Ladd Spec updated Sheet 6 B53347.pdf

PDF 829 KB Posted

Attached to
REBID District 3 Ladd and Sycamore Maintenance Yard Generator and Installation
Solicitation number
27-494DOT-FINAD-B-53347
Issued by
Dekalb County, Lee Center CDP, Illinois

About this file

This is an electrical specification sheet prepared by Prairie Engineers of Illinois, P.C. for the Illinois Department of Transportation (IDOT) District 3 Ladd Maintenance Yard Generator Installation project. The document provides detailed one-line electrical diagrams and technical specifications for the installation of a 96 kW/120 kVA natural gas standby engine generator with a 400-amp automatic transfer switch at the Ladd Maintenance Yard. The project includes installation of a NEMA 3R enclosed service disconnect switch, modifications to existing electrical panels (including new ground bars and breaker replacements), concrete generator pad construction measuring 10 feet by 5 feet by 6 inches thick, grounding field installation with three copper-clad grounding rods, conduit and conductor sizing specifications for above-grade and below-grade installations, and control wiring for the automatic transfer switch. Key electrical specifications include: 240/120VAC, 1-phase, 3-wire system configuration; (3) #4/0 and #4 ground conductors in 2-1/2-inch conduit below-grade; (2) sets of (3) #3/0 and #3 ground conductors in 2-inch conduit above-grade; and exothermic weld connections for grounding rod field connections 30 inches below finish grade. The sheet specifies coordination requirements with Ameren Illinois for electrical service modifications, temporary gas service disconnection/reconnection, and compliance with the 2023 National Electrical Code and NEC Section 240.21(B) for feeder tap installation.

The specification sheet establishes that all work must comply with manufacturer's written instructions for equipment installation, include legend plates identifying all service disconnects and panelboards, and incorporate weatherproof NEMA 3R-rated electrical enclosures. The document indicates that IDOT staff will perform surface material removal, backfill material and compaction, and aggregate sub-base replacement, while the contractor is responsible for equipment provision, programming, coordination, and utility connections. Demolition notes detail the removal of existing overhead service entrance conductors, electrical meter, weatherhead, and above-grade feeder circuitry while abandoning certain below-grade circuitry in place. The project requires coordination with utility providers regarding service modifications, temporary gas service connections, and transformer configurations. All work is subject to coordination with IDOT for trenching requirements, conduit installation protocols, and pad excavation specifications.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KEYED NOTES:

SECURELY MOUNTED TO BUILDING.

PROVIDE 200A, 2-POLE, NEMA 3R ENCLOSED CIRCUIT BREAKER, 65,000 AIC MINIMUM,

SECURELY TO BUILDING AT 4'-0" INTERVALS.

PROVIDE (3) #4/0 AND #4 GROUND IN 2-1/2" CONDUIT ABOVE GRADE., MOUNTED

LISTED CONNECTORS.

PANELS "PP-1" AND "D0222 MDP". TAPS SHALL COMPLY WITH NEC 240.21(B) UTILIZING

EXTERIOR. PROVIDE TAPS IN FEEDER FROM ATS-1 FOR FEEDERS TO EXISTING

PROVIDE 36"x36"x8" NEMA 3R JUNCTION BOX MOUNTED SECURELY TO BUILDING

INSTALLATION WITH I.D.O.T.

COORDINATE TRENCHING REQUIREMENTS FOR BELOW-GRADE CONDUT

INSTALLATION WITH I.D.O.T.

COORDINATE TRENCHING REQUIREMENTS FOR BELOW-GRADE CONDUIT

AS HIGH AS PRACTICAL, FASTENED SECURELY TO BUILDING AT 4'-0" INTERVALS.

PROVIDE (3) #3 AND #8 GROUND IN 1-1/4" CONDUIT. MOUNT ABOVE-GRADE CONDUITS

AMEREN AS REQUIRED FOR ELECTRICAL SERVICE MODIFICATIONS.

COORDINATE DISCONNECTION/RECONNECTION OF ELECTRICAL SERVICE WITH

ON SHEET 8 FOR ADDITIONAL GENERATOR PAD INFORMATION.

REFER TO DETAIL 5 COORDINATE PAD INSTALLATION WITH CONDUIT INSTALLATIONS.

PAD SHALL EXTEND 1'-0" BEYOND LIMITS OF EQUIPMENT IN ALL DIRECTIONS.

REPLACEMENT.. COORDINATE PAD DIMESIONS WITH ACTUAL EQUIPMENT PROVIDED,

I.D.O.T. FOR PAD EXCAVATION REQUIREMENTS AND AGGREGATE REMOVAL AND

PROVIDE 10' +/- X 5' +/- X 6" THICK CONCRETE GENERATOR PAD.COORDINATE WITH

WELDS.

BELOW FINISH GRADE. CONNECTION TO GROUND RODS SHALL BE EXOTHERMIC

BARE STRANDED COPPER GROUND FIELD CONDUCTOR. GROUND FIELD SHALL BE 30"

PROVIDE 3/4" X 10'-0" COPPER CLAD GROUNDING ROD (TYP. OF 3) CONNECTED TO #2

GRADE TO PROTECT CONDUCTORS FROM PHYSICAL DAMAGE.

40 PVC CONDUIT TO TRIAD GROUND FIELD. SCHEDULE 80 PVC TO BE USED ABOVE

PROVIDE #2 INSULATED STRANDED COPPER GROUND CONDUCTOR IN 1/2" SCHEDULE

EXOTHERMIC WELDS.

BE 30" BELOW FINISH GRADE. CONNECTION TO GROUND RODS SHALL BE

#1/0 BARE STRANDED COPPER GROUND FIELD CONDUCTOR. GROUND FIELD SHALL

PROVIDE 3/4" X 10'-0" COPPER CLAD GROUNDING ROD (TYP. OF 3) CONNECTED TO

USED ABOVE GRADE TO PROTECT CONDUCTORS FROM PHYSICAL DAMAGE.

SCHEDULE 40 PVC CONDUIT TO TRIAD GROUND FIELD. SCHEDULE 80 PVC TO BE

PROVIDE #1/0 INSULATED STRANDED COPPER GROUND CONDUCTOR IN 3/4"

SECURELY TO BUILDING AT 4'-0" INTERVALS.

PROVIDE 2 SETS OF (3) #3/0 AND #3 GROUND IN (2) 2" CONDUIT ABOVE-GRADE. MOUNT

AND CONDUITS FOR EACH CIRCUIT PER MANUFACTURER'S WRITTEN INSTRUCTIONS.

FROM PANEL "PP-1" TO GENERATOR (GEN-1). PROVIDE BREAKERS, CONDUCTORS

CHARGER, ETC) AS REQUIRED PER MANUFACTURER'S WRITTEN REQUIREMENTS

PROVIDE MAINTENANCE CIRCUITS IN 1" CONDUIT (ENGINE BLOCK HEATER, BATTERY

CONDUIT/CONDUCTORS PER MANUFACTURER'S WRITTEN INSTRUCTIONS.

GENERATOR (GEN-1) FOR CONTROL SYSTEM. PROVIDE QUANTITY OF

WRITTEN INSTRUCTIONS FROM AUTOMATIC TRANSFER SWITCH (ATS-1) TO

PROVIDE CONTROL WIRING IN 1" CONDUIT OR AS REQUIRED PER MANUFACTURER'S

COORDINATE WITH I.D.O.T. FOR REQUIRED LIMITS OF REMOVAL.

MATERIAL AS REQUIRED FOR CONCRETE PAD AND CONDUIT INSTALLATION.

I.D.O.T. STAFF SHALL REMOVE AND REPLACE EXISTING AGGREGATE SUB-BASE

WIRES TO NEW GROUND BAR.

PROVIDE GROUND BAR IN PANEL. RECONNECT EXISTING BRANCH CIRCUIT GROUND

FROM NEUTRAL BAR AND RECONNECT TO NEW GROUND BAR.

EXISTING PANEL "D0222". DISCONNECT EXISTING BRANCH CIRCUIT GROUND WIRES

EXISTING POWER PANEL "D0222" TO REMAIN. PROVIDE NEW GROUND BAR IN

REFER TO PANEL SCHEDULE ON SHEET 7 FOR BREAKER REQUIREMENTS.

REMAIN. RECONNECT EXISTING BRANCH CIRCUIT GROUND WIRES TO GROUND BAR.

PROVIDE BREAKERS AS REQUIRED TO RECONNECT EXISTING BRANCH CIRCUITRY TO

TRENCHING, BACKFILL MATERIAL AND COMPACTION REQUIREMENTS WITH I.D.O.T.

WITH NON-SHRINK GROUT AND MAKE WATER/WEATHER TIGHT. COORDINATE

MAIN BREAKER IN TIRE SHED. SEAL ANNULAR SPACE AROUND CONDUIT PENETRATION

PROVIDE 100A, 240/120VAC, 1ϕ, 3W, NEMA 1, 12 CIRCUIT POWER PANEL WITH 100A

NEW GROUND BAR.

EXISTING BRANCH CIRCUIT GROUND WIRES FROM NEUTRAL BAR AND RECONNECT TO

BREAKER AND GROUND BAR IN EXISTING PANEL "D0222 BAY #2". DISCONNECT

EXISTING POWER PANEL "D0222 BAY #2" TO REMAIN. PROVIDE NEW 100A, 2-POLE MAIN

COMPACTION TO BE BY I.D.O.T.

BAR. ALL SURFACE MATERIAL REMOVAL/REPLACEMENT, BACKFILL MATERIAL AND

CIRCUIT GROUND WIRES FROM NEUTRAL BAR AND RECONNECT TO NEW GROUND

AND GROUND BAR IN EXISTING PANEL "D0223 5-BAY". DISCONNECT EXISTING BRANCH

EXISTING POWER PANEL "D0223 5-BAY" TO REMAIN. PROVIDE NEW 40A MAIN BREAKER

ADDITIONAL INFORMATION

MATERIAL AND COMPACTION TO BE BY I.D.O.T. REFER TO DETAIL 2 ON SHEET 8 FOR

MAIN BREAKER. ALL SURFACE MATERIAL REMOVAL/REPLACEMENT, BACKFILL

2-POLE ENCLOSED CIRCUIT BREAKER TO MAIN DISTRIBUTION PANEL "D0222 MDP"

PROVIDE (3) #4/0 AND #4 GROUND IN 2-1/2" CONDUIT BELOW-GRADE FROM NEW 200A,

(FUSED AT 400 AMPS), SECURELY MOUNTED TO BUILDING EXTERIOR.

PROVIDE 400A, NEMA 3R, HEAVY-DUTY SERVICE RATED FUSED DISCONNECT SWITCH

INSTALLATION AND LOCATION.

AUTOMATIC TRANSFER SWITCH WITH AMEREN REGARDING REQUIREMENTS,

(ATS-1), SECURELY MOUNTED TO BUILDING EXTERIOR. COORDINATE INSTALLATION OF

PROVIDE NEMA 3R, 400A, 240/120VAC, 1ϕ, 3W, 3-POLE AUTOMATIC TRANSFER SWITCH

DISCONNECTION.

GENERATOR. COORDINATE WITH AMEREN FOR TEMPORARY GAS SERVICE

PROVIDE PRESSURE REGULATOR, STRAINER AND SHUT-OFF VALVE IN GAS PIPING TO

CONTRACTOR TO FIELD VERIFY SIZE OF EXISTING NATURAL GAS SERVICE PIPING.

EQUIPMENT INSTALLED) TO EXISTING 2" NATURAL GAS SERVICE PIPING.

GAS FEED FOR GENERATOR (COORDINATE REQUIREMENTS WITH ACTUAL

WEATHERPROOF HOUSING. PROVIDE FITTINGS AS REQUIRED TO CONNECT NEW 2"

PROVIDE 96KW/120KVA STANDBY NATURAL GAS ENGINE GENERATOR (GEN-1) IN

BOND NEUTRAL AND GROUNDING LUGS IN THIS LOCATION PER NEC REQUIREMENTS.

X

DEMOLITION NOTES:

PANEL"D0222 MDP" TO PANEL "D0222".

REMOVE EXISTING FEEDER CIRCUITRY AND ABOVE-GRADE CONDUIT FROM

PANEL "D0223 5 BAY". ABANDON EXISTING BELOW GRADE FEEDER CIRCUITRY IN PLACE.

REMOVE EXISTING ABOVE-GRADE FEEDER CIRCUITRY FROM PANEL "D0222 MDP" TO

TIRE SHED PANEL. ABANDON EXISTING BELOW GRADE FEEDER CIRCUITRY IN PLACE.

REMOVE EXISTING ABOVE-GRADE FEEDER CIRCUITRY FROM PANEL "D0222 BAY #2" TO

EXISTING MAIN DISTRIBUTION PANEL "PP-1".

REMOVE EXISTING CONDUIT/CONDUCTORS FROM EXISTING 400A CT METER CABINET TO

REMOVE EXISTING GROUND FIELD OR ABANDON IN PLACE.

#2".

REMOVE EXISTING FEEDER CIRCUITRY FROM PANEL "D0222 MDP" TO PANEL "D0222 BAY

RECONNECTED TO NEW BREAKERS.

REMOVE EXISTING TIRE SHED PANEL, EXISTING BRANCH CIRCUITRY TO REMAIN AND BE

ENTRANCE CONDUCTORS WITH AMEREN.

CONDUCTORS. COORDINATE DISCONNECTION AND REMOVAL OF OVERHEAD SERVICE

REMOVE EXISTING ELECTRICAL METER, WEATHERHEAD, AND SERVICE ENTRANCE 1

X

TO REMAIN

PANEL "PP1"

DISTRIBUTION

, 3W MAIN ϕ1

AMP, 240/120V,

EXISTING 400

TO REMAIN

PANEL "252-A"

, 3W ϕ1

AMP, 240/120V,

EXISTING 100

100A

TO REMAIN

CT METER/CABINET

EXISTING 400 AMP

REMAIN

PANEL "D0222 MDP" TO

1Ø, 3W MAIN DISTRIBUTION

EXISTING 200 AMP, 240/120V,

REMOVED BY UTILITY COMPANY

TRANSFORMER TO REMAIN OR

EXISTING UTILITY POLE MOUNTED

TO BE REMOVED

EXISTING METER

200A

50A

40A

100A60A

REMAIN

BAY #2" TO

PANEL "D0222

, 3W ϕ1

AMP, 240/120V,

EXISTING 100

REMOVED

TO BE

CABINET

200A CT

EXISTING

(815)343-8303

ATHOMPSON4@AMEREN.COM

ELECTRIC & GAS: AMEREN ILLINOIS

LADD IDOT YARD;

UTILITY INFORMATION

TO REMAIN

MOUNTED TRANSFORMER

, 3W PAD ϕAC, 1120/240 V

EXISTING 50 KVA, 7200V TO

SCALE:

NO SCALE

EXISTING LADD MAINTENANCE YARD - ONE LINE ELECTRICAL DIAGRAM

GENERATOR DATA - LADD

KVA (MINIMUM)

VOLTAGE

FREQUENCY

PHASE

WIRE

POWER FACTOR

FUEL

AUTOMATIC TRANSFER SWITCH

SCALE:

NO SCALE

PROPOSED LADD MAINTENANCE YARD - ONE LINE ELECTRICAL DIAGRAM

ATS-1

400A

GN

6 79 8

TO REMAIN

MOUNTED TRANSFORMER

, 3W PAD ϕ120/240V, 1

EXISTING 50 KVA, 7200V TO

N G

L

NE

100A

400A

"PP-1" TO REMAIN

3W MAIN DISTRIBUTION PANEL

,ϕEXISTING 400 AMP, 240/120V, 1

TO REMAIN

PANEL "252-A"

, 3W ϕ1

AMP, 240/120V,

EXISTING 100

"D0222 MDP" TO REMAIN

3W MAIN DISTRIBUTION PANEL

, ϕEXISTING 200 AMP, 240/120V, 1

100A

50A

40A

MB

100A

100A

PANEL

3W TIRE SHED

, ϕ240/120V, 1

100 AMP,

TO REMAIN

PANEL "D0222"

, 3W ϕ1

AMP, 240/120V,

EXISTING 50

BAY" TO REMAIN

PANEL "D0223 5

, 3W ϕ1

AMP, 240/120V,

EXISTING 40

G N

200A

MB

100A

ONE LINE DIAGRAM NOTES:

EQUIPMENT IS REMOVED WHILE ALTERNATE SOURCE IS ENERGIZED".

SEPARATELY DERIVED SYSTEM) LABELED "WARNING SHOCK HAZARD EXISTS IF GROUNDING ELECTRODE CONDUCTOR OR BONDING JUMPER CONNECTION IN THIS

INCLUDE WEATHERPROOF ENGRAVED PHENOLIC LEGEND PLATE FOR EACH SERVICE DISCONNECT THAT HAS A BACKUP ENGINE GENERATOR SET (THAT IS NOT A 9.

INCLUDE COPPER EQUIPMENT GROUND BAR FOR MAIN DISTIBUTION PANEL "D0222 MDP" AND ALL SUBPANELS.8.

EQUIPMENT.

DISCONNECTS, EQUIPMENT, ETC. IDENTIFYING THE EQUIPMENT AND/OR NOTING THE RESPECTIVE INCLUDE LEGEND PLATES FOR ALL PANELBOARDS, LOAD CENTERS, 7.

WEATHERPROOF ADHESIVE AND/OR MACHINE SCREWS.

OR PHENOLIC MATERIAL, 1/4” HIGH BLOCK LETTERS ON A WHITE BACKGROUND. SECURE WITH LEGEND PLATES SHALL BE WEATHERPROOF ENGRAVED PLASTIC 6.

PHASE, 3 WIRE, NOTE MAIN DISTRIBUTION PANEL "PP1" IS BACKED UP BY WHOLE YARD STAND-BY GENERATOR”.

DISTRIBUTION PANEL IN BUILDING D0390 LABELED “PP1, FED FROM AUTO TRANSFER SWITCH, 240/120VAC, 1 FURNISH AND INSTALL A LEGEND PLATE FOR THE MAIN 5.

GENERATOR NEUTRAL IS BONDED TO GROUND AT THE MAIN SERVICE DISCONNECT”.

GENERATOR BREAKER LABELED “GENERATOR BREAKER, 400A, 240/120VAC, 1 PHASE, 3 WIRE” AND “NOTE FURNISH AND INSTALL A LEGEND PLATE FOR THE ENGINE 4.

-240/120VAC, 1 PHASE, 3 WIRE

OR-EMERGENCY SOURCE FROM WHOLE YARD STAND-BY ENGINE GENERAT

-NORMAL SOURCE FROM UTILITY TRANSFORMER THROUGH MAIN DISTRIBUTION PANEL "PP1"

-AUTO TRANSFER SWITCH

SWITCH AS FOLLOWS:FURNISH AND INSTALL LEGEND PLATE FOR AUTOMATIC TRANSFER 3.

TO GROUND AT SERVICE DISCONNECT”.

DISCONNECT LABELED “BUILDING MAIN SERVICE DISCONNECT”AND “NOTE GENERATOR NEUTRAL IS BONDED FURNISH LEGEND PLATES FOR THE BUILDING MAIN SERVICE 2.

SWITCH SHALL BE INSTALLED IN FULL COMPLIANCE WITH AMEREN REQUIREMENTS.SERVICE ENTRANCE EQUIPMENT, GENERATOR AND TRANSFER 1.

MB

40A

400A

GN

TO REMAIN

METER/CABINET

400 AMP CT

EXISTING

REMAIN

BAY #2" TO

PANEL "D0222

, 3Wϕ1

AMP 240/120V,

EXISTING 100

TO REMAIN

PANEL "D0222"

, 3W ϕ1

AMP, 240/120V,

EXISTING 50

REMAIN

5 BAY" TO

PANEL "D0223

, 3W ϕ1

AMP, 240/120V,

EXISTING 40

(GEN-1)120

240/120

60HZ

.8

NATURAL GAS

(ATS-1)NEMA 3R400A

GGG

101010

14 14

REMOVED

PANEL TO BE

TIRE SHED

1ϕ, 3W

AMP, 240/120V,

EXISTING 60

400A

G N

200A

SECTION COUNTY

ILLINOIS

TOTAL

SHEETS

SHEET

NO.RTE.

(011,037) ELE,EG,MG

USER NAME =

PLOT DATE = DATE

DESIGNED

CHECKED

DRAWN

REVISED

REVISED

REVISED

REVISED

F.A.

SHEET OF 8 SHEETS STA. TO STA.

CWB

5/1/2025

8/5/2026

CONTRACT NO.

SCALE:

STATE OF ILLINOIS

DEPARTMENT OF TRANSPORTATION

ONE LINE DIAGRAMS - LADD MAINTENANCE YARD

I:

\J o b s \2

\1

.2

.0

O

P S

W O

-3

L a d d a n d S y c a m o re

G e n e ra to rs

\D ra w in g s \S h e e t\ .d g n

F

IL

E N

A M

E

E

.3

S h e e t]

M O

D E

L cbozarth

8/5/2026

N/A BUREAU

professional design firm no. 184-005965 www.prairieengineers.com

Copyright Prairie Engineers of Illinois, P.C. 2023

Columbia, IL 62236

(217) 605-0403

404 N. Main Street

Prairie Engineers, P.C.

Expires: 11/30/2025 Date: 5/1/2025

File details come from the government source that posted it. Updated .