The project encompasses architectural, structural, mechanical, and electrical systems for a facility renovation. Key scope items include: construction of a new compressor room with equipment relocation; expansion of existing roof walkways with aluminum grating and maintenance-free materials; installation of a certified horizontal lifeline system for fall protection using galvanized steel cable; construction of a sedimentation tank for wastewater treatment; installation of new compressed air, potable water, and discharge systems with multiple pumps and treatment equipment; roof waterproofing using TPO membrane; construction of structural steel support frames and concrete foundations; relocation of electrical panels and installation of new Panel #8; installation of fire alarm systems including Honeywell control panels and addressable detectors; lighting systems using LED luminaires; and comprehensive mechanical systems for stormwater, compressed air, potable water, and gray water management. The plans include detailed specifications for materials (structural steel per ASTM standards, concrete with f'c=280 kg/cm², PVC piping, stainless steel components), welding procedures referencing AWS standards, bolt specifications, and equipment schedules. Construction details, support structures, drain systems, valve installations, and safety systems are extensively documented across architectural, structural, mechanical, and electrical drawing sets with multiple cross-referenced sheets and detailed notes in both Spanish and English. The project appears to be a complete renovation of an existing incinerator facility with significant upgrades to operational and support systems.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ESCALA FECHA LAMINA
INDICADAS
e c o n s u l t struTel (506) 2290 4070
Fax (506) 2290 7122 Oficentro Alquimia, 100 m Sur de la Liga de la Caña La Uruca, San José, Costa Rica www.estru.com
CONTENIDO
PROYECTO :
MODIFICACION FECHA REVISO
E-01820
OGB--/--/--1
REMODELACION INCINERADOR
JUNIO 2026
INFORMACION REGISTRO PUBLICO
PROPIETARIO:
N° CATASTRO:
FOLIO REAL:
CORTE SUPREMA DE JUSTICIA
H-1096358-2006 213155-000
PODER JUDICIAL
-INDICE DE LAMINAS E INFORMACION GENERAL
-(SHEET INDEX AND GENERAL INFORMATION)
G0.1 e c o n s u l t struTel (506) 2290 4070 Fax (506) 2290 7122
Oficentro Alquimia, 100 m Sur de la Liga de la Caña
La Uruca, San José, Costa Rica www.estru.com
RESPONSABLES DE DISEÑO
ING. ORLANDO GEI BREALEY
G0.1-INDICE E INFORMACION GENERAL
(INDEX AND GENERAL INFORMATION)
G0.2-DETALLES E INFORMACION GENERAL
(GENERAL INFORMATION AND DETAILS)
G0.3-DETALLES E INFORMACION GENERAL
(GENERAL INFORMATION AND DETAILS)
G0.4-DETALLES E INFORMACION GENERAL
(GENERAL INFORMATION AND DETAILS)
G0.5-DETALLES E INFORMACION GENERAL
(GENERAL INFORMATION AND DETAILS)
GENERALES
(GENERAL)
A1.1-PLANTA ARQUITECTONICA EXISTENTE
(EXISTING ARCHITECTURAL PLAN)
A2.1-PLANTA ARQUITECTONICA REMODELADA
(REMODELED ARCHITECTURAL PLAN)
A5.1-PLANTA ARQUITECTONICA DE TECHOS
(ARCHITECTURAL ROOF PLAN)
ARQUITECTONICO
(ARCHITECTURAL)
INDICE DE LAMINAS
(SHEET INDEX)
LISTA DE MODIFICACIONES
(LIST OF MODIFICATIONS)
S2.1 - PLANTA DE TIPOLOGIA DE PAREDES EXISTENTE
(EXISTING WALL TYPOLOGY PLAN)
S2.2 - PLANTA DE TIPOLOGIA DE PAREDES REMODELADAS
(REMODELED WALL TYPOLOGY)
S2.3D -DETALLES ESTRUCTURALES
(ESTRUCTURAL DETAILS)
S2.4D -DETALLES ESTRUCTURALES
(ESTRUCTURAL DETAILS)
S2.5D -DETALLES ESTRUCTURALES
(ESTRUCTURAL DETAILS)
S2.6D -DETALLES ESTRUCTURALES
(ESTRUCTURAL DETAILS)
S5.1 - PLANTA DE TECHOS EXISTENTE
(EXISTING ROOF PLAN)
S5.2 - PLANTA ESTRUCTURAL DE TECHOS
(STRUCTURAL ROOF PLAN)
S5.3 - PLANTA ESTRUCTURAL DE TECHOS
(STRUCTURAL ROOF PLAN)
S5.4D - DETALLES ESTRUCTURALES DE TECHOS
(STRUCTURAL ROOF DETAILS)
S6.1 - SECCION GENERAL
(SECTION)
ESTRUCTURAL
(STRUCTURAL)
M1.1-PLANTA MECANICA SISTEMA DE AGUA PLUVIAL
(MECHANICAL PLAN STORMWATER SYSTEM)
M1.2-PLANTA MECANICA AIRE COMPRIMIDO
(MECHANICAL PLAN COMPRESSED AIR)
M1.3-PLANTA MECANICA DE AGUA POTABLE
(MECHANICAL DRINKABLE WATER PLAN)
M1.4-PLANTA MECANICA DE DESAGUE}
(DISCHARGE MECHANICAL PLAN)
M1.5D-DETALLES MECANICOS
(MECHANICAL DETAILS)
MECANICO
(MECHANICAL)
INDICE DE LAMINAS
(SHEET INDEX)
LISTA DE MODIFICACIONES
(LIST OF MODIFICATIONS)
E1.1 - PLANTA ELECTRICA DE ILUMINACION
(LIGHTING ELECTRICAL PLAN)
E1.2 - PLANTA ELECTRICA DE TOMACORRIENTES
(OUTLET ELECTRICAL PLAN)
E1.3 - PLANTA ELECTRICA DE INCENDIO
(ELECTRIC FIRE PLAN)
E1.4 - PLANTA ELECTRICA DE UBICACION DE PANELES
(ELECTRICAL PLAN FOR PANEL LOCATION)
E1.5 - PLANTA ELECTRICA DE REUBICACION DE PANELES
(ELECTRICAL PLAN FOR PANEL RELOCATION)
E1.6 - PLANTA ELECTRICA DE RECORRIDO DE TUBERIAS
(PIPELINE ROUTE POWER PLAN)
E1.7D - DETALLES ELECTRICOS
(ELECTRICAL DETAILS)
E1.8D - DETALLES ELECTRICOS
(ELECTRICAL DETAILS)
E1.9D - DISTRIBUCION DE TABLERO
(CABINET LAYOUT)
E1.10D - DIAGRAMAS ELECTRICOS
(ELECTRIC DIAGRAMS)
E1.11D - DIAGRAMAS ELECTRICOS
(ELECTRIC DIAGRAMS)
ELECTRICO
(ELECTRICAL)
e c o n s u l t struTel (506) 2290 4070
Fax (506) 2290 7122 Oficentro Alquimia, 100 m Sur de la Liga de la Caña La Uruca, San José, Costa Rica www.estru.com
CONTENIDO
PROYECTO :
MODIFICACION FECHA REVISO
E-01820
OGB--/--/--1
REMODELACION INCINERADOR
JUNIO 2026
INFORMACION REGISTRO PUBLICO
PROPIETARIO:
N° CATASTRO:
FOLIO REAL:
CORTE SUPREMA DE JUSTICIA
H-1096358-2006 213155-000
PODER JUDICIAL
-DETALLES E INFORMACION GENERAL
-(GENERAL INFORMATION AND DETAILS)
G0.2
ESPECIFICACION SOLDADURA
(SPECIFICATION WELDING)
TIPO DE PROCESO
(PROCESS TYPE)
GMAWSMAW
ER70S-XE6010
E7018SOLDADURA ESTRUCTURAL
(STRUCTURAL WELDING)
ER70T-6 ER70T-8
E6011 E6013
NOTAS GENERALES:
1. SE PUEDEN UTILIZAR LOS SIGUIENTES MÉTODOS DE SOLDADURA:
SOLDADURA DE ARCO SUMERGIDO (SMAW) O BIEN SOLDADURA
DE ARCO METALICO PROTEGIDO CON GAS (GMAW).
2. LOS PLANOS DE TALLER Y MONTAJE DEBERÁN INDICAR LAS SOLDADURAS
REQUERIDAS POR ESTOS PLANOS O SOLDADURAS ADICIONALES REQUERIDAS
POR ASPECTOS CONSTRUCTIVOS Y DEBERAN SER APROBADOS POR LA
INSPECCION.
3. PARA LA INSPECCION VISUAL DE LOS CORDONES DE SOLDADURA SE
ADOPTARAN LOS CRITERIOS DE LA NORMA AWS D1.1, D1.3 Y D1.8.
4. EN EL CASO DE CONEXIONES DE DEMANDA CRITICA O DONDE SE INDIQUE EN
PLANOS SE DEBERÁ REALIZAR PRUEBAS COMPLEMENTARIAS DE LIQUIDOS
PENETRANTES(PT), ULTRASONIDO (UT) O RADIOGRÁFICAS (RT) O PARTICULAS
MAGNETICAS (PM) O ALGUNA COMBINACIÓN DE ESTAS SEGUN SE DEFINA EN
PLANOS, ESPECIFICACIONES TECNICAS DEL PROCESO DE LICITACION O SI SE
SOLICITAN DURANTE EL PROCESO CONSTRUCTIVO.
5. TODO PROCESO DE SOLDADURA DEBE SER PRESENTADO EN FORMA DE WPS
(WELDING PROCEDURE SPECIFICATION) Y SE DEBERA SUBMITAR JUNTO CON LA
PRESENTACION DE LOS PLANOS DE TALLER.
6. LOS PLANOS DE TALLER DEBEN INDICAR EL PROCESO FINAL DE SOLDADURA QUE
SE VA A APLICAR.
7. TODOS LOS ELECTRODOS O INSUMOS DE SOLDADURA DE BAJO HIDROGENO
DEBEN MANTENERSE EN AMBIENTE CONTROLADO SIN HUMEDAD (USO DE
HORNOS PARA ELECTRODOS)
8. LA SUPERFICIE A SOLDAR DEBE LIMPIARSE DE ÓXIDO, GRASA, PINTURA Y
ESCALA DE MOLINO.
9. TODOS LOS BISELES, CORTES, RESPALDOS, AMPLITUD DE RAIZ DEBEN SEGUIR
LAS REOMENDACIONES DE AWS D1.1, D1.5 Ó D1.8 SEGUN CORRESPONDA
CON LAS TOLERANCIAS QUE INDIQUE EL PROCESO. SI EN PLANOS APARECE UNA
ANOTACIÓN QUE CONTRADIGA LO ESPECIFICADO EN AWS, RIGEN LOS PLANOS.
10. NINGUNA SOLDADURA PODRA SER RECUBIERTA, PULIDA A MAQUINA O
PINTADA HASTA NO SER APROBADA POR EL INSPECTOR, LA APROBACIÓN DEBE
CONSTAR EN BITACORA O CONSTAR EN UN INFORME DE ALGUNA EMPRESA DE
INSPECCIÓN ESPECIALIZADA SUBCONTRATADA POR PARTE DEL CLIENTE.
11. SE DEBEN CUMPLIR TODAS LAS LONGITUDES Y ESPESORES DE GARGANTA
EFECTIVOS QUE INDIQUE EL DETALLE DE PLANO DE TALLER.
CUALQUIER VARIACION AL PROCEDIMIENTO ORIGINAL DE SOLDADURA DEBE
SOMETERSE A VALIDACIÓN POR PARTE DEL INSPECTOR ESTRUCTURAL.
12. PARA SOLDADURA TIPO SMAW SE DEBEN SEGUIR LAS RECOMENDACIONES DE
SOLDADURA DEL FABRICANTE DEL ELECTRODO. DEBEN SOMETERSE A
APROBACIÓN DE LA INSPECCIÓN. COMO REFERENCIA SE INCLUYEN EN LA
TABLA SIGUIENTE ALGUNOS VALORES GENERALES RECOMENDADOS.
13. EL EQUIPO PARA REALIZAR SOLDADURA TIPO SMAW DEBE SER APROPIADO
PARA EL TIPO DE ELECTRODO Y ESTAR EN PERFECTAS CONDICIONES DE
MANTENIMIENTO, ASI COMO LOS ELECTRODOS EN PERFECTO ESTADO DE
CONSERVACIÓN.
14. TODO OPERARIO DE SOLDADURA DEBE CONTAR CON EL DEBIDO EQUIPO DE
PROTECCIÓN PARA MANOS, OJOS Y CABEZA. EN CASO DE SER TRABAJO EN
ALTURA DEBE ESTAR DEBIDAMENTE ASEGURADO A LAS LÍNEAS DE VIDA
PROVISTAS POR LA EMPRESA CONSTRUCTORA.
15. SE DEBE PRESENTAR LOS REGISTROS DE CALIFICACIÓN DE LOS SOLDADORES
RESPONSABLES DE LA OBRA.
16. SE DEBERÁ ELABORAR UNA HOJA DE TRABAJO CON UN REGISTRO TABULAR DE
LAS SOLDADURAS EJECUTADAS POR CADA SOLDADOR CON LA FINALIDAD DE
FACILITAR LA IDENTIFICACIÓN AL MOMENTO DE LA INSPECCIÓN
TIPO DE ACABADO
TIPO DE CONTORNO
BORDE DE LAS PIEZAS
ANCHO DE TAPON O
PROFUNDIDAD DE SUELDA
GARGANTA DE SUELDA
PROFUNDIDAD DE PREPARACION
LINEA DE REFERENCIA
REFERENCIA A ESPECIFICACION
COLA (SE OMITE SI NO HAY
REFERENCIA)
SIMBOLOGIA BASICA DE SUELDA
Y/O REFERIDO A DETALLE
LONGITUD DE SUELDA
ESPACIAMIENTO CENTRO A CEN-
TRO DE SUELDAS
SOLDADURA DE CAMPO
SOLDADURA TODO EL CONTORNO
SITIO DE SUELDA
NOTAS SOBRE ESTRUCTURAS METALICAS
(METAL STRUCTURES AND WELDING NOTES)
ESPECIFICACION DE MATERIALES
(MATERIALS SPECIFICATION)
ELEMENTO
(ELEMENT)
PERFIL W
(W PROFILE)
TUBOS HSS
(HSS PIPES)
PLATINAS
PLATES
ANGULARES
(ANGLES)
CANALES
(CHANNELS)
PERNOS
(BOLTS)
BARRAS DE ANCLAJE
(ANCHORAGE BARS)
RESISTENCIA
(RESISTANCE)
ESPECIFICACION
(SPECIFICATION)
fy = 3500 kg/cm2 fy = 3220 kg/cm2 fy = 2520 kg/cm2 fy = 2520 kg/cm2 fy = 2520 kg/cm2 fu = 10500 kg/cm2 fu = 8750 kg/cm2
ASTM A992
ASTM A500 Gr B
ASTM A36
ASTM A36
ASTM A 36
ASTM A490
ASTM F1554 Gr 105
LAMINADO EN FRIO (RT, TUBING, Z)
COLD ROLLED (RT, TUBING, Z)
fy = 2310 kg/cm2ASTM A1011-33
ESPECIFICACION SOLDADURA
(WELD SPECIFICATION)
TIPO DE PROCESO
(PROCESS TYPE)
SOLDADURA NO ESTRUCTURAL
(NO STRUCTURAL WELD)
GMAWSMAW
ER70S-XE6010
E7018SOLDADURA ESTRUCTURAL
(STRUCTURAL WELD)
ER70T-6 ER70T-8
E6011 E6013
RECOMENDACIONES PARA SOLDADURAS TIPO SMAW
(SMAW TYPE WELD RECOMMENDATIONS)
ELECTRODO
ELECTRODE
E6010
E6011
E6013
E7018
AMPERAJE RECOMENDADO
(RECOMMENDED AMPERAGE)
TIPO DE CORRIENTE
(CURRENT TYPE)
CD (+)
CDEN, CA
CDEP, CDEN, CA
CDEP, CA
2.4mm 50-90 3.2mm 80-120 4.0mm 120-160 4.8mm 140-220 2.4mm 40-70 3.2mm 70-100 4.0mm 100-140 4.8mm 140-220 2.4mm 60-100 3.2mm 90-140 4.0mm 150-190 4.8mm 180-240 2.4mm 65-90 3.2mm 100-140 4.0mm 140-190 4.8mm 180-250
FLECHA
AM
BO
S
LA
DO
S
(B O
TH
S
ID
ES
L T
N
SIMBOLOGIA PARA LA INDICACION DE
PROCEDIMIENTOS DE INSPECCION DE SOLDADURA
(SIMBOLOGY FOR WELDING INSPECTION
PROCEDURES INDICATION)
LA
DO
D E
LA
F
LE
CH
A (A
RR
O
W S
ID
E)
INSPECCION A TODO ALREDEDOR
3 INSPECCION EN CAMPO
4 LONGITUD A INSPECCIONAR
5 NUMERO DE ENSAYOS
6 LINEA DE BASE
7 ESPECIFICACION, NORMA O REFERENCIA
8 COLA
9 TIPO DE PRUEBA
(FINISH TYPE)
(CONTOUR TYPE)
(ELEMENT BORDER)
(PLUG WIDTH OR
WELD DEPTH)
(WELD THROAT)
(PREPARATION DEPTH)
(REFERENCE LINE)
(SPECIFICATION REFERENCE)
(TAIL (OMITTED IF
NO REFERENCE))
(BASIC WELD SYMBOLOGY
OR DETAIL REFERENCE)
(WELD LENGTH)
(WELD CENTRE TO CENTRE SPACEMEN)
(FIELD WELD)
(ALL AROUND WELD)
(WELD SITE)
B(E)
A
B T
F A
R
M M
S
S a
S
S a
S
S a
S
S a
S
S a
S
S a
S
S a
S
S a
S
S a
PERFILES NO ACEPTABLES
(UNACCEPTABLE PROFILES)
PERFILES DESEABLES
(DESIRABLE PROFILES)
CONCAVO
(CONCAVE)
CONVEXO
(CONVEX)
GARGANTA
INSUFICIENTE
(INSUFFICIENT
THROAT)
EXCESIVA
CONVEXIDAD
(EXCESSIVE
CONVEXITY)
PERFILES ACEPTABLES
(ACCEPTABLE PROFILES)
CONCAVO
(CONCAVE)
CONVEXO
(CONVEX)
EXCESIVA
SOCAVACION
(EXCESSIVE
UNDERCUT)
SOLAPADO
(OVERLAP)
INSUFICIENTES
MEDIDAS
(INSUFFICIENT
MEASUREMENTS)
SIMBOLOS SUPLEMENTARIOS DE SOLDADURA
(SUPPLEMENTARY WELD SYMBOLS)
TODO EL
CONTORNO
(ALL
AROUND)
SUELDA DE
CAMPO
(FIELD
WELD)
CONTORNO AL RAS
CONVEXO
(FLAT OR CONVEX
OUTLINE)
APOYO
(SUPPORT)
APOYO
(SUPPORT)
LOCALIZACION DE LOS ELEMENTOS
DEL SIMBOLO DE SOLDADURA
(WELD SYMBOL ELEMENTS LOCATION)
LADO
(SIDE)(F
LE
CH
A
LA
DO
(A
RR
O W
S
ID
E) (F
LE
CH
A
LA
DO
(A
RR
O W
S
ID
E)
(A M
BO
S
LA
DO
S) (B
O
TH
S
ID
ES
SIMBOLOGIA STANDARD PARA UNIONES SOLDADAS
(STANDARD SYMBOLOGY FOR WELDED JOINTS)
V U J
ATRAS
(BENEATH)
FILETE
(FILLET)
TAPON O RANURA
(PLUG OR SLOT) CUADRADA
(SQUARED)
BISEL
(BEVEL)
ACAMPANADA
(FLARE - V)
BISEL
ACAMPANADO
(FLARE - BEVEL)
RANURAS O PIEZAS A SER SOLDADAS
(OPENINGS OR PIECES BE WELDED)
LA
DO
D E
LA
F
LE
CH
A (A
RR
O
W S
ID
E)
AM
BO
S
LA
DO
S
(B O
TH
S
ID
ES
(ARROW)1
2 (ALL AROUND INSPECTION)
3 (FIELD INSPECTION)
4 (LENGTH TO BE INSPECTED)
5 (NUMBER OF TESTS)
6 (BASE LINE)
7 (SPECIFICATION, STANDARD OR REFERENCE)
8 (TAIL)
9 (TEST TYPE)
1. THE FOLLOWING WELDING METHODS MAY BE USED:
SUBMERGED ARC WELDING (SMAW) OR GAS PROTECTED METALLIC ARC WELDING
(GMAW).
2. THE WORKSHOP AND ASSEMBLY DRAWINGS MUST INDICATE THE WELDS
REQUIRED BY THESE DRAWINGS OR ADDITIONAL WELDS REQUIRED FOR
CONSTRUCTION ASPECTS AND MUST BE APPROVED BY THE INSPECTION.
3. FOR THE VISUAL INSPECTION OF THE WELDING BEADS, THE CRITERIA OF THE AWS
D1.1, D1.3 AND D1.8 STANDARD WILL BE ADOPTED.
4. IN THE CASE OF CRITICAL DEMAND CONNECTIONS OR WHERE INDICATED IN
DRAWINGS, COMPLEMENTARY TESTS OF PENETRANT LIQUIDS (PT), ULTRASOUND
TEST (UT), RADIOGRAPHIC TEST (RT), OR MAGNETIC PARTICLES (PM) SHOULD BE
PERFORMED, AS DEFINED IN DRAWINGS, TECHNICAL SPECIFICATIONS OF THE
BIDDING PROCESS OR IF REQUESTED DURING THE CONSTRUCTION PROCESS.
5. ALL WELDING PROCESS MUST BE PRESENTED IN THE FORM OF WPS (WELDING
PROCEDURE SPECIFICATION) AND MUST BE SUBMITTED TOGETHER WITH THE
PRESENTATION OF THE WORKSHOP DRAWINGS.
6. THE WORKSHOP DRAWINGS MUST INDICATE THE FINAL WELDING PROCESS TO BE
APPLIED.
7. ALL ELECTRODES OR LOW HYDROGEN WELDING SUPPLIES MUST BE KEPT IN A
CONTROLLED ENVIRONMENT WITHOUT HUMIDITY (USE OF OVENS FOR
ELECTRODES)
8. THE SURFACE TO BE WELDED MUST BE CLEANED OF RUST, GREASE, PAINT AND
MILL SCALE.
9. ALL BEVELS, CUTS, BACKS, ROOT WIDTH MUST FOLLOW AWS D1.1, D1.5 OR D1.8
RECOMMENDATIONS AS CORRESPONDING TO THE TOLERANCES INDICATED BY
THE PROCESS. IF ANNOTATION APPEARS IN THE PLANS THAT CONTRADICTS WHAT
IS SPECIFIED IN AWS, THE PLANS WILL BE PRIORIZED.
10. NO WELDING MAY BE COATED, MACHINE POLISHED OR PAINTED UNTIL
APPROVED BY THE INSPECTOR, THE APPROVAL MUST BE IN BITACORA OR
CONTAINED IN A REPORT FROM A SPECIALIZED INSPECTION COMPANY
SUBCONTRACTED BY THE CLIENT.
11. ALL EFFECTIVE THROAT LENGTHS AND THICKNESSES INDICATED IN THE
WORKSHOP DRAWING DETAIL MUST BE COMPLIED.
ANY VARIATION TO THE ORIGINAL WELDING PROCEDURE MUST BE SUBMITTED TO
VALIDATION BY THE STRUCTURAL INSPECTOR.
12. FOR SMAW WELDING, THE WELDING RECOMMENDATIONS OF THE ELECTRODE
MANUFACTURER MUST BE FOLLOWED. MUST BE SUBMITTED FOR APPROVAL
OF THE INSPECTION. AS A REFERENCE, SOME RECOMMENDED GENERAL VALUES ARE
INCLUDED IN THE FOLLOWING TABLE.
13. THE EQUIPMENT TO CARRY OUT SMAW TYPE WELDING MUST BE APPROPRIATE
FOR THE TYPE OF ELECTRODE AND BE IN PERFECT MAINTENANCE CONDITION, AS
WELL AS THE ELECTRODES IN PERFECT CONDITION OF CONSERVATION.
14. EVERY WELDING OPERATOR MUST HAVE THE PROPER PROTECTIVE EQUIPMENT
FOR HANDS, EYES AND HEAD. IN CASE OF BEING WORK AT HEIGHT, IT MUST BE
PROPERLY INSURED TO THE LIFELINES PROVIDED BY THE CONSTRUCTION
COMPANY.
15. THE QUALIFICATION RECORDS OF THE WELDERS RESPONSIBLE FOR THE WORK
MUST BE SUBMITTED.
16. A WORKSHEET MUST BE PREPARED WITH A TABULAR RECORD OF THE WELDS
EXECUTED BY EACH WELDER FOR THE PURPOSE OF FACILITATING IDENTIFICATION
AT THE TIME OF INSPECTION
SOLDADURA NO ESTRUCTURAL
(NO STRUCTURAL WELDING)
PROCESO DE INSTALACION DE PERNOS Y/O VARILLAS
(BOLTS AND STEEL BARS INSTALLATION PROCESS)
3 - LIMPIE EL AGUJERO CON UN EXTRACTOR DE POLVO O AGUA .EL
AGU-JERO PUEDE QUEDAR HUMEDO PERO NUNCA CON RESTOS DE AGUA.
DEBERA COMPROBARSE LA PROFUNDIDAD DEL HUECO DE MODO QUE
CUMPLA CON LO ESPECIFICADO PARA CADA VARILLA.
3- (DRILLED HOLES MUST BE CLEANED USING AN EXTRACTOR FOR DUST
AND/OR WATER. THE HOLE CAN REMAIN MOIST BUT NEVER WET. IT'S
DEPTH MUST BE VERIFIED TO COMPLY WITH THE SPECIFIED
MEASUREMENT FOR EACH BOLT SIZE.)
4 - UNA VEZ LIMPIO EL AGUJERO PARA EL PERNO SE DEBERA LLENAR DE
EPOXICO DEBIENDO GARANTIZAR. EL CONSTRUCTOR UNA PERFECTA Y TOTAL
APLICACION. POSTERIORMENTE SE DEBERA COLOCAR EL ACERO DE ANCLAJE Y
DEJAR EN REPOSO EL TIEMPO QUE SE ESPECIFICA SEGUN EL ADITIVO UTILIZADO.
4- (ONCE THE HOLE IS CLEANED, THE BOLT MUST BE FILLED WITH EPOXY IN
SUCH A WAY THAT A PERFECT AND COMPLETE APPLICATION IS GUARANTEED.
SUBSEQUENTLY, THE ANCHOR STEEL MUST BE PLACED AND ALLOWED TO SET
FOR THE SPECIFIED TIME ACCORDING TO MANUFACTURER'S INSTRUCTIONS)
2 - DEBE REALIZARSE UNA PERFORACION CON BROCA DE Ø TAL QUE SE
CUMPLA CON LAS ESPECIFICACIONES DE LOS DE LOS ADITIVOS
QUIMICOS U-TILIZADOS. NO DE PERMITIRAN EQUIPOS DE PERCUSION
EN LA PERFORACION. PARA EVITAR LA DESINTEGRACION DEL CONCRETO
EXISTENTE. TODAS LAS BRO-DEBERAN SER ROTATIVAS.
2- (A PERFORATION USING A BIT DIAMETER THAT COMPLIES WITH THE
CHEMICAL ADDITIVES USED MUST BE PERFORMED. PERCUSSION
EQUIPMENT WILL NO BE ALLOWED TO AVOID EXISTING CONCRETE
FRACTURE. ALL DRILL BITS MUST BE ROTARY.)
1- EN ELEMENTOS REFORZADOS SE DEBERA PRIMERAMENTE LOCALIZAR EL
REFUERZO UTILIZANDO PARA ESTO UN DETECTOR DE METALES TIPO
FERROSCAN DE HILTI O SIMILAR DE MANERA TAL QUE NINGUN AGUJERO
COINCIDA CON UNA VARILLA SUPERFICIAL QUE IMPIDA DARLE LA LONGITUD
DE EMPOTRAMIENTO ES-PECIFICADO A LA VARILLA
1-(IN REINFORCED CONCRETE ELEMENTS, STEEL REINFORCEMENT MUST BE
FIRST LOCATED USING A METAL DETECTOR (SUCH AS HILTI'S FERROSCAN), SO
THAT NO HOLE WILL MATCH A SHALLOW REBAR AND PREVENT THE SPECIFIED
INSTALLATION DEPTH TO BE REACHED.)
DIMENSIONES DE ELEMENTOS DE
SUJECION DE ALTA RESISTENCIA
MEDIDA
ANCHO DE
LLAVE F
ALTURA EN
H
LONGITUD
DE ROSCA
LARGO DEL
PERNO
A3
Y A4
P
ER
NO
S A5
TU
ER
CA ANCHO DE
LLAVE W
ALTURA EN
H
F4
A
RA
ND
EL
AS
CI
RC
UL
AR
ES
DIAMETRO NOMINAL
EXTERIOR OD
DIAMETRO NOMINAL
INTERIOR OD
MIN.
MAX.
TNCKNS.
T
DISTANCIA MINIMA
DE EXTREMIDAD E
DISTANCIA MINIMA
DE LADO A
MEDIDA THCKNS. T
F4
A
RA
ND
EL
AS
CU
AD
RA
DA
S
O
RE
CT
AN
GU
LA
RE
S
REDUCCION DE
GROSOR
DISTANCIA MINIMA
DE EXTREMIDAD E d a b c c, e
DIAMETRO NOMINAL DE PERNOS
12.7mm 15.88mm 19.05mm 25.4mm
22.22mm
7.94mm
25.4mm
17.46mm
22.22mm
12.30mm
26.98mm
13.49mm
2.46mm
4.49mm
11.11mm
11.11mm
44.45mm
7.94mm
26.98mm
9.99mm
31.17mm
22.22mm
26.98mm
14.28mm
33.33mm
17.46mm
3.98mm 3.09mm
4.49mm 4.49mm 4.49mm 4.49mm 4.49mm 4.49mm 4.49mm 4.49mm
3.09mm 3.95mm 3.95mm 3.95mm 3.95mm 3.95mm
14.28mm
44.45mm
7.94mm 7.94mm 7.94mm 7.94mm 7.94mm 7.94mm 7.94mm 7.94mm
14.28mm
31.75mm
11.90mm
34.25mm
25.4mm
31.75mm
18.65mm
37.30mm
20.63mm
44.45mm 44.45mm 44.45mm 57.15mm 57.15mm 57.15mm 57.15mm
16.66mm
16.66mm 19.84mm 22.22mm 25.4mm 27.78mm 30.56mm 49.21mm
19.84mm 22.22mm 25.4mm 27.78mm 30.56mm 49.21mm
22.22mm
11.11mm
12.89mm
38.1mm
28.57mm
36.51mm
21.82mm
44.45mm
23.81mm
41.28mm
15.47mm
44.45mm
31.75mm
41.28mm
25.00mm
50.8mm
34.92mm
28.57mm
46.03mm
31.75mm 34.92mm 38.10mm
50.8mm 62.76mm 60.33mm
17.46mm 19.84mm 21.09mm 60.33mm
50.8mm 50.8mm 57.15mm 57.15mm
38.1mm 41.27mm 44.45mm 47.63mm
46.03mm 50.8mm 55.56mm 60.33mm
28.17mm 30.95mm 34.13mm 37.30mm
57.15mm 63.5mm 69.85mm 76.20mm
31.75mm 34.93mm 41.28mm38.1mm d f a TOLERANCIA TAL COMO SE ESPECIFICA EN LA NORMA ASTM A325 Y A490.
b TOLERANCIA TAL COMO SE ESPECIFICA EN LA NORMA ASTM A563.
C ASTM F436 tolerancia arandela en:
-DIÁMETRO NOMINAL EXTERIOR -0.79mm;+0.79mm -DIÁMETRO NOMINAL DEL AGUJERO -0;0.79mm -PLANACIDAD: MÁX. DESVIACIÓN DE LA REGLA COLOCADA EN EL LADO DE CORTE NO DEBERÁ SOBREPASARSE. 0.254mm -CONCENTRICIDAD: CENTRO DEL AGUJERO AL DIÁMETRO EXTERIOR (DESVIACIÓN INDICADOR COMPLETO). 0.762mm -LA CABEZA DE LA TUERCA O TORNILLO NO PODRA PROSECTARSE SOBRE LA SUPERFIE DE LA ARANDELAADYACENTE MAS DE 0.254mm.
d SOLO PARA RECORTAR LAS ARANDELAS.
e PARA SU USO CON VIGAS DE AMERICAN STANDARD (S) Y LOS CANALES (C) f VALOR DE TABLA NO INCLUYE EL ESPESOR DE LAS ARANDELAS.
F H LARGO DEL PERNO H W
O .D
E
I.D O .D
I.D
E
A
A
T
T
2:12 2:12 2:12 2:12 2:12 2:12 2:12 2:12 2:12 d
B
(ABBREVIATION)
D
LT
R
LG
LD
H
ABREVIATURA
NOMENCLATURA
(NOMENCLATURE)
DESCRIPCION
(DESCRIPTION)
DIMENSION DE COLUMNAS SEGUN DISEÑO
(COLUMN DIMENSION ACCORDING TO DESIGN)
EFFECTIVE BEAM HEIGHT
(PERALTE EFECTIVO DE VIGA)
BAR DIAMETER ACCORDING TO TABLE
(DIAMETRO DE VARILLA SEGUN TABLA)
LONGITUD DE TRASLAPE SEGUN TABLA
(SPLICE LENGTH ACCORDING TO TABLE)
RADIO DE DOBLEZ SEGUN TABLA
(BENDING RADIO ACCORDING TO TABLE)
LONGITUD DE GANCHO EN AROS SEGUN TABLA
(STIRRUP HOOK LENGTH ACCORDING TO TABLE)
LONGITUD DE DOBLEZ EN REFUERZO LONGITUDINAL SEGUN TABLA
(BENDING LENGTH IN LONGITUDINAL REINFORCEMENT ACCORDING
TO TABLE)
NIVEL DE PISO TERMINADO
(FINISHED FLOOR LEVEL)
NIVEL INFERIOR DE CERCHA
(TRUSS BOTTOM LEVEL)
NIVEL SUPERIOR DE CERCHA
(TRUSS TOP LEVEL)
NIVEL SUPERIOR DE TAPICHEL
(BOND BEAM TOP LEVEL)
ZONA DE CONFINAMIENTO
CONFINEMENT ZONE
LONGITUD ZONA DE CONFINAMIENTO
(CONFINEMENT ZONE LENGTH)
NIVEL CIELO TERMINADO
(CEILING FINISHED LEVEL)
LONGITUD LIBRE DE COLUMNA
(FREE LENGTH IN COLUMN)
NIVEL SUPERIOR DE VIGA
(BEAM TOP LEVEL)
NCT
(CFL)
HZC
(CZL)
ZC
(CZ)
NST
(BBTL)
NSC
(TTL)
NIC
(TBL)
NSV
(BTL)
NPT
(FFL)
CABLE DE ACERO GALVANIZADO
CABLE DE ACERO GALVANIZADO CON ALMA DE
CABLE INDEPENDIENTE (I.W.R.C.), CONFIGURACIÓN
DE 6 TORONES X 25 ALAMBRES
3/8 0.26 7.55
DIAMETRO
(PULG.)
PESO
(LBS)
RESISTENCIA A
LA RUPTURA
(TON)
1 1.85 51.70
GUARDACABOS PARA CABLE
GUAEDACABOS PARA CABLE DE ACERO DE ALTA RESISTENCIA, GALVANIZADO POR
INMERSIÓN EN CALIENTE
SEGÚN ESPECIFICACIÓN FEDERAL FF-276 TIPO 3
1/2 0.51
A
TAMAÑO
(PULG.)
PESO
(LBS)
DIMENSIONES
(PULG.)
B C D E F G H
3.54 2.60 2.63 1.46 0.84 0.53 0.15 0.48
A
B
6.6
H
G
D C
F E
ABRAZADERAS PARA CABLE
ABRAZADERAS PARA CABLE DE ACERO MALEABLE , ELECTROGALVANIZADO /
ZINCADO
SEGÚN ESPECIFICACIÓN FEDERAL FF-C-450 TIPO 1, CLASE 2
3/4 0.84
A
TAMAÑO
(PULG.)
PESO
(LBS)
DIMENSIONES
(PULG.)
B C D E F G
3/4 1.26 1.65 0.56 1.33 2.40 2.70
G
A
F
E
B D
C
TENSORES "JAW & EYE"
GALVANIZADOS POR INMERCIÓN EN CALIENTE
SEGÚN ESPECIFICACIÓN FEDERAL FF-T791, TIPO 1, FORMA 1, CLASE 8 Y ASTM F-1145
1/2 x 6 2.200
A
DIAMETRO
ROSCA
TENSORA
(PULG.)
LIMITE CARGA
TRABAJO
(PULG.)
DIMENSIONES
(PULG.)
B E G J K M
0.50 0.68 2.75 1.06 18.29 12.29 19.48
N
13.48
R
1.44
S
0.72
X
3.231.53
PESO POR
PIEZA
(LBS)
CERRADO ABIERTO CERRADO ABIERTO CERRADO
BB
6.00
1.
J ABIERTO
K CERRADO
31.35
E CERRADO X CERRADO
BB
B G R
2 x 24 37.000 2.00 2.62 11.86 3.69 72.62 48.62 77.95 53.95 5.75 2.96 13.0989.00 24.00
Nº PIEZA
HDT12
Nº PIEZA
EGC34
Nº PIEZA
HG12X6JE
HG2X24JE
e c o n s u l t struTel (506) 2290 4070
Fax (506) 2290 7122 Oficentro Alquimia, 100 m Sur de la Liga de la Caña La Uruca, San José, Costa Rica www.estru.com
CONTENIDO
PROYECTO :
MODIFICACION FECHA REVISO
E-01820
OGB--/--/--1
REMODELACION INCINERADOR
JUNIO 2026
INFORMACION REGISTRO PUBLICO
PROPIETARIO:
N° CATASTRO:
FOLIO REAL:
CORTE SUPREMA DE JUSTICIA
H-1096358-2006 213155-000
PODER JUDICIAL
-DETALLES E INFORMACION GENERAL
-(GENERAL INFORMATION AND DETAILS)
G0.3
TABLA 3.3 DIMENSIONES DE AGUJERO NOMINAL ,cm
DIAMETRO
DE PERNO
NOMINAL ESTANDAR
(Dia.)
SOBRETAMAÑO
(Dia.)
RANURA CORTA
(ANCHOXLARGO)
RANURA LARGA
(ANCHOXLARGO)
1,27 cm
1,59 cm
1,91 cm
2,22 cm
2,54 cm
≥ 2,86 cm
1,43 cm
1,75 cm
2,06 cm
2,38 cm
2,7 cm d + 0,16 cm
1,59 cm
2,06 cm
2,38 cm
2,7 cm
3,18 cm d + 0,79 cm
1,43 cm x 1,75 cm
1,75 cm x 2,22 cm
2,06 cm x 2,54 cm
2,38 cm x 1,32 cm
2,7 cm x 3,33 cm
(d + 0,16 cm) x (d + 0,95 cm)
1,43 cm x 3,18 cm
1,75 cm x 3,97 cm
2,06 cm x 4,76 cm
2,38 cm x 5,56 cm
2,7 cm x 6,35 cm
(d +0,16 cm) x (2,5 x d )
TABLA 8.2. ROTACION DE TUERCAS A PARTIR DE LA CONDICION "SNUG-TIGHT" PARA
PRETENSADO TIPO "TURN-OF-NUT"
LONGITUD
DE PERNO
DISPOSICION DE LA CARA EXTERIOR DE LAS PARTES APERNADAS
AMBAS CARAS
PERPENDICULARES AL
EJE DEL PERNO
UNA CARA PERPENDICULAR
AL EJE DEL PERNO, LA OTRA
INCLINADA NO MAS DE 1:20
AMBAS CARAS INCLINADAS
NO MAS DE 1:20 DESDE EL
EJE DEL PERNO
a,b c d d
MENORES
A 4db
ENTRE 4d Y 8db b
ENTRE 8d Y 12db b
1/3 DE VUELTA
1/2 DE VUELTA
2/3 DE VUELTA
1/2 DE VUELTA
2/3 DE VUELTA
5/6 DE VUELTA
2/3 DE VUELTA
5/6 DE VUELTA
1 VUELTA
a: LA ROTACION DE LA TUERCA ES RELATIVA AL PERNO, SIN IMPORTAR CUAL SEA EL ELEMENTO
QUE SE ESTA ROTANDO (TUERCA O PERNO). PARA TODAS LAS ROTACIONES DE TUERCA
REQUERIDAS, LA TOLERANCIA ES +60° (1 / 6 DE VUELTA) Y -30°.
b: APLICA SOLAMENTE PARA UNIONES EN LAS CUALES TODO EL MATERIAL ES DE ACERO.
c: CUANDO LA LONGITUD DEL PERNO EXCEDE 12d , LA ROTACION DE LA TUERCA REQUERIDA SE
DEBERÁ DETERMINAR MEDIANTE ENSAYOS CON UN ADECUADO CALIBRADOR DE TENSION.
d: ARANDELAS BISELADAS NO INCLUIDAS.
b a: LA TOLERANCIA SUPERIOR EN LAS DIMENSIONES NOMINALES TABULADAS NO DEBERÁ EXCEDER 0.8 cm. EXCEPCIÓN:
EN EL ANCHO DE AGUJEROS DE RANURA, GUBIADOS DE MENOS DE 0,16 cm DE PROFUNDIDAD ESTÁN PERMITIDOS.
b: LOS AGUJEROS LIGERAMENTE CÓNICOS QUE NATURALMENTE RESULTAN DE PROCESOS DE PUNZONADO CON
PERFORADORAS Y MOLDES ADECUADOS SON ACEPTABLES.
b b b b b b
BOLT INSTALLATION
ALL BOLTS TO BE PROVIDED ON SITE. THEY MUST ENTER PACKAGED AND PROPERLY
PROTECTED FROM THE ENVIRONMENT.
BEFORE PLACING ANY BOLT, THE ENTIRE SURFACE MUST BE GREASED AND THE
PRETENSION INDICATED IN THE TABLES SUPPLIED IN THESE
DRAWINGS OR PROVIDED BY THE MANUFACTURER MUST BE APPLIED. IT IS NOTED THAT
THE VALUES WHICH CORRELATES TORQUE WITH PRETENSION ARE SUGGESTED BUT MAY
NOT CORRESPOND TO THE REALITY OF THE SPECIFIC ASSEMBLY, THEREFORE THE
CONTRACTOR MUST ALWAYS VERIFY THAT THE MINIMUM PRETENSION IS REACHED
WITH THAT TORQUE VALUE OR MAKE THE CORRESPONDING CORRECTIONS.
THE STRIPPING SEQUENCE OF THE BOLTS MUST BE SUCH THAT IT DOES NOT CAUSE
OTHER BOLTS TO LOOSEN OR INCUR IN NON-TOLERABLE OVER EXTRACTS. A STRICT
ORDER MUST BE FOLLOWED IN THE BOLT TIGHTENING PROCESS.
BOLTS BENT, FRACTURED, WITH NOTORIOUS DENTS, WEAR ON THE THREADS, CANNOT
BE INSTALLED.
HOLE SIZES AND ALIGNMENT MUST BE ACCORDING TO PLANS, IF FOR ANY REASON
THERE WAS NO COINCIDENCE IN THE ASSEMBLY OF THE PARTS THE STRUCTURAL
INSPECTION MUST BE CONSULTED TO DEFINETHE CORRECTION TO APPLY.
THE NUTS AND WASHERS MUST COMPLY WITH THE CORRESPONDING STANDARDS AND
MANUFACTURER'S CERTIFICATES MUST BE PROVIDED FOR PROOF.
THE ATTACHED TABLE INDICATES THE TYPE OF SOCKET REQUIRED IN BOLTS TO ENSURE
AN ADEQUATE PRETENSION OF THEM.
SPLICES AND HOLES
WITH THE INTENTION OF MAXIMUM USE OF THE MATERIALS, WELDED JOINTS WILL BE
ACCEPTED (FULL PENETRATION WELDING) WITH PIECES OF AT LEAST 6m LENGTH (IN PIECES LESS THAN 6m, JOINTS WILL NOT BE ACCEPTED).
JOINTS SHOULD NOT BE LOCATED IN HIGH DEMAND AREAS AT THE TIME.
THE BOLT HOLES WILL BE MADE WITH MECHANICAL MEANS AND WILL NOT BE ALLOWED
TO BE MADE WITH TORCH OR PUNCHES. FOR THE SIZING OF THE HOLES IT IS ALLOWED
TO USE A STANDARD HOLE IN THE STRUCTURAL ELEMENT AND AN OVERSIZED HOLE
ACCORDING TO TABLE J.3.3 OF THE AISC 360-16 FOR CONNECTION PLATES.
IT IS NOT ALLOWED TO SUBSTITUTE BOLTS FOR PLUG WELDS.
IN CASE THE HOLES ON ONE PART DO NOT COINCIDE WITH ANOTHER PART IT MUST BE
SUBMITTED TO A REVIEW BY THE STRUCTURAL INSPECTOR TO DEFINE THE CORRECTIVE
PROCEDURE.
CUTS
MECHANICAL OR THERMAL METHODS ARE ALLOWED FOR CUTS IN METAL. CUTS
USING TORCHES OR BURNING BY MEANS OF ELECTRODES ARE STRICTLY PROHIBITED.
TOLERANCES IN THE CUTS COMPARED TO THE DRAWING MEASURES SHOULD BE
DETAILED IN WORKSHOP PLANS AND COMPLIED WITH DURING WORK EXECUTION.
PAINTING
THE MANUFACTURED PARTS AND ELEMENTS MUST BE CLEANED FOLLOWING AT
LEAST PROCEDURE SP1 AND SP2 OF THE SSPC MANUAL. (SEE TABLE 2.7 OF THE AISC S
TEEL CONSTRUCTION MANUAL).
AT LEAST 2 LAYERS, OR AT LEAST 50 MICRONS OF THICKNESS (TOTAL 4MILS), OF
DIFFERENT COLORED ANTI-CORROSIVE PAINT SHOULD BE PLACED. FOR THE FINAL
FINISH, A LAYER OF DIFFERENT COLOR OF AT LEAST 50 MICRONS OF THICKNESS (2
MILS) IS RECOMMENDED. GALVANIZED PROFILES NEED ANTI-CORROSIVE PAINT ONLY
IN UNIONS THAT HAVE BEEN WELDED.
THE LAST PAINT LAYER WILL BE APPLIED ONCE THE STRUCTURE ASSEMBLY IS
CONCLUDED, IN ORDER TO CORRECT SCRATCHED PARTS OR PAINT DEFECTS. THIS
PROCEDURE APPLIES TO ALL METAL COMPONENTS.
NO WELDED CONNECTION SHOULD BE PAINTED, BEFORE WELDING OR AFTER
WELDING,UNTIL THE VISUAL INSPECTION PROCESSES HAVE BEEN CONCLUDED. IT IS
RECOMMENDED TO ELIMINATE THE PAINTING OF A STRIPE OF AT LEAST 5CM TO EACH
SIDE OF THE CENTER OF THE SEAM TO BE WELDED.
IF THE PARTS TO BE PAINTED HAVE A TUBULAR SHAPE AND WILL BE SEALED AT THEIR
ENDS, THEY MUST BE PAINTED ONLY ON THE FACE EXPOSED TO THE WEATHER. IF THEY
ARE OPEN ENDED, PAINT MUST BE PLACED THROUGHOUT THE INTERNAL AND
EXTERNAL SURFACE, OTHERWISE ANY DIFFERENT CORROSION PROTECTION SYSTEM
MAY BE USED.
WORKSHOP MANUFACTURING:
PRIOR TO THE BEGINNING OF THE MANUFACTURING, THE CONTRACTOR MUST SUBMIT
FOR APPROVAL THE WORKSHOP AND ASSEMBLY DRAWINGS OF THE METALLIC
STRUCTURE. AS A MINIMUM, THE FOLLOWING MUST BE INDICATED:
WORKSHOP PLANS
1. ELEMENT CODING PLANTS.
2. GENERAL GEOMETRY.
3. UNION DETAILS.
4. INDICATION OF PREPARATION OF MATERIALS AND SURFACES.
5. FINISHES IN WORKSHOP AND ON SITE.
6. INDICATION OF FINISHED PIECE AND ITS DETAILS OF UNION WITH CONTIGUOUS
ELEMENTS AND / OR SUPPORT DETAILS.
7. INDICATION OF WELDING TYPE AND LENGTH.
8. DETAILS OF THE LIFTING POINTS.
9. SPLICE DETAILS.
10. DIMENSIONAL TOLERANCES OF THE PARTS, CONSIDERING THE ASSEMBLY.
ASSEMBLY DRAWINGS
1. CODIFICATION OF ELEMENTS.
2. CONDITIONS OF HANDLING, STOCKING AND ASSEMBLY.
3. DETAILS AND LOCATION OF PLATES AND INSERTS ON THE SITE, IN ORDER TO RECEIVE
THE PREFABRICATED STRUCTURE.
4. DETAILS OF TEMPORARY AND FINAL UNIONS.
5. TEMPORARY AND FINAL SUPPORT DETAILS.
6. PERMANENT AND PROVISIONAL DEFORMATION CONTROL.
7. MILL CERTIFICATES OF ALL METAL PARTS, BOLTS, ANCHOR BARS, WELDING
CONSUMABLES, PAINTS.
8. WELDING PROCEDURES FOR ALL CONNECTIONS (WPS)
9. WELDING QUALIFICATION RECORD ACCORDING TO AWS APPLICABLE STANDARD.
10. BOLT INSTALLATION PROCEDURE.
INSPECCION DE SOLDADURA Y CONEXIONES APERNADAS
WELDED CONNECTIONS
WELDING INSPECTION IS MANDATORY. IT IS OBLIGATORY TO HAVE CONTINUOUS INSPECTION BY
THE MANUFACTURERS OF QUALITY CONTROL OF THE MANUFACTURER AND REGULAR
INSPECTION BY THE PERSONS IN CHARGE OF THE QUALITY ASSURANCE. IN AISC 360-16 CHAPTER
N AND AISC 341-16 CHAPTER J, THE RESPONSIBILITIES OF EACH PARTY AND THE SCOPE OF
INSPECTIONS ARE ESTABLISHED.
IT IS THE OBLIGATION OF THE CONTRACTOR TO DELIVER A FULL REPORT OF FIELD APPROVAL IN
THE FIELD OF THE EXECUTION OF ALL WPS PREVIOUSLY DESIGNED AND APPROVED BY THE
STRUCTURAL INSPECTION.
A VISUAL INSPECTION MUST BE PERFORMED TO IDENTIFY AND CORRECT DEFECTS AS SET OUT IN
AWS D1.1 TABLE 6.1.
COMPLEMENTARY NON-DESTRUCTIVE TESTS MUST BE PERFORMED AS REQUESTED BY THE COSTA
RICAN SEISMIC CODE IN CHAPTER 10.9, WHERE THESE PLANS, TECHNICAL SPECIFICATIONS,
DOCUMENTS OF THE BIDDING DOCUMENTS OR AS REQUIRED BY THE CLIENT.
WHERE INSPECTION WITH PENETRANT LIQUIDS (PT) OR MAGNETIC PARTICLES (MT) IS REQUIRED, ALL SURFACES TO BE INSPECTED SHOULD BE FREE OF PAINTING. MECHANICAL POLISHING OF THE ELEMENT SURFACE IS PROHIBITED, EXCEPT WHEN USING WIRE BRUSHES. CLEANING WILL BE TO
ELIMINATE SCOUR.
WELDS THAT REQUIRE ULTRASONIC TESTS MUST BE CARRIED OUT AT AN APPROPRIATE MOMENT
IN SUCH A WAY THAT IT CAN BE ACCESSED WITH THE EQUIPMENT. THE PHYSICAL SPACE MUST
ALLOW THE PERFORMANCE OF THE TEST.
ALL EQUIPMENT TO BE USED IN NON-DESTRUCTIVE TESTS MUST HAVE FACTORY CALIBRATION
CERTIFICATE AND STANDARDIZED WITH STANDARD BLOCKS THAT CORRESPOND ACCORDING TO
THE SPECIFICATION REQUESTED IN PLANS AND SPECIFICATIONS. THE AWS D1.1 STANDARD MUST BE USED IF PLANS OR SPECIFICATIONS DO NOT INDICATE THE PROCEDURE TO BE PERFORMED.
THE ACCEPTANCE OR REJECTION CRITERIA ARE THOSE PROVIDED FOR IN THE RULES THAT
INDICATE THE DRAWINGS AND SPECIFICATIONS OR, FAILING THIS, THE CRITERIA ESTABLISHED IN
AWS D1.1 WILL BE USED.
THE COMPANY THAT PROVIDES THE TESTS MUST HAVE QUALIFIED TECHNICIANS AND SHOULD
PROVIDE THE INSPECTOR WITH THE COMPANY'S WRITTEN PRACTICE MANUAL, WHICH DESCRIBES
THE TYPE OF TESTS, THE METHODOLOGY TO PERFORM THEM AND OTHER HANDLING
PROCEDURES, PRESENTATION AND PROTECTION PROCEDURES. THE REPORTS MUST BE ADAPTED
TO THIS MANUAL, EXCEPT IN SPECIFIC CASES THAT MAY COME DURING THE REVIEW PROCESS.
FOR THE CORRECT DEFINITION OF TESTS, THE DEVELOPMENT OF A DETAILED INSPECTION PLAN IS RECOMMENDED, INDICATING THE SITES TO BE INSPECTED, THE TYPE OF TESTS TO BE CARRIED OUT. IT SHOULD ALSO INDICATE THE MOMENT FOR THE TESTS TO BE CARRIED OUT, IN A WAY SUCH THAT THERE IS CERTAINTY THAT THEY CAN BE EXECUTED TIMELY, WITHOUT ANY DELAYS OR
REPROCESSES.
THE OWNER AND THE COMPANY IN CHARGE OF THE MANUFACTURE OF THE STRUCTURE HAS THE
OBLIGATION TO PERFORM THE REQUIRED CORRECTIONS AND PERFORM ALL COMPLEMENTARY
STUDIES THAT ARE NEEDED IN ORDER TO CERTIFY THAT THEY HAVE BEEN CORRECTED PROPERLY.
IN CASE OF DOUBT, THE DESIGNER AND STRUCTURAL INSPECTOR WILL INDICATE THE
CORRECTION PROCEDURE TO BE CARRIED OUT, AS WELL AS INDICATE IF ADDITIONAL TESTS ARE
REQUIRED.
BOLTED CONNECTIONS
BOLTED CONNECTIONS MUST HAVE CONTINUOUS INSPECTION BY THE MANUFACTURER'S
QUALITY CONTROL TEAM AND BE REGULARLY INSPECTED BY THE QUALITY ASSURANCE TEAM.
THE RESPONSIBILITIES OF EACH OF THE PARTIES ARE ESTABLISHED IN THE AISC 360-16 MANUAL.
ALL BOLTED CONNECTIONS MUST BE CHECKED ACCORDING TO THE CRITERIA ESTABLISHED IN
AISC 360-16 CHAPTER N, AND AISC 341-16 CHAPTER J.
THE PRE-TENSION OF THE BOLTS MUST BE ASSURED BY ANY OF THE METHODS INDICATED IN
"SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH STRENGTH BOLTS" OF THE RESEARCH
COUNCIL ON STRUCTURAL CONNECTIONS, OR ANY OTHER APPLICABLE STANDARDS AND AS
INDICATED IN PLANS.
THE USE OF ULTRASONIC ELONGATION SENSORS AND CALIBRATED TORQUEMETERS IS ALLOWED
FOR BOLT PRE-TENSION REVIEWS, AS LONGS AS THE EQUIPMENT CALIBRATION CERTIFICATES
ARE PRESENTED.
INSTALACION DE PERNOS
TODOS LOS PERNOS A PROVEERSE EN SITIO. DEBEN INGRESAR EMBALADOS Y
DEBIDAMENTE PROTEGIDOS DEL AMBIENTE.
ANTES DE COLOCAR CUALQUIER PERNO SE DEBE ENGRASAR TODA SU SUPERFICIE Y
APLICAR LA PRETENSIÓN INDICADA EN LAS TABLAS SUMISITRADAS EN ESTOS PLANOS
O BIEN PROVISTAS POR EL FABRICANTE. SE HACE NOTAR QUE LOS VALORES QUE
CORRELACIONAN TORQUE CON PRETENSIÓN SON SUGERIDAS PERO PUEDEN NO
CORRESPONDER A LA REALIDAD DEL MONTAJE ESPECIFICO, POR LO CUAL EL
CONTRATISTA DEBE SIEMPRE VERIFICAR QUE LA PRETENSIÓN MINIMA SE ALCANZA
CON ESE VALOR DE TORQUE O HACER LAS CORRECCIONES CORRESPONDIENTES.
LA SECUENCIA DE SOCADO DE LOS PERNOS DEBE SER TAL QUE NO PRODUZCA QUE
OTROS PERNOS SE AFLOJEN O INCURRAN EN SOBREESFUERZOS NO TOLERABLES. SE
DEBE SEGUIR UN ORDEN ESTRICTO EN EL PROCESO DE AJUSTE DE LOS PERNOS.
PERNOS DOBLADOS, FRACTURADOS, CON GOLPES NOTORIOS, DESGASTES EN LAS
ROSCAS, NO SE PUEDEN INSTALAR.
LOS TAMAÑOS DE LOS HUECOS Y EL ALINEAMIENTO DEBE SER CONFORME A PLANOS,
SI POR ALGUN MOTIVO NO HUBIERA COINCIDENCIA EN EL ARMADO DE LAS PIEZAS SE
DEBE CONSULTAR A LA INSPECCION ESTRUCTURAL PARA DEFINIR LA CORRECCIÓN A
APLICAR.
LAS TUERCAS Y ARANDELAS DEBEN CUMPLIR LAS NORMAS CORRESPONDIENTES Y SE
DEBEN ENTREGAR CERTIFICADOS DEL FABRICANTE PARA DEMOSTRARLO.
EN LA TABLA ADJUNTA SE INDICA EL TIPO DE SOCADO REQUERIDO EN PERNOS PARA
ASEGURAR UNA ADECUADA PRETENSIÓN DE LOS MISMOS.
EMPALMES Y AGUJEROS
CON LA INTENCION DE UN MAXIMO APROVECHAMIENTO DE LOS MATERIALES, SE
ACEPTARA EMPALMES SOLDADOS (SOLDADURA DE PENETRACION COMPLETA) CON
PIEZAS DE AL MENOS 6m DE LONGITUD, EN PIEZAS DE MENOS DE 6m NO SE
ACEPTARAN EMPALMES).
LOS EMPALMES NO DEBEN QUEDAR UBICADOS EN ZONAS DE ALTA DEMANDA DE
MOMENTO.
LOS AGUJEROS PARA PERNOS SE REALIZARAN CON MEDIOS MECÁNICOS Y NO SE
PERMITIRA REALIZARLO CON SOPLETE O PUNZONES. PARA EL DIMENSIONADO DE LOS
AGUJEROS SE PERMITE UTILIZAR UN HUECO STANDARD EN EL ELEMENTO
ESTRUCTURAL Y UN AGUJERO CON SOBREDIMENSION SEGUN TABLA J.3.3 DEL AISC
360-16 PARA LAS PLACAS DE CONEXION.
NO SE PERMITE SUSTITUIR PERNOS POR SOLDADURAS DE TAPÓN.
EN CASO DE QUE LOS AGUJEROS DE UNA PARTE NO COINCIDAN CON OTRA PARTE SE
DEBE SOMETER A REVISION DEL INSPECTOR ESTRUCTURAL PARA DEFINIR EL
PROCEDIMIENTO CORRECTIVO.
CORTES
PARA LOS CORTES EN METAL SE PERMITEN MEDIOS MECANICOS O TÉRMICOS. EL
CORTE USANDO SOPLETES O QUEMANDO POR MEDIO DE ELECTRODOS ESTÁ
TERMINANTEMENTE PROHIBIDO.
LAS TOLERANCIAS EN LOS CORTES EN COMPARACIÓN CON LAS MEDIDAS DE PLANOS
DEBE SER DETALLADO EN PLANOS DE TALLER Y CUMPLIRSE EN OBRA.
PINTURA
LAS PARTES Y ELEMENTOS FABRICADOS DEBERAN LIMPIARSE SIGUIENDO AL MENOS
EL PROCEDIMIENTO SP1 Y SP2 DEL MANUAL SSPC. (VER TABLA 2.7 DEL MANUAL DE
CONSTRUCCION EN ACERO DE AISC).
SE DEBERAN COLOCAR AL MENOS 2 CAPAS DE ANTICORROSIVO DE DIFERENTE COLOR
O DE AL MENOS 50 MICRAS DE ESPESOR (4MILS TOTAL). PARA EL ACABADO FINAL SE
RECOMIENDA UNA CAPA DE COLOR DIFERENTE DE AL MENOS 50 MICRAS DE ESPESOR
(2 MILS). LOS PERFILES GALVANIZADOS NECESITAN PINTURA ANTICORROSIVA
UNICAMENTE EN LAS UNIONES QUE HAYAN SIDO SOLDADAS.
LA ULTIMA MANO DE PINTURA SE APLICARA UNA VEZ CONCLUIDO EL MONTAJE DE LA
ESTRUCTURA PARA CORREGIR PIEZAS RAYADAS O DEFECTOS DE PINTURA. EL
PROCEDIMIENTO APLICA PARA TODOS LOS COMPONENTES METALICOS.
NINGUNA CONEXIÓN SOLDADA DEBE PINTARSE NI ANTES DE SOLDAR NI DESPUÉS
DE SOLDAR HASTA QUE NO SE HAYAN CONCLUIDO LOS PROCESOS DE INSPECCIÓN
VISUAL. SE RECOMIENDA ELIMINAR LA PINTURA DE UNA FRANJA DE AL MENOS 5CM
A CADA LADO DEL CENTRO DEL CORDÓN A SOLDAR.
SI LAS PIEZAS A PINTAR SON DE TIPO TUBULAR Y ESTARÁN SELLADAS EN SUS
EXTREMOS DEBERÁN PINTARSE SÓLO EN LA CARA EXPUESTA A LA INTEMPERIE. EN
CASO DE QUE ESTÉN ABIERTAS DEBERÁ PROVEERSE PINTURA EN TODA LA SUPERFICIE
INTERNA Y EXTERNA O BIEN USAR ALGUN SISTEMA DISTINTO DE PROTECCIÓN A LA
CORROSIÓN.
FABRICACION EN TALLER:
PREVIO AL INICIO DE LA FABRICACION EL CONTRATISTA DEBERÁ PRESENTAR PARA
APROBACION, LOS PLANOS DE TALLER Y DE MONTAJE DE LA ESTRUCTURA METALICA. DEBE
INDICAR COMO MINIMO LO SIGUIENTE:
PLANOS DE TALLER
1. PLANTAS DE CODIFICACION DE ELEMENTOS
2. GEOMETRIA GENERAL
3. DETALLES DE UNION
4. INDICACION DE PREPARACION DE LOS MATERIALES Y SUPERFICIES
5. ACABADOS EN TALLER Y EN SITIO
6. INDICACION DE PIEZA ACABADA Y SUS DETALLES DE UNION CON ELEMENTOS
CONTIGUOS Y/O DETALLES DE APOYO.
7. INDICACION DE TIPO Y LONGITUD DE SOLDADURA
8. DETALLES DE LOS PUNTOS DE IZAJE
9. DETALLES DE EMPALME Y SUS DETALLES
10. TOLERANCIAS DIMENSIONALES DE LAS PIEZAS CONSIDERANDO EL MONTAJE.
PLANOS DE MONTAJE
1. CODIFICACION DE ELEMENTOS
2. CONDICIONES DE MANEJO, ESTOQUEO Y MONTAJE
3. DETALLES Y UBICACION DE PLACAS E INSERTOS EN SITIO PARA RECIBIR LA
ESTRUCTURA PREFABRICADA.
4. DETALLES DE UNION TEMPORAL Y FINAL.
5. DETALLES DE APOYO TEMPORAL Y FINAL.
6. CONTROL DE DEFORMACIONES PERMANENTES Y PROVISIONALES.
7. CERTIFICADOS DE MOLINO DE TODAS LAS PIEZAS METALICAS, PERNOS, BARRAS DE
ANCLAJE, CONSUMIBLES DE SOLDADURA, PINTURAS.
8. PROCEDIMIENTOS DE SOLDADURA PARA TODAS LAS CONEXIONES (WPS)
9. REGISTRO DE CALIFICACION DE SOLDADURES SEGÚN NORMA AWS APLICABLE.
10. PROCEDIMIENTO DE INSTALACION DE PERNOS.
INSPECCION DE SOLDADURA Y CONEXIONES APERNADAS
CONEXIONES SOLDADAS
LA INSPECCION DE LA SOLDADURA ES DE CARACTER OBLIGATORIO. DEBEN CONTAR
CON INSPECCIÓN CONTINUA POR PARTE DE LOS ENCARGADOS DE CONTROL DE
CALIDAD DEL FABRICANTE E INSPECCIÓN REGULAR POR PARTE DE LOS ENCARGADOS
DEL ASEGURAMIENTO DE LA CALIDAD. EN EL AISC 360-16 CAPITULO N Y EL AISC
341-16 CAPITULO J, SE ESTABLECEN LAS RESPONSABILIDADES DE CADA UNA DE LAS
PARTES Y EL ALCANCE DE LAS INSPECCIONES.
ES OBLIGACIÓN DEL CONTRATISTA ENTREGAR EL INFORME COMPLETO DE LA
APROBACIÓN EN CAMPO DE LA EJECUCION DE TODAS LAS WPS PREVIAMENTE
DISEÑADAS Y APROBADAS POR LA INSPECCIÓN ESTRUCTURAL.
SE DEBE REALIZAR UNA INSPECCION VISUAL PARA IDENTIFICAR Y CORREGIR
DEFECTOS SEGÚN LO ESTABLECIDO EN AWS D1.1 TABLA 6.1.
SE DEBEN REALIZAR ENSAYOS NO DESTRUCTIVOS COMPLEMENTARIOS SEGUN LO
SOLICITA EL CÓDIGO SISMICO DE COSTA RICA EN EL CAPITULO 10.9 O BIEN DONDE LO
SOLICITEN ESTOS PLANOS, LAS ESPECIFICACIONES TÉCNICAS, LOS DOCUMENTOS DEL
CARTEL DE LICITACION O DONDE SE REQUIERA POR SOLICITUD EXPLICITA DE LA
INSPECCION O EL CLIENTE.
DONDE SE REQUIERA INSPECCION CON LIQUIDOS PENETRANTES (PT) O PARTICULAS
MAGNÉTICAS (MT), TODAS LAS SUPERFICIES A INSPECCIONAR DEBEN ESTAR LIBRES DE
PINTURA Y SE PROHIBE TERMINANTE APLICAR PULIDO DE LA SUPERFICIE POR
MEDIOS MECÁNICOS CON LA EXCEPCIÓN DE UN CEPILLO DE CERDAS DE ALAMBRE. LA
LIMPIEZA SERÁ PARA ELIMINAR LOS RESIDUOS DE ESCORIA DE SOLDADURA.
SOLDADURAS QUE REQUIERAN REVISION POR MEDIO DE PRUEBAS ULTRASONICAS
DEBEN REALIZARSE EN UN MOMENTO APROPIADO DE TAL FORMA QUE SE PUEDE
ACCEDER CON EL EQUIPO. EL ESPACIO FÍSICO DEBE PERMITIR LA REALIZACIÓN DE LA
PRUEBA.
TODOS LOS EQUIPOS A USAR EN ENSAYOS NO DESTRUCTIVOS DEBEN CONTAR CON
CERTIFICADO DE CALIBRACIÓN DE FÁBRICA Y ESTANDARIZADOS CON LOS BLOQUES
STANDARD QUE CORRESPONDA SEGÚN LA ESPECIFICACIÓN SOLICITADA EN PLANOS Y
ESPECIFICACIONES. EN SU DEFECTO SE DEBE USAR LA NORMATIVA AWS D1.1.
LOS CRITERIOS DE ACEPTACION O RECHAZO SON LOS ESTIPULADOS EN LAS NORMAS
QUE INDIQUEN LOS PLANOS Y ESPECIFICACIONES Y EN SU DEFECTO SE UTILIZARÁN
LOS ESTABLECIDOS EN AWS D1.1.
LA EMPRESA QUE SUMINISTRE LOS ENSAYOS DEBE CONTAR CON TÉCNICOS
CALIFICADOS Y DEBERÁN PROVEER AL INSPECTOR EL MANUAL ESCRITO DE PRÁCTICAS
DE LA EMPRESA LA CUAL DESCRIBE EL TIPO DE PRUEBAS, LA METODOLOGÍA PARA
REALIZARLAS Y OTROS PROCEDIMIENTOS DE MANEJO, PROTECCIÓN Y PRESENTACIÓN
DE LA INFORMACIÓN. LOS INFORMES DEBEN ADAPTARSE A ESTE MANUAL, EXCEPTO
EN CASOS ESPECÍFICOS QUE PUEDAN SURGIR DURANTE EL PROCESO DE REVISIÓN.
PARA LA CORRECTA DEFINICIÓN DE PRUEBAS SE RECOMIENDA LA REALIZACIÓN DE UN
PLAN DE INSPECCIÓN DETALLADO INDICANDO LOS SITIOS A INSPECCIONAR, EL TIPO
DE PRUEBAS A REALIZAR Y EL MOMENTO A REALIZARLAS DE FORMA TAL QUE EXISTA
CERTEZA DE QUE SE PUEDEN EJECUTAR, QUE NO VAN A PRODUCIR RETRASOS O
REPROCESOS POR ACTUAR A DESTIEMPO.
EL PROPIETARIO Y LA EMPRESA ENCARGADA DE LA FABRICACIÓN DE LA ESTRUCTURA
TIENE LA OBLIGACIÓN DE REALIZAR LAS CORRECCIONES NECESARIAS Y CORREN POR
SU CUENTA LOS ESTUDIOS COMPLEMENTARIOS QUE DEBA APORTAR PARA
CERTIFICAR QUE SE HAN CORREGIDO ADECUADAMENTE. EN CASO DE DUDA TANTO
EL DISEÑADOR E INSPECTOR ESTRUCTURAL TIENEN LA ULTIMA PALABRA DEL
PROCEDIMIENTO DE CORRECCIÓN A REALIZAR Y SI REQUERIRÁN O NO ENSAYOS
COMPLEMENTARIOS.
CONEXIONES APERNADAS
LAS CONEXIONES APERNADAS DEBEN CONTAR CON INSPECCIÓN CONTINUA POR
PARTE DE LOS ENCARGADOS DE CONTROL DE CALIDAD DEL FABRICANTE E
INSPECCIÓN REGULAR POR PARTE DE LOS ENCARGADOS DEL ASEGURAMIENTO DE LA
CALIDAD. EN EL AISC 360-16 SE ESTABLECEN LAS RESPONSABILIDADES DE CADA UNA
DE LAS PARTES.
TODOS LOS PERNOS DE CONEXIONES SE DEBEN REVISAR SEGÚN LOS CRITERIOS QUE
SE ESTABLECEN EN EL AISC 360-16 CAPITULO N, AISC 341-16 CAPITULO J.
LA PRETENSION DE LOS PERNOS DEBE ASEGURARSE POR ALGUNO DE LOS MÉTODOS
INDICADOS EN "SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH STRENGTH
BOLTS" DEL RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS, O ALGUNA OTRA
NORMA APLICABLE Y SOLICITADA EN PLANOS Y ESPECIFICACIONES.
SE PERMITE EL USO DE SENSORES ULTRASONICOS DE ELONGACIÓN Y TORQUÍMETROS
CALIBRADOS PARA LAS REVISIONES DE PRETENSIÓN DE PERNOS, SIEMPRE Y CUANDO
EN AMBOS CASOS SE PRESENTEN LOS CERTIFICADOS DE CALIBRACIÓN DE LOS
EQUIPOS.
TABLE 8.2. NUT ROTATION FROM SNUG-TIGHT CONDITION FOR TURN-OF-NUT
PRETENSIONING
BOLT LENGTH
DISPOSITION OF OUTER FACES OF BOLTED PARTS
BOTH FACES NORMAL
TO BOLT AXIS
ONE FACE NORMAL TO BOLT
AXIS, OTHER SLOPED NOT
MORE THAN 1:20
BOTH FACES SLOPED NOT
MORE THAN 1:20 FROM
NORMAL TO BOLT AXIS
a,b c d d
NOT MORE
THAN 4db
MORE THAN 4d BUT NO MORE THAN 8db b
1/3 TURN
1/2 TURN
2/3 TURN
1/2 TURN
2/3 TURN
5/6 TURN
2/3 TURN
5/6 TURN
1 TURN
a: NUT ROTATION IS RELATIVE TO BOLT REGARDLESS OF THE ELEMENT (NUT OR BOLT) BEING
TUMED. FOR ALL REQUIRED NUT ROTATIONS, THE TOLERANCE IS PLUS 60 DEGREES (1/6
TURN) AND MINUS 30 DEGREES
b: APPLICABLE ONLY TO JOINTS IN WHICH ALL MATERIAL WITHIN THE GRIP IS STEEL c: WHEN THE BOLT LENGHT EXCEEDS 12 d THE REQUIRED NUT ROTATION STALL BE
DETERMINED BY ACTUAL TESTING IN A SUITABLE TENSION CALIBRATOR THAT SIMULATES THE
CONDITIONS OF SOLIDLY FITTING STEEL
d: BEVELED WASHER NOT USED b
MORE THAN 8d BUT NO MORE THAN 12db b a,b
TABLE 3.1. NOMINAL BOLT HOLE DIMENSIONS , cm
NOMINAL
BOLT
DIAMETER
d , cm
STANDAR
(DIAMETER)
OVERSIZED
(DIAMETER)
SHORT-SLOTTED
(WIDTH x LENGTH)
LONG - SLOTTED
(WIDTH x LENGTH)
1,27 cm
1,59 cm
1,91 cm
2,22 cm
2,54 cm
≥ 2,86 cm
1,43 cm
1,75 cm
2,06 cm
2,38 cm
2,7 cm d + 0,16 cm
1,59 cm
2,06 cm
2,38 cm
2,7 cm
3,18 cm d + 0,79 cm
1,43 cm x 1,75 cm
1,75 cm x 2,22 cm
2,06 cm x 2,54 cm
2,38 cm x 1,32 cm
2,7 cm x 3,33 cm
(d + 0,16 cm) x (d + 0,95 cm)
1,43 cm x 3,18 cm
1,75 cm x 3,97 cm
2,06 cm x 4,76 cm
2,38 cm x 5,56 cm
2,7 cm x 6,35 cm
(d +0,16 cm) x (2,5 x d ) a: THE UPPER TOLERANCE ON THE TABULATED NOMINAL DIMENSIONS SHALL NOT EXCEED 1/32 in. EXCEPTION: IN THE
WIDTH OF SLOTTED HOLES, GOUGES NOT MORE THAN 1/16 in. DEEP ARE PERMITTED b: THE SLIGHTLY CONICAL HOLE THAT NATURALLY RESULTS FROM PUNCHING OPERATIONS WITH PROPERLY MATCHED
PUNCHES AND DIES IS ACCEPTABLE
b b b b b b a,b b
NOTAS SOBRE PERFILES:
1- TODOS LOS PERFILES TIPO Z INDICADOS EN PLANOS SON
PERFILES DOBLADOS EN FRIO, DE ACERO TIPO A-570-33 CON UN
ESFUERZO DE CEDENCIA fy=2310 kg/cm2.
2- LAS MEDIDAS INDICADAS EN PLANOS CORRESPONDEN A LOS PER-
FILES DISTRIBUIDOS COMERCIALMENTE POR METALCO S.A.
3- SI NO SE CONSIGUEN EN EL MERCADO, DEBERAN FABRICARSE CON
LAS MEDIDAS Y ESPESORES DADOS EN TALLERES COMO METALCO
O INDESA.
4- TODOS LOS PERFILES TIPO RT DEBERAN PINTARSE CON DOS MA-
NOS DE PINTURA ANTICORROSIVA DE BASE DE DIFERENTE COLOR Y
DOS MANOS DE PINTURA ESMALTE SEGUN ESPECIFICACIONES Y CO-
LOR A ESCOGER POR INSPECCION.
5- TODAS LAS SOLDADURAS DEBERAN REALIZARSE CON ELECTRODOS
TIPO E6013 Y SE HARAN SIGUIENDO TODAS LAS NORMAS
DE A.W.S. (AMERICAN WELDING SOCIETY)
6- EN LA SIGUIENTE TABLA SE INDICAN LOS DIAMETROS DE LOS ELEC-
TRODOS Y LOS AMPERIOS QUE SE DEBERAN UTILIZAR PARA SOLDAR
PERFILES SEGUN SU ESPESOR
EL VALOR DE AMPERAJE PODRA AJUSTARSE SEGUN LO INDICADO POR
EL FABRICANTE DEL ELECTRODO A UTILIZAR
NOTA IMPORTANTE:
1- TODAS LAS MEDIDAS DEBERAN SER VERIFICADAS EN EL SITIO Y A-
PROBADAS POR LA INSPECCION. SE RECOMIENDA TRAZAR LA ES-
TRUCTURA EN CUERDAS PRIMERO. EN CASO DE DUDA SE DEBERA
CONSULTAR CON LA INSPECCION ARQUITECTONICA.
2- EN TODAS LAS UNIONES SE DEBE ELIMINAR LA ESCORIA PRODUCTO
DE LA SOLDADURA Y POSTERIORMENTE SE DEBERA PINTAR AL IGUAL
QUE EL RESTO DE LOS ELEMENTOS.
20-30 45-65
90-100
AMPERAJEESPESOR
mm
LAMINA
cal
ELECTRODO
Ø
1.51 2.30 3.03
1/16" 3/32" 1/8"
NOTAS SOBRE ESTRUCTURA DE TECHO
NOTES ABOUT PROFILES:
1- ALL COLD FORMED TYPE Z PROFILES, AS INDICATED IN DRAWINGS,
WILL BE MADE OFASTM A570, GRADE 33, COMPLIANT STEEL WITH A
YIELD STRENGTH OF f'y = 2310 kg/cm2.
2- MEASUREMENTS OF C CHANNELS, INDICATED IN DRAWINGS, ARE
SECTIONS WHICH ARE DISTRIBUTED BY METALCO S.A.
3- IF NOT AVAILABLE ON THE MARKET, THE SECTIONS MUST BE
FABRICATED IN WORKSHOPS SUCH AS METALCO OR INDESA WITH THE
INDICATED MEASUREMENTS AND THICKNESS.
4- ALL C CHANNELS SHALL BE PAINTED WITH TWO BASE ANTICORROSIVE
LAYERS, WITH A DIFFERENT COLOR THAN THE FINISH COATS, AND TWO
ENAMEL PAINT COATS, ACCORDING TO SPECIFICATIONS AND COLORS
INDICATED BY THE INSPECTOR.
5- ALL WELDS MUST BE DONE USING E6013 ELECTRODES, COMPLYING
WITH THE ALL OF THE RELEVANT A.W.S. STANDARDS.
6-ELECTRODE DIAMETERS AND AMPERAGE, WHICH MUST BE USED FOR
DIFFERENT MATERIAL THICKNESS, ARE INDICATED IN THE FOLLOWING
TABLE:
THE AMPERAGE VALUE CAN BE ADJUSTED ACCORDING TO THE
ELECTRODE MANUFACTURER'S INDICATION.
IMPORTANT NOTES:
1- ALL MEASUREMENTS MUST BE VERIFIED, CHECKED ON-SITE AND
APPROVED BY THE INSPECTOR. A PRELIMINARY ROPE LAYOUT IS
ADVISED. IN CASE OF DOUBT, THE ARCHITECTONIC INSPECTOR MUST
BE CONSULTED.
2- WELD SLAG MUST BE REMOVED FROM EVERY JOINT, AFTER WHICH
THE SAME PROTECTION AND PAINT SYSTEM AS THE REST OF THE
STRUCTURE MUST BE APPLIED.
20-30 45-65
90-100
AMPERAGETHICKNESS
mm
SHEET GAUGE
cal
ELECTRODE
Ø
1.51 2.30 3.03
1/16" 3/32" 1/8"
ROOF STRUCTURE NOTES
e c o n s u l t struTel (506) 2290 4070
Fax (506) 2290 7122 Oficentro Alquimia, 100 m Sur de la Liga de la Caña La Uruca, San José, Costa Rica www.estru.com
CONTENIDO
PROYECTO :
MODIFICACION FECHA REVISO
E-01820
OGB--/--/--1
REMODELACION INCINERADOR
JUNIO 2026
INFORMACION REGISTRO PUBLICO
PROPIETARIO:
N° CATASTRO:
FOLIO REAL:
CORTE SUPREMA DE JUSTICIA
H-1096358-2006 213155-000
PODER JUDICIAL
-PLANTA ARQUITECTONICA EXISTENTE
-(EXISTING ARCHITECTURAL PLAN)
A1.1
PORTON DE
ACCESO
PRIMARIO
MALLA
CICLON
MALLA
CICLON
RA
M
PA
N. 0.00
N. 0+50
N. 0.00
N. 0.00 S
N. 0.00
43685k65 or EQUAL43685k65 or EQUAL43685k65 or EQUAL43685k65 or EQUAL43685k65 or EQUAL43685k65 or EQUAL43685k65 or EQUAL43685k65 or EQUAL43685k65 or EQUAL 43685k65 or EQUAL 43685k65 or EQUAL 43685k65 or EQUAL 43685k65 or EQUAL 43685k65 or EQUAL 43685k65 or EQUAL 43685k65 or EQUAL
1 2
A
C
D
B
6.
6.
6.
S
ACOTADO cm PLANTA ARQUITECTONICA EXISTENTE1 ESCALA 1:75 DIMENSIONS IN cm
EXISTING ARCHITECTURAL PLAN1 SCALE 1:75
PRIMARY
ACCESS
GATE
138.11
S S
E
F
G
8.
.1
TRANSFORMADOR
TANQUE
DE DIESEL
DIESEL
TANK
N. +70
S
4" B
EA
M
B 2%
CICLONE
MESH
CICLONE
MESH
CICLONE
MESH TO BE
DEMOLISHED
EXISTENTE
EXISTING
EXISTENTE
EXISTING
EXISTENTE
EXISTING
N. 0.00
MALLA
A DEMOLER
CICLON
EXISTING AIR
COMPRESSORS TO
RELOCATE
COMPRESORES DE
AIRE EXISTENTES
A REUBICAR
RESUMEN DE TRABAJOS DEL INCINERADOR A REALIZAR :
INCINERATOR SCOPE OF WORK :
1 CONSTRUCTION OF A NEW COMPRESSOR ROOM, INCLUDING ALL NEW ELECTRICAL AND MECHANICAL
WORKS REQUIRED TO RELOCATE THE EQUIPMENT. THIS INCLUDES THE INSTALLATION OF ALL OVERHEAD PIPING TO CONNECT THE INCINERATOR TO THE AIR COMPRESSORS, INCLUDING THEIR FILTERS.
RELOCATE THE EXISTING COMPRESSOR EQUIPMENT TO THE NEW EQUIPMENT ROOM. THIS INCLUDES LABELING ALL NEW PIPING AND TESTING THE PROPER START-UP AND SHUTDOWN OF THE COMPRESSORS.
EXPAND THE EXISTING ROOF WALKWAY TO PROVIDE SAFE ACCESS FOR MAINTENANCE OF THE CHIMNEYS.
THIS INCLUDES INSTALLING A MAINTENANCE-FREE ALUMINUM STRUCTURE WITH FIBERGLASS BAR
GRATING.
THE WORK PLATFORM ON THE ROOF PROVIDING ACCESS TO THE INCINERATOR CHIMNEYS SHALL BE EXTENDED. FOR THIS PURPOSE, METAL CLAMPS SHALL BE INSTALLED AND ATTACHED TO THE STANDING SEAM ROOF WITHOUT PENETRATING IT. THE WALKWAY DECK SHALL CONSIST OF FIBERGLASS BAR
GRATING. THIS EXTENSION SHALL ALSO INCLUDE THE INDICATED LATERAL WALKWAYS.
A METALLIC SAMPLING PLATFORM SHALL BE INSTALLED ON THE FIRST CHIMNEY TO ALLOW QUALITY CONTROL LABORATORIES TO COLLECT FLUE GAS SAMPLES AT THE OUTLET. THE PLATFORM SHALL BE ATTACHED TO THE CHIMNEY STRUCTURE USING STEEL CLAMPS AND 3/8-INCH DIAMETER BOLTS.
AT THE ROOF PENETRATIONS WHERE THE TWO CHIMNEYS ARE LOCATED, A 3.2 MM THICK STEEL FLASHING COLLAR SHALL BE WELDED TO ACT AS A DRIP EDGE. THIS COLLAR SHALL BE ATTACHED TO THE CHIMNEY STEEL COLUMN AND SHALL REMAIN INDEPENDENT OF THE STANDING SEAM ROOF, WHICH SHALL HAVE ITS OWN WHITE ENAMELED 24-GAUGE SHEET METAL FLASHING AROUND THE ENTIRE PERIMETER. DIRECT
CONTACT BETWEEN THE CHIMNEY AND THE ROOF SYSTEM SHALL BE AVOIDED.
A CERTIFIED HORIZONTAL LIFELINE SYSTEM SHALL BE INSTALLED OVER THE ENTIRE ROOF AREA. STEEL CABLE SUPPORTS SPECIFICALLY DESIGNED FOR STANDING SEAM ROOFS SHALL BE USED SO THAT THE ROOF IS NOT PENETRATED. THE CONTRACTOR SHALL INSTALL THE INDICATED PERIMETER GALVANIZED STEEL CABLE AND PROVIDE TWO COMPLETE SAFETY HARNESS SETS FOR USE WITH THE LIFELINE SYSTEM.
THE GUTTER OUTLETS TO THE RAINWATER DOWNSPOUTS ARE SIDE DISCHARGE. THE OUTLET
CONNECTIONS SHALL BE WATERPROOFED USING A TPO MEMBRANE.
CONSTRUCT A SEDIMENTATION TANK FOR THE TREATMENT AND SEPARATION OF SEDIMENTS GENERATED
BY THE NEW SYSTEM.
CONSTRUCT A STRUCTURAL STEEL SUPPORT FRAME FOR THE CENTRIFUGAL TANK, DESIGNED TO
WITHSTAND OPERATIONAL AND MAINTENANCE LOADS.
CONSTRUCT ALL REQUIRED PIPE SUPPORTS AND ANCHORAGES FOR THE NEW PIPING SYSTEM.
INSTALL THE NEW COMPRESSED AIR AND POTABLE WATER SUPPLY LINES REQUIRED FOR THE OPERATION
OF THE NEW SYSTEM.
INSTALL THE DRAINAGE SYSTEM FOR SEDIMENTS AND GRAY WATER, INCLUDING ALL REQUIRED PIPING, FITTINGS, AND CONNECTIONS.
CONSTRUCT A TANK FOR THE COLLECTION AND DRAINAGE OF THE DEWATERING BAGS, ENSURING
ADEQUATE OPERATION AND MAINTENANCE.
RELOCATE ELECTRICAL PANEL #1, INCLUDING COMPLETE REWIRING OF ITS POWER SUPPLY AND
COMMISSIONING OF THE SYSTEM.
SUPPLY, INSTALL, AND COMMISSION ELECTRICAL PANEL #8, INCLUDING COMPLETE POWER SUPPLY
WIRING.
A WRITTEN WARRANTY SHALL BE PROVIDED COVERING THE ABSENCE OF LEAKS AND WATER INFILTRATION
FOR A MINIMUM PERIOD OF TWO (2) YEARS FOR ALL ROOFING WORK PERFORMED.
CONSTRUCCIÓN DE UNA NUEVA SALA DE COMPRESORES, INCLUYENDO TODAS LAS NUEVAS OBRAS
ELÉCTRICAS Y MECÁNICAS PARA REUBICAR EL EQUIPO. INCLUYE LA INSTALACIÓN DE TODAS LAS TUBERÍAS
AÉREAS PARA CONECTAR EL INCINERADOR A LOS COMPRESORES DE AIRE CON SUS FILTROS.
REUBİCAR EL EQUİPO DE COMPRESORES EXİSTENTE EN LA NUEVA SALA DE MÁQUİNAS. INCLUYE
ETİQUETAR TODAS LAS NUEVAS TUBERÍAS Y PROBAR EL CORRECTO ENCENDİDO Y APAGADO DE
LOS COMPRESORES.
AMPLİACİÓN DE LA PASARELA EXİSTENTE DEL TEJADO PARA PODER ACCEDER Y MANTENER LAS
CHİMENEAS. INCLUYE İNSTALAR UNA ESTRUCTURA DE ALUMİNİO LİBRE DE MANTENİMİENTO Y
REJİLLA DE BARRAS DE FİBRA DE VİDRİO
SE DEBERÁ AMPLIAR LA PLATAFORMA DE TRABAJO EN LA CUBIERTA QUE DA ACCESO A LAS CHIMENEAS DEL INCINERADOR. PARA ESTO SE PROPONE COLOCAR CLIPS METÁLICOS QUE SE FIJAN A LA CUBIERTA DE “STANDING SEAM” SIN PERFORARLA. EL PISO DE LA PASARELA SERÁ UNA LÁMINA TIPO “BAR GRATING” DE FIBRA DE VIDRIO. ESTA EXTENSIÓN INCLUYE TAMBIÉN LAS PASARELAS LATERALES INDICADAS.
EN LA PRIMERA CHIMENEA SE DEBERÁ INSTALAR UNA BANDERA METÁLICA QUE PERMITA LA TOMA DE MUESTRAS DE GASES EN LA SALIDA POR PARTE DE LOS LABORATORIOS DE CONTROL DE CALIDAD.