LBNL Type 5 Wildland Engine (Patrol) SOS_11-10-23.docx
DOCX document 16 KB Posted
- Attached to
- Type 1 and Type 5 Fire Engine Leasing Services
- Solicitation number
- LBNL_9-18-23
- Issued by
-
Department of Energy
About this file
This document outlines requirements for a Type 5 Wildland Engine lease opportunity with Lawrence Berkeley National Laboratory. The subcontractor will provide an on-site Type 5 Wildland Engine that meets NFPA standards with a minimum 400-gallon water tank, 150 GPM pump, and foam capabilities. The chassis must be a four-door F-550 or equivalent with four-wheel drive and seating for four. Required equipment includes a stokes basket, shore power, lighting, backup alarm, siren, and warning lights. The subcontractor must keep the engine on-site at all times, performing on-site maintenance as needed and off-site maintenance within two hours of engine removal, also providing an on-site replacement during that time. Training will be provided on-site to LBNL firefighters upon engine delivery. This lease opportunity is associated with the Department of Energy solicitation for Type 1 and Type 5 Fire Engine Leasing Services under opportunity number LBNL_9-18-23.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions and Answers.pdf | ||
| RFP LBNL 9-18-23 Amendment No.2.doc | DOC document | |
| Revised Sample SubK_11-10-23.docx | DOCX document | |
| LBNL Type 1 Fire Engine SOS_11-10-23.docx | DOCX document | |
| RFP LBNL 9-18-23 Amendment No.1.pdf | ||
| Offerors_Pricing.xlsx | XLSX spreadsheet | |
| Offerors References Form.docx | DOCX document | |
| Rep Cert Form.docx | DOCX document | |
| LBNL Type 1 Fire Engine SOS_9-27-23.pdf | ||
| General Provisions for Equipment Lease.pdf | ||
| RFP-LBNL_9-18-23.pdf | ||
| LBNL Type 5 Wildland Engine (Patrol) SOS_9-27-23.pdf | ||
| Sample SubK_9-26-23.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Lawrence Berkeley National Laboratory (LBNL) Type 5 Wildland Engine Statement of Leasing Services 11-10-23
Subcontractor Responsibilities:
Provide to LBNL, at One Cyclotron Road, Berkeley, CA, a Type 5 Wildland Engine (Patrol) to be used for initial attack of wildland fire response and acts as a support platform for structural fire and rescue response. The apparatus must meet the minimums of a Type 5 fire engine as defined by the National Wildfire Coordinating Group or equivalent, must not be greater than 10 years old, and must meet the below specifications. These specifications are required due to Berkeley Lab’s geography and fire response needs to support the execution of LBNL requirements including dispatch time, turn out time, and response times.
Chasse specifications:
· Four door F-550 Chassis or equivalent with seating for four
· Four-wheel drive system with dual rear wheels
· Limited slip rear differential
· Diesel powered
· Front bumper that protects front grille and has a skid plate
· Front mounted winch with 12,000lb or great capacity, 12V
Fire suppression capability:
· Water tank, minimum of 400-gallon capacity
· Fire pump with “pump and roll” capability with diesel engine
· Fire pump with operating pressures:
· minimum of 150 GPM at 50 PSI
· minimum of 50 GPM at 300 PSI
· Fire pump must be plumbed to front discharge manifold
· Fire pump must be plumbed to support .75” and 2.5” hose at rear
· Ground sweep discharges at the front bumper
· Fire hose minimums: 2 hose reels with 100 feet of .75” hose
· Foam System capable of 200 psi with selectable proportioning rates and flow meter
Equipment minimums:
· Stokes basket or equivalent
· Shore tie receptacle with auto eject for 120V, 20A service
· Appropriate scene and work lighting to safely operate in low light conditions
· Back up alarm
· Siren system
· Flashing warning lights that conform to California Title 13
The subcontractor shall provide tools and equipment to make the apparatus fully operational.
Fire Engine Maintenance The subcontractor must provide to LBNL a fully operational Type 5 Fire Engine onsite at LBNL 24 hours per day, 365 days per year. The Subcontractor will perform all of the required onsite and offsite Fire Engine maintenance. Onsite maintenance is maintenance that the subcontractor performs that does not require the Fire Engine to be out of service, and does not result in any degradation of immediate emergency service response. Offsite maintenance is maintenance that the subcontractor performs that requires the Fire Engine to be out of service. The subcontractor must perform all of the Fire Engine offsite maintenance at the subcontractor’s facilities. When the subcontractor is performing offsite Fire Engine maintenance, the Subcontractor must provide a replacement, onsite Fire Engine in kind, that has the same performance specifications. For offsite maintenance, an onsite replacement Fire Engine must be provided within 2 hours or less after the Fire Engine is taken out of service
Training Upon delivery of the Type 5 Fire Engine to LBNL, the subcontractor will provide training that covers each shift, within the first week of delivery, for the firefighters working at LBNL. The training will be provided in-person at LBNL. The training will cover the operating of all systems on the fire engine. The training will be conducted by an Original Equipment Manufacturer (OEM) trained instructor.