This is an Addendum No. 2 issued by Hurtig, Gardner, Froelich, Architects, Inc. for the Lamar Community College Bowman Building Lecture Halls Remodel project located at 2602 N. Elizabeth Street in Pueblo, Colorado, with the project site at 2401 S. Main Street in Lamar, Colorado. The addendum modifies specifications and drawing requirements for the lecture hall renovation work and is applicable to all known bidders. Bidders are required to acknowledge receipt of this two-page addendum on the bid form and attach it to the scope of work. Key specification modifications include allowing the General Contractor to maintain a local field office within 30 miles of the College Campus as an alternative to an on-site portable field office, and adding requirements for aisle light fixtures and designated aisle seats with articulating armrests that comply with 2012 IBC Section 1108.2.5 in the lecture room seating specification. Drawing clarifications address electrical demolition, new work lighting plans, and power plans across multiple sheets, including modifications to EM inverter ratings, alternate provisions for extension rings in Lecture Halls 139 and 138, automatic lighting control system hours, emergency egress wiring for Type F fixtures, and coordination of furniture-integrated step lights with existing circuits.
The addendum establishes coordination responsibilities requiring the General Contractor to oversee all subcontractor work and submit Requests for Information to the Owner and Architect prior to electrical or mechanical rough-in if coordination conflicts arise. Additional clarifications specify that MC cable use is restricted to feeding lighting fixtures from ceiling junction boxes, fishing existing walls for concealed branch circuits, and fishing sections where EMT cannot be installed. The electrical contractor must confirm mechanical equipment connections prior to rough-in, coordinate occupancy sensor locations per manufacturer recommendations, coordinate with all trades to maintain NEC clearances, and obtain architect approval for any exposed raceway routing. Cost implications include potential relocation expenses for occupancy sensors at the electrical contractor's expense if devices fail to achieve required coverage. No pricing terms, set-asides, funding sources, or contract award dates are specified in this addendum document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Asbestos Abatement Bid Info and Document.doc | DOC document | |
| LCC Lecture Halls Addendum No 3 - 0825816.pdf | ||
| LCC Lecture Halls Addendum No 1 - 08 18 16.pdf | ||
| Lecture Halls.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM NO. 2 HURTIG, GARDNER, FROELICH, ARCHITECTS, INC.
Lamar Community College 2602 N. Elizabeth Street, Pueblo, CO 81003 Bowman Building Lecture Halls Remodel August 24, 2016 2401 S. Main Street Lamar, CO 81052 This Addendum consists of 2 pages This Addendum is issued to all known bidders. Bidders shall attach this Addendum to the scope of work and acknowledge receipt on the Bid Form. All information and instructions given herein shall become a part of the contract documents.
SPECIFICATION ITEMS
Item No. 1: Section 01 50 13 – Temporary Facilities:
Delete paragraph 1.06, A. Field Office in its entirety.
Replace previous paragraph 1.06, A with the following:
o A. Field Office: General Contractor shall provide and maintain for the duration of the work, in an Owner approved location, a field office of construction. Provide own office furniture, supplies, equipment, temporary light, heat, and telephone. Office may be trailer on wheels or other portable type as approved. Properly file all drawings and specifications for the project and make them accessible at all times for the Owner and Architect. Maintain a clean, sanitary condition at all times.
o NOTE: A local office within 30 miles of the College Campus is acceptable in lieu of an on-site portable field office.
Item No. 2: Section 12 61 10 – Lecture Room Seating:
Add the following to paragraph 2.01, C:
9. Aisle Lights: Provide, install, and power connect Aisle Light Fixtures on end of seat mounted beam at seat rows where removed aisle light fixtures were previously located.
Add the following to paragraph 2.01, C, 2, Plastic Armrests:
a. Seats adjacent to aisles at two top-most rows shall be Designated Aisle Seats and shall comply with 2012 IBC Section 1108.2.5.
b. Armrests at designated aisle seats shall articulate and move back out of the seating row accessway.
DRAWING ITEMS
Item No. 1: Sheet E0.1 – Fixture Schedule and Symbol Legends:
1. Dimming Panel Note Schedule clarifications: Both EM Inverters are to be rated 2100va. RE:
Detail on Lighting Control Diagram.
Item No. 2: Sheet E1.1 – Electrical Demolition Plan:
1. Electrical Contractor to take great care in disconnecting existing furniture mounted step lights – maintain circuit continuity and reuse circuit to feed new lights as shown on New work plan.
2. Add Alternate No. 5: Lecture Hall 139: Provide extension rings as required (RE: Architectural drawing A1.2) to accommodate for furring of walls.
3. Add Alternate No. 6: Lecture Hall 138: Provide extension rings as required (RE: Architectural drawing A1.2) to accommodate for furring of walls.
Item No. 3: Sheet E2.1 – New Work - Lighting Plan:
1. Provide automatic On-Off hours for Lighting Control Systems. Coordinate hours with Owner’s schedule.
2. Type F fixtures to be wired with emergency egress. Rewire as required.
3. Electrical Contractor to coordinate with G.C to install new Furniture Step Lights under base bid.
Coordinate cutting and patching as required.
4. Clarifications: Add Alternates No. 1 & 2 - Integral step lights are to be provided with furniture. RE:
Architectural. Electrical Contractor to connect these to existing circuit.
Item No. 4: Sheet E3.1– New Work – Power Plan:
1. Final Location of Floor box in Lecture Hall 139 by Owner.
CLARIFICATION ITEMS
Item No. 1: General Contractor and Subcontractor Coordination:
It shall be the responsibility of the General Contractor (G.C.) to coordinate all subcontractors work.
The G.C. shall bring to the attention of the Owner and Architect any coordination issues or conflicts for resolution in the form of an RFI prior to rough-in of electrical or mechanical work.
Item No. 2: Electrical General Notes:
1. Per Specifications: MC Cable only to be used under the following conditions
a. To feed Lighting Fixtures from Ceiling Junction Boxes
b. To fish existing walls to conceal branch circuits.
c. To fish sections of building of which EMT cannot be installed.
NO OTHER USE WILL BE PERMITTED.
2. ONLY APPROVED PRODUCTS LISTED IN AN ADDENDUM WILL BE ACCEPTED.
3. Refer to Mechanical Drawings and Addendums for exact location of all Mechanical Equipment.
4. Ceiling Mounted Occupancy Sensors are to be located per plans for coverage and per manufacturer’s recommendations. Failure of this will result in relocation of devices at the expense of the Electrical Contractor. Should there be a conflict, a request in written format shall be submitted to the Architect for resolution.
5. Electrical Contractor to confirm all mechanical equipment connections prior to rough-in.
6. Electrical Contractor shall refer to Architectural drawings prior to rough-in for coordination.
7. Routing of any exposed raceway to be approved by architect prior to installation.
8. Coordinate with all trades to maintain NEC Clearances for ALL Electrical Equipment.