J009 Field Checkout Checklist.pdf

PDF 32 KB Posted

Attached to
Screening Information Request (SIR) for Runway Incursion Prevention through Situational Awareness (RIPSA)
Solicitation number
693KA8-21-R-00000
Issued by

View the file

Other files

File Type Posted
J002 Labor Category and Skill Level Descriptions.pdf PDF
J011 RIPSA FA CDRL List.doc DOC document
20210301 Part A RIPSA Cost Price Workbook.xlsx XLSX spreadsheet
J004 Predelivery Document Checklist.pdf PDF
J007 SAT Checklist - Copy.pdf PDF
J008 CAI Checklist.pdf PDF
J016 RIPSA Tech Description DIDs.doc DOC document
J005 FAT Checklist.pdf PDF
J001 Preliminary Program Requirements for RIPSA.pdf PDF
J013 RIPSA PM CDRL List.doc DOC document
J014 RIPSA PM DIDs.doc DOC document
J012 RIPSA FA DIDs.doc DOC document
J015 RIPSA Tech Desription CDRL List.doc DOC document
J010 Past Performance Questionnaire.doc DOC document
RIPSA SIR Final.docx DOCX document
J006 First Article Delivery Checklist.pdf PDF
J003 Referenced Documents.pdf PDF
Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment J009 – Field Checkout Checklist

The requirements specified in the table below are to be verified before Field Checkout can be completed. Verification method used Analysis (A), Inspection (I), Demonstration (D), Test (T)

Requirement/ Deliverable number

Requirement Details Verification Methods

Requirement met

(Y/N) J001 3.2.1 The FLS must assign each protected system with a dedicated series circuit running from its power supply in the electrical vault.

I

J001 3.2.2 The FLS must include a single primary Constant Current Regulator (CCR) to power all the series circuits, using an internal or external circuit selector switch to determine which circuits are energized and de-energized.

A I

J001 3.2.3 The CCR must conform to the appropriate performance requirements specified by the current version of Advisory Circular (AC) 150/5345-10, Type L-829 and those detailed in this solicitation.

A I

J001 3.2.4 The CCR must be certified or certifiable with regard to performance and environmental requirements contained in AC 150/5345-10 latest revision.

A I

J001 3.2.5 The CCR maximum output current must not exceed 6.6A with output current adjustable providing a LED light output range from 100% down to a minimum necessary to support the system design.

A I

J001 3.2.6 The CCR kilowatt rating must be suitable for the intended small load providing optimum efficiency of energy transfer.

A I

J001 3.2.7 The FLS must include light fixtures with LED light source of type L-852S, Class 2, mode 1, style 3 mounted on installed L-868 class 1A size B base.

I

J001 3.2.8 The FLS light fixtures must be certified in conformance with the AC

I

Field Checkout Completed YES ____ NO ____

FAA Comments requirements as described in FAA Advisory Circular AC 150/5340-30J and Engineering Brief EB64-D.

J001 3.2.9 The FLS must include a standard series circuit transformer to provide light fixtures with electrical isolation from the primary series circuit, and must be certified for use per AC 150/5345-47C (latest revision).

I

J001 3.2.10 The FLS must include a Light Computer (LC) that must control and monitor the

CCR.

I

J001 3.2.11 The FLS must include a remote “kill” switch to enable the CCR to be turned off manually

T

J001 3.2.12 The FLS must log and timestamp all received light commands.

I

J001 3.2.13 The FLS must log and timestamp all changes in light fixture on/off state, circuit power, and system maintenance and availability status.

I