Jackson County Courthouse Cooling Tower Repla.pdf

PDF 1 MB Posted

Attached to
Jackson County Courthouse - Cooling Tower Replacement
Solicitation number
PE-67800-NONST-2024-000000012
Issued by
Jefferson County, Georgia

About this file

This document is a set of construction drawings and specifications for the replacement of the existing cooling tower at the Jackson County Courthouse in Jefferson, Georgia. The intent of the project is to demolish and replace the existing nominal 500-ton, two-cell, counterflow cooling tower (CT-1) with a new cooling tower of equal capacity. The demolition work includes the removal of the existing cooling tower, portions of the associated above-ground condenser piping, and one of the two variable frequency drives (VFDs) located in the basement mechanical room. The new cooling tower is to be a direct replacement of the existing tower with accessory upgrades. The electrical scope includes the modification of the power supply for connection to the replacement cooling tower, associated basin heaters, heat trace, and VFDs. The BAS controls sequence of operations and points are to remain the same as currently programmed.

The design basis includes the applicable building codes and standards, as well as the design intent and general notes for the project. A cooling tower schedule is provided detailing the specifications of the new tower. The drawings include demolition and new work plans, elevations, and details for the mechanical yard and basement mechanical and electrical rooms.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AUGUST 30, 2024

Cooling Tower Replacement

JOHNSON, SPELLMAN & ASSOCIATES, INC

350 RESEARCH COURT, SUITE 130

PEACHTREE CORNERS, GA 30092

CONTACT - BRAD WAGES

PHONE - 678-336-5419

PROJECT MANAGER - KASON RHENEY

PHONE - 678-336-5431

PRIME CONSULTANT /

MECHANICAL ENGINEER

Jackson County Courthouse

FOR CONSTRUCTION DOCUMENTS

SITE LOCATION MAP

SCALE: NONE

VICINITY MAP

SCALE: NONE

JACKSON COUNTY

JEFFERSON, GA

PROJECT SITE

Jackson County Government

ELECTRICAL ENGINEER

BARNETT CONSULTING ENGINEERS

655 ENGINEERING DRIVE, SUITE 150

PEACHTREE CORNERS, GA 30092

CONTACT - LEAH BENINCASA

PHONE - 404-382-9554

at The Jackson County Courthouse 5000 Jackson Parkway Jefferson, GA 30549

SHEETS

JOB NUMBER

DRAWN BY

CHECKED BY

DATE

DRAWING NUMBER

Phone (770) 447-4555

350 Research Court, Suite 130 visit us at www.jsace.com

Peachtree Corners, Georgia 30092

Johnson, Spellman & Associates, Inc.

RE

VI

SI

O

N S

N O

D

AT

E

JA

CK

SO

N

C O

U N

TY

CO

U

RT

H O

U

SE

C O

O

LI

N G

TO

W

ER

R

EP

LA

CE

M

EN

T

JE

FF

ER

SO

N , G

A

COVER SHEET

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text

DRAWING INDEX

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

FOR CONSTRUCTION DOCUMENTS 8/30/2024

AutoCAD SHX Text

GENERAL DRAWINGS

AutoCAD SHX Text

COVER

AutoCAD SHX Text

COVER SHEET, MAP

AutoCAD SHX Text X

AutoCAD SHX Text

MECHANICAL DRAWINGS

AutoCAD SHX Text M-0

AutoCAD SHX Text

HVAC GENERAL NOTES, LEGEND, SCHEDULES, DESIGN INTENT, & DETAILS

AutoCAD SHX Text X

AutoCAD SHX Text M-1

AutoCAD SHX Text

HVAC PART PLANS - DEMOLITION & NEW WORK, ELEVATIONS

AutoCAD SHX Text X

AutoCAD SHX Text c 2024 Johnson, Spellman & Associates, Inc.

AutoCAD SHX Text

24JS63

AutoCAD SHX Text

KKR

AutoCAD SHX Text

BSW

AutoCAD SHX Text 08/30/2024

OF SHEETS

JOB NUMBER

DRAWN BY

CHECKED BY

DATE

DRAWING NUMBER

Phone (770) 447-4555

350 Research Court, Suite 130 visit us at www.jsace.com

Peachtree Corners, Georgia 30092

Johnson, Spellman & Associates, Inc.

RE

VI

SI

O

N S

N O

D

AT

E

JA

CK

SO

N

C O

U N

TY

CO

U

RT

H O

U

SE

C O

O

LI

N G

TO

W

ER

R

EP

LA

CE

M

EN

T

JE

FF

ER

SO

N , G

A

HVAC GENERAL NOTES,

LEGEND, SCHEDULES,

DESIGN INTENT, & DETAILS

AutoCAD SHX Text

DESIGN INTENT

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

1. EXISTING EQUIPMENT AND PIPING TO REMAIN, UNLESS NOTED TO BE REMOVED. EXISTING EQUIPMENT AND PIPING TO REMAIN, UNLESS NOTED TO BE REMOVED. 2. VERIFY LOCATIONS OF EXISTING PIPING AND EQUIPMENT PRIOR TO BEGINNING VERIFY LOCATIONS OF EXISTING PIPING AND EQUIPMENT PRIOR TO BEGINNING WORK. 3. REMOVE CONDENSER WATER PIPING TO EQUIPMENT AS NOTED ON DRAWINGS. REMOVE CONDENSER WATER PIPING TO EQUIPMENT AS NOTED ON DRAWINGS. 4. ALL EXISTING EQUIPMENT AND PIPING IS SHOWN DASHED, NEW EQUIPMENT AND ALL EXISTING EQUIPMENT AND PIPING IS SHOWN DASHED, NEW EQUIPMENT AND PIPING SHOWN SOLID. 5. ROUTE PIPING AS TIGHT TO STRUCTURE AS POSSIBLE, UNLESS OTHERWISE ROUTE PIPING AS TIGHT TO STRUCTURE AS POSSIBLE, UNLESS OTHERWISE NOTED. 6. PROTECT ALL MATERIALS AND EQUIPMENT FROM DAMAGE. PROTECT ALL MATERIALS AND EQUIPMENT FROM DAMAGE. 7. CONTRACTOR SHALL VERIFY EQUIPMENT & PIPING'S AREA OF SERVICE PRIOR TO CONTRACTOR SHALL VERIFY EQUIPMENT & PIPING'S AREA OF SERVICE PRIOR TO DEMOLISHING OR RELOCATING ANY PIECE OF EQUIPMENT. 8. CONTRACTOR SHALL MAKE ALL ACCOMMODATIONS REQUIRED TO LEAVE THE JOB CONTRACTOR SHALL MAKE ALL ACCOMMODATIONS REQUIRED TO LEAVE THE JOB SITE IMPACTED BY THE REPLACEMENT OF THE COOLING TOWER IN A MANNER SIMILAR TO PRE-CONSTRUCTION STATE.

AutoCAD SHX Text

HVAC LEGEND & ABBREVIATIONS

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

OR

AutoCAD SHX Text

CONCENTRIC REDUCER

AutoCAD SHX Text

PIPE UNION

AutoCAD SHX Text

PIPE RISE

AutoCAD SHX Text

PIPE DROP

AutoCAD SHX Text

ISOLATION VALVE

AutoCAD SHX Text

BUTTERFLY VALVE

AutoCAD SHX Text

BALANCING VALVE

AutoCAD SHX Text

TWO WAY MODULATING MOTORIZED CONTROL VALVE

AutoCAD SHX Text

BALL VALVE

AutoCAD SHX Text

PIPING OR EQUIPMENT TO BE REMOVED

AutoCAD SHX Text

PIPE FLOW ARROW

AutoCAD SHX Text

GRADE ARROW-INDICATES RISE OR DROP IN DUCT OR PIPE

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

OR

AutoCAD SHX Text

CONDENSER WATER RETURN

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CONDENSER WATER SUPPLY

AutoCAD SHX Text

CWS

AutoCAD SHX Text

ECCENTRIC REDUCER FLAT SIDE ON BOTTOM OR FLAT SIDE ON TOP

AutoCAD SHX Text

EXTENT OF DEMO

AutoCAD SHX Text

EWT

AutoCAD SHX Text

DESIGN BASIS

AutoCAD SHX Text

COOLING TOWER SCHEDULE

AutoCAD SHX Text

EVAPCO AT 29-221

AutoCAD SHX Text

95%%DF

AutoCAD SHX Text

AutoCAD SHX Text

MARK

AutoCAD SHX Text

CT-1

AutoCAD SHX Text

LWT

AutoCAD SHX Text

85%%DF

AutoCAD SHX Text

GPM

AutoCAD SHX Text 1,200

AutoCAD SHX Text

78%%DF

AutoCAD SHX Text

FAN HP

AutoCAD SHX Text 2@7.5

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text (1)(2)

AutoCAD SHX Text

VOLTAGE

AutoCAD SHX Text 480v/3%%C

AutoCAD SHX Text

AutoCAD SHX Text

NOMINAL TONNAGE

AutoCAD SHX Text

NO. CELLS

AutoCAD SHX Text

WET BULB

AutoCAD SHX Text

(1) PROVIDE INVERTER DUTY MOTOR FOR USE WITH VARIABLE FREQUENCY DRIVE. PROVIDE INVERTER DUTY MOTOR FOR USE WITH VARIABLE FREQUENCY DRIVE. (2) EXISTING COOLING TOWER IS AN EVAPCO, MODEL AT 29-221, SERIAL NUMBER M035229. THE NEW COOLING TOWER EXISTING COOLING TOWER IS AN EVAPCO, MODEL AT 29-221, SERIAL NUMBER M035229. THE NEW COOLING TOWER IS TO BE FABRICATED TO BE A EXACT REPLACEMENT OF THE EXISTING TOWER, WITH ACCESSORY UPGRADES. SEE SPECIFICATIONS.

AutoCAD SHX Text A. APPLICABLE CODES AND STANDARDS APPLICABLE CODES AND STANDARDS 1. INTERNATIONAL BUILDING CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS (2020), (2022), (2024) INTERNATIONAL BUILDING CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS (2020), (2022), (2024) 2. INTERNATIONAL PLUMBING CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS (2020), (2022), (2023), (2024) INTERNATIONAL PLUMBING CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS (2020), (2022), (2023), (2024) 3. INTERNATIONAL MECHANICAL CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS (2020), (2024) INTERNATIONAL MECHANICAL CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS (2020), (2024) 4. INTERNATIONAL FUEL GAS CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS (2020), (2022) INTERNATIONAL FUEL GAS CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS (2020), (2022) 5. NATIONAL ELECTRICAL CODE, 2020 EDITION, WITH GEORGIA AMENDMENTS (2021) NATIONAL ELECTRICAL CODE, 2020 EDITION, WITH GEORGIA AMENDMENTS (2021) 6. INTERNATIONAL ENERGY CONSERVATION CODE, 2015 EDITION, WITH GEORGIA SUPPLEMENTS AND AMENDMENTS (2020), (2022), (2023) INTERNATIONAL ENERGY CONSERVATION CODE, 2015 EDITION, WITH GEORGIA SUPPLEMENTS AND AMENDMENTS (2020), (2022), (2023) 7. ALL CITY, COUNTY, STATE, REGIONAL, AND OTHER ORDINANCES APPLICABLE TO THE WORK SHALL APPLY. ALL CITY, COUNTY, STATE, REGIONAL, AND OTHER ORDINANCES APPLICABLE TO THE WORK SHALL APPLY. B. PROJECT DESIGN SCOPE PROJECT DESIGN SCOPE 1. The intent of the project is to demolish and replace the existing nominal 500 ton, two cell, counterflow The intent of the project is to demolish and replace the existing nominal 500 ton, two cell, counterflow Cooling Tower (CT-1). The new Cooling Tower shall be of equal capacity as the existing. The new Cooling CT-1). The new Cooling Tower shall be of equal capacity as the existing. The new Cooling ). The new Cooling Tower shall be of equal capacity as the existing. The new Cooling Tower is to be fabricated to be a direct replacement of the existing Cooling Tower with accessory upgrades. 2. Demolition work shall include the removal of the existing Cooling Tower and portions of the associated Demolition work shall include the removal of the existing Cooling Tower and portions of the associated above-ground condenser piping, and one of the two Variable Frequency Drive (VFDs) in the Basement Mechanical Room. 3. The electrical scope shall include the modification of the power supply for connection to the replacement The electrical scope shall include the modification of the power supply for connection to the replacement Cooling Tower, associated basin heaters, heat trace, and VFDs. 4. The BAS controls sequence of operations and points shall remain the same as currently programmed by The BAS controls sequence of operations and points shall remain the same as currently programmed by Convergint. Convergint shall provide the same sequence of operations and points for all new and existing equipment.

AutoCAD SHX Text

CONNECT TO EXISTING

AutoCAD SHX Text

BULB

AutoCAD SHX Text

AS SPECIFIED

AutoCAD SHX Text

HEAT TAPE WRAP

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

CONDUIT BY ELECTRICAL

AutoCAD SHX Text

JUNCTION BOX AND

AutoCAD SHX Text

EXPOSED TO AMBIENT

AutoCAD SHX Text

WATER PIPE

AutoCAD SHX Text

INSULATION

AutoCAD SHX Text NOTE: 1. PROVIDE A FULLY FUNCTIONAL HEAT TRACE SYSTEM FOR ALL PROVIDE A FULLY FUNCTIONAL HEAT TRACE SYSTEM FOR ALL EXISTING/NEW ABOVE GRADE CONDENSER WATER PIPING.

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

HEAT TAPE DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

COOLING TOWER PIPING DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

CWR

AutoCAD SHX Text

CWS

AutoCAD SHX Text

TWO CELL COOLING TOWER

AutoCAD SHX Text

3" DRAIN/OVERFLOW, TYP.

AutoCAD SHX Text 6"

AutoCAD SHX Text 8"

AutoCAD SHX Text

NC

AutoCAD SHX Text

NC

AutoCAD SHX Text

NO

AutoCAD SHX Text

8" EQUALIZATION

AutoCAD SHX Text

3" DRAIN/OVERFLOW

AutoCAD SHX Text 6,000

AutoCAD SHX Text

MBH

AutoCAD SHX Text

3/4" DRAIN WITH VALVE AND MALE HOSE END CONNECTION

AutoCAD SHX Text c 2024 Johnson, Spellman & Associates, Inc.

AutoCAD SHX Text

24JS63

AutoCAD SHX Text

KKR

AutoCAD SHX Text

BSW

AutoCAD SHX Text 08/30/2024

AutoCAD SHX Text

OF SHEETS

JOB NUMBER

DRAWN BY

CHECKED BY

DATE

DRAWING NUMBER

Phone (770) 447-4555

350 Research Court, Suite 130 visit us at www.jsace.com

Peachtree Corners, Georgia 30092

Johnson, Spellman & Associates, Inc.

RE

VI

SI

O

N S

N O

D

AT

E

JA

CK

SO

N

C O

U N

TY

CO

U

RT

H O

U

SE

C O

O

LI

N G

TO

W

ER

R

EP

LA

CE

M

EN

T

JE

FF

ER

SO

N , G

A

HVAC PART PLANS -

DEMOLITION & NEW

WORK, ELEVATIONS

AutoCAD SHX Text

KEYNOTES - DEMOLITION

AutoCAD SHX Text 1 EXISTING COOLING TOWER IN MECHANICAL YARD AND ASSOCIATED VARIABLE EXISTING COOLING TOWER IN MECHANICAL YARD AND ASSOCIATED VARIABLE FREQUENCY DRIVE VFD-CT-1 IN BASEMENT MECHANICAL ROOM TO BE DRIVE VFD-CT-1 IN BASEMENT MECHANICAL ROOM TO BE REMOVED AND REPLACED. EXISTING VFD CT-2 IS TO REMAIN. COORDINATE WITH NEW WORK. 2 REMOVE EXISTING PORTIONS OF CONDENSER WATER PIPING FROM THE 6" REMOVE EXISTING PORTIONS OF CONDENSER WATER PIPING FROM THE 6" BUTTERFLY VALVE TO LIMITS SHOWN ON DRAWINGS. EXISTING CONTROL VALVES TO REMAIN AND BE REUSED. 3 EXISTING SUPPORTS CONSISTING OF CONCRETE PEDESTALS AND WIDE FLANGED EXISTING SUPPORTS CONSISTING OF CONCRETE PEDESTALS AND WIDE FLANGED BEAMS TO REMAIN AND BE REUSED. COORDINATE WITH NEW WORK. 4 EXISTING PORTIONS OF UNDERGROUND CONDENSER WATER PIPING TO REMAIN AND EXISTING PORTIONS OF UNDERGROUND CONDENSER WATER PIPING TO REMAIN AND BE REUSED. COORDINATE WITH NEW WORK. 5 REMOVE AND REPLACE ALL EXISTING OVERFLOW/DRAIN PIPING. COORDINATE WITH REMOVE AND REPLACE ALL EXISTING OVERFLOW/DRAIN PIPING. COORDINATE WITH NEW WORK. 6 EXISTING DRAIN UNDERNEATH COOLING TOWER TO REMAIN AND BE REUSED. EXISTING DRAIN UNDERNEATH COOLING TOWER TO REMAIN AND BE REUSED. COORDINATE WITH NEW WORK. 7 REMOVE PORTIONS OF EXISTING HEAT TRACE SYSTEM AS REQUIRED BY PIPING REMOVE PORTIONS OF EXISTING HEAT TRACE SYSTEM AS REQUIRED BY PIPING REMOVAL. COORDINATE WITH NEW WORK. 8 COORDINATE WITH DIVISION 23 TO DISCONNECT POWER SERVING COOLING TOWER COORDINATE WITH DIVISION 23 TO DISCONNECT POWER SERVING COOLING TOWER BASIN HEATERS FOR REPLACEMENT OF EQUIPMENT. REPLACE EXISTING 30A/3/NF/WP DISCONNECT AND HOMERUN WIRING. PROTECT EXISTING CONDUIT BACK TO PANELBOARD HOMA FOR RECONNECTION TO NEW EQUIPMENT. 9 COORDINATE WITH DIVISION 23 TO DISCONNECT POWER SERVING COOLING TOWER COORDINATE WITH DIVISION 23 TO DISCONNECT POWER SERVING COOLING TOWER FANS FOR REPLACEMENT OF EQUIPMENT. REPLACE EXISTING 100A/3/NF/WP DISCONNECTS AND HOMERUN WIRING. PROTECT EXISTING CONDUIT BACK TO VARIABLE FREQUENCY DRIVES FOR RECONNECTION TO NEW EQUIPMENT. 10 COORDINATE WITH DIVISION 23 TO DISCONNECT MISCELLANEOUS 120V POWER COORDINATE WITH DIVISION 23 TO DISCONNECT MISCELLANEOUS 120V POWER SERVING VIBRATION SWITCHES, LEVEL CONTROLLER, AND HEAT TAPE FOR THE REPLACEMENT OF THE COOLING TOWER. PROTECT EXISTING WIRING FOR RECONNECTION.

AutoCAD SHX Text

%%UEXIST. CT

AutoCAD SHX Text

EXIST. 6"CWS&R (BELOW GRADE)

AutoCAD SHX Text

EXIST. 3"D (OVERFLOW)

AutoCAD SHX Text

EXIST. 6"CWS&R (BELOW GRADE)

AutoCAD SHX Text

EXIST. 8"CWS&R (BELOW GRADE)

AutoCAD SHX Text

CELL CT-1

AutoCAD SHX Text

CELL CT-2

AutoCAD SHX Text

EXIST. 6"CWS&R (BELOW GRADE)

AutoCAD SHX Text

EXIST. 6"CWS&R (BELOW GRADE)

AutoCAD SHX Text

3"D (OVERFLOW)

AutoCAD SHX Text

6"CWS&R

AutoCAD SHX Text

6"CWS&R

AutoCAD SHX Text

EXIST. 8"CWS&R (BELOW GRADE)

AutoCAD SHX Text

3"D (OVERFLOW)

AutoCAD SHX Text

CELL CT-1

AutoCAD SHX Text

CELL CT-2

AutoCAD SHX Text

8"EQUALIZATION

AutoCAD SHX Text

CT-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text M-1

AutoCAD SHX Text

AutoCAD SHX Text M-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

6"CWR

AutoCAD SHX Text

6"CWS

AutoCAD SHX Text

EXIST. 6"CWS&R BELOW GRADE

AutoCAD SHX Text

CT-1

AutoCAD SHX Text

3"D (OVERFLOW)

AutoCAD SHX Text

EXIST. CWR BUTTERFLY VALVE

AutoCAD SHX Text

EXIST. CWS BUTTERFLY VALVE

AutoCAD SHX Text

3"D (OVERFLOW)

AutoCAD SHX Text

EXIST. CWR CONTROL VALVE

AutoCAD SHX Text

8"EQUALIZATION

AutoCAD SHX Text

KEYNOTES - NEW WORK

AutoCAD SHX Text 1 INSTALL NEW COUNTERFLOW COOLING TOWER ON EXISTING CONCRETE PEDESTALS INSTALL NEW COUNTERFLOW COOLING TOWER ON EXISTING CONCRETE PEDESTALS AND BEAMS AS SHOWN. SEE DETAILS AND SCHEDULES FOR MORE INFORMATION. 2 CONNECT NEW CONDENSER WATER PIPING TO EXISTING AS SHOWN ON CONNECT NEW CONDENSER WATER PIPING TO EXISTING AS SHOWN ON DRAWINGS. HEAT TAPE TO BE ADDED TO ALL NEW CONDENSER PIPING. 3 ROUTE NEW OVERFLOW PIPING TO EXISTING DRAIN AS SHOWN. ROUTE NEW OVERFLOW PIPING TO EXISTING DRAIN AS SHOWN. 4 REPLACE PORTIONS OF HEAT TRACE SYSTEM AS NEEDED TO PROVIDE A FULLY REPLACE PORTIONS OF HEAT TRACE SYSTEM AS NEEDED TO PROVIDE A FULLY OPERATIONAL HEAT TRACE SYSTEM FOR ALL ABOVE GROUND PORTIONS OF NEW AND EXISTING CONDENSER WATER PIPING. 5 EXISTING CONTROL VALVE AND ASSOCIATED WEATHERPROOF ENCLOSURES TO EXISTING CONTROL VALVE AND ASSOCIATED WEATHERPROOF ENCLOSURES TO REMAIN. 6 PROVIDE NEW HEAVY-DUTY 30A/3/NF/WP DISCONNECT FOR NEW BASIN HEATER PROVIDE NEW HEAVY-DUTY 30A/3/NF/WP DISCONNECT FOR NEW BASIN HEATER CONNECTION AT COOLING TOWER. PROVIDE 3#10, #10G IN EXISTING CONDUIT BACK TO PANELBOARD HOMA-8,10,12. REPLACE EXISTING 20A/3p BREAKER WITH NEW 30A/3p BREAKER. REFER TO COOLING TOWER SHOP DRAWINGS. MAKE FINAL CONNECTION TO HEATERS IN ACCORDANCE WITH MANUFACTURER'S SHOP DRAWINGS. 7 PROVIDE NEW REAPLACEMENT HEAVY-DUTY 100A/3/NF/WP DISCONNECTS FOR PROVIDE NEW REAPLACEMENT HEAVY-DUTY 100A/3/NF/WP DISCONNECTS FOR NEW COOLING TOWER FANS. PROVIDE 3#4, #8G (VFD CABLE) IN EXISTING CONDUIT FROM VARIABLE FREQUENCY DRIVE TO NEW DISCONNECT SWITCH. MAKE FINAL CONNECTION TO NEW COOLING TOWER FANS. REFER TO MANUFACTURER'S SHOP DRAWINGS FOR ADDITIONAL REQUIREMENTS. 8 RECONNECT EXISTING MISCELLANEOUS 120V CIRCUITS TO VIBRATION SWITCHES RECONNECT EXISTING MISCELLANEOUS 120V CIRCUITS TO VIBRATION SWITCHES AND LEVEL CONTROLLER. COORDINATE WITH EQUIPMENT SHOP DRAWINGS. 9 INTERCEPT EXISTING 120V CIRCUIT SERVING HEAT TAPE. PROVIDE 30A/1/NF/WP INTERCEPT EXISTING 120V CIRCUIT SERVING HEAT TAPE. PROVIDE 30A/1/NF/WP DISCONNECT AT TOWER. EXTEND TO EXISTING HEAT TRACE AND NEW FAN MOTOR WINDING HEATERS. REPLACE EXISTING 20A/1p BREAKER IN PANELBOARD LOR WITH 20A/1p BREAKER WITH GROUND FAULT PROTECTION FOR EQUIPMENT. 10 EXISTING VARIABLE FREQUENCY DRIVES SERVING COOLING TOWER FANS ARE EXISTING VARIABLE FREQUENCY DRIVES SERVING COOLING TOWER FANS ARE EXISTING TO REMAIN. 11 8" EQUALIZATION PIPING, THIS IS A DEVIATION FROM EXISTING COOLING TOWER.8" EQUALIZATION PIPING, THIS IS A DEVIATION FROM EXISTING COOLING TOWER.

AutoCAD SHX Text

6"CWR

AutoCAD SHX Text

6"CWS

AutoCAD SHX Text

6"CWR

AutoCAD SHX Text

CT-1

AutoCAD SHX Text

EXIST. 6"CWS&R BELOW GRADE

AutoCAD SHX Text

EXIST. 6"CWS&R BELOW GRADE

AutoCAD SHX Text

6"CWS

AutoCAD SHX Text

3"D (OVERFLOW)

AutoCAD SHX Text

3"D (OVERFLOW)

AutoCAD SHX Text

EXIST. CONTROL VALVE

AutoCAD SHX Text

EXIST. CONTROL VALVE

AutoCAD SHX Text

8"EQUALIZATION

AutoCAD SHX Text

8"CHWR

AutoCAD SHX Text

VFD SP-1

AutoCAD SHX Text

1-1/2"RR

AutoCAD SHX Text

VFD CT-2

AutoCAD SHX Text

VFD CT-1

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text E-01

AutoCAD SHX Text

HDP

AutoCAD SHX Text

EHDP

AutoCAD SHX Text

EHEQ

AutoCAD SHX Text

HOL

AutoCAD SHX Text

LC

AutoCAD SHX Text

LOR

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text M-01

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text C-04

AutoCAD SHX Text

HOMA

AutoCAD SHX Text c 2024 Johnson, Spellman & Associates, Inc.

AutoCAD SHX Text

24JS63

AutoCAD SHX Text

KKR

AutoCAD SHX Text

BSW

AutoCAD SHX Text 08/30/2024

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text 8'

AutoCAD SHX Text 4'

AutoCAD SHX Text

HVAC MECHANICAL YARD DEMOLITION PART PLAN

AutoCAD SHX Text

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text %%uKEY PLAN

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text N

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text 8'

AutoCAD SHX Text 4'

AutoCAD SHX Text

HVAC MECHANICAL YARD NEW WORK PART PLAN

AutoCAD SHX Text

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text 8'

AutoCAD SHX Text 4'

AutoCAD SHX Text

HVAC MECHANICAL YARD NEW WORK - ELEVATION 1

AutoCAD SHX Text

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text 8'

AutoCAD SHX Text 4'

AutoCAD SHX Text

HVAC MECHANICAL YARD NEW WORK - ELEVATION 2

AutoCAD SHX Text

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text 8'

AutoCAD SHX Text 4'

AutoCAD SHX Text HVAC BASEMENT MECHANICAL ROOM REFERENCE PLAN - COOLING TOWER VFDs

AutoCAD SHX Text

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text 8'

AutoCAD SHX Text 4'

AutoCAD SHX Text

HVAC BASEMENT ELECTRICAL ROOM - HDP PANEL

AutoCAD SHX Text

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text 8'

AutoCAD SHX Text 4'

AutoCAD SHX Text

HVAC BASEMENT MECHANICAL ROOM - HOMA PANEL

AutoCAD SHX Text

AutoCAD SHX Text

NOTE: PART PLAN SHOWN FOR REFERENCE ONLY

NOTE: PART PLAN SHOWN FOR REFERENCE ONLY

COVER
M-0
M-1

File details come from the government source that posted it. Updated .