WO# D423F
J-1502000 Table of Contents Page 1
SECTION J
DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS
TABLE OF CONTENTS
ATTACHMENT NUMBER ATTACHMENT TITLE
J-1502000-01 Definitions and Acronyms
J-1502000-02 References and Technical Documents
J-1502000-03 Facilities Property and Equipment Inventory
J-1502000-03.1 Equipment Inventory, Cubicle Type Secondary Unit Substations (under UEM Controlled)
J-1502000-03.2 List of Reference Drawings (Ref-DWG)
J-1502000-04 Site Map, Location Map
J-1502000-05 Historical Trouble Call Data
J-1502000-06 Items to be Included in PM Program
J-1502000-06.1 Tentative Power Outage Schedule for Contractor’s PM
J-1502000-06.2 Base Period Specific Requirements, Current Concerns, Additional Information
J-1502000-06.3 Secondary Unit Substations/Cubicles That Are or May be Hooked with Generator
J-1502000-07 Historical IDIQ Task Order Data
J-1502000-01 Page 1
ATTACHMENT J-1502000-01
DEFINITIONS AND ACRONYMS
DEFINITION DESCRIPTION
CRANE, CATEGORY 1 Portal cranes, Hammerhead cranes, Locomotive cranes, Derricks, Floating cranes (YD), Tower cranes, Container cranes, Mobile cranes (except those indicated as category 4), including truck, cruiser, crawler, warehouse/industrial cranes, and cranes used for dragline, pile driving, clamshell, magnet, bucket work, and Aircraft crash cranes.
CRANE, CATEGORY 2 & 3 Cranes with rated capacities of 20,000 pounds or greater are category 2.
Examples are Over head traveling cranes, Gantry cranes (rail mounted), Wall cranes, Jib cranes, Pillar cranes, Pillar jib cranes, Monorails and associated hoists, Fixed hoists, including chain falls. Pedestal mounted commercial boom assemblies (fixed length, telescoping, and articulating types) attached to stake trucks, trailers, flatbeds, or railcars, or stationary mounted to piers, etc., with OEM rated capacities less than 2,000 pounds.
CRANE, CATEGORY 4 Commercial truck mounted cranes, Truck mounted articulating boom cranes, Pedestal mounted commercial boom assemblies (fixed length, telescoping, and articulating types) attached to stake trucks, trailers, flatbeds, or railcars, or stationary mounted to piers, etc., with OEM rated capacities of 2,000 pounds and greater. Commercial truck mounted cranes and truck mounted articulating boom cranes with OEM capacities of 2,000 pounds and greater require a licensed operator even if the cranes are down rated below 2,000 pounds capacity for administrative purposes.
EQUIPMENT, COLLATERAL Encompasses built-in and large substantially affixed equipment/property that is normally acquired and installed as part of a facility project.
EQUIPMENT, INSTALLED Encompasses building-type equipment, built-in equipment, and large, substantially affixed equipment/property, and is normally acquired and installed as part of a facility project. Installed equipment is normally required to make a facility useful and operable. Removing such equipment would impair the usefulness, safety, or environment of the facility or the facility restoration work required after its removal, is substantial.
EQUIPMENT, PERSONAL
PROPERTY
Personal property equipment includes all equipment other than collateral equipment. Such equipment, when acquired and used in a facility or a test apparatus, can be severed and removed aster erection or installation without substantial loss of value or damage thereto or to the premises where installed.
FACILITIES LIFE CYCLE A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal.
FACILITIES MAINTENANCE
MANAGEMENT
The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.”
Integrated Maintenance Program
(IMP)
IMP is a recurring state-of-the-art, reliability-centered inspection, testing, maintenance and repair program that determines best practices for managing the functions and consequences of failures of facilities equipment and system components. IMP encompasses accepted commercial practices, including reactive, preventive, predictive and proactive maintenance, into one optimal program. The IMP approach gives the Contractor full responsibility to maintain systems and equipment and perform repairs whenever necessary to
J-1502000-01 Page 2 ensure equipment and systems are operational and remain in a constant state of readiness. Service calls will not be issued for accomplishment of repairs on systems and equipment maintained under IMP.
LIFE-CYCLE COSTS A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life.
MAINTENANCE, PREVENTIVE Maintenance designed to increase the availability of the facilities/equipment by reducing the number of unexpected breakdowns or service interruptions.
It is any planned maintenance activity that improves equipment life and avoid any unplanned maintenance requirements.
MANAGEMENT
INFORMATION SYSTEMS-
MAINTENANCE
A computerized system that will provide sufficient information for management to evaluate differences between budgets and actual costs and evaluate performance.
REPAIR Repair is the restoration of facilities or equipment to such a condition that it may be effectively utilized for its designated purposes by overhaul, reconstruction, or replacement of constituent parts or materials which have deteriorated by action of the elements or usage, and which have not been corrected through maintenance. This term also applies to replacement of the entire unit or system if beyond economical repair. The intent of repair is to have the equipment at normal working condition.
REPLACEMENT Replacement, as a distinct work element, is confined to a program of planned replacement of a facility or its components. It may be further limited to major components such as air conditioning compressors, furnaces or hot water heaters. Replacement is performed when the equipment has reached the end of its useful life; when it no longer can perform due to degradation of its internal components and repair is no longer cost effective. Included under the replacement would be the major rebuilding of any component, since rebuilding also restores performance.
RESTORATION Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes.
SUSTAINMENT Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities.
TROUBLE CALL Any work required to return a facility, system, equipment or component to normal working condition. Trouble calls are minor facility problem requests or requests for facilities-related work that are too small to be planned and estimated.
TROUBLE CALL CYCLE Count down starts when the customer is notified that the work has been accepted to be accomplished to the time when the work chit is turned in by the craftsmen as complete is one complete cycle period for a service call.
TROUBLE CALL,
EMERGENCY
Emergency trouble call is work to prevent immediate danger to personnel and equipment, prevent loss or damage to property, and/or preclude fulfillment of an essential activity operation or training mission.
TROUBLE CALL, SERVICE Maintenance and repair work that requires a minimal amount of planning or processing and can be accomplished in a short time, but is not of an emergent nature
WEIGHT HANDLING
EQUIPMENT (WHE)
Weight handling equipment consists of cranes (e.g., portal cranes, jib cranes), rigging gear (e.g., slings, shackles), and associated equipment (e.g., portable hoists, dynamometers). For purposes of this technical sub-annex, WHE does not include mobile or transportable truck, crawler, and railway mounted locomotive cranes covered in 1700000 BSVE.
J-1502000-01 Page 3
Acronym Title BPVC Boiler and Pressure Vessel Code HVAC Heating, Ventilation, and Air Conditioning RPIE Real Property Inventory Equipment SCADA Supervisory Control And Data Acquisition SRM Sustainment, Restoration and Modernization UFC Unified Facilities Criteria UPV Unfired Pressure Vessel VTE Vertical Transportation Equipment
LBS Load Break Switch T ( )Or TR Transformer CT Current Transformer VT Voltage Transformer V Volt Meter A Ammeter WH Wat Hour Meter W Wattmeter AS ( )Ammeter Changeover Switch VS (Volt Meter Changeover Switch) MCCB Molded Case Circuit Breaker OCR Over Current Relay DS Disconnecting Switch LA Lightning Arrestor GCB Gas Circuit Breaker PF Power Fuse VCB Vacuum Circuit Breaker UVR Undervoltage Relay CH Cable Head GR Ground Relay ZCT Zero-phase-sequence Current Transformer PCS or PC Primary Cutout Switch LDS Load Disconnecting Switch OCGR Over Current Ground Relay VCS Vacuum Contactor Switch ER (Residual current sensing and relaying equipment) DGR Directional Ground Relay C or SC Capacitor CTT Current Test Terminal CS Control Switch
Also, refer to Reference Drawings that may have some abbreviations.
J-1502000-02 Page 1
ATTACHMENT J-1502000-02
REFERENCES AND TECHNICAL DOCUMENTS
References are also listed in J-0200000-03 and other attachments of J-0200000 series.
Reference Title NFAP (National Fire Protection Association)
NFPA 780 Standard for the Installation of Lightning Protection Systems
Unified Facility Criteria (UFC) UFC 3-560-01 Electrical Safety, O & M
Japanese Industrial Standards
(JIS)
JIS C 2101 Testing Methods of Electrical Insulating Oils
Publications, Ministry of Land, Infrastructure, Transport and Touring (MLIT) of Japan
Facility Maintenance Work Common Specification (Kenchiku hozen gyoumu kyotsuu siyousho)
EM 385-1-1 U.S. Army Corps of Engineers, Safety and Health Requirements
DOD Instruction 1000-18 Federal and State Occupational Safety and Health Inspection and Investigation at Contractor Workplace on Department of Defense Installations
U.S. Public Law P.L. 91-596 Occupational Safety and Health Act
COMNAVFORJAPANINST
(Commander Naval Forces Japan Instruction)
COMNAVFORJAPANINST 11320.2(series) Fire Prevention Regulation COMNAVAIRFORINST 4790.2 (series) Naval Aviation Maintenance Program
Note: Latest version of references shall be applied.
J-1502000-03 Page 1
ATTACHMENT J-1502000-03
FACILITIES PROPERTY AND EQUIPMENT INVENTORY
Notes:
This attachment (including sub-attachment J-1502000-03.1) lists up major equipment.
Reference Drawings (Ref-DWGs) are listed up in sub-attachment J-1502000-03.2.
Some minor equipment including but not limited to panel lighting, panel indicators, fuses, mold case circuit breakers, cable heads, bus duct, and devices/parts in panels may not be listed, however, they shall be contractor’s maintenance responsible equipment.
PRIOR TO INITIAL INSPECTION (normally in Base Period or in the First Option Period), the Contractor shall conduct site check to understand equipment location, system diagram, connection, function. If any difference noted on ref-dwg, correct. (Refer to Spec Item 3.)
J-1502000-03 Page 2
Part AA: NAVFAC FE UTILITIES AND ENERGY MANAGEMENT (UEM) FACILITIES:
1. MAIN ELECTRICAL SUBSTATION (Bldg. 27 Area) (Location: NAF Atsugi):
Building No. Name Year Built System System Age
27 Main Electrical Substation
1982 Main Electrical Substation System
36 years
SYSTEM EQUIPMENT INVENTORY: MAIN ELECTRICAL SUBSTATION #27
Main Receiving Lines:
Line Disconnecting Switch (DS), Line Switch (LS)
- 800A, 72KV (1 ea.) (Nakaayase No.2 Line, Primary) (made in 1987)
- 800A, 72KV (1 ea.) (Nakaayase No.1 Line, Primary) (made in 1987)
- 800A, 72KV (1 ea.) (No.2 Line, earthing switch) (made in 1987)
- 800A, 72KV (1 ea.) (No.1 Line, earthing switch) (made in 1987)
- 800A, 72KV (1 ea.) (No.2 Line Secondary) (made in 1981)
- 800A, 72KV (1 ea.) (No.1 Line Secondary) (made in 1981)
- 800A, 72KV (1 ea.) (66kV Lightning Arrestor) (made in 1981)
- 800A, 72KV (1 ea.) (No.2 Line to G/I/J Lines Primary) (made in 1981)
- 800A, 72KV (1 ea.) (No. 1 Line to H/JMSDF Lines Primary) (made in 1995)
Vacuum Circuit Breakers (VCB)
- 72KV, 1200A, 25KA (Nakaayasen No.2) (made in 1987)
- 72KV, 800A, 25KA, with 3 CT, 300-100/5A (Nakaayasen No.1) (made in 2011)
Current Transformers (CT) (including Zero Current Transformer/ZCT):
(Note: Some VCBs contain CT. Refer to “Vacuum Circuit Breakers”.)
- 300-150/5A, 40VA, oil-immersed (3 ea.) (Nakaayase No. 2 Line, secondary of VCB) (made in 1987)
Lightning Arresters (LA):
- 84kV, 10kA (3 ea.) (66kV Primary) (made in 1995)
Protective Relays Digital Protective Relays:
(Note: 1 ea. per each unless otherwise specified) Type: PACIR-21T2-011 (Takaoka Co. Ltd) (made in 1996) (66kV No.1 Receiving, Bldg. 27, 1st Floor) Type: MR90S1-03 (Meidensha Co. Ltd) (made in 1996) (66kV No.2 Receiving, Bldg. 27, 1st Floor)
J-1502000-03 Page 3
Control Gear/Remote Control Panel
1st Floor;
- DC Power Panel (with Battery Charger; battery HS 150 Ah, 54 cells, Meidensya Co. Ltd, 8F9253TH) (made in 1996) Note: The battery is planned to be replaced with new in summer of 2013.
- 66 KV No. 1 Receiving Panel (M13) (made in 1981)
- 66 KV No. 2 Receiving Panel (made in 1996) 2nd Floor;
- Receiving Panel (M6) (Note: Ammeter 1 ea.)
J- Line:
- 600A, 72KV (1 ea.) (J Line Primary) (made in 1981)
- 72KV, 600A, 25KA (J-Line) (made in 1981)
- 15KV, 600A, 20KA (J-Line secondary side) (made in 1981)
Transformers (T, or TR):
- 4000KVA, 3-phase, 63KV/13.8KV (J-Line), Gas-filling Oil-Immersed (made in 1981) Note: This transformer contains a slight amount of PCB in oil.
- 80-40/5A, 40VA, oil-immersed (3 ea.) (J-Line, between VCB and main transformer) (made in 1981)
- 100/5A (1 ea.) (J-Line, Secondary, in cubicle) (made in 1981)
- 200/5A, BCT (bushing current transformer (3 ea.) (J-Line, Secondary, in cubicle) (made in 1981)
- 200/5A (3 ea.) (J-Line, in cubicle, secondary to VCB) (made in 1981)
Potential (Voltage) Transformers (PT or VT):
- 13.8KV/110V, (2 ea.) (J-Line Secondary, Cubicle) (made in 1981)
- 18kV (3 ea.) (J-Line) (made in 1981)
J-1502000-03 Page 4
Over Current Relay (OCR):
Type: KI0-C6P (6 ea.) (Meidensha Co. Ltd) (made in 1981) (J-Line Cubicle, for Transformer primary side)
Ratio-Differential Relay (RDFR):
Type: KID-TIYP (3 ea.) (Meidensha Co. Ltd) (made in 1981) (J-Line Cubicle, for Transformer)
Over Current Ground Relay (OCGR, GR):
Type: K10-L6P (Meidensha Co. Ltd) (made in 1981) Type: K10-LGP (Meidensha Co. Ltd) (made in 1981) (J-Line Cubicle, for transformer)
Under Voltage Relay (UVR):
Type: KIU-KP (Meidensha) (made in 1981) (J-Line Cubicle, for transformer)
Control Gear/Remote Control Panel/Switching Gear (Cubicle)
2nd Floor:
- J-Line Panel (M3) (Note: Watt-hour meter; 1 ea. Ammeter; 1 ea. Volt Meter; 1 ea.
Wattmeter 1 ea.)
Cubicle:
- Refer to Ref-DWG 4.
G- Line:
- 800A, 72KV (1 ea.) (G Line Primary) (made in 1981)
- 600A, 24KV (1 ea.) (G-Line Secondary) (made in 1970)
- 24KV (1 ea.) (G-Line GPT) (made in 1970)
- 400A, 12KV (1 ea.) (G-Line LA) (made in 1970)
- 72KV, 800A, 20KA, with 3-CT, 100/5A (G-Line) (made in 2010)
- 24KV, 600A, 20KA, with 3-CT, 200/5A (G-Line secondary side) (made in 2010)
Transformers (T, or TR)
- 4000KVA, 3-phase, 63KV/13.8KV, Gas-filling Oil-Immersed, (G-Line) (made in 1970) Note: This transformer contains PCB in oil.
- 5 kVA, 3-phase, 13.8KV/210V, Oil-Immersed (G-Line, for Main substation facility) (made in 2005)
J-1502000-03 Page 5
Current Transformers (CT) (including Zero Current Transformer/ZCT)
- 200-100/5A (1 ea.) (G-Line, Secondary, grounding) (made in 1970) Note: This CT contains PCB in oil.
- 200/5A, BCT (3 ea.) (G-Line, Secondary)
Potential (Voltage) Transformers (PT or VT)
- 13.8KV/110V, 110/3V, 200/50VA (1 ea.) (G-Line Secondary, GPT) (made in 1970)
Lightning Arresters (LA)
- 18kV (3 ea.) (G-Line) (made in 1970)
Over Current Relay (OCR):
Type: KI0-CP (3 ea.) (Meidensha) (made in 1981) (G-Line Panel, G-line transformer, Bldg. 27 2nd Floor) Type: CIO2-IH2D (3 ea.) (Takaoka Co. Ltd) (made in 1981) (66kV G&H-Line, Bldg. 27, 1st Floor)
Ratio-Differential Relay (RDFR):
Type: KID-TIP (3 ea.) (Meidensha Co. Ltd) (made in 1981) (G-Line panel, G-line transformer, Bldg. 27 2nd Floor)
Over Current Ground Relay (OCGR, GR):
Type: K10-L6P (Meidensha Co. Ltd) (made in 1981) Type: K10-LGP (Meidensha Co. Ltd) (made in 1981) (G-Line Panel, G-line transformer, Bldg. 27 2nd Floor)
Under Voltage Relay (UVR):
Type: KIU-KP (Meidensha) (made in 1981) (G-Line panel, G-line transformer, Bldg. 27 2nd Floor)
1st Floor:
- 66 KV G, H-Line Panel (made in 1981) Note: The panel is now for G-Line.
2nd Floor:
- G-Line Panel (M4) (Note: Watt-hour meter; 1 ea. Ammeter; 1 ea. Volt Meter; 1 ea.
Wattmeter; 1 ea. For relays, refer to above “Protective Relays.”)
- Refer to Ref DWG 4.
J-1502000-03 Page 6
I- Line:
- 800A, 72KV (1 ea.) (I Line Primary)(made in 1981)
- 1200A, 7.2KV (1 ea.) (I-Line Secondary, Cubicle, transformer secondary/6.6KV receiving) (made in 1996)
- 72KV, 800A, 20KA, with 3-CT, 100/5A (I-Line) (made in 2010)
- 7.2KV, 1200A, 20KA (I-Line secondary side, in Metal-Enclosed Switchgear, i.e., Cubicle Station) (made in 1996)
- 7.2KV, 600A, 12.5KA (5 each) (I-Line Cubicle Station) (made in 1996)
- 7500KVA, 3-phase, 63KV-6.6KV, Oil-Immersed (I-Line) (made in 1996)
- 30KVA, 3-phase, 6.6KV/210V-105V (I-Line, Cubicle/Transformer Panel, for Main substation facility) (made in 1996)
Vacuum Contactor (or Combination) Switches (VCS)
- 7.2KV/6.6KV, 200A, 4KA (3 each) (I-Line SC Capacitor Panels) (made in 1996)
Load Break Switch (LBS)
- 200A, 7.2KV (1 ea.) (I-Line Cubicle, transformer panel) (made in 1996)
- 750/5A (2 ea.) (I-Line, Secondary, Cubicle, transformer secondary/6.6KV receiving) (made in 1996)
- 1000/5A (3 ea.) (I-Line, Secondary, Cubicle, transformer secondary/6.6KV receiving) (made in 1996)
- 200/5A (4 ea.) (I-Line, Secondary, Cubicle, Feeder panel I1/I2) (made in 1996)
- ZCT, 1200A (1 ea.), 2000A (1 ea.) (I-Line, Secondary, Cubicle, Feeder panel I1/I2) (made in 1996)
- 200/5A (4 ea.) (I-Line, Secondary, Cubicle, Feeder panel I3/I4) (made in 1996)
- ZCT, 1200A (1 ea.), 2000A (1 ea.) (I-Line, Secondary, Cubicle, Feeder panel I3/I4) (made in 1996)
- 200/5A (2 ea.) (I-Line, Secondary, Cubicle, SC primary) (made in 1996)
- 75/5A (3 ea.) (1 ea. per each in I-Line Secondary Cubicle, SC Panel No. 1 through No. 3) (made in 1996)
J-1502000-03 Page 7
- 6600/110V, 200VA (2 ea.) (I-Line Secondary, Cubicle, Transformer Secondary) (made in 1996)
- 6600/110V, 100VA (6 ea.) (I-Line Cubicle, 2 ea. per each SC Panel No. 1 through No. 3) (made in 1996)
- 6600/110V, 190/3V, 200VA (1 ea.) (I-Line Secondary, GPT, Cubicle SC Primary) (made in 1996)
- 8.4kV, 10kA (3 ea.) (I-Line) (made in 1995)
Power Capacitors (SC)
- 6.6kV, 266kvar (6 ea; 1 ea. made in 2007, 1 ea. made in 2006, 4 ea. made in 2012) (I-Line Cubicle, SC Panel No. 1 through No. 3)
Series Reactors (SR)
- 6.6kV, 30 (31.9) kvar (3 ea. 1 ea. made in 2007, 2 ea. made in 2012) (I-Line Cubicle, SC Panel No. 1 through No. 3)
Type: MT90S2-02 (Meidensha Co. Ltd) (made in 1996) (66kV I-Line, Bldg. 27 1st Floor) Type: MT90S1-04 (Meidensha Co. Ltd) (made in 1996) (I-Line Cubicle, Transformer Secondary) Type: MB90S1-03 (Meidensha Co. Ltd) (made in 1996) (I-Line Cubicle, SC Primary Panel, Bus Voltage) Type: MF90S1-07 (Meidensha Co. Ltd) (made in 1996) (I-Line Cubicle, total 4 ea., 1 ea per each Feeder Panel I1 through I4) Type: MB90S1-03 (Meidensha Co. Ltd) (made in 1996) (I-Line Cubicle, SC Primary Panel)
- 66 KV I-Line Panel (M14) (made in 1996) 2nd Floor;
- 6.6kV I-Line Panel (M1) (Note: Watt-hour meter; 4 ea. Var Meter; 1 ea. Ammeter; 5 ea.
Volt Meter 1 ea. Wattmeter; 1 ea.)
- I-Line Panel (M2) (Note: Watt-hour meter; 1 ea. Ammeter; 1 ea. Volt Meter; 1 ea.
Wattmeter 1 ea.)
Cubicle:
- Refer to Ref-DWG 2.
(Note: Wattmeter; 1 ea. in Transformer Secondary/I-Line 6.6kVA Receiving)
J-1502000-03 Page 8
H-Line (New H-Line):
Note: “H-Line” under this specification may be referred to “New H-Line” on site, in order to distinguish from “old H-Line” which was used for JMSDF line.
- 800A, 72KV (1 ea.) (H Line Primary) (made in 1995)
- 1200A, 7.2KV (1 ea.) (H-Line, Secondary, Cubicle, transformer secondary/6.6KV receiving) (made in 1995)
- 72KV, 800A, 25KA (H-Line primary) (made in 1995)
- 7.2KV, 1200A, 20KA (H-Line secondary side, Cubicle Station, High voltage receiving panel) (made in 1995)
- 7.2KV, 600A, 20KA (5 each) (H-Line Cubicle Station) (made in 1995)
- 10,000KVA, 3-phase, 63KV-6.6KV, Oil-Immersed (H-Line) (made in 1982)
- 7.2KV/6.6KV, 200A, 4KA (6 each) (H Line SC Capacitor Panels) (made in 1995)
- 200-100/5A, 40VA, oil-immersed (3 ea.) (H-Line, between VCB and main transformer) (made in 1995)
- 1000-500/5A (2 ea.) (H-Line, Secondary, Cubicle, Transformer Secondary/ H Line 6.6KV receiving) (made in 1995)
- 1000-500/5A (3 ea.) (H-Line, Secondary, Cubicle, Transformer Secondary/ H Line 6.6KV receiving) (made in 1995)
- 600-300/5A (2 ea.) (H-Line Secondary Cubicle, Feeder panel H1/H2) (made in 1995)
- 400-200/5A (2 ea.) (H-Line Secondary Cubicle, Feeder panel H1/H2) (made in 1995)
- ZCT, 1200A (1 ea.), 2000A (1 ea.) (H-Line Secondary Cubicle, Feeder panel H1/H2) (made in 1995)
- 600-300/5A (4 ea.) (H-Line Secondary Cubicle, Feeder panel H3/H4) (made in 1995)
- ZCT, 1200A (1 ea.), 2000A (1 ea.) (H-Line Secondary Cubicle, Feeder panel H3/H4) (made in 1995)
- 400/5A (2 ea.) (H-Line Secondary Cubicle, Bus-Tie Panel) (made in 1995)
- 75/5A (6 ea.) (1 ea. per each in H-Line Secondary Cubicle, SC Panel No. 1 through
J-1502000-03 Page 9
No. 6) (made in 1995)
- 6600/110V, 200VA (2 ea.) (H-Line Secondary, Cubicle, Transformer Secondary) (made in 1995)
- 6600/110V, 100VA (12 ea.) (H-Line Cubicle, 2 ea. per each SC Panel No. 1 through No. 6) (made in 1995)
- 6600/110V, 190/3V, 200VA (1 ea.) (H-Line Secondary, GPT, Cubicle BUS-TIE Panel) (made in 1996)
- 8.4kV, 10kA (3 ea.) (H-Line) (made in 1995)
- 6.6kV, 266kvar (12 ea; 5 ea. made in 2007, 7 ea. made in 2006) (H-Line Cubicle, SC Panel No. 1 through No. 6)
- 6.6kV, 30 (31.9) kvar (6 ea; 3 ea. made in 2007, 3 ea. made in 2006) (H-Line Cubicle, SC Panel No. 1 through No. 6)
(Note: 1 ea. per each unless otherwise specified) Type: MT90S2-02 (Meidensha Co. Ltd) (made in 1994) (66kV H-Line, Bldg. 27 1st Floor) Type: MT90S1-04 (Meidensha Co. Ltd) (made in 1995) (H-Line Cubicle, Transformer Secondary) Type: MB90S1-03 (Meidensha Co. Ltd) (made in 1995) (H-Line Cubicle, BUS-DE Panel, Bus Voltage) Type: MF90S1-07 (Meidensha Co. Ltd) (made in 1995) (H-Line Cubicle, total 4 ea., 1 ea per each Feeder Panel H1 through H4) Type: MF90S1-06 (Meidensha Co. Ltd) (made in 1995) (H-Line Cubicle, BUS-DE Panel) (made in 1995)
- 66 KV H-Line Panel (M11) (made in 1994) 2nd Floor:
- (6.6KV) H-Line Panel (M7) (Note: Watt-hour meter; 5 ea. Var Meter; 1 ea. Ammeter; 6 ea.
Volt Meter; 1 ea. Wattmeter; 1 ea.)
- Ref-DWG 3.
J-1502000-03 Page 10
(Note: Wattmeter; 1 ea. in Transformer Secondary/H-Line 6.6kVA Receiving)
FOR JMSDF LINES (JMSDF West Line, JMSDF East Line):
- 800A, 72KV (1 ea.) (for JMSDF west/east lines primary) (made in 1997)
JMSDF West Line:
- 800A, 72KV (1 ea.) (JMSDF West Line Primary) (made in 1997)
- 400A, 7.2KV (1 ea.) (JMSDF West Cubicle, high-voltage receiving/transformer secondary) (made in 1996)
- 72KV, 800A, 25KA (JMSDF West Line) (made in 1997)
- 7.2KV, 600A, 12.5KA (2 each) (JMSDF West Cubicle Station, High voltage receiving panel, and No. 1 feeder panel) (made in 1996)
- 7.2KV, 600A, 12.5KA (3 each) (JMSDF West Cubicle Station, No. 1 feeder panel, No. 2 feeder panel, Capacitor main panel) (made in 1995)
- 7.2KV, 600A, 12.5KA (1 each) (JMSDF West Cubicle Station, No. 2 feeder panel) (made in 2000)
- 5000 KVA, 3 phase, 63KV/6.3KV-3.15KV, Oil-Immersed (JMSDF West Line) (made in 1987)
- 50kVA, 3-phase, 6.6KV/210V-105V, Oil-Immersed (JMSDF West Line Cubicle Station) (made in 1996) Note: Above transformers may or may not contain a slight amount of PCB in oil.
No analysis result has been made.
Load Break Switch (LBS)
- 200A, 7.2KV (1 ea.) (JMSDF West Line, Cubicle, transformer panel/syonai dengenban) (made in 1996)
- 50/5A, 40VA, oil-immersed (3 ea.) (JMSDF West Line, between VCB and main transformer) (made in 1981)
- 400/5A (2 ea) (JMSDF West Line, Secondary, Cubicle, Transformer secondary/ high voltage receiving) (made in 1997)
- 500/5A (3 ea.) (JMSDF West Line, Secondary, Cubicle, Transformer secondary/
J-1502000-03 Page 11 high voltage receiving) (made in 1997)
- Exact capacity unknown (8 ea.) (JMSDF West Line, Secondary, Cubicle, Feeder panel No. 1, Feeder panel No. 2, Capacitor main) (made in 1997)
- 6600/110V, 190/3V, 200VA (1 ea.) (JMSDF West Line Cubicle, Capacitor Main GTV, GPT) (made in 1996)
- 6600/110V, 100VA (2 ea.) (JMSDF West Line Cubicle, Transformer Secondary/ High voltage receiving) (made in 1996)
- 6.6KV/3.3KV, 200A, 4KA (4 each) (JMSDF West Cubicle Station) (made in 1996)
- 8.4kV (3 ea.) (JMSDF West-Line, Transformer Secondary) (made in 1996)
- 6.6kV, 300kvar (4 ea.) (JMSDF West-Line Cubicle, No. 1 through No. 4 SC Panel) (made in 2004)
- 6.6kV, 18 kvar (4 ea.) (JMSDF West-Line Cubicle, No. 1 through No. 4 SC Panel) (made in 1996)
Type: CIO2-IH2D (3 ea.) (Takaoka Co. Ltd) (made in 1981) (JMSDF West-Line transformer primary side) Type: MOC-EIV-R (Mitsubishi Electric Co. Ltd) (made in 1996) (1 ea. JMSDF West-Line Cubicle, transformer secondary) (4 ea. JMSDF West-Line Cubicle, Feeder panels) (1 ea. JMSDF West-Line Cubicle, Capacitors main)
Ratio-Differential Relay (RDFR):
Type: CIR2-QD (3 ea.) (Takaoka Electric Co. Ltd) (made in 1981) (JMSDF West-Line transformer)
Over Current Ground Relay (OCGR, GR):
Type: MVG-E2V-R (Mitsubishi Electric Co. Ltd) (made in 1996) (JMSDF West-Line, Kohatsu Bosen)
Under Voltage Relay (UVR):
Type: MUV-EIV-R (Mitsubishi Electric. Co. Ltd) (made in 1996)
J-1502000-03 Page 12
(JMSDF West-Line, Bus Bar, Kohatsu Bosen)
Over Voltage Ground Relay (OVGR):
Type: MVG-E2V-R (Mitsubishi Electric Co. Ltd) (made in 1996) (JMSDF West-Line, Bus Bar, Kohatsu Bosen)
Directional Ground Relay (DGR):
Type: MDG-E2V-R (4 ea.) (Meidensha Co. Ltd) (made in 1996) (JMSDF West-Line Cubicle, Feeder panels)
Cubicle
- Refer to Ref-DWG 5.
JMSDF East Line:
Line Disconnecting Switch (DS)
- 800A, 72KV, 25kA (1 ea.) (JMSDF East Line Primary, in Gas Insulated Switch Gear) (made in 2012)
- 600A, 7.2kV, 20kA (1 ea.) (JMSDF East Line Secondary, Cubicle, transformer secondary (1)) (made in 2012)
- 600A, 7.2kV, 12.5kA (2 ea.) (JMSDF East Line Secondary, Cubicle, Change-Over Panel (1)) (made in 2012)
- 72kV, 800A, 25kA (1 ea.) (JMSDF East Line Primary, in Gas Insulated Switch Gear) (made in 2012)
- 7.2kV, 600A, 12.5kA (1 ea.) (JMSDF East Line Secondary, Cubicle, transformer secondary (2)) (made in 2012)
- 7.2kV, 600A, 12.5kA (1 ea.) (JMSDF East Line Secondary, Cubicle, change-over panel (1)) (made in 2012)
- 7.2kV, 600A, 12.5kA (2 ea.) (JMSDF East Line Secondary, Cubicle, change-over panel (2)) (made in 2012)
Transformers (T, or TR):
- 5000KVA, 3-phase, 63KV/6.6KV, Gas-filling Oil-Immersed (JMSDF East Line) (made in 2012)
Current Transformers (CT) (including Bushing Current Transformer/BCT):
- BCT 150/1A (JMSDF East Line, Gas Insulated Switch Gear) (made in 2012)
- 600/5A (3 ea.) (JMSDF East Line, Secondary, Cubicle, transformer secondary (2)) (made in 2012)
- 600/5A (3 ea.) (JMSDF East Line, Secondary, Cubicle, change-over panel (2)) (made in 2012)
- 600/5A (3 ea.) (JMSDF East Line, Secondary, Cubicle, change-over panel (2))
J-1502000-03 Page 13
Potential (Voltage) Transformers (PT or VT):
- 6600V/110V/ 190/3V, 200VA (2 ea.) (JMSDF East Line Cubicle, transformer secondary (2)) (made in 2012)
- 8.4kV (3 ea.) (JMSDF East-Line, Cubicle) (made in 2012)
Protective Relays:
Type: MT85B-04A (3 ea.) (Meidensha Co. Ltd) (made in 2012) (JMSDF-East-Line Cubicle, transformer secondary (1)) Type: MW85B-01 (2 ea.) (Meidensha Co. Ltd) (made in 2012) (JMSDF East-Line Cubicle, transformer secondary (2))
Ratio-Differential Relay (RDFR):
Type: MT85B-04A (3 ea.) (Meidensha Co. Ltd) (made in 2012) (JMSDF East-Line Cubicle, transformer secondary (1))
Over Current Ground Relay (OCGR, GR):
Type: MW85B-01 (Meidensha Co. Ltd) (made in 2012) (JMSDF East-Line Cubicle, transformer secondary (2))
Under Voltage Relay (UVR):
Type: MW85B-01 (Meidensha Co. Ltd) (made in 2012) (JMSDF East-Line Cubicle, transformer secondary (2))
- Refer to Ref-DWG 5.
(Note: Watt-hour meter; 1 ea. Ammeter; 3 ea. Volt Meter; 1 ea.
Wattmeter; 1 ea. Power Factor Meter; 1 ea.)
Monitoring System:
(Located at 2nd Floor of Bldg. 27 unless otherwise indicated) Monitoring Equipment for Main Substation #27 (installed in 2010);
(This monitoring system is a system made by Yokogawa Co. Ltd.)
Switch Panel, System Keyboard, Monitoring Panel, UPS, Transducer (product of Yokogawa Co. Ltd.) Personnel Computer set, Printer, Control Processing Unit (located at 1st Floor)
Monitoring Equipment for 60 Cycle Power Plant (Bldg. 201);
(This monitoring system is a system made by Meidensha Co. Ltd.)
Central Processing Unit, Monitoring Panel, UPS, Transducer (product of Meidensha Co. Ltd.) Personnel Computer set, J-1502000-03 Page 14
See “2. Bldg. 201” for equipment located in Bldg. 201.
J-1502000-03 Page 15
2. 60HZ POWER PLANT (BLDG. 201 Area) (Location: NAF Atsugi):
201 60 CYCLE
POWER PLANT
1961 60 Hz Frequency Converter Power Plant
30 years
SYSTEM EQUIPMENT INVENTORY: 60 CYCLE POWER PLANT #201
Cubicle (Secondary Unit Switchgear) Unit C-201 (H-1 Line):
- Lightning Arresters; 8.4kV (3 ea.) (made in 1995)
- Potential Transformer; 6.6kV/110V (2 ea.)
- Vacuum Circuit Breaker, 7.2kV, 600A, 12.5KA (1 ea.) (made in 1996)
- Meters: Voltmeter, 0 - 15,000V; Ammeter, 150A; Reactive Volt/Ampere Meter (Var Meter)
- Over Current Relay, Type: KI0-CP (3 ea.) (Meidensha Co. Ltd) (made in 1988)
- Current Transformer, 200/5A (3 ea.)
- Bus Duct
- Oil-Immersed Transformer, 3000kVA, 3-phase, 6.6kV/3.3kV (made in 1995, Aichi)
- Cable Head (3 ea.)
Battery/Charger Panel (BC) (made in 1988):
- Rectifier Unit
- Voltage Stabilizing Unit
- Alarm Trouble Lamp Circuits
- Charging Indicator/Monitor Circuit
- Lead Acid Wet Cell Batteries (9 each), 54 cells total
- Meters: DC Ammeter, DC Voltmeter, DC Ammeter for Rectifier
3Ø3W 3.3kV 50Hz Incoming Panel (H1A)/Tie Feeder Panel (H1B):
- Vacuum Circuit Breaker, 3.6kV, 600A, 12.5kA (1 ea.) (made in 1988)
- Ammeter (2 ea.)
- Over Current Relay, Type: KI0-CP (3 ea.) (Meidensha Co. Ltd) (made in 1988)
- Ground Directional Relay, Type: KIG-CFP (1 ea.) (Meidensha Co. Ltd) (made in 1988)
- Current Transformer, 600-300/5A (6 ea.) (made in 1988)
- Cable Head (6 ea.)
3Ø 3W 3.3kV 50Hz Station Service Transformer Panel (H2):
- Load Break Switch, 200A, 7.2kV (1 ea.) (made in 1988)
- Transformer, dry-type, 3-phase, 75kVA, 3.3kV/208-120V (made in 1988, Meidensha Co. Ltd)
- Ammeter (1 ea.), 300A
J-1502000-03 Page 16
- Voltmeter (1 ea.), 300V
- Current Transformer, 300/5A (made in 1988)
- MCCB, 400A (1 ea.), 100A (5 ea.), 50A (7 ea.)
3Ø 3W 3.3kV 50Hz No.1 Synchronous Motor Panel (M11):
- Vacuum Circuit Breaker, 3.6kV, 600A, 12.5kA (1 ea.) (made in 1988)
- Current Transformer, 600-300/5A (3 ea.) (made in 1988)
- Ground Potential Transformer, 3.3kV/110V, 110/3V (1 ea.) (made in 1988)
- Voltmeter, 4500V
- Frequency Meter, 45 - 55 Hz
- Under Voltage Relay (UVR), Type: KIU-KP (1 ea.) (Meidensha Co. Ltd) (made in 1988)
- Over Voltage Ground Relay (OVGR), Type: KIE1-KP (1 ea.) (Meidensha Co.
Ltd) (made in 1988)
- Cable Head (3 ea.)
3Ø 3W 3.3kV 50Hz No.1 Exciter Panel for Synchronous Motor (M12):
- Speed Relay, Type: NTN-03 (1 ea.) (Meidensha Co. Ltd) (made in 1990)
- Ammeter
- Vacuum (magnetic) Contactor Switch, Type: VSR-342EA (Meidensha Co. Ltd) 3300V, 400A (made in 1988)
- Thyristor Unit for Manual Voltage Regulation, 110V, 30A, 50 Hz
- Lightning Arresters (3 each) and Surge Capacitor
- Transformer, 2kVA 210/110V
- Cable Head (3 ea.)
3Ø 3W 3.3kV 50Hz No.1 Motor Starter Panel (M13) (made in 1988):
- Vacuum Circuit Breaker, 3.6KV, 600A, 12.5kA (1 ea.)
- Trouble Alarm Indicator Circuits and Lamps
- Cable Head, 3.3KV (3 each)
- Meters: Volt/Ampere Reactive (Var meter); Watt meter ; Watthour meter;
Power Factor meter; Ammeter (1 ea. per each)
- Over Current Relay (OCR), Type: KI0-C6P (3 ea.) (Meidensha Co. Ltd)
- Over Current open-phase Relay (OLR), Type: NTY-16 (Meidensha Co. Ltd) (made in 2010)
- Stepout Relay, Type: KCZ-R011Z (Meidensha Co. Ltd)
- Power Factor Relay (PFR)
3Ø 3W 6.6kV 60Hz No.1 Generator Panel (G11) (made in 1988):
- Potential Transformer 6.6kV-3.3kV/110V (4 ea.)
- Current Transformer, 600-300/5A (3 ea.)
- Vacuum Circuit Breaker, 7.2kV, 600A, 12.5kA
- Over Voltage Relay (OVR), Type: KIE-KP (Meidensha Co. Ltd)
- Voltage Control Over Current Relay (VR OCR), Type: KIZ-C3RP (3 ea.)
(Meidensha Co. Ltd)
J-1502000-03 Page 17
- Meters: Voltmeter, 4500v; Frequency Meter; Wattmeter; Watthour Meter;
Power Factor Meter; Ammeter
- Cable head, 6.6KV (3 ea.)
- Filter (2 ea.)
3Ø 3W 6.6kV 60Hz No.1 Generator Control Panel (G12) (made in 1988):
- Automatic Voltage Regulator with Manual Adjustment
- Trouble Lamp Indicator Circuits
- Winding Temperature Thermometer
- Transformer, 2kVA 210/110V
3Ø 3W 6.6kV 60Hz South Feeder Panel (F1) (made in 1988):
Note: South Feeder Panel (F1) is for facilities located on 60-2 Line.
- Vacuum Circuit Breaker, 7.2kV, 600A, 12.5kA
- Current Transformer, 600-300/5A (3 ea.)
- Zero Phase Current Transformer
- Over Current Relay (OCR), Type: KI0-CP (3 ea.) (Meidensha Co. Ltd)
- Ground Directional Relay (DGR), Type: LDG-21 (Hikari Co. Ltd)
- Ammeter
- Ground Potential Transformer, 6.6-3.3kV/110V/110/3V
- Voltmeter (4500V)
- Zero Sequence Voltmeter, Zero Sequence Potential Device
- Cable Head (3 ea.)
3Ø 3W 3.3kV 50Hz No.2 Synchronous Motor Panel (M21) (made in 1988):
- Vacuum Circuit Breaker, 3.6kV, 600A, 12.5kA
- Disconnecting Switch (3 ea.) 3.6kV 400A
- Lightning Arresters (3 ea.) and Surge Capacitor
- Current Transformer, 600-300/5A (3 ea.)
3Ø 3W 3.3kV 50Hz No.2 Exciter Panel for Synchronous Motor (M22) (made in 1988):
- Speed Relay, Type: NTN-03 (1 ea.) (Meidensha Co. Ltd) (made in 1990)
- Vacuum (magnetic) Contactor Switch, Type: VSR-342EA (Meidensha Co. Ltd) 3300V, 400A
- Ammeter
- Thyristor Unit for Manual Voltage Regulation, 110V, 30A, 50 Hz
- Lightning Arresters (3 ea.) and Surge Capacitor
- Transformer, 2kVA 210/110V
- Cable head (3 ea.)
3Ø 3W 3.3kV 50Hz No.2 Motor Starter Panel (M23) (made in 1988):
- Vacuum Circuit Breaker, 3.6KV, 600A, 12.5kA (1 ea.)
- Trouble Alarm Indicator Circuits and Lamps
J-1502000-03 Page 18
- Cable head, 3.3KV (3 each)
- Meters: Volt/Ampere Reactive (Var meter); Watt meter ; Watthour meter;
Power Factor meter; Ammeter (1 ea. per each)
- Over Current Relay (OCR), Type: KI0-C6P (3 ea.) (Meidensha Co. Ltd)
- Over Current open-phase Relay (OLR), Type: NTY-16 (Meidensha Co. Ltd) (made in 2010)
- Stepout Relay, Type: KCZ-R011Z (Meidensha Co. Ltd)
- Power Factor Relay (PFR)
3Ø 3W 6.6kV 60Hz No.2 Generator Panel (G21) (made in 1988):
- Potential Transformer 6.6kV-3.3kV/110V (4 ea.)
- Current Transformer, 600-300/5A (3 ea.)
- Vacuum Circuit Breaker, 7.2kV, 600A, 12.5kA
- Over Voltage Relay (OVR), Type: KIE-KP (Meidensha Co. Ltd)
- Voltage Control Over Current Relay (VR OCR), Type: KIZ-C3RP (3 ea.)
(Meidensha Co. Ltd)
- Meters: Voltmeter, 4500v; Frequency Meter; Wattmeter; Watthour Meter;
Power Factor Meter; Ammeter
- Cable head (3 ea.)
3Ø 3W 6.6kV 60Hz No.2 Generator Control Panel (G22) (made in 1998):
- Automatic Voltage Regulator with Manual Adjustment
- Trouble Lamp Indicator Circuits
- Winding Temperature Thermometer
- Transformer, 2kVA 210/110V
- Disconnecting Switch, 7.2kV, 400A (3 ea.)
- Lightning Arresters, 4.2kV, (3 ea.) and Surge Capacitor (3 ea.)
- Zero Phase Capacitor
- Cable head (3 ea.)
3Ø 3W 6.6kV 60Hz North Feeder Panel (F2) (made in 1988):
Note: North Feeder Panel (F2) is for facilities located on 60-1 Line.
- Vacuum Circuit Breaker, 7.2kV, 600A, 12.5kA
- Current Transformer, 600-300/5A (3 ea.)
- Zero Phase Current Transformer
- Over Current Relay (OCR), Type: KI0-CP (3 ea.) (Meidensha Co. Ltd)
- Ground Directional Relay (DGR), Type: LDG-21 (Hikari Co. Ltd)
- Ground Over Voltage Relay (GVR), Type: LVG-3C (Hikari Co. Ltd) (made in 1998)
- Ammeter
- Cable Head (3 ea.)
No.1 Starting Transformer Panel (ST1) (made in 1988):
- 3 Phase Starting Transformer with Taps, 3144-6162 KVA
J-1502000-03 Page 19
- Capacitor, 3-phase, 0.2 µ F (farad) (3 ea.)
- Cable head 6.6kV (3 ea.)
No.2 Starting Transformer Panel (ST2) (made in 1988):
- 3 Phase Starting Transformer with Taps, 3144-6162 KVA
- Capacitor, 3-phase, 0.2 µ F (farad) (3 ea.)
- Cable head 6.6kV (3 ea.)
Motor Generator Set No.1 (MS1, GS1) (made in 1988):
- Synchronous Motor, 3.3KV, 3-phase, 50 Hz, 1600KW, 10-pole (Meidensha Co. Ltd, Type: E-YF)
- Synchronous Generator/Alternator, 6.6KV, 3-phase, 60 Hz, 1875 KVA, 12-pole (Meidensha Co. Ltd, Type: E-AF)
- Cable Terminations for Synchronous Motor, 3.3KV (3 each)
- Cable Terminations for Generator/Alternator, 6.6KV (3 each)
- Silicon Controlled Rectifier, 22 KW, 50V, 440A (2 each)
- Alternating Current Exciter Units, 25 KVA, 600 RPM, 60 Hz, 16-pole (2 each)
- Bearing Temperature Thermometers (4 each)
Motor Generator Set No.2 (MS1, GS1) (made in 1988):
- Synchronous Motor, 3.3KV, 3-phase, 50 Hz, 1600KW, 10-pole (Meidensha Co. Ltd, Type: E-YF)
- Synchronous Generator/Alternator, 6.6KV, 3-phase, 60 Hz, 1875 KVA, 12-pole (Meidensha Co. Ltd, Type: E-AF)
- Cable Terminations for Synchronous Motor, 3.3KV (3 each)
- Cable Terminations for Generator/Alternator, 6.6KV (3 each)
- Silicon Controlled Rectifier, 22 KW, 50V, 440A (2 each)
- Alternating Current Exciter Units, 25 KVA, 600 RPM, 60 Hz, 16-pole (2 each)
- Bearing Temperature Thermometers (4 each)
Monitoring System:
Monitoring Equipment for 60 Cycle Power Plant (Bldg. 201);
(This monitoring system is a system made by Meidensha Co. Ltd.)
Remote Station Panel (RS):
- RS contains various device including but not limited to;
Noise Filter, DC Converter, Optical Reputor, Transceiver Units, and PC Controller
Field Interface Panel (1F) (made in 1988):
- Current Transducer (9 ea.)
- Voltage Transducer (6 ea.)
- Frequency Transducer (3 ea.)
- Watt Transducer (4 ea.)
- Var Transducer (3 ea.)
- Power Factor Transducer (4 ea.)
J-1502000-03 Page 20
Auto Logging Panel (made in 2003) (Yokogawa Co. Ltd, with power monitor model#: PR201) Monitoring Panel (made in 2009)
CRT Monitoring PC Set with UPS (located in office room)
Fiber Optic Control Cables from 60 Cycle Power Plant #201 to Main Electrical Substation #27
Followings are located in Bldg. 27 main substation 2nd floor;
- Central Processing Unit, Monitoring Panel, UPS, Transducer (product of Meidensha Co. Ltd.,) Personnel Computer set, System and Equipment Grounding:
- Receiving Station Transformers Lightning Arrester Grounding
- Exterior System Grounding Connections/Ground Bus
- Ground Terminal Block within the 60 Cycle Power Plant
- All Grounding and Bonding Conductors and Connections within Plant
- All Grounding and Bonding Conductors and Connections outside Plant
Facility Ventilation System:
- Power Control Panel "P" with Roof Ventilator Controls and Meters
- Roof Ventilators (3 each)
J-1502000-03 Page 21
3. CUBICLE TYPE SECONDARY UNIT SUBSTATIONS (under UEM Controlled):
Refer to Attachment J-1502000-03.1.
J-1502000-03 Page 22
Part AB: NAF ATSUGI Station Facilities:
1. BLDG. 914 (On G-Line):
914 Housing Mid-rise
1972 Secondary Unit Substation (located in B floor electrical room)
41 yeas;
SYSTEM EQUIPMENT INVENTORY: BLDG. # 914 (G-Line)
Transformers
- 200 KVA, 13.8KV/6.6KV - 220/110V, 1-phase, 50 Hz (3 each) (made in 2007)
- 50 KVA, 13.8KV/6.6KV - 220V, 3-phase, 50 Hz (made in 2007) Note: Above transformers may or may not contain a slight amount of PCB in oil.
No analysis result has been made.
Disconnecting Switch:
- 400A, 22KV (12 each), Non-fused
- 30A, 3.45KV (5 each), Fused
Oil Circuit Breaker:
- Oil Circuit Breaker, 300A, 22KV, 1000 MVA
Potential Transformer:
- Potential Transformers, 100V, 50VA, 3.45KV (2 each)
Current Transformer:
- Current Transformer, 300/5A (3 each)
Protective Relays:
- Over Current Relay (3 ea.) (Mitsubishi, Type: MOC-A1V-R) (made in 2007)
Meters (in 13.8kV Receiving Panel):
- Watthour Meter (made in 2007);
- Voltmeters (made in 2007);
- Demand Meter (made in 2007)
J-1502000-03 Page 23
MCB:
- 1000AF/1000AT (3 ea.) (made in 2007), 30AF/20AT (3 ea.), 30AF/30AT (4 ea.)
Meters (in Lighting Panel):
- Voltmeter (0 - 300V) (4 ea.) (made in 2007)
- Demand Meter (0 - 1000A) (3 ea.) (made in 2007), Demand Meter (0 - 100A)
Meters (in Power Panel):
- Voltmeter (20kV) (1 ea.) (made in 2007)
Miscellaneous Equipment (13.8kV Receiving Panel):
- Voltage Adapter (3W, 220V, 50Hz-100VDC) (2 ea.)
Miscellaneous Equipment (Lighting Panel):
- Current Transformer; 1000/5A x 2 ea. (3 ea.), 100/5A x 2 ea. (made in 2007)
- Dry Transformer, 1-phase 3W, 50VA
- Double Throw Switch
Panels:
- 3kV Receiving Panel
- 13.8KV Receiving Panel
- Lighting Panel
- Power Panel
J-1502000-03 Page 24
2. BLDG. 194 (C-194, On H-3 Line and 60-2 Line):
Building No. Name Year Built System System Age
194 AIMD
(Aircraft Intermediate
Maintenance Department)
1988 Secondary Unit Substation
25 years
SYSTEM EQUIPMENT INVENTORY: BLDG. #194
C-194 SECONDARY UNIT SUBSTATION
(made in 1987)
50-HZ LINE (H-3 Line)
- Transformer, oil-immersed, 600 KVA, 6.6KV/208V/120V, 3-phase (ph), 4-wire, 50-Hz (made in 1995) Note: Above transformers may or may not contain a slight amount of PCB in oil.
No analysis result has been made.
- Transformer, 6.6KV/110V, Single Phase, 50-Hz
- Transformer, 208V/105V, Single Phase, 2-wire
- Molded Case Circuit Breaker, 2-pole, 50AT, 50AF
- Vacuum Circuit Breaker (VCB), 7.2KV, 400A
- Fused Disconnect, 6.6KV (3 each)
- Lightning Arrester, 14KV (3 each)
- 400A Bus in duct at transformer primary (3 each)
- Potential Transformer (PT), 6.6KV/110V, 50VA (2 each) (made in 1995)
- Current Transformer (CT), 75/5A (3 each) (made in 1995)
- Meters: Voltmeter, 0 - 9KV/150V (made in 1995); Voltmeter, 300V Ammeter, 0 - 75A (made in 1995), 2500/5A, Watthour Meter
- Cable Heads, 6.6KV (3 ea.)
- Over Current Relay (3 each) (Type: KIO-C6P, Meidensha Co. Ltd)
- Fuse, 7.2KV, 3A (2 each)
- Over Current Ground Relay (Type: KIO-LGP, Meidensha Co. Ltd)
- Bus Duct
- MCB; 400AF/400AT (4 ea.), 400AF/300AT (1 ea.), 50AF/20AT (3 ea.), 600AF/600AT (1 ea.), 400AF/NT (1 ea.) 225AF/225AT (2 ea.), 100AF/30AT (1 ea.), 50AF/50AT (1 ea.)
NOTE: Originally, the 50Hz line was on 13.8kV, but it was changed to 6.6kV in 1995.
60-HZ LINE (60-2 Line)
- Transformer, 200 KVA, 6.6KV/3.3KV/208V/120V, 3-ph, 4-wire, 60-Hz
- Transformer, 300 KVA, 6.6KV/3.3KV/440V, 3-ph, 3-wire, 60-Hz Note: Above transformers may or may not contain a slight amount of PCB in oil.
No analysis result has been made.
J-1502000-03 Page 25
- Transformer, 3.3/6.6kV/110V, 1-ph
- Vacuum Circuit Breaker, 7.2KV, 400A
- Lightning Arresters, 7.2KV (3 each)
- Load Break Switches, 7.2KV, 200A, 40 - 75A Fuse, 40KA 7.2KV, 200A, 60 - 75A Fuse, 40KA
- Power Fuse, 7.2KV with power fuse (3 each)
- Potential Transformers, 6.6KV/110V (3 each) and 440V/110V (2 each)
- Current Transformers, 150/75/5A (2 each); 750/5A (3 each); 600/5A (2 each);
- Zero-phase Sequence Current Transformer (3 ea.)
- Meters: Voltmeter, 0 - 4500/9000V/150V; Voltmeter, 300V; Voltmeter 600/150V Ammeter, 0 - 150/75/5A; Ammeter 750/5A; Ammeter 600/5A Watthour Meter
- Cable Heads, 6.6KV (3 each)
- Over Current Relay (2 ea.) (Type: MOC-2I-D, Mitsubishi)
- Over Current Ground Relay (2 each) (Type: LEG-142, Hikari)
- Molded Case Circuit Breaker; 400/400, 600/500, 225/225, 400/300, 400/400, 225/225
C-194 at Bldg. 194
J-1502000-03 Page 26
Part AC: Housing Facilities:
(Location: NAF Atsugi)
1. BLDG. 3069 (On G-Line):
Building No. Name Year Built System System Age
3069 Housing High-Rise
1996 Secondary Unit Substation (located in 1st floor electrical
SYSTEM EQUIPMENT INVENTORY: BLDG. # 3069 (G-Line)
Oil-Immersed Transformers:
- 300 KVA, 3-phase, 13.8/6.6kV/208-120V (2 ea.) (made in 2013)
Disconnect Switches (DS), Load Break Switches (LBS):
- DS, 24KV, 600A Non-fused (3 ea.)
- LBS, 15KV, 630A, 40kA(PF) (2 ea.)
Vacuum Circuit Breakers:
- 15KV, 600A, 20KA
Potential Transformers:
- 13.8KV/110V, 400VA (2 ea.)
- 13.8KV/110V, 100VA (2 ea.)
Current Transformers:
- 50/5A (3 ea.) (in 13.8kV Receiving Panel)
Meters (in 13.8kV Receiving Panel):
- Voltmeter, 20KV
- Ammeter, 50/5A
- Demand watt meter
- Watt Hour Meter
- Kilo Watt Meter
- Power Factor Meter
- Demand Controller (FM76W, Fuji Denki Co. Ltd)
Protective Relays:
- Over Current Relay (OCR), Type: ICO1D-AT2H (Toshiba) (3 ea.)
(in 13.8kV Receiving Panel)
Panels:
- Disconnect Switch Panel
- 13.8KV Receiving Panel
- 13.8KV Feeder Panel No. 1 and No. 2
- Lighting Feeder Panel
J-1502000-03 Page 27
- Security Power Feeder Panel
- Power Feeder Panel
- Grounding Terminal Box
Miscellaneous Equipment (Low Voltage Side):
- 1500/5A (3 ea.) (in Lighting Feeder Panel)
- 1000/5A (3 ea.) (in Power Feeder Panel)
- Volt Meters, 300V (2 ea.) (in Lighting Feeder Panel and in Power Feeder Panel)
- Demand Watt Meters, 1500/5A, 1000/5A (in Lighting Feeder Panel and in Power Feeder Panel)
- Watt Hour Meters, (2 ea.) (in Lighting Feeder Panel and in Power Feeder Panel)
- Thermal Over Current Relay (2 ea.)
(in Lighting Feeder Panel and in Power Feeder Panel)
- MCCBs
J-1502000-03 Page 28
2. BLDG. 3042 (On J-Line):
Building No. Name Year Built System System Age
3042 Housing High-Rise
1981 Secondary Unit Substation (located in 1st floor electrical
SYSTEM EQUIPMENT INVENTORY: BLDG. # 3042 (J-Line)
- 150 KVA, 13.8KV - 210/105V, 1-phase (2 ea.) (made in 1981)
- 250 KVA, 13.8KV – 210/105V, 1-phase (made in 2001)
- 5 KVA, 13.8KV - 210V, 1-phase (made in 1981) (Control Board) Note: Above transformers may or may not contain a slight amount of PCB in oil.
No analysis result has been made.
Transformers, Dry:
- 300 KVA, 13.8KV/6.6kV - 210V, 3-phase (made in 2013)
Fused Disconnects:
- 15KV, 5A, 600 MVA (2 ea.) (in Control Board)
- 15KV, 10A, 2000 MVA (3 ea.) (in Control Board)
- 15KV, 15A, 600MVA (6 ea.)
- 15KV, 30A, 600 MVA (3 ea.)
Vacuum Circuit Breaker (VCB):
- 15KV, 600A, 20KA (made in 2001) (in 13.8kV Receiving Board)
Potential Transformer:
- 13.8KV - 110V (2 ea.) (in 13.8kV Receiving Board)
Current Transformer:
- Current Transformer, 40 VA, 40/5A (3 each) (made in 2011) (in 13.8kV Receiving Board)
Meters (in 13.8kV Receiving Board):
- Multi-Meter with Transmitter (made in 2011):
Voltmeter, Ammeter, Watthour Meter, Watt Meter, Power Factor Meter, etc.
Protective Relays (in 13.8kV Receiving Board):
- Over Current Relay (OCR), Type: MR63M-01C-D (3 ea.) (Meidensha) (made in 2012)
- Under Voltage Relay (UVR), Type: MS63M-U1 (Meidensha) (made in 2012)
- Over Current Ground Relay (OCGR), Type: MR63M-01C-D (Meidensha)
- Capacitor Tripping Device
J-1502000-03 Page 29
Power Capacitors (SC) (in Control Board):
- 13.8KV, 50 KVA
Series Reactor (SR) (in Control Board):
- 13.8KV, 3 KVA
Panels:
- 13.8kV Receiving Board (with 2 ea. front doors)
- Control Board (right next to 13.8kV Receiving Board, with 2 ea. front doors)
- Lighting Boards (with 4 ea. front doors)
Miscellaneous Equipment (Lighting Boards):
- Voltmeter, 300V, 3 ea.
- Ammeter, 3 ea.
- Kilo-wattmeter, 300kW, 3 ea.
- Current Transformer, 750/5A, 6 ea.
- Transformer, 210/105V, 10KVA
- MCBs
Miscellaneous Equipment (Power Boards):
- Voltmeter, 300V, 1 ea.
- Ammeter, 1 ea.
- Kilo-wattmeter, 600kW, 1 ea.
- Current Transformer, 1200/5A, 2 ea.
- MCDT, 500V 3P 200A
- MCBs
J-1502000-03 Page 30
3. BLDG. 3043 (On J-Line):
Building No. Name Year Built System System Age
3043 Housing High-Rise
1981 Secondary Unit Substation (located in 1st floor electrical
SYSTEM EQUIPMENT INVENTORY: BLDG. # 3043 (J-Line)
- 150 KVA, 13.8KV - 210/105V, 1-phase (2 ea.) (made in 1981)
- 250 KVA, 13.8KV – 210/105V, 1-phase (made in 2001)
- 5 KVA, 13.8KV - 210V, 1-phase (made in 1981) (Control Board)
Transformers, Dry:
- 300 KVA, 13.8KV/6.6kV - 210V, 3-phase (made in 2013)
Fused Disconnects:
- 15KV, 5A, 600 MVA (2 ea.) (in Control Board)
- 15KV, 10A, 2000 MVA (3 ea.) (in Control Board)
- 15KV, 15A, 600MVA (6 ea.)
- 15KV, 30A, 600 MVA (3 ea.)
Vacuum Circuit Breaker (VCB):
- 15KV, 600A, 12.5KA (made in 2012) (in 13.8kV Receiving Board)
Potential Transformer:
- 13.8KV - 110V (2 ea.) (in 13.8kV Receiving Board)
Current Transformer:
- Current Transformer, 40 VA, 40/5A (3 each) (made in 2011) (in 13.8kV Receiving Board)
Meters (in 13.8kV Receiving Board):
- Multi-Meter with Transmitter (made in 2011):
Voltmeter, Ammeter, Watthour Meter, Watt Meter, Power Factor Meter, etc.
Protective Relays (in 13.8kV Receiving Board):
- Over Current Relay (OCR), Type: MR63M-01C-D (3 ea.) (Meidensha) (made in 2012)
- Under Voltage Relay (UVR), Type: MS63M-U1 (Meidensha) (made in 2012)
- Over Current Ground Relay (OCGR), Type: MR63M-01C-D (Meidensha) (made in 2012)
- Capacitor Tripping Device
Power Capacitors (SC) (in Control Board):
J-1502000-03 Page 31
- 13.8KV, 50 KVA
Series Reactor (SR) (in Control Board):
- 13.8KV, 3 KVA
Panels:
- 13.8kV Receiving Board (with 2 ea. front doors)
- Control Board (right next to 13.8kV Receiving Board, with 2 ea. front doors)
- Lighting Boards (with 4 ea. front doors)
Miscellaneous Equipment (Lighting Boards):
- Voltmeter, 300V, 3 ea.
- Ammeter, 3 ea.
- Kilo-wattmeter, 300kW, 3 ea.
- Current Transformer, 750/5A, 6 ea.
- Transformer, 210/105V, 10KVA
- MCBs
Miscellaneous Equipment (Power Boards):
- Voltmeter, 300V, 1 ea.
- Ammeter, 1 ea.
- Kilo-wattmeter, 600kW, 1 ea.
- Current Transformer, 1200/5A, 2 ea.
- MCDT, 500V 3P 200A
- MCBs
J-1502000-03 Page 32
4. BLDG. 3050 (On J-Line):
Building No. Name Year Built System System Age
3050 Housing High-Rise
1991 Secondary Unit Substation (located in 1st floor electrical room)
1 (System is supposed to be renewed in 2013~2014.)
NOTE:
This building will be under whole house revitalization. Under the revitalization work, substation system will be renewed in 2013 ~ 2014. Below list is provided based on the initial design concept of the revitalization work. The offeror should prepare proposal based on this list. After the revitalization is completed, and if there is any difference, amendment or modification may be issued.
SYSTEM EQUIPMENT INVENTORY: BLDG. # 3050 (J-Line)
- 300 KVA,…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .