J01b - Construction Drawings - Structural and Mechanical.pdf

PDF 7 MB Posted

Attached to
Whiteriver HVAC Upgrades & USP 797-800 Compliance
Solicitation number
75H701-24-R-00026
Issued by

About this file

This document appears to be a set of construction drawings and specifications related to a federal contract opportunity for HVAC upgrades and USP 797-800 compliance at the Whiteriver Indian Hospital in Whiteriver, Arizona.

The key details are:

  • This is a solicitation for a construction project to renovate the existing HVAC systems serving the hospital operating rooms, central sterile processing, dental clinic, and server room. The project also includes upgrades to the inpatient pharmacy to comply with USP 797 & 800 standards.
  • The contract is a single Firm Fixed Price award anticipated to be between $1,000,000 and $5,000,000.
  • The period of performance is 365 calendar days from the notice to proceed.
  • The solicitation is being procured as a Request for Proposal under FAR Part 36 procedures with Lowest Price Technically Acceptable evaluation criteria.
  • A site visit is scheduled for April 2, 2024.
  • TERO fees apply and the TERO contact is provided.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FOR COMPLETE DIMENSIONS SEE ARCHITECTURAL DRAWINGS

STRUCTURAL WELDING

SPECIAL INSPECTION:

THE FOLLOWING PORTIONS OF THE WORK REQUIRE SPECIAL INSPECTION TO

BE PERFORMED IN ACCORDANCE WITH CHAPTER 17 OF THE INTERNATIONAL

BUILDING CODE.

FOOTFT.

GYPSUM

GLU-LAM

GALVANIZED

GAUGE

INTERIOR

HEATING/VENTILATING

HEIGHT

HEADED STUD ANCHOR

HORIZONTAL

LONG LEG HORIZONTAL

LIVE LOAD

KNOCK OUT

KIP (1OOO)

MANUFACTURER

MECHANICAL

MACHINE BOLT

MAXIMUM

MATERIAL

LONG LEG VERTICAL

OPENING

ON CENTER

NOT TO SCALE

NOT IN CONTRACT

MISCELLANEOUS

SCHEDULE

REQUIRED

REINFORCE (D)

PLYWOOD

MINIMUM

SQUARE

SPECIFICATION

SIMILAR

TOP OF FOOTING

TOP OF BEAM

THICKNESS

TOP AND BOTTOM

SYMMETRICAL

VERTICAL

UNLESS NOTED OTHERWISE

TYPICAL

TOP OF WALL

TOP OF STEEL

WELDED WIRE MESH

WITHOUT

TOP OF JOIST

SECTION

FOOTING

SHEETSHT.

W.W.M.

T.O.F.

TYP.

W/ W/O

U.N.O.

VERT.

T.O.S.

T.O.W.

T.O.J.

WITH

ST.

T. & B.

T.O.B.

THK.

SYM.

SPEC.

SQ.

SIM.

STEEL

O.C.

REINF.

SCHED.

SECT.

REQD.

LP

PT.

PWD.

OPNG.

PLATE

POINT

MFR.

N.I.C.

N.T.S.

MISC.

MIN.

M.B.

MECH.

MAT.

MAX.

H.V.A.C.

K

L.L.

L.L.V.

L.L.H.

KO.

INT.

JT.

JST.

IN.

JOINT

JOIST

INCH

G.L.

H.S.A.

HT.

HORIZ.

GYP.

GA.

GALV.

FTG.

CONSTRUCTION

12 K1

W 8x10

32 LHO7

11 7/8" TJI/35P

JOIST MARK

JOIST MARK

"K" SERIES

STEEL BEAM

SIZE

"LH" SERIES

JOIST

PLYWOOD TRUS

JOINT

F

C.J.

A

C

LC

DEPRESSION

CONTROL/

DECK SPAN

COLUMN GRID

OPENINGS

SLAB

FOOTING MARK

COLUMN MARK

CENTER LINE

EQUAL

FINISH

ALTERNATE

ARCHITECT ENGINEER

AMERICAN CONCRETE INSTITUTE

ANCHOR BOLT

AMERICAN INSTITUTE OF ARCHITECTS

BOARD

BOTTOM

ARCHITECT (URAL)

BOTTOM OF FOOTING

BUILDING

BLOCKING

BETWEEN

BASEMENT

CAST IN PLACE

CEMENT

CHANNEL

CONNECT (ION)

CONCRETE

COLUMN

CONCRETE MASONRY UNIT

CONTROL/CONSTRUCTION JOINT

DIAMETER

DETAIL

DEMOLITION

DOUBLE

CENTER LINE

CONTINUOUS

DIMENSION

DRAWING

CONSTRUCT (ION)

EXISTING

EACH WAY

EQUIPMENT

ENGINEER

ELECTRICAL

FRAMING

FINISH FLOOR

FOUNDATION

EXTERIOR

EXPANSION

ELEVATION

BEARING

B.O.F.

DIA., Ø

EQ.

EXT.

F.F.

FRMG.

FIN.

FDN.

EXTG.

EXP.

EQUIP.

EW.

EA.

ELEC.

ENG.

EL.

DN.

DO.

DWG.

DIM.

EACH

DOWN

DITTO

COL.

CONT.

DEMO.

DET.

LC

DBL.

CONN.

CONST.

CONC.

CEM.

C.J.

C.M.U.

CLR.

C.I.P.

CHAN.

BSMT.

BRG.

CLEAR

AT@

BLDG.

BLKG.

BM.

BLK.

BTWN.

BD.

BOT.

BEAM

BLOCK

A.E.

ARCH.

A.I.A.

ALT.

A.B.

A.C.I.

STEEL

DETAIL NUMBER

WALL NUMBER

DETAIL NUMBER

SHEET NUMBER

KEYNOTE NUMBER

S STEP IN

FOOTING

REVISION

ELEVATION

TARGET

DETAIL TITLE

SHEAR WALL

KEYNOTE

SECTION CUT

GRANULAR

PLYWOOD

SHEATHING

COURSE

BASE

C.M.U.

D. SOIL PRESSURE: 1500 PSF PER IBC SECTION 1806.

5. ALL DETAILS SHOWN APPLY WHETHER SPECIFICALLY REFERENCED OR NOT.

6. ALL STRUCTURAL CALCULATIONS SUBMITTED TO THE ARCHITECT/ENGINEER

CONSTRUCTION. THE ARCHITECT/ENGINEER SHALL BE NOTIFIED OF ANY

3. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING

FOR REVIEW, SHALL BEAR THE SEAL OF A PROFESSIONAL ENGINEER

(STRUCTURAL) REGISTERED IN THE STATE OF ARIZONA.

4. DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON

DISCREPANCIES OR INCONSISTENCIES.

DRAWINGS.

C. WIND LOAD: BASIC WIND SPEED = 115 MPH

BUILDING CODE, 2021 EDITION WITH LOCAL MODIFICATIONS.

2. DESIGN LOADS:

EXPOSURE

RISK CATEGORY

1. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE INTERNATIONAL

I. GENERAL

A. ROOF LIVE LOAD: 20 PSF

HSS SHAPES SHALL BE ASTM A500, GRADE B. ALL OTHER SHAPES AND

A. ALL STRUCTURAL STEEL CONSTRUCTION SHALL COMPLY WITH AISC

AND AISC "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS", AND

THE APPLICABLE PROVISIONS OF THE AWS , "STRUCTURAL WELDING

"CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES",

CODE".

1. STRUCTURAL STEEL:

II. METALS:

C. ALL UNFINISHED BOLTS AND NUTS SHALL BE ASTM A-325.

B. ALL STRUCTURAL WIDE FLANGE SHAPES SHALL BE ASTM A992. ALL

IV

B. ROOF DEAD LOAD: 10 PSF

PLATES SHALL BE ASTM A36.

D. E70XX ELECTRODES SHALL BE USED FOR ALL WELDS.

E. ALL ANCHOR BOLTS SHALL BE ASTM F-1554, GRADE 36.

C

FIXTURES, PIPING, AND CONDUIT INCLUDING SLEEVES, CONCRETE INSERTS,

ALL DIMENSIONS OF EXISTING CONSTRUCTION HAVE BEEN TAKEN FROM AS-BUILT

THREADED RODS AND HANGERS.

THIS PROJECT INVOLVES ADDITIONS AND ALTERATIONS TO EXISTING

CONFORM WITH EXISTING CONSTRUCTION IN ACCORDANCE WITH THE AS-BUILT

DRAWINGS. IF CONDITIONS ARE UNCOVERED WHICH DIFFER FROM WHAT IS

SHOWN ON THE DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT

AND STRUCTURAL ENGINEER FOR RECOMMENDATIONS PRIOR TO PROCEEDING

DRAWINGS AND SITE SURVEY INFORMATION. THE CONTRACTOR IS RESPONSIBLE

FOR VERIFYING ALL DIMENSIONS AND SHALL NOTIFY THE ARCHITECT OF ANY

DISCREPANCIES PRIOR TO PROCEEDING WITH THE WORK.

CONSTRUCTION, EVERY EFFORT HAS BEEN MADE TO DETAIL THE DRAWINGS TO

WITH THE WORK.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CUTTING OF ALL REQUIRED

OPENINGS THROUGH BUILDING FLOORS, WALLS, ROOFS, AND FOR THE

INSTALLATION OF WALL STRUCTURAL SUPPORT MEMBERS. THE CONTRACTOR

SHALL BE RESPONSIBLE FOR THE COMPLETE INSTALLATION OF ALL EQUIPMENT,

ANY EXISTING CONSTRUCTION OCCURS.

THAT MAY BE REQUIRED TO INSURE THAT NO SETTLEMENT OR MOVEMENT OF

MAINTENANCE OF ALL SHORING AND BRACING OF EXISTING CONSTRUCTION

THE CONTRACTOR IS RESPONSIBLE FOR THE DESIGN, PLACEMENT, AND

THIS NOTE APPLIES TO ALL EXISTING BUILDING AREAS:

1.

2.

3.

4.

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY:

CHECKED BY:

DATE DESCRIPTION

SHEET ______ OF ______

SHEET TITLE

261 North Court Avenue

Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

REVIEWED:

ES ARCHITECT / ENGINEER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

TURNER STRUCTURAL

ENGINEERING COMPANY

Engineering

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering

Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

6422 East Speedway

STANDARD STRUCTURAL

NOTES

S1.0

JDH

TBG

22052

AutoCAD SHX Text

GENERAL NOTES:

AutoCAD SHX Text

STANDARD STRUCTURAL NOTES

AutoCAD SHX Text -4"

AutoCAD SHX Text

DETAIL TITLE

AutoCAD SHX Text

ABBREVIATIONS

AutoCAD SHX Text SYMBOLS and LEGENDS

AutoCAD SHX Text

INDIAN HEALTH SERVICE

AutoCAD SHX Text

DIVISION OF FACILITIES ENGINEERING

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text L

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text

PHOENIX AREA

AutoCAD SHX Text t

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text Z

AutoCAD SHX Text n

AutoCAD SHX Text I

AutoCAD SHX Text g

AutoCAD SHX Text i

AutoCAD SHX Text S

AutoCAD SHX Text d

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text R

AutoCAD SHX Text a

AutoCAD SHX Text D

AutoCAD SHX Text t

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text g

AutoCAD SHX Text t

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text U.

AutoCAD SHX Text S.

AutoCAD SHX Text A.

AutoCAD SHX Text r

AutoCAD SHX Text a

AutoCAD SHX Text l

AutoCAD SHX Text

AutoCAD SHX Text c

AutoCAD SHX Text t

AutoCAD SHX Text u

AutoCAD SHX Text r

AutoCAD SHX Text u

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text e

AutoCAD SHX Text C

AutoCAD SHX Text d

AutoCAD SHX Text P

AutoCAD SHX Text r

AutoCAD SHX Text o

AutoCAD SHX Text f

AutoCAD SHX Text l

AutoCAD SHX Text a

AutoCAD SHX Text n

AutoCAD SHX Text o

AutoCAD SHX Text i

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text s

AutoCAD SHX Text s

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text O.

AutoCAD SHX Text n

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text i

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text E

AutoCAD SHX Text x

AutoCAD SHX Text p

AutoCAD SHX Text i

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text 09/

AutoCAD SHX Text 30/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

HART

AutoCAD SHX Text

JAMES D.

AutoCAD SHX Text 27343

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text #22052

AutoCAD SHX Text Tucson Az, 85712

AutoCAD SHX Text 2806 N. Alvernon Way Ste. 400

AutoCAD SHX Text

(520) 323-3422 kmakomaski Text Box kmakomaski Text Box

8 9

F

G

H

I

10 11 129A 9C

(E) W 16x36 (E) W 16x36 (E) W 16x36 (E) W 16x36

(E) W 16x40 (E) W 16x50 (E) W 16x88 (E) W 16x64

(E) W 21x44

(E) W 16x40

(E ) W

4x

(E ) W

(E) 16 H6 do do do do do

(E ) 2

8L H0

(E ) 2

8L H1

(E ) 2

8L H1

(E ) 2

8L H1

(E ) W

(E) W 16x36

(E ) 2

8L H0

(E ) 2

8L H0 do do do do

(E ) 2

8L H1

(E ) 2

8L H1 do do do do do

(E ) 2

8L H0

(E ) W

0x

(E) W 16x26(E) W 16x26

) 1

4H do do do do

(E ) 1

4H

(E ) W

(N x1

8 (E ) 2

8L H0

(N ) W x1

(N ) W x1

S2.1

4,700#

(E ) W

6x

) 2

8L H1

(E ) 2

8L H1

(E ) 2

8L H1

(E ) 2

8L H1

(E ) 2

8L H1

TY

P.

S2.1

S2.1

C 6x8.2, TYPICAL

S2.1

1 SCALE: 1/8" = 1'-0"

PARTIAL ROOF FRAMING PLAN 4' 8'0 16'

PLAN

NORTH

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY:

CHECKED BY:

DATE DESCRIPTION

SHEET ______ OF ______

SHEET TITLE

261 North Court Avenue

Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

REVIEWED:

ES ARCHITECT / ENGINEER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

TURNER STRUCTURAL

ENGINEERING COMPANY

Engineering

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering

Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

6422 East Speedway

PARTIAL ROOF

FRAMING PLAN

S1.1

JDH

TBG

22052

1. INDICATES NEW MECHANICAL UNIT ON ROOF. SEE MECHANICAL DRAWINGS FOR EXACT

SIZE AND LOCATION. PROVIDE FRAMING BELOW UNIT CURB PER DETAIL 2/S2.1.

2. EXISTING MECHANICAL PENTHOUSE.

3. INDICATES NEW DUCT PENETRATION THROUGH ROOF. SEE MECHANICAL DRAWINGS

FOR EXACT SIZE AND LOCATION. PROVIDE FRAMING AROUND DUCT PENETRATION

PER DETAIL 2/S2.1.

AutoCAD SHX Text

INDIAN HEALTH SERVICE

AutoCAD SHX Text

DIVISION OF FACILITIES ENGINEERING

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text L

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text

PHOENIX AREA

AutoCAD SHX Text t

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text Z

AutoCAD SHX Text n

AutoCAD SHX Text I

AutoCAD SHX Text g

AutoCAD SHX Text i

AutoCAD SHX Text S

AutoCAD SHX Text d

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text R

AutoCAD SHX Text a

AutoCAD SHX Text D

AutoCAD SHX Text t

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text g

AutoCAD SHX Text t

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text U.

AutoCAD SHX Text S.

AutoCAD SHX Text A.

AutoCAD SHX Text r

AutoCAD SHX Text a

AutoCAD SHX Text l

AutoCAD SHX Text

AutoCAD SHX Text c

AutoCAD SHX Text t

AutoCAD SHX Text u

AutoCAD SHX Text r

AutoCAD SHX Text u

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text e

AutoCAD SHX Text C

AutoCAD SHX Text d

AutoCAD SHX Text P

AutoCAD SHX Text r

AutoCAD SHX Text o

AutoCAD SHX Text f

AutoCAD SHX Text l

AutoCAD SHX Text a

AutoCAD SHX Text n

AutoCAD SHX Text o

AutoCAD SHX Text i

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text s

AutoCAD SHX Text s

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text O.

AutoCAD SHX Text n

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text i

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text E

AutoCAD SHX Text x

AutoCAD SHX Text p

AutoCAD SHX Text i

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text 09/

AutoCAD SHX Text 30/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

HART

AutoCAD SHX Text

JAMES D.

AutoCAD SHX Text 27343

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text #22052

AutoCAD SHX Text Tucson Az, 85712

AutoCAD SHX Text 2806 N. Alvernon Way Ste. 400

AutoCAD SHX Text

(520) 323-3422

AutoCAD SHX Text

KEYNOTES:

kmakomaski Text Box kmakomaski

E

F

G

H

(E) W 16x36

(E) W 16x58

(E ) 2

8L H0

(E ) 2

8L H0

(E

) W

2x

1x

) 2

8L H0

(E ) 2

8L H0

(E ) 2

8L H0

15 16 17

D

(E) W 16x58

(E ) W

1x

(E) W 16x36 (E) W 16x36 (E) W 16x36

(E) W 16x58 (E) W 16x58 (E) W 16x78

(E ) 2

8L H0

(E ) 2

4L H0

(E ) 2

4L H0

(E ) 2

4L H0

(E ) 2

8L H0

(E ) 2

8L H0 do do do

(E ) 2

8L H1

(E ) 2

8L H1

(E ) 2

8L H1

(E ) 2

8L H0

(E ) 2

4L H0

(E ) 2

4L H0

(E ) 2

4L H0

(E ) 2

8L H0

(E ) 2

8L H0 do do do

(E ) 2

8L H1

(E ) 2

8L H1

(E ) 2

8L H1

(E) W 16x36 (E) W 16x36 (E) W 16x36

(E ) 2

8L H0

I

(E)

C 6x8.2, TYP.

TY

P.

S2.1

1,500#

TY

P.

S2.1 1,500#

TY

P.

S2.1

C 6x8.2, TYP.

BA C

(E ) W

(E) W 10x12

(E ) W

(E) W 8x10

) W

) B

F2

) 1

(E) 18 K3

(E) W 14x22

(E) 18 K3 do do do do do do do do do

(E) 14 K2

(E) W 14 k2 do do do do do do do do do do

TY

P.

S2.1

TY

P.

S2.1

C 6x8.2, TYP.

500#

1 SCALE: 1/8" = 1'-0"

PARTIAL ROOF FRAMING PLAN - Hospital 4' 8'0 16'

PLAN

NORTH

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY:

CHECKED BY:

DATE DESCRIPTION

SHEET ______ OF ______

SHEET TITLE

261 North Court Avenue

Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

REVIEWED:

ES ARCHITECT / ENGINEER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

TURNER STRUCTURAL

ENGINEERING COMPANY

Engineering

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering

Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

6422 East Speedway

PARTIAL ROOF

FRAMING PLANS

S1.2

JDH

TBG

22052

1. INDICATES NEW MECHANICAL UNIT ON ROOF. SEE MECHANICAL DRAWINGS FOR EXACT

SIZE AND LOCATION. PROVIDE FRAMING BELOW UNIT CURB PER DETAIL 2/S2.1.

2. EXISTING MECHANICAL UNIT.

3. EXISTING DUCT PENETRATION.

4. NEW DUCT PENETRATION THROUGH ROOF. SEE MECHANICAL DRAWINGS FOR EXACT

SIZE AND LOCATION. PROVIDE FRAMING AROUND OPENING PER DETAIL 2/S2.1.

2 SCALE: 1/8" = 1'-0"

PARTIAL ROOF FRAMING PLAN - Dental 4' 8'0 16'

PLAN

NORTH

AutoCAD SHX Text

INDIAN HEALTH SERVICE

AutoCAD SHX Text

DIVISION OF FACILITIES ENGINEERING

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text L

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text

PHOENIX AREA

AutoCAD SHX Text t

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text Z

AutoCAD SHX Text n

AutoCAD SHX Text I

AutoCAD SHX Text g

AutoCAD SHX Text i

AutoCAD SHX Text S

AutoCAD SHX Text d

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text R

AutoCAD SHX Text a

AutoCAD SHX Text D

AutoCAD SHX Text t

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text g

AutoCAD SHX Text t

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text U.

AutoCAD SHX Text S.

AutoCAD SHX Text A.

AutoCAD SHX Text r

AutoCAD SHX Text a

AutoCAD SHX Text l

AutoCAD SHX Text

AutoCAD SHX Text c

AutoCAD SHX Text t

AutoCAD SHX Text u

AutoCAD SHX Text r

AutoCAD SHX Text u

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text e

AutoCAD SHX Text C

AutoCAD SHX Text d

AutoCAD SHX Text P

AutoCAD SHX Text r

AutoCAD SHX Text o

AutoCAD SHX Text f

AutoCAD SHX Text l

AutoCAD SHX Text a

AutoCAD SHX Text n

AutoCAD SHX Text o

AutoCAD SHX Text i

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text s

AutoCAD SHX Text s

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text O.

AutoCAD SHX Text n

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text i

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text E

AutoCAD SHX Text x

AutoCAD SHX Text p

AutoCAD SHX Text i

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text 09/

AutoCAD SHX Text 30/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

HART

AutoCAD SHX Text

JAMES D.

AutoCAD SHX Text 27343

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text #22052

AutoCAD SHX Text Tucson Az, 85712

AutoCAD SHX Text 2806 N. Alvernon Way Ste. 400

AutoCAD SHX Text

(520) 323-3422

AutoCAD SHX Text

KEYNOTES:

kmakomaski Text Box kmakomaski

3/4" = 1'-0" TYPICAL UNLESS NOTED OTHERWISE

3"

1/

2"

1 1/2"

3/16

P 1/4" x 4 1/2" x 6" W/ 2 - 3/4" Ø A325

BOLTS SNUG TIGHT

L

BEAM, SEE

PLAN

EXISTING BEAM,

SEE PLAN

EXISTING ANGLE

3/16 WT 5x7.5 CONT.

2-12

EXISTING STEEL

DECK

S2.1

AUXILIARY WEB

MEMBER AS

REQ'D. PER

DET.

3/16 C 6x8.2, TYP.

3/16

C 6x8.2 x BELOW

MECH. CURB AND

AROUND ALL DUCT

PENETRATIONS

3/16 P 1/4" x 4" x 4", TYP.

L

EXTG. ROOF JOIST,

TYP.

MECH.

EQUIP.

SUPPORT

3/16

EA. END

A

NOTE:

DO NOT SUSPEND ANYTHING

FROM DECK OR BRIDGING

PROVIDE SUPPLEMENTAL

FRAMING MEMBERS AS

A

MECH. EQUIP.

SUPPORT

AUXILIARY JOIST WEB

L 1 1/4 x 1 1/4 x 1/4 WHERE

A > 9", OMIT WEB WHEN

A < 9"

NEW MECHANICAL

UNIT, SEE MECH.

DRAWINGS

REQUIRED.

EXISTING STEEL

DECK

3/16 WT 5x7.5

CONT.

C 6x8.2 C 6x8.2

3/16

BEAM, SEE

PLAN

3/16 P 1/4" x 4 3/4" x 6", TYP.

L

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY:

CHECKED BY:

DATE DESCRIPTION

SHEET ______ OF ______

SHEET TITLE

261 North Court Avenue

Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

REVIEWED:

ES ARCHITECT / ENGINEER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

STRUCTURAL

Turner Structural

2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

TURNER STRUCTURAL

ENGINEERING COMPANY

Engineering

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering

Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

6422 East Speedway

FRAMING

DETAILS

S2.1

22052

TBG

JDH

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NEW SUPPORT BEAM CONN. TO EXTG.

AutoCAD SHX Text

NEW OPENING/MECH. UNIT AT EXTG.

AutoCAD SHX Text

AUXILIARY WEB MEMBER

AutoCAD SHX Text

AutoCAD SHX Text

MECH. UNIT SUPPORT BEAMS

AutoCAD SHX Text

INDIAN HEALTH SERVICE

AutoCAD SHX Text

DIVISION OF FACILITIES ENGINEERING

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text H

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text L

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text

PHOENIX AREA

AutoCAD SHX Text t

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text Z

AutoCAD SHX Text n

AutoCAD SHX Text I

AutoCAD SHX Text g

AutoCAD SHX Text i

AutoCAD SHX Text S

AutoCAD SHX Text d

AutoCAD SHX Text e

AutoCAD SHX Text e

AutoCAD SHX Text R

AutoCAD SHX Text a

AutoCAD SHX Text D

AutoCAD SHX Text t

AutoCAD SHX Text s

AutoCAD SHX Text i

AutoCAD SHX Text g

AutoCAD SHX Text t

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text U.

AutoCAD SHX Text S.

AutoCAD SHX Text A.

AutoCAD SHX Text r

AutoCAD SHX Text a

AutoCAD SHX Text l

AutoCAD SHX Text

AutoCAD SHX Text c

AutoCAD SHX Text t

AutoCAD SHX Text u

AutoCAD SHX Text r

AutoCAD SHX Text u

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text e

AutoCAD SHX Text C

AutoCAD SHX Text d

AutoCAD SHX Text P

AutoCAD SHX Text r

AutoCAD SHX Text o

AutoCAD SHX Text f

AutoCAD SHX Text l

AutoCAD SHX Text a

AutoCAD SHX Text n

AutoCAD SHX Text o

AutoCAD SHX Text i

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text s

AutoCAD SHX Text s

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text O.

AutoCAD SHX Text n

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text g

AutoCAD SHX Text n

AutoCAD SHX Text i

AutoCAD SHX Text e

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text E

AutoCAD SHX Text x

AutoCAD SHX Text p

AutoCAD SHX Text i

AutoCAD SHX Text r

AutoCAD SHX Text e

AutoCAD SHX Text s

AutoCAD SHX Text 09/

AutoCAD SHX Text 30/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

HART

AutoCAD SHX Text

JAMES D.

AutoCAD SHX Text 27343

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text #22052

AutoCAD SHX Text Tucson Az, 85712

AutoCAD SHX Text 2806 N. Alvernon Way Ste. 400

AutoCAD SHX Text

(520) 323-3422 kmakomaski Text Box kmakomaski

EXISTING CONDITIONS NOTE

EVERY EFFORT HAS BEEN MADE TO PROVIDE ACCURATE INFORMATION REGARDING EXISTING CONDITIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS ABOVE THE CEILING PRIOR TO BIDDING THE PROJECT. ANY CONFLICTS DISCOVERED BY MECHANICAL CONTRACTOR DURING THE PRE-BID PROCESS WHICH MAY EFFECT THE SCOPE OR COST SHALL BE REPORTED TO THE ARCHITECT AND ENGINEER PRIOR TO PROVIDING A BID. THE SUBMISSION OF A BID SHALL INDICATE MECHANICAL CONTRACTOR COMPLETELY

UNDERSTANDS THESE CONTRACT DOCUMENTS AND THE EXISTING CONDITIONS.

MECHANICAL CONTRACTOR SHALL COORDINATE ALL PATCHING AND REPAIRING WORK WITH THE GENERAL CONTRACTOR AND ARCHITECT.

LEGEND

CEILING DIFFUSER - PRICE MODEL SMD, FRAME FOR HARD CEILINGCDA

RGA RETURN GRILLE - PRICE MODEL 80, FRAME FOR HARD CEILING

S ROOM TEMPERATURE SENSOR

RETURN DUCT UP

EXHAUST DUCT UP

RETURN DUCT DOWN

EXHAUST DUCT DOWN

FLEX CONNECTION

OPPOSED BLADE MANUAL DAMPER

SUPPLY DUCT DOWN

SUPPLY DUCT UP

ACCESS PANEL

SYMBOL DESCRIPTION

MECHANICAL SYMBOL LEGEND

1. FIELD COORDINATE EXACT LOCATION OF ROOM TEMPERATURE SENSORS WITH

ARCHITECT TO AVOID CONFLICT WITH FURNITURE, MILLWORK, ARTWORK, ETC.

2. COORDINATE EXACT LOCATION OF AIR DEVICES AND CEILING ACCESS PANELS WITH

ARCHITECTURAL REFLECTED CEILING PLAN, INTERIOR DESIGNER PLANS AND

ELECTRICAL LIGHTING PLANS.

3. FIELD COORDINATE FINAL EQUIPMENT NUMBERING (FAN POWERED BOXES, VAV BOXES,

CONSTANT VOLUME BOXES, SPLIT SYSTEM UNITS, EXHAUST FANS) WITH BUILDING

ENGINEER AND CONTROLS CONTRACTOR.

4. IN GENERAL FLEXIBLE DUCT LENGTHS TO BE 7'-0'' LONG. ABOVE CEILING EXISTING

STRUCTURE CONDITIONS MAY CAUSE FOR LONGER RUNS.

5. IN GENERAL THE EXHAUST DUCT SHALL BE LOCATED ABOVE THE MEDIUM PRESSURE

AND BE ROUTED THROUGH THE EXISTING CONCRETE BEAM OPENINGS.

6. TAB CONTRACTOR TO BALANCE RETURN AND EXHAUST TO MEET THE PRESSURE

RELATIONSHIP REQUIRED PER ASHRAE 170 SECTION 7.1.

7. FCDA CEILING DIFFUSERS TO INCLUDE MERV 14 FILTERS PER ASHRAE 170 SECTION 6.4.

FIRE DAMPER / FIRE SMOKE DAMPER

GENERAL NOTES

EGA EXHAUST GRILLE - PRICE MODEL 80, FRAME FOR HARD CEILING

CEILING FILTER DIFFUSER - PRICE MODEL AMDC, FRAME FOR HARD CEILINGFCDA

P ROOM PRESSURE SENSOR

M0.1

MECHANICAL

GENERAL INFORMATION

22063

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

PROJECT No.

(520)-200-2612 ZonaMEP.com

MECHANICAL . PLUMBING . ELECTRICAL

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY: KM

CHECKED BY: SM

DATE DESCRIPTION

DFE BRANCH CHIEF

APPROVED:

CONCURRENCE

DFE CHIEF

REVIEWED:

ES ARCHITECT / ENGINEER DATE

DATE

DATE

SHEET ______ OF ______

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

SHEET TITLE

261 North Court Avenue Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

STRUCTURAL

Turner Structural Engineering 2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering 6422 East Speedway Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

M1.2

SHEET ______ OF ______

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

4A

4B

4D

4C

MECHANICAL DEMO FLOOR PLAN - SURGERY SUITE

SCALE: 1/8" = 1'-0"

4' 8'0 16'

E

F

G

H

I

(E) AHU-7

(E) TMB-2

(E) TMB-3

(E) TMB-3

REMOVE (E) AHU-9

ON ROOF

(E) STEAM HUMIDIFIER

REMOVE (E) RETURN

DUCT TO POC

POC

REMOVE (E) SUPPLY

DUCT TO POC

POC (TYP. 2 PL.)

REMOVE (E) DUCT TO POC

OH.

REMOVE (E) DUCT AND CAP

14''

RND.

16x16 16'' RND. 14'' RND.

S

20x20

S x1

18'' RND.

16''

RND.14'' RND.

x1

4 H

OT

x1

8 C

OL

D

16x12 x8

8x12 x1

12x12

S

8'' RN

D.

10x12 10x12 x1

8x x1

10x12

S

8'' R

ND

8'' RN

D.

7'' RN

D.

IT ROOM

PATIENT

REGISTRATION

170B CARETEAM

WORKSTATIONS

170A

HALLWAY

GENERAL

TREATMENT

GENERAL

TREATMENT

ORTHO

EXAM

STORAGE

ORTHO

DIRTY/CSR

WOUND

CARE EXAM

WOUND

CARE EXAM

P.T. OFFICE

179A

INPATIENT

P.T.

179B

TRIAGE/VITALS

PODIATRY

EXAM

PODIATRY

EXAM

STORAGE

GEN/PODIATRY

WAITING

8''

RND.

12x4

12x4

8'' R

ND

16x18

S

14''

RND.

TB-1

REMOVE (E) AIR DEVICE AND

ASSOC. BRANCH SUPPLY AIR DUCT.

CAP (E) DUCT OH. AT NEAREST

BRANCH DUCT. FIELD VERIFY

EXTENT OF DEMOLITION

(E) SOUND

ATTENUATOR

DEMO FLOOR PLAN

MECHANICAL

SURGERY STE

M1.2 22063

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

PROJECT No.

(520)-200-2612 ZonaMEP.com

MECHANICAL . PLUMBING . ELECTRICAL

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY: KM

CHECKED BY: SM

DATE DESCRIPTION

DFE BRANCH CHIEF

APPROVED:

CONCURRENCE

DFE CHIEF

REVIEWED:

ES ARCHITECT / ENGINEER DATE

DATE

DATE

SHEET ______ OF ______

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

SHEET TITLE

261 North Court Avenue Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

STRUCTURAL

Turner Structural Engineering 2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering 6422 East Speedway Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

IT ROOM

HALLWAY

GENERAL

TREATMENT

GENERAL

TREATMENT

172WAITING

DECONTAMINATION

ROOM

CSR ANTE

ROOM

4A

4B

4D

4C

PATIENT REG.

170B

9'-0"

CARETEAM

170A

9'-0"

SUPPLY & EQ.

9'-0"

TRIAGE

9'-0"

LACTATION RM

9'-0"

TOILET

9'-0"

COLOR CK RM

9'-0"

LAB

9'-0"

NOURSH.

9'-0"

MEDS

9'-0"

TOILET

9'-0"

WAITING

9'-0"

INFANT CHECK RM

265A

9'-0"

NURSE STA.

9'-0"

SOILED UTILITY

9'-0"

LOUNGE

9'-0"

TOILET

9'-0"

OFFICE

9'-0"

CORRIDOR

265A

9'-0"

TOILET

9'-0"

2-BED ROOM

9'-0"

JAN.

9'-0"

1-BED ROOM

9'-0"

TOILET

9'-0"

EQ. ALCOVE

9'-0"

RECOVERY #3

9'-0"

TOILET

9'-0"

RECOVERY #4

9'-0"

SOILED UTILITY

9'-0"

CORRIDOR

9'-0"

RECOVERY #2

9'-0"

RECOVERY #1

9'-0"

STERILE SUPPLY

9'-0"

PYXIS STA.

257C

9'-0"

DOC DICTATION

257B

9'-0"

TOILET

9'-0"

LOUNGE

9'-0"

CHANGE

9'-0"

CHANGE

9'-0"

CORRIDOR

245A

9'-0"

JAN.

9'-0"

NURSE STATION

257A

9'-0"

OPERATING ROOM

9'-0"

OPERATING ROOM

244A

9'-0"

STERIS

9'-0"

STERILE SUPPLIES

9'-0"

CORRIDOR

9'-0"

LDR

9'-0"

MECHANICAL FLOOR PLAN - SURGERY SUITE

SCALE: 1/8" = 1'-0"

4' 8'0 16'

F

G

H

I

S S

(E) AHU-7

(E) TMB-2

(E) TMB-3

(E) TMB-3

36x18 R/A DTR. PROVIDE

HIGH-EFF TAKE-OFF TO

30x16 R/A DUCT OH.

ON ROOF

30x16

POC

36x18 S/A DTR. TRANS FROM 36x18 TO 24x18 OH.

POC

(TYP. 2 PL.)

28x20 x1

4 18x14

AHU

x1

(E) HC-2

1,600 CFM

x1

14x14 14x14

OH.HC

IT ROOM

HALLWAY

GENERAL

TREATMENT

GENERAL

TREATMENT

172WAITING

DECONTAMINATION

ROOM

CSR ANTE

ROOM

4B

4D

PATIENT REG.

170B

9'-0"

CARETEAM

170A

9'-0"

SUPPLY & EQ.

9'-0"

TRIAGE

9'-0"

LACTATION RM

9'-0"

TOILET

9'-0"

COLOR CK RM

9'-0"

LAB

9'-0"TOILET

9'-0"

WAITING

9'-0"

9'-0"

RECOVERY #1

9'-0"

STERILE SUPPLY

9'-0"

JAN.

9'-0"

NURSE STATION

257A

9'-0"

9'-0"9'-0"

STERIS

9'-0"

STERILE SUPPLIES

9'-0"

CORRIDOR

9'-0"

MECHANICAL PIPING FLOOR PLAN - SURGERY SUITE

SCALE: 1/8" = 1'-0"

4' 8'0 16'

F

G

ON ROOF

POC

AHU

(E) REHEAT COILS

(TYP. 2 PL.)

OH.HC

(E) AHU-6

14x14 S/A ABV. 12x10

R/A OH.

12/10 12/10

POC

(E) SCD

160 CFM

(TYP. 10 PL.)

(E) HC-1

1,200 CFM

(E) SCD

300 CFM

(TYP. 4 PL.) H

H

8x8 CD

200 CFM

24x12 RG

150 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(TYP. 2 PL.)

(E) RG

100 CFM

(E) CD

125 CFM

S H

SH

FLOOR PLANS

MECHANICAL

SURGERY SUITE

M1.3 22063

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

PROJECT No.

(520)-200-2612 ZonaMEP.com

MECHANICAL . PLUMBING . ELECTRICAL

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY: KM

CHECKED BY: SM

DATE DESCRIPTION

DFE BRANCH CHIEF

APPROVED:

CONCURRENCE

DFE CHIEF

REVIEWED:

ES ARCHITECT / ENGINEER DATE

DATE

DATE

SHEET ______ OF ______

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

SHEET TITLE

261 North Court Avenue Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

STRUCTURAL

Turner Structural Engineering 2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering 6422 East Speedway Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

1/4" = 1'-O"

PENTHOUSE NO. 4 DEMO MECHANICAL PLAN

(E) 144x48 RELIEF AIR LOUVER

(TYP 2 PL)

x2 x1

1/4" = 1'-O"

PENTHOUSE NO. 4 MECHANICAL PLAN

x2 x1

REMOVE (E) AHU & ASSOCIATED ROOF CURB ON ROOF.

MECH. CONTRACTOR SHALL COORD. SEQUENCE OF

INSTALLATION AND DEMOLITION OF ROOFTOP EQUIP.

W/ GEN. CONTRACTOR PRIOR TO BID

HW

CW

AHU

ON FACTORY

EQUIPMENT CURB

x24 x12

HW

CW

x24 x12

PENTHOUSE 4

MECHANICAL ROOF PLAN

SURGERY SUITE

M1.4 22063

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

PROJECT No.

(520)-200-2612 ZonaMEP.com

MECHANICAL . PLUMBING . ELECTRICAL

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY: KM

CHECKED BY: SM

DATE DESCRIPTION

DFE BRANCH CHIEF

APPROVED:

CONCURRENCE

DFE CHIEF

REVIEWED:

ES ARCHITECT / ENGINEER DATE

DATE

DATE

SHEET ______ OF ______

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

SHEET TITLE

261 North Court Avenue Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

STRUCTURAL

Turner Structural Engineering 2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering 6422 East Speedway Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

IT ROOM

ORTHO

EXAM

ORTHO

EXAM

ORTHO

EXAM

STORAGE

ORTHO

DECONTAMINATION

ROOM

CSR ANTE

ROOM

CENTRAL

STERILE

ROOM

CORRIDOR

IT ROOM

ORTHO

EXAM

ORTHO

EXAM

ORTHO

EXAM

STORAGE

ORTHO

DECONTAMINATION

ROOM

CSR ANTE

ROOM

CENTRAL

STERILE

ROOM

CORRIDOR

MECHANICAL DEMO FLOOR PLAN - CSR

SCALE: 1/8" = 1'-0"

4' 8'0 16'

MECHANICAL FLOOR PLAN - CSR

SCALE: 1/8" = 1'-0"

4' 8'0 16'

MECHANICAL DEMO ROOF PLAN - CSR

SCALE: 1/8" = 1'-0"

4' 8'0 16'

12''

24x24 RG

1050 CFM

22x10 TGA W/ OBMD

MECHANICAL ROOF PLAN - CSR

SCALE: 1/8" = 1'-0"

4' 8'0 16'

ON ROOF

REMOVE (E) RTU & ASSOC COND. PIPING.

COORD. RELOCATION OF (E) ELECT. CIRCUIT W/

ELECT. CONTRACTOR. RETAIN (E) ROOF CURB &

ASSOC. DUCTWORK

(E) RTU

22x10 TGA

(E) S/A & R/A DUCT THRU ROOF. MECH. CONTRACTOR

SHALL FIELD VERIFY AND DOCUMENT ROUTING AND SIZE

OF ALL PRIOR TO THE START OF CONSTRUCTION.

CONTRACTOR SHALL ENSURE ALL EXISTING DUCTWORK IS

SEALED WITH DUCT SEALANT AT EACH JOINT. PROVIDE A

SHOP DRAWING TO THE IHS PROJECT MANAGER &

ENGINEER OF RECORD

(E) HUMIDIFIER TO BE REMOVED. COORD. EXTENT OF

DEMO FOR (E) DI WATER SUPPLY & ASSOCIATED DRAIN

E

F

E

F

E

F

G

E

F

G

(E) RTU

RTU

x1 x1

18x18 SA DUCT ON ROOF. TRANS. FROM 18x18 TO (E) 20x20 DTR. FIELD VERIFY EXACT

SIZE PRIOR TO START OF DEMOLITION

28x14 R/A DUCT ON ROOF. TRANS. FROM 28x14 TO (E) 18x18 DTR. FIELD VERIFY EXACT

SIZE PRIOR TO START OF DEMOLITION

FILL (E) CURB WITH BATT INSULATION &

PROVIDE SHEETMETAL CAP OVER (E) CURB.

WELD ALL SEAMS AND PROVIDE SILICONE

DUCT SEALANT AT ALL JOINTS

PROVIDE 316SS OR ALUM DUCT

SECTION W/ DRAIN TO MEET

HUMID. MANUFACTURER'S

WETTED SECTION

RI

SE

DR

OP

(E) RG

250 CFM

3/4" STEAM SUPPLY & 3/4"

STEAM COND. UP/DN FROM

ROOF. FOR CONT. SEE

3/4" STEAM COND. OH & DN ON

WALL TO (E) SAN. FLR DRAIN

FIELD VERIFY EXACT LOCATION

(E) S/A & R/A DUCT THRU ROOF.

FOR CONT. SEE

(E) CD

300 CFM

10x10 CD - 2W

200 CFM

12x12 EG

150 CFM

3/4" STEAM SUPPLY & 3/4" STEAM COND.

UP/DN THRU ROOF. FOR CONT. SEE

12x12 CD - 3W

300 CFM

(TYP. 4 PL.)

REMOVE (E) EG & CAP (E) EXH. DUCT ABV. CLG.

MECH. CONTRACTOR SHALL FIELD VERIFY AND

DOCUMENT ROUTING AND SIZE OF ALL PRIOR

TO THE START OF CONSTRUCTION

REMOVE (E) CD & CAP (E) DUCT OH.

REMOVE (E) CD IN COORDINATION WITH THE REFINISH

OF THE EXISTING CEILING. REINSTALLATION SHALL

INCLUDE SEALING THE (E) AIR DEVICE TO THE EXISTING

CEILING TO MINIMIZE VAPOR TRANSMISSION

(TYP. 6 PL.)

REMOVE (E) RG IN COORDINATION WITH THE REFINISH

OF THE EXISTING CEILING. REINSTALLATION SHALL

INCLUDE SEALING THE (E) AIR DEVICE TO THE EXISTING

CEILING TO MINIMIZE VAPOR TRANSMISSION

(TYP. 2 PL.)

REMOVE (E) CD/RG & CAP (E) DUCT OH.

REMOVE (E) EG IN COORDINATION WITH THE REFINISH

OF THE EXISTING CEILING. REINSTALLATION SHALL

INCLUDE SEALING THE (E) AIR DEVICE TO THE

EXISTING CEILING TO MINIMIZE VAPOR TRANSMISSION

(TYP. 2 PL.)

REMOVE (E) CD/RG & CAP (E) DUCT OH.

CAP (E) S/A AND R/A DUCT OH ABOVE CORRIDOR.

ABANDON (E) DUCTWORK OH ABV. CSR

(E) EXH. FAN ON ROOF

(TYP. 2 PL.)

(E) ROOFTOP EXH. FANS

(TYP. 4 PL.)

(E) EXH. FAN ON ROOF.

REBALANCE TO 150 CFM

12''

22x10 TGA W/ OBMD

22x10 TGA

12''

22x10 TGA W/ OBMD

22x10 TGA

(E) HUMIDIFIER TO REMAIN. FIELD VERIFY EXACT

LOCATION W/ OWNER PRIOR TO START OF

CONSTRUCTION. DRI-STEEM VAPORMIST VM-6

(18.0 lbs/hr, 208/1 V, 28.8 FLA)

WITH BLOWER MOUNTED ON

TOP OF UNIT

FLOOR PLANS

MECHANICAL

CSR

M1.5 22063

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

PROJECT No.

(520)-200-2612 ZonaMEP.com

MECHANICAL . PLUMBING . ELECTRICAL

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY: KM

CHECKED BY: SM

DATE DESCRIPTION

DFE BRANCH CHIEF

APPROVED:

CONCURRENCE

DFE CHIEF

REVIEWED:

ES ARCHITECT / ENGINEER DATE

DATE

DATE

SHEET ______ OF ______

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

SHEET TITLE

261 North Court Avenue Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

STRUCTURAL

Turner Structural Engineering 2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering 6422 East Speedway Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

FECAP AP

HALL

DC178

HALL

DC181

HALL

DC180

CLEAN

WORK

DC176

SOILED

UTILITY

DC177

DENTAL

LAB

DC174

STERILE

WORK

DC175

ENLARGED MECHANICAL FLOOR PLAN

SCALE: 1/4" = 1'-0"

2' 4'0 8'

14x14 EDTR TO EF-1 ON ROOF.

FOR CONT. SEE

14x14

12x8 EXH. OH & DN IN SHAFT. PROVIDE 12x24 EG @ ;12'' AFF (400 CFM)

(TYP. 2 PL.)

DEMO (E) RG.

(TYP. 2 PL.)

(E) HP-24 REBALANCE TO 600 CFM

SUPPLY, 450 RETURN AND 150 CFM

OUTSIDE AIR

COORD. EXPANSION OF (E) SHAFT W/

GEN. CONTRACTOR

P P P P

PRESSURE MONITORS

(TYP. 4 PL.)

CB

24x24 RG. REBALANCE

TO 450 CFM

24x24 RG

450 CFM

DEMO (E) RG.

(TYP. 2 PL.)

12x8 EXH. OH & DN IN SHAFT. PROVIDE 12x24 EG @ +/-12'' AFF (400 CFM)

(TYP. 2 PL.)

(E) HP-25 REBALANCE TO 600 CFM

SUPPLY, 450 RETURN AND 150 CFM

OUTSIDE AIR

(E) CD. REBALANCE

TO 300 CFM

(TYP. 2 PL.)

(E) CD. REBALANCE TO 300 CFM

(TYP. 2 PL.)

SCALE: 1/8" = 1'-0"

4' 8'0 16'

MECHANICAL ROOF PLAN

14x14 EDTR.

FOR CONT. SEE

EF

ON ROOF

SEE

PR

OV

ID

E M

IN

. 2

5'

CL

EA

RA

NC

E B

ET

WEE

N

EX

H.

TE

RM

IN

AT

IO

N

& O /A

IN

TA

KE

4.2

MECHANICAL PLANS

DENTAL OPERATORY

DENTAL BLDG

M1.6 22063

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

PROJECT No.

(520)-200-2612 ZonaMEP.com

MECHANICAL . PLUMBING . ELECTRICAL

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY: KM

CHECKED BY: SM

DATE DESCRIPTION

DFE BRANCH CHIEF

APPROVED:

CONCURRENCE

DFE CHIEF

REVIEWED:

ES ARCHITECT / ENGINEER DATE

DATE

DATE

SHEET ______ OF ______

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

SHEET TITLE

261 North Court Avenue Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

STRUCTURAL

Turner Structural Engineering 2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering 6422 East Speedway Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

ENLARGED MECHANICAL FLOOR PLAN

SCALE: 1/4" = 1'-0"

2' 4'0 8'

JAN

039A

HALL

BIOMED

STAFF TOILET

IRM OFFICE

STORAGE

FE

IRM OFFICE

CORRIDOR

MDF

IM-007

STAIR

ST-01

(E) MODULAR MDF SERVER W/ FOUR (4) 10 kW

WATER-COOLED IN-RACK COOLING UNITS

24'' HIGH-EFF. TAP W/ MAN. BALANCING

DAMPER & PROVIDE 24''~ TO 48x24 CD

3,000 CFM (TYP. 2 PL.)

ON FLOOR-MOUNTED FACTORY FLOOR STAND &

DISHARGE AIR PLENUM

REFRIG PIPING (2-CIRCUITS) UP IN WALL TO

OH. SEAL WALL PENETRATION WATER-TIGHT

(TYP. 2 PL.)

RELOCATE (E) EMCS CONTROL PANEL.

COORD. EXACT LOCATION W/ GEN.

CONTRACTOR & CONTRACT OFFICER

ROUTE S/A DUCTWORK ABOVE CEILING

BETWEEN STRUCTURAL BEAMS

REFRIG PIPING (2-CIRCUITS)

DN IN WALL TO CRAC UNIT

(TYP. 2 PL.)

ROUTE S/A DUCTWORK ABOVE CEILING BETWEEN STRUCTURAL

BEAMS. COORDINATE ROUTING TO PROVIDE CLEARANCE ROUTING

TO PROVIDE CLEARANCE ABV CLG IN MDF ROOM ON NORTH WALL

OF BIOMED #008

C

CRAC

CRAC

ON CONCRETE EQUIP. PAD BY GEN.

CONTRACTOR

C

ON CONCRETE EQUIP. PAD BY GEN.

CONTRACTOR

ON FLOOR-MOUNTED FACTORY FLOOR STAND &

DISHARGE AIR PLENUM 24'' HIGH-EFF. TAP W/ MAN. BALANCING

DAMPER & PROVIDE 24''~ TO 48x24 CD

3,000 CFM (TYP. 2 PL.)

MECHANICAL PLANS

MDF ROOM

DENTAL BLDG

M1.7 22063

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

PROJECT No.

(520)-200-2612 ZonaMEP.com

MECHANICAL . PLUMBING . ELECTRICAL

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY: KM

CHECKED BY: SM

DATE DESCRIPTION

DFE BRANCH CHIEF

APPROVED:

CONCURRENCE

DFE CHIEF

REVIEWED:

ES ARCHITECT / ENGINEER DATE

DATE

DATE

SHEET ______ OF ______

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

SHEET TITLE

261 North Court Avenue Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

STRUCTURAL

Turner Structural Engineering 2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering 6422 East Speedway Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

R

S

D

R

S

D

OSA

RA

Grating

SA

Grating

FINAL FILTER SECTION

SUPPLY FAN SECTION

COOLING COIL SECTION

HUMIDIFICATION SECTION

(FUTURE)

HEATING COIL SECTION

SUPPLY AIR CONNECTION

PRE-FILTER SECTION

RETURN AIR

CONNECTION

MIXED AIR SECTION

MI

N.

'-0

AB

OV

E

RO

OF

DUCT & SUPPORT SHALL BE PAINTED PER

NOTE:

MIN. 60''

OWNER'S REQUEST.

NOTE:

ELECTRICAL CONTRACTOR SHALL NOT

MOUNT DISCONNECT TO UNISTRUT

PROVIDE TRANS. FROM DISCHARGE EXH. DUCT TO

NOZZLE

2'' WIDE, 18 GA. SHEET METAL STRAP -

SECURE TO UNISTRUT WITH APPROVED

UNISTRUT CLAMPS

TRANS FROM RECT. DUCT FAN CONN.

TO RND.

RAINGUARD

FLEX. CONN.

UPBLAST DISCHARGE NOZZLE (MIN.

1,000 FPM.)

20^ MAX

SHEET METAL SCREW TO DUCT (MIN. 4

PLACES EACH STRAP)

UNISTRUT OR ANGLE

SUPPORT DUCT TO FAN AS REQUIRED -

COORD. W/ MANUFACTURER

PROVIDE SCROLL DRAIN (OPEN)

MASON MODEL 1'' SPRING ISOLATORS

2''x12'' @ 16'' O.C. WOOD STAND

COVERED W/ 3/4'' PLYWOOD & SHT. MTL.

COVER

ROOFLINE

2''x12'' WOOD CURB W/ CANT. FLASH

RAIN TIGHT.

EXHAUST DUCT THRU ROOF

CEILING DIFFUSER

WRAPPED PER SPECS

SHT. MTL. PLENUM OVER CD'S,

SAGGING. MAX. 5'-0'' O.C.

CLOSE INTERVALS TO AVOID

STRUCTURE ABOVE, SUPPORT AT

24 GA. STRAPS SUPPORTED FROM

HEMMED EDGES 12'' LONG

PROVIDE CRADLE WITH

W/ DUCT WRAP

SHT. MTL S/A DUCT

FLEX DUCT (MAX 8'-0'' LONG) -

& \ CIR. OF DUCT

AIR FLOW

AIR FLO

W

DRYWALL CLG.

T-BAR OR

HIGH-EFFICIENCY DUCT TAKE-OFF WITH MANUAL

DAMPER NO DOVE TAIL CONNECTIONS). SEAL JOINT

WITH HARDCAST

NOTE:

MECHANICAL CONTRACTOR SHALL PAINT THE INTERIOR

SHEET METAL OF THE CLG. DIFF. PLENUM FLAT BLACK.

SECURE WITH METAL CINCH BANDS

N.T.S.

12" FACTORY STAND

AIR FILTER RACK

C-PORT '' C-STRUT'' ROOFTOP

SUPPORT SYSTEM

REFRIGERANT PIPING ON

ROOF FOR CONT. SEE

FLOOR PLAN

PROVIDE REVERSE TRAPS

PER MFGR'S RECOMMENDATIONS

SERVER ROOM AC CONDENSER

UNIT SIZE W/ GENERAL CONTRACTOR.

N.T.S.

N.T.S.

N.T.S.

N.T.S. DUCTED RETURN GRILLE SIMILAR

FLEX CONN.

S/A DUCT. SEE FLOOR PLAN FOR

CONT.

UNISTRUT SECURED TO CROSSBEAM

WITH BEAM CLAMPS OR TACK WELDED

UNISTRUT

(3) SHEET METAL SCREWS

PER DUCT HANGER

(TYP.)

3'' MIN.

(TYP.)

DUCT

1-1/4'' 18 GA. GI. DUCT HANGER

WRAP AROUND UNISTRUT AND

BOLT TOGETHER

TWIST ONCE

(TYP.)

(3) SHEET METAL SCREWS

4 MIN. PER DUCT

(TYP.)

N.T.S.

DETAILS

MECHANICAL

M3.1 22063

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

PROJECT No.

(520)-200-2612 ZonaMEP.com

MECHANICAL . PLUMBING . ELECTRICAL

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY: KM

CHECKED BY: SM

DATE DESCRIPTION

DFE BRANCH CHIEF

APPROVED:

CONCURRENCE

DFE CHIEF

REVIEWED:

ES ARCHITECT / ENGINEER DATE

DATE

DATE

SHEET ______ OF ______

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

SHEET TITLE

261 North Court Avenue Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

STRUCTURAL

Turner Structural Engineering 2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering 6422 East Speedway Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

ALL JOINTS SOLDERED

''C-PORT'' DUCT SUPPORTS OR

EQUIVALENT. INSTALL AT INTERVALS

PER MANUFACTURER'S GUIDELINES

FLEX. CONNECTION

W/RAINGUARD

TURNING VANES

RAINTIGHT

FLASH

2''x8'' CURB

P-TRAP

3/4'' COND

EXIST. ROOF

MASON MODEL N.D. R.I.S.

ISOLATORS

2''x 8'' @ 16'' O.C. WOOD

STAND COVERED WITH 3/4''

PLYWOOD & SHT. MTL. COVERSHEET METAL COVER & FLASHINGS

BY GENERAL CONTRACTOR.

WOOD COVER, CURBS & STAND

NOTE:

BY MECHANICAL CONTRACTOR

N.T.S.

ROOF FELT

(TYP.)

RAINTIGHT

FLASH

2''x8'' CURB

''C-PORT'' DUCT SUPPORTS OR

EQUIVALENT. INSTALL AT INTERVALS

PER MANUFACTURER'S GUIDELINES

TURNING VANES

FLEX CONNECTION

WITH RAIN GUARD

FACTORY ROOF CURB

GASKET

(TYP.)

RIGID INSULATION

(TYP.)

NAILER STRIP

(TYP.)

EXIST. ROOF

N.T.S.

FLEX CONNECTION

(TYP.)

RETURN DUCT THRU ROOF

SUPPLY DUCT THRU ROOF

M

2 WAY CONTROL VALVE

BELL REDUCER AS REQ'D

FLOW CONTROL VALVE WITH BALL

VALVE, AND P-T PORTS GRISWOLD

CPP-2 IRIS PROVIDE 2 - 32 PSIG

RANGE EQUAL OF HAYS

HWR

HWS

PROVIDE BALL VALVE, Y-STRAINER

W/ BLOW DOWN, AND P/T PORT.

GRISWOLD CPP-2 IRIS OR EQUAL

OF HAYS

DRAIN WITH SOV

HEATING

COIL

UNION (TYP.)

BALL VALVE

MANUAL AIR VENT

S

D

C

N.T.S.

3/8'' DIA. ALL THREAD ROD

(TYP. EA. CORNER)

SUPPORT FROM STRUCTURE ABOVE -

LOW PRESSURE SUPPLY OUT

EXHAUST OUT

MEDIUM PRESSURE SUPPLY IN

EXHAUST IN

2'' x 1'' x 3/16'' STEEL CHANNEL

(TYP. EA. SIDE)

SUPPLY VALVE

EXHAUST VALVE

DOUBLE NUT

(TYP.)

FLEX CONNECTION

LOCATE SO NOT TO INTERFERE WITH ACCESS

N.T.S.

SUPPLY

RETURN

M

N.T.S.

3-WAY CONTROL VALVE

BELL REDUCER AS REQ'D.

(TYP.)

TA MANUAL BALANCING

VALVE WITH P-T PORTS

BUTTERFLY VALVE

(TYP.)

STRAINER

PETE'S PLUG

(TYP.)

DRAIN WITH SOV

HEATING COIL

UNION OR FLANGE

(TYP.)

BALL VALVE

(TYP.)

MANUAL AIR VENT

TWIN SPHERE FLEX CONNECTOR

(TYP.)

THERMOMETER

(TYP.)

PRESSURE GAUGE

(TYP.)

1/2'' FILTERED WATER

SOV

UNION

1'' DRAIN LINE. PROVIDE

2'' AIR GAP AT TERMINATION

FACTORY STEAM SUPPLY AND

CONDENSATE RETURN TUBING

HUMIDIFIER ON WALL

ABOVE CEILING

FACTORY WALL BRACKET

N.T.S.

FACTORY AIR PROVING SWITCH

DOWNSTREAM OF DISPERSION PIPING

SUPPLY AIR DUCTWORK. PROVIDE

MIN. 2' OF STRAIGHT DUCT UPSTREAM

AND MIN. 3' OF STRAIGHT DUCT

FACTORY DISPERSION PIPING

FACTORY HIGH LIMIT SWITCH

AIR FLOW

AIR FLOW

24V. LOCAL LOOP CONTROL TO

HUMIDIFIER - BY MECHANICAL

CONTRACTOR

SLOPE BOTTOM OF DUCT

TO DRAIN

SLOPE MIN. 1%

STEAM CONDENSATE RETURN

PIPING TO SAN. FLOOR DRAIN

CLEAN-OUT

(TYP.)

PRE INSULATED 1-1/2''

STEAM SUPPLY TUBING

DUCT DRAIN - SEE FLOOR

PLANS FOR TERMINATION

D

MIN. 6'' TRAP

N.T.S.

DETAILS

MECHANICAL

M3.2 22063

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

PROJECT No.

(520)-200-2612 ZonaMEP.com

MECHANICAL . PLUMBING . ELECTRICAL

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY: KM

CHECKED BY: SM

DATE DESCRIPTION

DFE BRANCH CHIEF

APPROVED:

CONCURRENCE

DFE CHIEF

REVIEWED:

ES ARCHITECT / ENGINEER DATE

DATE

DATE

SHEET ______ OF ______

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

SHEET TITLE

261 North Court Avenue Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

STRUCTURAL

Turner Structural Engineering 2806 N. Alvernon Way, Suite 400 Tucson, AZ 85712 Phone: 520.323.3422

MECH/PLUMBING/ELECTRICAL

ZONA Technical Engineering 6422 East Speedway Blvd., #130 Tucson, AZ 85710 Phone: 520.200.2612

Expires 12/31/202112/31/2024

06/ kmakomaski Text Box kmakomaski

EMCS

SAOA

EMCS

HW

S

HW

R

M

(E) LCI TO FIRE ALARM PANEL BY

ELECT. CONTRACTOR

PO

M

M

PO

EI

AFC

(E) SMOKE DETECTOR RELOCATED

IN RA DUCT

RA

SD

NTS

TYP. AHU CONTROLS SCHEMATIC

STR

EMCS

S

NOTES:

· EXH. FAN MAY BE CEILING

MOUNTED OR INLINE CABINET.

NTS

TYP. EXHAUST FAN CONTROL SCHEMATIC

DPS

O

F

EMCS

EI

COORD. LOCATION OF STARTERS AT

EXHAUST FANS W/ ELECT. CONTRACTOR

F

EI

FEI

DP

CH

W

S

CH

W

R

M

S

EMCS

HE

AT

T

EMCS

RARA

H

SA

FROM

AHU

T

EMCS

FI

NA

L

FI

LT

ER

HW

H

EA

TI

NG

CH

W

CO

OL

IN

G

PR

E-

FI

LT

ER

FU

TU

RE

D

X

CO

OL

IN

G

CO

IL

C

NO

NCC

NO

NC

PO PO

EMCS

DP

NTS

TYP. SURGERY SUITE CONTROL SCHEMATIC

HW

S

HW

R

M C

NO

NC

PO

120 V POWER SUPPLY TO EACH CONTROLLER BY CONTROL

CONTRACTOR FROM NEAREST ELECT. PANEL IN COORD. W/ UAFM ELECT.

SHOP. 120/24 V POWER TRANSFORMER BY CONTROL CONTRACTOR

S

(E) EXH. DUCT TO

EF-X ON ROOF

CVS

LLC BY CONTROL

CONTRACTOR

PANTE COMPOUNDING

EMCS

P

EMCS

EI

CVE

STR

S

EMCS

O

C

FAN FILTER UNITS SHALL BE

GROUPED PER ROOM

NTS

TYP. PHARMACY CONTROL SCHEMATIC

S

EMCS

HE

AT

DPEMCS

NTS

TYP. STERILE STORAGE CONTROL SCHEMATIC

SA

FROM

AHU

RA TO

AHU

H

R

FIL

TE

R

S

DX

C

OI

L

R

T

OA

RA

STR

FACTORY LLC

FACTORY CONTROL

PANEL

EMCS

EI

O

DPS

EL

EC

TR

IC

H

EA

T

EMCS

M

PO M PO

FACTORY TEMP & RELATIVE HUMIDITY

SENSORS PROVIDED BY MECH. CONTRACTOR

& INSTALLED BY CONTROL CONTRACTOR

H

LLC BY CONTROL CONTRACTOR

NTS

TYP. ROOFTOP HP UNIT CONTROL SCHEMATIC

T

HW

S

HW

R

M C

NO

NC

PO

EMCS

EI(E) DRI-STEEM

VAPORMIST VM-6 (18.0

lbs/hr, 208/1 V, 28.8 FLA).

PROVIDE BACnet MS/TP

EMCS INTERFACE

HL F

(E) LLC

R

FIL

TE

R

T

DX

C

OI

L

R

T

OA

RA

STR

FACTORY LLC

FACTORY CONTROL

PANEL

EMCS

EI

O

DPS

EL

EC

TR

IC

H

EA

T

EMCS

M

PO M PO

H

LLC BY CONTROL CONTRACTOR

STR

S

C

O

EMCS

NTS

TYP. ROOFTOP HP UNIT CONTROL SCHEMATIC

(CENTRAL STERILE ROOM)

(IP PHARMACY ROOM)

EI

(E) DRI-STEEM

VAPORMIST VM-6 (18.0

lbs/hr, 208/1 V, 28.8 FLA).

PROVIDE BACnet MS/TP

EMCS INTERFACE

HL F

(E) LLC

FACTORY TEMP & RELATIVE

HUMIDITY SENSORS PROVIDED BY

MECH. CONTRACTOR & INSTALLED

BY CONTROL CONTRACTOR

(TYP. 2 PL.)

(E) ROOFTOP DOWNBLAST

EXHAUST FANS ON ROOF

(TYP. 2 PL.)

EMCS

(DENTAL OPERATORY)

T

EMCS

T

EMCS

DP

T

S

RA / EA

STR

S

EMCS

O

C

T

LLC FROM FACTORY TEMPERATURE

SENSOR TO ROOFTOP PACKAGED

HP CONTROL PANEL BY CONTROL

CONTRACTOR

S

(TYP. 2 PL.)

FACTORY LLC

FACTORY LLC

STR

S

C

O

EMCS

(E) HAZARDOUS

COMPOUNDING UTILITY SET

EXHAUST FAN ON ROOF

CONTROLS

MECHANICAL

M4.1 22063

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

PROJECT No.

(520)-200-2612 ZonaMEP.com

MECHANICAL . PLUMBING . ELECTRICAL

1 2 3 4

A

B

C

B

C

1 2 3 4

REV

ISSUE: 06/09/2023 - CONSTRUCTION DOCUMENTS

PROJECT NO: 1818.013

CAD DWG FILE:

DRAWN BY: KM

CHECKED BY: SM

DATE DESCRIPTION

DFE BRANCH CHIEF

APPROVED:

CONCURRENCE

DFE CHIEF

REVIEWED:

ES ARCHITECT / ENGINEER DATE

DATE

DATE

SHEET ______ OF ______

WHITERIVER HVAC

UPGRADES AND

USP797/800 COMPLIANCE

Whiteriver, Arizona

IHS PROJECT NO. PH22WR02H8

SHEET TITLE

261 North Court Avenue Tucson, Arizona 85701

520.795.2705 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

ARCHITECTS

CONSULTANTS

U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

STRUCTUR…