23R4 013316.00 HANSCOM B1994 Updated DWG Submission_9MAY23.pdf
PDF 7 MB Posted
- Solicitation number
- MXRD170051-RFP
About this file
This document is a comprehensive set of architectural and engineering design drawings for the HVAC replacement project at the Child Development Center (Building 1994) at Hanscom Air Force Base. The project involves replacing the existing HVAC systems, including multiple air conditioning units (AC-1, AC-2, AC-3), an air handling unit (AHU-1), exhaust fans (EF-1, EF-2), and associated ductwork and controls. The design specifications include detailed mechanical, electrical, and structural plans for installing new HVAC equipment with specific requirements such as concrete equipment pads, security fencing, duct routing, and integration with the existing building control systems. The drawings outline precise installation details, equipment specifications, and sequence of operations, with a focus on maintaining building functionality during the renovation and ensuring proper system performance, including occupancy mode controls, temperature management, and safety protocols.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REGIONAL MAP SITE MAP
PROJECT LOCATION
HANSCOM AIR
FORCE BASE
SHEET ID
D
EP
A R
TM
EN
T O
F
TH
E A
IR
F
O R
C E
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
TE
U.S. AIR FORCE
M A
R K
D
ES
C R
IP
TI
O N
HANSCOM AIR FORCE BASE
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H
AN
SC
O
M A
IR
F
O R
C E
BA
SE
M
AS
SA
C
H U
SE
TT
S
M
AR
O N
C O
N
TR
U
SC
TI
O
N C
O
IN
C
BU
TT
O
N H
O
LE
D R
IV
E
PR
O
VI
D
EN
C
E, R
I 0
MARON CONSTRUCTION CO., INC.
180 BUTTONHOLE DRIVE
PROVIDENCE, RI 02909
BB
IX
, L
LC
SO
U
TH
S
TR
EE
T
BO
ST
O
N , M
A
UPDATED SUBMISSION
APRIL 20, 2023
G-000
C O
VE
R
S H
EE
T
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H A
N
SC
O M
A
IR
F O
R C
E B
A
SE
VC
S
AS
4/
/2
100% SUBMISSION
R
EP
LA
C
E H
VA
C
, C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R
PR
O
JE
C T
N U
M B
ER
: M
XR
D
6-
CHILD DEVELOPMENT CENTER, B1994
HANSCOM AIR FORCE BASE
REPLACE HVAC, CHILD DEVELOPMENT CENTER
PROJECT NUMBER: MXRD 16-0009
SHEET LIST
SHEET NUMBER SHEET NAME
G-000 COVER SHEET
G-001 GENERAL NOTES
D-101 DEMOLITION KEY PLAN
D-102 DEMOLITION PLANS
D-103 DEMOLITION PHOTOS
M-001 MECHANICAL ABBREVIATIONS, NOTES, AND SYMBOLS
M-101 NEW MECHANICAL PLANS
M-401 CONTROL SCHEMATICS
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
E-101 ELECTRICAL PLANS
E-600 ELECTRICAL PANELBOARD SCHEDULE
D-104 NEW HVAC DEMO PLAN EAST
A-101 INFILL AT OPENING OF DUCTWORK ELEV. & DETAILS
M-102 NEW HVAC TAB PLAN WEST
M-103 M-104
NEW HVAC TAB PLAN CENTER
NEW HVAC TAB PLAN EAST
LE
AD
P R
O
FE
SS
IO
N
AL
S-101 STRUCTURAL DETAILS
M-402 NETWORK ARCHITECTURE SCHEMATIC
HANSCOM AIR
FORCE BASE
SHEET ID
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H
AN
SC
O
M A
IR
F
O R
C E
BA
SE
M
AS
SA
C
H U
SE
TT
S
M
AR
O N
C O
N
ST
R U
C
TI
O N
C O
IN
C
BU
TT
O N
H O
LE
D
R
IV
E
PR
O
VI
D
EN
C E, R I 0
N
LE
AD
P R
O
FE
SI
O
N
AL
BB
IX
, L
LC
SO
U
TH
S
TR
EE
T
BO
ST
O
N , M
A
G-001
G
EN
ER
AL
N O
TE
S
CH
IL
D
DE
VE
LO
PM
EN
T
CE
NT
ER
, B
HA
NS
CO
M A
IR
F
O
RC
E
BA
SE
VC
S
AS
/2
1/
100% SUBMISSION
RE
PL
AC
E
HV
AC
, C
HI
LD
D
EV
EL
O
PM
EN
T
CE
NT
ER
PR
O
JE
CT
N
UM
BE
R:
M
XR
D
-0
GENERAL DEMOLITION NOTES:
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ADHERE TO THE FOLLOWING:
1. ERECT AND MAINTAIN TEMPORARY STAGING, LIGHTS, BARRICADES, WARNING SIGNS, AND GUARDS NECESSARY TO PROTECT ADJACENT TENANTS FROM INJURY, AND/OR DAMAGE, ALL IN ACCORDANCE WITH APPLICABLE RULES AND REGULATIONS.
2. DO NOT CLOSE OR OBSTRUCT THE PATH OF EGRESS, CORRIDORS, OR OTHER OCCUPIED OR USED SPACES OR FACILITIES WITHOUT THE WRITTEN PERMISSION OF THE OWNER AND THE AUTHORITIES HAVING JURISDICTION. DO NOT INTERRUPT UTILITIES WITHOUT THE WRITTEN PERMISSION OF THE AUTHORITIES HAVING JURISDICTION. IF NECESSARY PROVIDE TEMPORARY UTILITIES. PRIOR TO OBSTRUCTION OF EGRESS PATHS OR IMPAIRMENT OF FIRE/LIFE SAFETY COMPONENTS.
3. CEASE OPERATION IF PUBLIC SAFETY OR REMAINING STRUCTURES ARE ENDANGERED. PERFORM TEMPORARY CORRECTIVE
MEASURES UNTIL OPERATIONS CAN BE CONTINUED PROPERLY.
4. THE CONTRACTOR WILL VISIT THE SITE AND VERIFY THE EXTENT AND LOCATION OF SELECTIVE DEMOLITION REQUIRED PRIOR TO STARTING THE WORK AT NO ADDITIONAL COST TO THE OWNER. CAREFULLY IDENTIFY THE LIMITS OF SELECTIVE DEMOLITION. MARK INTERFACE SURFACES AS REQUIRED TO ENABLE THE WORKMEN TO IDENTIFY THE ITEMS TO BE REMOVED
AND STORED, AS WELL AS THE ITEMS TO BE LEFT IN PLACE INTACT.
5. USE MEANS NECESSARY TO PREVENT DUST FROM BECOMING A NUISANCE TO THE PUBLIC, NEIGHBORING BUILDINGS, AND TO
ANY OTHER WORK BEING PERFORMED.
6. EXECUTE DEMOLITION WORK TO ENSURE THE SAFETY OF PERSONS AND ADJACENT PROPERTY AGAINST DAMAGE.
7. IN THE EVENT OF DEMOLITION OF ITEMS NOT SO SCHEDULED TO BE DEMOLISHED, PROMPTLY REPLACE SUCH ITEMS TO THE APPROVAL OF THE CONTRACTING OFFICER AT NO ADDITIONAL COST TO THE OWNER. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO REPAIR ANY DAMAGE DONE TO EXISTING FEATURES AS A RESULT OF THIS WORK. DAMAGED ITEMS SHALL
BE REPLACED IN KIND AND AT NO ADDITIONAL COST TO THE OWNER.
8. SHORE, BRACE AND SUPPORT EXISTING CONDITIONS AS REQUIRED PRIOR TO REMOVAL OF EXISTING CONSTRUCTION OR
INSTALLATION OF THE NEW WORK.
9. COORDINATE THE REMOVAL, RELOCATION, REPLACEMENT, RE-USE, SHUT-OFF, STUB-OFF, CAPPING-OFF OR UPGRADING OF ALL EXISTING PLUMBING, HVAC, SECURITY, FIRE ALARM, ELECTRICAL SYSTEMS, AND TELECOM SYSTEMS EQUIPMENT, AND APPURTENANCES - INCLUDING, BUT NOT LIMITED TO , UTILITY LINES, DUCTS, CONNECTIONS, PANELS, VENTS, FANS, ELECTRICAL BASEBOARD HEAT, PIPING , DEVICES, CONTROLS, SWITCHES, OUTLETS, AND CONDUIT DURING THE PHASED CONSTRUCTION AS REQUIRED, AS SCHEDULED OR AS SPECIFIED IN ACCORDANCE WITH ALL LOCAL, MUNICIPAL, STATE AND
FEDERAL CODES.
10. THE CONTRACTOR SHALL REMOVE AND LEGALLY DISPOSE OF ANY HAZARDOUS MATERIALS AND IN DOING SO SHALL COMPLY WITH ALL APPLICABLE OSHA REGULATIONS AND ALL OTHER FEDERAL, STATE AND LOCAL GUIDELINES REGARDING ASBESTOS-
CONTAINING MATERIAL REMOVAL AND DISPOSAL.
11. OWNER AND ARCHITECT/ENGINEER SHALL NOT BE HELD RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES FOR SAFETY PRECAUTIONS OR FOR THE CONTRACTORS FAILURE TO CARRY OUT THE WORK IN STRICT ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS. OWNER AND ARCHITECT/ENGINEER SHALL NOT BE RESPONSIBLE FOR ERRORS OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTORS OR THEIR AGENTS OR EMPLOYEES OR
ANY OTHER PERSONS PERFORMING ANY OF THE WORK.
12. THE CONTRACTOR SHALL COORDINATE ALL ABOVE CEILING MEP AND STRUCTURAL ELEMENTS PRIOR TO DEMOLITION OF WALLS AND/OR CEILING. CONTRACTOR IS ULTIMATELY RESPONSIBLE FOR FIRE SAFETY DURING PROJECT BEING IN
COMPLIANCE WITH IBC, IFC AND NFPA 241.
13. COORDINATE, TERMINATE, RELOCATE ALL ASSOCIATED WALL & CEILING ELECTRICAL (TELECOM/POWER OUTLETS, SWITCHING, THERMOSTAT, ETC.) DEVICES THAT ARE LOCATED ON OR IN WALLS & CEILINGS SCHEDULED FOR REMOVAL, GC
TO V.I.F PRIOR TO THE COMMENCEMENT OF WORK.
14. REMOVE ALL EXISTING FLOORING TO FACE OF EXISTING CONCRETE SLAB. ABATE SPECIAL WASTE MATERIALS (I.E. VINYL TILE) AND TURN OVER TO BASE ENVIRONMENTAL IN ACCORDANCE WITH SECTION 01560. DISPOSE OF ALL OTHER MATERIALS SET FOR DEMOLITION. WHERE EXISTING CERAMIC TILE IS LOCATED UNDER VINYL TILE AND NEW VINYL TILE IS TO BE INSTALLED, THE EXISTING CERAMIC TILE IS NOT REQUIRED TO BE REMOVED, ONLY VINYL TILE ABOVE IT.
15. FLOORS SHALL BE LEVEL AND PATCHED AS REQUIRED TO MEET THE MANUFACTURER'S REQUIREMENTS OF THE NEW
MATERIALS AS SPECIFIED.
16. REMOVE AND DISPOSE OF ALL WALLS SHOWN TO BE REMOVED, EXISTING EXTERIOR WOOD STUD WALLS, FURRING AREAS AND WALL TILE MATERIALS AND MATERIALS DAMAGED FROM THEIR REMOVAL. ABATE MASONRY PAINTED WALLS CONTAINING
LEAD BASED PAINT, REFER TO ASBESTOS CONTAINING MATERIAL NOTES.
17. PATCH ALL EXISTING WALLS ADJACENT TO ALL WALLS SCHEDULED FOR REMOVAL. PATCHWORK WILL BE CONSISTENT WITH THE WALL RATING. ANY STRUCTURAL STEEL DAMAGED OR MISSING SFRM SHALL BE REPLACED AFTER COMPLETION OF
APPROPRIATE SURFACE PREPARATION WORK AND ITS INSPECTION BY FPE.
18. REMOVE AND DISPOSE OF ALL DOORS INDICATED ON DEMOLITION PLAN. ALL OTHER DOORS SHALL HAVE HARDWARE
REMOVED AND DISPOSED OF. TAKE CARE NOT TO DAMAGE DOORS AS THEY WILL BE REUSED.
19. PROVIDE TERMITE TREATMENT IN COMPLIANCE WITH HANSCOM BFS, EPA REQUIREMENTS AND UFGS 31 31 16.13. TREATMENT SHALL CARRY A 5 YEAR WRITTEN WARRANTY COVERING RETREATMENT OF SITE AS REQUIRED TO ELIMINATE INFESTATION
AND REPAIR OF DAMAGE.
20. SUBMIT DEMOLITION SCHEDULE FOR APPROVAL INCLUDING SCHEDULE AND METHODS OF CAPPING AND CONTINUING UTILITY
SERVICE.
21. THE CONTRACTOR SHALL COMPLY WITH NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS AND 29 CFR 1910.34, COVERAGE AND DEFINITIONS, 29 CFR 1910-35, COMPLIANCE WITH NFPA 101-2009, LIFE SAFETY CODE, 2014,.29 CFR 1910-36, DESIGN AND CONSTRUCTION REQUIREMENTS FOR EXIT ROUTES, 29 CFR
1910-37, MAINTENANCE, SAFEGUARDS, AND OPERATIONAL FEATURES FOR EXIT ROUTES.
DUST CONTROL PROVISIONS:
1. THE GC SHALL PROVIDE A CONTAINMENT STRUCTURE AT ALL ENTRY AND EGRESS PATHS IN AND OUT OF THE LIMIT OF WORK AREA. REPLACE AS OFTEN AS NEEDED TO ENSURE AGAINST MIGRATION OF DUST AND CONSTRUCTION DEBRIS OUTSIDE OF THE WORK AREA. THE CONTRACTOR SHALL COMPLY WITH THE MARKING OF EGRESS IN
ACCORDANCE WITH THE CODE REQUIREMENT THROUGHOUT THE DEMOLITION.
2. THE GC SHALL PROVIDE STEP-OFF PADS (TACK MATS) AT ALL ENTRY AND EGRESS PATHS IN AND OUT OF THE LIMIT OF WORK AREA. THE GC SHALL REPLACE THE DUST BARRIER AS OFTEN AS NEEDED, TO ENSURE AGAINST
MIGRATION OF DUST AND CONSTRUCTION DEBRIS OUTSIDE OF THE WORK AREA.
3. THE GC SHALL PROVIDE DAILY REMOVAL OF ALL DEMOLITION DEBRIS. DO NOT STORE ANY DEMOLITION DEBRIS
ON THE FLOOR OVERNIGHT.
4. THE GC SHALL MAINTAIN A CLEAN AND SAFE WORK AREA THROUGHOUT THE PERIOD OF DEMOLITION. THE GC SHALL, AT THE END OF EACH WORK DAY, REMOVE ALL DEMOLITION DEBRIS AND HAZARDOUS AND POTENTIALLY
DANGEROUS MATERIALS USED IN THE WORK.
5. THE GC SHALL COLLECT CONSTRUCTION MATERIAL AND DEBRIS FREQUENTLY AND DISPOSE OF OR RECYCLE
DEBRIS AND REFUSE AWAY FROM THE CENTER IN A LAWFUL MANNER.
6. THE GC SHALL CLEAN THE EXTERIOR PUBLIC AREAS IMPACTED BY CONSTRUCTION DUST, DIRT AND DEBRIS ON A DAILY BASIS. THE GC SHALL BE RESPONSIBLE FOR ALL FEES, PERMITS, ETC., REQUIRED FOR WASTE DISPOSAL.
7. THE GC SHALL PROVIDE MEANS TO KEEP DUST AND HAZARDOUS MATERIALS FROM ENTERING ALL HVAC AIR SYSTEMS. ANY FILTRATION SHALL BE CHANGED AS RECOMMENDED BY THE FILTERING SYSTEM MANUFACTURER.
GENERAL NOTES:
1. THESE DRAWINGS REPRESENT THE EXISTING CONDITIONS AT THE PRESENT TIME, TO THE BEST OF OUR KNOWLEDGE, GIVEN THE LIMITS OF VISIBLE CONDITIONS, WITHOUT THE BENEFIT OF SUBSTANTIAL INVESTIGATIVE
DEMOLITION OR REMOVALS.
2. ALL DIMENSIONS SHALL BE VERIFIED BY THE GENERAL CONTRACTOR BEFORE INSTALLATION OF THE WORK INVOLVED. ANY DISCREPANCIES SHOULD BE BROUGHT TO THE ATTENTION OF THE PROJECT MANAGER BEFORE
PROCEEDING.
3. CONTRACTOR TO VERIFY ALL DIMENSIONS AND CLEARANCES OF BUILDING ELEMENT PRIOR TO FABRICATION OR INSTALLATION. ANY DISCREPANCIES SHOULD BE BROUGHT TO THE ATTENTION OF THE ARCHITECT BEFORE
PROCEEDING.
4. WHERE WORK-IN-PLACE IS REJECTED OR OTHERWISE FOUND TO BE INCOMPLETE, INCONSISTENT WITH THE CONTRACT DOCUMENTS, OR OTHERWISE DEFICIENT, IT SHALL BE THE CONTRACTOR'S OPTION TO REMOVE THE REJECTED ELEMENT AND PROVIDE A COMPLETELY NEW ELEMENT, RATHER THAN ATTEMPT A REPAIR.
5. ALL DEFICIENT ELEMENTS THAT ARE REPAIRED SHALL MEET THE REQUIREMENTS OF THE CONTRACT DOCUMENTS COMPLETELY, AND THE CONTRACTOR SHALL WARRANTEE THAT REPAIRED WORK TO THE
SATISFACTION OF THE OWNER.
6. CONSTRUCTION LIMIT LINES SHALL BE AS INDICATED ON THE DRAWINGS, HOWEVER, IN ORDER TO COMPLETE INDICATED WORK, THE CONTRACTOR MAY BE REQUIRED TO CARRY OUT WORK ADJACENT TO, BUT OUTSIDE INDICATED LIMITS. ALL BUILDING AND SITE ELEMENTS DAMAGED OR DISTURBED BY SUCH WORK SHALL BE
RESTORED BY THE CONTRACTOR TO ORIGINAL CONDITION AT HIS COST.
7. WORK UNDER THIS CONTRACT IS TO INCLUDE THE RELOCATION OR REPAIR OF EXISTING WATER SERVICE TO THE CONNECTION LOCATIONS SHOWN ON THE DRAWINGS. NO ADDITIONAL COSTS WILL BE CONSIDERED FOR EXTENDING UTILITIES TO MAKE A COMPLETE AND FUNCTIONING CODE COMPLIANT UTILITY SERVICE.
8. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE REQUIREMENTS OF THE HANSCOM AFB FACILITY STANDARDS (BFS) UNIFIED FACILITY GUIDE SPECIFICATIONS (UFGS) UNIFIED FACILITY CRITERIA (UFC) ENGINEERING TECHNICAL LETTERS (ETL) AND ALL APPLICABLE BUILDING AND HANDICAP ACCESSIBILITY CODES.
9. ALL EXIT AND ESCAPE FACILITIES SHALL BE CONTINUOUSLY MAINTAINED AT ALL TIMES DURING CONSTRUCTION.
IN THE EVENT ANY REQUIRED EXIT MUST BE TEMPORARILY CLOSED, COORDINATE WITH BUILDING OWNERS AND
PROVIDE OTHER MEASURES AND OR MEANS WHICH WILL PROVIDE EQUIVALENT SAFETY.
22' - 0"
8'
0"
13' - 7"
CONCRETE UTILITY PAD
CONCRETE UTILITY PAD
7'
8"
12' - 9"
1/ 2"
22' - 0 1/2"
5' - 5 3/4"
/2
19' - 1 1/2"
7' - 9"
"CONCRETE
UTILITY PAD
7' - 9"
15' - 7"
CONCRETE
UTILITY PAD
HANSCOM AIR
FORCE BASE
SHEET ID
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H
AN
SC
O
M A
IR
F
O R
C E
BA
SE
M
AS
SA
C
H U
SE
TT
S
M
AR
O N
C O
N
ST
R U
C
TI
O N
C O
IN
C
BU
TT
O N
H O
LE
D
R
IV
E
PR
O
VI
D
EN
C E, R I 0
N
LE
AD
P R
O
FE
SI
O
N
AL
BB
IX
, L
LC
SO
U
TH
S
TR
EE
T
BO
ST
O
N , M
A
D-102
D
EM
O
LI
TI
O
N P
LA
N
S
CH
IL
D
DE
VE
LO
PM
EN
T
CE
NT
ER
, B
HA
NS
CO
M A
IR
F
O
RC
E
BA
SE
VC
S
AS
/2
1/
100% SUBMISSION
RE
PL
AC
E
HV
AC
, C
HI
LD
D
EV
EL
O
PM
EN
T
CE
NT
ER
PR
O
JE
CT
N
UM
BE
R:
M
XR
D
-0
1/4" = 1'-0"1 AC-1 ENCLOSURE
1/4" = 1'-0"2 AC-2 ENCLOSURE
1/4" = 1'-0"3 AC-3 ENCLOSURE
1/4" = 1'-0"4 AC-4 ENCLOSURE
DEMOLITION GENERAL NOTES:
1. THE CDC FACILITY AND ALL ADJACENT SPACES TO THE LIMIT OF WORK NEEDS TO REMAIN OPERATIONAL AT ALL TIMES DURING THE DEMOLITION AND CONSTRUCTION ACTIVITIES. ISOLATE THE SUPPLY AND RETURN AIR DUCTWORK TO ENSURE THAT NO AIR IS TRANSFERRED IN/OUT OF THE LIMIT OF WORK AREA. PROVIDE TEMPORARY VENTILATION IF REQUIRED.
2. THE SCOPE OF THE DEMOLITION INCLUDES THE REMOVAL OF WINDOW AC UNITS AS WELL AS DEMOLITION OF AC-1, AC-2, AC-3, AC-4, AND AHU-1. THE REMOVAL AND SALVAGE OF THE WINDOW UNITS IS SHOWN SCHEMATICALLY AND IS NOT INTENDED TO IDENTIFY THE
INDIVIDUAL WINDOW AC UNITS.
3. BEFORE BEGINNING ANY DEMOLITION WORK, THE CONTRACTOR SHALL SURVEY THE SITE AND EXAMINE THE DRAWINGS AND SPECIFICATIONS TO DETERMINE THE EXTENT OF THE WORK. ALL DEMOLITION WORK SHALL BE PERFORMED WITH "DUE CARE AND DILIGENCE" SO AS TO PREVENT THE UNNECESSARY DESTRUCTION AND OR DAMAGE TO SYSTEMS THAT SHALL REMAIN IN OPERATION AT THE CONCLUSION OF THIS WORK. DETERMINE THE EXACT LOCATIONS OF ALL EXISTING EQUIPMENT, DEVICES AND WIRING BEFORE
COMMENCING WORK.
4. LOCATE AND PRESERVE ALL PORTIONS OF THE EXISTING HVAC SYSTEMS WHICH SHALL REMAIN.
5. NOT ALL CONTROL DEVICES AND WIRING ARE INDICATED ON THE MECHANICAL DEMOLITION DRAWINGS. REMOVAL SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR. COORDINATE WITH ENGINEER PRIOR TO START OF DEMOLITION.
6. THE MECHANICAL CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING HVAC DEVICES, EQUIPMENT AND WIRING PRIOR TO COMMENCING ANY WORK. THE MECHANICAL CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR ANY AND ALL DAMAGES THAT MIGHT OCCUR BECAUSE OF THE CONTRACTOR'S FAILURE TO ACCURATELY DISCOVER, LOCATE AND PROTECT ANY AND ALL
PORTIONS OF THE EXISTING HVAC SYSTEM.
7. WHERE THE EXISTING MECHANICAL EQUIPMENT AND DEVICES SHALL BE REMOVED, THE MECHANICAL CONTRACTOR SHALL REMOVE ALL ASSOCIATED DUCTWORK, PIPING AND CONTROLS THAT SHALL NOT REMAIN IN OPERATION BACK TO THEIR RESPECTIVE SOURCE
OR TO THE POINT ON A SHARED SYSTEM FROM WHERE THE EQUIPMENT OR DEVICE IS SERVED.
8. BEFORE COMMENCING WITH WORK ENSURE ALL ELECTRICAL POWER IS TURNED OFF TO THE EXISTING EQUIPMENT. COORDINATE WITH THE ELECTRICAL CONTRACTOR TO ENSURE WORKING POWER HAS BEEN EITHER TERMINATED OR TURNED OFF AT THE PANEL
AND LOCKED OUT AND TAGGED.
9. THE MECHANICAL CONTRACTOR SHALL COMPLETELY REMOVE ALL ITEMS INDICATED AND SHALL BE RESPONSIBLE FOR DISPOSAL PER LOCAL, STATE AND FEDERAL REGULATIONS AND PAY FOR ALL ASSOCIATED COSTS OF DISPOSAL.
10. IF REQUIRED, RELOCATE AS NECESSARY ALL EXISTING DUCTWORK, PIPING AND CONTROLS FOUND PASSING THROUGH THE AREA OF CONSTRUCTION, AND WHICH ARE PRESENTLY IN USE IN OTHER PORTIONS OF THE BUILDING UNAFFECTED BY THIS PROJECT PHASE, TO MAINTAIN THE CONTINUITY OF SERVICE.
11. ALL DUCTWORK, GRILLES AND DEVICES WITHIN THE AREA OF CONSTRUCTION WHICH ARE NOT INDICATED TO BE REUSED OR TURNED
OVER TO THE OWNER SHALL BE DISPOSED OF BY THE CONTRACTOR.
12. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL CUTTING AND PATCHING NECESSARY TO REPAIR ANY DAMAGE CAUSED BY CONSTRUCTION ACTIVITIES UNDER HIS/HER CONTRACT. THIS WORK INCLUDES AREAS OUTSIDE ANY LIMITS OF CONSTRUCTION LINES
INDICATED ON THE DRAWINGS.
13. RUBBISH AND DEBRIS SHALL BE REMOVED FROM THE WORK AREAS DAILY, UNLESS OTHERWISE DIRECTED, TO AVOID ACCUMULATION AT THE DEMOLITION SITE. MATERIALS THAT CANNOT BE REMOVED DAILY SHALL BE STORED IN AREAS SPECIFIED.
14. THE EXISTING UNITS’ REFRIGERANT IS R-22. THIS REFRIGERANT SHALL BE CAPTURED AND LEGALLY DISPOSED IN ACCORDANCE WITH
THE FEDERAL AND STATE REGULATIONS.
DEMOLITION KEYED NOTES:
DEMOLISH AND REMOVE AC UNIT INCLUDING ALL APPURTENANCES, SUPPORTS, ELECTRICAL AND MECHANICAL CONNECTIONS, ETC.
DEMOLISH AND REMOVE THE SUPPLY AND RETURN AIR CONNECTION TO THE BUILDING. DEMOLISH THE OUTSIDE AIR DUCT CONNECTION. DEMOLITION SHALL INCLUDE ALL INSULATION, DAMPERS, FRAMES, FLANGES, FLEX CONNECTIONS, ETC. ENSURE THE
AREA IS CLEAR FOR THE INSTALLATION OF THE NEW AC UNIT.
DEMOLISH AND REMOVE THE EXISTING CONCRETE PAD. DEMOLITION SHALL INCLUDE ALL FOOTINGS, BASE, UNDERLAYMENTS, ETC.
CLEAR ALL DEBRIS AND PREPARE AREA TO RECEIVE NEW CONCRETE PAD.
DEMOLISH AND REMOVE THE ORNAMENTAL BRICK ENCLOSURE AND DOOR. DEMOLITION SHALL INCLUDE FOUNDATIONS, FOOTINGS, AND REINFORCEMENTS. EXERCISE CAUTION NOT TO DAMAGE EXISTING EXTERIOR BUILDING BRICK WALL. PREPARE AREA TO RECEIVE
NEW FENCING.
DEMOLISH AND REMOVE AC-4 FENCING AND PAD. PATCH PAVEMENT WHERE REQUIRED.
DEMOLISH AND REMOVE ALL WINDOW AC UNITS, FRAMES, SUPPORTS, AND ALL OTHER APPURTENANCES. THE DEMOLITION OF THE WINDOW UNITS IS SHOWN SCHEMATICALLY AND IS NOT INTENDED TO IDENTIFY THE INDIVIDUAL WINDOW AC UNITS.
PHASING PLAN:
1. AC UNITS SHALL BE DEMOLISHED AND REMOVED ONE AT A TIME. THE INTENT IS TO USE THE EXISTING WINDOW AC UNITS AS TEMPORARY COOLING FOR THE SPACES BEING AFFECTED. THE CONSTRUCTION PHASING PLAN SHALL SHOW THE SEQUENCE OF
DEMOLITION.
2. PRIOR TO DEMOLITION OF THE AC UNITS, PROVIDE 72 HOURS WRITTEN NOTIFICATION TO THE OWNER FOR ALL SHUTDOWN ACTIVITIES.
3. ONCE AN AC UNIT HAS BEEN REPLACED WITH THE NEW UNIT, PERFORM STARTUP AND TESTING OF THE NEW UNIT TO PROVIDE COOLING TO THE BUILDING. THIS STARTUP AND TESTING IS NOT A SUBSTITUTION FOR THE SYSTEM COMMISSIONING.
4. ONCE ALL NEW AC UNITS HAVE BEEN INSTALLED, PERFORM THE REQUIRED SYSTEM WIDE COMMISSIONING FOR THE BUILDING HVAC.
5. CONTRACTOR SHALL PROVIDE A CONSTRUCTION SCHEDULE AND CONSTRUCTION PHASING PLAN FOR GOVERNMENT APPROVAL PER THE BASIC MACC CONTRACT PRIOR TO COMMENCING WORK. SERVICE TO MORE THAN ONE ZONE SHALL NOT BE REMOVED FROM ACTIVE SERVICE SIMULTANEOUSLY DURING PHASED CONSTRUCTION. HVAC SERVICES SHALL NOT BE INTERRUPTED WITHOUT PRIOR APPROVAL OF GOVERNMENT AND TEMPORARY SERVICES SHALL BE PROVIDED FOR OUTAGES DURING WORKING HOURS AND LONGER
THAN 8 HOURS.
2 5
HANSCOM AIR
FORCE BASE
SHEET ID
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H
AN
SC
O
M A
IR
F
O R
C E
BA
SE
M
AS
SA
C
H U
SE
TT
S
M
AR
O N
C O
N
ST
R U
C
TI
O N
C O
IN
C
BU
TT
O N
H O
LE
D
R
IV
E
PR
O
VI
D
EN
C E, R I 0
N
LE
AD
P R
O
FE
SI
O
N
AL
BB
IX
, L
LC
SO
U
TH
S
TR
EE
T
BO
ST
O
N , M
A
D-103
D
EM
O
LI
TI
O
N P
H O
TO
S
CH
IL
D
DE
VE
LO
PM
EN
T
CE
NT
ER
, B
HA
NS
CO
M A
IR
F
O
RC
E
BA
SE
VC
S
AS
/2
100% SUBMISSION
RE
PL
AC
E
HV
AC
, C
HI
LD
D
EV
EL
O
PM
EN
T
CE
NT
ER
PR
O
JE
CT
N
UM
BE
R:
M
XR
D
-0
N.T.S.1 DEMOLITION PHOTOS
DEMOLITION GENERAL NOTES:
1. THE CDC FACILITY AND ALL ADJACENT SPACES TO THE LIMIT OF WORK NEEDS TO REMAIN
OPERATIONAL AT ALL TIMES DURING THE DEMOLITION AND CONSTRUCTION ACTIVITIES.
ISOLATE THE SUPPLY AND RETURN AIR DUCTWORK TO ENSURE THAT NO AIR IS
TRANSFERRED IN/OUT OF THE LIMIT OF WORK AREA. PROVIDE TEMPORARY VENTILATION
IF REQUIRED.
2. THE SCOPE OF THE DEMOLITION INCLUDES THE REMOVAL OF WINDOW AC UNITS AS WELL
AS DEMOLITION OF AC-1, AC-2, AC-3, AC-4, AND AHU-1. THE DEMOLITION OF THE WINDOW
UNITS IS SHOWN SCHEMATICALLY AND IS NOT INTENDED TO IDENTIFY THE INDIVIDUAL
WINDOW AC UNITS.
3. BEFORE BEGINNING ANY DEMOLITION WORK, THE CONTRACTOR SHALL SURVEY THE SITE
AND EXAMINE THE DRAWINGS AND SPECIFICATIONS TO DETERMINE THE EXTENT OF THE
WORK. THE CEILING SPACE IN THE LIMIT OF WORK IS HIGHLY CONGESTED. ALL
DEMOLITION WORK SHALL BE PERFORMED WITH "DUE CARE AND DILIGENCE" SO AS TO
PREVENT THE UNNECESSARY DESTRUCTION AND OR DAMAGE TO SYSTEMS THAT SHALL
REMAIN IN OPERATION AT THE CONCLUSION OF THIS WORK. DETERMINE THE EXACT
LOCATIONS OF ALL EXISTING EQUIPMENT, DEVICES AND WIRING BEFORE COMMENCING
WORK.
4. LOCATE AND PRESERVE ALL PORTIONS OF THE EXISTING HVAC SYSTEMS WHICH SHALL
REMAIN.
5. NOT ALL CONTROL DEVICES AND WIRING ARE INDICATED ON THE MECHANICAL
DEMOLITION DRAWINGS. REMOVAL SHALL BE THE RESPONSIBILITY OF THE MECHANICAL
CONTRACTOR. COORDINATE WITH ENGINEER PRIOR TO START OF DEMOLITION.
6. THE MECHANICAL CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL
EXISTING HVAC DEVICES, EQUIPMENT AND WIRING PRIOR TO COMMENCING ANY WORK.
THE MECHANICAL CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR ANY AND ALL
DAMAGES THAT MIGHT OCCUR BECAUSE OF THE CONTRACTOR'S FAILURE TO
ACCURATELY DISCOVER, LOCATE AND PROTECT ANY AND ALL PORTIONS OF THE EXISTING
HVAC SYSTEM.
7. WHERE THE EXISTING MECHANICAL EQUIPMENT AND DEVICES SHALL BE REMOVED, THE
MECHANICAL CONTRACTOR SHALL REMOVE ALL ASSOCIATED DUCTWORK, PIPING AND
CONTROLS THAT SHALL NOT REMAIN IN OPERATION BACK TO THEIR RESPECTIVE SOURCE
OR TO THE POINT ON A SHARED SYSTEM FROM WHERE THE EQUIPMENT OR DEVICE IS
SERVED.
8. BEFORE COMMENCING WITH WORK ENSURE ALL ELECTRICAL POWER IS TURNED OFF TO
THE EXISTING EQUIPMENT. COORDINATE WITH THE ELECTRICAL CONTRACTOR TO ENSURE
WORKING POWER HAS BEEN EITHER TERMINATED OR TURNED OFF AT THE PANEL AND
LOCKED OUT AND TAGGED.
9. THE MECHANICAL CONTRACTOR SHALL COMPLETELY REMOVE ALL ITEMS INDICATED AND
SHALL BE RESPONSIBLE FOR DISPOSAL PER LOCAL, STATE AND FEDERAL REGULATIONS
AND PAY FOR ALL ASSOCIATED COSTS OF DISPOSAL.
10. IF REQUIRED, RELOCATE AS NECESSARY ALL EXISTING DUCTWORK, PIPING AND
CONTROLS FOUND PASSING THROUGH THE AREA OF CONSTRUCTION, AND WHICH ARE
PRESENTLY IN USE IN OTHER PORTIONS OF THE BUILDING UNAFFECTED BY THIS PROJECT
PHASE, TO MAINTAIN THE CONTINUITY OF SERVICE.
11. ALL DUCTWORK, GRILLES AND DEVICES WITHIN THE AREA OF CONSTRUCTION WHICH ARE
NOT INDICATED TO BE REUSED OR TURNED OVER TO THE OWNER SHALL BE DISPOSED OF
BY THE CONTRACTOR.
12. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL CUTTING AND PATCHING NECESSARY
TO REPAIR ANY DAMAGE CAUSED BY CONSTRUCTION ACTIVITIES UNDER HIS/HER
CONTRACT. THIS WORK INCLUDES AREAS OUTSIDE ANY LIMITS OF CONSTRUCTION LINES
INDICATED ON THE DRAWINGS.
13. RUBBISH AND DEBRIS SHALL BE REMOVED FROM THE WORK AREAS DAILY, UNLESS
OTHERWISE DIRECTED, TO AVOID ACCUMULATION AT THE DEMOLITION SITE. MATERIALS
THAT CANNOT BE REMOVED DAILY SHALL BE STORED IN AREAS SPECIFIED.
DEMOLITION KEYED NOTES:
DEMOLISH AND REMOVE AHU-1 UNIT. DEMOLITION SHALL INCLUDE ALL GAUGES,
INSTRUMENTATION, CONTROLS, SUPPORTS, ELECTRICAL AND MECHANICAL
CONNECTIONS, AND ALL APPURTENANCES.
RETAIN THE SUPPLY AND RETURN DUCTWORK AS INDICATED. PRESERVE THE
CONNECTIONS SUCH THAT THESE CAN BE REUSED TO CONNECT TO THE NEW UNIT.
DISCONNECT ALL HOT WATER SUPPLY AND RETURN PIPING TO THE UNIT. RETAIN THE
PIPING FOR CONNECTION TO THE NEW UNIT.
DISCONNECT AND DEMOLISH THE OUTDOOR CONDENSING UNIT, HOUSEKEEPING PAD,
AND ALL REFRIGERANT PIPING TO THE EXISTING AHU-1. DEMOLITION SHALL INCLUDE
ALL REFRIGERANT PIPING, SUPPORTS, HANGERS, ALL APPURTENANCES INCLUDING
THE CONDENSING UNIT.
DEMOLISH AND REMOVE THE OUTSIDE AIR INTAKE AS SHOWN. EXTEND THE LOUVER
BLOCKAGE TO INCLUDE THE OPENING.
EXTERIOR LOUVER SHALL REMAIN AND BE PROTECTED DURING DEMOLITION OR
CONSTRUCTION ACTIVITIES. ANY DAMAGE SHALL BE REPAIRED BY THE CONTRACTOR
AT NO COST TO THE GOVERNMENT.
ALSSS
G
F
E
D
C
B
A f-' I I l I
FP-1 I ':>
lilh 11111 =''d'·
IILE-- :.,
FP-.J-IC
( I I f-1 I 1 · - ·, 1;1 ==,c,;
c::_ I b ::)
i I
I --� I i I (I 1 f • . - 4 1
CD NEW HVAC DEMO PLAN EAST
1/8"=1'
[1 -- ,/ 4 1 I 11
,A.: . [,SS1 , -
ll-l1(!
ILC:T-,Q
1 ?
I f--------------
.�; ¼-' '
•TT FOR ' !
! I I I .
ET--
. �n,.___1::·,
• - rr. FOR "I • :' I
I I
=-l
1/-1 lvl-1
I I I
I
C· '/:
rRE T:C:DLE::OS
1 t .' I
I !
11 I ) ;.. \ 0 Ii ' � c; rm I[: OF [l 'Vlrv-
--------tH-+=� 2, C l1'VI"--+---""'--.,;::---+-, '.' / ,; :J 'S"""l!,..,,,..=---'-tt,c--.-�---:N=C""l - 55
I lJ
N -· N .J _/L__L- -----NlXI N1 1 • I N r; '-I --r -I Ii�·� =r1 .. E 2 -.1,, W--
N -x,:L�F''1 I 15
IC 1 C
I 01) 11 lh N
' I \I 'F[ I '
-i-----,1 :_�, I. U ri--' .
. ! 4
(I,-' f')-1 41
:c 7Tl .. -2C1 i]A -371 1111 L= '' IILET=i3'
,:-1\1 1.,1
._l
, /:'.,.ii I - I t � .!'
IS.3 :"_1
l '0•• I
� � I : l\ I 11 f I
� 10 I
KEYED NOTES:
I
0 I I -- -"
,-I
:B f�
I.I - I 9. ·1 CF .I
1111 - :,•J':, :-1 I 11'11 - =i-''
IIF i•JIT3 I I ,..
f
---1 =1
- 71 n
' ' ·. 11 C 1__::1 -; _,, 111.�. = 4 1.1 ,1
11111 __ , 'JC 1 FI.
11.ILC:--i3'
1. DEMOLISH AND REMOVE EXISTING 28X20 AND
28X10 MAIN DUCT LINES AS INDICATED.
1P-IJ- -
I.I = 'T3 I.Ill -231 :1H
11\I - "
1·,, ;:u11
F II ID
I I I
.l __ _,,,..,_, C:,IJFFL
PC:HPl=-cl- ,:c
-r• --:c ·I
EXISTING TO DEMO
SEE D-1 01
Hfl-- Fr-.!- 5 Iii --2':, lvlll .=Id
II _ET= ::1"
,: ii ,1 I
[,I. -T Sl1IJl<E 1;f f .• _.1;,, �111, 1T I F:F'
RETAIN ALL FPTU'S BRANCH DUCTS AND
FITTINGS TO BE RECONNECTED TO NEW DUCT.
RETAIN AND PROTECT ALL HWS/HWR PIPING.
2. PREPARE THE AREA TO RECEIVE NEW DUCT
WORK. REFER TO M-104 FOR NEW WORK
DETAILS.
3. DEMOLISH AND REMOVE EXISTING DUCT CAP
PREVIOUSLY INSTALLED. DEMOLITION SHOULD
BE COMPLETE TO MAKE ROOM FOR NEW DUCT.
KEY
--EXISTING
---DEMOLISH
KEV Pl AN
,,.....N
�J
HANSCOM AIR
FORCE BASE
z ci z .. 0 z w - I- !.: � !.: � ClOI- Ct:'. w � u 1- :::) (\J :J zCll- 0 0 W�cn t'..)
z tJ woo Nz en< w tJ tt:
LL tt:
<(w I-
LL
0 I-z w ::!i
Ii:
�w
0, 0, � "'w -Cl)�tt: <( MW Cl r-. I- � zwo WUC/l Utt:�!z t2 w w tt: Cl) ::. - ::, C. <I 0::; u ....IO c7jwuC/l> Cl) <(Wz:,,C <( CI ..J I u a:: wI-z w en en CJ en... I- 0 ID W o
Zo
• (I) w ' ffi<C::E�I-ID II.. Qzwoa::w<J...J>< (.) a:: w ::EI- 0 > a:: z LL.
w w a:: Q w::E-CID II.. <C :::! ::Eo::E:i:::=i ...JO<JzW(.) "I- >(/)CJ (.)Wz <C WC<(> -, Q :i::: :i::: 0...J w a::
:i::: (.) II..
II..wa::
t.i ='WmO>o
t) a:: O') zo� Ow-� ....I ct'.'. uO ::, I Wtt:zU 1-0 z C/l 1-w z r- g 0::, > umo z Ott:
o�a.
tt: <( :a:
I-z <C...J :i: w 0
�:i:::
s: w z
SHEET ID
D-104
100% SUBMISSION
GROUND
0' - 0"
8" CONCRETE PAD
20 GA MIN. METAL STRAPS, GALVANIZED
OR EQUAL. WRAP CONTINUOUS AROUND
POSTS W/MINIMUM 24" OVERLAP. PROVIDE
#10 SCREWS AT 6" O.C. AT OVERLAP
UNISTRUT P1001 SUPPORT POST EACH
SIDE OF DUCT. STRONG AXIS
ORIENTED PARALLEL TO GOOSENECK.
GALVANIZED OR EQUAL.
NOTE:
BIRD SCREEN
AC UNIT
SUPPLY AND RETURN
DUCTWORK NOT SHOWN
FOR CLARITY.
6X6 METAL
PLATE AT BASE
OF UNISTRUT.
ALL (4) SIDES
COMPACTED SUBBASE (TYP.)
NEW 8" THICK CONCRETE PAD
(4) - ½"Ø HILTI KWIK ANCHOR
BOLT TZ2. PROVIDE 6" MINIMUM
EMBEDMENT INTO SLAB. (TYP.)
PHP SYSTEMS/DESIGNS 6"x6"
POST BASE ON CONCRETE
(TYP)
INTAKE DUCT
UNISTRUCT DUCT
SUPPORT FRAME
4" MIN. (TYP.)
6" M
IN
T/ CONC. PAD
EL. VERIFY IN FIELD
T/ DUCT SUPPORT
EL. VERIFY IN FIELD
PHP-D SUPPORT STAND (4 POSTS)
1/2" Ø HILTI KWIK ANCHOR
BOLT TZ2 MIN. 6" EMBEDMENT,
(4) REQ'D. PER 6x6 PLATE.
8" CONC. SLAB W/
W.W.F. 6x6 - W2.1xW2.1
FL
EX
C O
N N
EC
TI
O N
(F C
AC UNIT
RETURN SIDE ELEVATION
FACTORY CURB
NEW SUPPLY/RETURN
EXIST. BLDG.
3/16" SIMPSON TITAN TURBO MASONRY
SCREWS @ 6" O.C. MIN. 2" EMBED IN BRICK
3" x 3" x 16 GAUGE GALVANIZED
UTILITY ANGLE FULL WIDTH OF DUCT
#10 TEK SCREWS @ 6" O.C. INTO DUCT
THREE #6 CORROSION RESISTANT BUGLE
HEAD SCREWS INTO EACH STUD @ 6" O.C.
STRUCTURAL NOTES:
2.
A.
B.
C.
D.
E.
F.
G.
H.
GENERAL NOTES:
CONSTRUCTION SHALL FOLLOW I.B.C. 2018.
THE CONTRACTOR SHALL FIELD VERIFY ALL DUCT DIMENSIONS BEFORE PREPARING
SHOP DRAWINGS, ORDERING OR FABRICATING ANY MATERIALS. ALL EXPANSION JOINTS AND
CONSTRUCTION SHALL ALIGN WITH AND MATCH EXISTING CONSTRUCTION. CONFIRM WITH
ARCHITECTURAL PLANS. REPORT ANY DISCREPANCIES TO ENGINEER PRIOR TO
PROCEEDING WITH WORK.
THE CONTRACTOR SHALL PROTECT EXISTING FACILITIES, STRUCTURES AND UTILITY LINES
FROM ALL DAMAGE.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATE BRACING OF DUCTS
AND NON-STRUCTURAL ITEMS DURING CONSTRUCTION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING A CLEAN AND WORKMANLIKE
APPEARANCE. ALL DEBRIS SHALL BE REMOVED FROM THE SITE CONFORMING TO THE
GOVERNING LAW.
THE CONTRACTOR SHALL COMPLY WILL ALL GOVERNING CODES AND LAWS AFFECTING THE
WORK. THIS SHALL BE INCLUSIVE OF ANY LOCAL, STATE, OR FEDERAL LAWS AND CODES.
PRIOR TO EXCAVATING OR DEMOLISHING, NOTIFY THE ONE CALL SYSTEM IN THE REGION TO
ASSURE THAT UNDERGROUND FACILITIES ARE IDENTIFIED. LAW REQUIRES NO LESS THAN
THREE NOR MORE THAN TEN WORKING DAYS NOTICE BEFORE YOU DIG.
ALL REFERENCED STANDARDS REFER TO LATEST EDITION.
3.
A.
B.
C.
CONCRETE:
CONCRETE SHALL EXHIBIT A 28-DAY COMPRESSIVE STRENGTH OF 4,000 P.S.I.
REINFORCING SHALL CONFIRM TO A.S.T.M. A615, GRADE 60, UNLESS NOTED OTHERWISE.
CONCRETE SHALL MEET THE REQUIREMENTS OF A.C.I. 318.
C.
1.
2.
WIND LOADS:
BASIC WIND SPEED (3 SECOND GUST)
OVERALL EXPOSURE CATEGORY
E.
1.
2.
3.
4.
5.
6.
7.
SEISMIC:
SPECTRAL RESPONSE SHORT PERIODS
SPECTRAL RESPONSE 1 s PERIOD
SEISMIC IMPORTANCE FACTOR
OCCUPANCY CATEGORY
SEISMIC CATEGORY
SITE CLASS
SEISMIC RESPONSE COEFFICIENT
Ss = 29.8 % S1 = 6.91 % 1.5
IV
C C Cs = .0776
= 109 MPH
= C
B.
1.
2.
3.
4.
SNOW LOADS:
GROUND SNOW LOAD
DUCT SNOW LOAD
SNOW EXPOSURE FACTOR
SNOW LOAD IMPORTANCE FACTOR
Pg = 50 PSF Pf = 35 PSF Ce = 1.0 ls = 1.0
A. BUILDING CODE: 2018 IBC / UFC 3-301-01
1. DESIGN CRITERIA:
4.
A.
STEEL CONSTRUCTION
STEEL MEMBERS FOR DUCT SUPPORT SHALL BE UNISTRUT OR EQUAL, SIZE AS SHOWN ON THE
DRAWINGS.SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS AND CODE OF STANDARD PRACTICE, F. RISK CATEGORY: II
HANSCOM AIR
FORCE BASE
SHEET ID
D
EP
A R
TM
EN
T O
F
TH
E A
IR
F
O R
C E
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
F
E
D
C
B
A
D A
TE
M
A R
K D
ES
C
R
IP
TI
O
N
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H
AN
SC
O
M A
IR
F
O R
C E
BA
SE
M
AS
SA
C
H U
SE
TT
S
M
AR
O N
C O
N
ST
R U
C
TI
O N
C O
IN
C
BU
TT
O N
H O
LE
D
R
IV
E
PR
O
VI
D
EN
C E, R I 0
N
LE
A
D P
R O
FE
SI
O N
A L
BB
IX
, L
LC
SO
U
TH
S
TR
EE
T
BO
ST
O
N , M
A
S-100
ST
R
U C
TU
R
AL
D
ET
AI
LS
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H A
N
SC
O M
A
IR
F O
R C
E B
A
SE
/2
0/
R
EP
LA
C
E H
VA
C
, C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R
PR
O
JE
C T
N U
M B
ER
: M
XR
D
6-
SCALE = N.T.S.1 INTAKE SIDE ELEVATION
SCALE = N.T.S.2 INTAKE SUPPORT DETAIL
SCALE = N.T.S.3 RETURN SIDE ELEVATION
SCALE = N.T.S.4 SECTION THRU EXTERIOR WALL
Tom New Stamp
EQUIPMENT DESIGNATIONS
ABBREVIATIONS MECHANICAL GRAPHIC SYMBOLS
MIN MINIMUM
RELIEF HOOD
UNIT HEATER
SUPPLY FANSF
FAN TERMINAL UNITFT
UH
WATER COLUMN
STAINLESS STEEL
STATIC PRESSURE
REVOLUTIONS PER MINUTE
PRESSURE DROP
PLUMBING CONTRACTOR
OUTSIDE AIR TEMPERATURE
NORMALLY OPEN
NOT IN CONTRACT
NORMALLY CLOSED
COOLING COIL
EXHAUST FAN
WB WET BULB
EF
F
CC
WC
WG
FILTER
WATER GAUGE
RPM
TYP
V
SS
SP
SENS.
SA
OA
PD
PC
OAT
RA
PH
NC
MTD
NTS
NO
NIC
TYPICAL
SENSIBLE HEAT
SUPPLY AIR
VOLTS
RETURN AIR
OUTSIDE AIR
NOT TO SCALE
MOUNTED
PHASE
RH
BUILDING AUTOMATION SYSTEM
CUBIC FEET PER MINUTE
AIR PRESSURE DROP
ABOVE FINISHED FLOOR
LEAVING AIR TEMPERATURE
HERTZ, CYCLES PER SECOND
GENERAL CONTRACTOR
FEET PER MINUTE
ELECTRICAL CONTRACTOR
ENTERING AIR TEMPERATURE
DIRECT EXPANSION
MECHANICAL CONTRACTOR
MIXED AIR TEMPERATURE
MFR
MC
MBH
MAT
LAT
Hz
HP
IN
FD
GC
FPM
F
EC
EAT
EA
DX
DEG
INCHES
HORSEPOWER
MANUFACTURER
1000 BTUH
DEGREES
FLOOR DRAIN
FAHRENHEIT
EXHAUST AIR
APD
BAS
CFM
BTUH
BTU
DB
AFF
BTU / HOUR
DRY BULB
DP DIFFERENTIAL PRESSURE SENSOR
HIGH DENSITY POLYETHYLENE PIPINGHDPE
FEETFT
FIRE DAMPERFD
AIR HANDLING UNITAHU
VARIABLE AIR VOLUME BOX
CABINET UNIT HEATER
AIR CONDITIONING UNIT
CONDENSING UNIT
VAV
CUH
AC
CU
BRITISH THERMAL UNITS
AIR CURTAIN UNITARC
HEATING COILHC
NOTE: NOT ALL SYMBOLS ARE USED IN THIS PROJECT.
1. ALL THERMOSTATS ARE TO BE MOUNTED 5’-6” ABOVE FINISH FLOOR.
2. THE HVAC CONTRACTOR SHALL SEAL THE PIPING PENETRATIONS THROUGH
WALLS WITH APPROVED FIRE STOP MATERIAL.
3. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S APPROVED PUBLISHED LITERATURE.
4. ALL WORK UNDER THE SECTION SHALL BE COORDINATED WITH ALL OTHER
TRADES BEFORE INSTALLATION IS MADE.
5. REFER TO ARCHITECTURAL DRAWINGS FOR LOUVER INFORMATION..
6. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF 'ALL'
SUBCONTRACTORS AND THEIR EQUIPMENT, PIPING, CONDUITS, VALVING, ETC. IF
LOCATIONS CAN NOT BE INSTALLED DUE TO FIELD CONDITION. RELOCATION OR
ADJUSTMENT OF SUCH ITEMS MUST BE INCLUDED IN BASE BID OF CONTRACTORS
AND WILL NOT BE CONSIDERED AS AN EXTRA.
GENERAL CONSTRUCTION NOTES
1. THE BUILDING WILL REMAIN OCCUPIED DURING DEMOLITION ACTIVITIES. DUST
CONTROL PROVISIONS ARE REQUIRED TO ENSURE AGAINST MIGRATION OF ALL
DUST AND DEMOLITION DEBRIS TO OCCUPIED SPACES.
2. THE CONTRACTOR SHALL COMPLY WITH THE MARKING OF EGRESS IN
ACCORDANCE WITH THE CODE REQUIREMENT THROUGHOUT THE DEMOLITION.
3. THE CONTRACTOR SHALL PROVIDE STEP-OFF PADS (TACK MATS) AT ALL ENTRY
AND EGRESS PATHS IN AND OUT OF THE LIMIT OF WORK AREA. THE CONTRACTOR
SHALL REPLACE THE STEP-OFF PADS AS OFTEN AS NEEDED, TO ENSURE AGAINST
MIGRATION OF DUST AND CONSTRUCTION DEBRIS OUTSIDE OF THE WORK AREA.
1. THE BUILDING WILL REMAIN OCCUPIED DURING DEMOLITION ACTIVITIES. NOISE
CONTROL PROVISIONS ARE REQUIRED TO ENSURE AGAINST DISTURBANCE OR
DISRUPTION OF WORK ACTIVITIES OF THE BUILDING OCCUPANTS.
2. ANY PROPOSED INTERRUPTION TO TENANT OPERATIONS DURING DEMOLITION
MUST HAVE PRIOR APPROVAL FROM THE OWNER WITH A MINIMUM OF 72 HOURS
ADVANCE NOTICE.
3. THE DEMOLITION SUBCONTRACTOR SHALL ADOPT QUIETER TYPES OF
DEMOLITION AS IS PRACTICAL BY USING POWER TOOLS EQUIPPED WITH
SILENCERS.
4. THE CONTRACTOR SHALL PROVIDE PROVISIONS TO ENSURE AGAINST SOUND AND
VIBRATION NOISE TO THE BUILDING OCCUPANTS.
DUST CONTROL PROVISIONS
NOISE CONTROL PROVISIONS
1. DRAWINGS, PLANS AND DIAGRAMS INDICATE GENERAL LOCATION AND
ARRANGEMENT OF EQUIPMENT AND PIPING. PROVIDE ALL
APPURTENANCES/ACCESSORIES NECESSARY FOR THE PROPER INSTALLATION,
COORDINATION AND OPERATION OF SYSTEMS. ALL SYSTEMS AND EQUIPMENT
SHALL BE INSTALLED IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL
CODES.
2. INSTALL EQUIPMENT ACCORDING TO APPROVED SUBMITTAL DATA. INSTALL
EQUIPMENT LEVEL, PLUMB AND PARALLEL TO BUILDING AND WITH
MANUFACTURER'S RECOMMENDED MINIMUM CLEARANCES FOR MAINTENANCE,
REPAIR AND REPLACEMENT.
3. REFER TO DETAILS AND SPECIFICATIONS FOR ALL NECESSARY
APPURTENANCES AND METHODS AND COMPLY WITH THE REQUIREMENTS.
4. VERIFY EXACT SIZE AND LOCATION OF EXISTING UTILITIES BEFORE START OF
DEMOLITION.
5. RELOCATE, REMOVE, AND ADJUST ALL MECHANICAL AND ELECTRICAL ITEMS TO
COORDINATE WITH NEW WORK PLANS.
6. ALL MECHANICAL ITEMS SHOWN ARE EXISTING AND SHOWN IN SCHEMATIC
FORM ONLY.
7. REMOVE EXISTING PIPING, DUCTWORK AND CONTROL WIRING BACK TO LAST
ACTIVE SERVICE. UPON DEMOLITION OF MECHANICAL UNIT AND ASSOCIATED
CONTROL WIRING, THE BAS CONTRACTOR SHALL UPDATE THE SOFTWARE
SYSTEM GRAPHICS TO INDICATE UNIT IS NO LONGER IN SERVICE.
8. REMOVED FIXTURES AND EQUIPMENT SHALL REMAIN THE PROPERTY OF THE
OWNER. ALL EQUIPMENT AND MATERIALS NOT CLAIMED BY THE OWNER SHALL
BE REMOVED FROM THE PREMISES BY THE CONTRACTOR.
9. IN AREAS WHERE EXISTING CONSTRUCTION IS REMOVED AND NO ADDITIONAL
CONSTRUCTION IS INDICATED. PATCH EXISTING CONSTRUCTION TO MATCH
EXISTING CONDITION. FIRE SEAL ALL EXISTING OPENINGS IN ALL WALLS AND
FLOORS WHERE EXISTING PENETRATIONS ARE TO REMAIN.
10. CONNECTIONS TO, AND SHUTDOWNS OF, EXISTING SYSTEMS SHALL BE
COORDINATED WITH OWNER TO ALLOW MINIMUM INTERFERENCE WITH
OWNER'S OPERATION AND MINIMUM DOWNTIME OF EXISTING SERVICES.
CONTRACTOR SHALL SUBMIT TO OWNER FOR REVIEW AND APPROVAL OF THE
PROPOSED PHASING PLAN FOR CONNECTING NEW SERVICES TO EXISTING
SERVICES.
11. CONTRACTOR SHALL COMPLY WITH GENERAL CONDITIONS AND PROTECTION
PROVISIONS SPECIFIED FOR JOINT OWNER/CONTRACTOR OCCUPANCY WORK
AREAS.
12. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS BEFORE BEGINNING WORK.
CONTRACTOR SHALL PROTECT EXISTING UTILITIES, EQUIPMENT AND MATERIALS
FROM DAMAGE DURING CONSTRUCTION. ANY EXISTING UTILITIES, EQUIPMENT,
MATERIALS AND SERVICES DAMAGED SHALL BE REPAIRED AT NO EXPENSE TO
THE OWNER. CONTRACTOR SHALL TEMPORARILY MOVE OR TAKE OUT
EQUIPMENT SERVICES AS NECESSARY TO COMPLETE WORK. SUCH SERVICES
SHALL BE REPAIRED IN ACCORDANCE WITH THE SPECIFICATION.
NOTE: APPLICABLE TO ALL DRAWINGS
GENERAL NOTES
T/H
EQUIPMENT DESIGNATION
SECTION REFERENCES
KEYED NOTE SYMBOL
INDICATES POINT OF CONNECTION
BETWEEN NEW AND EXISTING
THERMOSTAT
FIN TUBE RADIATOR
MOTORIZED CONTROL VALVE
RTU
M
HANSCOM AIR
FORCE BASE
SHEET ID
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H
AN
SC
O
M A
IR
F
O R
C E
BA
SE
M
AS
SA
C
H U
SE
TT
S
M
AR
O N
C O
N
ST
R U
C
TI
O N
C O
IN
C
BU
TT
O N
H O
LE
D
R
IV
E
PR
O
VI
D
EN
C E, R I 0
N
LE
AD
P R
O
FE
SI
O
N
AL
BB
IX
, L
LC
SO
U
TH
S
TR
EE
T
BO
ST
O
N , M
A
M-001
M
EC
H
AN
IC
AL
A
BB
R
EV
IA
TI
O N
S, N
O
TE
S, A
N D
SY
M
BO
LS
CH
IL
D
DE
VE
LO
PM
EN
T
CE
NT
ER
, B
HA
NS
CO
M A
IR
F
O
RC
E
BA
SE
VC
S
AS
/2
1/
100% SUBMISSION
RE
PL
AC
E
HV
AC
, C
HI
LD
D
EV
EL
O
PM
EN
T
CE
NT
ER
PR
O
JE
CT
N
UM
BE
R:
M
XR
D
-0
OUTSIDE
AIR INTAKE
SEE DETAIL
1/M-500
24" x 44"
RETURN
AIR
24" x 44"
SUPPLY
AIR
NEW
SECURITY
FENCE. SEE
SHEET M-502.
4'-0"
4' -0
4'-0"
21'-8"
NEW
CONCRETE
UTILITY PAD,
SLOPE
CONCRETE
UTILITY PAD
FOR POSITIVE
DRAINAGE
AWAY FROM
THE BUILDING
NEW
CONCRETE
UTILITY PAD,
SLOPE
CONCRETE
UTILITY PAD
FOR POSITIVE
DRAINAGE
AWAY FROM
THE BUILDING
OUTSIDE
AIR INTAKE
SEE DETAIL
1/M-500
24" x 44"
RETURN
AIR
24" x 44"
SUPPLY
AIR
NEW
SECURITY
FENCE. SEE
SHEET M-502.
4'-0"
4' -0
4'-0"
3'-1"
20'-10"
1"
OUTSIDE AIR INTAKE
SEE DETAIL 1/M-500
20" x 32"
RETURN
AIR
26" x 34"
SUPPLY
AIR
NEW SECURITY FENCE.
SEE SHEET M-502.
4' -0
4'-0"
4' -0
17' - 9"
'-8
17' - 9"
NEW CONCRETE
UTILITY PAD,
SLOPE
CONCRETE
UTILITY PAD
FOR POSITIVE
DRAINAGE
AWAY FROM
THE BUILDING
CU-1
AHU-1
24" x 16"
OUTSIDE
AIR INTAKE
HANSCOM AIR
FORCE BASE
SHEET ID
D
EP
A R
TM
EN
T O
F
TH
E A
IR
F
O R
C E
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
TE
M
A R
K D
ES
C
R
IP
TI
O
N
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H
AN
SC
O
M A
IR
F
O R
C E
BA
SE
M
AS
SA
C
H U
SE
TT
S
M
AR
O N
C O
N
ST
R U
C
TI
O N
C O
IN
C
BU
TT
O N
H O
LE
D
R
IV
E
PR
O
VI
D
EN
C E, R I 0
N
LE
A
D P
R O
FE
SI
O N
A L
BB
IX
, L
LC
SO
U
TH
S
TR
EE
T
BO
ST
O
N , M
A
M-101
N
EW
M
EC
H
AN
IC
AL
P
LA
N S
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H A
N
SC
O M
A
IR
F O
R C
E B
A
SE
VC
S
AS
4/
/2
100% SUBMISSION
R
EP
LA
C
E H
VA
C
, C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R
PR
O
JE
C T
N U
M B
ER
: M
XR
D
6-
1/4" = 1'-0"1 AC-1_NEW MECHANICAL
1/4" = 1'-0"2 AC-2_NEW MECHANCIAL
1/4" = 1'-0"3 AC-3_NEW MECHANICAL
1/4" = 1'-0"4 MECHANICAL AND ELECTRICAL ROOM
1.
2.
3.
4.
5.
6.
7.
GENERAL NOTES:
ALL INFORMATION AND WORK SHOWN AS EXISTING WAS TAKEN FROM FIELD VISITS BY
THE ENGINEER AND FROM OWNER PROVIDED PAST CONSTRUCTION DOCUMENTS.
EQUIPMENT AND DUCTWORK HAVE BEEN SHOWN IN AN APPROXIMATE WAY.
CONSEQUENTLY, THE INFO IS APPROXIMATE AT BEST.
ALL WORK SHALL BE PERFORMED WITH "DUE CARE AND DILIGENCE" SO AS TO PREVENT
THE UNNECESSARY DESTRUCTION AND OR DAMAGE TO SYSTEMS THAT SHALL REMAIN
IN OPERATION DURING THE PERFORMANCE OF THIS WORK.
DETERMINE THE EXACT LOCATIONS OF ALL EXISTING EQUIPMENT, DEVICES AND WIRING
BEFORE COMMENCING WORK. NOTIFY ENGINEER WITH ANY QUESTIONS.
THE CDC FACILITY AND ALL ADJACENT SPACES TO THE LIMIT OF WORK NEEDS TO
REMAIN OPERATIONAL AT ALL TIMES DURING THE DEMOLITION AND CONSTRUCTION
ACTIVITIES. ISOLATE THE SUPPLY AND RETURN AIR BRANCH DUCTWORK TO ENSURE
THAT NO AIR IS TRANSFERRED OUT OF THE LIMIT OF WORK AREA. PROVIDE
TEMPORARY VENTILATION IF REQUIRED.
CONTRACTOR SHALL PROVIDE A CONSTRUCTION SCHEDULE AND CONSTRUCTION
PHASING PLAN FOR GOVERNMENT APPROVAL PER THE BASIC MACC CONTRACT PRIOR
TO COMMENCING WORK. SERVICE TO MORE THAN ONE ZONE SHALL NOT BE REMOVED
FROM ACTIVE SERVICE SIMULTANEOUSLY DURING PHASED CONSTRUCTION. HVAC
SERVICES SHALL NOT BE INTERRUPTED WITHOUT PRIOR APPROVAL OF GOVERNMENT
AND TEMPORARY SERVICES SHALL BE PROVIDED FOR OUTAGES DURING WORKING
HOURS AND LONGER THAN 8 HOURS.
INSTALL UNITS IN A MANNER TO MEET THE MANUFACTURER'S RECOMMENDED
CLEARANCES AS REQUIRED.
INSTALL AN EMERGENCY HVAC SHUTOFF/POWER (EPO) PUSH BUTTON AT THE MAIN
FACILITY ENTRANCE. COORDINATE LOCATION OF EPO WITH THE GOVERNMENT.
KEYED NOTES:
AC-1
TRANSITION TO EXISTING 48X24 RETURN DUCT.
TRANSITION TO EXISTING 28X24 SUPPLY DUCT.
AC-2
TRANSITION TO EXISTING 42X24 RETURN DUCT.
TRANSITION TO EXISTING 24X24 SUPPLY DUCT.
AC-3
TRANSITION TO EXISTING 48X24 RETURN DUCT.
TRANSITION TO EXISTING 28X24 SUPPLY DUCT.
AHU-1
TRANSITION TO EXISTING 48X12 RETURN DUCT IN MECHANICAL ROOM.
TRANSITION TO EXISTING 36X14 SUPPLY DUCT IN MECHANICAL ROOM.
PROVIDE NEW INSULATED OUTSIDE AIR DUCT WITH MOTORIZED DAMPER. DAMPER
SHALL BE CLASS 1 A LOW LEAKAGE DAMPER.
INSTALL THE NEW CONDENSING UNIT ON NEW 6" CONCRETE PAD. PAD SHALL BE SIZED
TO EXTEND 6" BEYOND THE FOOTPRINT OF THE UNIT ON ALL SIDES. OBSERVE ALL
MANUFACTURER RECOMMENDED CLEARANCES.
8. CONTACT FIRE PREVENTION FOR ANY ISSUANCE OF HOT WORK PERMITS EXT. 5-5600
RECONNECT THE EXISTING HOT WATER HEADER TO NEW AHU-1 HEATING COIL.
STERILIZE AND DISINFECT ALL PIPING. FLUSH PIPING BEFORE PLACING INTO SERVICE.
SEE SPECIFICATION 23 05 15. SEE DETAIL 5/M-501
schmidtv Pencil schmidtv Pencil
BACKDRAFT
DAMPER
FAILURE
ALARM
CT
M
EX
HA
US
T
AI
R
MOTORIZED
DAMPER
A H
EXHAUST FANS EF-1 AND EF-2 SHALL BE INTERLOCKED
WITH AHU-1. WHENEVER EXHAUST FANS ARE ENERGIZED,
AHU-1 SHALL RUN.
C
H C
C
FS TSTS
HC
CT
VFD
SUPPLY AIRRETURN AIR
O U
TS
ID
E
AI
R F
R O
M G
O O
SE
N
EC
K
AB
O
VE
R
O O
F
LE
VE
L
DPS
FILTER
SPT
LOCATED 2/3 DOWN
SUPPLY DUCT
EXISTING
JCI
CONTROLLER
EXISTING PLANT NETWORK
FACTORY CONTROLS PROVIDED WITH AHU
BACNET
DIRTY ALARM
(.75" WC)
SPEED START/
STOP
SPEED ALARM
STATUS/FAILURE
ALARM
LIQ
VAP
HWS
HWR
SUPPLY FAN
M
H
TS
SD
FIRE ALARM SYSTEM DUCT
DETECTOR
M
OAS
TO EXHAUST FAN
INTERLOCK AND
ROOM PRESSURE
SENSOR
COOLING COIL
REFRIGERANT LINES
TO/FROM
CONDENSING UNIT
(LIQUID/VAPOR)
H
LEGEND:
HOA
CT CURRENT SENSOR/TRANSMITTER
DPS DIFFERENTIAL PRESSURE SWITCH
FLOW SENSOR/SWITCHFS
HUMIDITY SENSOR
HAND-OFF-AUTO
HWR
HWS
LIQ
M
SD
SPT
TS
VAP
VFD
HOT WATER RETURN
HOT WATER SUPPLU
REFRIGERANT LINE (LIQUID)
MOTOR/MOTOR OPERATED
SMOKE DETECTOR
STATIC PRESSURE SENSOR/TRANSMITTER
TEMPERATURE SENSOR/TRANSMITTER
REFRIGERANT LINE (VAPOR)
VARIABLE FREQUENCY DRIVE
OAS OUTDOOR AIR FLOW MONITORING STATION
H
A
H
AFS AIR FLOWER SENSOR
ROOF
AFS
TO FACP
AFSTS
T T
HANSCOM AIR
FORCE BASE
SHEET ID
D
EP
A R
TM
EN
T O
F
TH
E A
IR
F
O R
C E
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
TE
M
A R
K D
ES
C
R
IP
TI
O
N
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H
AN
SC
O
M A
IR
F
O R
C E
BA
SE
M
AS
SA
C
H U
SE
TT
S
M
AR
O N
C O
N
ST
R U
C
TI
O N
C O
IN
C
BU
TT
O N
H O
LE
D
R
IV
E
PR
O
VI
D
EN
C E, R I 0
N
LE
A
D P
R O
FE
SI
O N
A L
BB
IX
, L
LC
SO
U
TH
S
TR
EE
T
BO
ST
O
N , M
A
M-401
C O
N
TR
O L
SC
H
EM
AT
IC
S
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H A
N
SC
O M
A
IR
F O
R C
E B
A
SE
VC
S
AS
/1
8/
100% SUBMISSION
R
EP
LA
C
E H
VA
C
, C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R
PR
O
JE
C T
N U
M B
ER
: M
XR
D
6-
N.T.S.1 EXHAUST FAN CONTROL SCHEMATIC
N.T.S.2 AHU-1 CONTROL SCHEMATIC
1.
2.
3.
NOTE:
TAB CONTRACTOR AND ATC CONTRACTOR TO WORK
TOGETHER TO CALIBRATE OA FLOW MONITORING STATIONS
FOR ALL UNITS.
REPLACE ALL THERMOSTATS CONTAINING MERCURY. ALL
NEW THRERMOSTATS SHALL BE FURNISHED BY JCI
MARKING AND TAGGING SHALL BE IN COMPLIANCE WITH AFI
91-203, CHAPTER 20.
MS-TP
UH-1 EF-1
EF-2
NEW
EF POINTS
(TYP)
EXISTING
UH POINTS
(TYP)
EXISTING
FPTU/VAV POINTS
(TYP)
AHU-1
EXISTING
BOILER CONTROL
PANEL B-2
AC-3
EXISTING
HOT WATER
SYSTEM POINTS
EXISTING
BOILER CONTROL
PANEL B-1
AC-2AC-1
HWP-1
HWP-2
FPTU-1
FPTU-2
FPTU-3
FPTU-4
FPTU-5
FPTU-6
FPTU-7
FPTU-8
FPTU-9
FPTU-10
FPTU-11
FPTU-12
FPTU-13
FPTU-14
FPTU-15
FPTU-16
FPTU-17
FPTU-18
FPTU-19
FPTU-20
FPTU-21
FPTU-22
FPTU-23
VAV-1
JCI
CONTROLSEOL RESISTOR EOL RESISTOR
HANSCOM AIR
FORCE BASE
SHEET ID
D
EP
A R
TM
EN
T O
F
TH
E A
IR
F
O R
C E
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
TE
M
A R
K D
ES
C
R
IP
TI
O
N
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H
AN
SC
O
M A
IR
F
O R
C E
BA
SE
M
AS
SA
C
H U
SE
TT
S
M
AR
O N
C O
N
ST
R U
C
TI
O N
C O
IN
C
BU
TT
O N
H O
LE
D
R
IV
E
PR
O
VI
D
EN
C E, R I 0
N
LE
A
D P
R O
FE
SI
O N
A L
BB
IX
, L
LC
SO
U
TH
S
TR
EE
T
BO
ST
O
N , M
A
M-402
N
ET
W O
R K
AR
C
H
IT
EC
TU
R E
SC
H
EM
AT
IC
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H A
N
SC
O M
A
IR
F O
R C
E B
A
SE
VC
S
AS
4/
/2
100% SUBMISSION
R
EP
LA
C
E H
VA
C
, C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R
PR
O
JE
C T
N U
M B
ER
: M
XR
D
6-
09N.T.S.1 NETWORK ARCHITECTURE SCHEMATIC
EXHAUST FAN SCHEDULE
TAG MAKE MODEL TYPE MOTOR
HP CFM RPM SP
(IN WG)
VOLTAGE NOTES
EF-1 GREENHECK CUBE ROOF UPBLAST 3 3859 1625 2.75 460/3 1 THRU 4
EF-2 GREENHECK SQ-95 IN-LINE 1/4 535 1725 0.6 120V/1 1 THRU 3
NOTES:
1. PROVIDE UNIT WITH ALL ACCESSORIES, OPTIONS, AND APPURTENANCES FOR A COMPLETE FUNCTIONAL SYSTEM.
2. PROVIDE WITH DISCONNECT SWITCH.
3. EF-1 AND EF-2 SHALL BE INTERLOCKED TOGETHER AND TO AHU-1.
4. PROVIDE WITH MANUFACTURER RECOMMENDED ROOF CURB.
INPUT/OUTPUT SUMMARY TABLE
B1994 CONTROL PROGRAM FUNCTIONS
INPUT
OUTPUT
ANALOG DIGITAL
CONTROL POINTS LIST (EF-1 AND EF-2)
G R
AP
H
IC
D
IS
PL
AY
ST
AT
U S
AL
AR
M
EN
AB
LE
/D
IS
AB
LE
ST
AT
U S
O N
/O
FF
ST
AT
U S
O
PE
N /C
LO
SE
AL
AR
M R
EP
O
R
TS
TR
EN
D R
EP
O
R
TS
AI
R
F
LO
W R
AT
E
ST
AT
U S
O
PE
N /C
LO
SE
R U
N T
IM
E
AL
AR
M
AN
AL
O G
O U
TP
U
T
D
IG
IT
AL
O U
TP
U
T
FAN STATUS • • • • • • • • • •
EPO • • • • • •
AC UNIT SCHEDULE
TAG MAKE MODEL TOTAL AIR
FLOW (CFM)
OUTSIDE AIR
FLOW (CFM)
ESP
(IN WC) HP
COOLING ELECTRICAL
WEIGHT
(LBS) NOTES
TOTAL LOAD
(MBH)
SENSIBLE
LOAD (MBH)
EAT (⁰F)
(DB/WB)
LAT (⁰F)
(DB/WB) VOLTAGE MCA MFS
AC-1 TRANE TTH240G4 6,600 1,000 1.50 5.0 261.3 196 87.6/71.6 60.1/59.8 460/3 46 60 2514 1 THRU 11
AC-2 TRANE TTH300G4 8,200 2,600 1.40 7.5 307.1 231.6 87.6/71.6 61.4/60.5 460/3 56 70 2631 1 THRU 11
AC-3 TRANE TTH300G4 8,400 2,500 1.40 7.5 308.3 233.6 87.6/71.6 61.6/60.7 460/3 56 70 2631 1 THRU 11
NOTES:
1. OUTDOOR UNIT, WITH R-13 CABINET, INTEGRAL FRAME, GROUND MOUNTED, INTEGRAL SPRING ISOLATORS. PROVIDE UNIT WITH ALL ACCESSORIES, OPTIONS, AND APPURTENANCES FOR A COMPLETE FUNCTIONAL SYSTEM.
2. PROVIDE WITH FACTORY CONTROLS WITH JCI BACNET CONNECTIVITY INCLUDING ALL REQUIRED SENSORS, ACTUATORS, ETC.
3. PROVIDE WITH HORIZONTAL DISCHARGE AND HORIZONTAL RETURN.
4. PROVIDE WITH FACTORY MOUNTED AND WIRED DISCONNECT SWITCH WITH SINGLE POINT CONNECTION.
5. PROVIDE WITH CONDENSER HAIL GUARD.
6. PROVIDE WITH MERV 13 FILTERS.
7. PROVIDE WITH TRANE FACTORY KIT TO ALLOW CONVERSION OF UNIT TO VARIABLE AIR VOLUME SYSTEM. PROVIDE VFD ON SUPPLY FAN.
8. ANCHOR FACTORY CURB TO CONCRETE DECK.
9. PROVIDE WITH OA/RA MODULATING DAMPERS FOR ECONOMIZER CONTROL. OA DAMPER SHALL BE LOW LEAKAGE CLASS 1A.
10. PROVIDE UNIT WITH OUTSIDE AIR FLOW MONITORING UNIT.
11. PROVIDE FLEX CONNECTION AT DUCT CONNECTIONS TO UNIT.
INPUT/OUTPUT SUMMARY TABLE
B1994 CONTROL PROGRAM FUNCTIONS
INPUT
OUTPUT
ANALOG DIGITAL
CONTROL POINTS LIST EACH AC UNIT
(AC-1, AC-2, & AC-3)
G R
AP
H
IC
D
IS
PL
AY
ST
AT
U S
AL
AR
M
EN
AB
LE
/D
IS
AB
LE
ST
AT
U S
O N
/O
FF
ST
AT
U S
O
PE
N /C
LO
SE
TE
M
PE
R
AT
U
R E
PR
ES
SU
R
E
H U
M
ID
IT
Y
AL
AR
M R
EP
O
R
TS
TR
EN
D R
EP
O
R
TS
AI
R
F
LO
W R
AT
E
TE
M
PE
R
AT
U
R E
PR
ES
SU
R
E
H U
M
ID
IT
Y
ST
AT
U S
O
PE
N /C
LO
SE
R U
N T
IM
E
FI
LT
ER
D
IF
FE
R
EN
TI
AL
AL
AR
M
AN
AL
O G
O U
TP
U
T
D
IG
IT
AL
O U
TP
U
T
AC STATUS • • • • • • • • •
SUPPLY AIR TEMPERATURE • • • • • • • •
SUPPLY AIR HUMIDITY • • • • • • • •
RETURN AIR TEMPERATURE • • • • • • •
DUCT STATIC PRESSURE SENSOR • • • • • •
SUPPLY AIR FLOW • • • • • •
RETURN AIR FLOW • • • • • •
MIXED AIR TEMPERATURE • • • • • • •
OUTSIDE AIR DAMPER STATUS • • • • • • •
OUTSIDE AIR TEMPERATURE • • • •
OUTSIDE AIR HUMIDITY • • • •
OUTSIDE AIR FLOW RATE • • • • • • •
SPACE AIR TEMPERATURE (HI/LO ALARMS) • • • • • • • •
SPACE AIR HUMIDITY (HI/LO ALARMS) • • • • • • •
ECONOMIZER • • • • • • • • • • • •
FILTER STATUS • • • • • • •
FIRE ALARM SYSTEM ACTIVIATION • • • • • •
VFD SPEED • • • • • •
SMOKE DETECTION • • • • • •
EPO • • • • • •
HANSCOM AIR
FORCE BASE
SHEET ID
D
EP
A R
TM
EN
T O
F
TH
E A
IR
F
O R
C E
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
TE
M
A R
K D
ES
C
R
IP
TI
O
N
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H
AN
SC
O
M A
IR
F
O R
C E
BA
SE
M
AS
SA
C
H U
SE
TT
S
M
AR
O N
C O
N
ST
R U
C
TI
O N
C O
IN
C
BU
TT
O N
H O
LE
D
R
IV
E
PR
O
VI
D
EN
C E, R I 0
LE
A
D P
R O
FE
SI
O N
A L
BB
IX
, L
LC
SO
U
TH
S
TR
EE
T
BO
ST
O
N , M
A
/0
3/
R
EV
IS
IO
N
M-601
M
EC
H
AN
IC
AL
S C
H
ED
U
LE
S
C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R , B
H A
N
SC
O M
A
IR
F O
R C
E B
A
SE
VC
S/
TJ
G
AS
4/
/2
R
EP
LA
C
E H
VA
C
, C H
IL
D
D
EV
EL
O
PM
EN
T C
EN
TE
R
PR
O
JE
C T
N U
M B
ER
: M
XR
D
6-
SEQUENCE OF OPERATION - AC-1, AC-2, & AC-3
A. EACH AC UNIT SHALL OPERATE TO SERVE THE SPACES WITHIN
BUILDING 1994.
B. THE HVAC SYSTEM SHALL BE PROVIDED WITH BACNET
COMPATIBLE FACTORY CONTROLS AND PROGRAMMED TO
OPERATE THE HVAC SYSTEM IN THE APPROPRIATE MODE OF
OPERATION.
C. THE EXISTING FACILITY DDC CONTROL SYSTEM, ENERGY
MANAGEMENT CONTROL SYSTEM (EMCS), AND BASE WIDE
BUILDING CONTROLS, UTILITY MONITORING AND CONTROL
SYSTEM (UMCS), AT HANSCOM AFB ARE JCI METASYS USING
BACNET MS-TP PROTOCOL. THE MASTER CONTROL PANEL IS
LOCATED IN BUILDING 1810. ALL NEW CONTROLS SHALL BE
FURNISHED BY JCI. THE CONTRACTOR SHALL PROVIDE CONTROL
SYSTEMS USING BACNET MS-TP PROTOCOL AND SHALL
INTEGRATE THE NEW SYSTEM CONTROLS WITH THE EXITING JCI
METASYS SYSTEM. DESIGN AND PROVIDE GRAPHICS,
PROGRAMMING, SYSTEM INSTRUMENTATION DIAGRAM,
SEQUENCE OF OPERATIONS, SCHEMATICS, POINT LIST, LABEL,
AND DESCRIPTIONS, ONE-LINE DIAGRAM OF THE BUILDING
CONTROLS IDENTIFYING EXISTING AND NEW COMPONENTS AND
DEVICES.
D. THE HVAC SYSTEM SHALL BE CONTROLLED BY THE DDC SYSTEM.
THE DDC CONTROLLER'S MAIN FUNCTION IS TO OPERATE THE
HVAC SYSTEM IN THE APPROPRIATE MODE OF OPERATION. THE
HVAC DDC CONTROL SYSTEM SHALL BE CAPABLE OF AUTOMATIC
SYSTEM STARTUP BASED ON OPTIMAL START, NIGHT SETUP,
TIME SCHEDULE, RESTART FOLLOWING A FIRE ALARM, OR
RESTART FOLLOWING A POWER FAILURE.
E. THE BUILDING IS SERVED BY EXISTING TERMINAL UNITS (FPTU)
WITH HOT WATER COILS. THE FPTU'S PROVIDE BUILDING
HEATING AND ARE INTEGRATED WITH THE EXISTING DDC
SYSTEM. ON A CALL FOR SPACE HEATING THE HOT WATER
VALVES ON THE TERMINAL UNITS OPEN TO PROVIDE SPACE
HEATING. THE FUNCTION OF THE NEW AC UNITS WILL BE
INTEGRATED WITH THAT OF THE EXISTING TERMINAL UNITS.
F. THE EXISTING BUILDING HAS EXISTING DUCT PRESSURE
SENSORS (P-2) LOCATED AT COLUMN LINE 5-B (AC-1), COLUMN
LINE 14-E (AC-2), AND ROOM 160 (AC-3). THESE DUCT PRESSURE
SENSORS SHALL BE REPLACED WITH NEW SENSORS AND SHALL
BE INTEGRATED INTO THE DESIGN OF THE DDC SYSTEM.
G. THE EXISTING BUILDING HAS THREE BUILDING PRESSURIZATION
SENSORS SHALL REMAIN AND BE INTEGRATED INTO THE DDC
SYSTEM. THESE BUILDING PRESSURE SENSORS SHALL HAVE NO
OPERATIONAL FUNCTION.
OCCUPANCY MODE:
A. THE OCCUPANCY MODE SHALL BE COMMUNICATED OR
HARDWIRED TO THE CONTROLLER VIA A BINARY INPUT. VALID
OCCUPANCY MODES FOR THE UNIT SHALL BE:
OCCUPIED MODE - COOLING:
A. OCCUPIED ROOM COOLING SET POINT FOR SUMMER MONTHS
SHALL BE 74°F (ADJ).
B. IN OCCUPIED MODE, EACH AC UNIT SHALL OPERATE
CONTINUOUSLY TO SATISFY THE TEMPERATURE AND HUMIDITY
SETPOINTS. VFD'S WILL MODULATE SUPPLY FAN AIRFLOW BASED
ON DUCT STATIC PRESSURE TO MEET TEMPERATURE
REQUIREMENTS IN DESIGNATED ZONES.
C. UPON START-UP, THE CONTROL SYSTEM WILL OPEN THE
OUTSIDE AIR DAMPER TO ALLOW THE REQUIRED OUTSIDE AIR
FLOW INTO THE SPACE. THE RELIEF AIR DAMPER SHALL
MODULATE IN SYNC WITH THE OUTSIDE AIR DAMPER TO
MAINTAIN MINIMUM DUCT STATIC PRESSURE (0.6” WG ADJ).
D. WHEN THE SPACE TEMPERATURE IS ABOVE 74°F (ADJ), THE VFD'S
WILL MODULATE SUPPLY FAN AIRFLOW BASED ON DUCT STATIC
PRESSURE TO MEET TEMPERATURE REQUIREMENTS IN
DESIGNATED ZONES. THE RELIEF AIR DAMPER SHALL MODULATE
IN SYNC WITH THE OUTSIDE AIR DAMPER TO MAINTAIN MINIMUM
DUCT STATIC PRESSURE (0.6” WG ADJ).
E. IN COOLING MODE, THE SYSTEM SHALL OPERATE TO MAINTAIN
THE HUMIDITY LEVEL AT OR BELOW 50%. IF A ZONE'S SPACE
TEMPERATURE IS SATISFIED BUT HUMIDITY IS ABOVE 50%, THE
RESPECTIVE ZONE'S INTERIOR TERMINAL UNITS, SUCH AS FPTU'S
HOT WATER REHEAT COIL SHALL OPERATE TO PROVIDE
DEHUMIDIFICATION FUNCTION. THE RESPECTIVE FPTU'S REHEAT
COIL SHALL REMAIN IN OPERATION UNTIL THE SPACE HUMIDITY IS
AT 50% OR BELOW.
F. DURING DEHUMIDIFICATION MODE, EACH AC UNIT SHALL
CONTINUOUSLY OPERATE TO REMOVE HUMIDITY FROM THE
SUPPLY AIR.
G. THE ECONOMIZER SHALL BE ENABLED WHENEVER OUTSIDE AIR
TEMPERATURE IS LESS THAN 55 F DB (ADJ), THE OUTSIDE AIR
HUMIDITY IS LESS THAN 22 BTU/LB (ADJ), THE OUTSIDE AIR
TEMPERATURE IS LESS…
This is the start of the file's text. The full file is on GovTribe.