ITB_SUN250587_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Addendum__2.pdf
PDF 154 KB Posted
- Solicitation number
- ITB# SUN/250587
- Issued by
- Marion County, Orlando City, Florida
About this file
Addendum #2 for Solicitation Number ITB# SUN/250587 is issued by the City of Ocala, addressing the Construction of Union Station Restroom with Ticketing Kiosk project. The addendum provides clarifications to all bidders regarding two specific technical aspects of the project: fire alarm system requirements and security camera scope. For the fire alarm system, the city confirms a full functioning system is required, referencing specific technical sheets (FP-000, FP-201, and FP-901). Regarding security cameras, bidders are directed to review multiple electrical sheets (E-000 through E-903) and are instructed that the contractor must coordinate final camera locations and submit specifications for client approval.
The addendum is part of a larger procurement process for a construction project at 501 NE 1st Avenue in Ocala, Florida. While the addendum itself does not provide comprehensive details about pricing, funding, or complete project specifications, it is a critical document in the bidding process that provides essential technical clarifications. The document is dated May 21, 2025, and is from David Williams, the buyer for this solicitation, indicating an ongoing procurement process for the Union Station Restroom and Ticketing Kiosk construction project.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum # 2
Date: May 21, 2025
To: All bidders
From: David Williams, Buyer
Solicitation Number: ITB# SUN/250587
Solicitation Title: Construction of Union Station Restroom with Ticketing Kiosk
SECTION 1. SOLICITATION - CLARIFICATION
1. Will a full functioning fire alarm system be required for the building?
If not, will fire alarm monitoring be required for a tamper/flow switch at the fire sprinkler riser? Please advise.
• ANS: Yes, a full functioning fire alarm system is required per sheets FP-000, FP-201 and FP-901.
2. Can you clarify the scope of the security camera?
• ANS: See sheets E-000,E-001, E-002, E-100, E-201, E-301, E-501, E-901, E-902, and E-903. Contractor to coordinate final camera locations and submit specifications for approval with the client.
SECTION 1. SOLICITATION - CLARIFICATION