Geotechnical Investigation Report Summary
This is a Report of Geotechnical Investigation prepared by Environmental and Geotechnical Specialists, Inc. for Comprehensive Engineering Services, Inc. and the Florida Department of Transportation (FDOT) regarding proposed mast arm signal foundations at the intersection of State Road 20 and County Road 83A in Walton County, Florida. The investigation included the installation of two Standard Penetration Test soil borings to depths of 30 feet below ground surface, groundwater level measurements, laboratory testing of soil samples for classification and index properties, and development of geotechnical design parameters and recommendations. The site is located in Freeport with relatively flat topography at elevations of approximately 64 to 66 feet (NAVD 88). Two mast arm signals are proposed: Pole 1 located north of the T-intersection and Pole 2 located in the southeast corner. The subsurface investigation was conducted in December 2023, with soil boring WMA-1 and WMA-2 installed at depths of 30 feet.
The investigation revealed subsurface conditions consisting primarily of sand, with loose to medium dense sand in the upper 14 to 18 feet and medium dense to dense sand below. Groundwater was encountered at depths of 13 to 14 feet below ground surface. EGS recommends drilled shaft foundations for both mast arm signals, as spread footing foundations would require large footings impractical given utility proximity. For Pole 1, the standard FDOT Foundation (Drilled Shaft) in Standard Plans Index 649-030 is appropriate when the shaft is tipped below elevation 42 feet. For Pole 2, the standard foundation is not appropriate due to loose sands encountered, requiring custom design analysis for foundation sizing. EGS recommends groundwater be assumed at ground surface for design purposes and notes that subsurface conditions do not meet requirements for the Dry Method Shaft Construction due to loose sand and groundwater presence, necessitating alternative construction methods. The Report of Soil Borings plan sheets have been provided for inclusion in project plans.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
January 2024 61-78-23-01
REPORT OF
GEOTECHNICAL INVESTIGATION
MAST ARM FOUNDATIONS
SR 20 AT CR 83A (WEST BAY LOOP)
WALTON COUNTY, FLORIDA
FPID: 220918-2-52-29
Prepared For:
COMPREHENSIVE ENGINEERING SERVICES, INC.
201 SOUTH ORANGE AVENUE
SUITE 1300
ORLANDO, FLORIDA 32801
Prepared By:
ENVIRONMENTAL AND GEOTECHNICAL SPECIALISTS, INC.
3676 HARTSFIELD ROAD
TALLAHASSEE, FLORIDA 32303
(850) 386-1253
ENVIRONMENTAL AND GEOTECHNICAL SPECIALISTS, INC.
TALLAHASSEE / JACKSONVILLE / GAINESVILLE / OCALA / INVERNESS / FORT MYERS / WEST PALM BEACH
January 19, 2024
EGS File Number: 61-78-23-01
Comprehensive Engineering Services, Inc.
201 South Orange Avenue Suite 1300 Orlando, Florida 32801
ATTN: Arthur (Art) Shipley, P.E.
Vice President
SUBJECT: Report of Geotechnical Investigation Mast Arm Foundations
SR 20 at CR 83A (West Bay Loop) Walton County, Florida
FPID: 220918-2-52-29
Dear Art:
Environmental and Geotechnical Specialists, Inc. (EGS) has completed the Geotechnical Investigation, as authorized by Comprehensive Engineering Services, Inc. (CES) and the Florida Department of Transportation (FDOT), for the proposed mast arm signal foundations at the intersection of State Road (SR) 20 and County Road (CR) 83A in Walton County, Florida. The proposed mast arm signal foundations are associated with signalization improvements being made at the intersection. Presented in this Report is a summary of the geotechnical investigation, subsurface materials encountered, geotechnical design recommendations, and construction considerations.
SCOPE OF SERVICES
The Scope of Services authorized for this investigation consisted of the following:
• Installation of 2 Standard Penetration Test (SPT) soil borings to depths of 30 feet below the ground surface at the proposed mast arm pole locations;
• Measuring groundwater levels in the installed boreholes;
• Laboratory testing of representative soil samples collected from the soil borings for classification purposes and to evaluate soil index properties;
• Evaluation of the field and laboratory data for development of geotechnical design parameters and recommendations; and,
• Preparation of this Report.
Comprehensive Engineering Services, Inc.
Report of Geotechnical Investigation – Mast Arm Foundations SR 20 at CR 83A (West Bay Loop)
SITE LOCATION AND CONDITIONS
The project site is located at the intersection of SR 20 and CR 83A in Freeport, Walton County, Florida. A Project Location Map has been provided as Figure 1.
The United States Geological Survey (USGS) topographic contours have been overlain on an aerial photography in the Aerial View Map, provided as Figure 2. As can be seen in this Figure, the topography at the intersection is relatively flat with an existing ground surface elevation (EL) of approximately EL 64 to 66 feet at the soil boring locations, as referenced to the North American Vertical Datum of 1988 (NAVD 88).
The intersection is not currently signalized. The site setting is general rural with a residential neighborhood located to the south of the intersection. Overhead and/or buried utilities were observed in proximity to the proposed pole locations.
Two (2) mast arm signals are proposed for the intersection with Pole 1 located to the north of the T-intersection, and Pole 2 located in the southeast corner of the intersection.
SUBSURFACE INVESTIGATION
The subsurface investigation outlined in this Report was conducted in December of 2023.
Dylan Godden, E.I. served as the Staff Geotechnical Engineer. Craig Dunkelberger, P.E.
served as the Geotechnical Engineer of Record. Chandra Samakur, P.E. served as the Senior Geotechnical Engineer providing project oversight and Quality Assurance / Quality Control (QA/QC).
EGS installed 2 SPT soil borings labeled WMA-1 and WMA-2 to depths of 30 feet below the existing ground surface. The soil borings were installed as close as practical to the proposed mast arm foundation locations and labeled to correspond with the assigned pole numbers shown in the Signalization Plan, dated December 2023, provided by CES (e.g., Soil Boring WMA-1 was installed for Pole 1).
A summary of the soil boring labels, depths, and approximate locations are provided in TABLE 1 with a plan view of the soil boring locations shown in Figure 2 and on the Report of Soil Borings plan sheet provided in APPENDIX A.
In order to evaluate the relative strength and uniformity of the subsurface materials, SPT testing with split-spoon sampling was conducted on maximum vertical intervals of 2½ feet to the boring termination depth. To reduce potential impacts to mismarked or unmarked utilities, the soil borings were hand augered within the top 5½ feet coupled with static hand Cone Penetration Index (CPI) tests conducted on 1-foot intervals.
To facilitate uniformity of the subsurface data, CPI “C” values were converted to equivalent SPT “N” values using the correlation N=C/4. SPT sampling was performed with an automatic hammer and in accordance with ASTM D1586.
SR 20 at CR 83A (West Bay Loop)
Soil samples were collected and visually classified in the field by EGS personnel, then placed in sealed bags and transported to the EGS laboratory for classification testing.
The laboratory testing included the determination of water content, organic content, and grain-size distribution. The subsoils have been classified with respect to the Unified Soil Classification System (USCS). Select laboratory test results have been provided in the Report of Soil Borings plan sheets provided in APPENDIX A. The Soil Boring Logs and Soil Classification Data sheets are provided in APPENDICES B and C, respectively.
SUBSURFACE CONDITIONS
Existing Soils - The materials encountered in the soil borings drilled for this investigation consisted of mostly Sand. Within the upper 14 to 18 feet, the Sand was generally in a Loose condition. Below this, the Sand was generally Medium Dense to Dense to the maximum drilled depth of 30 feet.
“Generalized” Design Soil Profiles are provided as Figures 3A and 3B of this report.
Groundwater - Groundwater was encountered between depths of about 13 to 14 feet below the ground surface. Groundwater data, including Estimated “Normal” Seasonal High Groundwater levels, is provided in TABLE 1 and presented in the Report of Soil Borings plan sheets provided in APPENDIX A.
It should be recognized that the groundwater data reflects limited measurements.
Fluctuations in groundwater levels should be anticipated throughout the year in response to rainfall, surrounding development, and changes to drainage from development.
GEOTECHNICAL DESIGN RECOMMENDATIONS
A drilled shaft is the most common foundation type used by the FDOT to support mast arm signals. Based on the subsurface conditions encountered, a spread footing foundation could be considered; however, EGS believes the large footing size required to resist the design loads, and proximity of existing utilities makes this foundation option impractical. EGS recommends drilled shaft foundations be used to support the mast arm signals.
Groundwater - EGS recommends the groundwater level be assumed at the ground surface for design purposes.
SR 20 at CR 83A (West Bay Loop)
Geotechnical Design Parameters - EGS evaluated the subsurface conditions and determined that the Standard Foundation (Drilled Shaft) in FDOT Standard Plans Index 649-030 is appropriate at the location of Pole 1 for a drilled shaft tipped below a depth of 23 feet, or an elevation of about EL 42 feet (NAVD ’88).
At the location of Pole 2, the Standard Foundation (Drilled Shaft) in FDOT Standard Plans Index 649-030 is NOT appropriate due to the loose sands encountered. EGS understands that since the Standard Foundation is not appropriate a design analysis will be performed for sizing of the foundation.
To aid in the design analysis of the drilled shaft foundations, EGS has provided “Generalized” Design Soil Profiles as Figures 3A and 3B. Geotechnical Design Parameters for individual soil layers are provided in TABLES 2A and 2B, with average Combined Geotechnical Design Parameters provided in TABLES 3A and 3B for various shaft tip depths.
Plans Preparation - EGS recommends the Report of Soil Borings plan sheets, provided in APPENDIX A, be included in the Plans. An Electronic copy of the plan sheets has been provided with this Report.
Due to the presence of Loose Sand and groundwater, “cave-off” of the foundation excavations is likely. These soil conditions are not considered to be favorable for use of the Dry Construction Method; therefore, EGS recommends the following note be added to the Plans:
• The subsurface conditions do not meet the requirements for use of Dry Method Shaft Construction.
SR 20 at CR 83A (West Bay Loop)
CLOSURE
The data and results presented in this Report of Geotechnical Investigation are intended for use by Comprehensive Engineering Services, Inc. and the Florida Department of Transportation for the proposed mast arm foundations at the intersection of SR 20 and CR 83A in Walton County, Florida as identified herein. This data may not be used without the expressed written consent of Comprehensive Engineering Services, Inc. and the Florida Department of Transportation. This Report is not intended for any other use and will likely not be applicable. This Report shall not be reproduced, except in full, without the written approval of Environmental and Geotechnical Specialists, Inc. The data and recommendations presented in this Report are based on the borings made at the specific locations and depths noted. Subsurface conditions at other locations may vary significantly from those presented herein. Should data become available which is different from the data presented herein, Environmental and Geotechnical Specialists, Inc. requests the opportunity to review the data and make any modifications to the design recommendations that may be appropriate.
If you have any questions concerning the information contained in this Report, please do not hesitate to call me at (850) 536-8359.
Sincerely, Environmental & Geotechnical Specialists, Inc.
Certificate of Authorization: 6222
Craig E. Dunkelberger, P.E.
Chief Geotechnical Engineer FL P.E. No.: 49932
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY
CRAIG E. DUNKELBERGER ON THE DATE ADJACENT TO THE SEAL.
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIED.
TABLES
BORING BORING GROUND NORTHING EASTING
LABEL DEPTH 1 SURFACE
ELEVATION 2
DEPTH 1 ELEVATION 2 DEPTH 1 ELEVATION 2
WMA-1 30.0 65 552832 1442904 14.0 51 11 54
WMA-2 30.0 64 552677 1442922 13.0 51 10 54
NOTES: 1. DEPTHS MEASURED BELOW EXISTING GROUND SURFACE.
NOTES: 2. ELEVATIONS ARE APPROXIMATE AND WERE ESTIMATED USING THE TOPOGRAPHY SHOWN ON FIGURE 2 (DATUM: NAVD '88)
TABLE 1
SOIL BORING LOCATION AND GROUNDWATER DATA
MAST ARM FOUNDATIONS
SR 20 AT CR 83A (WEST BAY LOOP)
WALTON COUNTY, FLORIDA
(FEET) (FEET)(FEET) (FEET)
MEASURED GROUNDWATER
ESTIMATED "NORMAL"
SEASONAL HIGH
GROUNDWATER
(FEET) (FEET)
APPROXIMATE DESIGN SPT ANGLE OF TOTAL EFFECTIVE UNDRAINED SOIL
ELEVATION 1 SPT 'N' INTERNAL SOIL UNIT SOIL UNIT SHEAR DESCRIPTION
'N60' VALUE 3 FRICTION WEIGHT WEIGHT STRENGTH
VALUE 2
φ γ γ' c
(FEET) (DEGREES) (LB/FT3) (LB/FT3) (LB/FT2)
65 to 56 7 6 28 115 53 0
LOOSE TO MEDIUM DENSE
FINE SAND
(SP-SM)
56 to 48 9 7 30 115 53 0
LOOSE TO MEDIUM DENSE
SILTY FINE SAND
(SM)
48 to 35 25 20 32 115 53 0
MEDIUM DENSE TO DENSE
FINE SAND
(SP, SP-SM)
NOTES: 1. ESTIMATED USING USGS TOPOGRAPHIC MAPS.
NOTES: 2. SPT 'N60' VALUES ADJUSTED FOR HAMMER EFFICIENCY.
NOTES: 3. FIELD SPT 'N' VALUES.
NOTES: 4. DESIGN SUBSURFACE PROFILE SHOWN IN FIGURE 3A.
TABLE 2A
GEOTECHNICAL DESIGN PARAMETERS - INDIVIDUAL LAYERS
MAST ARM FOUNDATIONS
SR 20 AT CR 83A (WEST BAY LOOP)
POLE 1 (SOIL BORING WMA-1)
ELEVATION 1 SPT 'N' INTERNAL SOIL UNIT SOIL UNIT SHEAR DESCRIPTION
'N60' VALUE 3 FRICTION WEIGHT WEIGHT STRENGTH
VALUE 2
φ γ γ' c
(FEET) (DEGREES) (LB/FT3) (LB/FT3) (LB/FT2)
64 to 60 9 7 29 115 53 0
LOOSE
SILTY FINE SAND
(SM)
60 to 51 7 6 28 115 53 0
LOOSE
FINE SAND
(SP-SM)
51 to 44 15 12 31 115 53 0
MEDIUM DENSE
FINE TO MEDIUM SAND
(SP-SM)
44 to 34 10 8 30 115 53 0
MEDIUM DENSE
FINE SAND
(SP-SM)
NOTES: 1. ESTIMATED USING USGS TOPOGRAPHIC MAPS.
NOTES: 2. SPT 'N60' VALUES ADJUSTED FOR HAMMER EFFICIENCY.
NOTES: 3. FIELD SPT 'N' VALUES.
NOTES: 4. DESIGN SUBSURFACE PROFILE SHOWN IN FIGURE 3B.
TABLE 2B
GEOTECHNICAL DESIGN PARAMETERS - INDIVIDUAL LAYERS
MAST ARM FOUNDATIONS
SR 20 AT CR 83A (WEST BAY LOOP)
POLE 2 (SOIL BORING WMA-2)
ELEVATION SPT 'N' INTERNAL SOIL UNIT SOIL UNIT SHEAR DESCRIPTION
OF SHAFT TIP 1,2 'N60' VALUE 4 FRICTION WEIGHT WEIGHT STRENGTH
VALUE 3
φ γ γ' c
(FEET) (DEGREES) (LB/FT3) (LB/FT3) (LB/FT2)
65 to 56 7 6 - - 5 - - 5 - - 5 - - 5
LOOSE TO MEDIUM DENSE
FINE SAND
(SP-SM)
56 to 48 7 6 28 115 53 0
LOOSE TO MEDIUM DENSE
SILTY FINE SAND
(SM)
48 to 42 12 10 30 115 53 0
42 to 35 15 12 31 115 53 0
NOTES: 1. ELEVATIONS ARE APPROXIMATE AND WERE DETERMINED USING GOOGLE EARTH.
NOTES: 2. COMBINED SOIL LAYER PARAMETERS SHOWN ARE AVERAGE PARAMETER VALUES OF ALL SOILS ABOVE THE SHAFT TIP. THESE COMBINED SOIL LAYER NOTES: 2. PARAMETERS ARE INTENDED TO BE APPLIED OVER THE ENTIRETY OF THE EMBEDMENT DEPTH.
NOTES: 3. SPT 'N60' VALUES ADJUSTED FOR HAMMER EFFICIENCY.
NOTES: 4. FIELD SPT 'N' VALUES.
NOTES: 5. MINIMUM SHAFT EMBEDMENT DEPTH OF 9 FEET IS ASSUMED; THEREFORE, NO COMBINED PARAMETERS HAVE BEEN PROVIDED FOR THESE LAYERS.
NOTES: 6. DESIGN SUBSURFACE PROFILE SHOWN IN FIGURE 3A.
TABLE 3A
GEOTECHNICAL DESIGN PARAMETERS - COMBINED LAYERS
MAST ARM FOUNDATIONS
SR 20 AT CR 83A (WEST BAY LOOP)
WALTON COUNTY, FLORIDA
POLE 1 (SOIL BORING WMA-1)
SOIL PARAMETERS MEET MINIMUM CRITERIA PER STANDARD PLAN INDEX 649-030 FOR SHAFTS TIPPED BELOW ELEVATION 42 FEET.
MEDIUM DENSE TO DENSE
FINE SAND
(SP, SP-SM)
ELEVATION SPT 'N' INTERNAL SOIL UNIT SOIL UNIT SHEAR DESCRIPTION
OF SHAFT TIP 1,2 'N60' VALUE 4 FRICTION WEIGHT WEIGHT STRENGTH
VALUE 3
φ γ γ' c
(FEET) (DEGREES) (LB/FT3) (LB/FT3) (LB/FT2)
64 to 60 9 7 - - 5 - - 5 - - 5 - - 5
LOOSE
SILTY FINE SAND
(SP-SM)
60 to 51 7 6 - - 5 - - 5 - - 5 - - 5
LOOSE
FINE SAND
(SP-SM)
51 to 44 10 8 30 115 53 0
MEDIUM DENSE
FINE TO MEDIUM SAND
(SP-SM)
44 to 39 10 8 30 115 53 0
39 to 34 10 8 30 115 53 0
NOTES: 1. ELEVATIONS ARE APPROXIMATE AND WERE DETERMINED USING GOOGLE EARTH.
NOTES: 2. COMBINED SOIL LAYER PARAMETERS SHOWN ARE AVERAGE PARAMETER VALUES OF ALL SOILS ABOVE THE SHAFT TIP. THESE COMBINED SOIL LAYER NOTES: 2. PARAMETERS ARE INTENDED TO BE APPLIED OVER THE ENTIRETY OF THE EMBEDMENT DEPTH.
NOTES: 3. SPT 'N60' VALUES ADJUSTED FOR HAMMER EFFICIENCY.
NOTES: 4. FIELD SPT 'N' VALUES.
NOTES: 5. MINIMUM SHAFT EMBEDMENT DEPTH OF 13 FEET IS ASSUMED; THEREFORE, NO COMBINED PARAMETERS HAVE BEEN PROVIDED FOR THESE LAYERS.
NOTES: 6. DESIGN SUBSURFACE PROFILE SHOWN IN FIGURE 3B.
TABLE 3B
GEOTECHNICAL DESIGN PARAMETERS - COMBINED LAYERS
MAST ARM FOUNDATIONS
SR 20 AT CR 83A (WEST BAY LOOP)
WALTON COUNTY, FLORIDA
POLE 2 (SOIL BORING WMA-2)
MEDIUM DENSE
FINE SAND
(SP-SM)
SOIL PARAMETERS DO NOT MEET MINIMUM CRITERIA PER STANDARD PLAN INDEX 649-030 FOR SHAFTS; THEREFORE, AN ANALYSIS IS REQUIRED.
FIGURES
DRAWN:
D. GODDEN, E.I.
CHECKED:
A. CRAIG, E.I.
ENVIRONMENTAL AND GEOTECHNICAL
SPECIALISTS, INC.
3676 HARTSFIELD ROAD
TALLAHASSEE, FLORIDA 32303
OFFICE #: (850) 386-1253
TITLE:
PROJECT LOCATION MAP
MAST ARM FOUNDATIONS
SR 20 AT CR 83A (WEST BAY ROAD)
WALTON COUNTY, FLORIDA
ENGINEER:
C. DUNKELBERGER, P.E.
CLIENT:
COMPREHENSIVE ENGINEERING SERVICES, INC.
PROJ. NO.:
61-78-23-01
SCALE:
NOT TO SCALE
DATE:
JANUARY 2024
FIGURE NO.:
PROJECT LOCATION
NOT TO SCALE
C. DUNKELBERGER, P.E.
A
A
WMA-2
WMA-1
DRAWN:
ENGINEER:
CLIENT:
CHECKED:
PROJ. NO.: SCALE: DATE: FIGURE NO.:
TITLE:
ENVIRONMENTAL AND GEOTECHNICAL
SPECIALISTS, INC.
3676 HARTSFIELD ROAD
TALLAHASSEE, FLORIDA 32303
OFFICE #: (850) 386-1253
JANUARY 2024 2
AERIAL VIEW MAP
MAST ARM FOUNDATIONS
SR 20 AT CR 83A (WEST BAY LOOP)
WALTON COUNTY, FLORIDA
A. CRAIG, E.I.D. GODDEN, E.I.
COMPREHENSIVE ENGINEERING SERVICES, INC.
61-78-23-01
0 60
Feet
Legend A Approximate Soil Boring Location
USGS Topographic Contours (2-feet)
AS SHOWN
SR 20
CO
UN
TY
HI
GH
WA
Y 8 3A
W
P
P R
O X I
M A
T E
E
L E
V A
T I O
N
(F
E E
T
N
V D
'8
) A
P P
R O
X I
M A
T E
E
L E
V A
T I O
N
(F
E E
V D
'8
"GENERALIZED" DESIGN SOIL PROFILE
NOTES
2.
1.
PENETRATION.
PENETRATION TEST (SPT) N-VALUES FOR 12 INCH
NUMBERS LEFT OF BORING INDICATE STANDARD
GEOTECHNICAL DESIGN PARAMETERS.
SEE TABLE 2A AND 3A FOR ADDITIONAL
ϒ'=53 PCF
ϕ=28°
N =7
N=6
ϒ'=53 PCF
ϕ=32°
ϒ'=53 PCF
ϕ=29°
N =25
N=20
(SP-SM)
FINE SAND
LOOSE TO MEDIUM DENSE
(SM)
SILTY FINE SAND
LOOSE TO MEDIUM DENSE
N =9
N=7
DATE:
CHECKED:
SCALE:
61-78-23-01
DRAWN:
ENGINEER:
CLIENT:
PROJ. NO.:
AS SHOWN 3A
FIGURE:
SPECIALISTS, INC.
ENVIRONMENTAL AND GEOTECHNICAL
TITLE:
JANUARY 2024
OFFICE #: (850) 386-1253
TALLAHASSEE, FLORIDA 32303
3676 HARTSFIELD ROAD
D. GODDEN, E.I.
C. DUNKELBERGER, P.E.
K. SWEENEY, P.E.
CES, INC.
WALTON COUNTY, FLORIDA
SR 20 AT CR 83A (WEST BAY LOOP)
MAST ARM FOUNDATIONS
"GENERALIZED" DESIGN SOIL PROFILE
(SP, SP-SM)
FINE SAND
MEDIUM DENSE TO DENSE
ANGLE OF INTERNAL FRICTION (DEGREES)
FIELD SPT "N" VALUE
EXISTING GROUND SURFACE
N ϕ
N
FOR HAMMER EFFICIENCY)
DESIGN SPT "N" VALUE (CORRECTED
DESIGN GROUNDWATER LEVEL
ϒ' EFFECTIVE UNIT WEIGHT (PCF)
POLE 1 (SOIL BORING WMA-1)
N
*7
*7
*4
*4
*5
ELEVATION 65 FEET
LEGEND
P
P R
O X I
M A
T E
E
L E
V A
T I O
N
(F
E E
V D
'8
) A
P P
R O
X I
M A
T E
E
L E
V A
T I O
N
(F
E E
V D
'8
"GENERALIZED" DESIGN SOIL PROFILE
ϒ'=53 PCF
ϕ=28°
ϒ'=53 PCF
ϕ=31°
ϒ'=53 PCF
ϕ=30°
N =10
N=8
NOTES
2.
1.
PENETRATION.
PENETRATION TEST (SPT) N-VALUES FOR 12 INCH
NUMBERS LEFT OF BORING INDICATE STANDARD
GEOTECHNICAL DESIGN PARAMETERS.
SEE TABLE 2B AND 3B FOR ADDITIONAL
(SP-SM)
FINE SAND
MEDIUM DENSE
ϒ'=53 PCF
ϕ=29°
DATE:
CHECKED:
SCALE:
61-78-23-01
DRAWN:
ENGINEER:
CLIENT:
PROJ. NO.:
AS SHOWN 3B
FIGURE:
SPECIALISTS, INC.
ENVIRONMENTAL AND GEOTECHNICAL
TITLE:
JANUARY 2024
OFFICE #: (850) 386-1253
TALLAHASSEE, FLORIDA 32303
3676 HARTSFIELD ROAD
D. GODDEN, E.I.
C. DUNKELBERGER, P.E.
K. SWEENEY, P.E.
CES, INC.
WALTON COUNTY, FLORIDA
SR 20 AT CR 83A (WEST BAY LOOP)
MAST ARM FOUNDATIONS
"GENERALIZED" DESIGN SOIL PROFILE
N =9
N=7
N =7
N=6
N =15
N=12
(SP-SM)
FINE TO MEDIUM SAND
MEDIUM DENSE
(SP-SM)
FINE SAND
LOOSE
(SM)
SILTY FINE SAND
LOOSE
ANGLE OF INTERNAL FRICTION (DEGREES)
FIELD SPT "N" VALUE
EXISTING GROUND SURFACE
N ϕ
N
FOR HAMMER EFFICIENCY)
DESIGN SPT "N" VALUE (CORRECTED
DESIGN GROUNDWATER LEVEL
ϒ' EFFECTIVE UNIT WEIGHT (PCF)
POLE 2 (SOIL BORING WMA-2)
N
*7
*5
*7
*7
*5
ELEVATION 64 FEET
LEGEND
APPENDIX A
GEOTECHNICAL PLAN SHEET
SOIL BORING LOCATION MAP
$DATE$$USER$ $FILE$$TIME$
220918-2-52-29 WALTON SR 20
ROAD NO. FINANCIAL PROJECT IDCOUNTY
DATE DESCRIPTION
REVISIONS
DATE DESCRIPTION
NO.
SHEETSTATE OF FLORIDA
DEPARTMENT OF TRANSPORTATION
REPORT OF SOIL BORINGS
CRAIG E. DUNKELBERGER, P.E.
ENVIRONMENTAL & GEOTECHNICAL SPECIALISTS, INC.
3676 HARTSFIELD ROAD
TALLAHASSEE, FLORIDA 32303
P.E. NO.: 49932
T H
E
O F
F I
C I
L
R
C O
D
I
S
E E
T
E C
T R
O N
C
G I
T A
L
Y
G N
A L
U
D
L E
G
A
C
-200=
OC=
Wc=
*N
(SP)
-200 SIEVE
LABORATORY TESTING RESULTS
LEGEND
WATER CONTENT (%)
ORGANIC CONTENT (%)
N-VALUE EQUIVALENT (NOTE 2)
MEASURED GROUNDWATER LEVEL
SOIL BORING LOCATION
(SM)
SILTY FINE SAND
UNIFIED SOIL CLASSIFICATION GROUP
(SP/SP-SM)
FINE SAND
HIGH GROUNDWATER LEVEL
ESTIMATED "NORMAL" SEASONAL
N
15 60
Feet
NOTES
TOPOGRAPHIC MAPS.
ELEVATIONS ARE APPROXIMATE AND WERE ESTIMATED USING USGS
PERFORMING THE EXTRAPOLATION.
DATA TO OTHER LOCATIONS IS THE SOLE RESPONSIBILITY OF THE PERSON
EXCEPT AT THE LOCATIONS OF THE SOIL BORING. EXTRAPOLATION OF THE SOIL
ARE FOR THE SOIL BORING ONLY AND MAY NOT APPLY TO ANY OTHER LOCATIONS
SOIL DESCRIPTIONS, TEST DATA, AND STANDARD PENETRATION VALUES SHOWN
FLUCTUATIONS SHOULD BE ANTICIPATED.
ENCOUNTERED DURING THE SUBSURFACE INVESTIGATION. GROUNDWATER LEVEL
MEASURED GROUNDWATER LEVEL SHOWN IS THE GROUNDWATER LEVEL
CONE PENTROMETER TESTS.
N-VALUES DENOTED WITH AN ASTERISK (*) WERE DERIVED FROM STATIC HAND
N-VALUES FOR 12 INCH PENETRATION (UNLESS OTHERWISE NOTED).
NUMBERS LEFT OF BORING INDICATE STANDARD PENETRATION TEST (SPT)
5.
4.
3.
2.
1.
GREATER THAN 40
24 - 40
8 - 24
3 - 8
LESS THAN 3
GREATER THAN 24
12 - 24
6 - 12
3 - 6
1 - 3
LESS THAN 1
RELATIVE DENSITY
GRANULAR MATERIALS
(BLOWS/12 IN.)
SPT
CONSISTENCY
SILTS AND CLAYS
(BLOWS/12 IN.)
SPT
HARD
VERY STIFF
STIFF
FIRM
SOFT
VERY SOFT
VERY DENSE
DENSE
MEDIUM DENSE
LOOSE
VERY LOOSE
AUTOMATIC HAMMER
SPLIT-SPOON:
HAMMER WEIGHT: 140 lbs.
AVG. HAMMER DROP: 30.0 in.
OUTSIDE DIAMETER: 2.0 in.
INSIDE DIAMETER: 1.375 in.
WMA-1
SR 20 EASTBOUND
SR 20 WESTBOUND
C R
A
W E
B
Y
L
O O
P
WMA-2
-200=9
Wc=4
-200=7
Wc=4
-200=12
Wc=8
-200=4
Wc=22
-200=9
Wc=22
-200=23
Wc=11
-200=11
Wc=6
-200=9
Wc=7
-200=5
Wc=21
-200=6
Wc=19
OC=1.9
-200=5
Wc=24
N
*7
*7
*4
*4
*5
N
*7
*5
*7
*7
*5
RIG
HAMMER
DRILLER
DATE
ELEV.
EASTING
NORTHING
BOR #
RIG
HAMMER
DRILLER
DATE
ELEV.
EASTING
NORTHING
BOR #
FINE SAND (SP-SM)
LOOSE TO MEDIUM DENSE DARK GRAY TO BROWN
SILTY FINE SAND (SM)
LOOSE TO MEDIUM DENSE BROWN
SILTY FINE SAND (SM)
LOOSE GRAY TO BROWN
FINE SAND (SP-SM)
LOOSE TO MEDIUM DENSE BROWN
MEDIUM SAND (SP-SM)
MEDIUM DENSE GRAY
FINE SAND (SP-SM)
MEDIUM DENSE DARK GRAY TO GRAY
$DATE$$USER$ $FILE$$TIME$
220918-2-52-29 WALTON SR 20
ROAD NO. FINANCIAL PROJECT IDCOUNTY
DATE DESCRIPTION
REVISIONS
DATE DESCRIPTION
NO.
SHEETSTATE OF FLORIDA
DEPARTMENT OF TRANSPORTATION
REPORT OF SOIL BORINGS
CRAIG E. DUNKELBERGER, P.E.
ENVIRONMENTAL & GEOTECHNICAL SPECIALISTS, INC.
3676 HARTSFIELD ROAD
TALLAHASSEE, FLORIDA 32303
P.E. NO.: 49932
T
F I
C I
C O
E E
T
E C
T R
O N
C
G I
T A
L
Y
G N
A L
D
L E
G
A
C
D-25
AUTOMATIC
W. CHOMAT
12/19/2023
64 FEET
1442922
552677
WMA-2
AT ELEV. 35 FEET
BORING TERMINATED
AT ELEV. 34 FEET
BORING TERMINATED
D-25
AUTOMATIC
W. CHOMAT
12/19/2023
65 FEET
1442904
552832
WMA-1
FINE SAND (SP, SP-SM)
MEDIUM DENSE TO DENSE DARK GRAY TO GRAYA
P P
R O
X I
M A
T E
E
L E
V A
T I O
N
(F
E E
V D
'8
) A
P P
R O
X I
M A
T E
E
L E
V A
T I O
N
(F
E E
V D
'8
APPENDIX B
SOIL BORING LOGS
2.5
7.5
LOOSE
DARK GRAY
FINE SAND
LOOSE
BROWN
FINE SAND
MEDIUM DENSE
BROWN
FINE SAND
MEDIUM DENSE
BROWN
SILTY FINE SAND
LOOSE
BROWN
SILTY FINE SAND
MEDIUM DENSE
DARK GRAY
FINE SAND
DENSE
GRAY
FINE SAND
DENSE
GRAY
FINE SAND
SP-SM
SP-SM
SM
SM
SP
SP-SM
SP-SM
ORG%=
2.1
-200%=9
-200%=7
-200%=12
ORG%=
0.3
-200%=4
ORG%=
0.6
ORG%=
0.3
-200%=9
PROJECT: SR 20 AT CR 83A (WEST BAY LOOP)
CLIENT: CES, INC.
PROJECT NO.: 61-78-23-01
PROJECT LOCATION: WALTON COUNTY, FLORIDA
BORING NO.: WMA-1
DRILLER: W. CHOMAT
HAMMER TYPE: AUTOMATIC
NORTHING: 552832
EASTING: 1442904
ELEVATION (FEET): 65
DATE: 12/19/2023
FLUID LOSS: NONE
DEPTH TO WATER: INITIAL: 14.0' 24 HR: N/M CAVING: NONE
NOTES: N/M MEANS NOT MEASURED
N/A MEANS NOT AVAILABLE
D E
P T
H
M E
T E
R S
D E
P T
H
F E
E T
S A
M P
L E
S Y
M B
O L
DESCRIPTION USCS
TEST
RESULTS
Wc
Wc (%)
N
N-Value
T h is i n fo rm a ti o n p e rt a in s o n ly t o t h is b o ri n g a n d s h o u ld n o t b e i n te rp re te d a s b e in g i n d ic it iv e o f th e s it e
2.5
7.5
LOOSE
GRAY
SILTY FINE SAND
LOOSE
BROWN
SILTY FINE SAND
LOOSE
BROWN
FINE SAND
MEDIUM DENSE
BROWN
FINE SAND
MEDIUM DENSE
GRAY
MEDIUM SAND
MEDIUM DENSE
DARK GRAY
FINE SAND
MEDIUM DENSE
GRAY
FINE SAND
SM
SP-SM
SP-SM
SP-SM
SP-SM
-200%=23
-200%=11
-200%=9
-200%=5
ORG%=
0.5
-200%=5
ORG%=
1.9
ORG%=
0.8
-200%=6
PROJECT: SR 20 AT CR 83A (WEST BAY LOOP)
CLIENT: CES, INC.
PROJECT NO.: 61-78-23-01
PROJECT LOCATION: WALTON COUNTY, FLORIDA
BORING NO.: WMA-2
DRILLER: W. CHOMAT
HAMMER TYPE: AUTOMATIC
NORTHING: 552832
EASTING: 1442904
ELEVATION (FEET): 64
DATE: 12/19/2023
FLUID LOSS: NONE
DEPTH TO WATER: INITIAL: 13.0' 24 HR: N/M CAVING: NONE
NOTES: N/M MEANS NOT MEASURED
N/A MEANS NOT AVAILABLE
D E
P T
H
M E
T E
R S
D E
P T
H
F E
E T
S A
M P
L E
S Y
M B
O L
DESCRIPTION USCS
TEST
RESULTS
Wc
Wc (%)
N
N-Value
T h is i n fo rm a ti o n p e rt a in s o n ly t o t h is b o ri n g a n d s h o u ld n o t b e i n te rp re te d a s b e in g i n d ic it iv e o f th e s it e
APPENDIX C
SOIL CLASSIFICATION DATA
0.0-0.5 7 2.1 -- SP-SM LOOSE
DARK GRAY
FINE SAND
1.0-1.5 4 100 100 99 69 29 14 9 7 SP-SM LOOSE
BROWN
FINE SAND
2.0-2.5 10 7 SP-SM LOOSE
BROWN
FINE SAND
3.0-3.5 5 4 SP-SM LOOSE
BROWN
FINE SAND
4.0-4.5 5 4 SP-SM LOOSE
BROWN
FINE SAND
5.0-5.5 4 100 100 99 69 27 11 7 5 SP-SM LOOSE
BROWN
FINE SAND
6.0-7.5 6 6 SP-SM LOOSE
BROWN
FINE SAND
7.5-9.0 10 12 SP-SM MEDIUM DENSE
BROWN
FINE SAND
9.0-10.5 8 10 SM MEDIUM DENSE
BROWN
SILTY FINE SAND
10.5-12.0 8 100 100 98 73 33 17 12 7 SM LOOSE
BROWN
SILTY FINE SAND
12.5-14.0 14 4 SM LOOSE
BROWN
SILTY FINE SAND
15.0-16.5 19 7 SM LOOSE
BROWN
SILTY FINE SAND
17.0-19.0 20 0.3 18 SP MEDIUM DENSE
DARK GRAY
FINE SAND
ENVIRONMENTAL AND GEOTECHNICAL SPECIALISTS, INC.
SOIL CLASSIFICATION DATA
Project: SR 20 AT CR 83A (WEST BAY LOOP)
Client: CES, INC. Project No.: 61-78-23-01
Boring: WMA-1 Location: WALTON COUNTY, FLORIDA
DEPTH
(FEET)
Wc
-4
-10
-20
-40
-60
-100
-200
LL PI
Org.
N Value
USCS Description
20.0-21.5 22 100 100 96 63 22 6 4 0.6 20 SP MEDIUM DENSE
FINE SAND
22.5-24.0 21 0.3 16 SP MEDIUM DENSE
DARK GRAY
FINE SAND
25.0-26.5 22 100 100 99 92 61 22 9 25 SP-SM DENSE
GRAY
FINE SAND
28.0-30.0 20 27 SP-SM DENSE
GRAY
FINE SAND
ENVIRONMENTAL AND GEOTECHNICAL SPECIALISTS, INC.
SOIL CLASSIFICATION DATA
Project: SR 20 AT CR 83A (WEST BAY LOOP)
Client: CES, INC. Project No.: 61-78-23-01
Boring: WMA-1 Location: WALTON COUNTY, FLORIDA
DEPTH
(FEET)
Wc
-4
-10
-20
-40
-60
-100
-200
LL PI
Org.
N
0.0-0.5 14 -- SM LOOSE
GRAY
SILTY FINE SAND
1.0-1.5 11 100 100 97 83 67 46 23 7 SM LOOSE
GRAY
SILTY FINE SAND
2.0-2.5 7 5 SM LOOSE
GRAY
SILTY FINE SAND
3.0-3.5 5 7 SM LOOSE
BROWN
SILTY FINE SAND
4.0-4.5 6 100 100 99 73 32 16 11 7 SP-SM LOOSE
BROWN
FINE SAND
5.0-5.5 6 5 SP-SM LOOSE
BROWN
FINE SAND
6.0-7.5 11 3 SP-SM LOOSE
BROWN
FINE SAND
7.5-9.0 8 6 SP-SM LOOSE
BROWN
FINE SAND
9.0-10.5 7 100 100 98 73 33 15 9 7 SP-SM LOOSE
BROWN
FINE SAND
10.5-12.0 10 9 SP-SM MEDIUM DENSE
BROWN
FINE SAND
12.5-14.0 15 12 SP-SM MEDIUM DENSE
BROWN
FINE SAND
15.0-16.5 21 100 100 98 32 10 6 5 17 SP-SM MEDIUM DENSE
GRAY
MEDIUM SAND
17.0-19.0 21 8 SP-SM MEDIUM DENSE
GRAY
MEDIUM SAND
ENVIRONMENTAL AND GEOTECHNICAL SPECIALISTS, INC.
SOIL CLASSIFICATION DATA
Project: SR 20 AT CR 83A (WEST BAY LOOP)
Client: CES, INC. Project No.: 61-78-23-01
Boring: WMA-2 Location: WALTON COUNTY, FLORIDA
DEPTH
(FEET)
Wc
-4
-10
-20
-40
-60
-100
-200
LL PI
Org.
N
20.0-21.5 25 0.5 10 SP-SM MEDIUM DENSE
FINE SAND
22.5-24.0 24 100 100 99 84 26 8 5 1.9 8 SP-SM MEDIUM DENSE
DARK GRAY
FINE SAND
25.0-26.5 24 0.8 8 SP-SM MEDIUM DENSE
DARK GRAY
FINE SAND
28.0-30.0 19 100 100 99 90 60 20 6 14 SP-SM MEDIUM DENSE
GRAY
FINE SAND
ENVIRONMENTAL AND GEOTECHNICAL SPECIALISTS, INC.
SOIL CLASSIFICATION DATA
Project: SR 20 AT CR 83A (WEST BAY LOOP)
Client: CES, INC. Project No.: 61-78-23-01
Boring: WMA-2 Location: WALTON COUNTY, FLORIDA
DEPTH
(FEET)
Wc
-4
-10
-20
-40
-60
-100
-200
LL PI
Org.
N
| ADP75BD.tmp |
| TABLES |
| FIGURES |
| APPENDIX A |
| APPENDIX B |
| APPENDIX C |
| Table 1 - Soil Boring Location & Measured Groundwater Data.pdf |
| Table 1 |
| Tables 2-3 - Geotech Design Parameters.pdf |
| TABLE 2B |
| TABLE 2A |
| TABLE 3B |
| Figure 3 - Design Profiles.pdf |
| Figure 3 - Design Profiles02.pdf |
| Figure 3 - Design Profiles01.pdf |
| SPTBSG01.pdf |
| SPTBSG02.pdf |
| SPTBSG01.pdf |
| ADP8E12.tmp |
| REPORT OF |
| GEOTECHNICAL INVESTIGATION |
| MAST ARM FOUNDATIONS |
| SR 20 AT CR 83A (WEST BAY LOOP) |
| COMPREHENSIVE ENGINEERING SERVICES, INC. |
| ENVIRONMENTAL AND GEOTECHNICAL SPECIALISTS, INC. |
| ADP51D3.tmp |
| SCOPE OF SERVICES |
| The Scope of Services authorized for this investigation consisted of the following: |
| SITE LOCATION AND CONDITIONS |
| SUBSURFACE INVESTIGATION |
| GEOTECHNICAL DESIGN RECOMMENDATIONS |
| CLOSURE |