J.3 Attachment DRAWINGS.NORTH.REMODEL.SLRD.FINAL_Part2_2.15.2023.pdf
PDF 9 MB Posted
- Attached to
- Salt Lake District Office Renovation – Phase II
- Solicitation number
- 1240LT23R0024
- Issued by
-
Department of Agriculture Forest Service
About this file
This solicitation posting is for the Salt Lake District Office Renovation – Phase II project. The Forest Service is seeking bids for renovations to the Salt Lake Ranger District Office, including demolition work, new walls, electrical upgrades, and HVAC replacements. Bids are due by July 15, 2022 and the contract is expected to be awarded by August 15, 2022. The solicitation number is 1240LT23R0024. Pricing will be fixed-price and the project is set aside for small businesses.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
36" STAINLESS STEEL
GRAB BARS.
PROVIDE BLOCKING IN WALLS FOR ALL EQUIPMENT LISTED BELOW AND
SHOWN ELSEWHERE IN DRAWINGS AS REQ'D BY MANUF. RECOMMENDATIONS.
ALL ITEMS CONTRACTOR PROVIDED AND CONTRACTOR INSTALLED
TOILET PAPER HOLDER -
1 PER TOILET
42" STAINLESS STEEL
GRAB BARS
SOAP DISPENSERS
WALL TOWEL DISPENSER
18" STAINLESS STEEL
GRAB BARS
203 1 EA; 107 1 EA;
108 1 EA
STAINLESS STEEL HOOK AND
CELL PHONE HOLDER
MEN
WOMEN
2-1/2" HIGH
SYMBOL
RAISED.
QTY.
NOTES:
WALL MOUNTED SIGN TO BE LOCATED ON
LATCH SIDE OF DOOR 60" TO CENTERLINE
FROM FLOOR
ALL SIGNAGE SHALL MEET ADA
REQUIREMENTS.
U.N.O. SIGNS SHALL BE INSTALLED ON THE
WALL ADJACENT TO THE LATCH SIDE OF
THE DOOR. IN THE EVENT THIS IS NOT
POSSIBLE, NOTIFY CONTRACTING OFFICER
AND AWAIT INSTRUCTIONS.
COLORS AND FONTS SELECTED BY
CONTRACTING OFFICER'S
REPRESENTATIVE.
ROOMS
1" HIGH TEXT
BRAILLE
ROOM NAME
ROOM NAME
1" HIGH TEXT
BRAILLE
ROOM #
1" HIGH TEXT
BRAILLE
ROOM #
1-1/2" HIGH CLEAR
SLOT OVER FOR
REMOVABLE
ACRYLIC NAME TAG
MODEL:
B-6806-36
MODEL:
B-6806-42
MODEL:
B-2888
MODEL:
B-4112
MODEL:
B-6806-18
MODEL:
B-635
SANITARY NAPKIN DISPOSAL
MODEL:
B-254
LAVATORY WRAP
MODEL:HANDY-
SHIELD-MAXX
MODEL:
B-223X 36
STAINLESS MOP & BROOM
HOLDER
118, 1 EA
BOBRICK
OR EQUAL
PLUMEREX
OR EQUAL
EXISTING DRYERS
HAND DRYER
REINSTALL
SALVAGED
ACCESSORY SCHEDULE
ITEM MODEL ROOM NUMBERS COMMENTS
BOBRICK
OR EQUAL
BOBRICK
OR EQUAL
BOBRICK
OR EQUAL
BOBRICK
OR EQUAL
BOBRICK
OR EQUAL
BOBRICK
OR EQUAL
SIGN A
SIGN B
SIGN C
ROOM SIGNAGE NOTES:
SIGN A
SIGN B
SIGN D
SIGN E
SIGN TYPES:
BOBRICK
OR EQUAL
203 1 EA; 107 1 EA;
108 1 EA
203 1 EA; 107 1 EA;
206 1 EA
203 1 EA; 107 1 EA;
108 1 EA; 104, 1 EA
30 x36 STAINLESS STEEL
MIRROR
MODEL:
B-290 3036
BOBRICK
OR EQUAL
203 1 EA; 107 1 EA
BOBRICK
OR EQUAL
MODEL:
B-72860
107 1 EA; 108 1 EA
UNISEX
SIGN C
203 1 EA; 107 1 EA;
108 1 EA
MODEL: 4400/
RECESSED. NO
ALARM
KNOXBOX/ STANDARD
CAPACITY
EAST
ELEVATION/
ADDITION
KNOXBOX OR
EQUAL
203 1 EA; 107 1 EA;
108 1 EA
203 1 EA; 107 1 EA;
108 1 EA
203 1 EA; 107 1 EA;
108 1 EA
203 1 EA; 107 1 EA;
108 1 EA; 104, 1 EA
SHOWER GRAB BAR
(CORNER GRAB BAR)
SHOWER CURTAINS &
HOOKS
MODELS: 204-1
204-3
107, 1 EA, HOOKS AS REQ'D
108, 1 EA, HOOKS AS REQ'D
BOBRICK OR
EQUAL
BOBRICK OR
EQUAL
SHOWER BENCH SEAT
SHOWER BASKET
SWANSTONE
BF2300
K1896-S
SWANSTONE
OR EQUAL
KOHLER OR
EQUAL
MODEL:
B-6806,24X32
SHOWER SURROUND AND
RECEPTOR
SK363672,
36" X 36"
SWANSTONE OR
EQUAL
107 1 EA; 108 1 EA
107 1 EA; 108 1 EA
107 1 EA; 108 1 EA
107 1 EA; 108 1 EA
SIGN D
SIGN E
102, 103, 104, 106,110,111,112, 114, 115, 116, 118, 212, 213, 214, 215, 217, 220, TELE
8"
SIGN F
NO SMOKING
25' FROM
ENTRANCE
113, 216
SIGN F
EXTERIOR: AS DIRECTED
TYPES
2-1/2" HIGH
SYMBOL
RAISED.
1" HIGH TEXT
BRAILLE
GENERAL ELECTRIC
OR EQUAL
MICROWAVE
REFRIGERATOR
1 EA, 104; 1 EA 215
JES1145SHSS
21"x 12" x 16"
GSS25IYNFS
24.5 CUFT
GENERAL ELECTRIC
OR EQUAL
1 EA, 104; 1 EA 215
KOALA CARE OR
EQUAL
BABY CHANGING STATION
KB301
1 EA 203, 1 EA, 107; 1 EA
UNISEX
SIGN C
2-1/2" HIGH
SYMBOL
RAISED.
1" HIGH TEXT
BRAILLE
1 EA, 215
DA-LITE OR EQUAL
ELECTRIC CONTROLLED
PROJECTION SCREEN
CONTOUR ELECTROL
87" X 116" #923634LS
AND SMART LOW
VOLTAGE SWITCH
1 EA, 215
EPSON OR EQUAL
MULTIMEDIA PROJECTOR
PRO EX9240
8"
SIGN G
VISITOR
SERVICES
UPSTAIRS
SIGN G
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
R-4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL:
PHASE 2
UINTA WASATCH CACHE
NATIONAL FOREST
SALT LAKE RANGER DISTRICT
NORTH BUILDING,
ACCESSORY SCHEDULE
SMHW
SMHW
UWC STAFF
A903 74 132
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text E shillworthen Text Box
APPROVED 2/25/2022
STRUCTURAL NOTES :
A. GENERAL
1. THE STRUCTURAL NOTES ARE INTENDED TO COMPLEMENT THE PROJECT SPECIFICATIONS WHICH ARE PART OF THE CONSTRUCTION DOCUMENTS. SPECIFIC NOTES AND DETAILS ON THE DRAWINGS SHALL
GOVERN OVER THE STRUCTURAL NOTES AND TYPICAL DETAILS.
2. THESE DRAWINGS (AND, WHERE APPLICABLE, ACCOMPANYING WRITTEN SPECIFICATIONS) ARE THE
ONLY CONTRACT DOCUMENTS PROVIDED BY ARW ENGINEERS FOR THE PROJECT REPRESENTED
HEREIN. NOTHING IN ANY DIGITAL MODEL OR DIGITAL FILE RELATED TO THIS PROJECT SHALL BE TAKEN TO SUPERSEDE ANY INFORMATION SHOWN IN THESE DRAWINGS (INCLUDING, BUT NOT LIMITED
TO, DIMENSIONS, SIZES, ETC).
3. THE ARCHITECTURAL DRAWINGS ARE THE PRIME CONTRACT DRAWINGS. THE STRUCTURAL DRAWINGS ARE SUPPLEMENTARY TO AND MUST BE USED IN CONJUNCTION WITH THE ARCHITECTURAL DRAWINGS
AND OTHER CONSULTANTS DRAWINGS. ALL OMISSIONS OR CONFLICTS BETWEEN THE VARIOUS
ELEMENTS OF THE WORKING DRAWINGS AND/OR SPECIFICATIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER BEFORE PROCEEDING WITH ANY WORK INVOLVED. IN CASE OF CONFLICT, FOLLOW THE MOST STRINGENT REQUIREMENT AS DIRECTED BY THE
COR / GOVERNMENT AT NO ADDITIONAL COST TO THE COR / GOVERNMENT.
4. SEE SPECIFICATIONS FOR REQUIRED SUBMITTALS. SUBMITTALS SHALL BE MADE IN A TIMELY MANNER AS INDICATED IN SPECIFICATIONS. REVIEW OF SUBMITTALS BY ARW ENGINEERS IS FOR GENERAL
COMPLIANCE ONLY AND IS NOT INTENDED AS APPROVAL. CONTRACTOR IS RESPONSIBLE FOR
VERIFYING ALL SIZES, DIMENSIONS, AND ELEVATIONS ON SUBMITTALS AS RELATED TO DESIGN
DOCUMENTS. PREPARATION OF SHOP DRAWINGS FOR STRUCTURAL ELEMENTS WILL REQUIRE
INFORMATION (I.E. DIMENSIONS, ETC.) FOUND IN THE ARCHITECTURAL, STRUCTURAL, AND OTHER
CONSULTANTS DRAWINGS.
5. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE SITE. IF ACTUAL CONDITIONS DIFFER FROM THOSE SHOWN ON CONTRACT DOCUMENTS, CONTRACTOR SHALL NOTIFY
COR / GOVERNMENT PRIOR TO FABRICATION OR CONSTRUCTION OF ANY AFFECTED ELEMENTS.
6. THE CONTRACTOR SHALL COORDINATE AND VERIFY ALL LOCATIONS AND SIZES OF MECHANICAL EQUIPMENT OR OTHER EQUIPMENT BEFORE FABRICATING AND ERECTING STRUCTURAL ELEMENTS.
SIZES AND LOCATIONS THAT DIFFER FROM THOSE SHOWN ON THE CONTRACT DOCUMENTS SHALL BE
REPORTED TO THE COR / GOVERNMENT.
7. THE CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST TO THE COR / GOVERNMENT FOR COR /
GOVERNMENT AND/OR ENGINEER APPROVAL BEFORE PROCEEDING WITH ANY CHANGES,
MODIFICATIONS, OR SUBSTITUTIONS.
8. OBSERVATION VISITS TO THE SITE BY ARW ENGINEERS FIELD REPRESENTATIVES SHALL NEITHER BE
CONSTRUED AS INSPECTION NOR APPROVAL OF CONSTRUCTION.
9. DURING AND AFTER CONSTRUCTION, BUILDER AND/OR OWNER SHALL KEEP LOADS ON STRUCTURE
WITHIN THE LIMITS OF DESIGN LOADS AS NOTED IN THESE DOCUMENTS.
10. TYPICAL OR SIMILAR DETAILS AND SECTIONS SHALL APPLY WHERE SPECIFIC DETAILS ARE NOT
SHOWN. TYPICAL OR SIMILAR DETAILS REFER TO THE CONDITION ADDRESSED AND ARE NOT
NECESSARILY DETAILS LABELED “TYPICAL” OR “SIMILAR” IN THE PLANS AND DOCUMENTS.
11. DRAWINGS AND DETAILS HAVE BEEN PREPARED WITH THE INTENT TO VISUALLY REPRESENT INFORMATION PROVIDED IN SCALED FORM; HOWEVER CONTRACTOR/SUPPLIERS SHOULD NOT SCALE
PLANS OR DETAILS FOR DIMENSIONAL INFORMATION.
12. THE CONTRACTOR SHALL PROVIDE ADEQUATE TEMPORARY SHORING AND BRACING FOR ALL
STRUCTURAL ELEMENTS UNTIL THE ENTIRE STRUCTURAL SYSTEM IS COMPLETED. DESIGN OF ALL
SHORING AND BRACING IS BY OTHERS AT NO ADDITIONAL COST TO THE OWNER.
13. ENGINEER SHALL NOT BE RESPONSIBLE FOR ACTIVITIES UNDER CONTROL OF THE CONTRACTOR SUCH AS CONSTRUCTION SITE SAFETY, MEANS, METHODS AND SEQUENCING OF CONSTRUCTION. ENGINEER SHALL NOT BE RESPONSIBLE FOR FABRICATION, ERECTION AND CONSTRUCTION REQUIREMENTS AS PRESCRIBED BY OSHA OR OTHER REGULATORY AGENCIES REGARDLESS OF INDICATIONS IN THESE
DOCUMENTS.
14. NOTICE OF COPYRIGHT: THESE STRUCTURAL DRAWINGS ARE HEREBY COPYRIGHTED BY ARW
ENGINEERS, ALL RIGHTS RESERVED. THESE DOCUMENTS DEFINE A STRUCTURE AND ARE
INSTRUMENTS OF SERVICE, FOR ONE USE ONLY. REPRODUCTION AND DISTRIBUTION OF THESE
DRAWINGS IS ONLY ALLOWED AS REQUIRED FOR REGULATORY AGENCIES AND FOR CONVEYANCE OF INFORMATION TO PARTIES INVOLVED IN THE CONSTRUCTION OF THIS PROJECT. THESE DOCUMENTS
SHALL NOT BE REPRODUCED OR COPIED, IN PART OR WHOLE BY ANY PARTY FOR USE IN
PREPARATION OF SHOP DRAWINGS OR OTHER SUBMITTALS.
15. WHERE THE WORD "SHALL" OCCURS IN THESE DRAWINGS AND ANY ACCOMPANYING SPECIFICATIONS, IT IS CONSIDERED A MANDATORY OBLIGATION AND SYNONYMOUS WITH THE PHRASE "HAS DUTY TO".
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
R4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL
UINTA WASATCH CACHE
NATIONAL FOREST
TMD
BLP
JLA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
SALT LAKE RANGER DISTRICT
C
U se rs \b en ja m in p \D o cu m en ts \S
-2
S al t L ak e
R an g er
D is tr ic t
_s te n
.r vt
S001
STRUCTURAL NOTES
Structural Sheet Index
SHEET
NUMBER SHEET NAME
S001 STRUCTURAL NOTES
S002 STRUCTURAL NOTES
S003 STRUCTURAL NOTES
S004 STRUCTURAL NOTES
S005 STRUCTURAL NOTES
S006 SCHEDULES
S007 SCHEDULES
S008 SCHEDULES
S009 SCHEDULES
S010 SCHEDULES
S011 SCHEDULES
S101 FOOTING AND FOUNDATION PLAN
S102 FOOTING AND FOUNDATION PLAN
ENLARGED
S103 SHEARWALL AND HOLDOWN PLAN
S104 ROOF FRAMING PLAN
S201 DETAILS
S202 DETAILS
S203 DETAILS
S204 DETAILS
S205 DETAILS
S206 DETAILS
S207 DETAILS
S208 DETAILS
S209 DETAILS
S210 DETAILS
S211 DETAILS
S212 DETAILS
S213 DETAILS
shillworthen Text Box shillworthen
B. STATEMENT OF SPECIAL INSPECTIONS AND SPECIAL INSPECTIONS
1. THE DESIGNATED SEISMIC/WIND SYSTEMS AND SEISMIC/WIND-FORCE-RESISTING SYSTEMS
THAT ARE SUBJECT TO SPECIAL INSPECTIONS IN ACCORDANCE WITH IBC SECTION 1705.11
AND 1705.12 ARE IDENTIFIED ON THESE DOCUMENTS WITH A CIRCLE “L”. ALL OTHER ITEMS
REQUIRING SPECIAL INSPECTION ARE IDENTIFIED IN THE SPECIAL INSPECTION SCHEDULE ON
SHEET S007 AND S008.
2. SPECIAL INSPECTIONS AND TESTING ARE TO BE PROVIDED AS REQUIRED BY IBC SECTIONS
1704 THROUGH 1705 AND OTHER APPLICABLE SECTIONS OF THE IBC. THE TYPE AND
FREQUENCY OF TESTING AND SPECIAL INSPECTIONS SHALL BE AS NOTED IN THE SPECIAL
INSPECTION SCHEDULE, JOB SPECIFICATIONS, AND ACCORDANCE WITH IBC SECTION 110 AND
CHAPTER 17. CONTRACTOR SHALL COORDINATE AND COOPERATE WITH REQUIRED
INSPECTIONS.
3. ALL TESTING AND SPECIAL INSPECTION SHALL BE PROVIDED BY THE CONTRACTOR USING A
QUALIFIED INDEPENDENT SPECIAL INSPECTION AGENCY IN ACCORDANCE WITH IBC 1704 AND
AS OUTLINED IN THE JOB SPECIFICATIONS. REPORTS OF FINDINGS OR DISCREPANCIES SHALL
BE NOTED AND FORWARDED TO THE CONTRACTOR, ARCHITECT, ENGINEERS, AND BUILDING
OFFICIAL IN A TIMELY MANNER.
4. STRUCTURAL OBSERVATION VISITS SHALL BE PERFORMED BY A REPRESENTATIVE FROM ARW
ENGINEERS IN ACCORDANCE WITH THE CONTRACT AS NEEDED TO OBSERVE THE
CONSTRUCTION OF CRITICAL BUILDING ELEMENTS (I.E. FOOTINGS, BRACED FRAMES, MOMENT
FRAMES, DRAG STRUTS AND THEIR CONNECTIONS, COLLECTORS, AND ROOF AND FLOOR
DIAPHRAGMS). STRUCTURAL OBSERVATION REPORTS FOR EACH VISIT SHALL BE SENT
DIRECTLY TO THE COR / GOVERNMENT FOR DISTRIBUTION TO THE CONTRACTOR AND
BUILDING OFFICIAL. STRUCTURAL OBSERVATION VISITS SHALL NEITHER BE CONSTRUED AS
SPECIAL INSPECTION NOR APPROVAL OF COMPLETED CONSTRUCTION.
5. IN ACCORDANCE WITH IBC 1704.4, THE CONTRACTOR SHALL SUBMIT A WRITTEN
CONTRACTOR’S STATEMENT OF RESPONSIBILITY TO THE COR. THE STATEMENT SHALL BE
SUBMITTED PRIOR TO THE CONSTRUCTION OF ANY SEISMIC/WIND-FORCE-RESISTING SYSTEM,
DESIGNATED SEISMIC/WIND SYSTEM, OR COMPONENT IDENTIFIED IN THESE DOCUMENTS WITH
A CIRCLE “L”.
C. BASIS OF DESIGN
1. GOVERNING BUILDING CODE : INTERNATIONAL BUILDING CODE (IBC) 2018
RISK CATEGORY : II
2. ROOF LOADS
a. FLAT-ROOF SNOW LOAD, Pf : 26 PSF
1. GROUND SNOW LOAD, Pg : 37 PSF
2. SNOW EXPOSURE FACTOR, Ce : 1.0
3. SNOW LOAD IMPORTANCE FACTOR, Is : 1.0
4. THERMAL FACTOR, Ct : 1.0
5. SLOPE FACTOR, CS : 1.0
6. SNOW DRIFT : SHOWN ON PLANS WHERE APPLICABLE.
b. LIVE LOAD = 20 PSF
c. DEAD LOAD = 20 PSF
d. SPECIAL LOADS, IE. PHOTOVOLTAIC PANEL SYSTEMS, ETC. = 0 PSF
3. WIND DESIGN
a. BASIC WIND SPEED (3 SECOND GUST) : 105 MPH
b. ALLOWABLE STRESS DESIGN WIND SPEED, VASD : 81 MPH
c. WIND EXPOSURE : C
d. INTERNAL PRESSURE COEFFICIENT, GCPI : 0.18
e. COMPONENT AND CLADDING DESIGN WIND PRESSURE SHALL BE AS REQUIRED PER ASCE
7-16.
4. SEISMIC DESIGN :
a. SEISMIC IMPORTANCE FACTOR, IE : 1.0
b. SITE CLASS : D-DEFAULT
c. MAPPED SPECTRAL RESPONSE ACCELERATIONS : SS = 1.376 , S1 = 0.507
d. SPECTRAL RESPONSE COEFFICIENTS : SDS = 1.101 , SD1 = 0.61
e. SEISMIC DESIGN CATEGORY : D
f. BASIC SEISMIC-FORCE-RESISTING SYSTEM : LIGHT FRAMED WOOD SHEAR WALLS
g. DESIGN BASE SHEAR : VN-S = 2K, VE-W = 2.6K
h. SEISMIC RESPONSE COEFFICIENT, CS : 0.16
i. RESPONSE MODIFICATION FACTOR, R : 7.0
j. ANALYSIS PROCEDURE : STATIC
D. FOUNDATION
1. GENERAL
a. DESIGN SOIL PRESSURE : 1500 PSF
b. ALL FOOTINGS SHALL BE PLACED ON MECHANICALLY COMPACTED FILL COMPACTED TO NOT
LESS THAN 95% OF MODIFIED PROCTOR DENSITY (ASTM D-1557).
c. UNLESS NOTED OTHERWISE, ALL CONCRETE SLABS ON EARTH SHALL BEAR ON STRUCTURAL
FILL COMPACTED TO 90% OF MODIFIED PROCTOR DENSITY (ASTM D-1557).
TOP OF FOOTING ELEVATIONS SHOWN ON THE FOOTING AND FOUNDATION PLAN ARE BASED
ON PRELIMINARY GRADING INFORMATION AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION.
STEPS WHERE SHOWN ARE AT APPROXIMATE LOCATIONS. ACTUAL STEP LOCATIONS SHALL
BE AT THE CONTRACTOR’S DISCRETION BASED UPON FIELD CONDITIONS. ALL EXTERIOR
FOUNDATIONS SHALL BEAR A MINIMUM OF 30 INCHES BELOW LOWEST ADJACENT FINAL
GRADE.
d. ALL WALLS (EXCEPT CANTILEVERED RETAINING WALLS) SHALL BE ADEQUATELY BRACED
AGAINST LATERAL MOVEMENT PRIOR TO BACKFILLING. DESIGN AND ERECTION OF
BRACING/SHORING SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. BRACING
SHALL REMAIN IN PLACE UNTIL SUPPORTING STRUCTURAL ELEMENTS ARE IN PLACE AND
HAVE ATTAINED FULL STRENGTH.
e. UNLESS NOTED OTHERWISE, ALL FOOTINGS AT COLUMNS SHALL BE CENTERED BELOW
COLUMNS.
f. UNLESS NOTED OTHERWISE, ALL FOOTINGS SHALL HAVE VERTICAL FACES FORMED WITH
STANDARD FORMING MATERIALS (WOOD, METAL, ETC.). WITH PRIOR APPROVAL OF ARCHITECT
AND ENGINEER, CONCRETE FOR FOOTINGS CAN BE PLACED IN EXCAVATED SOIL “FORMS”
PROVIDED THAT THE DIMENSIONS ARE INCREASED 3” ON ALL SIDE.
E. CONCRETE
1. ALL CONCRETE MIX DESIGNS SHALL COMPLY WITH THE PROJECT SPECIFICATIONS AND THE
REQUIREMENTS LISTED BELOW :
a. FOOTINGS, GRADE BEAMS, FOUNDATION WALLS :
1. 28 DAY COMPRESSIVE STRENGTH : 3000 PSI
b. RETAINING WALLS (EXPOSURE CATEGORY F2) :
1. 28 DAY COMPRESSIVE STRENGTH : 4500 PSI
2. MAXIMUM W/C RATIO : 0.45
3. MAXIMUM AGGREGATE SIZE : 1"
4. AIR CONTENT : SEE SCHEDULE BELOW
c. INTERIOR SLABS ON GRADE (EXPOSURE CATEGORY F0) :
1. 28 DAY COMPRESSIVE STRENGTH : 3000 PSI
d. TOTAL AIR CONTENT FOR CONCRETE EXPOSED TO CYCLES OF FREEZING AND THAWING
SHALL BE DETERMINED IN ACCORDANCE WITH THIS SCHEDULE. TOLERANCE ON AIR CONTENT
AS DELIVERED SHALL BE +/- 1.5 PERCENT.
NOMINAL MAXIMUM TARGET AIR CONTENT, PERCENT
AGGREGATE SIZE, IN. F1 F2 AND F3
3/8 6 7.5 1/2 5.5 7 3/4 5 6 1 4.5 6 1-1/2 4.5 5.5 2 4 5 3 3.5 4.5
2. WATER USED IN MIXING CONCRETE SHALL CONFORM TO ASTM C1602.
3. NO PIPES, DUCTS, SLEEVES, ETC. SHALL BE PLACED IN STRUCTURAL CONCRETE UNLESS
SPECIFICALLY DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER. NO ALUMINUM
PRODUCTS SHALL BE EMBEDDED IN CONCRETE. PENETRATIONS THRU STRUCTURAL CONCRETE
ELEMENTS MUST BE APPROVED BY THE ENGINEER AND SHALL BE BUILT INTO THE ELEMENT
PRIOR TO CONCRETE PLACEMENT.
4. REFER TO ARCHITECTURAL DRAWINGS FOR MOLDS, GROOVES, ORNAMENTS, ETC. TO BE CAST IN
TO CONCRETE, AND FOR EXTENT AND LOCATION OF DEPRESSIONS, CURBS, RAMPS, ETC.
5. UNLESS NOTED OTHERWISE, MINIMUM REINFORCING IN ALL CONCRETE FOUNDATION WALLS
SHALL BE AS FOLLOWS:
TOP &
THICKNESS BOTTOM BARS VERTICAL HORIZONTAL
8” (2) #5 #4 AT 18”O.C. #4 AT 12”O.C.
12” (2) #5 #4 AT 18”O.C. EA FACE #4 AT 16”O.C. EA FACE
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
R4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL
UINTA WASATCH CACHE
NATIONAL FOREST
TMD
BLP
JLA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
SALT LAKE RANGER DISTRICT
C
U se rs \b en ja m in p \D o cu m en ts \S
-2
S al t L ak e
R an g er
D is tr ic t
_s te n
.r vt
S002
STRUCTURAL NOTES
shillworthen Text Box shillworthen
6. CONCRETE TEMPERATURE AT THE TIME OF INSTALLATION SHALL BE MONITORED BY THE
CONTRACTOR. CONTRACTOR SHALL COMPLY WITH ALL MANUFACTURER'S PRINTED
INSTALLATION INSTRUCTIONS (MPII) RELATIVE TO SUBSTRATE TEMPERATURE.
7. INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR UPWARDLY INCLINED TO SUPPORT
SUSTAINED TENSION LOADS SHALL BE PERFORMED BY PERSONNEL CERTIFIED BY AN
APPLICABLE CERTIFICATION PROGRAM. CERTIFICATION SHALL INCLUDE WRITTEN AND
PERFORMANCE TESTS IN ACCORDANCE WITH THE ACI/CRSI ADHESIVE ANCHOR INSTALLER
CERTIFICATION PROGRAM, OR EQUIVALENT IN ACCORDANCE WITH ACI 318-11 D.9.2.2. PROOF OF
CURRENT CERTIFICATION SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO
INSTALLATION. CONTINUOUS SPECIAL INSPECTION SHALL BE PROVIDED FOR THESE ANCHORS.
8. UNLESS NOTED OTHERWISE, ALL ADHESIVE ANCHORS INTO CONCRETE SHALL BE:
a. HILTI HIT-RE 500V3 (ESR-3814), OR HILTI HIT-HY 200-A (ESR-3187).
b. SIMPSON SET-3G (ESR-4057), OR AT-XP (ER-0263).
c. DEWALT PURE 110+ (ESR-3298), OR AC200+ GOLD (ESR-4027-COLD WEATHER).
9. UNLESS NOTED OTHER WISE, ALL MECHANICAL ANCHORS INTO CONCRETE SHALL BE:
a. HILTI KWIK BOLT TZ (ESR-1917).
b. SIMPSON STRONG-BOLT 2 (ESR-3037).
10. UNLESS NOTED OTHERWISE, ALL SCREW ANCHORS INTO CONCRETE SHALL BE:
a. SIMPSON TITEN HD (ESR-2713).
b. DEWALT SCREWBOLT+ (ESR-3889).
c. HILTI KWIK HUS-EZ (ESR-3027).
11. THE TESTING LABORATORY WILL PERFORM VISUAL INSPECTION OF ANCHORS AND DOWELS AS
SPECIFIED IN THE SPECIAL INSPECTION SCHEDULE AND THE APPROVED INDEPENDENT
EVALUATION REPORT. TENSION TESTING CAN BE REQUIRED AT THE DIRECTION OF THE
STRUCTURAL ENGINEER OF RECORD OR THE SPECIAL INSPECTOR.
12. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON THAT HOLE AND SHIFT THE
ANCHOR LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM SPACE OF (2)
ANCHOR HOLE DIAMETERS OR 1 INCH, WHICH EVER IS LARGER, OF SOUND
CONCRETE/MASONRY BETWEEN THE ANCHOR AND THE ABANDONED HOLE. FILL THE
ABANDONED HOLE WITH NON-SHRINK GROUT. AT CONTRACTORS OPTION, LOCATE EXISTING
REINFORCEMENT PRIOR TO DRILLING/CORING. IF THE ANCHOR OR DOWEL CANNOT BE
SHIFTED AS NOTED ABOVE, THE ENGINEER WILL DETERMINE A NEW LOCATION.
13. LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING
PLATES, MEMBERS, OR OTHER STEEL ASSEMBLIES ATTACHED WITH MECHANICAL ANCHORS.
H. REINFORCING STEEL
1. REINFORCING BAR STRENGTH REQUIREMENTS:
a. ALL REINFORCING BARS EXCEPT AS INDICATED IN NOTE b, SHALL CONFORM TO ASTM
STANDARD A-615 GRADE 60 AND ALL WELDED WIRE FABRIC SHALL CONFORM TO ASTM
STANDARD A-1064 AND SHALL BE SUPPLIED IN FLAT SHEETS. ADEQUATELY TIE AND
SUPPORT ALL REINFORCING STEEL AS SPECIFIED BY ACI 117, TO MAINTAIN EXACT
REQUIRED POSITION.
2. HEADED SHEAR STUD ASSEMBLIES SHALL CONFORM TO ASTM A1044.
3. STEEL DISCONTINUOUS FIBER REINFORCEMENT SHALL BE DEFORMED AND CONFORM TO ASTM
A820 AND SHALL HAVE A LENGTH TO DIAMETER RATIO NOT SMALLER THAN 50 AND NOT
GREATER THAN 100.
4. HEADED DEFORMED BARS SHALL CONFORM TO ASTM A970. OBSTRUCTIONS OR
INTERRUPTIONS OF THE BAR DEFORMATIONS, IF ANY, SHALL NOT EXTEND MORE THAN 2 BAR
DIAMETERS FROM THE BEARING FACE OF THE HEAD.
5. ALL REINFORCING STEEL SHALL BE TIED IN PLACE AND ADEQUATELY SUPPORTED PRIOR TO
PLACING CONCRETE. WET STABBING OF ANY REINFORCING STEEL IS NOT PERMITTED, UNLESS
SPECIFICALLY DETAILED OTHERWISE OR APPROVED BY THE ENGINEER.
6. ALL FIELD BENT DOWELS SHALL BE GRADE 40 WITH SPACING INDICATED REDUCED BY 1/3.
7. UNLESS NOTED OTHERWISE, REINFORCEMENT SHALL HAVE THE FOLLOWING CONCRETE
COVERAGE :
a. CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH ….. 3”
b. EXPOSED TO EARTH OR WEATHER :
1. #6 & LARGER ….. 2”
2. #5 & SMALLER …..1-1/2”
c. NOT EXPOSED TO WEATHER OR EARTH :
1. SLABS, WALLS, JOISTS, #11 & SMALLER ….. 3/4”
2. BEAMS, COLUMNS: MAIN REINFORCING OR TIES ….. 1-1/2”
d. SLAB ON GRADE :
1. PLACE REINFORCING AT CENTER OF SLAB UNLESS INDICATED OTHERWISE.
6. UNLESS NOTED OTHERWISE, CONCRETE SLABS ON EARTH SHALL BE REINFORCED AS
FOLLOWS:
4” THICK - UNREINFORCED
7. UNLESS NOTED OTHERWISE, FOR NON-DETAILED OPENINGS IN CONCRETE WALLS LARGER
THAN 12” AND SMALLER THAN 24” IN ANY DIRECTION ADD (2) #5 BARS ON ALL SIDES IN ADDITION TO REGULAR WALL REINFORCING AND EXTEND 24” EACH WAY BEYOND OPENING. IF 24” IS NOT
AVAILABLE ON EVERY SIDE, NOTIFY STRUCTURAL ENGINEER FOR FURTHER DIRECTION.
OPENINGS SHALL HAVE A MINIMUM OF 12" OF CONCRETE ABOVE THE OPENING, TYP.
8. CONSTRUCTION JOINTS NOT SHOWN ON THE PLANS SHALL BE MADE AND LOCATED SO AS TO
NOT IMPAIR THE STRENGTH OF THE STRUCTURE AND AS APPROVED BY THE STRUCTURAL
ENGINEER. PROVIDE 2 X 4 (SHAPED) KEYWAY IN ALL VERTICAL AND HORIZONTAL JOINTS UNLESS
NOTED OR DETAILED OTHERWISE. ALL STEEL REINFORCING SHALL BE CONTINUOUS THROUGH
COLD JOINTS UNLESS NOTED OTHERWISE. SEE TYPICAL DETAILS FOR COLD/CONSTRUCTION
JOINTS FOR SLABS ON GRADE.
9. WHERE NEW CONCRETE IS PLACED AGAINST PREVIOUSLY HARDENED CONCRETE, THE JOINT
SHALL BE CLEAN AND FREE OF LAITANCE. IMMEDIATELY BEFORE NEW CONCRETE IS PLACED,
CONSTRUCTION JOINTS SHALL BE PREWETTED AND STANDING WATER REMOVED.
F. ANCHOR BOLTS/EMBEDDED BOLTS
1. ALL ANCHOR BOLTS SHALL HAVE ASTM A-563 HEAVY HEX NUT AND ASTM F-436 WASHERS AT STANDARD OR OVERSIZED HOLES PER AISC SPECIFICATION TABLE J3.3. WHERE HOLE SIZES DO
NOT COMPLY WITH THE LIMITATIONS FOR OVERSIZED HOLES THE STRUCTURAL ENGINEER
SHALL BE NOTIFIED TO DETERMINE STEEL PLATE WASHER REQUIREMENTS. ANCHOR BOLTS
SHALL COMPLY WITH THE FOLLOWING :
a. AT WOOD STUD WALLS - ASTM A-307 GRADE HEADED BOLTS. ANCHOR BOLTS IN TREATED
LUMBER SHALL BE GALVANIZED OR STAINLESS STEEL. SEE TIMBER NOTES FOR MORE
INFORMATION.
b. AT ALL OTHER ANCHOR BOLTS (UNLESS NOTED OTHERWISE) - ASTM F1554 GRADE 36
HEADED BOLTS. (ASTM A36 THREADED ROD MAY BE USED WITH DOUBLE NUT AND WASHER.)
2. SEE TYPICAL ANCHOR BOLT DETAIL FOR DEFINITIONS OF EMBEDMENT LENGTH, ETC.
3. FURNISH TEMPLATES AND OTHER DEVICES AS NECESSARY FOR PRESETTING ALL BOLTS PRIOR
TO PLACING CONCRETE AND/OR GROUT.
4. IF THREADED RODS ARE USED AS PERMITTED ABOVE, THEY SHALL BE CLEAR OF SOIL AND DIRT.
5. WHERE REQUIRED FOR ERECTION, HOLES LARGER THAN OVERSIZED MAY BE PERMITTED WITH
THE USE OF STEEL PLATE WASHERS AT THE DISCRETION OF THE STRUCTURAL ENGINEER.
G. ADHESIVE/MECHANICAL ANCHORS
1. WITHOUT WRITTEN APPROVAL OF THE ENGINEER THROUGH THE COR, CONTRACTOR SHALL
NOT SUBSTITUTE POST-INSTALLED ANCHORS WHERE CAST-IN-PLACE ANCHORS ARE
SPECIFIED IN THE DRAWINGS.
2. WHERE STRUCTURAL DETAILS SPECIFY SPECIFIC BRANDS AND/OR TYPES OF ADHESIVES OR
ANCHORS, SUBSTITUTIONS OF OTHER BRANDS AND/OR TYPES IS NOT ALLOWED, WITHOUT
WRITTEN APPROVAL OF THE ENGINEER.
3. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS SHALL BE APPROVED IN WRITING BY
THE STRUCTURAL ENGINEER OF RECORD PRIOR TO USE. SUBSTITUTION REQUESTS SHALL
INCLUDE AN ICC ESR OR IAPMO REPORT AND SUPPORTING CALCULATIONS INDICATING
COMPLIANCE WITH DESIGN INTENT.
4. ALL ADHESIVE/MECHANICAL ANCHORS SHALL BE INSTALLED, INCLUDING HOLE DRILLING AND
PREPARATION, IN ACCORDANCE WITH AN APPROVED INDEPENDENT EVALUATION REPORT
(ICC-ES, IAPMO, OR APPROVED EQUAL), AS INDICATED BELOW, AND IN ACCORDANCE WITH ALL
MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS (MPII).
5. ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS
AT TIME OF ANCHOR INSTALLATION. ADHESIVE ANCHORS SHALL NOT BE FULLY LOADED UNTIL
CONCRETE HAS REACHED DESIGN STRENGTH.
6. UNLESS APPROVED BY THE ENGINEER OF RECORD, CONCRETE AND DRILLED ANCHOR HOLES
SHALL BE DRY AND FREE OF WATER FOR 24 HOURS PRIOR TO ADHESIVE INSTALLATION.
CONTACT THE ENGINEER OF RECORD FOR GUIDANCE IF THE CONTRACTOR CHOOSES TO
INSTALL IN WET OR DAMP HOLES.
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
R4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL
UINTA WASATCH CACHE
NATIONAL FOREST
TMD
BLP
JLA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
SALT LAKE RANGER DISTRICT
C
U se rs \b en ja m in p \D o cu m en ts \S
-2
S al t L ak e
R an g er
D is tr ic t
_s te n
.r vt
S003
STRUCTURAL NOTES
shillworthen Text Box shillworthen
J. TIMBER
1. WOOD GRADES (UNLESS NOTED OTHERWISE)
a. ALL FRAMING LUMBER SHALL BE DOUGLAS FIR/LARCH CLEARLY MARKED WITH
A STAMP BY WWPA APPROVED AGENCY AND SHALL BE GRADED AS FOLLOWS:
1. HORIZONTAL MEMBERS: JOISTS & RAFTERS: NO. 2, BEAMS & STRINGERS:
NO. 2.
2. VERTICAL MEMBERS: POST & TRIMMERS: 1 1/2" x 5 1/2" LSL 1.3E STUDS, STUDS: 1 1/2" x 5 1/2" LSL 1.3E STUDS.
b. ALL WALLS SHALL BE FRAMED USING FULL LENGTH STUDS. DO NOT STACK
WALLS OR SPLICE STUDS.
c. ALL FRAMING IN CONTACT WITH FOOTINGS, FOUNDATIONS OR SLABS ON
GRADE SHALL BE PRESSURE TREATED OR TIMBERSTRAND LSL TREATED
LUMBER WITH EQUIVALENT STRESS GRADES TO TYPICAL FRAMING MEMBERS.
d. UNLESS NOTED OTHERWISE, ALL ENGINEERED LUMBER SHALL BE FURNISHED
BY TRUS-JOIST CORPORATION OR APPROVED EQUAL AND SHALL HAVE THE
FOLLOWING MINIMUM PROPERTIES : MODULUS OF ELASTICITY
FLEXURAL STRESS RATING
LVL : 2,000,000 PSI 2,600 PSI
PSL : 2,000,000 PSI 2,900 PSI
LSL : 1,500,000 PSI 2,250 PSI
e. ALL WOOD “I” JOISTS AND BRIDGING SHALL BE FURNISHED BY TRUS-JOIST
CORPORATION OR APPROVED EQUAL.
2. SHEATHING SHALL BE APA RATED SHEATHING, EXPOSURE I, EXTERIOR GLUE AND
PANEL INDEX RATING AS NOTED BELOW UNLESS NOTED OTHERWISE :
LOCATION THICKNESS PANEL INDEX
WALLS : 15/32” 24/0
FLOORS : 23/32” 48/24
ROOFS : 19/32” 32/16
3. INDIVIDUAL PIECES OF SHEATHING AT ROOF, FLOOR, AND SHEAR WALLS SHALL
NOT BE SMALLER THAN 24” IN EITHER DIRECTION AND SHALL SPAN A MINIMUM OF
TWO FRAMING SPACES, UNO.
4. ALL 23/32” FLOOR SHEATHING SHALL BE TONGUE AND GROOVE UNLESS NOTED
OTHERWISE.
8. EXCEPT WHERE NOTED ON PLANS OR DETAILS CONTINUOUS REINFORCEMENT
SHALL BE SPLICED AT POINTS OF MINIMUM STRESS BY LAPPING PER THE REBAR
LAP SCHEDULE.
9. REINFORCING STEEL MAY BE SPLICED WITH MECHANICAL COUPLERS THAT HAVE
A TENSION CAPACITY OF AT LEAST 125% OF THE STRENGTH OF THE BAR.
MECHANICAL COUPLERS SHALL BE A POSITIVE CONNECTING TYPE COUPLER,
AND SHALL BE INSTALLED IN ACCORDANCE WITH AN APPROVED ICC RESEARCH
REPORT. WHERE THESE ARE USED, SPLICES ON ADJACENT BARS SHALL BE
STAGGERED AT LEAST 24 INCHES ALONG THE LENGTH OF THE BARS.
10. ALL VERTICAL REINFORCING IN STRUCTURAL ELEMENTS ABOVE SHALL BE
SPLICED WITH MATCHING DOWELS EMBEDDED WITHIN THE FOOTINGS OR
STRUCTURE BELOW. SPLICE LENGTHS SHALL COMPLY WITH REBAR LAP
SCHEDULE. DOWELS INTO FOOTINGS SHALL TERMINATE WITH A STANDARD
HOOK, AND SHALL EXTEND TO WITHIN 4” OF THE BOTTOM OF THE FOOTING, BUT
NEED NOT EXTEND MORE THAN 20” INTO FOOTING.
11. DO NOT WELD REINFORCING EXCEPT AS NOTED ON PLANS, WHERE
REINFORCING IS WELDED, USE ASTM A-706 REINFORCING.
12. REINFORCING BARS, TIES, AND TENDONS SHALL BE SUPPORTED BY NYLON
CONES, PLASTIC-COATED TIE-WIRES, OR PLASTIC-COATED CHAIRS.
REINFORCING IN FOOTINGS IS PERMITTED TO BE SUPPORTED ON CONCRETE
DOBIES.
13. UNLESS NOTED OTHERWISE, HOOKS, STIRRUPS, TIES, AND OTHER BENDS IN
REINFORCING STEEL SHALL MEET THE STANDARDS SET FORTH IN ACI
318/318R-14. UNLESS OTHERWISE PERMITTED BY THE ENGINEER, ALL
REINFORCEMENT SHALL BE BENT COLD. REINFORCEMENT PARTIALLY
EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT, EXCEPT AS SHOWN ON
THESE DRAWINGS OR OTHERWISE PERMITTED BY THE ENGINEER.
14. UNLESS SPECIFICALLY NOTED AND/OR DETAILED IN THE STRUCTURAL
DRAWINGS CONDUIT SHALL NOT BE IN CONTACT WITH REINFORCING STEEL.
5. CONNECTIONS, FASTENERS, AND ADHESIVE
a. ALL BOLTS THRU WOOD SHALL BE ASTM A307 AND SHALL HAVE HARDENED WASHERS UNDER ASTM
A563 HEAVY HEX NUT AND BOLT HEADS.
b. UNLESS NOTED OTHERWISE, 10d COMMON (0.148) NAILS SHALL BE USED TO FASTEN ALL PLYWOOD FLOOR
AND ROOF SHEATHING TO SUPPORTING TRUSSES, JOISTS, LEDGERS OR BLOCKING AS FOLLOWS:
1. BOUNDARY NAILING “BN”: 4”O.C. AT ALL BEARING WALLS, SHEAR WALLS, BLOCKING, AND WHERE
OTHERWISE INDICATED IN THE STRUCTURAL DRAWINGS.
2. PANEL EDGE NAILING “EN”: 6”O.C. AT ALL OTHER PLYWOOD PANEL EDGES.
3. PANEL FIELD NAILING “FN”: 12”O.C. AT INTERIOR SUPPORTS IN FIELD OF PANEL.
c. UNLESS NOTED OTHERWISE IN THE WOOD SHEAR WALL SCHEDULE ON SHEET S011, 8d COMMON (0.131) NAILS SHALL BE USED TO FASTEN ALL PLYWOOD SHEAR WALL SHEATHING TO STUDS AND BLOCKING AS FOLLOWS:
1. PANEL EDGE NAILING “EN”: 6”O.C.
2. PANEL FIELD NAILING “FN”: 12”O.C. AT INTERIOR SUPPORTS IN FIELD OF PANEL.
d. NAILS SHALL BE GALVANIZED OR STAINLESS STEEL AT EXPOSED LOCATIONS OR IN TREATED WOOD (SEE NOTE BELOW FOR FASTENERS CONNECTED TO OR IN CONTACT WITH TREATED WOOD). THE HEAD OF ALL NAILS
SHALL BE DRIVEN FLUSH WITH THE SURFACE OF THE SHEATHING.
e. UNLESS NOTED OTHERWISE, ALL NAILS SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES :
COMMON SHANK HEAD LENGTH MIN. PENETRATION
NAIL SIZE DIAMETER DIAMETER INTO SUPPORT MEMBER
6d 0.113” 0.266” 2” 1.25” 8d 0.131” 0.281” 2-1/2” 1.375” 10d 0.148” 0.312” 3” 1.50” 12d 0.148” 0.312” 3-1/4” 1.50” 16d 0.162” 0.344” 3-1/2” 1.62”
f. ALL FRAMING ANCHORS, POST CAPS, HOLD DOWNS, COLUMN BASES ETC. TO BE PROVIDED BY SIMPSON OR APPROVED EQUAL AND SHALL BE ATTACHED IN ACCORDANCE WITH MANUFACTURER’S PUBLISHED DATA, UNLESS NOTED OTHERWISE.
g. UNLESS NOTED OTHERWISE, ALL WALL BOTTOM PLATES TO BE ANCHORED TO FOUNDATIONS OR FOOTINGS WITH 3/4” DIAMETER ANCHOR BOLTS AT 32”O.C. WITH 8” MINIMUM EMBEDMENT. THERE SHALL BE A MINIMUM OF
(2) ANCHOR BOLTS PER PLATE WITH ONE BOLT LOCATED NOT MORE THAN 12” AND NOT LESS THAN 4” FROM
EACH END OF EACH PIECE.
h. WALL BOTTOM PLATES AT SHEAR WALLS SHALL INCLUDE 1/4” x 3” x 3” STEEL PLATE WASHERS BETWEEN THE SILL PLATE AND NUT OF THE ANCHOR BOLT. THE HOLE IN THE PLATE WASHER IS PERMITTED TO BE DIAGONALLY SLOTTED WITH A WIDTH UP TO 3/16” LARGER THAN THE BOLT DIAMETER AND SLOT LENGTH NOT TO EXCEED 1-3/4”, PROVIDED A STANDARD CUT WASHER IS PLACED BETWEEN THE PLATE WASHER AND THE NUT. THE PLATE WASHER SHALL EXTEND TO WITHIN ½” OF THE EDGE OF THE BOTTOM PLATE ON THE
SHEATHED SIDE.
i. FASTENERS CONNECTED TO OR IN CONTACT WITH PRESERVATIVE-TREATED AND/OR FIRE-RETARDANT- TREATED WOOD (EXCEPT FOR TIMBERSTRAND LSL TREATED LUMBER AND BORATE BASED TREATMENTS) SHALL BE OF G-185 HOT-DIP GALVANIZED STEEL OR 304 OR 316 STAINLESS STEEL. STAINLESS STEEL AND
GALVANIZED STEEL SHALL NEVER BE USED IN CONTACT WITH EACH OTHER.
j. EXCEPT WHERE NOTED OTHERWISE, THE NUMBER AND SIZE OF NAILS CONNECTING WOOD MEMBERS SHALL NOT BE LESS THAN THAT SET FORTH IN IBC TABLE 2304.10.1. CONNECTIONS FOR MULTIPLE PIECES
OF ENGINEERED LUMBER PIECES SHALL BE IN ACCORDANCE WITH THE MANUFACTURERS SPECIFICATIONS.
6. UNLESS NOTED OTHERWISE, ALL ROOF SHEATHING AND WALL SHEATHING AT SHEAR WALLS SHALL HAVE SOLID
BLOCKING AT ALL PANEL EDGES.
7. PROVIDE DOUBLE JOIST UNDER PARALLEL NONBEARING WALLS AND SOLID BLOCKING UNDER PERPENDICULAR
NONBEARING WALLS.
8. AT ALL OVERBUILD LOCATIONS, ROOF SHEATHING SHALL BE COMPLETE BELOW OVERBUILDS PRIOR TO
OVERBUILD CONSTRUCTION.
9. PROVIDE SOLID 2” (NOMINAL) FULL DEPTH BLOCKING AT ENDS AND SUPPORT LOCATIONS FOR ALL JOISTS AND
RAFTERS. BLOCKING SHALL BE ATTACHED TO SUPPORT FRAMING WITH A MINIMUM OF (1) SIMPSON A35 FRAMING
ANCHOR BETWEEN JOISTS UNLESS NOTED OTHERWISE.
10. UNLESS NOTED OTHERWISE, ALL BEARING WALLS SHALL BE 1 1/2" x 5 1/2" LSL STUDS SPACED AT 16“O.C. BLOCK
ALL NON-SHEATHED BEARING WALLS AT 4’-0”O.C.
11. VERIFY THE STUD SPACING WITH THE ANCHOR BOLT LAY-OUT. WHERE STUDS INTERFERE WITH ANCHOR BOLTS, PROVIDE AN ADDITIONAL FULL-HEIGHT STUD TO ENSURE THAT THE FULL CROSS-SECTIONAL AREA OF THE STUD IS
IN CONTACT WITH THE SILL PLATE.
12. UNLESS NOTED OTHERWISE, ALL EXTERIOR WALLS AND SHEAR WALLS SHALL HAVE DOUBLE 2X TOP PLATES THAT ARE SPLICED TOGETHER WITH A MINIMUM OF 48" OF OVERLAP AND SHALL BE CONNECTED TOGETHER WITH A MINIMUM OF (8) 10d COMMON NAILS EACH SIDE OF THE SPLICE. OUTSIDE OF THESE SPLICE LOCATIONS, TOP PLATES SHALL BE NAILED TOGETHER WITH 10d NAILS AT 12” O.C.
13. UNLESS NOTED OTHERWISE, ALL HORIZONTAL FRAMING MEMBERS SHALL BE INSTALLED WITH THE NATURAL
CROWN UP.
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
R4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL
UINTA WASATCH CACHE
NATIONAL FOREST
TMD
BLP
JLA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
SALT LAKE RANGER DISTRICT
C
U se rs \b en ja m in p \D o cu m en ts \S
-2
S al t L ak e
R an g er
D is tr ic t
_s te n
.r vt
S004
STRUCTURAL NOTES
shillworthen Text Box shillworthen
K. STRUCTURAL DELEGATED DESIGNS AND DEFERRED SUBMITTALS
1. STRUCTURAL DELEGATED DESIGNS AND SUBSEQUENT DEFERRED SUBMITTALS ARE FOR
ELEMENTS, PARTS, OR PORTIONS OF THE OVERALL STRUCTURAL SYSTEM THAT ARE
INDICATED OR REFERRED TO ON THESE DRAWINGS AND THAT ARE CRITICAL TO THE
PERFORMANCE OF THE OVERALL STRUCTURAL SYSTEM. DESIGN CRITERIA HAS BEEN
PROVIDED FOR THESE ITEMS IN THE STRUCTURAL NOTES, PLANS, AND DETAILS.
2. STRUCTURAL DEFERRED SUBMITTALS ARE COMPLETE PACKAGES TO BE SUBMITTED FOR
REVIEW THAT INCLUDE DRAWINGS AND CALCULATIONS FOR ALL DELEGATED DESIGN ITEMS
AND THEIR CONNECTIONS. DEFERRED SUBMITTALS SHALL BEAR THE STAMP AND SIGNATURE
OF THE DESIGN PROFESSIONAL RESPONSIBLE FOR THEIR DESIGN.
3. ARW ENGINEERS WILL REVIEW STRUCTURAL DEFERRED SUBMITTALS TO VERIFY DESIGN
CRITERIA IS COMPLIANT WITH THE APPROVED CONSTRUCTION DOCUMENTS.
4. STRUCTURAL DELEGATED DESIGN COMPONENTS SHALL NOT BE INSTALLED UNTIL APPROVED
BY THE BUILDING OFFICIAL.
5. STRUCTURAL DELEGATED DESIGN ITEMS REQUIRING DEFERRED SUBMITTALS INCLUDE, BUT
ARE NOT LIMITED TO :
a. HELICAL PIERS / MICRO PILES (SHALL INCLUDE, BUT NOT BE LIMITED TO, PIER LAY-OUT, QUANTITIES, SHAFT AND HELIX SIZES, FOUNDATION CONNECTION REQUIREMENTS, TEST
PIER REQUIREMENTS, APPLIED SAFETY FACTORS, ETC.).
L. NON-STRUCTURAL DELEGATED DESIGNS AND DEFERRED SUBMITTALS
1. NON-STRUCTURAL DELEGATED DESIGNS AND SUBSEQUENT DEFERRED SUBMITTALS ARE FOR
ITEMS NOT INCLUDED IN THE STRUCTURAL DELEGATED DESIGN SECTION. THESE ARE ITEMS
THAT ARE NOT CRITICAL TO THE OVERALL PERFORMANCE OF THE STRUCTURAL SYSTEM BUT
THAT IMPART LOADS AND FORCES TO THE STRUCTURAL SYSTEM.
2. NON-STRUCTURAL DEFERRED SUBMITTALS SHALL BEAR THE STAMP AND SIGNATURE OF THE
DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN.
3. ARW ENGINEERS WILL REVIEW NON-STRUCTURAL DEFERRED SUBMITTALS TO VERIFY DESIGN
CRITERIA IS COMPLIANT WITH THE APPROVED CONSTRUCTION DOCUMENTS.
4. IF THE STRUCTURAL DRAWINGS INCLUDE LOADS TO ACCOMMODATE NON-STRUCTURAL
ELEMENTS, THE CONTRACTOR SHALL SUBMIT DOCUMENTATION INDICATING THAT THE NON-
STRUCTURAL ELEMENTS COMPLY WITH THE LOADING CRITERIA PROVIDED HEREIN. SUCH
DOCUMENTATION SHALL BEAR THE STAMP AND SIGNATURE OF THE DESIGN PROFESSIONAL
RESPONSIBLE FOR THE DESIGN.
5. WHEN THE NON-STRUCTURAL DEFERRED SUBMITTAL INDICATES THAT THE ELEMENT WILL
IMPART FORCES IN EXCESS OF LOADS THAT ARE INDICATED ON THE STRUCTURAL
DRAWINGS, THE CONTRACTOR SHALL SUBMIT A DETAILED GRAPHICAL REPRESENTATION OF
THOSE DESIGN LOADS, INCLUDING MAGNITUDE, AND LOCATION. THE GRAPHIC SHALL BE
ACCOMPANIED BY DOCUMENTATION INDICATING THAT THE NON-STRUCTURAL ELEMENT
DESIGN COMPLIES WITH THE LOADING CRITERIA PROVIDED HEREIN. THE LETTER SHALL BEAR
THE STAMP AND SIGNATURE OF THE DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN.
6. NON-STRUCTURAL DELEGATED DESIGN ITEMS REQUIRING DEFERRED SUBMITTALS SHALL
INCLUDE, BUT ARE NOT LIMITED TO :
a. SEISMIC BRACING OF ALL ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL
ITEMS WHERE REQUIRED BY THE MOST RECENT VERSION OF ASCE 7 AND THE PROJECT
CONTRACT DOCUMENTS.
b. PIPE RAILINGS AND METAL LADDERS.
M. EXISTING BUILDING NOTES
1. ARW ENGINEERS EXPRESSLY DISCLAIMS RESPONSIBILITY FOR ANY PORTION OF THE
EXISTING BUILDING NOT SPECIFICALLY ADDRESSED IN THESE DRAWINGS.
2. DRAWINGS AND DETAILS HAVE BEEN PREPARED TO REFLECT THE EXISTING
CONDITIONS AND CONFIGURATIONS OF STRUCTURAL ELEMENTS. HOWEVER, THE
CONTRACTOR IS ULTIMATELY RESPONSIBLE FOR VERIFYING ALL EXISTING
CONDITIONS AND ALERTING THE ENGINEER OF ANY DISCREPANCIES FOUND PRIOR TO
FABRICATING OR INSTALLING STRUCTURAL ELEMENTS.
3. THE CONTRACTOR IS RESPONSIBLE FOR MAKING SURE THAT THE BUILDING AND
ELEMENTS WITHIN THE BUILDING REMAIN STABLE UNTIL CONSTRUCTION IS
COMPLETE. AT NO ADDITIONAL COST TO THE OWNER, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING SHORING OR OTHER TEMPORARY SUPPORT OF
STRUCTURAL MEMBERS UNTIL THE FINAL CONFIGURATION HAS BEEN COMPLETED.
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
R4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL
UINTA WASATCH CACHE
NATIONAL FOREST
TMD
BLP
JLA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
SALT LAKE RANGER DISTRICT
C
U se rs \b en ja m in p \D o cu m en ts \S
-2
S al t L ak e
R an g er
D is tr ic t
_s te n
.r vt
S005
STRUCTURAL NOTES
shillworthen Text Box shillworthen
S S
LEGEND OF SYMBOLS AND ABBREVIATIONS
AB = ANCHOR BOLT
ABV = ABOVE
ARCH = ARCHITECT
BLW = BELOW
BN = BOUNDARY NAILING
BS = BOUNDARY SCREW
BRB = BUCKLING RESTRAINED BRACE
BRBF = BUCKLING RESTRAINED BRACE FRAME
CJP = COMPLETE JOINT PENETRATION
CL = CENTERLINE
CMU = CONCRETE MASONRY UNIT
COL = COLUMN
CONC = CONCRETE
CP = CONCRETE PIER
DC = DEMAND CRITICAL
DIA / Ø = DIAMETER
DBA = DEFORMED BAR ANCHOR
DBE = DECK BEARING ELEVATION
ELEV = ELEVATION
EN = EDGE NAILING
EOD = EDGE OF DECK
FDN = FOUNDATION
FN = FIELD NAILING
FTG = FOOTING
FFE = FINISHED FLOOR ELEVATION
GB = CONCRETE GRADE BEAM
HSA = HEADED STUD ANCHOR
JBE = JOIST BEARING ELEVATION
KB = KICKER BRACE
MAX = MAXIMUM
MB = MASONRY BEAM
MC = MASONRY COLUMN
MECH = MECHANICAL
MEZZ = MEZZANINE
MIN = MINIMUM
MJ = MASONRY JAMB
MW = MASONRY WALL
NS, FS = NEAR SIDE, FAR SIDE
OAE = OR APPROVED EQUAL
OPP = OPPOSITE
PAF = POWDER ACTUATED FASTENER
PL = PLATE
REINF = REINFORCING
REQ'D = REQUIRED
SIM = SIMILAR
SSH = STEEL STUD HEADER
SSJ = STEEL STUD JAMB
SSS = STEEL STUD SILL
SSW = STEEL STUD WALL
TOB = TOP OF BEAM ELEVATION
TOC = TOP OF CONCRETE SLAB
TOF = TOP OF FOOTING
TOG = TOP OF GIRDER ELEVATION
TOM = TOP OF MASONRY
TOS = TOP OF STEEL ELEVATION
TYP = TYPICAL
UNO = UNLESS NOTED OTHERWISE
CONCRETE BEAM
FOOTING STEP
TOP OF FOUNDATION WALL OR
COLUMN PIER ELEV.
SHEET NUMBER
TOP OF FOOTING ELEV.
SECTION MARK
FOOTING MARK
ITEMS, DETAILS, & SYSTEMS WHICH
ARE PART OF THE LATERAL FORCE
RESISTING SYSTEM.
L
ELEVATION
SHEAR WALL - SEE SCHEDULE
MIN. LENGTH OF SHEAR WALL
DEPRESS FDN./WALL AND POUR
FLOOR SLAB OVER AT CONCRETE
FOUNDATION WALL
HD - SIMPSON HOLDOWN SIZE
POST - SIZE OF END POST CONNECTED
TO HOLDOWN
"A" - PLAN CONFIGURATION AT
HOLDOWN AT FOUNDATION
"A
PO
STH
D
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
R4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL
UINTA WASATCH CACHE
NATIONAL FOREST
TMD
BLP
JLA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
SALT LAKE RANGER DISTRICT
C
U se rs \b en ja m in p \D o cu m en ts \S
-2
S al t L ak e
R an g er
D is tr ic t
_s te n
.r vt
S006
SCHEDULES
shillworthen Text Box shillworthen
ESTABLISHED PER 2018 IBC SECTION 110 AND CHAPTER 17
ITEM PERIODIC3CONTINUOUS3 REFERENCE COMMENTS
SEE IBC TABLE 1705.3 - REF. NOTE C1
REFERENCE NOTE C4
REFERENCE NOTE C5
REFERENCE NOTE C2
REFERENCE NOTES P1 & P2
REFERENCE NOTE C3
EPOXY / EXPANSION ANCHOR PLACEMENT
VERIFICATION OF IN-SITU STRENGTH
CURING TEMPERATURE / TECHNIQUES
CONCRETE PLACEMENT / SAMPLING
VERIFYING REQUIRED DESIGN MIX
EMBEDDED BOLTS & PLATES
WELDING OF REINFORCING STEEL
REINFORCING STEEL PLACEMENT
CONCRETE CONSTRUCTION (IBC 1705.3)
SPECIAL INSPECTION SCHEDULE 1, 2
PRE-FAB CONSTRUCTION (IBC 1704.2)
1. SPECIAL INSPECTION IS NOT REQUIRED WHERE THE WORK IS DONE ON THE PREMISES
OF A FABRICATOR REGISTERED AND APPROVED TO PERFORM SUCH WORK WITHOUT
SPECIAL INSPECTION, PROVIDED THE FABRICATOR COMPLIES WITH IBC.
2. INSPECTION FOR PREFABRICATED CONSTRUCTION SHALL BE THE SAME AS IF THE
MATERIAL USED IN THE CONSTRUCTION TOOK PLACE ON SITE. SPECIAL INSPECTION
WILL NOT BE REQUIRED DURING PREFABRICATION IF THE APPROVED AGENCY
CERTIFIES THE CONSTRUCTION AND FURNISHES EVIDENCE OF COMPLIANCE. (SEE
NOTE 2).
1. SPECIAL INSPECTION IS NOT REQUIRED FOR CONC. ISOLATED SPREAD FOOTINGS,
CONTINUOUS FOOTINGS, NON-STRUCTURAL SLABS, FOUNDATION WALLS, PATIOS,
DRIVEWAYS, AND SIDEWALKS PROVIDED THE REQUIREMENTS OF IBC 1705.3 ARE MET.
2. PERIODIC SPECIAL INSPECTION IS ALLOWED FOR VERIFICATION OF THE WELDABILITY OF
REINFORCING STEEL RESISTING FLEXURAL AND AXIAL FORCES IN INTERMEDIATE AND
SPECIAL MOMENT FRAMES, BOUNDARY ELEMENTS OF SPECIAL REINFORCED CONCRETE
SHEAR WALLS, AND SHEAR REINFORCEMENT. PERIODIC SPECIAL INSPECTION IS
ALLOWED FOR WELDING OF OTHER ASTM A 706 REINFORCING STEEL NOT INCLUDED IN
THE CONTINUOUS SPECIAL INSPECTION REQUIREMENTS NOTED ABOVE.
3. PERFORM AIR, SLUMP AND TEMP. TESTS WHEN CONCRETE SAMPLES ARE CAST.
4. PERIODIC SPECIAL INSPECTION IS REQUIRED FOR VERIFICATION OF IN-SITU CONCRETE
STRENGTH FOR POST-TENSIONED CONCRETE PRIOR TO TENSIONING TENDONS OR
REMOVING SHORING OR FORMS.
5. EPOXY AND EXPANSION ANCHORS INTO MASONRY OR CONCRETE MAY BE USED ONLY
WHEN APPROVED BY COR USING AN APPROVED PRODUCT WITH CURRENT PUBLISHED
ICC RESEARCH REPORT NUMBERS. COORDINATE CONTINUOUS/PERIODIC SPECIAL
INSPECTION REQUIREMENTS WITH ICC REPORT.
C
C
C C
C
P
P
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
R4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL
UINTA WASATCH CACHE
NATIONAL FOREST
TMD
BLP
JLA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
SALT LAKE RANGER DISTRICT
C
U se rs \b en ja m in p \D o cu m en ts \S
-2
S al t L ak e
R an g er
D is tr ic t
_s te n
.r vt
S007
SCHEDULES
L shillworthen Text Box shillworthen
ESTABLISHED PER 2018 IBC SECTION 110 AND CHAPTER 17
ITEM
GENERAL SPECIAL INSPECTION NOTES :
PERIODIC3CONTINUOUS3 REFERENCE COMMENTS
REFERENCE NOTE W1
REFERENCE NOTE F1
REFERENCE NOTE F1
REFERENCE NOTE F1
REFERENCE NOTE F2
REFERENCE NOTE W2
REFERENCE NOTE F1
REFERENCE NOTE F2
HIGH LOAD DIAPHRAGMS (ROOF / FLOOR)
SITE-BUILT ASSEMBLIES
PROPERLY PREPARED SITE AND SUB-GRADE PRIOR
TO FILL.
VERIFY ADEQUATE MATERIALS BELOW FOOTINGS
EXCAVATIONS EXTEND TO PROPER DEPTH AND
REACH PROPER MATERIAL
CLASSIFY & TEST CONTROLLED FILL MATERIALS
PERFORM MATERIALS, DENSITIES, AND LIFT
THICKNESSES DURING PLACEMENT AND
COMPACTION OF CONTROLLED FILL.
SHEAR WALL & DIAPHRAGM NAILING
DRAG STRUTS
BRACES & SHEAR PANELS
HOLDOWNS
SPECIAL INSPECTION SCHEDULE 1, 2
WOOD (IBC 1705.5 & 1705.11.1 & 1705.12.2)
SOILS (IBC 1705.6)
1. WOOD STRUCTURAL PANEL SHEATHING SHALL BE INSPECTED TO ASCERTAIN THAT
GRADE AND THICKNESS ARE IN COMPLIANCE WITH APPROVED BUILDING PLANS.
NOMINAL SIZE OF FRAMING MEMBERS AT ADJOINING PANEL EDGES, THE NAIL OR
STAPLE DIAMETER AND LENGTH, THE NUMBER OF FASTENER LINES, AND SPACING
BETWEEN FASTENERS IN EACH LINE AND AT EDGE MARGINS SHALL ALSO BE
INSPECTED AND VERIFIED FOR COMPLIANCE WITH APPROVED BUILDING PLANS.
2. SPECIAL INSPECTION IS NOT REQUIRED FOR WOOD SHEAR WALLS, WOOD
DIAPHRAGMS, INCLUDING NAILING, & BOLTING, AND OTHER FASTENING TO OTHER
COMPONENTS WHERE THE SPACING OF THE SHEATHING FASTENERS IS GREATER
THAN 4"o.c.
3. SPECIAL INSPECTION SHALL BE PERFORMED TO VERIFY THAT THE INSTALLATION OF
TEMPORARY AND PERMANENT RESTRAINT/BRACING IS INSTALLED IN ACCORDANCE
WITH THE APPROVED TRUSS SUBMITTAL PACKAGE.
1. SPECIAL INSPECTION OF SOILS SHALL REFERENCE THE APPROVED SOILS REPORT TO
DETERMINE COMPLIANCE.
2. WHERE SOILS REPORT IS NOT PROVIDED SPECIAL INSPECTIONS ARE REQUIRED TO
VERIFY THAT THE IN-PLACE DRY DENSITY OF THE COMPACTED FILL IS NOT LESS THAN
90 PERCENT OF THE MAXIMUM DRY DENSITY AT OPTIMUM MOISTURE CONTENT
DETERMINED IN ACCORDANCE WITH ASTM D 1557.
GLUING OPERATIONS
1. THE ITEMS MARKED WITH A " " IN THE SPECIAL INSPECTION SCHEDULE SHALL BE INSPECTED IN ACCORDANCE WITH IBC CHAPTER 17 BY A CERTIFIED SPECIAL INSPECTOR FROM AN ESTABLISHED TESTING AGENCY. FOR MATERIAL SAMPLING AND TESTING REQUIREMENTS, REFER TO THE MATERIAL SAMPLING AND TESTING SECTION, THE PROJECT SPECIFICATIONS, AND THE SPECIFIC GENERAL NOTES SECTIONS. THE TESTING AGENCY SHALL SEND COPIES OF ALL STRUCTURAL TESTING AND INSPECTION REPORTS DIRECTLY TO THE COR, ENGINEER, AND CONTRACTOR. ANY ITEMS WHICH FAIL TO COMPLY WITH THE APPROVED CONSTRUCTION DOCUMENTS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF DISCREPANCIES ARE NOT CORRECTED, THEY SHALL BE BROUGHT TO THE ATTENTION OF THE COR, ARCHITECT, AND ENGINEER PRIOR TO COMPLETION OF THAT PHASE OF WORK. SPECIAL INSPECTION
TESTING REQUIREMENTS APPLY EQUALLY TO ALL BIDDER DESIGNED COMPONENTS.
2. ANY CONSTRUCTION OR MATERIAL THAT HAS FAILED INSPECTION SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT.
3. CONTINUOUS SPECIAL INSPECTION MEANS THE FULL-TIME OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED. PERIODIC
SPECIAL INSPECTION MEANS THE PART-TIME OR INTERMITTENT OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK HAS BEEN OR IS BEING
PERFORMED AND AT THE COMPLETION OF THE WORK. (IBC SECTION 202)
F
F
W
W
W
METAL-PLATE-CONNECTED WOOD TRUSSES WITH
HEIGHTS GREATER THAN OR EQUAL TO 60"
REFERENCE NOTE W2
METAL-PLATE-CONNECTED WOOD TRUSSES WITH
SPANS GREATER THAN OR EQUAL TO 60 FEET
REFERENCE NOTE W3
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
R4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL
UINTA WASATCH CACHE
NATIONAL FOREST
TMD
BLP
JLA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
SALT LAKE RANGER DISTRICT
C
U se rs \b en ja m in p \D o cu m en ts \S
-2
S al t L ak e
R an g er
D is tr ic t
_s te n
.r vt
S008
SCHEDULES
L shillworthen Text Box shillworthen
TYP. FOOTING SECTION
THICKWIDTHMARK LENGTH
LENGTHWISE REINF.
NO. SIZE NO. SIZE SPA.
CROSSWISE REINF.
REMARKS
FOOTING SCHEDULE
FC2 2'-0" CONT. 12" (2) #5 -- -- --
F3 3'-0" 3'-0" 12" (3) #5 (3) #5 --
TYPICAL FOOTING REINFORCING
3" CLEAR EQ. EQ. EQ. 3" CLEAR
3" CLEAR
FC3 3'-0" CONT. 12" (3) #5 -- -- --
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
R4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL
UINTA WASATCH CACHE
NATIONAL FOREST
TMD
BLP
JLA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
SALT LAKE RANGER DISTRICT
C
U se rs \b en ja m in p \D o cu m en ts \S
-2
S al t L ak e
R an g er
D is tr ic t
_s te n
.r vt
S009
SCHEDULES
shillworthen Text Box shillworthen
TYPE STRENGTH
FOR CONCRETE APPLICATIONS (ACI 318 - 14)
BAR LOCATION
CONCRETE
#3
BAR SIZE
CONCRETE REINFORCING & SPLICE LENGTHS (IN)
2018 IBC CONCRETE REBAR LAP SPLICE SCHEDULE
VERT. WALL BARS,
FILL ON METAL DECK
NWC 4500 PSI 14
NOTES :
1. MECHANICAL COUPLERS MAY BE USED IN LIEU OF LAP SPLICES SHOWN. SEE STRUCTURAL NOTES FOR MINIMUM COUPLER CAPACITY. WHERE MECHANICAL COUPLERS ARE USED, STAGGER ADJACENT SPLICES A MINIMUM OF 24" AS
INDICATED ABOVE.
2. DEVELOPMENT LENGTHS SHALL BE INCREASED BY 50% FOR STRAIGHT BAR DEVELOPMENT AND 20% FOR HOOKED BARS WHERE EPOXY COATING IS USED.
3. WHEN SPLICING BARS OF DIFFERENT SIZES, USE LAP SPLICE LENGTH OF LARGER BARS UNO.
4. SPLICE BARS LARGER THAN #11 USING MECHANICAL COUPLERS.
HORIZ. WALL BARS,
FOOTING TOP BARS
BEAM BOTTOM BARS,
COLUMN BARS
FOOTING BOTTOM
BARS
BEAM TOP BARS
SLAB ON GRADE
NWC 4500 PSI
NWC 4500 PSI
NWC 4500 PSI
NWC 4500 PSI
NWC 4500 PSI
ℓd ℓs ℓdh
18 7
14 18 7
14 18 7
12 16 7
18 23 7
12 16 7
#4 ℓd ℓs ℓdh
23 6
#5 ℓd ℓs ℓdh
#6 ℓd ℓs ℓdh
#7 ℓd ℓs ℓdh
18 23 6
18 23 9
12 16 6
24 31 9
12 16 6
#8 ℓd ℓs ℓdh
#9 ℓd ℓdh
#10 ℓd ℓdh
#11 ℓd ℓdh
23 30 8
23 30 8
23 30 11
14 18 8
30 39 11
14 18 8
27 35 9
27 35 9
27 35 13
17 22 9
35 46 13
17 22 9
40 52 11
40 52 11
40 52 16
24 31 11
51 66 16
27 35 11
45 59 13
45 59 13
45 59 18
27 35 13
59 77 18
34 44 13
66 14
66 14
66 20
40 14
86 20
57 14
73 16
73 16
73 22
44 16
95 22
73 16
81 25
81 25
81 25
48 25
104 25
81 25
TYPE STRENGTH
BAR LOCATION
CONCRETE
#3
BAR SIZE
CONCRETE REINFORCING & SPLICE LENGTHS (IN)
VERT. WALL BARS,
FILL ON METAL DECK
NWC 3000 PSI 17
HORIZ. WALL BARS,
FOOTING TOP BARS
BEAM BOTTOM BARS,
COLUMN BARS
FOOTING BOTTOM
BARS
BEAM TOP BARS
SLAB ON GRADE
NWC 3000 PSI
NWC 3000 PSI
NWC 3000 PSI
NWC 3000 PSI
NWC 3000 PSI
ℓd ℓs ℓdh
22 8
#4 ℓd ℓs ℓdh
29 8
#5 ℓd ℓs ℓdh
#6 ℓd ℓs ℓdh
#7 ℓd ℓs ℓdh
#8 ℓd ℓs ℓdh
#9 ℓd ℓdh
#10 ℓd ℓdh
#11 ℓd ℓdh
28 36 10 33 43 12 48 62 13 55 72 15 81 17 90 19 99 30
17 22 8
17 22 8
12 16 8
22 29 8
12 16 8
22 29 8
22 29 11
14 18 8
29 38 11
14 18 8
28 36 10
28 36 14
17 22 10
36 47 14
17 22 10
33 43 12
33 43 16
20 26 12
43 56 16
20 26 12
48 62 13
48 62 19
29 38 13
63 82 19
32 42 13
55 72 15
55 72 22
33 43 15
72 94 22
42 55 15
81 17
81 25
48 17
105 25
69 17
90 19
90 27
55 19
117 27
90 19
99 30
99 30
60 30
127 30
99 30
DEVELOPMENT LENGTH
ℓd
LAP SPLICE LENGTH
ℓs
FACE OF JOINT OR
CRITICAL SECTION
FACE OF JOINT OR
CRITICAL SECTION
ℓdh
CLEAR
2' - 0"
COUPLER OR
WELDED SPLICE
HOOK DEVELOPMENT LENGTH
ℓs ℓs ℓs ℓs ℓs ℓs
62 69 76
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
FO
RES
T SERV ICE
D E P A
R TMENT OF AGR I CU
LT
U R E
United States Department of Agriculture
Forest Service
R4
INTERMOUNTAIN REGION
SALT LAKE
RANGER
DISTRICT
REMODEL
UINTA WASATCH CACHE
NATIONAL FOREST
TMD
BLP
JLA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
SALT…