J009 Field Checkout Checklist.pdf
PDF 32 KB Posted
- Attached to
- Screening Information Request (SIR) for Runway Incursion Prevention through Situational Awareness (RIPSA)
- Solicitation number
- 693KA8-21-R-00000
View the file
Other files
| File | Type | Posted |
|---|---|---|
| J002 Labor Category and Skill Level Descriptions.pdf | ||
| J011 RIPSA FA CDRL List.doc | DOC document | |
| 20210301 Part A RIPSA Cost Price Workbook.xlsx | XLSX spreadsheet | |
| J004 Predelivery Document Checklist.pdf | ||
| J007 SAT Checklist - Copy.pdf | ||
| J008 CAI Checklist.pdf | ||
| J016 RIPSA Tech Description DIDs.doc | DOC document | |
| J005 FAT Checklist.pdf | ||
| J001 Preliminary Program Requirements for RIPSA.pdf | ||
| J013 RIPSA PM CDRL List.doc | DOC document | |
| J014 RIPSA PM DIDs.doc | DOC document | |
| J012 RIPSA FA DIDs.doc | DOC document | |
| J015 RIPSA Tech Desription CDRL List.doc | DOC document | |
| J010 Past Performance Questionnaire.doc | DOC document | |
| RIPSA SIR Final.docx | DOCX document | |
| J006 First Article Delivery Checklist.pdf | ||
| J003 Referenced Documents.pdf |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment J009 – Field Checkout Checklist
The requirements specified in the table below are to be verified before Field Checkout can be completed. Verification method used Analysis (A), Inspection (I), Demonstration (D), Test (T)
Requirement/ Deliverable number
Requirement Details Verification Methods
Requirement met
(Y/N) J001 3.2.1 The FLS must assign each protected system with a dedicated series circuit running from its power supply in the electrical vault.
I
J001 3.2.2 The FLS must include a single primary Constant Current Regulator (CCR) to power all the series circuits, using an internal or external circuit selector switch to determine which circuits are energized and de-energized.
A I
J001 3.2.3 The CCR must conform to the appropriate performance requirements specified by the current version of Advisory Circular (AC) 150/5345-10, Type L-829 and those detailed in this solicitation.
A I
J001 3.2.4 The CCR must be certified or certifiable with regard to performance and environmental requirements contained in AC 150/5345-10 latest revision.
A I
J001 3.2.5 The CCR maximum output current must not exceed 6.6A with output current adjustable providing a LED light output range from 100% down to a minimum necessary to support the system design.
A I
J001 3.2.6 The CCR kilowatt rating must be suitable for the intended small load providing optimum efficiency of energy transfer.
A I
J001 3.2.7 The FLS must include light fixtures with LED light source of type L-852S, Class 2, mode 1, style 3 mounted on installed L-868 class 1A size B base.
I
J001 3.2.8 The FLS light fixtures must be certified in conformance with the AC
I
Field Checkout Completed YES ____ NO ____
FAA Comments requirements as described in FAA Advisory Circular AC 150/5340-30J and Engineering Brief EB64-D.
J001 3.2.9 The FLS must include a standard series circuit transformer to provide light fixtures with electrical isolation from the primary series circuit, and must be certified for use per AC 150/5345-47C (latest revision).
I
J001 3.2.10 The FLS must include a Light Computer (LC) that must control and monitor the
CCR.
I
J001 3.2.11 The FLS must include a remote “kill” switch to enable the CCR to be turned off manually
T
J001 3.2.12 The FLS must log and timestamp all received light commands.
I
J001 3.2.13 The FLS must log and timestamp all changes in light fixture on/off state, circuit power, and system maintenance and availability status.
I