M-101.pdf

PDF 1 MB Posted

Attached to
Mims Water Treatment Plant Mixing Improvement
Solicitation number
B-7-25-41
Issued by
Brevard County, Miramar Beach CDP, Florida

About this file

The document is a mechanical engineering plan (Drawing M-101) for the Brevard County Utilities Mims Water Treatment Plant Mixing Improvements project, prepared by Black & Veatch Corporation. The drawing provides detailed mechanical plans for the Chlorine Contact Basin No. 1, featuring lower and operating level mechanical layouts that illustrate proposed modifications including new mixers in different zones, pipe relocations, valve installations, and access improvements. The plan includes specific technical details such as elevation measurements, pipe specifications (including 12" and 10" DIP pipes), new mixer placements, and modifications to existing infrastructure like sampling pipes, ammonia pipes, and chlorine solution pipes.

The drawing is part of a 90% submittal and is not yet approved for construction, indicating it is in the final design stages before actual implementation. Notable technical specifications include replacing existing ammonia piping, installing new chlorine solution pipes along the chamber's east wall, relocating sampling pipes, and adding new access hatches. The project involves precise infrastructure upgrades with specific requirements for pipe supports, wall penetrations, and structural modifications. The drawing includes several technical notes providing guidance on installation methods, material specifications, and coordination requirements for the contractor, with specific references to specification sections and approved materials like Sika Armatex 110 Epocem for filling existing handrail support anchor holes.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LINK SEAL

SEE DRAWING

C-101 FOR

CONTINUATION

NEW 1"

CHLORINE

(NOTE 2)

LINK SEAL

VALVE BOX

B M-501

B M-501

C M-501

M-101

M-101

ZONE 4

ZONE 1 ZONE 2 ZONE 3

NEW 12" DIP

CL EL 45.25'

10'-6"

RELOCATED

SAMPLING PIPE

(NOTE 4)

NEW 1/2" AMMONIA

PIPE (NOTE 5)

EXISTING

SAMPLING

PUMP

MIXER

MIXER SUPPORT

MIXER

MIXER SUPPORT

LINK SEAL REMOVABLE ENCLOSUREREMOVABLE ENCLOSURE A

M-501

A M-501

M-101

M-101

EXISTING HATCH

TO REMAIN

NEW ACCESS

HATCH DOOR

(NOTE 7)

EXISTING 6" pH

SENSOR CONN

MXP-102MXP-101

EL 44.71'

EL 48.54' 6"

CL EL 29.23'

NEW 12" x 10"

REDUCING 90°

BEND (FLG)

NEW

10" DIP

CL EL 45.25'

NEW 10"

FLOW METER

EL 49.04'

6' -9

NEW

MIXER

CL

6'-0"

2' -1

4' -9

NEW 1/2" PE AMMONIA

PIPE (NOTE 2)

NEW 1" CPVC

CHLORINE

(NOTE 3)

CL EL 47.54'

LINK SEAL

10'-6"

EXISTING CO2 DIFFUSER

EL 38.00'

EL 37.84'

10" GATE VALVE

EL 34.30'

NEW 12" X 10"

REDUCING BEND

(MECHANICAL JOINT)

EL 36.47'

CL EL 41.30'

NEW SIDE MOUNTED

HANDRAIL, SEE DWG S-503

ZONE 4

ZONE 3

ZONE 2

ZONE 1

B M-501

A M-501 A

M-501

REMOVABLE ENCLOSURE

REMOVABLE ENCLOSURE

GV-4

NEW

12" DIP

3' -1

2' -2

NEW

MIXER

CL MIXER SUPPORT

STRUCTURE (TYP)

3' -0

MIXER MOTOR MIXER MOTOR

MXP-101

MXP-102

NEW ACCESS

HATCH DOOR

(NOTE 7)

(NOTE 8)

3' -1

0"

12" 6" 0 7'6'5'4'3'2'1'

3/8"=1'-0"

SECTION1

- 3/8" = 1'-0"

LOWER LEVEL - MECHANICAL PLAN

3/8" = 1'-0"

OPERATING LEVEL - MECHANICAL PLAN

3/8" = 1'-0"

NOTES:

1. REPLACE EXISTING AMMONIA PIPING WITH NEW

PIPING OF THE SAME SIZE AND CONFIGURATION

AS THE EXISTING.

2. INSTALL 1" CHLORINE SOLUTION PIPE ALONG

THE INSIDE OF THE CHLORINE CONTACT

CHAMBER EAST WALL. REFER TO

SPECIFICATION SECTION 15140 FOR PIPE

SUPPORT REQUIREMENTS.

3. RELOCATE SAMPLING PIPE ALONG THE OUTSIDE

WALL. REFER TO SPECIFICATION SECTION 15140

FOR PIPE SUPPORT REQUIREMENTS.

CONTRACTOR TO COORDINATE PIPE

INSTALLATION WITH HANDRAIL WALL SUPPORTS.

4. REPLACE EXISTING 1/2" AMMONIA PIPE FROM

GROUND ELEVATION UP TO EXISTING PIPE

PENETRATION.

5. WORKS ASSOCIATED WITH THE IMPROVEMENTS

TO CHLORINE CONTACT CHAMBER NUMBER 2

SHALL CONFORM TO REQUIREMENTS OF

SPECIFICATION 01900 CONSTRUCTION

SEQUENCE.

6. CONTRACTOR SHALL SUPPLY AND INSTALL

HALLIDAY ACCESS HATCH DOOR (PART NUMBER

0300030CBD-C).

7. FILL EXISTING HANDRAILS SUPPORT ANCHOR

HOLES WITH SIKA ARMATEX 110 EPOCEM OR

APPROVED EQUAL.

APPROVED:

DESIGNED:

DETAILED:

CHECKED:

DATE:

REVISIONS AND RECORD OF ISSUE

OF

PROJECT NO.:

43211/20(SCALE BAR IS 4" AT FULL SCALE)

SUBCONSULTANT:

G

FI

LE

PL

O

TT

ED

Certificate No. 8132 201 South Orange Avenue, Suite 500

Orlando, Florida 32801

Black & Veatch Corporation

FG

C :\P

W _W

O R

KI

N

G \B

VW

_A

M

ER

IC

AS

_2 \D

5\

M -1

.D

W G

5/ 1/

:5

2:

P M

BREVARD COUNTY

UTILITIES MIMS WTP

MIXING IMPROVEMENTS

416085

90% SUBMITTAL

NOT FOR

CONSTRUCTION

AUGUST 2024

M-101

MECHANICAL

CHLORINE CONTACT

BASIN NO.1 PLAN AND

SECTION

RS

HK

RE

RS

ADDENDUM NO. 1

04/25 ISSUED WITH MODIFICATION PER1

File details come from the government source that posted it. Updated .