M-101.pdf

PDF 1 MB Posted

Attached to
Mims Water Treatment Plant Mixing Improvement
Solicitation number
B-7-25-41
Issued by
Brevard County, Miramar Beach CDP, Florida

About this file

The document is a mechanical engineering drawing (Sheet M-101) for the Brevard County Utilities Mims Water Treatment Plant Mixing Improvements project, prepared by Black & Veatch Corporation. The drawing provides detailed plans for the Chlorine Contact Basin No. 1, including lower and operating level mechanical plans with specific improvements such as new mixers (MXP-101 and MXP-102), pipe relocations, valve installations, and access modifications. The drawing is marked as a 90% submittal and is not for construction, with a note indicating Addendum No. 1 was issued on 04/25.

The drawing includes technical specifications for replacing existing ammonia piping, installing new chlorine solution pipes, relocating sampling pipes, and adding new access hatches. Specific details include new 12-inch and 10-inch ductile iron pipes, a new flow meter, side-mounted handrails, and modifications to various zones within the contact basin. The drawing provides elevation details, pipe routing, and notes on contractor responsibilities, such as coordinating pipe installation with handrail wall supports and using specific materials like Sika Armatex 110 Epocem for filling existing handrail support anchor holes. The document is part of a comprehensive upgrade to the water treatment facility's mixing and infrastructure systems.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LINK SEAL

SEE DRAWING

C-101 FOR

CONTINUATION

NEW 1"

CHLORINE

(NOTE 2)

LINK SEAL

VALVE BOX

B M-501

B M-501

C M-501

M-101

M-101

ZONE 4

ZONE 1 ZONE 2 ZONE 3

NEW 12" DIP

CL EL 45.25'

10'-6"

RELOCATED

SAMPLING PIPE

(NOTE 4)

NEW 1/2" AMMONIA

PIPE (NOTE 5)

EXISTING

SAMPLING

PUMP

MIXER

MIXER SUPPORT

MIXER

MIXER SUPPORT

LINK SEAL REMOVABLE ENCLOSUREREMOVABLE ENCLOSURE A

M-501

A M-501

M-101

M-101

EXISTING HATCH

TO REMAIN

NEW ACCESS

HATCH DOOR

(NOTE 7)

EXISTING 6" pH

SENSOR CONN

MXP-102MXP-101

EL 44.71'

EL 48.54' 6"

CL EL 29.23'

NEW 12" x 10"

REDUCING 90°

BEND (FLG)

NEW

10" DIP

CL EL 45.25'

NEW 10"

FLOW METER

EL 49.04'

6' -9

NEW

MIXER

CL

6'-0"

2' -1

4' -9

NEW 1/2" PE AMMONIA

PIPE (NOTE 2)

NEW 1" CPVC

CHLORINE

(NOTE 3)

CL EL 47.54'

LINK SEAL

10'-6"

EXISTING CO2 DIFFUSER

EL 38.00'

EL 37.84'

10" GATE VALVE

EL 34.30'

NEW 12" X 10"

REDUCING BEND

(MECHANICAL JOINT)

EL 36.47'

CL EL 41.30'

NEW SIDE MOUNTED

HANDRAIL, SEE DWG S-503

ZONE 4

ZONE 3

ZONE 2

ZONE 1

B M-501

A M-501 A

M-501

REMOVABLE ENCLOSURE

REMOVABLE ENCLOSURE

GV-4

NEW

12" DIP

3' -1

2' -2

NEW

MIXER

CL MIXER SUPPORT

STRUCTURE (TYP)

3' -0

MIXER MOTOR MIXER MOTOR

MXP-101

MXP-102

NEW ACCESS

HATCH DOOR

(NOTE 7)

(NOTE 8)

3' -1

0"

12" 6" 0 7'6'5'4'3'2'1'

3/8"=1'-0"

SECTION1

- 3/8" = 1'-0"

LOWER LEVEL - MECHANICAL PLAN

3/8" = 1'-0"

OPERATING LEVEL - MECHANICAL PLAN

3/8" = 1'-0"

NOTES:

1. REPLACE EXISTING AMMONIA PIPING WITH NEW

PIPING OF THE SAME SIZE AND CONFIGURATION

AS THE EXISTING.

2. INSTALL 1" CHLORINE SOLUTION PIPE ALONG

THE INSIDE OF THE CHLORINE CONTACT

CHAMBER EAST WALL. REFER TO

SPECIFICATION SECTION 15140 FOR PIPE

SUPPORT REQUIREMENTS.

3. RELOCATE SAMPLING PIPE ALONG THE OUTSIDE

WALL. REFER TO SPECIFICATION SECTION 15140

FOR PIPE SUPPORT REQUIREMENTS.

CONTRACTOR TO COORDINATE PIPE

INSTALLATION WITH HANDRAIL WALL SUPPORTS.

4. REPLACE EXISTING 1/2" AMMONIA PIPE FROM

GROUND ELEVATION UP TO EXISTING PIPE

PENETRATION.

5. WORKS ASSOCIATED WITH THE IMPROVEMENTS

TO CHLORINE CONTACT CHAMBER NUMBER 2

SHALL CONFORM TO REQUIREMENTS OF

SPECIFICATION 01900 CONSTRUCTION

SEQUENCE.

6. CONTRACTOR SHALL SUPPLY AND INSTALL

HALLIDAY ACCESS HATCH DOOR (PART NUMBER

0300030CBD-C).

7. FILL EXISTING HANDRAILS SUPPORT ANCHOR

HOLES WITH SIKA ARMATEX 110 EPOCEM OR

APPROVED EQUAL.

APPROVED:

DESIGNED:

DETAILED:

CHECKED:

DATE:

REVISIONS AND RECORD OF ISSUE

OF

PROJECT NO.:

43211/20(SCALE BAR IS 4" AT FULL SCALE)

SUBCONSULTANT:

G

FI

LE

PL

O

TT

ED

Certificate No. 8132 201 South Orange Avenue, Suite 500

Orlando, Florida 32801

Black & Veatch Corporation

FG

C :\P

W _W

O R

KI

N

G \B

VW

_A

M

ER

IC

AS

_2 \D

5\

M -1

.D

W G

5/ 1/

:5

2:

P M

BREVARD COUNTY

UTILITIES MIMS WTP

MIXING IMPROVEMENTS

416085

90% SUBMITTAL

NOT FOR

CONSTRUCTION

AUGUST 2024

M-101

MECHANICAL

CHLORINE CONTACT

BASIN NO.1 PLAN AND

SECTION

RS

HK

RE

RS

ADDENDUM NO. 1

04/25 ISSUED WITH MODIFICATION PER1

File details come from the government source that posted it. Updated .