BESS-Additional-SiteData-N3943020T2238 Amd 1.pdf
PDF 8 MB Posted
- Solicitation number
- N3943020T2238
View the file
Other files
| File | Type | Posted |
|---|---|---|
| N3943020T2238 BESS RFQ Amd 0003.pdf | ||
| Generator Specs-Attachment-2.xlsx | XLSX spreadsheet | |
| MDP Photos-Attachment-1.pdf | ||
| J-2_Financial_Inst_Bank_Information-Revised.docx | DOCX document | |
| N3943020T2238 BESS RFQ Amd 0002.pdf | ||
| N3943020T2238 BESS RFQ Amendment 0001.pdf | ||
| IMG_1804.pdf | ||
| N3943020T2236 BESS RFQ.pdf | ||
| IMG_1811.pdf | ||
| PH-372 BCO Ventura ESS Node Site.pdf | ||
| IMG_1812.pdf | ||
| 372B7Oct19MeterData.xlsx | XLSX spreadsheet | |
| J-2_Financial_Inst_Bank_Information.docx | DOCX document | |
| B372-Map.pdf | ||
| J-3_Pricing Sheet.xlsx | XLSX spreadsheet | |
| J-1_Non-Disclosure.docx | DOCX document |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BESS Project
• Incoming power supply
Primary transformer
Main service disconnect to Bldg. and Meter
Step down transformer to Bldg. (75KVA 208-480Y/277
"Approved for public release: distribution unlimited."
Transformer Data Plate that Feeds PH 372
Main service disconnect and Meter
Close up of Meter voltage supplying power to MDP Panel (Note: ATS and emergency generator is not connected to this panel)
Generator and ATS
"Approved for public release: distribution unlimited."
Generator Data Plate
125 Amp ATS
• This panel is connected to the
ATS
• There is no disconnect or main breaker (Main breaker is located upstream, 200 Amp service disconnect)
• Panel supplies power to two sub panels-NMCI panel that has two 20 amp Single pole breakers and a DC panel that has a 100 amp main breaker
• Service connections are supplied on power bus bar and connected to both sub panels
• Pictures attached for reference
• Grid power is supplied to ATS and is connected to panel. Panel supplies power to sub panels from main lugs
• Two Air Conditioning systems are powered from this panel Circuit breaker 1,3,5- 3 pole 30amp Circuit breaker 7,9,11- 3 pole 40 amp
• MDP panel has a 200 Amp service breaker that supplies power to this panel (200 amp panel is upstream)
Incoming power (Grid) supplied from ATS and connected to two sub panels
• Direct Current 100Amp panel, (services UPS system)
DC Service panel
100Amp DC Panel
Sub Panel Qty 2-2 pole 20 amp sub panel (supplies power to computer systems)
Direct Current UPS System
UPS Battery’s
• Older wall mounted AC unit 3 pole 40 amp breaker.
Data Plate for Pad mounted Air Conditioning -208v 3 pole 30 amp breaker
"Approved for public release:
distribution unlimited."
NMCI 2
pole 20 A
Communication panel backed up from Generator
DC panel to UPS system125A ATSG
Main Dist. MDP 200Amp
208/120v 3PH 4W
XFMR to
BLDG
208/120v
3PH 4W
Meters
POLE
Connection Diagram
Disclaimer: Accuracy of Information is not guaranteed. Contractors shall verify the accuracy.
| BESS Project |
| Slide Number 2 |
| Slide Number 3 |
| Slide Number 4 |
| Slide Number 5 |
| Generator Data Plate |
| 125 Amp ATS |
| Slide Number 8 |
| Slide Number 9 |
| Slide Number 10 |
| Slide Number 11 |
| Slide Number 12 |
| Direct Current UPS System |
| UPS Battery’s |
| Slide Number 15 |
| Slide Number 16 |
| Slide Number 17 |
File details come from the government source that posted it. Updated .