTECTED, HIGH POWER

FACTOR (>0.9), ELECTRONIC TYPE WITH <20% THD AND 'A' SOUND RATING. SEE

LUMINAIRE SCHEDULE FOR OPTIONS SUCH AS DIMMING CAPABILITY.

6. CERTIFICATIONS - UL 1598, DAMP LOCATION, UL 924 WHEN EQUIPPED WITH

EMERGENCY BATTERY BACK-UP.

7. MOUNTING - RECESSED IN SUSPENDED ACOUSTICAL TILE OR HARD CEILING.

8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT

MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A

CERTAIN MANUFACTURER OR PREFERENCE.

SURFACE FLUORESCENT WRAPAROUND

REVISED: APRIL 2016 NL-6LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR

RIGIDITY; ENDCAPS SAME MATERIAL AS HOUSING, SECURED WITH TABS, SCREWS OR

RIVETS. OPTIONAL LENGTHS OF 2FT OR 4FT.

2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH

HIGH-REFLECTANCE, WHITE POLYESTER POWDER COAT, PAINTED AFTER FABRICATION.

3. LENS - 100% VIRGIN ACRYLIC, CLEAR PRISMATIC DIFFUSER WITH MINIMUM 0.1 INCH

THICKNESS, CONTINUOUSLY SUPPORTED ALONG SIDES OF LUMINAIRE.

4. LIGHT SOURCE - LINEAR T8 OR T5, WITH QUANTITY AND WATTAGE AS INDICATED IN

LUMINAIRE SCHEDULE. 3500K CCT UON; MINIMUM CRI OF 80.

5. BALLAST - PROGRAMMED-START, CLASS P, THERMALLY-PROTECTED < 20% TOTAL

HARMONIC DISTRIBUTION, HIGH POWER FACTOR (> 0.9), ELECTRONIC TYPE WITH 'A' SOUND

RATING. DIMMING OPTION AVAILABLE

6. CERTIFICATION - UL 1598, DAMP LOCATION, AND ROHS COMPLIANT. UL 924 WHEN

EQUIPPED WITH EMERGENCY BATTERY BACK-UP

7. MOUNTING - SURFACE ON CEILING OR SUSPENDED.

8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT

MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A

CERTAIN MANUFACTURER OR PREFERENCE.

WALL MOUNTED FLUORESCENT

REVISED: APRIL 2016 NL-10LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR

RIGIDITY; END CAPS SAME MATERIAL AS HOUSING, SECURED WITH TABS, SCREWS OR

RIVETS. WHITE ENAMEL FINISH APPLIED AFTER FABRICATION. OPTIONAL LENGTHS OF 2

FT, 3 FT OR 4 FT.

2. LENS - ACRYLIC PRISMATIC (CLEAR PRISMATIC PATTERN A12) OR WHITE OPAL, WITH

MINIMUM THICKNESS OF 0.125 IN.

3. LIGHT SOURCE - LINEAR T8, T5 OR T5HO FLUORESCENT TUBES WITH QUANTITY AND

CHARACTERISTICS AS INDICATED IN LUMINAIRE SCHEDULE.

4. BALLAST - PROGRAMMED-START, CLASS P, THERMALLY-PROTECTED, HIGH POWER

FACTOR (>0.9), ELECTRONIC TYPE WITH <20% THD AND 'A' SOUND RATING.

5. CERTIFICATION - UL 1598, DAMP LOCATION, UL 924 WHEN EQUIPPED WITH

EMERGENCY BATTERY BACK-UP.

6. MOUNTING - SURFACE ON WALL.

7. OPTIONS - EMERGENCY BACK-UP, <10% THD BALLAST, DOWNLIGHT COMPONENT ONLY.

8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE

THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE

A CERTAIN MANUFACTURER OR PREFERENCE.

FLUORESCENT ENCLOSED AND GASKETED

REVISED: APRIL 2016 NL-12LIGHTING PLATE:

LUMINAIRE REQUIREMENTS:

1. HOUSING - FIBERGLASS OR FIBERGLASS-REINFORCED POLYESTER OUTER HOUSING,

WITH ALUMINUM COMPONENT TRAY. OPTIONAL LENGTHS OF 4 FT OR 8 FT.

2. LENS - IMPACT-RESISTANT ACRYLIC OR OPTIONAL POLYCARBONATE, WITH CONTINUOUS

CLOSED-CELL POLYURETHANE GASKET, SECURED WITH STAINLESS STEEL OR OPTIONAL

POLYCARBONATE LATCHES.

3. LIGHT SOURCE - LINEAR T8, T5 OR T5HO FLUORESCENT TUBES WITH QUANTITY AND

CHARACTERISTICS AS INDICATED IN LUMINAIRE SCHEDULE.

4. BALLAST - PROGRAMMED-START, CLASS P, THERMALLY-PROTECTED, HIGH POWER

FACTOR (>0.9), ELECTRONIC TYPE WITH <20% THD AND 'A' SOUND RATING.

5. CERTIFICATION - UL 1598, WET LOCATION (IP65, IP66, IP67), UL 924 WHEN

EQUIPPED WITH EMERGENCY BATTERY BACK-UP.

6. MOUNTING - SURFACE-MOUNTED OR SUSPENDED FROM CEILING.

7. OPTIONS - EMERGENCY BACK-UP, INTEGRAL MOTION SENSOR, DIMMING.

8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT

MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A

CERTAIN MANUFACTURER OR PREFERENCE.

HOUSING - DIE-CAST ALUMINUM. SINGLE OR DOUBLE FACED AS INDICATED

LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. RED OR GREEN LETTERS

FINISH (ON CAST ALUMINUM HOUSING ONLY) - TEXTURED POWDER COAT FINISH

OPTIONS INCLUDE WHITE, WHITE WITH BRUSHED ALUMINUM FACE, BLACK, OR BLACK

EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY CHARGER WITH

MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-FIXTURE

ILLUMINATION - PROVIDED BY RED, GREEN OR WHITE HIGH-OUTPUT LEDS INSIDE

1.

2.

3.

4.

5.

6.

LUMINAIRE REQUIREMENTS:

REVISED: AUGUST 2004 NL-63

MOUNTING.

AS INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR BOTH

MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND

LIGHTING PLATE:

LED EXIT SIGN

13"

NOMINAL

NOMINAL

9"

WITH BRUSHED ALUMINUM FACE.

DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING AS REQUIRED.

TEST SWITCH.

OF FIXTURE HOUSING. PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH

FREQUENCY-MATCHED SILKSCREEN COATING FOR MAXIMUM LED LIGHT OUTPUT.

CERTIFICATION - UL LISTED AND CERTIFIED FOR DAMP LOCATIONS.7.

PRISMATIC LENS RECESSED 4' FLUORESCENT TROFFER

HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR

LENS - 100% ACRYLIC, CLEAR PRISMATIC, PATTERN #12 WITH MINIMUM

FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH HIGH

REFLECTANCE (MINIMUM 85%), BAKED WHITE ENAMEL FINISH.

LAMPS - LINEAR FLUORESCENT T8, TYPICALLY WITH WATTAGES AS INDICATED. SEE

BALLAST - CLASS P, THERMALLY-PROTECTED, HIGH POWER FACTOR ( .95),

CERTIFICATION - UL LISTED AND LABELED.

PHOTOMETRICS - MINIMUM VALUE OF COEFFICIENT OF UTILIZATION (CU) AND

EFFICIENCY, GIVEN INTERIOR CAVITY REFLECTANCES OF 80-50-20:

1.

2.

3.

4.

5.

6.

7.

LUMINAIRE REQUIREMENTS:

REVISED: AUGUST 2004 NL-2

ELECTRONIC TYPE WITH SOUND RATING A. SEE SPECIFICATION OR LIGHTING FIXTURE

RIGIDITY. ENDCAPS SECURED WITH TABS, SCREWS OR RIVETS. FIXTURE SHALL NOT

0.125" THICKNESS.

LIGHTING FIXTURE SCHEDULE.

LIGHTING PLATE:

4" NOMINAL

SCHEDULE FOR BALLAST OPTIONS AND SPECIFICS.

EFFICIENCY - 65%

4 51

2 LAMP (F32/T8)

RCR

CU

PERMANENTLY DEFORM OUT OF "SQUARE" WHEN PICKED UP FROM ANY CORNER. DEPTH

AS INDICATED UNLESS SPECIFICALLY MANUFACTURED FOR OPTIMAL USE WITH T8 LAMPS.

REVISED: AUGUST 2004 NL-48LIGHTING PLATE:

WALL-MOUNTED HIGH ABUSE FIXTURE

FLUORESCENT LAMPS.

COAT FINISH IN BLACK.

PROVIDE WITH WATTAGES AS INDICATED. SEE LIGHTING FIXTURE SCHEDULE.

ELECTRONIC TYPE WITH 10% TOTAL HARMONIC DISTORTION FOR COMPACT

CERTIFICATION - UL LISTED AND LABELED FOR WET LOCATIONS.

LAMPS - MULTI-TUBE COMPACT FLUORESCENT WITH 4-PIN BASE OR INCANDESCENT.

WITH MINIMUM 1/8" THICKNESS. DIFFUSER SECURED WITH TAMPER-RESISTANT

DIFFUSER - CLEAR PRISMATIC, UV-STABILIZED, INJECTION-MOLDED POLYCARBONATE

BALLAST - CLASS P, HIGH POWER FACTOR ( .95), PROGRAMMED RAPID START

HOUSING - ONE-PIECE, DIE-CAST ALUMINUM WITH BAKED-ON POLYESTER POWDER

6.

LUMINAIRE REQUIREMENTS:

5.

4.

2.

1.

STAINLESS STEEL SCREWS. BLACK HORIZONTAL FRONT EYELID FOR CUTOFF.

GASKET - ONE-PIECE, CLOSED-CELL NEOPRENE TO DISCOURAGE MOISTURE,3.

INSECTS AND DEBRIS.

6"

NOMINAL

NOMINAL

9"

NOMINAL

7"

FUSE

LIGHTING CONTROLLER

CABINET (NEMA 3R)

ON AT DUSK (10 F.C.)

OFF AT MIDNIGHT (ADJUSTABLE)

ON AT 5:00 A.M. (ADJUSTABLE)

OFF AT DAWN (10 F.C.)

SELECTOR

SWITCH

PHOTOCELL ON

ROOF, SPDT TYPE

SEVEN DAY

ELECTRONIC TIMER

WITH THREE DAY

BATTERY BACKUP

CLOSE

AUTO

OFF

ON

PERM,

MAGNETIC

LATCH TYPE

CONTACTOR

OPEN

120V

C

M

NEUTRAL

FIXTURE

CIRCUITS

C-31

K-25

Q-15

SPARE

29610

NO

RT

H CAROL INA

PR

OFESS I ONA L

SEAL

E

N G I N E E

R

R O

B E

R T S C O T T P E R

K I

N S

320-C Midland Parkway, Summerville, SC, 29485

ENGINEERING | ARCHITECTURE

CEMS Project No: Project Manager: R. Alvar

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY

MARINE CORPS BASE

CAMP LEJEUNE, NORTH CAROLINA

NAVAL FACILITIES ENGINEERING COMMAND

SIZE CODE IDENT NO. NAVFAC DRAWING NO.

SCALE: SPEC. SHEET OF

E1 80091

300 N. 3rd St., Suite 110, Wilmington, NC, 28401 843.875.3637 910.363.1640

CONSTR. CONTR. NO.:

ISSUE DATE:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF

THE CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICE HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME

CONTRACTOR TO THE CONTRACTING OFFICER.

DISCLOSURE OF INFORMATION

NONE

C. COOPER

N. HEBEL

S. PERKINS

INTERIOR & EXTERIOR REPAIRS AT BEQ

M440

ELECTRICAL LIGHTING DETAILS

E-501

138 14528 JULY 2017

60020351

15153G

N40085-17-B-0019

05-17-0019

LIGHTING FIXTURE SCHEDULE

C

B

STYLE NO. & TYPE VOLTAGE MOUNTING NOTESFIXTURE

SYMBOL

NUMBER AND TYPE

OF LAMPS

NL-4 2-17W/T8 120 RECESSED CEILING

SURFACE MTD.1202-32W/T8NL-6

NL-63X1 120 WALL MTD.

8'-0" A.F.F.LED

NL-12F1 120 WALL MTD.

6'-6" A.F.F.2-32W/T8

NL-10D 120 WALL MTD.

7'-0" A.F.F.2-32W/T8

NL-67Y 120 WALL MTD.

8'-0" A.F.F.LED

A NL-2 2-32W/T8 120 RECESSED CEILING

NL-48G 1201-18W/CFL WALL MTD.

7'-6" A.F.F.

NL-12F2 120 SURFACE MTD.2-32W/T8

NL-63X2 120 WALL MTD.

8'-0" A.F.F.LED 1, 2

NOTES:

1. EQUIPPED WITH TWO EMERGENCY HEADS.

2. FIXTURE TO BE VANDALPROOF.

REVISED: AUGUST 2004 NL-67LIGHTING PLATE:

DECORATIVE EMERGENCY LIGHTING UNIT

MR16 HALOGEN LAMPS SHALL BE 5 WATTS, HIGH-OUTPUT OR AS INDICATED IN

HOUSING - UV STABLE, FLAME-RATED, HIGH-IMPACT THERMOPLASTIC IN WHITE OR

BLACK TEXTURED FINISH.

INTERNAL COMPONENTS - FULLY AUTOMATIC, SOLID STATE, CONSTANT VOLTAGE,

CURRENT-LIMITED BATTERY CHARGER; MAINTENANCE-FREE LEAD-ACID BATTERY;

EXTERIOR HOUSING INDICATORS - LED AC-ON INDICATOR AND INTEGRAL TEST SWITCH.

LAMP HEADS - UV STABLE, FLAME RATED POLYCARBONATE THERMOPLASTIC.

MOUNTING - DIRECTLY TO 4" OCTAGONAL OR SQUARE OUTLET BOX.

CERTIFICATION - UL LISTED AND LABELED. COMPLIES WITH UL 924 AND NFPA 101

OPTIONS - VOLTMETER, VANDEL-RESISTANT SHIELD, SELF-DIAGNOSTIC/TESTING7.

6.

REQUIREMENTS. LISTED FOR DAMP LOCATIONS.

LUMINAIRE REQUIREMENTS:

1.

3.

5.

4.

2.

AND BUILT-IN OVERLOAD AND LOW-VOLTAGE BATTERY PROTECTION.

13"

NOMINAL

NOMINAL

5"

MAX. DEPTH

4" NOMINAL

ELECTRONICS AND WIRE GUARD.

LIGHTING FIXTURE SCHEDULE.

SCALE: NOT TO SCALE1 EXTERIOR LIGHTING SCHEMATIC

NOTES:

1. ALL OF THE TELEPHONE/DATA WIRING IS TO BE IN AN APPROVED

PATHWAY FROM THE OUTLET BACK TO THE BACKBOARD PER

SPECIFICATIONS AND STANDARDS. OPEN FACE TELECOMM SUPPORTS

SUCH AS BRIDAL RINGS AND J-HOOKS ARE NOT AUTHORIZED.

2. PROVIDE ALL COMMUNICATIONS CABLING, EQUIPMENT, AND JACK SET

ASSEMBLIES ASSOCIATED WITH OFFICE AREAS (WHERE APPLICABLE)

AND AREAS SERVICED BY BASE TELEPHONE SYSTEM PER CAMP

LEJEUNE COMMUNICATIONS SPECIFICATION 27 10 00. ALL WORK SHALL

BE DONE BY A QUALIFIED COMMUNICATIONS SUBCONTRACTOR.

CONTACT CONSTRUCTION MANAGER REGARDING ANY

COMMUNICATIONS QUESTIONS.

1 1/4" CONDUIT WITH FOUR (4

PAIR

UTP, 24 AWG, CAT 6 CABLES)

NOTE 1

SINGLE GANG

PLASTER RING

5" SQUARE BOX SURFACE

MOUNTED ON WALL

TELEPHONE

EQUIPMENT

RACKS

TELEPHONE/DATA

DROPS (TYP)

TWO 4'Hx8'Wx3/4"D

PLYWOOD BACKBOARDS

TELEPHONE

BACKBOARD

FIRST FLOOR

SECOND FLOOR

COMM ROOM

KEYNOTES:

NOTES:

GROUND FOR BACKBOARD TO BE MADE WITH GREEN

SHEATH #6 STRANDED COPPER IN 3/4"C TO COPPER BUS

BAR.

FROM TELECOMMUNICATIONS MANHOLE, AS SHOWN ON ES101,

PROVIDE SERVICE ENTRANCE IN (1) - 4 INCH PVC BELOW GRADE/SLAB

WITH TRANSITION TO (1) - 4 INCH EMT ABOVE GRADE/SLAB TO ROOM

224 AS DESIGNATED BY TSD. SEE ES101 FOR CONTINUATION.

PROVIDE 1/4"x4"x10" COPPER BUS BAR WITH INSULATING BRACKETS

AT TELEPHONE BACKBOARD IN ACCORDANCE WITH ANSI/TIA-607.

CONDUITS SHOULD EITHER COME UP FROM THE FLOOR OR DOWN

FROM THE CEILING AND TERMINATE 3" ON THE BACKBOARD AND

ALL BEBONDED TOGETHER AND GROUNDED WITH A GROUNDING

LUG ON THE END.

1. COORDINATE BACKBOARD LOCATION WITH BASE TELEPHONE.

2. PROVIDE ALL COMMUNICATIONS CABLING, EQUIPMENT, AND JACK SET ASSEMBLIES ASSOCIATED WITH OFFICE AREAS AND AREAS SERVICED BY BASE TELEPHONE SYSTEM PER CAMP LEJEUNE COMMUNICATIONS SPECIFICATION 27 10 00. ALL WORK SHALL BE DONE BY A QUALIFIED COMMUNICATIONS SUBCONTRACTOR. CONTACT CONSTRUCTION MANAGER REGARDING ANY COMMUNICATIONS QUESTIONS.

3. PROVIDE 1 1/4" CONDUIT WITH TWO CAT 6 CABLES FROM TELECOMMUNICATIONS RACK TO FACP. PROVIDE DUAL DATA/COMMUNICATIONS

JACK IN FACP. COORDINATE WITH LOCATION OF RACK AND FINAL LOCATION OF FACP.

4. TELEPHONE BACKBOARDS - PROVIDE VOID-FREE, INTERIOR GRADE PLYWOOD 3/4" THICK. BACKBOARDS SHALL BE FIRE RETARDANT TREATED PLYWOOD, WITH THE FIRE STAMP VISIBLE. BOARDS SHOULD BE INSTALLED 4' WIDTH BY 8' HEIGHT SECURELY FASTENED TO THE

WALL ANYWHERE EQUIPMENT IS TO BE MOUNTED.

5. ALL METALLIC CONDUIT AND EQUIPMENT MUST BE BONDED TO THE TMGB AND BUILDING GROUND PER ANSI/TIA-607 WITH MINIMUM #6

STRANDED GREEN SHEATH CONDUCTOR.

6. ALL CONDUITS NEED TO BE SECURELY MOUNTED, FIRE STOPPED, AND OVER LAP THE BACKBOARD BY 3-6".

7. INSTALL CABLES IN AN APPROVED PATHWAY PER THE SPECIFICATIONS AND STANDARDS; INSTALL ALL LADDER RACKS WITHIN TELECOMM ROOM, PATCH PANELS, CABINETS, BUILDING PROTECTORS, OSP CABLE, RISER CABLE, AND EQUIPMENT IAW BASE TELE 27 10 00. OPEN FACE TELECOMMUNICATIONS SUPPORTS ARE NOT ACCEPTABLE, E.G. BRIDAL RINGS AND J-HOOKS ARE NOT ACCEPTABLE.

NOTES:

1" CONDUIT WITH ONE RG-6

CABLE AND TWO (4 PAIR UTP, 24

AWG, CAT 6 CABLES)

SINGLE GANG

PLASTER RING

5" SQUARE BOX SURFACE

MOUNTED ON WALL

CATV

TELEPHONE

NOTE 1

1. ALL OF THE TELEPHONE/DATA WIRING IS TO BE IN AN APPROVED

PATHWAY FROM THE OUTLET BACK TO THE BACKBOARD PER

SPECIFICATIONS AND STANDARDS. CATV TO BE RG-6 AND TERMINATE

AT PATCH PANEL. OPEN FACE TELECOMM SUPPORTS SUCH AS

2. PROVIDE ALL COMMUNICATIONS CABLING, EQUIPMENT, AND JACK SET

ASSEMBLIES ASSOCIATED WITH OFFICE AREAS (WHERE APPLICABLE)

AND AREAS SERVICED BY BASE TELEPHONE SYSTEM PER CAMP

LEJEUNE COMMUNICATIONS SPECIFICATION 27 10 00. ALL WORK SHALL

BE DONE BY A QUALIFIED COMMUNICATIONS SUBCONTRACTOR.

CONTACT CONSTRUCTION MANAGER REGARDING ANY

COMMUNICATIONS QUESTIONS.

3. IN EACH SLEEPING ROOM, PROVIDE TWO TELEPHONE AND ONE CATV

JACK IN EACH FACEPLATE. PROVIDE TWO FACEPLATE CONFIGURATIONS

PER SLEEPING ROOM FOR A COMBINED TOTAL FOUR TELEPHONE

DROPS AND TWO CATV DROPS.

BRIDAL RINGS AND J-HOOKS ARE NOT AUTHORIZED.

CONC. SLAB

DUCTS ENTERING BUILDING

FOOTING

GROUND LEVEL

EXTERNAL WALL

24" MIN.

BELOW

GRADE

4" MIN.

FROM WALL

40" MINIMUM RADIUS

FOR CONDUITS 3"

AND LARGER AND

18" FOR CONDUITS

SMALLER THAN 3"

STUB UP 4" ABOVE

CONCRETE SLAB AND

2" BETWEEN DUCTS

STEEL PVC

4" MIN.

4"

CONCRETE ENCASEMENT

FLOOR

W

AL

L

PLASTIC

COATED RIGID

STEEL CONDUIT

PVC TO STEEL

ADAPTER

2"

2' - 0" MIN.

1 1/2" TYP.

4"

2"

1"

1"

1"

5/ 8"

3/8" DIA. HOLE TYP.

1/4" DIA. HOLE TYP.

1/2" NUT

1/4" DIA.

MOUNTING HOLE

TYP. OF 4

GENERAL NOTES:

1. ALL HARDWARE SHOWN SHALL BE STAINLESS STEEL.

2. PROVIDE 1 MOUNTING POINT PER 24" OF BAR LENGTH.

3. HOLES MAY BE ADDED IF REQUIRED.

1"

A

A

PLAN

SECTION A-A

2"

5"

1/2" DIA.x2"L BOLT TYP OF 2

1/2" NUT

STEEL EXPANSION

ANCHOR FOR CMU

WALLS, SCREW TO

STUDS FOR GYP.

WALLS

1/2" LOCK WASHER

1/2" STANDARD WASHER

1/2" FENDER WASHERS (EACH

SIDE)

3" DEEP FIBERGLASS CHANNEL

SAME LENGTH AS CU BUSS

29610

NO

RT

H CAROL INA

PR

OFESS I ONA L

SEAL

E

N G I N E E

R

R O

B E

R T S C O T T P E R

K I

N S

320-C Midland Parkway, Summerville, SC, 29485

ENGINEERING | ARCHITECTURE

CEMS Project No: Project Manager: R. Alvar

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY

MARINE CORPS BASE

CAMP LEJEUNE, NORTH CAROLINA

NAVAL FACILITIES ENGINEERING COMMAND

SIZE CODE IDENT NO. NAVFAC DRAWING NO.

SCALE: SPEC. SHEET OF

E1 80091

300 N. 3rd St., Suite 110, Wilmington, NC, 28401 843.875.3637 910.363.1640

CONSTR. CONTR. NO.:

ISSUE DATE:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF

THE CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICE HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME

CONTRACTOR TO THE CONTRACTING OFFICER.

DISCLOSURE OF INFORMATION

AS NOTED

C. COOPER

N. HEBEL

S. PERKINS

INTERIOR & EXTERIOR REPAIRS AT BEQ

M440

ELECTRICAL DETAILS

E-502

139 14528 JULY 2017

60020352

15153G

N40085-17-B-0019

05-17-0019

SCALE: NOT TO SCALE1 OFFICE TELEPHONE/DATA OUTLET DETAIL (TYPICAL)

SCALE: NOT TO SCALE2 VOICE/DATA SYSTEM RISER

SCALE: NOT TO SCALE3 SLEEPING ROOM TELEPHONE/CATV OUTLET DETAIL (TYPICAL)

SCALE: NOT TO SCALE4 DUCT ENTRY INTO BUILDING

SCALE: NOT TO SCALE5 ENCASED UNDERSLAB STUB-UPS

SCALE: NOT TO SCALE6 GROUNDING BAR DETAIL

1 1 3' ALL SIDES

#4/0 AWG BARE COPPER IN 3/4" PVC TO GROUNDING LUG.

WELDED

CONNECTION

(TYP.)

3/4" x 10' MIN.

LENGTH GROUND

ROD (TYP.)

GROUND RING: #4/0 AWG BARE

COPPER DIRECT-BURIED 1'

BELOW GRADE

PRECAST BOX PAD

PAVED

CONDITION

4"

4"

WARNING TAPE

AND TRACER

WIRE 12" BELOW

GRADE

APPROVED

COMPACTED

BACKFILL IN

6" MAX. LIFTS

GRASS

CONDITION

UNDISTURBED

EDGE OF TRENCH

CONCRETE ENCASED

DUCTBANK, NUMBER

AND SIZE INDICATED

ON PLANS

GRANULAR BEDDING

NOTE: SEE SPECIFICATIONS

FOR BURIAL DEPTHS.

GRADE

" M

IN

3000 PSI CONCRETE

3"

NOTE:

1. AT EACH CORNER, PROVIDE #4

REINFORCING ROD INSTALLED AT 1 1/2"

FROM DUCT BANK SURFACE FOR ALL

DUCT BANKS UNDER ROADWAYS OR

PARKING AREAS.

3" 3"

3000 PSI CONCRETE

3"

NOTE:

1. AT EACH CORNER AND MIDDLE, PROVIDE

#4 REINFORCING ROD INSTALLED AT 1

1/2" FROM DUCT BANK SURFACE FOR ALL

DUCT BANKS UNDER ROADWAYS OR

PARKING AREAS.

3" 3"

NOTES:

1. ASSEMBLY TO BE PLACED ON A 6" BASE OF CRUSHER

RUN FOR EASE OF INSTALLATION AND EVEN LOAD

DISTRIBUTION.

2. ILLUSTRATION IS TYPICAL ONLY OF GENERAL SERIES

CONFIGURATION: FOR SPECIFIC CONFIGURATION

COORDINATE WITH MANUFACTURER.

3. ALL CONDUITS TO EXTEND 1" ABOVE TOP OF PAD.

4. COORDINATE PAD AND COMPARTMENT OPENING

DIMENSION REQUIREMENTS WITH TRANSFORMER

MANUFACTURER.

3'-0" ∅ 4'-0" x 5'-0"

MANHOLE VAULT

OPENING OPENING

A

B

C

D

TRANSFORMER PAD

LOWER SECTION

MINIMUM EXCAVATION SIZE:

4'-8" x 7'-8" x DEPTH REQUIRED.

E

F

30" X 48" ACCESS COVER

UNISTRUT

PULLING INSERTS

16" X 16" CORNER KNOCKOUTS - VARIOUS SIZES AVALIABLE

3'-6"

7'-0"

6"

3'-8"

D

B

6'-8"

3'-0"

6'-0" 3'-6"

E

C

4'-0"

F A

TRANSFOMER CABLE ACCESS OPENINGS AVALIABLE

IN DIFFERENT SIZES.

G

G

FIBERGLASS SLEEVE (EXPOSE

6" ABOVE GRADE)

3 PHASE, 4 POINT STEEL

15KV, 200A JUNCTION BOX

GROUND LUGS (TYP)

CONNECT GROUNDS TO

GROUND LOOP USING

SQUEEZE-ON

CONNECTIONS (TYP)

3/4IN X 10FT

GND ROD (TYP)

SERVICE LOOP CONDUCTORS

FROM EXISTING MANHOLE

SET SLEEVE ON 8" CRUSHED

STONE OR GRAVEL

CAD WELD GND ROD CONNECTIONS

#4/0 BARE CU GROUND LOOP

PARKING STAND (TYP)

15KV LOAD BREAK ELBOW

WITH TEST POINT (TYP)

PVC ELBOW, SIZE TO MATCH

EXISTING CONDUIT (TYP)

SPARE WELL (TYP OF 3 PER PHASE)

EXISTING SERVICE

LOOP CONDUCTORS

CONDUIT AND CONDUCTORS TO M440 PAD MOUNTED

TRANSFORMER, SEE RISER DIAGRAM FOR CONTINUATION

SPARE CONDUIT 5"

NOTE: PROVIDE NEW SECTIONALIZER CABINET WITH

LOOP FEED ADAPTER FOR ONE WELL.

GRADE

TO PANEL 'C' TO SSHP-1

ALUMINUM SQUARE TUBE

4"x4"x1/2" TOP CAP SET SQUARE

TUBE (COATED IN BITUMASTIC

IN CONCRETE PAD

ALUMINUM FLAT BAR 3"x1/2" ALL BOLTS, NUTS WASHERS, AND MISC. HARDWARE

SHALL BE STAINLESS STEEL. BONDING

JUMPERS SHALL BE PROVIDED ACROSS

ALL BOLTED JOINTS. FRAM MAY BE

WELDED. FRAME SHALL BE GROUNDED.

ON

OFF

30A ELECTRICAL DISCONNECT,

NEMA 3R

29610

NO

RT

H CAROL INA

PR

OFESS I ONA L

SEAL

E

N G I N E E

R

R O

B E

R T S C O T T P E R

K I

N S

320-C Midland Parkway, Summerville, SC, 29485

ENGINEERING | ARCHITECTURE

CEMS Project No: Project Manager: R. Alvar

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY

MARINE CORPS BASE

CAMP LEJEUNE, NORTH CAROLINA

NAVAL FACILITIES ENGINEERING COMMAND

SIZE CODE IDENT NO. NAVFAC DRAWING NO.

SCALE: SPEC. SHEET OF

E1 80091

300 N. 3rd St., Suite 110, Wilmington, NC, 28401 843.875.3637 910.363.1640

CONSTR. CONTR. NO.:

ISSUE DATE:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF

THE CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICE HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME

CONTRACTOR TO THE CONTRACTING OFFICER.

DISCLOSURE OF INFORMATION

AS NOTED

C. COOPER

N. HEBEL

S. PERKINS

INTERIOR & EXTERIOR REPAIRS AT BEQ

M440

ELECTRICAL DETAILS

E-503

140 14528 JULY 2017

60020353

15153G

N40085-17-B-0019

05-17-0019

SCALE: NOT TO SCALE2 SERVICE TRANSFORMER GROUNDING DETAIL

SCALE: NOT TO SCALE3 CONCRETE ENCASED DUCTBANK TRENCH DETAIL

SCALE: NOT TO SCALE4 2-WAY CONCRETE ENCASED DUCTBANK DETAIL

SCALE: NOT TO SCALE5 4-WAY CONCRETE ENCASED DUCTBANK DETAIL

SCALE: NOT TO SCALE1 SERVICE TRANSFORMER PAD WITH VAULT DETAIL

SCALE: NOT TO SCALE6 SECTIONALIZER CABINET DETAIL

SCALE: NOT TO SCALE7 EQUIPMENT PEDESTAL DETAIL

120/208V 3 4 1600A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM.

TOTAL DEMAND

TOTAL CONNECTED

65,000 508,959

468,461 1301VA AMPS

B A

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

1600A

PANEL NO. MDP

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

31 32 33 34 35 36 37 38 39 40 41 42

C

B A

C

B A

C

B A

C

B A

C

B A

C

B A

C

PANEL A225

PANEL C225

PANEL D400

PANEL Q225

PANEL R225

PANEL M1125

PANEL M2125

PANEL M3225

PANEL O225

PANEL H225

PANEL K225

PANEL L225

PANEL F225

SPD60

39500

42699

83000

33111

35500

26024

25304

46760

35500

35500

35061

35500

35500

PROVIDE MDP WITH FOUR EXTRA 3 POLE SPACES.

120/208V 3 4 225A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM.

TOTAL DEMAND

TOTAL CONNECTED

22,000 39,500

37,250 103VA AMPS

B A

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. A

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

31 32 33 34 35 36 37 38 39 40 41 42

C

B A

C

B A

C

B A

C

B A

C

B A

C

B A

C

RCPT-101 (A)20 20

A - CIRCUIT BREAKER TO BE ARC-FAULT CIRCUIT-INTERRUPTER TYPE

(X) - DENOTES TYPICAL SLEEPING ROOM CIRCUIT. SEE ENLARGED ROOM NEW WORK PLAN.

LGT-101, 101B (B)

PANEL 'B'

A A A A A A A A

A A A A A A

RCPT-102 (A)

LGT-102, 102B (B)

20324

RCPT-103 (A)

LGT-103, 103B (B)

RCPT-105 (A)

LGT-105, 105B (B)

RCPT-107 (A)

LGT-107, 107B (B)

RCPT-104 (A)

LGT-104, 104B (B)

RCPT-106 (A)

LGT-106, 106B (B)

RCPT-108 (A)

LGT-108, 108B (B)

A A

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

30 SITE LIGHTING 4000

120/208V 3 4 125A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM.

TOTAL DEMAND

TOTAL CONNECTED

10,000 20,324

18,074 50VA AMPS

B A

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. B

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

C

B A

C

B A

C

B A

C

20 20

A A A A

20 FPB-101-108

20 FPB-111-118

A A A A

A - CIRCUIT BREAKER TO BE ARC-FAULT CIRCUIT-INTERRUPTER TYPE

(X) - DENOTES TYPICAL SLEEPING ROOM CIRCUIT. SEE ENLARGED ROOM NEW WORK PLAN.

B A

C

RCPT-111 (A)

LGT-111, 111B (B)

RCPT-113 (A)

LGT-113, 113B (B)

RCPT-115 (A)

LGT-115, 115B (B)

RCPT-117 (A)

LGT-117, 117B (B)

A A A A A A

RCPT-112 (A)

LGT-112, 112B (B)

RCPT-114 (A)

LGT-114, 114B (B)

RCPT-116 (A)

LGT-116, 116B (B)

RCPT-118 (A)

LGT-118, 118B (B)

A A

SPARE

SPARE

SPARE

SPARE

120/208V 3 4 225A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM.

TOTAL DEMAND

TOTAL CONNECTED

22,000 42,699

40,449 112VA AMPS

B A

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. C

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

31 32 33 34 35 36 37 38 39 40 41 42

C

B A

C

B A

C

B A

C

B A

C

B A

C

B A

C

RCPT-119,121-12320 20

LGT-119,121-126

AHU-1C 119

FACP

XMTR

RCPT-WASHER 121

RCPT-WASHER 121

DRYER 121

HAND DRYER 122

RCPT-126

RCPT-125,126

RCPT-VENDING

RCPT-VENDING

RCPT-VENDING

RCPT-EWC

RCPT-124

RCPT-WASHER 121

30 DRYER 121

30 DRYER 121

L - CIRCUIT BREAKER TO BE LOCK-ON TYPE

R - CIRCUIT BREAKER HANDLE TO BE RED IN COLOR

NOTE:

1. IN ADDITION TO THE PANEL NAMEPLATE. PROVIDE A LABEL WITH THE FOLLOWING

INSCRIPTION: 'FIRE PROTECTION/LIFE SAFETY EQUIPMENT'. CONSTRUCT AND FASTEN

LABEL INDENTICAL TO THE PANEL NAMEPLATE. EXCEPT THE LABEL MUST BE RED

LAMINATE PLASTIC WITH WHITE CENTER CORE.

20 LGT-120,220,320

L,R L,R

20 LGT- EXTERIOR

UH-1 121

EF-1 121

FPB1B-21 124

SPARE

L

30 DRYER 121 5000

25 CU-1 3952

120/208V 3 4 400A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM.

TOTAL DEMAND

TOTAL CONNECTED

22,000 83,000

83,000 231VA AMPS

B A

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. D

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

31 32 33 34 35 36 37 38 39 40 41 42

C

B A

C

B A

C

B A

C

B A

C

B A

C

B A

C

RCPT-WASHER 126

DRYER 126

DRYER 126 30 5000

30 5000

30 5000

30 5000

DRYER 126

DRYER 126

DRYER 126

DRYER 126

DRYER 126

DRYER 126

DRYER 126

DRYER 126

DRYER 126

DRYER 126

DRYER 126

DRYER 126

DRYER 126

RCPT-WASHER 126

RCPT-WASHER 126

RCPT-WASHER 126

RCPT-WASHER 126

RCPT-WASHER 126

RCPT-WASHER 126

RCPT-WASHER 126

RCPT-WASHER 126

RCPT-WASHER 126

120/208V 3 4 225A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM. TOTAL DEMAND

TOTAL CONNECTED

22,000

35,500

33,250 92VA AMPS

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. F

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

PANEL 'G'

B A

31 32 33 34 35 36 37 38 39 40 41 42

C

B A

C

B A

C

B A

C

B A

C

B A

C

B A

C

RCPT-127 (A)20 20

RCPT-127, 127B (B)

A A A A A A A A

A A A A A A

SPARE

SPARE

SPARE

SPARE SPARE

SPARE

SPARE

SPARE

20324

A - CIRCUIT BREAKER TO BE ARC-FAULT CIRCUIT-INTERRUPTER TYPE

(X) - DENOTES TYPICAL SLEEPING ROOM CIRCUIT. SEE ENLARGED ROOM NEW WORK PLAN.

RCPT-129 (A)

RCPT-129, 129B (B)

RCPT-131 (A)

RCPT-131, 131B (B)

RCPT-133 (A)

RCPT-133, 133B (B)

RCPT-128 (A)

RCPT-128, 128B (B)

RCPT-130 (A)

RCPT-130, 130B (B)

RCPT-132 (A)

RCPT-132, 132B (B)

A A

RCPT-134 (A)

RCPT-134, 134B (B)

120/208V 3 4 125A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM.

TOTAL DEMAND

TOTAL CONNECTED

10,000 VA AMPS

B A

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. G

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

C

B A

C

B A

C

B A

C

SPARE

SPARE

SPARE

SPARE

20,324 18,074 50

RCPT-137 (A)20 20

RCPT-137, 137B (B)

A A A A

A A A

20 FPB-127-134

20 FPB-137-144

A A A A

A A A

A - CIRCUIT BREAKER TO BE ARC-FAULT CIRCUIT-INTERRUPTER TYPE

(X) - DENOTES TYPICAL SLEEPING ROOM CIRCUIT. SEE ENLARGED ROOM NEW WORK PLAN.

B A

C

RCPT-139 (A)

RCPT-139, 139B (B)

RCPT-141 (A)

RCPT-141, 141B (B)

RCPT-143 (A)

RCPT-143, 143B (B)

RCPT-144 (A)

RCPT-144, 144B (B)

RCPT-142 (A)

RCPT-142, 142B (B)

RCPT-140 (A)

RCPT-140, 140B (B)

RCPT-138 (A)

RCPT-138, 138B (B)

120/208V 3 4 225A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM. TOTAL DEMAND

TOTAL CONNECTED

22,000

35,500

33,250 92VA AMPS

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. H

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

31 32 33 34 35 36 37 38 39 40 41 42

B A

C

B A

C

125 PANEL 'J' 20324

B A

C

B A

C

B A

C

B A

C

B A

C

RCPT-201 (A)20 20

LGT-201, 201B (B)

A A A A A A A A

A A A A A A

RCPT-202 (A)

LGT-202, 202B (B)

RCPT-203 (A)

LGT-203, 203B (B)

RCPT-205 (A)

LGT-205, 205B (B)

RCPT-207 (A)

LGT-207, 207B (B)

RCPT-204 (A)

LGT-204, 204B (B)

RCPT-206 (A)

LGT-206, 206B (B)

RCPT-208 (A)

LGT-208, 208B (B)

A A

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

A - CIRCUIT BREAKER TO BE ARC-FAULT CIRCUIT-INTERRUPTER TYPE

(X) - DENOTES TYPICAL SLEEPING ROOM CIRCUIT. SEE ENLARGED ROOM NEW WORK PLAN.

29610

NO

RT

H CAROL INA

PR

OFESS I ONA L

SEAL

E

N G I N E E

R

R O

B E

R T S C O T T P E R

K I

N S

320-C Midland Parkway, Summerville, SC, 29485

ENGINEERING | ARCHITECTURE

CEMS Project No: Project Manager: R. Alvar

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY

MARINE CORPS BASE

CAMP LEJEUNE, NORTH CAROLINA

NAVAL FACILITIES ENGINEERING COMMAND

SIZE CODE IDENT NO. NAVFAC DRAWING NO.

SCALE: SPEC. SHEET OF

E1 80091

300 N. 3rd St., Suite 110, Wilmington, NC, 28401 843.875.3637 910.363.1640

CONSTR. CONTR. NO.:

ISSUE DATE:

CONTRACTOR SHALL COMPLY AS FOLLOWS:

A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF

THE CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

1. THE CONTRACTING OFFICE HAS GIVEN PRIOR WRITTEN APPROVAL; OR

2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE.

B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING

OFFICER AT LEAST 45 DAYS BEFORE PROPOSED DATE FOR RELEASE.

C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME

CONTRACTOR TO THE CONTRACTING OFFICER.

DISCLOSURE OF INFORMATION

NONE

C. COOPER

N. HEBEL

S. PERKINS

INTERIOR & EXTERIOR REPAIRS AT BEQ

M440

ELECTRICAL PANEL SCHEDULES

E-601

141 14528 JULY 2017

60020354

15153G

N40085-17-B-0019

05-17-0019

120/208V 3 4 225A

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM. TOTAL DEMAND

TOTAL CONNECTED

22,000 VA AMPS

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. O

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

A- CIRCUIT BREAKER TO BE ARC-FAULT CIRCUIT-INTERRUPTER TYPE

(X)- DENOTES TYPICAL SLEEPING ROOM CIRCUIT. SEE ENLARGED ROOM NEW WORK PLAN.

35,500 33,250 92

31 32 33 34 35 36 37 38 39 40 41 42

B A

C

B A

C

125 PANEL 'P' 20324

B A

C

B A

C

B A

C

B A

C

B A

C

RCPT-301 (A)20 20

LGT-301, 301B (B)

A A A A A A A A

A A A A A A

RCPT-302 (A)

LGT-302, 302B (B)

RCPT-303 (A)

LGT-303, 303B (B)

RCPT-305 (A)

LGT-305, 305B (B)

RCPT-307 (A)

LGT-307, 307B (B)

RCPT-304 (A)

LGT-304, 304B (B)

RCPT-306 (A)

LGT-306, 306B (B)

RCPT-308 (A)

LGT-308, 308B (B)

A A

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

120/208V 3 4 125A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM. TOTAL DEMAND

TOTAL CONNECTED

10,000 VA AMPS

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. J

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

A- CIRCUIT BREAKER TO BE ARC-FAULT CIRCUIT-INTERRUPTER TYPE

(X)- DENOTES TYPICAL SLEEPING ROOM CIRCUIT. SEE ENLARGED ROOM NEW WORK PLAN.

20,324 18,074 50

18C

B A

C

SPARE

SPARE

SPARE

SPARE

20 FPB-201-208

20 FPB-211-218

B A

C

B A

C

B A

C

B A

20 20

20 20

A A A A 20

A A A A

RCPT-211 (A)

LGT-211, 211B (B)

RCPT-213 (A)

LGT-213, 213B (B)

RCPT-215 (A)

LGT-215, 215B (B)

RCPT-217 (A)

LGT-217, 217B (B)

A A A A A A

RCPT-212 (A)

LGT-212, 212B (B)

RCPT-214 (A)

LGT-214, 214B (B)

RCPT-216 (A)

LGT-216, 216B (B)

RCPT-218 (A)

LGT-218, 218B (B)

A A

120/208V 3 4 225A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM. TOTAL DEMAND

TOTAL CONNECTED

22,000 VA AMPS

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. K

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

B A

31 32 33 34 35 36 37 38 39 40 41 42

C

B A

C

B A

C

B A

C

B A

C

B A

C

B A

C

RCPT-219-22320 20

AHU-2C 219

RCPT-WASHER 221

DRYER 221

HAND DRYER 222

RCPT-226

RCPT-225,226

RCPT-224 COMM. RACK

L - CIRCUIT BREAKER TO BE LOCK-ON TYPE

35,061 32,811 91

RCPT-EWC 720

20 RCPT-224 COMM. RM. 720

RCPT-224 COMM. RM. 720

RCPT-224 COMM. RM. 360

RCPT-224 COMM. RACK 360

RCPT-224 COMM. RACK 360

LGT-219,221-226

835LGT-EXTERIOR

RCPT-WASHER 221

RCPT-WASHER 221

DRYER 221

DRYER 221

SPARE

SPARE

UH-2 221

EF-2 221

SPARE

SPARE

L

30 5000DRYER 221

30 SPD

120/208V 3 4 225A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM. TOTAL DEMAND

TOTAL CONNECTED

22,000 VA AMPS

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. L

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

A- CIRCUIT BREAKER TO BE ARC-FAULT CIRCUIT-INTERRUPTER TYPE

(X)- DENOTES TYPICAL SLEEPING ROOM CIRCUIT. SEE ENLARGED ROOM NEW WORK PLAN.

PANEL 'N'

31 32 33 34 35 36 37 38 39 40 41 42

B A

C

B A

C 125 20324

B A

C

B A

C

B A

C

B A

C

B A

C

RCPT-227 (A)20 20

RCPT-227, 227B (B)

A A A A A A A A

A A A A A A

SPARE

SPARE

SPARE

SPARE SPARE

SPARE

SPARE

SPARE

RCPT-229 (A)

RCPT-229, 229B (B)

RCPT-231 (A)

RCPT-231, 231B (B)

RCPT-233 (A)

RCPT-233, 233B (B)

RCPT-228 (A)

RCPT-228, 228B (B)

RCPT-230 (A)

RCPT-230, 230B (B)

RCPT-232 (A)

RCPT-232, 232B (B)

A A

RCPT-234 (A)

RCPT-234, 234B (B)

35,500 33,250 92

120/208V 3 4 125A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM. TOTAL DEMAND

TOTAL CONNECTED

10,000 VA AMPS

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. N

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

A- CIRCUIT BREAKER TO BE ARC-FAULT CIRCUIT-INTERRUPTER TYPE

(X)- DENOTES TYPICAL SLEEPING ROOM CIRCUIT. SEE ENLARGED ROOM NEW WORK PLAN.

20,324

18C

B A

C

SPARE

SPARE

SPARE

SPARE

20 FPB-227-234

20 FPB-237-244

B A

C

B A

C

B A

C

B A20

20 20

18,074 50

RCPT-237 (A)20 20

RCPT-237, 237B (B)

A A A A

A A A

A A A A

A A A

RCPT-239 (A)

RCPT-239, 239B (B)

RCPT-241 (A)

RCPT-241, 241B (B)

RCPT-243 (A)

RCPT-243, 243B (B)

RCPT-244 (A)

RCPT-244, 244B (B)

RCPT-242 (A)

RCPT-242, 242B (B)

RCPT-240 (A)

RCPT-240, 240B (B)

RCPT-238 (A)

RCPT-238, 238B (B)

120/208V 3 4 225A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM. TOTAL DEMAND

TOTAL CONNECTED

22,000 VA AMPS

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. R

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

A- CIRCUIT BREAKER TO BE ARC-FAULT CIRCUIT-INTERRUPTER TYPE

(X)- DENOTES TYPICAL SLEEPING ROOM CIRCUIT. SEE ENLARGED ROOM NEW WORK PLAN.

PANEL 'S'

31 32 33 34 35 36 37 38 39 40 41 42

B A

C

B A

C 125 20324

35,500 33,250 92

B A

C

B A

C

B A

C

B A

C

B A

C

RCPT-327 (A)20 20

RCPT-327, 327B (B)

A A A A A A A A

A A A A A A

SPARE

SPARE

SPARE

SPARE SPARE

SPARE

SPARE

SPARE

RCPT-329 (A)

RCPT-329, 329B (B)

RCPT-331 (A)

RCPT-331, 331B (B)

RCPT-333 (A)

RCPT-333, 333B (B)

RCPT-328 (A)

RCPT-328, 328B (B)

RCPT-330 (A)

RCPT-330, 330B (B)

RCPT-332 (A)

RCPT-332, 332B (B)

A A

RCPT-334 (A)

RCPT-334, 334B (B)

120/208V 3 4 225A

SIZENO.NO.

INTERRUPTING AMPERE CURRENT

RATING FOR THIS ASSEMBLY

SHALL BE A. RMS SYM. TOTAL DEMAND

TOTAL CONNECTED

22,000 VA AMPS

CKT.

SIZE

BRKR CKT.LOAD VA LOADBRKR VA

MLO

PANEL NO. Q

VA

VOLTAGE PHASE WIRE BUS SIZE MCB

B A

31 32 33 34 35 36 37 38 39 40 41 42

C

B A

C

B A

C

B A

C

B A

C

B A

C

B A

C

RCPT-319,321-32320 20

AHU-3C 319

RCPT- WASHER 321

DRYER 321

HAND DRYER 322

RCPT-326

RCPT-325, 326

SPARE

SPARE

SPARE

SPARE

SPARE

33,111 30,861 86

RCPT-EWC 720

RCPT-324 360

LGT-319, 321-326

835LGT-EXTERIOR

SPARE

SPARE

RCPT- WASHER 321

RCPT- WASHER 321

DRYER 321

DRYER 321

UH-3 321

EF-3…