This document is a pre-demolition asbestos and limited lead-containing paint survey report for the Toilet and Shower Building located at Cheboygan State Park in Cheboygan, Michigan. The survey was conducted on December 7 and 8, 2022 by Atlas Technical Consultants LLC on behalf of the Michigan Department of Natural Resources. The purpose of the survey was to identify and collect samples of suspected asbestos-containing materials (ACMs) and lead-containing paint (LCP) prior to the demolition of the building. Thirty-six bulk samples were collected from twelve homogenous areas and analyzed, with none of the samples containing asbestos. Three paint chip samples were also collected and analyzed, with all three containing lead levels greater than the laboratory reporting limits.
The report provides conclusions and recommendations regarding the identified ACMs and LCP. It states that if any additional materials are discovered during the demolition activities, they must be assumed to contain asbestos until proven otherwise through sampling and analysis. The report also outlines the regulatory requirements related to the management and disposal of LCP and LBP waste and construction debris.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PRE-DEMOLITION ASBESTOS AND LIMITED LEAD-CONTAINING PAINT SURVEY
CHEBOYGAN STATE PARK – TOILET AND SHOWER BUILDING
4490 Beach Road Cheboygan, MI 49721
Project #188BS22769
PREPARED FOR:
Michigan Department of Natural Resources
PREPARED BY:
Atlas Technical Consultants LLC 46555 Humboldt Drive, Suite 100 Novi, Michigan 48377 January 16, 2023
Page | 1
46555 Humboldt Drive, Suite 100 Novi, Michigan 48377
(248) 669-5147 | oneatlas.com
January 16, 2023
Mr. David M Dekett Unit Supervisor Clear Lake State Park 20500 M-33 North Atlanta, Michigan 49709
Subject: Pre-Demolition Asbestos and Limited Lead-Containing Paint Survey Cheboygan State Park – Toilet and Shower Building
Andrew DeLodder State of Michigan Asbestos Inspector Atlas Technical Consultants LLC
Respectfully submitted, If you have any questions, please call us at 248.669.5140.
Response Act of 1987 (AHERA).
Construction Industry Standard (29 CFR 1926.1101), and the Asbestos Hazard and Emergency specified in the Occupational Safety and Health Administration’s (OSHA) Asbestos certified asbestos inspector. The sampling was conducted in accordance with sampling criteria and December 7 and 8, 2022 by Industrial Hygienist, Mr. Andrew DeLodder, State of Michigan The pre-demolition asbestos and lead-containing paint sampling was conducted on December 7 and lead-containing paint (LCP) prior to demolition activities.
sampling was to identify and collect samples of suspect asbestos-containing materials (ACMs) limited lead-containing paint survey performed at the above referenced site. The purpose of this Atlas is pleased to present this report detailing the findings of the pre-demolition asbestos and
Dear Mr. Dekett:
Cheboygan, MI 49721 4490 Beach Road
Atlas Technical Consultants LLC Project Manager Martin Gamble
Page | i
CONTENTS
EXECUTIVE SUMMARY
1. INTRODUCTION
1.1 Purpose
1.2 Pre-Demolition Asbestos Survey
2. GENERAL SITE CONDITIONS
2.1 General Property and Building Information
2.2 Exterior Finish Descriptions
2.3 Interior Building Descriptions
3. PRE-DEMOLITION ASBESTOS SURVEY
3.1 Homogeneous Areas
3.2 Hazard Assessment Factors
3.3 Laboratory Analytical Methodology
3.4 Sampling Results
4. LEAD-CONTAINING PAINT SAMPLING
5. CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos-Containing Materials
5.2 Lead-Containing Paint
6. ASSUMPTIONS AND LIMITATIONS
TABLES
Table 3-1 ACM Sampling Results
Table 4-1 Lead-Containing Paint Sampling Results
APPENDICES
Appendix A Asbestos Laboratory Report Appendix B Lead-Containing Paint Laboratory Report
Page | 2
EXECUTIVE SUMMARY
Atlas representative Mr. Andrew DeLodder completed the pre-demolition asbestos and limited lead-containing paint survey of the Toilet and Shower Building, located in Cheboygan State Park located at 4490
Beach Road, in Cheboygan, Michigan on December 7 and 8, 2022.
Thirty-six (36) asbestos bulk samples, taken from twelve (12) homogenous areas, were collected and submitted for analysis by PLM. Of the 36 samples submitted, fifty-seven (57) sample layers were analyzed.
The results of laboratory testing indicated that none of the suspect materials contain asbestos.
Three (3) representative samples of paint, taken from interior and exterior areas of the building, were collected and submitted for analysis by Flame AAS. The results of laboratory testing indicated that three
(3) samples contained levels of lead greater than the laboratory reporting limits.
If any additional materials are discovered during renovation/demolition activities, such materials must be assumed to contain asbestos until sampling and analysis proves otherwise.
Page | 3
1. INTRODUCTION
1.1 Purpose
The purpose of this project was to conduct a pre-demolition asbestos and limited lead-containing paint survey of the Toilet and Shower Building in Cheboygan State Park located at 4490 Beach Road, in
Cheboygan, Michigan (herein referred to as “the property”).
1.2 Pre-Demolition Asbestos Survey
The scope of the pre-demolition asbestos survey included the following:
Review of existing asbestos reports for the building, if available;
Survey of the property building(s);
Identification of accessible suspect asbestos-containing materials (ACMs);
Collection and analysis of bulk samples of suspect friable and non-friable materials.
2. GENERAL SITE CONDITIONS
2.1 General Property and Building Information
The purpose of this project was to conduct a pre-demolition asbestos and limited lead-containing paint survey of the Toilet and Shower Building.
General property and building information is presented in the following table:
General Property and Building Information
Date of Inspection: December 7, 2022 & December 8, 2022
Inspectors Andrew Delodder, Inspector # A48677
Property Address: 4490 Beach Road, in Cheboygan, Michigan
Property Owner Michigan Department of Natural Resources
Building Description: Cheboygan State Park Restroom Building
2.2 Exterior Finish Descriptions
The exterior of the building included brick and masonry with a shingled-sloped roof.
2.3 Interior Building Descriptions
The interior finishes of the building included plastered walls and ceiling, and floor tiled floors.
3. PRE-DEMOLITION ASBESTOS SURVEY
Atlas representative Mr. Andrew DeLodder conducted the pre-demolition asbestos inspection of the Toilet and Shower building on December 7 and 8, 2022. Mr. DeLodder is a State of Michigan Certified Asbestos
Inspector’s (Certification No. A48677). The building was visually inspected for the presence of building materials that are suspected to contain asbestos. Bulk samples of suspect ACMs were collected and placed into individual containers for transport to a National Voluntary Lab Accreditation Program (NVLAP)-accredited laboratory for analysis. Materials typically known as non-asbestos items (i.e. fibrous glass, foam rubber, wood, etc.) were not sampled. The asbestos inspection consisted of the following three basic procedures:
Page | 4
> Conducting a visual inspection of the structures;
> Identifying homogeneous areas (HAs) of suspect surfacing, thermal system insulation, and miscellaneous materials; and
> Sampling accessible, friable and non-friable suspect materials.
3.1 Homogeneous Areas
Prior to collecting any samples, homogenous areas (HAs) were identified. A homogeneous sampling area can be described as one or more areas of material that are similar in appearance and texture and that have the same apparent installation date, appearance and function. Actual number of samples collected from each homogeneous sampling area may vary, based on the type of material and professional opinion of the inspector.
3.2 Hazard Assessment Factors
From the list of suspect homogeneous areas, a physical assessment was performed for each material on the list. A physical assessment includes evaluating the condition, assessing the potential for disturbance, and determining the friability of each material. By definition, "friable" materials are those that can be crumbled or reduced to powder by hand pressure when dry. Each material identified was further classified into one of three categories: surfacing materials, thermal systems insulation (TSI) and miscellaneous materials. Each of the three categories have specific sampling requirements, outlined below.
Surfacing Materials: Refers to spray-applied or troweled surfaces such as plaster ceilings and walls, fireproofing, textured paints, textured plasters, and spray-applied acoustical surfaces.
Thermal System Insulation: Refers to insulation used to inhibit heat gain or loss on pipes, boilers, tanks, ducts, and various other building components.
Miscellaneous Materials: Refers to friable and non-friable products and materials that do not fit in any of the above two categories such as resilient floor covering, baseboards, mastics, adhesives, roofing material, caulking, glazing, and siding. This category also contains wallboard and ceiling tile.
All materials were assessed related to their condition in one of the three categories: good (intact), fair
(damaged) or poor (significantly damaged) per Title 40 Code of Federal Regulations Part 763. Material with localized, significant damage was also assessed as poor.
3.3 Laboratory Analytical Methodology
Bulk samples were analyzed by Environmental Testing Laboratories, Inc. (ETL) using polarized-light microscopy (PLM) and dispersion staining (Method Reference: 40 CFR Part 763, Volume 47, No. 103, May
27, 1982 pg. 23376). This laboratory participates in the National Voluntary Laboratory Accreditation Program
(NVLAP #201028-0), a quality assurance program for PLM analysis, and is accredited by the National Institute of Standards and Technology (NIST) as well as accreditation requirements under 15 CFR Part 25.
Copies of the laboratory analytical report and corresponding chain-of-custody forms are included in
Appendix A. Positive sample results are reported in percent asbestos by volume of the sample and the type of asbestos material within the sample. Other common non-asbestos components may also be noted on the analytical reports.
3.4 Sampling Results
Bulk samples were collected from the site building and analyzed by polarized light microscopy (PLM), EPA
Method 600/R-93/116.
The following table provides a summary of accessible suspect and confirmed ACMs from the Site buildings:
Page | 5
Table 3-1 ACM Sampling Results
Sample ID/Material
Location of
Materials Material
Estimated Quantity
Asbestos Content
1-CC-A,B,C EA 1,3,4
Concrete Chip- Poured Concrete Pad/
Exterior Concrete
NA ND
2-EC-A,B,C EA 2,3,4
Exterior Caulk- Brown Window/
Door Frames/ Roofline
NA ND
3-EC-A,B,C EA 1
Exterior Caulk- Black, Perimeter of Fiberglass Window
NA ND
4-RM-A,B,C EA 5
Roofing Materials-
Black Asphalt Shingle
NA ND
5-GM-A,B,C FS 1,2,3
Ceramic Tile, Grout & Mortar-
6” Red Floor Tile
NA ND
6-GM-A,B,C FS 1
Ceramic Tile, Grout & Mortar-
12” Red Floor Tile
NA ND
7-IC-A,B,C FS 1,2,3
Interior Caulk-
Gray, Soft, Along Wood Trim
NA ND
8-BM-A,B,C FS 2,3 Brick Mortar- Glazed Block Wall NA ND
9-GM-A,B,C FS 2,3
Ceramic Tile, Grout & Mortar-
1” Multi-Colored Bathroom Counter
NA ND
10-IC-A,B,C FS 2,3
Interior Caulk- White, Perimeter of Toilets Sinks, & Urinals
NA ND
11-IC-A,B,C FS 5
Interior Caulk- Gray, Hard, Perimeter of Door Frames
NA ND
12-PI-A,B,C FS 5
Pipe Insulation-
Fiberglass Wrapped in Duct Tape
NA ND
EA=Exterior Area FS Functional Space NA=Not Applicable ND= None Detected
In the event additional suspect material is discovered during renovation activities, this material should be treated as presumed asbestos-containing material (PACM) in accordance with regulations 29 CFR
1926.1101 and 1910.1001 and other applicable state and local regulations and either sampled to confirm or nullify asbestos content or be treated as ACM and handled accordingly.
4. LEAD-CONTAINING PAINT SAMPLING
Atlas representative Mr. Andrew DeLodder conducted the lead-containing paint (LCP) sampling of the Toilet and Shower building on December 7 and 8, 2022. The sampling included physical sampling of paint coatings that were deemed representative of the predominant paint coatings observed.
Three (3) paint chip samples were collected and submitted to Accurate Analytical Testing Laboratory, 30105
Beverly Road, Romulus, Michigan for lead analysis. Bulk samples were analyzed using the Environmental
Protection Agency's Test Method SW 846-7420 and 3050B using Flame AAS to determine lead concentration in percent (%) by weight. Copies of the laboratory analytical report and corresponding chain-of-custody forms are included in Appendix B.
Page | 6
The following table provides a summary of the LCP sampling:
Table 4-1 Lead-Containing Paint Sampling Results
Sample ID Sample Location Color Lead
Content
1-LBP-Brown Exterior & Interior Paint Brown 0.0068
2- LBP-White Interior Paint White 0.0234
3- LBP-Beige Interior Paint Beige 0.0405
5. CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos-Containing Materials
The results of laboratory testing during the pre-renovation asbestos survey conducted at the property indicate that the following materials sampled were found to contain asbestos:
Sample ID/Material
Location of Materials
Material Estimated Quantity
Asbestos Content
None Contain Asbestos
If any additional materials are discovered during renovation/demolition activities, such materials must be assumed to contain asbestos until sampling and analysis proves otherwise.
5.2 Lead-Containing Paint
Three (3) representative samples of paint, taken from interior and exterior areas of the Toilet and Shower building, were collected and submitted for analysis by Flame AAS. The results of laboratory testing during the limited lead-containing paint sampling conducted at the property indicate that the three (3) samples contained levels of lead greater than the laboratory reporting limits.
The presence of lead-containing paint requires, under OSHA 1926.62 requirements, that the contractor performing renovation, surface preparation, and other activities that impact or potentially impact the lead-coated components, evaluate potential worker exposures to airborne lead. This evaluation can be based, for the specific activities denoted in 1926.62, on objective data obtained by the contractor on other, similar, worksites within the prior calendar year. In addition, lead-containing paint and lead-coated waste and construction debris must be evaluated and, on a case-by-case basis depending on this evaluation, quantitative analysis be performed on these waste steams to ensure compliance with EPA waste disposal regulations.
The presence of Lead-Containing Paint (LCP) and/or Lead-Based Paint (LBP) does not, in itself, trigger regulatory compliance actions. However, when these materials are disturbed, the requirements of OSHA
(1926.1101) and EPA may become operative. Appropriate actions in terms of removal methods, emissions control, worker protection, and waste disposal should be considered by the general contractor and applicable subcontractors while completing renovation activities.
Page | 7
6. ASSUMPTIONS AND LIMITATIONS
The results, findings, conclusions, and recommendations expressed in the report are based only on conditions that were noted during the NESHAP inspections conducted on December 7 and 8, 2022 performed by Atlas. Selection of sample locations and frequency of sampling were based on EPA Guidance documents, Atlas’s observations, and the assumption that building vintage and renovation history information presented to Atlas allowed the proper designation of homogenous materials for each building.
This document does not contain the elements necessary for an Abatement Work plan, and this document does not contain, nor should it take the place of technical specifications for ACM removal.
Our professional services have been performed, our findings obtained, and our conclusions and recommendations prepared in accordance with customary principles and practices in the fields of environmental science and engineering. This statement is in lieu of other statements either expressed or implied. This report does not warrant against changes to material from future operations or conditions, nor does it warrant against operations or conditions against present ACM material in locations not investigated.
The scope of services performed in execution of this evaluation may not be appropriate to satisfy the needs of other users, and use or re-use of this document or the findings, conclusions, or recommendations is at the risk of said user.
APPENDIX A
ASBESTOS LABORATORY REPORT
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive Romulus, Michigan 48174
(734) 955-6600
Fax: (734) 955-6604
To:
Attention:
Atlas - Novi
46555 Humboldt Dr. Suite 100
Novi, Michigan 48377
Project Location: Restroom Building; Cheboygan State Park
Client Project: 188BS22769
253265ETL Job:
Report Date: 12/16/2022
Robert Smith
Lab Sample Number Client Sample Number Sample Type Completed
1432922 Asbestos01-CC-A 12/16/2022
1432923 Asbestos01-CC-B 12/16/2022
1432924 Asbestos01-CC-C 12/16/2022
1432925 Asbestos02-EC-A 12/16/2022
1432926 Asbestos02-EC-B 12/16/2022
1432927 Asbestos02-EC-C 12/16/2022
1432928 Asbestos03-EC-A 12/16/2022
1432929 Asbestos03-EC-B 12/16/2022
1432930 Asbestos03-EC-C 12/16/2022
1432931 Asbestos04-RM-A 12/16/2022
1432932 Asbestos04-RM-B 12/16/2022
1432933 Asbestos04-RM-C 12/16/2022
1432934 Asbestos05-GM-A 12/16/2022
1432935 Asbestos05-GM-B 12/16/2022
1432936 Asbestos05-GM-C 12/16/2022
1432937 Asbestos06-GM-A 12/16/2022
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this information in error, please notify ETL immediately. Thank you.
Lab Sample Number Client Sample Number Sample Type Completed
1432938 Asbestos06-GM-B 12/16/2022
1432939 Asbestos06-GM-C 12/16/2022
1432940 Asbestos07-IC-A 12/16/2022
1432941 Asbestos07-IC-B 12/16/2022
1432942 Asbestos07-IC-C 12/16/2022
1432943 Asbestos08-BM-A 12/16/2022
1432944 Asbestos08-BM-B 12/16/2022
1432945 Asbestos08-BM-C 12/16/2022
1432946 Asbestos09-GM-A 12/16/2022
1432947 Asbestos09-GM-B 12/16/2022
1432948 Asbestos09-GM-C 12/16/2022
1432949 Asbestos10-IC-A 12/16/2022
1432950 Asbestos10-IC-B 12/16/2022
1432951 Asbestos10-IC-C 12/16/2022
1432952 Asbestos11-IC-A 12/16/2022
1432953 Asbestos11-IC-B 12/16/2022
1432954 Asbestos11-IC-C 12/16/2022
1432955 Asbestos12-PI-A 12/16/2022
1432956 Asbestos12-PI-B 12/16/2022
1432957 Asbestos12-PI-C 12/16/2022
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
Lab Sample Number Client Sample Number Sample Type Completed
Reviewed by:
Summary
Sample Layer MasticMethod
PLM 57Emily Nowacki
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
Certificate of Analysis
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Restroom Building; Cheboygan State Park
ETL Job :
Client Project :
253265
188BS22769
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432922
01-CC-A
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432923
01-CC-B
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432924
01-CC-C
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432925
02-EC-A
PLM 98% OtherPLM 2% CelluloseBrownExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432926
02-EC-B
PLM 98% OtherPLM 2% CelluloseBrownExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432927
02-EC-C
PLM 98% OtherPLM 2% CelluloseBrownExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Restroom Building; Cheboygan State Park
ETL Job :
Client Project :
253265
188BS22769
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432928
03-EC-A
PLM 99% OtherPLM 1% CelluloseBlackExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432929
03-EC-B
PLM 99% OtherPLM 1% CelluloseBlackExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432930
03-EC-C
PLM 99% OtherPLM 1% CelluloseBlackExterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432931
04-RM-A
PLM 98% OtherPLM 2% CelluloseBlackRoofing Materials- Asphalt
Shingle Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432932
04-RM-B
PLM 98% OtherPLM 2% CelluloseBlackRoofing Materials- Asphalt
Shingle Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432933
04-RM-C
PLM 98% OtherPLM 2% CelluloseBlackRoofing Materials- Asphalt
Shingle Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Restroom Building; Cheboygan State Park
ETL Job :
Client Project :
253265
188BS22769
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432934
05-GM-A
PLM 98% OtherPLM 2% CelluloseRedCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432934
05-GM-A
PLM 98% OtherPLM 2% CelluloseRedGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432934
05-GM-A
PLM 97% OtherPLM 3% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432935
05-GM-B
PLM 98% OtherPLM 2% CelluloseRedCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432935
05-GM-B
PLM 98% OtherPLM 2% CelluloseRedGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432935
05-GM-B
PLM 97% OtherPLM 3% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Restroom Building; Cheboygan State Park
ETL Job :
Client Project :
253265
188BS22769
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432936
05-GM-C
PLM 98% OtherPLM 2% CelluloseRedCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432936
05-GM-C
PLM 98% OtherPLM 2% CelluloseRedGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432936
05-GM-C
PLM 97% OtherPLM 3% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432937
06-GM-A
PLM 98% OtherPLM 2% CelluloseGrayCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432937
06-GM-A
PLM 98% OtherPLM 2% CelluloseGrayGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432937
06-GM-A
PLM 98% OtherPLM 2% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Restroom Building; Cheboygan State Park
ETL Job :
Client Project :
253265
188BS22769
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432938
06-GM-B
PLM 98% OtherPLM 2% CelluloseGrayCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432938
06-GM-B
PLM 98% OtherPLM 2% CelluloseGrayGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432938
06-GM-B
PLM 98% OtherPLM 2% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432939
06-GM-C
PLM 98% OtherPLM 2% CelluloseGrayCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432939
06-GM-C
PLM 98% OtherPLM 2% CelluloseGrayGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432939
06-GM-C
PLM 98% OtherPLM 2% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Restroom Building; Cheboygan State Park
ETL Job :
Client Project :
253265
188BS22769
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432940
07-IC-A
PLM 98% OtherPLM 2% CelluloseGrayInterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432941
07-IC-B
PLM 98% OtherPLM 2% CelluloseGrayInterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432942
07-IC-C
PLM 98% OtherPLM 2% CelluloseGrayInterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432943
08-BM-A
PLM 97% OtherPLM 3% CelluloseGrayBrick Mortar
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432944
08-BM-B
PLM 97% OtherPLM 3% CelluloseGrayBrick Mortar
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432945
08-BM-C
PLM 97% OtherPLM 3% CelluloseGrayBrick Mortar
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Restroom Building; Cheboygan State Park
ETL Job :
Client Project :
253265
188BS22769
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432946
09-GM-A
PLM 98% OtherPLM 2% CelluloseBrownCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432946
09-GM-A
PLM 98% OtherPLM 2% CelluloseRedGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432946
09-GM-A
PLM 98% OtherPLM 2% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432947
09-GM-B
PLM 98% OtherPLM 2% CelluloseBrownCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432947
09-GM-B
PLM 98% OtherPLM 2% CelluloseRedGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432947
09-GM-B
PLM 98% OtherPLM 2% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Restroom Building; Cheboygan State Park
ETL Job :
Client Project :
253265
188BS22769
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432948
09-GM-C
PLM 98% OtherPLM 2% CelluloseBrownCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432948
09-GM-C
PLM 98% OtherPLM 2% CelluloseRedGrout
Non-Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432948
09-GM-C
PLM 98% OtherPLM 2% CelluloseGrayMortar
Non-Fibrous
Homogenous Layer-3 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432949
10-IC-A
PLM 99% OtherPLM 1% CelluloseWhiteInterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432950
10-IC-B
PLM 99% OtherPLM 1% CelluloseWhiteInterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432951
10-IC-C
PLM 99% OtherPLM 1% CelluloseWhiteInterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Restroom Building; Cheboygan State Park
ETL Job :
Client Project :
253265
188BS22769
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432952
11-IC-A
PLM 98% OtherPLM 2% CelluloseGrayInterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432953
11-IC-B
PLM 98% OtherPLM 2% CelluloseGrayInterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432954
11-IC-C
PLM 98% OtherPLM 2% CelluloseGrayInterior Caulk
Non-Fibrous
Homogenous Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432955
12-PI-A
PLM 8% OtherPLM 90% Fiberglass
PLM 2% Cellulose
YellowPipe Insulation
Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432955
12-PI-A
PLM 25% OtherPLM 75% CelluloseGrayDuct Tape
Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Restroom Building; Cheboygan State Park
ETL Job :
Client Project :
253265
188BS22769
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/08/2022
12/15/2022
Date Collected :
Date Received :
PLM None Detected 1432956
12-PI-B
PLM 8% OtherPLM 90% Fiberglass
PLM 2% Cellulose
YellowPipe Insulation
Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432956
12-PI-B
PLM 25% OtherPLM 75% CelluloseGrayDuct Tape
Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432957
12-PI-C
PLM 8% OtherPLM 90% Fiberglass
PLM 2% Cellulose
YellowPipe Insulation
Fibrous
Homogenous Layer-1 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
PLM None Detected 1432957
12-PI-C
PLM 25% OtherPLM 75% CelluloseGrayDuct Tape
Fibrous
Homogenous Layer-2 Analyst: Dave Cousino
Date Analyzed : 12/16/2022
Lab Supervisor/Other Signatory
Dave Cousino
Analyst:
400 Point Count Results by EPA 600/R-93/116 PLM (denoted by "PC")
Item 198.1: PLM Methods for Identifying and Quantitating Asbestos in Bulk Samples
Item 198.6: PLM Methods for Identifying and Quantitating Asbestos in Non-Friable Organically Bound Bulk Samples
EPA 600/R-93/116: Method for Determination of Asbestos in Bulk Building Materials
EPA 600/M4-82-020: Interim Method for Determination of Asbestos in Bulk Insulation Samples
A % Asbestos result of "Trace" indicates that the analyzed material was found to contain less than 1% asbestos and would not be considered an Asbestos Containing Material (ACM).
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
APPENDIX B
LEAD-CONTAINING PAINT LABORATORY REPORT
Certificate of Analysis: Lead In Paint by EPA SW-846 Method 7000B/3050B*
Client Project :
868388
12/22/2022
12/23/2022
Date Reported :
Date Analyzed :
Date Received :
AAT Project :
Phone :
Email :
Fax : 248-669-5147 dawn.lecesne@oneatlas.com
248-669-5140
Dawn LeCesne
Atlas Technical Consultants
Attn :
Client :
4490 BEACH ROAD CHEBOYGAN MI 49721Project Location :
188BS522769
Novi, MI 48377
46555 Humboldt Dr.
30105 Beverly Road
Romulus, MI 48174
Ph: 734-629-8161; Fax: 734-629-8431
Sampling Date : 12/07/2022
12/23/2022
Lab Sample ID Result Lead
(% by weight) PPMSample DescriptionClient Code
Calculated R L
(% by weight)
1-LBP-BROWN EXT AND INT BROWN PAINT8066981 68 0.0068 0.0026
2-LBP-WHITE INT WHITE PAINT8066982 234 0.0234 0.0013
3-LBP-BEIGE INT BEIGE PAINT8066983 405 0.0405 0.0052
Analyst Signature
Tom Hamlin
868388 AAT Project:Date Printed: 12/23/2022 12:00PM
ND = Not Detected, N/A = Not Available, RL = Reporting Limit, Analytical Reporting Limit is 5 ug/sample. For true values assume (2) significant figures. The method, batch, and sample Quality Control are acceptable unless otherwise stated. AAT internal SOP S218. The laboratory operates in accord with ISO 17025 guidelines and holds limited scopes of accreditation under AIHA-LAP and NY State DOH ELAP programs. These results are submitted pursuant to AAT, LLC current terms and conditions of sale, including the company's standard warranty and limitation of liability provisions. Analytical results relate to the samples as received by the lab. Results in mg/cm2 are calculated based on sample area dimensions supplied by the client.AAT will not assume any liability or responsibility for the manner in which the results are used or interpreted. Reproduction of this document other than in its entirety is not authorized by AAT, LLC. AAT does not blank correct reported values. Sample data apply only to items analyzed. Current EPA/HUD Interim Standard for lead in paint samples is: 5000 PPM (parts per million) or ug/g which is equivalent to 0.5% by weight. EPA definition of lead-based paint: 1.0 mg/cm2. New York City Regulatory Limits: 0.25% by weight or 0.5 mg/cm2 for investigations for a child. MD and Philadelphia definition of lead-based paint: 0.7 mg/cm2. Note: Samples are stored for 15 days following report date. *=
Validated modified method
AIHA LAP- Lab ID #100986, NY State DOH ELAP -Lab ID #11864, State of Ohio- Lab ID # 10042
Atlas Technical ConsultantsTo :
Attn :
Phone :
AAT Project :
Client Project :
Date Reported :
Project Location :
Email :Dawn LeCesne
248-669-5140 dawn.lecesne@oneatlas.com
868388
188BS522769
4490 BEACH ROAD CHEBOYGAN MI 49721
46555 Humboldt Dr.
Novi, MI 48377
30105 Beverly Road
Romulus, MI 48174
Ph: 734-629-8161; Fax: 734-629-8431
12/23/2022
Sample CompletedAnalysis RequestedClient Code Analyst
8066981 12/23/2022Lead Paint1-LBP-BROWN Tom Hamlin
8066982 12/23/2022Lead Paint2-LBP-WHITE Tom Hamlin
8066983 12/23/2022Lead Paint3-LBP-BEIGE Tom Hamlin
Quality Assurance Coordinator
Reviewed By Elyse Bidle
868388 AAT Project:Date Printed: 12/23/2022 12:00PM
This report is intended for use solely by the individual or entity to which it is addressed. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this information in error, please notify AAT immediately. Thank you.
NY State DOH ELAP -Lab ID #11864, Michigan State Lab # 9996