Joaquin_Murriera_Park_-_Splash_Pad_Plans.pdf
PDF 35 MB Posted
- Attached to
- Joaquin Murrieta Park Splash Pad
- Solicitation number
- 250041
- Issued by
- Pima County, Tucson City, Arizona
About this file
The document is a comprehensive set of engineering and design plans for the Joaquin Murrieta Park Splash Pad project, prepared for the City of Tucson, Arizona. The project involves constructing a splash pad facility at 1400 N. Silverbell Road, with detailed specifications for site improvements, electrical systems, plumbing, and aquatic feature design. The splash pad will feature multiple water play elements, including jet nozzles, spray cannons, and interactive water features, with a total surface area of approximately 2,935 square feet. The design includes a dedicated equipment room, circulation pumps, filtration systems, chemical treatment equipment, and associated infrastructure such as fencing, concrete work, and landscaping.
The project plans specify extensive technical details for water circulation, with a design flow rate of 145 gallons per minute and multiple pumps dedicated to different water feature zones. The splash pad will include sanitation equipment like a chemistry controller, UV system, and backwash tank, with precise specifications for valves, gauges, and electrical components. Electrical systems include specialized control mechanisms, such as a Pentair spa remote button and controller, and the facility will adhere to National Electric Code requirements for grounding and safety. The documentation indicates this is a public infrastructure project funded by municipal resources, with comprehensive design specifications to ensure safe, efficient, and compliant water feature installation.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
X X
X X
X
X X
51014 2320.753
GV
A
AA
A
80356 2326.298
CONC1
8" W
8" W
8" W
8" W
8" W
8" W
4''W
4''W
4''W
4''W
4''W
GAS
GAS
G
AS
G
AS
G
AS
G
AS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS GAS
GAS
GAS
GAS
G
AS
A
AA
A
A
A
A
E
E
E
E
E
E
S
IL
V E
R C
R O
FT
W
A S
H
N
. SILVERBELL RO
AD
W. ELM STREET
INDEX OF SHEETS
SITE MAP
LOCATION
PROJECT
ANKLAM WASH
100% BID SET
NOT FOR
CONSTRUCTION
GENERAL NOTES:
GRADING & CONSTRUCTION NOTES:
CLEARING & GRUBBING NOTES:
DEVELOPMENT PACKAGE NOTES:
DEVELOPMENT PACKAGE CALCULATIONS:
ZONING AND LAND USE NOTES:
LIST OF DEFERRED SUBMITTALS/SEPARATE PERMIT ITEMS:
LIST OF STRUCTURAL ITEMS INCLUDED IN PERMIT (REQUIRES SPECIAL INSPECTION)
BUILDING CODE ANALYSIS:
100% BID SET
NOT FOR
W
G
AS
G
AS
G
AS
G
AS
G
AS
G
AS
G
AS
+0" -2" -3" -3" -2"
+0"
-1"-1"
SS
SS
N
SILVERBELL RO
AD
CONSTRUCTION NOTES
Construct 4-inch thick concrete sidewalk as per COT std. dtl. 200, Class 'A', 3,000 PSI. Concrete pavement as per PAG specification section 908 and 1006 with sub-grade preparation as per geotechnical report. As per section 1 on sheet PVD01.
QTY
2 Contractor to install ramada as per details 1, 2, & 3 on sheet PVD03, size per plan.
3 Splash pad see, splash pad plans for details.
2,935 SF
3 EA
1 EA
Install aluminum fencing and gates at splash pad with powder coat paint finish, color by owner as per detail 4 and 5 on sheet PVD02.
4 212 LF
5 10' custom concrete bench as per detail 4 on sheet PVD03. 1 EA
6 Concrete trash can cover as per detail 5 on sheet PVD03. 1 EA
7 6' Masonry Wall with single gate as per detail 3 and 6 on sheet
PVD02.
80 LF
8 Concrete header as per detail 1 on sheet PVD02. 315 LF
100% BID SET
NOT FOR
CONCRETE REINFORCEMENT SECTION - TYPICAL ALL CONCRETE PAVEMENT
SCALE: NTS1 EXPANSION JOINT - CONCRETE PAVEMENT
SCALE: NTS2
CONTRACTION JOINT, CONCRETE PAVEMENT
SCALE: NTS3
EXPANSION JOINT DETAIL, CONCRETE PAVEMENT
SCALE: NTS6
COLD JOINT FOR SEPARATE POUR, CONCRETE PAVEMENT
SCALE: NTS4
SAWCUT DETAIL, CONCRETE PAVEMENT
SCALE: NTS7
SAW CUT JOINT, CONCRETE PAVEMENT
SCALE: NTS5
100% BID SET
NOT FOR
CONCRETE HEADER AT TURF/D.G.
3/4" RADIUS ALL EXPOSED EDGES
(TYP)
CAST-IN-PLACE OR EXTRUDED
CONCRETE CURB WITH MEDIUM
BROOM FINISH
FINISHED GRADE OF TURF
FINISHED GRADE OF D.G.
COMPACTED SUBGRADE
NOTE:
1. HEADER SHALL BE FLUSH WITH ADJACENT WALK/PATH, PAVEMENT OR CURB.
2. LANDSCAPE ARCHITECT SHALL APPROVE FORMWORK PRIOR TO PLACING CONCRETE IF
POURED IN PLACE.
3. CONCRETE SHALL BE MAG. CLASS "B"
4. EXPANSION JOINTS @ 30', CONTROL JOINTS 10' O.C.
5. STRAIGHT SECTIONS TO MEET CURVED SECTIONS AT TRUE TANGENT POINTS WITH NO
BROKEN CURVE SECTIONS.
6. CURVED SECTIONS TO BE FORMED IN SMOOTH, EVEN CURVES AS SHOWN ON PLANS.
7. FORM STAKING SHALL NOT ALLOW DEFORMING OR LEAKING. ALL SPILL OF EXCESS
CONCRETE SHALL BE CLEANED UP AND REMOVED FROM SITE BY CONTRACTOR.
3"
6"
6" 1"
SPECIAL NOTE:
FINISHED GRADE OF TURF AND D.G. TO BE
FLUSH W/ HEADER IN DRAINAGE AREAS. THE
CONTRACTOR SHALL IDENTIFY THESE AREAS IN
THE FIELD PRIOR TO CONSTRUCTION.
3/4" RADIUS (TYP)
CONCRETE SLAB, WALK, OR
CURB.
COMPACTED SUBGRADE
(TYP)
FINISH GRADE/D.G. OR
PLANTING AREA
NOTE:
1.FINISH GRADE-HOLD DOWN 1" FROM TOP OF WALK, SLAB, OR CURB. SLOPE AWAY AT 2% FOR 3', THEN SIDE SLOPE TO MEET EXISTING GRADE AT 5:1 MAX., OR AS SHOWN ON THE GRADING
PLANS.
2%
3'-0" MIN.
5:1 MAX.
1"
CONCRETE HEADER AT TURF/ D.G.
SCALE: N.T.S.1 FINISH GRADE AT SLAB/ CURB
SCALE: N.T.S.2
SCALE: N.T.S.4 AMERISTAR ECHELON II GENESIS FENCE
SCALE: N.T.S.5 AMERISTAR ECHELON II GENESIS DOUBLE GATE
SCALE: N.T.S.6 AMERISTAR ECHELON II GENESIS SINGLE GATE
MASONRY MATERIAL NOTES:
6' MASONRY WALL
SCALE: N.T.S.3
JOINT NOTES:
100% BID SET
NOT FOR
NORTHWEST STYLE RAMADA BY CLASSIC
RECRATION STRUCTURES - IMAGE
SCALE: N.T.S.1 SCALE: N.T.S.2 SCALE: N.T.S.3
NORTHWEST STYLE RAMADA BY CLASSIC
RECRATION STRUCTURES - FRONT ELEVATION
NORTHWEST STYLE RAMADA BY CLASSIC
RECRATION STRUCTURES - SIDE ELEVATION
SCALE: N.T.S.5 CONCRETE TRASH CAN COVER (#514) BY OUTDOOR CREATIONS INC.
SCALE: N.T.S.4 10' CUSTOM CONCRETE BENCH
100% BID SET
NOT FOR
30.10SW30.01SW
30.01SW
29.94SW
29.94SW
30.01SW
29.94SW
29.94SW
30.01SW
29.94SW
30.01SW
29.94SW
30.01SW
30.10SW
30.10SW
31.10SW
31.10SW
31.10SW
30.10SW
30.10SW
31.10SW
31.10SW
30.96SW
30.96SW
29.98SW
30.10SW
30.01P
29.93P 29.85P
29.76R
29.76R
29.76R 29.85P
29.93P
29.85P
29.93P 30.01P
30.10SW30.10SW
30.10SW
30.10SW
30.01SW
30.01P
30.01SW
29.93SW
29.85SW
29.85SW
29.93SW
30.01SW
29.85SW
29.93SW
30.01SW
30.01SW
RIM:30.87
INV:30.37
RIM:30.87
INV:30.54
W
W
G
AS
G
AS
G
AS
G
AS
G
AS
G
AS
G
AS
+0" -2" -3" -3" -2"
+0"
-1"-1"
SS
SS
N
SILVERBELL RO
AD
LEGEND
TC - TOP OF CURB
P - PAVEMENT
C - CONCRETE
G - GUTTER
BW - BOTTOM OF WALL
TW - TOP OF WALL
FG - FINISH GRADE
INV - INVERT
SW - SIDEWALK
SC - SCUPPER
100% BID SET
NOT FOR
SS
W
W
G
AS
G
AS
G
AS
G
AS
G
AS
G
AS
G
AS
+0" -2" -3" -3" -2"
+0"
-1"-1"
N
SILVERBELL RO
AD
1 Install 3-inch SDR21 rubber gasket water line (blue pipe color) with all necessary fittings and pipe bedding and trench backfill, tracer wire and marking tape as per Tucson Water Std Dtl SD-115 & SD-116. Install thrust blocking as per SD 610.
2 Install 2-inch SDR21 rubber gasket water line (blue pipe color) with all necessary fittings and pipe bedding and trench backfill, tracer wire and marking tape as per Tucson Water Std Dtl SD-115 & SD-116. Install thrust blocking as per SD 610.
3 Install 1-inch pvc, sch 80 water line with all necessary fittings and pipe bedding and trench backfill, tracer wire and marking tape as per Tucson Water Std Dtl SD-115 & SD-116. Install thrust blocking as per SD 610.
4 Install 22.5° SDR21 rubber gasket bend, size as per plan.
12 Install 1-inch ball valve with valve box and cover as per Tucson Water SD-300.
13 Install 2-inch ball valve with valve box and cover as per Tucson Water SD-300.
7 Install 3"x3"x1" sch 80 pvc tee with thrust blocking as per Tucson Water std. dtl. SD 610.
15 Install MDF Locable hose bib as per detail 7 on sheet PVD13.
1. All water line construction shall be as per the Tucson Water Standard Specification and details manual.
2. Horizontal separation of waste water and water utilities shall be 6' and vertical separation of utilities shall be 2' minimum unless otherwise notes.
3. All water / sanitary sewer crossings shall be per Tucson Water std. dtl.
SD-106 to provide minimum 2 ft vertical separation from outer water pipe diameter with outer sanitary sewer pipe diameter. Reclaimed water line shall be treated as sanitary sewer lines and require the same vertical and horizontal separation from potable water lines.
4. Restrain all joints and fittings prior to construction.
5. Contractor to field verify utilities prior to construction.
NOTES
PRIVATE WATER CONSTRUCTION NOTES
1 EA
22 LF
28 LF
76 LF
2 EA
1 EA
1 EA
2 EA
QTY
10 Install 2"x2"x2" sch SDR21 rubber gasket tee with thrust blocking as per Tucson Water std. dtl. SD 610.
1 EA
14 Install 3-inch gate valve with valve box and cover as per Tucson Water SD-300.
1 EA
9 Install 3"x3"x3" sch 80 pvc tee with thrust blocking as per Tucson Water std. dtl. SD 610.
1 EA
100% BID SET
NOT FOR
6" INV:2325.53
6" INV:2325.42
W
W
G
AS
G
AS
G
AS
G
AS
G
AS
G
AS
G
AS
+0" -2" -3" -3" -2"
+0"
-1"-1"
N
SILVERBELL RO
AD
SANITARY SEWER CONSTRUCTION NOTES
Install 6-inch pvc sdr 35, sanitary sewer line with all necessary fittings and pipe bedding and trench backfill, tracer wire and marking tape as per Pima County Wasterwater Reclamation std dtl RWRD 104.
Install sanitary sewer clean out as per Pima County Wastewater Reclamation std. dtl. RWRD 404.
Install sanitary sewer two way building clean out.7
61 LF
QTY
1 EA
1 EA
1. HORIZONTAL SEPARATION OF WASTE WATER AND WATER UTILITIES SHALL BE 6'
AND VERTICAL SEPARATION OF UTILITIES SHALL BE 2' MINIMUM UNLESS OTHERWISE
NOTES.
2. ALL WATER / SANITARY SEWER CROSSINGS SHALL BE AS PER TUCSON WATER
STD. DTL. SD-106 TO PROVIDE MINIMUM 2 FT VERTICAL SEPARATION FROM OUTER
WATER PIPE DIAMETER WITH OUTER SANITARY SEWER PIPE DIAMETER. WATER
LINE TO REQUIRE 2 FT HORIZONTAL SEPARATION FROM OUTER WATER PIPE
DIAMETER WITH OUTER SANITARY SEWER PIPE DIAMETER. RECLAIMED WATER LINE
SHALL BE TREATED AS SANITARY SEWER LINES AND REQUIRE THE SAME VERTICAL
AND HORIZONTAL SEPARATION FROM POTABLE WATER LINES.
3. CONTRACTOR TO FIELD VERIFY UTILITIES PRIOR TO CONSTRUCTION.
NOTES
100% BID SET
NOT FOR
LOCKOUT - TAGOUT - TESTOUT
100%
REVIEW
NOT FOR
CONSTRUCTION
REFER TO PROJECT MANUAL FOR SPECIAL
MATERIAL PROCUREMENT AND LABOR WAGE
REQUIREMENTS APPLICABLE TO THIS PROJECT
c a d se rv e r2 C A D D D a ta p ro je c ts
Jo a q u in
M u rr ie ta
P a rk
R E V
IS
IO
N
P A C K A G E (1 E
(E
LN
.d w g
:5 :4
P M
LIGHT FIXTURE NOTES:
100%
REVIEW
NOT FOR
CONSTRUCTION
LIGHTING FIXTURE SCHEDULE
c a d se rv e r2 C A D D D a ta p ro je c ts
Jo a q u in
M u rr ie ta
P a rk
R E V
IS
IO
N
P A C K A G E (1 E
(E
LN
d w g
:5 :0
P
X
X
X X
X X
X
XXXX
X X
X
X
X
X
X X
X
X
X
XX
X X
X X
X X X
X X
X X
X
X X
X
XX
X
X
X
X
X
X
X X
X
XX
60257 2326.400
SCUP B
60258 2326.522
SCUP
60259 2326.481
SCUP
60260 2326.535
SCUP
60261 2326.572
SCUP
60262 2326.528
SCUP60263
2326.541
SCUP PC
60267 2326.497
60268 2326.208
SCUP E
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X X X X X X
X X
X X
X
X
X
X
X
X
X X
X X
X X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
XX
XXXXXXXXXXX
X
X X
X X
X X
X X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
UGE
UGE
U G
E
UGE
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
W A
P A
FOx FOx FOx FOx FOx FOx
ANKLAM WASH
S
IL
V
E R
C R
O
FT
W A
S H
N. SILVERBELL RO
AD
N. SILVERCRO
FT AVE.
W. ELM STREET
SEE SHEET ESP01
ELECTRICAL KEYNOTES THIS SHEET ONLY
1" = 100' - 0"
OVERALL ELECTRICAL REFERENCE SITE PLAN1
10050 200
SCALE 1" = 100'
LOCKOUT - TAGOUT - TESTOUT
100%
REVIEW
NOT FOR
CONSTRUCTION
c a d se rv e r2 C A D D D a ta p ro je c ts
Jo a q u in
M u rr ie ta
P a rk
R E V
IS
IO
N
P A C K A G E (1 E S
(E S P d w g
:5 :0
P
X
X
X
X X
X
X
X
X
X X
X
X
X
X
X X
X
X
X X
X
X
X
X
X X
X
X
X
UGE UGE UGE UGE UGE UGE UGE
P P P P P P P P P
UGE
UGE
P
P
UG
E
U G
E
P P
U G
E U
G E
U G
E U
G E
P P
P P
LOCKOUT - TAGOUT - TESTOUT
100%
REVIEW
NOT FOR
CONSTRUCTION
ELECTRICAL KEYNOTES
(NOT ALL KEYNOTES USED ON THIS SHEET)
ALL WORK SHOWN IS
EXISTING TO REMAIN, U.N.O.
c a d se rv e r2 C A D D D a ta p ro je c ts
Jo a q u in
M u rr ie ta
P a rk
R E V
IS
IO
N
P A C K A G E (1 E S
(E S P d w g
:5 :3
P
Splash Pad Equipment
RR 3
RR 2
RR 1
RR 4
205CHLOR
ACID
Splash Pad Equipment
RR 3
RR 2
RR 1
RR 4
205CHLOR
ACID
Splash Pad Equipment
RR 3
RR 2
RR 1
RR 4
205CHLOR
ACID
100%
REVIEW
NOT FOR
CONSTRUCTION
LOCKOUT - TAGOUT - TESTOUT
ELECTRICAL KEYNOTES THIS SHEET ONLY
1/8" = 1' - 0"
SPLASHPAD RESTROOM BLDG. -
SPECIAL SYSTEMS PLAN3 84 16
SCALE 1/8" =1'-0"
84 16
SCALE 1/8" =1'-0"
1/8" = 1' - 0"
SPLASHPAD RESTROOM BLDG. -
GROUNDING SYSTEMS PLAN4 84 16
SCALE 1/8" =1'-0"
84 16
SCALE 1/8" =1'-0"
1/4" = 1' - 0"
SPLASHPAD RESTROOM BLDG. - POWER PLAN
SCALE 1/4"=1'-0"
42 8
1/8" = 1' - 0"
SPLASHPAD
RESTROOM BLDG. - LIGHTING PLAN2 84 16
SCALE 1/8" =1'-0"
84 16
SCALE 1/8" =1'-0"
NOT USED
R p ro je c ts
Jo a q u in
M u rr ie ta
P a rk
R E V
IS
IO
N
P A C K A G E (5 E
(E
LP
d w g
:3 :1
P M M o n ra d sv e la sc o
NOT TO SCALE
NEW ELECTRICAL ONE LINE DIAGRAM2
ELECTRICAL KEYNOTES
PROVIDE APPROVED ARC-FLASH
HAZARD WARNING ON ALL REQUIRED
ELECTRICAL EQUIPMENT PER NEC 110.16
Electric Arc Flash Hazard Will cause severe injury or death Wear proper personal protective equipment before opening or performing diagnostic measurements while energized. (See NFPA 70E)
(THIS SHEET ONLY)SHORT CIRCUIT CALCULATIONS:
LOAD CONSIDERATIONS:
M
LOCKOUT - TAGOUT - TESTOUT
100%
REVIEW
NOT FOR
CONSTRUCTION
ALL WORK SHOWN IS
EXISTING TO REMAIN U.N.O.
c a d se rv e r2 C A D D D a ta p ro je c ts
Jo a q u in
M u rr ie ta
P a rk
R E V
IS
IO
N
P A C K A G E (1 E
(E
LS
d w g
:4 :3
P
REVIEW
NOT FOR
CONSTRUCTION
LOCKOUT - TAGOUT - TESTOUT
R p ro je c ts
Jo a q u in
M u rr ie ta
P a rk
R E V
IS
IO
N
P A C K A G E (7 E
(E
LS
d w g
:3 :4
P M M o n ra d sv e la sc o
REVIEW
NOT FOR
CONSTRUCTION
NOT TO SCALE
RESTROOM DOOR CONTROL DETAIL1
NOT TO SCALE
RESTROOM DOOR CONTROL DIAGRAM2
NOT TO SCALE
TRENCH DETAIL4
NOT TO SCALE
AREA LIGHT - FLUSH POLE BASE DETAIL3
c a d se rv e r2 C A D D D a ta p ro je c ts
Jo a q u in
M u rr ie ta
P a rk
R E V
IS
IO
N
P A C K A G E (1 E
(E
LD
d w g
:4 :5
P
PLANTING NOTES MAINTENANCE SCHEDULE:
PLANTING LEGEND
100% BID SET
NOT FOR
G
AS
G
AS
G
AS
G
AS
G
AS
G
AS
G
AS
+0" -2" -3" -3" -2"
+0"
-1"-1"
SS
SS
N
SILVERBELL RO
AD
PLANTING LEGEND
CONSTRUCTION NOTES
QTY
Construct 4-inch thick concrete sidewalk as per COT std. dtl. 200, Class 'A', 3,000 PSI. Concrete pavement as per PAG specification section 908 and 1006 with sub-grade preparation as per geotechnical report. As per section 1 on sheet PVD01.
Contractor to install ramada as per details 1, 2, & 3 on sheet PVD03, size per plan.
Splash pad see, splash pad plans for details.
2,935 SF
3 EA
1 EA
Install aluminum fencing and gates at splash pad with powder coat paint finish, color by owner as per detail 4 and 5 on sheet PVD02.
212 LF
8 Concrete header as per detail 1 on sheet PVD02. 315 LF
100% BID SET
NOT FOR
SCALE: N.T.S.1 TREE PLANTING DETAIL
SCALE: N.T.S.2
SCALE: N.T.S.4 FINISH GRADE AT CURB AND PAVING
TREE STAKING DETAIL
SCALE: N.T.S.3 TREE PLANTING AT SIDEWALK DETAIL
100% BID SET
NOT FOR
FOx
FOx
FOx
6''
6''
6''
6''8''
8''
8''
4''
4'
4'
4'
4''
4''
4''
A86
1"
TREE
A85
Q
A82
1"
TREE
A83
1"
TREE
A84
1"
TREE
1.5
1.5
A55
1"
TURF
A54
2"
TURF
8 4
4 4
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Q
A44
1.5"
TURF
A43
1.5"
TURF
A42
2"
TURF
A46
1"
TURF
A45
1"
TURF
A47
1.5"
TURF
A48
2"
TURF
8 4
3"
1.5"
1.5"
2.5"
2"
2"
1.5"
1.5"
2" 2" 1.5"2"
2"
1.5"
1.5"
2.5"
1.5"
1.5" 1.5"
2"
2" 1.5"
1.5"
3"
3"
2"
1.5"
1.5"
2"
1.5"
1.5"
2"
2"
1.5"
2.5"
2"
2"
1.5"
2.5" 2"
1.5"
2"
1.5"
2"
2"
1.5"
1.5" 2"
2"
1.5"
1.5"
2.5"
2"
SPLASHPAD PIPE
CONNECTION TO ORIGINAL
PLANS, TYPICAL
W LESTER ST
N
SILVERBELL RD
100%
REVIEW
NOT FOR
CONSTRUCTION
0' 30'15' 60' 90'
1" = 30'
LEGEND
SCH 40 PVC SPRINKLER LATERAL PIPE: 1" UNLESS OTHERWISE SHOWN
1" SCH 40 PVC PVC TREE DRIP LATERAL PIPE: REFER TO DETAILS
UNCONNECTED PIPE CROSSING
DRIP EMITTERS
HUNTER MPE-XX SERIES
EMITTER ACCESS SLEEVE: SALCO DAS-8
PLANT EMITTER QUANTITIES
ACCENTS/SHRUBS: ONE MPE-10 PER 6 PLANTS WITHIN 6'
CACTUS: ONE MPE-05
TREES: TWO MPE-20, 12 OPEN OUTLETS
ROTOR SPRINKLER: HUNTER I-20-04-SS-R @ 45 PSI
NOZZLE FLOW(GPM) RADIUS(FEET)
1.5 1.5 31' 2 2 34'
2.5 2.5 35' 3 3 38' 4 4 40' 5 5 42' 6 6 43' 8 8 44'
- VALVE CONTROLLER AND STATION NUMBER
- FLOW (GPM)
- VALVE SIZE (INCHES)
- ZONE DESCRIPTION
*ALL MAINLINE AND LATERAL PIPE IS TO BE PURPLE.
*ALL SPRINKLERS ARE TO BE INSTALLED ON HUNTER SWING JOINTS
TRANSITION POINT FROM ORIGINAL SITE IMPROVEMENT PLANS TO THESE SPLASH
PAD PLANS
A1
2"
GRASS
REFER TO JOAQUIN MURRIETA PHASE ONE SITE IMPROVEMENT PLANS DATED 08.11.2023 FOR IRRIGATION ON THE ENTIRE SITE.
CONTRACTOR IS RESPONSIBLE FOR CONFIRMING LOCATIONS AND PROPER OPERATION OF EXISTING IRRIGATION EQUIPMENT, INCLUDING PIPE ROUTING, OUTSIDE OF LIMIT OF WORK BOUNDARY PRIOR TO BIDDING AND CONSTRUCTION, AND REPORTING
ANY DISCREPANCIES IN WRITING TO CITY OF TUCSON REPRESENTATIVES.
100% BID SET
NOT FOR
CONSTRUCTION
https://www.aquaengineering.com/ https://www.aquaengineering.com/ https://www.aquaengineering.com/ https://www.aquaengineering.com/ https://www.aquaengineering.com/ https://www.aquaengineering.com/ https://www.aquaengineering.com/
SPN01
AQUATIC FEATURE DATA
1. SPLASH PAD (SURGE TANK)
PERIMETER: 40 FT.
SURFACE AREA: 96 SQFT.
APPROXIMATE VOLUME: 4,042 GAL
MINIMUM TURN OVER: 30 MIN
MINIMUM FLOW RATE: 144 GPM
DESIGN TURN OVER: 28 MIN
DESIGN FLOW RATE: 145 GPM
FILTRATION RATE: 10.26 GPSF
1. SPN01 SPLASH PAD COVER AND GENERAL NOTES
2. SPP01 SPLASH PAD SITE PLAN
3. SPD01 SPLASH PAD CUTSHEETS
4. SPD02 SPLASH PAD CUTSHEETS
5. SPD03 SPLASH PAD CUTSHEETS
6. SPD04 SPLASH PAD CUTSHEETS
7. SPD05 SPLASH PAD LAYOUT PLAN
8. SPD06 SPLASH PAD PLUMBING
9. SPD07 EQUIPMENT KEYNOTES
10.SPD08 SPLASH PAD SECTIONS
11.SPD09 SPLASH PAD DETAILS
12.SPD10 SPLASH PAD DETAILS
13.SPD11 SPLASH PAD DETAILS
14.SPD12 SPLASH PAD DETAILS
INSPECTIONS
SHEET INDEX
AQUATIC CONSULTANT
AQUADESIGN INTERNATIONAL
7536 N. LA CHOLLA BLVD.
TUCSON, AZ 85741
520-219-8929 Attn: TERRY JOHANSEN
POOL CONTRACTOR OR ARCHITECT SHALL NOTIFY AQUA DESIGN
INTERNATIONAL FOR THE FOLLOWING AQUATIC FEATURE INSPECTION
COORDINATION:
1. PLUMBING INSTALLATION AND PRESSURE TEST
2. HEALTH DEPARTMENT FINAL APPROVAL
3. PUNCH LIST - PROJECT SIGNOFF
quaDesign International
R
SUBMITTALS
1. PRODUCT SUBMITTAL:
POOL CONTRACTOR TO INCLUDE MANUFACTURER'S DATA,
INSTALLATION INSTRUCTIONS AND GENERAL RECOMMENDATIONS FOR
EACH SPECIFIED PRODUCT.
2. SHOP DRAWING SUBMITTAL:
SHOP DRAWINGS OF EACH ITEM SPECIFIED SHOWING
LAYOUT,PROFILES, METHODS OF JOINING AND ANCHORAGE DETAILS.
3. SUBMITTAL FORM:
USE SUBMITTAL FORM AS A COVER PAGE FOR EACH PRODUCT AND
SHOP DRAWING. SEE SPECIFICATIONS FOR SUBMITTAL FORM.
1. LANDSCAPE ARCHITECT SHALL HAVE A SITE MEETING TO REVIEW
PROJECT BEFORE START OF WORK.
2. CONTRACTOR SHALL REVIEW ALL SPECIAL CONDITION LISTED BY THE
PIMA HEALTH DEPARTMENT AND REVIEW AND COORDINATE WITH
OWNER BEFORE START OF WORK.
3. ANY CHANGES IN CONSTRUCTION PLANS OR EQUIPMENT MUST BE
APPROVED BY THE PIMA COUNTY HEALTH DEPARTMENT. CHANGES
MAY REQUIRE ADDITIONAL PLAN CHECK FEES AND RE-SUBMITTAL OF
PLANS.
4. PLAN APPROVAL DOES NOT AUTHORIZE THE VIOLATION OF ANY LAW,
ORDINANCE, OR REGULATION AND FINAL APPROVAL IS SUBJECT TO
FIELD INSPECTION AND EVALUATION BY LANDSCAPE ARCHITECT AND
PIMA COUNTY HEALTH DEPARTMENT.
5. PROVIDE OWNER WITH 15 DAY NOTICE OF COMPLETION SO THAT THEY
CAN APPLY FOR A PIMA COUNTY HEALTH USE PERMIT.
6. THE CONTRACTOR SHALL TEST COLD WATER SUPPLY BEFORE SURGE
TANK IS FILLED WITH WATER AND PROVIDE CHEMICALS TO BALANCE
THE WATER PER PIMA COUNTY HEALTH STANDARDS
7. THE OWNER SHALL CONTRACT OR HIRE A CERTIFIED POOL OPERATOR
(CPO) AND HAVE THAT PERSON ON SITE THE DAY OF TRAINING BY THE
CONTRACTOR.
8. THE CONTRACTOR SHALL PROVIDE TWO TRAINING DAYS BEFORE
SYSTEM IS TURNED OVER THE OWNER AT LEAST THREE DAYS APART.
ALL OPERATIONAL MANUALS WILL BE PROVIDED DURING THE FIRST
TRAINING. ALL TRAINING SHALL BE VIDEO AND PROVIDED TO OWNER.
9. THE CPO IS RESPONSIBLE TO PROVIDE A DAILY RECORD OF
MAINTENANCE AND WATER QUALITY. THIS WRITTEN INFORMATION
SHALL BE KEEP IN THE EQUIPMENT YARD AND AVAILABLE FOR
INSPECTION AND REVIEW BY THE HEALTH DEPARTMENT..
10. BARRIER/ENCLOSURE SHALL BE PROVIDED TO MEET LOCAL HEALTH
DEPARTMENT AGREEMENT WITH THE OWNERS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR BLUE STAKE IN ALL AREAS
OF EXCAVATION PRIOR TO WORK.
PROJECT NOTES
1. WARRANTY
1.1. ALL EQUIPMENT SHALL BE WARRANTED BY THE MANUFACTURER
AND OR CONTRACTOR FOR A MINIMUM OF TWO (2) YEARS
FOLLOWING THE DATE OF SUBSTANTIAL COMPLETION.
1.2. WARRANT FINISH SURFACES AND FINISHES FOR (1) YEAR AGAINST
DELAMINATING.
2. OPERATION AND MAINTENANCE MANUALS
2.1. MANUALS, GENERAL
2.1.1. ORGANIZE EACH MANUAL INTO A SEPARATE SECTION FOR
EACH SYSTEM AND SUBSYSTEM, AND A SEPARATE SECTION
FOR EACH PIECE OF EQUIPMENT NOT PART OF A SYSTEM.
EACH MANUAL SHALL CONTAIN THE FOLLOWING MATERIALS,
IN THE ORDER LISTED
2.2. OPERATION MANUALS
2.2.1. SYSTEM, SUBSYSTEM, AND EQUIPMENT DESCRIPTIONS
2.2.2. OPERATING STANDARDS
2.2.3. OPERATING PROCEDURES
2.2.4. OPERATING LOGS
2.2.5. WIRING DIAGRAMS
2.2.6. PIPED SYSTEMS DIAGRAMS
2.2.7. PRECAUTIONS AGAINST IMPROPER USE
2.3. MAINTENANCE MANUALS
2.3.1. PRODUCT INFORMATION
2.3.2. MAINTENANCE PROCEDURES
2.3.3. REPAIR INSTRUCTIONS, MATERIALS AND SOURCES
2.4. DRAWINGS
2.4.1. MOST RECENT SET OF CONSTRUCTION DRAWINGS
2.4.2. AS-BUILT DRAWINGS
WARRANTY NOTES
CODE COMPLIANCE
1. 2018 INTERNATIONAL BUILDING CODE
2. 2018 INTERNATIONAL PLUMBING CODE
3. 2018 INTERNATIONAL MECHANICAL CODE
4. 2018 INTERNATIONAL ENERGY CONSERVATION CODE
5. 2017 NATIONAL ELECTRIC CODE
6. 2009 ICC A117.1
7. AMERICANS WITH DISABILITIES ACT
8. DEPARTMENT OF PUBLIC HEALTH - PIMA COUNTY HEALTH DEPT.
PROJECT PLUMBING NOTES
1. ALL ELECTRICAL WORK SHALL COMPLY WITH FOLLOW: NEC - ARTICLE
680 - SWIMMING POOL INSTALLATIONS - SEE: ELECTRICAL SHEETS FOR
ADDITIONAL NOTES:
- 680.3 - CORD AND PLUG-CONNECTED EQUIPMENT
- 680.8 - OVERHEAD CONDUCTOR CLEARANCES
- 680.10 - UNDERGROUND WIRING LOCATION
- 680.11 - EQUIPMENT ROOM AND PITS
- 680.12 - DISCONNECTING MEANS
- 680.21 - MOTORS
- 680.24 - JUNCTION BOXES
- ANY ADDITIONAL STATE AND LOCAL REQUIREMENTS
ELECTRICAL NOTES
1. PIPE ROUTING IS FOR DIAGRAM ONLY. THE SPLASH PAD CONTRACTOR
AND G.C. SHALL COORDINATE ROUTING LOCATIONS.
2. ALL PIPING FOR THE SPLASH PAD SYSTEMS IN THE EQUIPMENT YARD
AND 5' OUTSIDE YARD WALL SHALL BE SCHEDULE 80 PVC, ALL SUPPLY
PIPING TO EACH PAD FROM THIS POINT OF CONNECTON SHALL BE
SCHEDULE 40 PVC. ALL GRAVITY PIPE SHALL BE SCH. 40 PVC.
3. THE PIPING INSTALLATION IN THE EQUIPMENT ROOM SHALL BE
SUPPORTED BY A UNISTRUT SYSTEM IN ACCORDANCE WITH IPC.
CONTRACTOR SHALL SUBMIT SUPPORT SYSTEM DESIGN TO ADI
BEFORE START OF THIS WORK FOR APPROVAL.
4. ALL PIPE PENETRATIONS INTO TANK SHALL BE COORDINATED WITH
THE TANK SUPPLIER AND SHOP DRAWINGS. VERTICAL LID
PENETRATIONS CAN BE CAULKED, ALL HORIZONTAL PENETRATIONS
SHALL USE LINK SEALS TO SECURE PIPING SYSTEMS AND PROVIDE A
WATER TIGHT SEAL.
5. INSTALL TRACER WIRE FOR ALL PLUMBING NOT INSTALLED UNDER
CONCRETE. PROVIDE A DIMENSIONED PLAN LOCATING PIPE OUTSIDE
OF PAVEMENT AT PROJECT TURNOVER/START UP PHASE.
ABBREVIATIONS
GALLONS PER MINUTE
POUNDS PER SQUARE INCH
NOT TO SCALE
MECHANICAL ELECTRICAL PLUMBING
NATIONAL SANITATION FOUNDATION
GPM
FINISHED FLOOR ELEVATIONFFE
PSI
NTS
MEP
NSF
ELEVATIONELV
pH POTENTIAL HYDROGEN
ADA AMERICANS WITH DISABILITIES ACT
BACKFLOW PREVENTION ASSEMBLYBPA
1. ALL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S
INSTRUCTIONS.
2. ALL EQUIPMENT AND MATERIALS NOT SHOWN OR SPECIFIED ON THE
CONTRACT DOCUMENTS, BUT REQUIRED TO COMPLETE THIS PROJECT,
SHALL BE SUPPLIED BY THE CONTRACTOR AS PART OF THIS
CONTRACTED WORK.
3. THE CONTRACTOR SHALL PERFORM A HYDROSTATIC TEST TO 50 PSI
FOR 30 MINUTES AND KEEP A MINIMUM OF 15 PSI ON SYSTEM UNTIL ALL
DECKING AND PLANTING IS COMPLETED IN THE AREA OF THE PIPING
SYSTEMS.
4. PRESSURE GAUGES SHALL BE BE INSTALLED ON THE INLET AND
OUTLET OF EACH FILTER SYSTEM AND LOCATED WHERE THEY CAN BE
EASILY READ.
5. VACUUM GAUGES SHALL BE INSTALLED ON THE INLET TO EACH PUMP
AND INSTALLED IN WHERE THEY CAN BE EASILY READ.
6. LABEL PIPE SIZE, TYPE, AND FLOW DIRECTION FOR ALL EQUIPMENT
WITH A MINIMUM OF 3/4 INCH TEXT PER ANSI A13.
7. ALL EQUIPMENT, PLUMBING, AND VALVES, SHALL BE INSTALLED FOR
EASY ACCESS AND REPAIR. GAUGES, FLOW METERS AND BLEED
VALVES WILL BE LOCATED IN A CONSISTENT LOCATION FOR EACH
BOOSTER PUMP SYSTEM.
8. FILTER BACKWASH SHALL TAKE PLACE WHEN THE THE DIFFERENTIAL
PRESSURE BETWEEN THE INFLUENT AND INFLUENT PRESSURE
GAUGES READ APPROXIMATELY 4-5 PSI DIFFERENCE.
9. OWNER SHALL SUPPLY BACKWASH PIPING RISER IN EQUIPMENT YARD
SLOPED A MINIMUM OF .5% TO SITE DETENTION BASIN.
10. BACKWASH WATER VOLUME WITH EQUAL 105 GPM FOR 5 MINUTE EACH
FILTER.
EQUIPMENT NOTES
1. WATER FEATURES SHALL NOT BE FILLED WITH WATER UNTIL FILTRATION SYSTEM
AND CHLORINATION SYSTEM ARE COMPLETE AND READY FOR START-UP.
CONTRACTOR SHALL NOTIFY OWNER IN WRITING OF START-UP AT LEAST TWO
WEEKS PRIOR TO WATER FEATURE FILLING PHASE. OWNER IS RESPONSIBLE FOR
SUPPLYING HALOGEN PRODUCTS AND pH CONTROL PRODUCTS FOR
MAINTENANCE OF WATER FEATURES.
2. THE WATER FEATURE CONTRACTOR SHALL FLUSH ENTIRE SYSTEM, INCLUDING
WATER SOURCE, PRIOR TO INSTALLATION OF FEATURE JETS.
3. THE WATER FEATURE CONTRACTOR SHALL MAINTAIN EACH WATER FEATURE FOR
14 CONSECUTIVE DAYS IN CONJUNCTION WITH MECHANICAL SYSTEM
OPERATIONAL TEST. THIS MAINTENANCE PERIOD SHALL BE EXTENDED WITH
MECHANICAL SYSTEM OPERATIONAL TEST IF REQUIRED PER MANUFACTURE
GUIDELINES. DURING THIS TIME, CLEAN ENTIRE WATER FEATURE INTERIOR TWICE
DAILY STARTING IMMEDIATELY AFTER FILLING WATER FEATURES. PERIODICALLY
CLEAN GRATES UNTIL NO FURTHER ACCUMULATION OF FOREIGN MATERIALS
OCCURS, AND ADD CHEMICALS AS REQUIRED FOR ACCEPTABLE WATER QUALITY.
WATER FEATURE CONTRACTOR MAY USE VACUUM SPECIFIED DURING THIS
START UP PHASE BUT WILL PROVIDE NEW CARTRIDGE FILTER ELEMENT IN
UNOPENED BOX AT TURN OVER OF WATER FEATURE SYSTEMS TO OWNER.
4. THE OWNER SHALL BE TRAINED ON ALL SYSTEMS AFTER COMPLETION OF 14 DAY
START UP PERIOD. PROVIDE VIDEO OR OTHER ELECTRONIC DOCUMENTATION TO
OWNER OF TRAINING.
WATER FEATURE START-UP
WATERPROOFING NOTES
1. SEAL ALL PENETRATIONS THROUGH CONCRETE/SHOTCRETE SLAB WITH
AQUABOND UW-5000 EPOXY AT CONNECTION OF PVC TO SLAB.
2. PROVIDE WATERPROOFING SYSTEM AQURON CPSP BY AQURON CORPORATION
INTERNATIONAL (WWW.AQURON.COM) APPLY TWO COATS OVER FINISH SLAB.
1. ALL GROUNDING SHALL BE COMPLETED IN ACCORDANCE WITH NATIONAL
ELECTRIC CODE (NEC) AND THE LOCAL AUTHORITY HAVING
JURISDICTION.
2. THESE PLANS ARE DIAGRAMMATIC AND MAY NOT REPRESENT THE FINAL
LOCATIONS OF THE EQUIPMENT. THE IWF CONTRACTORS SHALL
COORDINATE ALL GROUNDING REQUIREMENTS AND EQUIPMENT
ELECTRICAL CONNECTIONS WITH ALL OTHER WORK TO BE COMPLETED
WITH CONSIDERED FIELD CONDITIONS.
3. THE GROUNDING GRID TO BE INSTALLED WITHIN THE INTERACTIVE
WATER FEATURE ASSEMBLIES SHALL BE INSTALLED WITH A MINIMUM OF
BARE #8 GROUND WIRE (99% PURE COPPER) AND INSTALLATION IS TO BE
COORDINATED WITH FINAL FEATURE CONSTRUCTION.
4. GROUNDING GRID SHALL BE INSTALLED A MINIMUM OF 3 FEET AROUND
THE EXTENTS OF THE SPLASH PAD EDGES IN ACCORDANCE WITH NEC.
5. ALL GROUNDING CONNECTIONS SHALL BE CAD-WELDED OR AS
OTHERWISE REQUIRED, CAD WELDING SHALL BE COPPER TO COPPER
WITH 6% SILVER FOR DUCTILITY.
6. PROVIDE #8 BARE COPPER WIRE SPACED AT 1 FOOT APART FOR ENTIRE
LENGTH OF BONDING GRID, COPPER WELD AT EACH JOINT. PROVIDE #8
COPPER GROUNDING CONDUCTOR FROM LIGHTS, RAILS, AND OTHER
REQUIRED ACCESSORIES PER BONDING DIAGRAM DETAIL.
BONDING & GROUNDING
VICINITY MAP
SYMBOL KEY
Scale: 1:1
VIEW TITLE1
SECTION REFERENCE:
DETAIL BLOCK REFERENCE:
SHEET LOCATION:
SP001
SP001
DETAIL NUMBER
REFERENCE NUMBER / SHEET NUMBER
SECTION LETTER / SHEET NUMBER
VEW DIRECTION
WINDOW BOX
100% BID SET
NOT FOR
+7
SPA EQUIPMENT ROOM
+7
SPA EQUIPMENT ROOM
-1"+0" -2" -3" -3" -2" -1"
+30.25 = 0" AT
PERIMETER
EDGE
-2"
+7
SPA EQUIPMENT ROOM
Gator Storage
Men's
Women's
Storage
Wash
Chase
Family
BBQ
Office
Storage
Concessions
Splash Pad Equipment
RR 3
RR 2
RR 1
RR 4
205CHLOR
ACID
Scale: 1:50
SPLASH PAD SITE PLAN1
SP101
SPD07
SPP01
100% BID SET
NOT FOR
-1" +0"
-2" -3" -3" -2" -1"
+30.25 = 0" AT
PERIMETER
EDGE
-2"
Scale: 1/8"=1'
SPLASH PAD KEYNOTE AND LAYOUT PLAN1
I1. PAD DRAIN: DALDORADO; 12" PVC DRAIN, 74 LINEAR FEET. SEE: SHEET
SPD09, DETAIL 2.
I2. SERPENT NO2: VORTEX; MODEL VOR-7214. SET AT 8 GPM. SEE: SHEET
SPD09, DETAIL 6. (QTY. 1)
I3. TWIN SPLASH: VORTEX; MODEL VOR-7242. SET AT 15 GPM. SEE: SHEET
SPD09, DETAIL 7. (QTY. 1)
I4. FUMBLING FIVE: VORTEX; MODEL VOR-7384. SET AT 30 GPM. SEE: SHEET
SPD09, DETAIL 8. (QTY. 1)
I5. SILHOUETTE NO2: VORTEX; MODEL VOR-7773. SET AT 6 GPM EACH. SEE:
SHEET SPD09, DETAIL 9. (QTY. 1)
I6. SPRAY CANNON: VORTEX; MODEL VOR-0201. SET AT 6 GPM EACH. SEE:
SHEET SPD09, DETAIL 5. (QTY. 6)
I7. BUTTERFLY NO1: VORTEX; MODEL VOR-7792. SET AT 8 GPM EACH. SEE:
SHEET SPD09, DETAIL 4. (QTY. 1)
I8. JET NOZZLE: CRYSTAL FOUNTAINS; NLG SERIES, NLG 202, 3FT SPRAY
HEIGHT, 25 GPM. SEE: SHEET SPD10, DETAIL 1. (QTY. 8)
I9. JET NOZZLE: CRYSTAL FOUNTAINS; NLG SERIES, NLG 203, 3FT SPRAY
HEIGHT, 26 GPM. SEE: SHEET SPD10, DETAIL 2. (QTY. 10)
IMBEDI
DE1. SPLASH PAD COATING: REINFORCED CONCRETE WITH COATING PER
LANDSCAPE ARCHITECT, COORDINATE COLOR WITH LANDSCAPE
ARCHITECT. SLOPE TO DRAIN AT 2% MAX.
DESIGN ELEMENTDE
ELECTRICALE
E1. BOLLARD: PENTAIR SPA REMOTE BUTTON AND CONTROLLER TO TURN
ON PUMPS; PROVIDE 1" CONDUIT TO CUSTOM POST- 12 GAUGE
CIRCUIT FROM CONTROLLER TO POST. CONTACT JOHN WATT
JOHN.WATT@PENTAIR.COM FOR CONTROL SYSTEM. POST IS CUSTOM
FABRICATED OF STAINLESS STEEL AND POWDER COATED WHITE. SEE
DETAIL 4, SPD10 (QTY. 1)
E2. BONDING DIAGRAM: PER NEC REQUIREMENTS. SEE: SHEET SP502,
DETAIL 3.
ACCESSORIES & SAFETYA
SPLASH PAD RULES - CAUTION FOR YOUR SAFETY
1. USE AT YOUR OWN RISK.
2. CHILDREN MUST HAVE ADULT SUPERVISION AT ALL TIMES.
3. NO PETS, GLASS, ROCKS, BOTTLES, OR WATER BALLOONS.
4. NO SKATEBOARDS, ROLLER SKATES, ROLLERBLADES, SCOOTERS, OR
BICYCLES.
5. DO NOT USE SPLASH PAD DURING LIGHTNING STORMS.
6. USE THE RESTROOM BEFORE ENTERING THE SPLASH PAD.
7. DO NOT ALLOW CHILDREN WHO ARE ILL ONTO THE SPLASH PAD.
8. INFANTS AND TODDLERS MUST WEAR A SWIM DIAPER.
9. DO NOT CHANGE DIAPERS WITHIN THE SPLASH PAD AREA.
10. DO NOT DRINK THE SPLASH PAD WATER.
11. NO PET WASHING, CLOTHES WASHING, OR BATHING IN THE SPLASH PAD.
12. NO FOOD OR DRINKS ALLOWED WITHIN THE SPLASH PAD AREA.
I9
I2
I6
I3
I9
I6
E1
I4
I1
I7
I5
I6
I9
I8
I8
SPD05
100% BID SET
NOT FOR
+30.25 = 0" AT
PERIMETER
EDGE
-2"
Scale: 1/8"=1'
SPLASH PAD PLUMBING1
MATCH LINE
Scale: 1/8"=1'
SPLASH PAD PLUMBING2
CIRCULATION SYSTEMC
ALL PIPING TO BE SCH 40.
CIRCULATION SYSTEM DESIGN FLOW RATE - 145 GPM
C1. GRAVITY TRUNK: (SIZED FOR COMBINED TOY FLOW - 255 GPM)
8" PVC - 255 GPM - 100% COMBINED TOY FLOW @ 1.8 FPS < 3.0 FPS
C2. GRAVITY RISER: (QTY. 2)
6" PVC - 127.5 GPM - 50% COMBINED TOY FLOW @ 1.6 FPS < 3.0 FPS
C3. SUCTION TRUNK LINE: (FROM SURGE TANK TO CIRCULATION PUMP)
4" PVC - 145 GPM - 100% MAX. FLOW @ 3.8 FPS < 5.0 FPS
C4. SUCTION TRUNK LINE: (FROM GRAVITY TRUNK TO CIRCULATION PUMP)
2" PVC - N/A
C5. INLET TRUNK LINE: (FROM CIRCULATION PUMP TO SURGE TANK)
3" PVC - 145 GPM - 100% MAX. FLOW @ 6.5 FPS < 8.0 FPS
C6. COLD WATER SUPPLY: (PER MEP)
1-1/2" MIN. - N/A
C7. FILL LINE: (FROM LEVELOR TO SURGE TANK)
4" PVC - N/A
TOY PUMP [P-2] PLUMBINGTA
ALL PIPING TO BE SCH 40.
TOY PUMP [P-2] DESIGN FLOW RATE - 95 GPM
TA1. SUCTION TRUNK LINE: (FROM SURGE TANK TO PUMP [P-2])
4" PVC - 95 GPM @ 2.5 FPS < 5.0 FPS
TA2. FUMBLING FIVE INLET TRUNK LINE:
2" PVC - 30 GPM @ 2.9 FPS < 8.0 FPS
TA3. TWINSPLASH INLET TRUNK LINE:
2" PVC - 15 GPM @ 1.4 FPS < 8.0 FPS
ACTUATOR VALVE TO SPLIT UP FLOW TO (6) PORTS.
PORT 1/4:
TA4. INLET TRUNK LINE: (NLG202 - QTY. 2)
2" PVC - 50 GPM @ 4.8 FPS < 8.0 FPS
PORT 2/5:
TA5. INLET TRUNK LINE: (NLG203 - QTY. 2)
2" PVC - 50 GPM @ 4.8 FPS < 8.0 FPS
PORT 3/6:
TA6. INLET TRUNK LINE: (NLG202 - QTY. 1 & NLG203 - QTY. 1):
2" PVC - 50 GPM @ 4.8 FPS < 8.0 FPS
TOY PUMP [P-3] PLUMBINGTB
ALL PIPING TO BE SCH 40.
TOY PUMP [P-3] DESIGN FLOW RATE - 58 GPM
TB1. SUCTION TRUNK LINE: (FROM SURGE TANK TO PUMP [P-3])
3" PVC - 58 GPM @ 2.6 FPS < 5.0 FPS
TB2. SILHOUETTE NO2 & SPRAY CANNON INLET TRUNK LINE:
2" PVC - 18 GPM @ 1.9 FPS < 8.0 FPS
TB3. BUTTERFLY NO1 INLET TRUNK LINE:
2" PVC - 8 GPM @ 0.8 FPS < 8.0 FPS
TB4. SPRAY CANNON INLET TRUNK LINE:
2" PVC - 12 GPM @ 1.4 FPS < 8.0 FPS
TB5. SERPENT NO2 INLET TRUNK LINE:
2" PVC - 8 GPM @ 0.8 FPS < 8.0 FPS
TB6. SPRAY CANNON INLET TRUNK LINE:
2" PVC - 12 GPM @ 1.4 FPS < 8.0 FPS
TOY PUMP [P-4] PLUMBINGTC
ALL PIPING TO BE SCH 40.
TOY PUMP [P-4] DESIGN FLOW RATE - 100 GPM
TC1. SUCTION TRUNK LINE: (FROM SURGE TANK TO PUMP [P-4])
4" PVC - 100 GPM @ 2.5 FPS < 5.0 FPS
ACTUATOR VALVE TO SPLIT UP FLOW TO (6) PORTS.
PORT1/4:
TC2. INLET TRUNK LINE: (NLG202 - QTY. 2)
2" PVC - 50 GPM @ 4.8 FPS < 8.0 FPS
PORT 2/5:
TC3. INLET TRUNK LINE: (NLG203 - QTY. 2)
2" PVC - 50 GPM @ 4.8 FPS < 8.0 FPS
PORT 3/6:
TC4. INLET TRUNK LINE: (NLG203 - QTY. 2)
2" PVC - 50 GPM @ 4.8 FPS < 8.0 FPS
ACTUATOR VALVE TO SPLIT UP FLOW TO (6) PORTS.
PORT 1/4:
TC5. INLET TRUNK LINE: (NLG202 - QTY. 2)
2" PVC - 50 GPM @ 4.8 FPS < 8.0 FPS
PORT 2/5:
TC6. INLET TRUNK LINE: (NLG203 - QTY. 2)
2" PVC - 50 GPM @ 4.8 FPS < 8.0 FPS
PORT 3/6:
TC7. INLET TRUNK LINE: (NLG202 - QTY. 1 & NLG203 - QTY. 1):
2" PVC - 50 GPM @ 4.8 FPS < 8.0 FPS
C1
TC7
TC6
TC5
TB6
TB5
TA3
TC4
TA2
TC2
TB3
TB2
TC3
TB4
TA4
TA5
TA6
SPD06
100% BID SET
NOT FOR
SANITATION EQUIPMENTS
S1. CHEMISTRY CONTROLLER: BECSYS5 WATER CHEMISTRY CONTROLLER, MODEL: BECSYS5,
115V, 12.25 AMPS. SEE: SHEET SPD12, DETAIL 4. (QTY. 1)
S2. PUMSAR PRECISSION CAL HYPO FEEDER. 120V 15A POWERS BOTH FEEDERS.
S3. PULSARM ACID PLUS ACID TAB FEEDER SHAIRS POWER WITH PULSAR TAB FEEDER
S4. EYEWASH STATION - PER MEP (QTY. 1)
S5. UV SYSTEM: CHLORKING; SAG480-CR, 120V, 7.2 AMP BREAKER REQUIRED. SEE: SHEET SPD11, DETAIL 5. (QTY. 1)
S6. BACKWASH TANK: CHEM-TAINER; RECTANGULAR L SERIES, 530 GALLON, 54"X54"X42"H. WITH
STAINLESS STEEL SUPPORT FRAME. SEE: SHEET SPD12, DETAIL 2. (QTY. 1)
S7. PORTABLE VACUUM: WATER CO.; MODEL: ULTRA VAC, 3/4HP MULTICYCLONE 12 ULTRA, 50FT
CORD, #16V1275. (QTY. 1)
VALVES & GAUGESV
V1. PRESSURE-VACUUM GAUGES: PRODUCT OF MILJOCO CORPORATION. MODEL
#PLF2598LZ005SS, INDUSTRIAL GAUGE, 2.5-INCH DIAL, 316 STAINLESS STEEL CASE,
GLYCERIN FILLED. RANGE OF 0-100 PSI FOR PRESSURE, AND 0-30 INCHES OF MERCURY
FOR VACUUM. (ONE ON EACH PUMP INLET/OUTLET, ONE ON EACH FILTER OUTLET)
V2. BALL VALVES: ASAHI/AMERICA. TYPE 21, 1-INCH, WITH EPDM SEALS AND TEFLON SEATS.
(QTY. AS NEEDED)
V3. BUTTERFLY VALVE: ASAHI AMERICA, TYPE 57, PVC, LEVER (3" TO 6"), EPDM SEALS, EPDM
SEATS, POOL CONTRACTOR TO PROVIDE FLANGES & S.S. HARDWARE (QTY. AS NEEDED)
V4. MULTI-PORT VALVES: JANDY NEVERLUBE. 2-INCH, 2 & 3 PORT (QTY. PER PLAN) USE ON 2"
PIPING SYSTEMS (QTY. AS NEEDED)
V5. FLOW METER VALVE: H2FLOW, FLOWVIS, USE 3" AFTER EXIT OF FILTER, USE 2/2.5"
(NON-CHECK VALVE STYLE) ON EXIT OF BOOSTER PUMPS. USE 2/2.5"(CHECK VALVE STYLE
ON FILTER BACKWASH LINES) QTY. 1, 3 & 2.
V6. ACTUATOR VALVE: A&A; 6-PORT ACTUATOR VALVE. SEE: SHEET SPD11, DETAIL 2. (QTY. 3)
V7. RPZ: PER MEP. SEE: SHEET SPD11, DETAIL 1. BY CIVIL ENGINEER-ADI DETAIL FOR
REFERENCE ONLY.
V8. CHECK VALVE: ASAHI AMERICA, WAFER STYLE, 3" ON EXIT OF CIRCULATION PUMP WITH
FLANGES AND STAINLESS STEEL HARDWARE.
E1. AUTOFILL: BECS AUTOFILL CONTROL AND SENSOR 110V, 15AMP CIRCUIT. SEE: SHEET SPD11, DETAIL 3. (QTY. 1)
E2. GFCI: BY OTHERS
E3. SPLASH PAD CONTROL SYSTEM: PENTAIR; SINGLE BODY SYSTEM - I10P UPGRADE KIT #522047, INTELLICENTER POWER CENTER #522044, SPA SWITCH #RCS1. CONTACT JOHN WATT AT
623-444-4386 OR 623-451-3151 PRIOR TO INSTALLATION.
E4. ELECTRICAL TRANSFORMER: BY OTHERS
ELECTRICALE
C1. SPLASH PAD CIRCULATION PUMP [P-1]: PENTAIR; WHISPERFLO XF VS, #022035, 5 HP, 208, SINGLE PHASE, 20 AMPS. (QTY. 1)
C2. SPLASH PAD CIRCULATION FILTER: PENTAIR; TR140C, #140316, 7.06SF. (QTY. 2)
C3. TOY SPRAY PUMP [P-2]: PENTAIR; INTELLIFLO3, #011075, 3 HP, 208V, SINGLE PHASE, 12.4 AMPS.
(QTY. 1)
C4. TOY SPRAY PUMP [P-3]: PENTAIR; INTELLIFLO3, #011075, 3 HP, 208V, SINGLE PHASE, 12.4 AMPS.
(QTY. 1)
C5. TOY SPRAY PUMP [P-4]: PENTAIR; INTELLIFLO3, #011075, 3 HP, 208V, SINGLE PHASE, 12.4 AMPS.
(QTY. 1)
C6. PRE-FILTER: WATERCO; MODEL: MULTI CYCLONE 16 PRO. PRODUCT #200385. (QTY. 5)
C7. EXTRA STRAINER: HAYWARD SB SERIES SIMPLEX BASKET STRAINER 3" PVC ON 2" LINE FROM
GRAVITY TANK LINE.
C8. SURGE TANK WITH POLYPROPYLENE LADDER AND 36"X36" BILCO LID, TYPE TER. SEE DETAIL
SHEETS.
MAIN CIRCULATION EQUIPMENTC
Scale: 1/4"=1'
EQUIPMENT PLAN 2
C8
SURGE TANK
SEE SP301
TOILET/SINK
CLEANOUTS
TOILET/SINK
CLEANOUTS
TOILET/SINK
CLEANOUTS
SPD07
100% BID SET
NOT FOR
a7.1
N-S section 1/8" = 1'-0"
CLASS
A129B
10'-0"
11'-3 3/4"
LANDING 2
a1.0
A a6.3
G
F
E
D a6.1 a9.2 a1.0 a1.0 a7.2 a7.2 a5.2
ELEVATION INDICATOR
PARTITION TYPE
KEYNOTE
CEILING HEIGHT
WINDOW MARK
DOOR NUMBER
ROOM NAME / NUMBER
EXTERIOR ELEVATIONS
INTERIOR ELEVATIONS
ENLARGED AREA
SECTION / DETAIL TAG
BUILDING SECTION TAG
DRAWING TITLE
WALL SECTION TAG
symbols legend
H
S.
EG
RA
R
NZI O U.A
IS
D
ET
ER ARC
CE
A.
T
IT
KEVIN A.
BARBER
37165
N
TACIFI
A D
DENG
S
T E
I
R
C
E T E
O
JO
A Q U
IN
M U R R
IE
T A
P A R K
P H A S E
S
IT
E
IM
P R O V E M E N T S
N
S
IL
V E R B E
LL
R O A D
T U C S O N A Z
Project #:
Date:
Designed by:
Drawn by:
Checked by:
098134091
Revision Record
No.
DateDescription
Sheet Number: of
3300 EAST SUNRISE
DR, SUITE 130
TUCSON, AZ 85718
(p) 520.615.9191
Case #:
TD-DEV-0623-00272
7350 EAST SPEEDWAY 210
TUCSON, ARIZONA 85710
(520) 326-3700
(520) 326-1148 www.swaimaia.com
OFFICE
FAX
ASSOCIATES LTD
ARCHITECTS AIA
11.10.23Contractor/COT RFIs
/3
/2
:0
:3
P
M C
A c ti v e
R e v it P ro je c ts
\2
R
J o a q u in M u rr ie ta
S
IT
E
C
F T im o th y
S m it h .r v t
08.11.2023
AN01
abbreviations and symbols general project notesabbreviations
& AND
@ AT
AB ANCHOR BOLT
ABC AGGREGATE BASE
COURSE
ABI ADDITIVE BID ITEM
AC AIR CONDITIONING
ACC ACCESSIBLE
ACOUST ACOUSTICAL
ACT ACOUSTIC CEILING TILE
AD AREA DRAIN
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AGGR AGGREGATE
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
AP ACCESS PANEL
APC ACOUSTICAL PANEL
CEILING
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASPH ASPHALT
ATTN ATTENTION
AUTO AUTOMATIC
AV AUDIOVISUAL
BD BOARD
BET BUILDING ENTRANCE
TERMINAL
BFF BELOW FINISHED FLOOR
BIT BITUMINOUS
BL BASELINE
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM, BENCHMARK
BO BOTTOM OF
BOS BOTTOM OF STEEL
BOT BOTTOM
BRG BEARING
BRK BRICK
BRKT BRACKET
BSMNT BASEMENT
BUR BUILT-UP ROOFING
C CONDUIT
CA COMPRESSED AIR
CAB CABINET
CAT CATEGORY
CB CATCH BASIN
CB CEMENT BOARD
CBU CEMENTITIOUS BACKER
UNIT
CC CENTER TO CENTER
CCTV CLOSED CIRCUIT
TELEVISION
CEM CEMENT
CER CERAMIC
CG CORNER GUARD
CH CHILLER
CI CAST IRON
CIP CAST-lN-PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLKG CAULKING
CLR CLEAR
CNTR COUNTER
CO CLEANOUT
COL COLUMN
CONC CONCRETE
COND CONDITION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR
CPT CARPET
CT CERAMIC TILE
CTR CENTER
CTSK COUNTERSUNK
CW COLD WATER
D DEEP, DEPTH
DBL DOUBLE
DEG DEGREE
DEMO DEMOLISH OR DEMOLITION
DEMO DEMOLITION
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFUSER
DIM DIMENSION
DIMS DIMENSIONS
DISP DISPENSER
DIV DIVISION
DMPF DAMP PROOFING
DN DOWN
DO DOOR OPENING
DR DOOR
DRN DRAIN
DS DOWNSPOUT
DS DOWN SPOUT
DTL DETAIL
DW DISHWASHER
DWG DRAWING
DWR DRAWER
CMU CONCRETE MASONRY UNIT
E EAST
EA EACH
EB EXPANSION BOLT
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
ENG ENGINEER
EP ELECTRICAL PANEL
EPDM ETHYLENE PROPYLENE
DIENE M-CLASS
EQ EQUAL
A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE EXISTENCE AND LOCATION OF ALL UNDERGROUND OR CONCEALED UTILITIES IN ADVANCE OF ANY CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE TO HIRE A PRIVATE UTILITY LOCATING SERVICE TO LOCATE ALL
UNDERGROUND UTILITIES ON OR NEAR THE PROJECT SITE.
B. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ANY OR ALL EXISTING CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY UTILITIES FOUND TO BE IN THE WAY OF THE NEW CONSTRUCTION SHALL BE REMOVED, RELOCATED OR REPLACED AS DIRECTED. REFER TO
PLUMBING, ELECTRICAL, MECHANICAL AND/OR CIVIL PLANS FOR SPECIFIC REQUIREMENTS.
C. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO REMOVE ALL ABANDONED (RETIRED) UTILITIES THAT INTERFERE WITH THE CONSTRUCTION PROJECT. THE CONTRACTORS AND LOCAL UTILITY AND TRAFFIC CREWS SHALL COORDINATE WORK SCHEDULES SO AS TO
PREVENT ANY CONFLICTING WORK CONDITIONS.
D. CONTRACTOR SHALL REPAIR ANY AND ALL UTILITIES DAMAGED DURING THE COURSE OF CONSTRUCTION IN ACCORDANCE WITH LOCAL
SPECIFICATIONS, AT NO ADDITIONAL COST.
E. CONTRACTOR TO NOTIFY "BLUE STAKE" @ 1-800-782-5348, AT LEAST 48-HOURS IN ADVANCE OF ANY EXCAVATION. UTILITY LOCATIONS SHALL
BE COORDINATED WITH THE ARCHITECT.
F. ALL ITEMS REMOVED SHALL BE TEMPORARILY STORED IN A LOCATION APPROVED BY THE OWNER, AND THE OWNER SHALL REVIEW ALL ITEMS PRIOR TO ANY DISPOSAL. ANY ITEM WHICH IS DEEMED SALVAGEABLE SHALL REMAIN THE OWNER'S PROPERTY, AND WILL BE REMOVED TO STORAGE FACILITIES DESIGNATED BY THE OWNER FOR FUTURE USE. IF THE OWNER DEEMS AN ITEM AS NON-SALVAGEABLE, THE
CONTRACTOR SHALL DISPOSE OF IT.
G. THE CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF ANY DEBRIS RESULTING FROM THE DEMOLITION AND CONSTRUCTION. AT NO TIME SHALL ANY OF THIS MATERIAL OBSTRUCT THE NORMAL OPERATION.
H. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ANY OR ALL EXCESS EXCAVATION AND CONSTRUCTION RELATED DEBRIS, AT
THE END OF EACH WORK DAY.
I. THE CONTRACTOR IS ADVISED THAT DAMAGE TO ANY PORTION OF THIS PROJECT'S BUILDING(s) & SURROUNDING AREA AS A RESULT OF THIS
PROJECT IS TO BE REPAIRED AT THE CONTRACTOR'S EXPENSE.
J. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT THE JOB SITE TO FAMILIARIZE HER/HIM SELF WITH ALL THE EXISTING CONDITIONS
THAT COULD AFFECT THE INSTALLATION OF ANY WORK SET FORTH IN THESE PLANS.
K. THE JOB SITE, AT THE COMPLETION OF CONSTRUCTION, SHALL BE CLEANED OF ANY DEBRIS OR SPOILS RESULTING FROM THE
CONSTRUCTION.
L. THE CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL EXISTING RECORDED DIMENSIONS INDICATED AND ALL EXISTING CONDITIONS THAT
IMPACT NEW CONSTRUCTION.
M. THE CONTRACTOR SHALL ESTABLISH ALL QUANTITIES BASED ON ACTUAL CONDITIONS. THESE DRAWINGS ARE NOT TO BE SCALED.
N. BLOCK WALLS ARE DIMENSIONED TO FACE OF BLOCK. DIMENSIONS ARE NOMINAL THICKNESS. BLOCK WALL OPENINGS ARE DIMENSIONED TO
ROUGH OPENING.
O. METAL STUD PARTITIONS ARE DIMENSIONED TO FACE OF STUD. ALL ROUGH OPENINGS ARE LOCATED 4" TO NEAREST ADJACENT WALL
UNLESS DIMENSIONED OTHERWISE.
P. COMPLY WITH ALL APPLICABLE CODES, RULES AND REGULATIONS. OBTAIN AND PAY FOR ALL PERMITS AND LICENSES REQUIRED.
Q. REFER TO BUILDING CODE ANALYSIS SHEETS FOR ADDITIONAL CODE REQUIREMENTS.
R. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AT LEAST 72 HOURS IN ADVANCE OF ANY CONSTRUCTION THAT REQUIRES SPECIAL/REQUIRED INSPECTION(s).
S. REFERENCE ALL ARCHITECTURAL, CIVIL, LANDSCAPING, MECHANICAL, PLUMBING, AND ELECTRICAL SHEETS FOR SCOPE OF WORK &
COORDINATION.
T. ALL MATERIALS REQUIRED SHALL BE OF A GRADE AND QUALITY CONSISTENT WITH THE INTENDED USE AS SPECIFIED & APPROVED BY THE
ARCHITECT.
U. ALL EQUIPMENT OR MATERIALS NOT SHOWN OR SPECIFIED ON THE PLANS OR IN THE SPECIFICATIONS, BUT ARE REQUIRED TO COMPLETE THE INSTALLATION SHALL BE SUPPLIED BY THE CONTRACTOR AS PART OF THE CONTRACT WORK.
V. UNLESS OTHERWISE NOTED ALL BLOCKING OR BACKING MATERIAL SHALL BE SOLID WOOD FOR ALL WALL MOUNTED ITEMS.
W. INSTALL A CONTINUOUS BEAD OF SEALANT AT ALL GAPS/SEAMS BETWEEN IMMOVABLE EQUIPMENT AND WALLS.
X. ALL SURFACES SHALL BE PAINTED OR FINISHED PER SPECIFICATION. REFER TO FLOOR PLANS, ROOM FINISH SCHEDULE, BUILDING/WALL SECTIONS, DETAILS AND SPECIFICATIONS FOR ADDITIONAL PAINTING & FINISH REQUIREMENTS.
Y. ALL TERMINATIONS OF CARPET, TILE, OR VCT TO ANOTHER FLOOR MATERIAL SHALL HAVE TRANSITION OR REDUCER STRIPS - SEE SPECS.
Z. ALL INTERIOR FINISHES SHALL CONFORM TO THE REQUIREMENTS OF CHAPTER 8 OF THE 2018 INTERNATIONAL BUILDING CODE.
AA. PROVIDE AN ESCUTCHEON AT EACH PIPE PENETRATION @ FLOOR AND/OR WALL SURFACES, TYPICAL.
BB. ALL CORES INTO WALLS AND SLABS SHALL BE PRIOR APPROVED BY THE ARCHITECT AND STRUCTURAL ENGINEER.
CC. INSTALL GYPSUM BOARD CONTROL JOINTS AT ALL LOCATIONS INDICATED OR IF NOT INDICATED AS ACCORDING TO THE REQUIREMENTS THAT
ARE ESTABLISHED IN THE SPECIFICATIONS.
DD. FIRE LANES SHALL BE MAINTAINED IN A CONDITION TO ASSURE ACCESS TO ALL BUILDINGS DURING CONSTRUCTION.
EE. ALL NEW ROOFING SYSTEMS TO HAVE A CLASS "A" FIRE RATING PER SPECIFICATION SECTION 07527.
FF. UPON COMMENCEMENT OF INTERIOR WORK, SMOKING WITHIN THE BUILDING IS PROHIBITED.
EQUIP EQUIPMENT
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FB FACE BRICK
FD FLOOR DRAIN
FD FLOOR DRAIN OR FIRE
DEPARTMENT
FDC FIRE DEPARTMENT
CONNECTION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FF&E FURNITURE, FIXTURES AND
EQUIPMENT
FFB FLUSH FLOOR BOX
FFEL FINISH FLOOR ELEVATION
FH FLAT HEAD
FHC FIRE HOSE CABINET
FIN FINISH
FIXT FIXTURE
FLASH FLASHING
FLR FLOOR
FLUOR FLUORESCENT
FND FOUNDATION
FO FACE OF
FP FIRE PROTECTION
FPG FIREPROOFING
FR FIRE RESISTANT
FRC FIBER REINFORCED
CONCRETE
FRT FIRE RETARDANT TREATED
FT FEET/FOOT
FTG FOOTING
FURN FURNITURE
FURR FURRING
FWC FABRIC WALL COVERING
FWP FABRIC WRAPPED PANEL
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACT(OR)
GEN GENERAL
GFRC GLASS FIBER REINFORCED
CONCRETE
GL GLASS
GLAZ GLAZING
GRAN GRANULAR
GRD GROUND
GRFG GLASS FIBER REINFORCED
GYPSUM
GSM GALVANIZED SHEET METAL
GV GAS VALVE
GWB GYPSUM WALL BOARD
GYP GYPSUM
H HIGH/HEIGHT
HB HOSE BIB
HB HOSE BIBB
HC HANDICAPPED
HDWD HARDWOOD
HDWR HARDWARE
HGT HEIGHT
HM HOLLOW METAL
HNDRL HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HR HOUR
HRC HOSE REEL CABINET
HTG HEATING
HVAC HEATING VENTILATION AND
AIR CONDITIONING
HW HOT WATER
ID INSIDE DIAMETER
IN INCH/INCHES
INCAND INCANDESCENT
INCL INCLUDED/INCLUDING
INFO INFORMATION
INSUL INSULATION
INSUL INSULATED OR INSULATION
INT INTERIOR
INTERM INTERMEDIATE
INV INVERT
JAN JANITOR
JC JANITOR'S CLOSET
JST JOIST
JT JOINT
KIT KITCHEN
KO KNOCK OUT
LAM LAMINATE
LAV LAVATORY
LB POUNDS
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
MAS MASONRY
MAX MAXIMUM
MECH MECHANICAL
MED MEDIUM
MEMBR MEMBRANE
MFR MANUFACTURER
MH MAN HOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MR MOISTURE RESISTANT
MTD MOUNTED
MTG MOUNTING
MTL METAL
MULL MULLION
N NORTH
NA NOT APPLICABLE
NC NOISE CRITERIA
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NON
COMB
NON COMBUSTIBLE
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER
OD OVERFLOW DRAIN
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLED
OFF OFFICE
OFOI OWNER FURNISHED,
OWNER INSTALLED
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
P PAINT
PAV PAVING
PBD PARTICLE BOARD
PC PRECAST
PDF POWER DRIVEN FASTENER
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PI. PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PNL PANEL
PNT PAINT OR PAINTED
POL POLISHED
PR PAIR
PREFAB PREFABRICATED
PROJ PROJECT
PSF POUNDS PER SQUARE
FOOT
PT POINT
PT PRESSURE TREATED
PTD PAINTED
PTN PARTITION
PVC POLYVINYL CHLORIDE
QT QUARRY TILE
QTY QUANTITY
R RADIUS/RISER
RA RETURN AIR
RAD RADIUS
RB RESILIENT BASE
RBR RUBBER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
RECPT RECEPTACLE
REF REFERENCE
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCED
REINFORCING
REINF REINFORCED
REL RELOCATE
REM REMOVABLE
REOOM RECOMMENDED
REQ REQUIRE/REQUIRED
REQD REQUIRED
RESIL RESILIENT
REV REVISION/REVISED
RM ROOM
RO ROUGH OPENING
RTD RATED
RTG RATING
RWL RAIN WATER LEADER
S SOUTH
SA SUPPLY AIR
SAF SELF ADHERED FLASHING
SC SOLID CORE
SCHED SCHEDULE
SD STORM DRAIN
SECT SECTION
SF SQUARE FEET/FOOT
SH SPRINKLER HEAD
SHR SHOWER
SHT SHEET
SIM SIMILAR
SM SHEET METAL
SM SURFACE MOUNTED
SP STANDPIPE
SPEC SPECIFICATION
SPEC SPECIFIED OR
SPECIFICATION
SPK SPRINKLER OR SPEAKER
SPKR SPEAKER
SQ SQUARE
SS STAINLESS STEEL
SSK SERVICE SINK
STA STATION
STC SOUND TRANSMISSION
COEFFICIENT
STL STEEL
STOR STORAGE
STRG STRINGER
STRUCT STRUCTURAL
STRUCT STRUCTURE OR
STRUCTURAL
SUBCAT SUBCATEGORY
SUSP SUSPENDED
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TB TOWEL BAR
TEL TELEPHONE/TELECOM
TELE TELEPHONE
TEMP TEMPERATURE
TEMP TEMPORARY
THK THICKNESS
THRU THROUGH
TKBD TACK BOARD
TLT TOILET
TMPD TEMPERED
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOS TOP OF STEEL
TS TUBE STEEL
TV TELEVISION
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED
OTHERWISE
UON UNLESS OTHERWISE
NOTED
URNL URINAL
VAC VENTILATION AND AIR
CONDITIONING
VAR VARIES
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VP VISION PANEL
VR VAPOR RETARDER
VT VINYL TILE
VWC VINYL WALL COVERING
W WIDE/WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WIN WINDOW
WM WIRE MESH
WP WATERPROOF/WATERPRO
OFING
WPM WATERPROOF MEMBRANE
WS WEATHER-STRIPPING
WSCT WAINSCOT
WT WEIGHT
WV WATER VALVE
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
x OCCUPANT LOAD
EXITING DIRECTION
EXITING LOAD AND DIRECTION
EXIT WIDTH REQUIRED
EXIT WIDTH PROVIDED
5"
72" P
R
WALL MOUNTED FIRE
EXTINGUISHER
FE
occupancy legend
Splash Pad Equipment
RR 4
RR 3
RR 2
RR 1
0" R 35" P
A
C C
E S
S
IB
L E
R O
U T
E
2018 IBC code analysis
GENERAL
OCCUPANCY: B
AREA SEPARATION: NONE REQUIRED.
OCCUPANCY SEPARATION (TABLE 508.4): NONE REQUIRED
TYPE OF CONSTRUCTION(TABLE 503): TYPE IIB (NO SPRINKLERS)
ALLOWABLE FLOOR AREA (TABLE 506.2): 23,000 S.F. @ B
ALLOWABLE HEIGHT (TABLE 504.3): 55'
ALLOWABLE STORIES (TABLE 504.4): THREE STORY
BUILDING ELEMENTS (TABLE 601): 0 HRS.
FIRE RATING AT EXTERIOR WALLS (TABLE 602): > 10<30 NO RATING REQUIRED.
ACTUAL GROSS BUILDING AREA
BUILDING 697 TOTAL SF (23,000 SF. ALLOWABLE)
OCCUPANT LOAD (TABLE 1004.5)
BUILDING 5 TOTAL OCCUPANCY
H
S.
EG
RA
R
NZI O U.A
IS
D
ET
ER ARC
CE
A.
T
IT
KEVIN A.
BARBER
37165
N
TACIFI
A D
DENG
S
T E
I
R
C
E T E
O
JO
A Q U
IN
M U R R
IE
T A
P A R K
P H A S E
S
IT
E
IM
P R O V E M E N T S
N
S
IL
V E R B E
LL
R O A D
T U C S O N A Z
Project #:
Date:
Designed by:
Drawn by:
Checked by:
098134091
Revision Record
No.
DateDescription
Sheet Number: of
3300 EAST SUNRISE
DR, SUITE 130
TUCSON, AZ 85718
(p) 520.615.9191
Case #:
TD-DEV-0623-00272
7350 EAST SPEEDWAY 210
TUCSON, ARIZONA 85710
(520) 326-3700
(520) 326-1148 www.swaimaia.com
OFFICE
FAX
ASSOCIATES LTD
ARCHITECTS AIA
11.10.23Contractor/COT RFIs
/3
/2
:0
:3
P
M C
A c ti v e
R e v it P ro je c ts
\2
R
J o a q u in M u rr ie ta
S
IT
E
C
F T im o th y
S m it h .r v t
08.11.2023
AN03
code analysis restroom n o rt h1/8" = 1'-0"AN03 restroom egress plan
1. DO NOT SCALE DRAWINGS. COORDINATE ALL WORK
BETWEEN ARCHITECTURAL, STRUCTURAL, CIVIL,
MECHANICAL, PLUMBING, COMMUNICATIONS AND
ELECTRICAL DRAWINGS, CONFLICTS SHALL BE BROUGHT TO
THE ATTENTION OF THE ARCHITECT PRIOR TO THE
IMPLEMENTATION OF WORK.
2. REFER TO PLUMBING, MECHANICAL AND ELECTRICAL
DRAWINGS AND APPLICABLE CODES FOR REQUIRED
CLEARANCES OF EQUIPMENT.
3. REFER TO SHEET AD13 FOR TYPICAL ACCESSIBLE DETAILS
AND CLEARANCES.
general notes
CLASS
A129B
3 PARTITION TYPE
DOOR NUMBER
ROOM NAME / NUMBER
SEE SHEET SERIES "AD06
& AD07"
SEE SHEET SERIES "AD08"
floor plan sheet legend
SEE SHEET SERIES "AD06
& AD07"
AD024
AD02
AD02
AD02 8
AD02
AD02
Splash Pad Equipment
RR 1
RR 2
RR 3
RR 4
AD022
M4 M3
M4
6'-0"
5'- 0"
1'- 4"
3'- 4"
3'- 4"
4'- 0"
3'- 4"
8" 1'-
4" 3'-
4" 3'-
4" 4'-
0" 3'-
4" 1'-
4"
'-8
14'-8"
22.3
22.1
11.2
26.2
10.1
3.8
22.6
4.1
3.2
8.1
3.1
4.8
4.8
3.1
EM
EM
EM
EM
22.9
1.1
1.1
10.2
10.2
10.2
10.2
22.9
7'-3"
6'-8" 3'-4" 4'-8" 6'-8 1/2" 5'-11 1/2" 2'-8"
'-8
22.6
11.9
1.1
2'- 8"
6'-8 1/2"
AD08
M4
10.3
8'- 0"
'-8
8'-
0"
M5
8.13.1
4.14
4.14
H
S.
EG
RA
R
NZI O U.A
IS
D
ET
ER ARC
CE
A.
T
IT
KEVIN A.
BARBER
37165
N
TACIFI
A D
DENG
S
T E
I
R
C
E T E
O
JO
A Q U
IN
M U R R
IE
T A
P A R K
P H A S E
S
IT
E
IM
P R O V E M E N T S
N
S
IL
V E R B E
LL
R O A D
T U C S O N A Z
Project #:
Date:
Designed by:
Drawn by:
Checked by:
098134091
Revision Record
No.
DateDescription
Sheet Number: of
3300 EAST SUNRISE
DR, SUITE 130
TUCSON, AZ 85718
(p) 520.615.9191
Case #:
TD-DEV-0623-00272
7350 EAST SPEEDWAY 210
TUCSON, ARIZONA 85710
(520) 326-3700
(520) 326-1148 www.swaimaia.com
OFFICE
FAX
ASSOCIATES LTD
ARCHITECTS AIA
11.10.23Contractor/COT RFIs
/3
/2
:0
:4
P
M C
A c ti v e
R e v it P ro je c ts
\2
R
J o a q u in M u rr ie ta
S
IT
E
C
F T im o th y
S m it h .r v t
08.11.2023
AP02
splash pad RR floor plan n o rt h1/4" = 1'-0"AP02 floor plan restroom
1.1 LINE OF SHADE CANOPY ABOVE
3.1 CONCRETE SIDEWALK. SEE CIVIL AND LANDSCAPE
DRAWINGS FOR CONTINUATION.
3.2 4" CONCRETE SLAB ON 4" ABC. LIGHT BROOM FINISH.
EXPANSION JOINT AROUND PERIMETER OF SLAB AGAINST
WALLS. CAULK JOINT. SLOPE OUT OF DOOR AT 1%.
3.8 4" CONCRETE SLAB ON 4" ABC. LIGHT BROOM FINISH.
EXPANSION JOINT AROUND PERIMETER OF SLAB AGAINST
WALLS. CAULK JOINT. SLOPE AT 1% TO FLOOR DRAINS.
4.1 CMU WALL, PAINT EXTERIOR. REFER TO FINISH PLAN FOR
INTERIOR SIDE.
4.8 CMU COLUMN BASE WITH STEEL COLUMN AT CENTER. -
TYP.
4.14 MASONRY SCREEN WALL - REFER TO LANDSCAPE AND
CIVIL.
8.1 HOLLOW METAL DOOR IN HOLLOW METAL FRAME. PRIME
AND PAINT - TYP.
10.1 36", 42" AND 18" GRAB BARS PER ADA GUIDELINES - TYP.
10.2 HC RESTROOM SIGNAGE. SEE DETAIL 6 /AD12
10.3 BABY CHANGING STATION MOUNTED TO WALL.
11.2 TOILET PAPER DISPENSER - TYP.
11.9 PLAYGROUND + SHADE CANOPIES - REFER TO
LANDSCAPE.
22.1 TOILET - TYP. SEE PLUMBING DRAWINGS.
22.3 URINAL - TYP. SEE PLUMBING DRAWINGS.
22.6 HAND WASH SINK - REFER TO PLUMBING.
22.9 SPLASH PAD EQUIPMENT. REFER TO POOL DESIGN
DRAWINGS.
26.2 ELECTRICAL DISTRIBUTION PANEL - SEE ELECTRICAL
DRAWINGS.
keynotes
BETWEEN ARCHITECTURAL, STRUCTURAL, MECHANICAL,
PLUMBING, COMMUNICATIONS AND ELECTRICAL DRAWINGS
SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT
PRIOR TO THE IMPLEMENTATION OF WORK.
2. REFER TO PLUMBING, MECHANICAL AND ELECTRICAL
DRAWINGS FOR ALL APPLICABLE CODES FOR REQUIRED
CLEARANCES OF EQUIPMENT.
3. SEE MECHANICAL, PLUMBING AND ELECTRICAL FOR ALL
PENETRATIONS THROUGH ROOFS. REFER TO TYPICAL
DETAILS.
4. ROOF HEIGHTS…