M-102.pdf
PDF 1 MB Posted
- Attached to
- Mims Water Treatment Plant Mixing Improvement
- Solicitation number
- B-7-25-41
- Issued by
- Brevard County, Miramar Beach CDP, Florida
About this file
The document is a mechanical engineering plan (Drawing M-102) for the Brevard County Utilities Mims Water Treatment Plant Mixing Improvements project, prepared by Black & Veatch Corporation. The drawing specifically details the Chlorine Contact Basin No. 2 plan and section, showing mechanical modifications including new mixers, piping configurations, access hatches, and infrastructure upgrades across four distinct zones. The plan indicates installation of new 12" and 10" ductile iron pipes, a new flow meter, mixer supports, relocated sampling pipes, new chlorine and ammonia piping, and side-mounted handrails. The document is marked as a 90% submittal, not for construction, dated June 2024, with an Addendum No. 1 issued on 04/25.
The drawing provides technical specifications and notes for contractors, including requirements for pipe replacement, pipe support installation, and construction sequencing. Specific installation instructions cover details such as using Link Seals, replacing existing ammonia piping, installing chlorine solution pipes along chamber walls, and filling existing handrail support anchor holes with specified epoxy materials. The plan includes precise elevation measurements and structural details, with a scale of 3/8" = 1'-0" for both lower and operating level mechanical plans. The document is part of a comprehensive water treatment plant improvement project that involves critical infrastructure upgrades to enhance the facility's operational capabilities.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING
1" CS
EXISTING
DRAIN
EXISTING
CO2 DIFFUSER
M-102 M-102
NEW 12" DIP
CL EL 45.42'
LINK SEAL B
M-501
LINK SEAL
NEW CL2
DIFFUSER
B M-501
EXISTING ADJUSTABLE
WEIR GATE
ZONE 4
ZONE 3 ZONE 2 ZONE 1
C M-501
VALVE BOX
EXISTING
6" pH SENSER CONN
EXISTING HATCH
TO REMAIN
M-102
M-102
EXISTING
HANDRAIL (TYP)
EXISTING
SAMPLING
PUMP
EXISTING FILTER
FLOW INDICATOR
EXISTING
ADJUSTABLE
WEIR GATE
RELOCATED
SAMPLING PIPE
(NOTE 4)
NEW 1/2" CPVC
AMMONIA PIPE
(NOTE 5)
RELOCATED EXISTING
pH TRANSMITTER
NEW ACCESS
HATCH DOOR
(NOTE 7)
HB
1" PW
MIXER
MIXER SUPPORT MIXER
MIXER SUPPORT
REMOVABLE ENCLOSUREA
M-501
A M-501
REMOVABLE ENCLOSURE
MXP-202
MXP-201
NEW
10" DIP
CL EL 45.42'
NEW 10"
FLOW METER
EL 48.95'
EL 37.20'
3' -1
2' -2
6"
NEW
MIXER
CL
MIXER SUPPORT
STRUCTURE (TYP)
6' -9
NEW
MIXER
CL
8'-4"±
4'-6"
2' -1
4' -9
1/2" PE AMMONIA
PIPE (NOTE 2)
NEW 1" CPVC
CHLORINE
(NOTE 3)
EL 48.45'
CL EL 29.23'
CL EL 47.95'
LINK SEAL B
M-501
EL 36.41'
NEW 12" x 10"
REDUCING 90°
BEND (FLG)
NEW 12" x 10"
REDUCING BEND
(MECHANICAL JOINT)
CL EL 41.20'
NEW SIDE MOUNTED
HANDRAIL, SEE DWG S-503
ZONE 4
ZONE 3
ZONE 2
ZONE 1
A M-501
REMOVABLE ENCLOSURE
REMOVABLE ENCLOSURE
NEW 10"
GATE VALVE
CL EL 34.20'
A M-501
EL = 44.71'
NEW
12" DIP
3' -1
0"
3' -0
MIXER MOTOR
MIXER MOTOR
MXP-202
MXP-201
NEW ACCESS
HATCH DOOR
(NOTE 7)
GV-3
(NOTE 8)
NOTES:
1. REPLACE EXISTING AMMONIA PIPING WITH NEW
PIPING OF THE SAME SIZE AND CONFIGURATION
AS THE EXISTING.
2. INSTALL 1" CHLORINE SOLUTION PIPE ALONG
THE INSIDE OF THE CHLORINE CONTACT
CHAMBER EAST WALL. REFER TO
SPECIFICATION SECTION 15140 FOR PIPE
SUPPORT REQUIREMENTS.
3. RELOCATE SAMPLING PIPE ALONG THE OUTSIDE
WALL. REFER TO SPECIFICATION SECTION 15140
FOR PIPE SUPPORT REQUIREMENTS.
CONTRACTOR TO COORDINATE PIPE
INSTALLATION WITH HANDRAIL WALL SUPPORTS.
4. REPLACE EXISTING 1/2" AMMONIA PIPE FROM
GROUND ELEVATION UP TO EXISTING PIPE
PENETRATION.
5. WORKS ASSOCIATED WITH THE IMPROVEMENTS
TO CHLORINE CONTACT CHAMBER NUMBER 2
SHALL CONFORM TO REQUIREMENTS OF
SPECIFICATION 01900 CONSTRUCTION
SEQUENCE.
6. CONTRACTOR SHALL SUPPLY AND INSTALL
HALLIDAY ACCESS HATCH DOOR (PART NUMBER
030030CBD-C).
7. FILL EXISTING HANDRAILS SUPPORT ANCHOR
HOLES SIKA ARMATEC 110 EPOCEM OR
APPROVED EQUAL.
12" 6" 0 7'6'5'4'3'2'1'
3/8"=1'-0"
SEE DRAWING
C-101 FOR
CONTINUATION
SECTION1
- 3/8" = 1'-0"
LOWER LEVEL - MECHANICAL PLAN
3/8" = 1'-0"
OPERATING LEVEL - MECHANICAL PLAN
3/8" = 1'-0"
APPROVED:
DESIGNED:
DETAILED:
CHECKED:
DATE:
REVISIONS AND RECORD OF ISSUE
OF
PROJECT NO.:
43211/20(SCALE BAR IS 4" AT FULL SCALE)
SUBCONSULTANT:
G
FI
LE
PL
O
TT
ED
Certificate No. 8132 201 South Orange Avenue, Suite 500
Orlando, Florida 32801
Black & Veatch Corporation
FG
C :\P
W _W
O R
KI
N
G \B
VW
_A
M
ER
IC
AS
_2 \D
5\
M -1
.D
W G
5/ 1/
:3
6:
P M
BREVARD COUNTY
UTILITIES MIMS WTP
MIXING IMPROVEMENTS
416085
90% SUBMITTAL
NOT FOR
CONSTRUCTION
JUNE 2024
M-102
MECHANICAL
CHLORINE CONTACT
BASIN NO.2 PLAN AND
SECTION
RS
HK
RE
RS
ADDENDUM NO. 1
04/25 ISSUED WITH MODIFICATION PER1
File details come from the government source that posted it. Updated .