J-1a Drawings MFE ATCT FLS Upgrade.pdf
PDF 2 MB Posted
- Attached to
- MFE Fire and Safety Upgrade Federal contract opportunity
- Solicitation number
- 697DCK-22-R-00483
About this file
This solicitation requests proposals for a fire and safety system upgrade at the McAllen International Airport air traffic control tower in McAllen, Texas. The Federal Aviation Administration requires upgrading the existing fire and safety systems to current standards, including upgrades to the fire alarm, detection, and suppression systems. Interested offerors must register in the System for Award Management and submit proposals in accordance with the solicitation instructions by the specified due date. A pre-proposal site visit is scheduled on August 23rd for interested parties to attend. Questions regarding the solicitation are due by August 30th. Offerors must be properly registered in SAM to be eligible for award.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 3_Past Peformance revised L and M.pdf | ||
| 697DCK22R00483_Amendment 0003.pdf | ||
| MFE Fire and Safety Upgrade QAs 6 Sep 22.pdf | ||
| 697DCK22R00483_Amendment 0002.pdf | ||
| 697DCK22R00483_Amendment 0001 Signin Sheet.pdf | ||
| Site Visit Signin Sheet.pdf | ||
| J-7 FAA Certification Vaccination PRAv7_Blank.pdf | ||
| J-4 eInvoicing Vendor Notification Letter.pdf | ||
| J-3 Construction Waste Management Form.xls | XLS spreadsheet | |
| L1 - Past Performance Questionnaire.pdf | ||
| 697DCK-22-R-00483 15 Aug 22.pdf | ||
| L3 - Form 7460-1.pdf | ||
| J-5 COVID 19 Memo Contractor_8-17-21.pdf | ||
| J-1 Specifications MFE ATCT FLS Upgrade.pdf | ||
| L2 - Price Proposal.xlsx | XLSX spreadsheet | |
| J-6 COVID-19 Contractual Requirement Rev 1 8-26-20.pdf | ||
| J-2 Wage Determinations.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
TX
KET
KET 1700774
C O
N S
T R
U
IO
ENGINEERING SERVICES
TERMINAL
ATCT
FIRST THROUGH THIRD FLOOR
TOWER FLOOR PLAN
FIRE/LIFE SAFETY UPGRADE
MILLER INTERNATIONAL AIRPORTMC ALLEN
PROJECT ENGINEER MGR: ENGINEERING - FORT WORTH
02/17/2022
MFE-D-ATCT-A008
m fe -d -a tc t-a .d g n
THIS DRAWING PRODUCED ON ASW REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
6 7
ISS
UE
D
FO
R:
$WATERMARK$
FIRST FLOOR PLAN
SCALE 1/8"=1'-0" SCALE 1/8"=1'-0"
SECOND FLOOR PLAN
SCALE 1/8"=1'-0"
THIRD FLOOR PLAN
SCALE: 1/8" = 1'-0"
8' 16'08'
M
IL
E
F A A
IN
I
IC
UP
CABLE PITDUCTS
UTILITY
CORRIDOR
STORAGE
EQUIP. RM.
GROUND
MECHANICAL
ELECTRICAL
PANEL RM.
ELECTRIC
SERVICE
TOILET
STAIR WELL
TELEPHONE
ROOM
G
DN.
CABLESDUCTS
GENERAL OFFICE
TOILET SECRETARY'S
OFFICE
DUCTS CABLES
DN. STAIR WELL
GENERAL AREA
IS
-d -a tc t-a
/0
/2
:1
:3
P lo tt e d b y
V
-C
-E
B
H
8 7 6 5 4 3 2 1
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
REDLINE
APVD
CONSTRUCTION NOTES
REMOVE DOOR
BELTS FOR STAIR PRESSURIZATION FAN
PROVIDE AND INSTALL 2 BELT PULLEY AND NEW
LABELED 'ICSS FAA INTERFACE DEM'
FIRESTOP 4"X4" HOLE IN BACK OF CABINET
FIRESTOP 4" CONDUIT PENETRATION
CHANGE DAMPER LINKAGE TO FAILSAFE CLOSED
ADD MAGNETIC DOOR HOLDERS. CONNECT TO FIRE ALARM SYSTEM
FIRESTOP 2"X2" HOLE IN WALL
ADJUST DOOR TO CLOSE AND LATCH PROPERLY
BE A LATCHING HANDLE. CONTRACTOR TO PROVIDE 'BEST' KEY CORE.
REPLACE DOOR HARDWARE AND DOOR CLOSER. DOOR HARDWARE TO
ADJUST ACCESS HATCH TO CLOSE AND LATCH PROPERLY
IV
ID
L
L P
IO R
IO F
IO M
mfe-d-atct-a008
2022-05-25T08:12:33-0500
WILLIAM C GRAY
2022-05-05T07:08:12-0500
KYLE E TANNER
FOURTH FLOOR THROUGH CAB
TOWER FLOOR PLAN
MFE-D-ATCT-A009
-d -a tc t-a
1 1
FOURTH FLOOR PLAN FIFTH FLOOR PLAN
CAB FLOOR PLAN
DN
ACCESS
HATCH
CABLES
DUCTS
MECHANICAL EQUIPMENT
JUNCTION ROOM
EXHAUST PLENUM
LOW ROOF
HATCH
RM.
LADDER
-d -a tc t-a
:4 lo tt e
GENERAL NOTES
WITH CABLE TRAY. PROVIDE ENGINEER JUDGEMENT
REMOVE OLD FIRESTOP. FIRESTOP 8"X24" HOLE
SCREWS AND PAINTED TO MATCH.
SHEET METAL COVER. COVER TO BE ATTACHED VIA
POSITION. PROVIDE AND INSTALL NEW INSULATED
AND DUCT. LOCK EXISTING DAMPER IN THE CLOSED
REMOVE EXISTING COVER SEALING OFF THE DAMPER
BLACK OR GRAY. ADJUST DOOR TO CLOSE AND LATCH PROPERLY.
DOOR SWEEP. EXTEND VINYL FLOOR UNDER DOOR. VINYL COLOR TO BE
REMOVE AIR SEAL FROM BOTTOM OF DOOR. REPLACE WITH MECHANICAL
MECHANICAL CHASE
PROVIDE AND INSTALL NEW 24"X24" FIRE RATED HATCH INTO THE
ADJUST DOOR TO CLOSE AND LATCH PROPERLY
BE A LATCHING HANDLE. CONTRACTOR TO PROVIDE 'BEST' KEY CORE.
REPLACE DOOR HARDWARE AND DOOR CLOSER. DOOR HARDWARE TO
mfe-d-atct-a009
2022-05-25T08:12:48-0500
WILLIAM C GRAY
2022-05-05T07:08:23-0500
KYLE E TANNER
MFE-D-ATCT-A010
-d -a tc t-a
FIRESTOPPING FLOWCHART
TYPE
ASSEMBLY
DETERMINE
WALL
GYPSUM
PENETRATION
FLOOR
CONCRETE
CONDUIT
METAL
PIPE
TRAY
CABLE
TUBES/PIPES
PVC DROP
DROP TUBES
POLYETHYLENE
NELSON
UL # C-AJ-1041
DETAIL # 3
COATINGS
PROTECTIVE
INTERNATIONAL
UL # C-AJ-1008
DETAIL # 2
MANUFACTURING
AND
MINNESOTA MINING
UL # C-AJ-1006
DETAIL # 1
HILTI
UL # C-AJ-4019
DETAIL # 5
UL # C-AJ-4002
DETAIL # 6
UL # C-AJ-4025
DETAIL # 4
UL # C-AJ-3004
DETAIL # 9
UL # C-AJ-3020
DETAIL # 8
UL # C-AJ-3021
DETAIL # 7
UL # C-AJ-2032
DETAIL # 12
UL # C-AJ-2001
DETAIL # 10
UL # C-AJ-2007
DETAIL # 11
ES-1547
SOLUTION
ENGINEERED
DETAIL # 13
CORP.
RECTORSEAL
C97-10-60B
DETAIL # 14
UL # W-L-1009
DETAIL # 15
UL # W-L-1005
DETAIL # 16
UL # W-L-1012
DETAIL # 17
UL # W-L-1009
DETAIL # 15
UL # W-L-1005
DETAIL # 16
UL # W-L-1012
DETAIL # 17
UL # W-L-4004
DETAIL # 18
UL # W-L-4009
DETAIL # 19
UL # W-L-3087
DETAIL # 20
GYPSUM
UNITED STATES
UL # W-L-3023
DETAIL # 21
UL # W-L-3047
DETAIL # 22
UL # W-L-2002
DETAIL # 23
UL # W-L-2086
DETAIL # 24
UL # W-L-2010
DETAIL # 25
ES-1548
DETAIL # 26
C97-10-60A
DETAIL # 27
ON SHEET A07
SEE DETAIL 1
TECHNOLOGY
SPECIFIED
UL # FA-3015
DETAIL # 3A
SEE DETAIL 2
UL # W-L-3218
DETAIL # 22A
DECISION TREE FOR UTILIZATION OF THROUGH PENETRATION FIRESTOP ASSEMBLIES
UL # C-AJ-3021
DETAIL # 7
UL # C-AJ-3020
DETAIL # 8
UL # C-AJ-3004
DETAIL # 9
UL # C-AJ-2032
DETAIL # 12
UL # C-AJ-2007
DETAIL # 11
UL # C-AJ-2001
DETAIL # 10
ES-1547
DETAIL # 13
C97-10-60B
DETAIL # 14
SEE DETAIL 3
UL # W-J-3098
DETAIL # 9A
TILE WALL
CMU/CLAY
GENERAL NOTES:
4.
3.
THE FACILITY.
FOR PROTECTING PENETRATIONS THROUGH WALL AND FLOOR/CEILING ASSEMBLIES IN
DETERMINING THE PROPER UL-LISTED THROUGH PENETRATION FIRESTOP ASSEMBLIES
THIS DECISION TREE IS PROVIDED TO GIVE GENERAL GUIDANCE TO CONTRACTORS IN
WITH UL DESIGN AND MANUFACTURER'S INSTALLATION INSTRUCTIONS.
THROUGH PENETRATION FIRESTOP ASSEMBLIES SHALL BE INSTALLED IN ACCORDANCE
IN THE FACILITY.
SUBMITTED TO THE RESIDENT ENGINEER FOR APPROVAL PRIOR TO INSTALLATION
FIRESTOP ASSEMBLIES, INCLUDING UL DESIGN NUMBER AND A DETAIL, SHALL BE
PENETRATING ITEMS FOUND IN THE FIELD. EQUIVALENT THROUGH PENETRATION
PENETRATION FIRESTOP ASSEMBLIES THAT ARE UL LISTED FOR USE WITH THE
FIELD. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING AND UTILIZING THROUGH
EXACT PENETRATING ITEMS OR QUANTITIES OF PENETRATING ITEMS FOUND IN THE
SOME CASES, THE ASSEMBLIES IDENTIFIED MAY NOT BE LISTED FOR THE USE WITH
CONSTITUTE THE ONLY ASSEMBLIES PERMITTED FOR USE WITHIN THE FACILITY. IN
DECISION TREE ARE PROVIDED AS EXAMPLES OF APPROVED ASSEMBLIES AND DO NOT
UL DESIGNS FOR THROUGH PENETRATION FIRESTOP ASSEMBLIES IDENTIFIED IN THE2.
1.
SEE SPECIFICATION SECTION 07 84 00 FOR FIRESTOPPING DETAIL DESCRIPTION.
-d -a tc t-a
:5 lo tt e mfe-d-atct-a010
2022-05-25T08:15:31-0500
WILLIAM C GRAY
2022-05-05T07:08:33-0500
KYLE E TANNER
MFE-D-ATCT-A011
-d -a tc t-a
FIRESTOPPING DETAILS
Section A-A
System No. F-A-3015
SPECIFIED TECHNOLOGIES INC - EZ PATH
120 or 129 Sealant, SpecSeal Putty
SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105, *Bearing the UL Classification Mark
1A 1B
System No. W-L-3218
Directory and shall incorporate the following construction features:
and in the manner described within the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance
1. Wall Assembly - The 1, 2, 3 or 4 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials
24 in. (610 mm) OC.
(51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in.
The hourly F Rating of the firestop system is dependent upon the hourly rating of the wall in which it is installed.
Opening in gypsum board to be max 1/4 in. (6 mm) larger then width and height dimensions of firestop device(s).
B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design.
device module and the cutout in the gypsum board may be filled with gypsum joint compound or fill material (Item 4).
1/8 in. (3.2 mm) gap between the firestop device module and the cutout in the gypsum board. Gap between the firestop device modules, the gypsum board shall be installed as specified in the individual U300 or U400 Design with a maximum steel wall plates shall be secured to the stud by means of steel screws. After installation of the steel wall plates and firestop 24 in. (406 and 610 mm) center-to-center stud spacing, respectively, prior to installation of the gypsum board layers. The As an alternate, the four- and seven-gang steel wall plates may be installed directly against the studs for walls having 16 and projecting an equal distance beyond each surface of the wall assembly.
of steel set screws provided with wall plates. Firestop device and extension module(s) assembly to be installed with ends with product. Steel wall plates installed on both sides of wall and secured to each device or extension module(s) by means (Item 2) and extension module(s) secured in place by means of steel wall plates installed with gasketing material supplied module to be installed in accordance with the accompanying installation instructions. When module is used, firestop device consists of a 3 by 3 by 6 in. (76 by 76 by 152 mm) long galv steel tube with an intumescent material lining. Extension 76 by 267 mm) long firestop device (Item 3) to increase its length to facilitate installation in thicker walls. Each module 2A. Firestop Device* - Extension Module - (Optional, Not Shown) - Module attached to ends of 3 by 3 by 10-1/2 in. (76 by
SPECIFIED TECHNOLOGIES INC - EZ PATH Extension supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
fill. Cable fill to be distributed at a uniform height across the width of the firestop device module. Cables to be rigidly
3. Cables - Within the loading area for each firestop device module, the cables may represent a 0 to 100 percent visual of the wall assembly when four- and seven-gang steel wall plates are installed directly against the wood or steel studs.
gap between the firestop device module and the cutout in the gypsum board may be sealed with fill material on each side
4. Fill, Void or Cavity Material* - Sealant or Putty 15/32 (Not Shown) - As an alternate to gypsum joint compound, the
SpecSeal LCI Sealant, SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105, 120 or 129 Sealant, 2 cfm at 400F.
3G or 3H is used, the L Rating for each firestop device module with 100 percent visual fill of cable is 7 cfm at ambient and for each firestop device module with 100 percent visual fill of cable is 4 cfm at ambient and 3 cfm at 400F. When Item 3F, cable is used or when Item 3F, 3G, 3H or 3I is used, the maximum F Rating is 4 hr. When Item 3A is used, the L Rating Item 3A, 3B, 3C, 3D or 3E is used, the maximum F Rating is 2 hr. When max 200 pair No. 24 AWG telecommunication is greater than 1 hr, the T Rating is 3/4 hr when Item 3A, 3B, 3C, 3D or 3E is used. Otherwise the T Rating is 1 hr. When When the hourly rating of the wall assembly is 1 hr, the T Rating is 3/4 hr. When the hourly fire rating of the wall assembly
L Rating At 400F - 2 or 3 cfm (See Item 3) L Rating At Ambient - 4 or 7 cfm (See Item 3)
T Ratings - 3/4 and 1 Hr (See Item 3) F Ratings - 1, 2, 3 and 4 Hr (See Items 1)
June 14, 2004 and insulation.
A. Max 25 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing
(16 mm).
D. Fiber optic cable with polyvinyl chloride PVC or polyethylene (PE) jacket and insulation having a max diam of 5/8 in.
C. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing.
and insulation.
B. Max four pair No. 22 AWG (or smaller) copper conductor data cable with polyvinyl chloride PVC or plenum rated jacketing
SpecSeal Putty
T Rating - 1/2 Hr
F Ratings - 4 Hr
February 27, 2003 of firestop device module(s).
kg/m3) concrete floor. Opening to be min 1/4 in. (6 mm) to max 1/2 in. (13 mm) larger than width and height dimensions
1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 the restraint plates are optional.
beyond each surface of the floor. As an option, devices may be cast into floor assembly. When device is cast in place, module(s) with steel set screws. Each firestop device module is to be installed with ends projecting an equal distance 1/2 in. (13 mm) on floor surface. Steel restraint plates installed on both sides of floor and secured to firestop device two, three, four or seven modules. Restraint plates provided with a closed cell silicone gasket and sized to lap approx (6 mm). Firestop device module(s) secured in place by means of steel restraint plates sized to accommodate either one, between the firestop device module(s) and the periphery of the opening shall be min 1/8 in. (3.2 mm) to max 1/4 in.
Firestop device modules to be installed in accordance with the accompanying installation instructions. The space module consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining.
2. Firestop Device* - One, two, three, four or seven firestop device modules ganged together. Each firestop device thickness of sealant or putty installed in annular space flush with top surface of floor.
3. Fill, Void or Cavity Material* - Sealant or Putty - Prior to installation of steel restraint plates, min 1 in. (25 mm) may be used:
be rigidly supported on both sides of the floor or wall assembly. Any combination of the following types of cables visual fill. Cable fill to be distributed at a uniform height across the width of each firestop device module. Cables to
4. Cables - Within the loading area for each firestop device module, the cables may represent a 0 to 100 percent rated insulation and jacketing.
B. Max 4 pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum polyvinyl chloride (PVC) insulation and jacketing.
A. Max 25 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with
SCALE: NONE
DETAIL
with ends projecting an equal distance beyond each surface of the wall assembly.
gypsum board layers and penetrate 1/2 in. (13 mm) into the framing member. Each firestop device module is to be installed Each four- and seven-gang steel wall plate shall be fastened to the studs with steel screws sized to extend through the wall plates installed on both sides of wall and secured to each device by means of steel set screws provided with device.
device module(s) secured in place by means of steel wall plates installed with gasketing material supplied with product. Steel device module(s) and the periphery of the opening shall be min 0 in. ( 0 mm, point contact) to max 1/8 in. (3.2 mm). Firestop device modules to be installed in accordance with the accompanying installation instructions. The space between the firestop consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop
2. Firestop Device* - One, two, three, four or seven firestop device modules ganged together. Each firestop device module
System No. W-J-3098
Directory for names of manufacturers.
See Concrete Blocks (CAZT) category in the Fire Resistance
L Rating At 400F - 2 or 3 cfm (See Item 3) L Rating At Ambient - 4 or 7 cfm (See Item 3)
T Ratings - 3/4 and 1 Hr (See Item 3) F Ratings - 4 Hr
June 14, 2004
B. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC with polyvinyl chloride (PVC) jacketing and insulation.
A. Max 25 pair No. 24 AWG (or smaller) copper conductor telecommunication cable and 2 scfm at 400F.
3B or 3C is used, the L Rating for each firestop device module with 100 percent visual fill of cable is 7 scfm at ambient each firestop device module with 100 percent visual fill of cable is 4 scfm at ambient and 3 scfm at 400F. When Item The T Rating is 3/4 hr. when item 3A is used. Otherwise the T Rating is 1 hr. When Item 3A is used, the L Rating for on both sides of the wall assembly. Any combination of the following types of cables may be used:
Cable fill to be distributed at a uniform height across the width of the firestop device module. Cables to be rigidly supported
3. Cables - Within the loading area for each firestop device module, the cables may represent a 0 to 100 percent visual fill.
SPECIFIED TECHNOLOGIES INC - EZ PATH Extension projecting an equal distance beyond each surface of the wall assembly.
of steel set screws provided with wall plates. Firestop device and extension module(s) assembly to be installed with ends with product. Steel wall plates installed on both sides of wall and secured to each device or extension module(s) by means (Item 2) and extension module(s) secured in place by means of steel wall plates installed with gasketing material supplied module to be installed in accordance with the accompanying installation instructions. When module is used, firestop device consists of a 3 by 3 by 6 in. (76 by 76 by 152 mm) long galv steel tube with an intumescent material lining. Extension 76 by 267 mm) long firestop device (Item 3) to increase its length to facilitate installation in thicker walls. Each module 2A. Firestop Device* - Extension Module - (Optional, Not Shown) - Module attached to ends of 3 by 3 by 10-1/2 in. (76 by steel wall plates are optional.
assembly. As an option, devices may be cast or grouted into wall assembly. When device is cast or grouted in place, the Each firestop device module is to be installed with ends projecting an equal distance beyond each surface of the wall wall plates installed on both sides of wall and secured to each device by means of steel set screws provided with device.
device module(s) secured in place by means of steel wall plates installed with gasketing material supplied with product. Steel device module(s) and the periphery of the opening shall be min 0 in. ( 0 mm, point contact) to max 1/8 in. (3.2 mm). Firestop device modules to be installed in accordance with the accompanying installation instructions. The space between the firestop consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop
2. Firestop Device* - One, two, three, four or seven firestop device modules ganged together. Each firestop device module larger than width and height dimensions of firestop device(s).
concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*. Opening to be max 1/4 in. (6 mm)
1. Wall Assembly - Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3 )
-d -a tc t-a
:0 lo tt e mfe-d-atct-a011
2022-05-25T08:15:55-0500
WILLIAM C GRAY
2022-05-05T07:08:42-0500
KYLE E TANNER
FIRST THROUGH THIRD FLOOR
TOWER FIRE ALARM PLAN
MFE-D-ATCT-F003
-d -a tc t-f0
3 3
FIRST FLOOR PLAN
SECOND FLOOR PLAN
THIRD FLOOR PLAN
CABLESDUCTS
DUCTS CABLES
GENERAL OFFICE
GENERAL AREA
MANAGER'S
SECRETARY'S
IL
CABLE PITDUCTS
CORRIDOR
STORAGE
GROUND
ELECTRICAL
PANEL RM.
ELECTRIC
SERVICE
TELEPHONE
-d -a tc lo tt e
NEW SMOKE DETECTOR
CABLE SHAFT
RELOCATE AND REPLACE HORN/STROBE FROM STAIRWELL INTO
NEW HORN/STROBE
OF STAIRWELL
RELOCATE AND REPLACE PULL STATION FROM INSIDE ROOM TO WALL
REPLACE ALL EXISTING DEVICES WITH NEW UNLESS OTHERWISE NOTED
AND SAIL SWITCH
MONITOR MODULES FOR INTAKE DAMPER OPEN AND CLOSED, STAIR FAN POWER,
CONTROL MODULES FOR INTAKE DAMPER OPERATION AND STAIR FAN OPERATION
MONITOR MODULE FOR 'STAIR FAN BACKUP POWER SYSTEM'
CM
MM
ID
L P
IO R
IO F
IO M
mfe-d-atct-f003
2022-05-25T08:16:10-0500
WILLIAM C GRAY
2022-05-05T07:08:53-0500
KYLE E TANNER
FOURTH FLOOR THROUGH CAB
MFE-D-ATCT-F004
-d -a tc
TOWER FIRE ALARM PLAN
11 2
FAAP
F F
JUNCTION ROOM
EXHAUST PLENUM
LOW ROOF
DUCTS
MECHANICAL EQUIPMENT
DN
FOURTH FLOOR PLAN FIFTH FLOOR PLAN
CAB FLOOR PLAN
-d -a tc
:2 lo tt e
UNLESS OTHERWISE NOTED
REPLACE ALL EXISTING DEVICES WITH NEW
CAB STAIR TO NEAR EXIT DOOR
RELOCATE AND REPLACE PULL STATION FROM
STROBE TO NEW LOCATION
REMOVE AND REPLACE FAAP AND RED LENS
FOR AHU SHUTDOWN
PROVIDE AND INSTALL NEW CONDUIT AND WIRING FOR CONTROL CIRCUIT
RELOCATE PULL STATION FROM INSIDE ROOM TO STAIRWELL WALL
CONTROL MODULE FOR DAMPER CONTROL
CONTROL MODULE AND RELAY FOR AHU SHUDOWN
mfe-d-atct-f004
2022-05-25T08:18:35-0500
WILLIAM C GRAY
2022-05-05T07:09:04-0500
KYLE E TANNER
MFE-D-ATCT-F005
-d -a tc
FIRE ALARM RISER DIAGRAM
-d -a tc
:3 lo tt e
RISER DIAGRAM
NOT TO SCALE
NOTES:
2.
K
FACP
W
CAB
DACT
IF
IR
IT
Y
NOTE 2
ISO
ISO CM
DESIGN CONDITIONS
THE ORDER, AND NUMBER OF DEVICES MAY CHANGE DO TO
RISER LAYOUT IS DIAGRAMATIC ONLY. ACTUAL LAYOUT,
CM CM
FIFTH FLOOR
FOURTH FLOOR
THIRD FLOOR
SECOND FLOOR
FIRST FLOOR, GROUND LEVEL
FIFTH FLOOR
FOURTH FLOOR
THIRD FLOOR
SECOND FLOOR
FIRST FLOOR, GROUND LEVEL
PROVIDE NEW POWER CIRCUIT AND BREAKER
ONE YEAR.
FAA TO EXTEND MONITORING SERVICE
THE DACT IS EXISTING, COORDINATE WITH
V-33 WITH RED LENS.
ARE SPACE-AGE ELECTRONICS
STROBES IN CAB AND TRACON
75 75
75 75
75 15
15 15
757575
1515 75
15 15 15
CM CM MM MM MM MM MM
mfe-d-atct-f005
2022-05-25T08:19:43-0500
WILLIAM C GRAY
2022-05-05T07:09:15-0500
KYLE E TANNER
MFE-D-ATCT-F006
-d -a tc
FIRE ALARM LEGEND AND DETAILS
Q W
SPACEN MBVCXZ
A S D F G H J K L
% : \ . I ?
Lower Case
Enter
Esc
Esc
POWER
FIRE ALARM
PRE-ALARM
SECURITY
SUPERVISORY
SYSTEM
OTHER
SIGNALS
POINT
CPU
SILENCED
FAILURE
DISABLED
TROUBLE
EVENT
RESET
FIRE ALARM
TROUBLE
OTHER EVENT
SUPERVISORY
DRILL
SILENCE
SIGNAL
ACKNOWLEDGE
SCROLL DISPLAY
HOLD 2 SEC.
SELECTION
SELECTION
PREVIOUS
NEXT
LAMP F1
DISABLE
TEST
SCREEN
ENABLE
SECURITY
CONTROLS
ACTIVE
BATTERY
LEVELS
F2
SYSTEM - NORMAL
CURRENT TIME CURRENT DATE
FACP
LEGEND
PRNT
MLTI
DH
LAMP TEST
DRILL
FIRE
BYPASS
RAP
DOOR HOLDER
NAC
ON/OFF
SF-1
X
EXIT
FIRE ALARM SYSTEM MATRIX OF OPERATION
TELEPHONE JACK
EXISTING FIREFIGHTER
ON FIRE DETECTION
ARROW LIGHTS BASED
DIRECTIONAL EXIT SIGN
ELECTROMAGNETIC DOOR HOLDER
HEAVY DUTY RELAY FOR AHU SHUTDOWN
ADDRESSABLE MONITOR MODULE
ADDRESSABLE CONTROL MODULE
ISOLATOR MODULE
MANUAL FIRE ALARM (PULL) STATION
DUCT SMOKE DETECTOR
UNDERFLOOR SMOKE DETECTOR - PHOTOELECTRIC
SMOKE DETECTOR - PHOTOELECTRIC
HEAT DETECTOR
(CEILING)
FIRE ALARM HORN STROBE UNIT
(WALL)
FIRE ALARM HORN STROBE UNIT
FIRE ALARM STROBE (CEILING)
FIRE ALARM STROBE (WALL)
INCANDESCENT
FIRE ALARM STROBE, RED,
FIRE ALARM PRINTER
MULTIPOINT GROUND
REMOTE ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
SAMPLE FIRE ALARM CONTROL PANEL 1
F001 NOT TO SCALE
SMOKE DETECTORS (TOWER)
SMOKE DETECTORS (TOWER SHAFT)
CAUSE REMARKS
RA - REMOTE ANNUNCIATOR
A/S - AUDIBLE/STROBE
(OPEN, SHORTS, OR GROUNDS)
FIRE ALARM SUPERVISION
SHUT DOWN RESPECTIVE AHU OR AHU'S
IZ
IZ
L L
E
CS - CENTRAL STATION
IM
MANUAL FIRE ALARM STATIONS (TOWER)
.A
K
R E S P E C
'S
L
FACP LOSS OF POWER (30 SEC DELAY)
STAIR FAN ITEM NOT FUNCTIONING PROPERLY
E
E
E
.A
SHUT DOWN STAIR PRESSURIZATION FANSTAIR PRESSURIZATION FAN (DD SMOKE)
AHU-1
AHU-2
DUCT DETECTOR
MULT
FD
DH
MULTIPOINT GROUND PLATE
FIRE DAMPER
FIRE SMOKE DAMPER
DOOR HOLDER
FSD
ALL AUTO
LAMP TEST
ACKNOWLEDGED
LOCAL
MANUAL
CLOSED
OPEN
AUTO
TROUBLE THEN MOVE
PULL SWITCH
TROUBLETHEN MOVE
NOTES:
SHUT DOWN ASSOCIATED AHU'S
FOR FIREFIGHTER SMOKE CONTROL STATION
PROVIDE ALL FUNCTIONS REQUIRED BY NFPA 92
DAMPER
SUPPLY
RELIEF
SMOKE DETECTOR (ELEVATOR LOBBY)
-d -a tc
:4 lo tt e mfe-d-atct-f006
2022-05-25T08:19:58-0500
WILLIAM C GRAY
2022-05-05T07:09:24-0500
KYLE E TANNER
COVERSHEET AND DRAWING INDEX
MFE-D-ATCT-G005
-d -a tc t-g
ED
DRAWING LIST
GENERAL
ARCHITECTURAL
FIRE PROTECTION
AVIA
TRAT
SI
NI
MCALLEN, TX
MCALLEN INTERNATIONAL AIRPORT
T OF TRANSPO
T A
OF
STATES
IT
TM
EN
CORR.
RADIO
PURPOSE
MULTI-
WELL
STAIR
CAB FLOOR
GROUND FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
EQUIPMENT
RADIO
MECH.
EQUIPMENT
5TH FL. LOW ROOF
MFE-D-ATCT-G006
MFE-D-ATCT-G005
MFE-D-ATCT-A011
MFE-D-ATCT-A010
MFE-D-ATCT-A009
MFE-D-ATCT-A008
MFE-D-ATCT-F006
MFE-D-ATCT-F005
MFE-D-ATCT-F004
MFE-D-ATCT-F003
MFE-D-ATCT-M006
COVER SHEET AND DRAWING INDEX
FIRESTOPPING DETAILS
FIRESTOPPING FLOWCHART
TOWER FLOOR PLAN, FOURTH FLOOR THROUGH CAB
TOWER FLOOR PLAN, FIRST THROUGH THIRD FLOOR
FIRE ALARM MATRIX OF OPERATIONS
FIRE ALARM RISER DIAGRAM
TOWER FIRE ALARM PLAN, FOURTH FLOOR THROUGH CAB
TOWER FIRE ALARM PLAN, FIRST THROUGH THIRD FLOOR
MECHANICAL DETAILS, STAIR PRESSURIZATION FAN DETAILS
-d -a tc t-g lo tt e mfe-d-atct-g005
2022-05-25T08:12:04-0500
WILLIAM C GRAY
2022-05-05T07:07:48-0500
KYLE E TANNER
MFE-D-ATCT-G006
-d -a tc t-g
ARCHITECTURE GENERAL NOTES
APPROVED BY THE FAA AND MUST USE FIRE RETARDANT TREATED MATERIALS.
USE OF ANY WOOD FRAMING, BLOCKING, NAILERS, PLYWOOD, ETC. MUST BE
WHEN DISTURBING THOSE AREAS.
PROVIDES EXACT LOCATIONS IF ACM EXISTS. USE FAA APPROVED METHODS
INSULATION, WALLS AND FLOORS MAY CONTAIN ACM. THE SPECIFICATION
WALLS.
PROVIDE DUST BARRIERS ON DOOR TO ROOMS IF FURRING OUT
EXISTING DEVICES.
WALLPAPERS ON WALLS AS NEEDED AFTER REMOVAL OF
DO NOT CUT ANY NEW OPENINGS IN FINISHED WALLS. REPLACE
OR DEVICES.
DAMAGED OR REQUIRED FOR INSTALLATION OF NEW CONDUIT
MATCH AND REPLACE EXISTING ACOUSTIC CEILING TILES WHERE
CABLES OR PLASTIC PIPE. AS-BUILT DRAWINGS TO SHOW ACTUAL LISTING.
SYSTEMS THAT INCLUDE NON-STANDARD OPENINGS AND OPENINGS WITH
PENETRATED. PROVIDE ENGINEERING JUDGEMENTS FOR ALL FIRESTOPPING
FIRESTOP ASSEMBLY FOR PENETRATING ITEM AND ASSEMBLY BEING
SHEET MFE-D-ATCT-A010 TO DETERMINE THE APPROPRIATE UL-LISTED
SUBCONTRACTOR SHALL REFER TO FIRESTOP ASSEMBLY FLOW CHART ON
ALL FIRE STOPPING SHALL ACHIEVE A MINIMUM 2-HOUR RATING.
7.
6.
5.
13.
12.
11.
10.
9.
8.
CONTRACTOR TO PROVIDE POWER TO ALL NEW MOTORIZED DAMPERS
INSTALL FIRE/SMOKE DAMPERS IN PLANE OF WALL AND FLOOR.
PROGRESS OF WORK WITH NEW INSULATION EQUIVALENT TO THE ORIGINAL.
REPLACE DUCT AND PIPE INSULATION REMOVED OR DAMAGED DURING THE
PROVEN TO BE FULLY OPERATIONAL AND USABLE.
SYSTEMS SHALL BE FINISHED, TESTED, BALANCED, ADJUSTED, AND
COMPLETE THE IMPROVEMENTS SHOWN ON THESE DRAWINGS. ALL
FULFILL ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS AND
IMPROVEMENTS ACCORDINGLY.
LOCATION OF DUCTWORK. COORDINATE INSTALLATION OF
IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE ACTUAL
DUCTWORK SHOWN IS EXISTING UNLESS OTHERWISE NOTED AND IT
SERVICE, INSPECT, AND REPAIR ALL DUCT-MOUNTED SMOKE DETECTORS.
ACCESSIBLE. ADD ALL NECESSARY ACCESS DOORS REQUIRED TO
ALL FIRE OR COMBINATION FIRE/SMOKE DAMPERS NOT OTHERWISE
PROVIDE AND INSTALL DUCT MOUNTED HINGED ACCESS DOORS FOR
EXISTING EQUIPMENT TO REMAIN.
PERFORM ALL WORK REQUIRED TO TIE IN NEW WORK TO
SHOWN OR SPECIFIED OTHERWISE.
EXISTING WORK IS TO REMAIN EXCEPT WHERE SPECIFICALLY
AND CLEARANCES AT BUILDING SITE PRIOR TO COMMENCING WORK.
ALL MATERIALS SHALL FIT THE SPACE AVAILABLE. VERIFY DIMENSIONS
MANUFACTURER'S RECOMMENDATIONS.
INSTALL EQUIPMENT AND MATERIALS IN COMPLIANCE WITH
NOTICE ARE REQUIRED.
BE RECONNECTED. PRIOR APPROVAL BY THE RE, AND 15 DAYS
OF EQUIPMENT OR BECAUSE OF BUILDING ALTERATIONS THEY SHALL
IN SERVICE ARE DISCONNECTED FOR THE REMOVAL OR RELOCATION
WHERE PIPES, CONTROL DEVICES AND WIRING WHICH ARE TO REMAIN
TO THE ATTENTION OF THE RESIDENT ENGINEER (RE).
ANY WORK. ANY CONFLICTS OR DISCREPANCIES SHALL BE BROUGHT
CONDITIONS SHOWN ON DRAWINGS PRIOR TO PROCEEDING WITH
CHECK AND VERIFY ALL MEASUREMENTS AND EXISTING
FIELD VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION.
ALL EXISTING EQUIPMENT AND DUCTWORK TO REMAIN IS SHOWN.
FOR CLARITY IN DEFINING THE WORK OF THIS CONTRACT. NOT
MECHANICAL NOTESGENERAL NOTES
13.
FIRE ALARM SYSTEM NOTES
RATED FIRE BARRIERS.
ROOMS, SHAFTS, AND CHASES ARE CONSIDERED TO BE 2-HOUR
ALL FLOORS AND WALLS AROUND ELECTRICAL AND MECHANICAL
AND LATCH
ADJUST ALL DOORS IN EGRESS STAIR TO PROPERLY CLOSE
PRESSURIZATION FAN RUNNING.
ADJUST ALL STAIRWELL DOORS TO LATCH WITH AND WITHOUT
ADJUST ALL CABLE CHASE DOORS TO CLOSE AND LATCH.
DURING CONSTRUCTION.
REPLACE CARPET AND CEILING TILES IF DAMAGED
AVAILABLE IN THIS FACILITY.
LOCATIONS. THERE IS NO TEMPORARY STORAGE SPACE
SHALL BE UNPACKED AND REPLACED IN THEIR ORIGINAL
COMPLETION OF WORK, ALL FURNISHINGS AND EQUIPMENT
PERFORM ALL WORK SHOWN ON THESE DRAWINGS. UPON
STORE FURNISHINGS AND EQUIPMENT AS REQUIRED TO
TEMPORARY STORAGE SPACE TO PACK, REMOVE AND
CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS AND
CONTRACT SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
HOLDERS, REMOTE DEVICE TRANSFORMERS, ETC. SEE
DAMPERS, LOUVERS, MOTORS, CONTROL PANELS, DOOR
COMPONENTS TO THE FIRE ALARM SYSTEM SUCH AS
NEW COMPONENTS AND RECONNECTION OF EXISTING
NECESSARY ITEMS ASSOCIATED WITH THE CONNECTION OF
CONDUIT, WIRE, BREAKERS, PULL BOXES, AND OTHER
CONTRACTOR SHALL FURNISH AND INSTALL ALL REQUIRED
DOCUMENTS AND MANUFACTURER'S RECOMMENDATIONS.
REFERENCED DOCUMENTS, FAA CRITERIA, CONTRACT
ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS,
SYSTEM(S) COMPONENTS INSTALLED ENTIRELY IN
SPECIFICATIONS IN EVERY RESPECT, RESULTING IN
ALL WORK SHALL BE PERFORMED PURSUANT TO THE
INFORMATION.
OF WORK, AND SPECIFICATIONS FOR ADDITIONAL
GENERAL AND SUPPLEMENTARY CONDITIONS, STATEMENT
DESIGN DOCUMENTS FOR THIS WORK. REFER TO THE
THESE DRAWINGS ARE NOT INTENDED TO BE THE ENTIRE
INITIATING ANY WORK.
SHOP DRAWINGS FOR GOVERNMENT APPROVAL PRIOR TO
OR INSTALLATION. CONTRACTOR IS REQUIRED TO PROVIDE
ARE NOT TO BE USED FOR MEASUREMENT, FABRICATION,
DESIGN DOCUMENTS ARE CONCEPTUAL IN NATURE AND
CONTRACT.
CONDITIONS AND DIMENSIONS PRIOR TO EXECUTION OF
CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
THE DRAWINGS IS TO BE CONSIDERED APPROXIMATE.
DO NOT SCALE DRAWINGS. ALL INFORMATION SHOWN ON
PRIOR TO COMMENCEMENT.
COMPONENTS ARE APPROXIMATE AND SHOULD BE VERIFIED
FIELD VERIFICATION. LOCATIONS SHOWN FOR EXISTING
ON A REVIEW OF THE EXISTING DOCUMENTS AND LIMITED
INFORMATION CONTAINED IN THESE DRAWINGS IS BASED
FOR AIRPORT TRAFFIC CONTROL TOWERS.
LIFE SAFETY CODE, AND 29 CFR 1920.60 ALTERNATIVE STANDARD
AIRPORT TO ACHIEVE COMPLIANCE WITH NFPA 101,
TRAFFIC CONTROL TOWER AT THE MCALLEN INTERNATIONAL
THE FIRE/LIFE SAFETY SYSTEMS OF THE AIRPORT
THE WORK REQUIRED FOR THIS PROJECT IS TO UPGRADE
1. CONTRACTOR IS TO FURNISH AND INSTALL ALL MATERIALS,
USED.
REQUIREMENTS.
ALL MATERIALS SHALL BE LISTED FOR USE IN UL CLASSIFIED
SYSTEM TO ACHIEVE THE SPECIFIED RATING. EACH MATERIAL
USED SHALL BE SUITABLE AND CLASSIFIED FOR THE
PENETRATIONS AND CONSTRUCTION FOR WHICH IT IS
THE STATEMENT OF WORK, AND DRAWINGS FOR TYPES AND
VARY WITH LOCATION. COORDINATE LOCATIONS SHOWN ON
THESE DRAWINGS WITH REQUIREMENTS IN SPECIFICATION
NOTED ON THE AS-BUILT DRAWINGS
THE SPECIFIC FIRESTOPPING ASSEMBLIES SHALL BE
FIRESTOPPING NOTES
DEVICES, ASSEMBLIES AND LABOR TO INSTALL FIRESTOPPING
WHERE SHOWN.
FIRESTOPPING TYPES AND REQUIREMENTS
SECTION 07 84 00.
REFER TO SPECIFICATION SECTION 07 84 00,
INSTALLATION TO CONTRACTING OFFICER FOR APPROVAL
SUBMIT PLAN TO PROTECT CABLES 4 WEEKS PRIOR TO
DOOR HOLD OPEN DEVICES MAY BE CONTROLLED BY A SINGLE RELAY
ALL TERMINATIONS SHALL USE TERMINAL STRIPS IN A MINIMUM 6"X6" BOX
SUPPLIED SMOKE TEST TUBE FROM GROUND LEVEL
ALL DETECTORS SHALL BE PLACED TO ALLOW TESTING WITH CONTRACTOR
INSTALL UNDERFLOOR DETECTORS DIRECTLY BELOW CEILING DETECTORS
INSTALL 4" X 4" DUCT ACCESS HATCHES FOR ALL NEW DUCT DETECTORS
DOCUMENTS.
WITH THE APPLICABLE CODES AND STANDARDS AND THE CONTRACT
NECESSARY FOR A COMPLETE AND FUNCTIONAL SYSTEM IN ACCORDANCE
OF PANELS, DEVICES, WIRING AND ALL ASSOCIATED EQUIPMENT AS
CONTRACTOR IS RESPONSIBLE FOR LOCATING THE APPROPRIATE NUMBER
SPECIFIC DEVICES, CIRCUITS AND PANELS WILL VARY BY MANUFACTURER.
INSTALLED. DIAGRAM SHOWS INTENT OF SYSTEM ARCHITECTURE ONLY.
SHOW THE ACTUAL NUMBER OF DEVICES OR CIRCUITS TO BE
THE FIRE ALARM DRAWINGS ARE SCHEMATIC AND DO NOT NECESSARILY
USE NFPA 170 SYMBOLS FOR FIRE ALARM SHOP DRAWINGS
JUNCTION BOXES/DEVICES WITH T-BARS.
CENTER OF TILE UNLESS OTHERWISE INDICATED. SUPPORT
ALL CEILING MOUNTED DEVICES SHALL BE LOCATED IN THE
CONCEALED IN WALLS. CONDUIT SHALL BE PAINTED TO MATCH
SUSPENDED CEILINGS SHALL BE RUN ABOVE THE CEILING OR
WITH SUSPENDED CEILINGS. CONDUIT IN AREAS WITH
TOWER AND BASE BUILDING WITH THE EXCEPTION OF AREAS
SURFACE MOUNTED CONDUIT IS ACCEPTABLE IN THE CONTROL
ALL NEW WIRING SHALL BE IN CONDUIT.
IMPLEMENT A FIRE WATCH.
SYSTEM IS DOWN FOR MORE THAN 2 HOURS, CONTRACTOR MUST
OPERATION WITH SHOP DRAWINGS SUBMITTAL. IF FIRE ALARM
CONTRACTOR TO SUBMIT PLAN TO KEEP FIRE ALARM SYSTEM IN
NFPA 72 - 2019 EDITION, NFPA 70 - 2020 EDITION.
INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF
MAY REUSE EXISTING CONDUIT AND WIRE WHERE FEASIBLE. THE ENTIRE
THE SPECIFICATIONS AND SHOWN ON THE DRAWINGS. CONTRACTOR
PROVIDE REPLACEMENT FIRE ALARM SYSTEM AS DESCRIBED IN
-d -a tc t-g lo tt e
12AM TO 6AM
FIRE ALARM HORN TESTING SHALL SHALL BE FROM
WORK IN THE CAB SHALL BE FROM 12AM TP 6AM
WORKING CONDITIONS
mfe-d-atct-g006
2022-05-25T08:12:22-0500
WILLIAM C GRAY
2022-05-05T07:08:02-0500
KYLE E TANNER
STAIR PRESSURIZATION FANS DETAILS
MECHANICAL DETAILS
MFE-D-ATCT-M006
-d -a tc
PHOTOHELIC
.20 .40 .60
.80
1.0
DWYER
8"
8 7/16"
STAIRWELL SIDE
M002
DETAIL - BAROMETRIC PRESSURE GAUGE/SWITCH PG-1
ED
SENS
COOLING CAP ENTERING
AIR F
LEAVING
AIR F
DB WB DB WB
MOTOR DATA
HP V PH HZ
ELECTRICAL HEATING COIL
KW MBH V PH HZ
MANUFACTURER AND MODEL NO.MARK LOCATION SERVES TYPE FLOW
AIR
SCFM
SP IN WG
EXTERNAL
TOTAL
MBH MBH
AIR HANDLING UNIT SCHEDULE
ACU-4
ACU-2
ACU-1
3RD FLOOR
TOWER CAB
TOWER CAB
ELECTRONIC
EQUIP. RM
VERTICAL
3,600
4,000
4,000
1.80
2.20
2.20
117.6
103.3
62.5
56.2
TRANE TWE120B3
DIMENSIONS
FACENECK
AIR DEVICE SCHEDULE
REMARKSCFM
SR-1 (2) TITUS 300 R *1800 X (2) 30 49 FT TOWER
MAX.
NC
PD
WG
PROTOTYPE
MARK TYPECFM
MOTOR
FAN SCHEDULE
IN.WG.
WHEEL
R P M
DRIVEDRIVE
HPHP
1ST FL IN-LINE 9501.0 B3600 1½
LOCATION SERVICE
ESP
HORIZONTAL
ARRANGEMENT
DIA.(IN)TYPE
CENTRIF 21
MOTOR
RPM VOLTS HERTZSPHASE
208 60 49 FT TOWER
REMARKSPROTOTYPE
UNIT
SUPPLY REGISTER
PRESSURIZE STAIR 1200 GREENHECK BSQ-180-15
LOUVER
MOTORIZED
HANGER RODS TO STRUCTURE
FLEXIBLE CONNECTION
2ND FLOOR
26 X 18 UP. SEE
FLOOR PLANS FOR
CONTINUATION
26 X 18
LINE OF
DOOR
FIRE RATED (2-HOUR) FAN
ENCLOSURE WITH ACCESS
DOOR
& DUCT
SHAFT
1ST FL.
DUCTWORK TO LOUVER
SF-1 3
ABOVE
2-HOUR RATED
ENCLOSURE FOR
DUCT TO SHAFT
24x18 (2)
0.11
RD-1 (1) 2520RELIEF DAMPER CD-36
M02
.35
MECH. ROOM
STAIR PRESSURIZATION FAN SECTION
THE ADJACENT AREAS BETWEEN 0.11" H2O AND 0.2" H2O.
TO ADJUST THE DIFFERENTIAL PRESSURE BETWEEN THE STAIRWELL AND
OF TOWER. HIGH PRESSURE TUBING IN STAIRWELL-OPENING. CONTRACTOR
0.20" WC AND CLOSE AT 0.11" WC LOW PRESSURE TUBING OUTSIDE
AND BUG PROTECTIONS, CONNECTED TO RELIEF DAMPER TO OPEN IT AT
DIFFERENTIAL PRESSURE GAUGE/SWITCH PG-1, WITH CLEAR PLASTIC TUBING
-d -a tc
:5 lo tt e
OUTSIDE
mfe-d-atct-m006
2022-05-25T08:36:02-0500
WILLIAM C GRAY
2022-05-05T07:09:36-0500
KYLE E TANNER
File details come from the government source that posted it. Updated .