ITB_SUN250587_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_F-1_-_Restroom_and_Kiosk_ELECTRICAL.pdf
PDF 2 MB Posted
- Solicitation number
- ITB# SUN/250587
- Issued by
- Marion County, Orlando City, Florida
About this file
This electrical specification document is for the Ocala SunTran Restrooms & Kiosk project, prepared by Carbon design & architecture and Volt Air engineering for the City of Ocala, Florida. The electrical plans and specifications cover a comprehensive electrical system for an approximately 1,000-square-foot facility at Union Station, including detailed drawings and specifications for power distribution, lighting, grounding systems, device mounting, and electrical equipment. The documents include a complete set of electrical design drawings (E-000 through E-903) covering legend, specifications, schedules, site plans, power and lighting plans, riser diagrams, and technical details.
The electrical design specifies a 150-amp electrical service at 208/120V, with an estimated total connected load of 19.61 kVA and a total demand load of 19.883 kVA. The project includes provisions for various electrical systems such as receptacles, lighting, mechanical equipment connections, telecommunications infrastructure, and exterior lighting controls. The specifications mandate compliance with current national and local electrical codes, including the 2020 National Electrical Code, 2023 Florida Building Code, and other relevant standards. The design emphasizes detailed coordination with architectural, mechanical, and structural plans, with specific requirements for equipment installation, grounding, conduit routing, and device placement.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MISCELLANEOUS RECEPTACLE(S) LIGHTING
CODES AND STANDARDS
GENERAL NOTES
SHEET INDEX
SWITCHES
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
NFPA 70
NFPA 101
NFPA 110
2023 FBC.
2023 FFPC
2023 FBC-EC
NATIONAL ELECTRICAL CODE (2020)
LIFE SAFETY CODE (2021)
STANDARD FOR EMERGENCY AND STAND-BY POWER
SYSTEM (2021)
FLORIDA BUILDING CODE (2023)
FLORIDA FIRE PREVENTION CODE (2023)
FLORIDA BUILDING CODE - ENERGY CONSERVATION (2023)
LOCAL JURISDICTION CODES AND / OR OWNER DESIGN
GUIDELINES
SYMBOL DESCRIPTION
1. THE ELECTRICAL CONTRACT DOCUMENTS ARE SCHEMATIC IN NATURE AND
INDICATE THE GENERAL CONFIGURATION OF SYSTEMS AND WORK. EXAMINE
ARCHITECTURAL, CIVIL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE
PROTECTION DRAWINGS AND SPECIFICATIONS FOR LOCATIONS AND
REQUIREMENTS OF DEVICES, EQUIPMENT, LUMINARIES, AND SYSTEMS.
CONTENT INDICATED ON THE SPECIFICATIONS BUT NOT THE DRAWINGS, OR
CONTENT INDICATED ON THE DRAWINGS BUT NOT THE SPECIFICATIONS, SHALL
BE INTERPRETED AS BEING PRESENT ON BOTH.
2. PROVIDE ALL DEVICES, EQUIPMENT, ACCESSORIES, MATERIALS, AND LABOR
REQUIRED FOR A COMPLETE, FUNCTIONAL, AND CODE-COMPLIANT ELECTRICAL
SYSTEM. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE CODES
AND STANDARDS INDICATED ON THIS SHEET.
3. ALL DEVICES, EQUIPMENT, ACCESSORIES, AND MATERIALS SHALL BE NEW, AND,
WHERE APPLICABLE, SHALL BE LISTED BY U.L. OR ANOTHER APPROVED
ELECTRICAL TESTING AGENCY.
4. COORDINATE LOCATIONS AND REQUIREMENTS OF EQUIPMENT REQUIRING
ELECTRICAL SERVICE (I.E. PRINTERS, APPLIANCES, ETC.) WITH APPROVED
SHOP DRAWINGS, SPECIFICATION SHEETS, MANUFACTURER’S INSTALLATION
LITERATURE, AND EQUIPMENT NAMEPLATE DATA, PRIOR TO ROUGH-IN AND
INSTALLATION. PROVIDE ELECTRICAL CONNECTIONS (AS REQUIRED).
5. BID SHALL INCLUDE COSTS ASSOCIATED WITH BACKFILLING, CORE DRILLING,
DIRECTIONAL BORING, EXCAVATING, AND REPAIRING OF SURFACES.
6. PAY ALL FEES, TAXES, AND OTHER COSTS ASSOCIATED WITH THE WORK
ENCOMPASSED BY THE ELECTRICAL CONTRACT DOCUMENTS. PROVIDE ALL
REQUIRED NOTICES AND OBTAIN ALL REQUIRED PERMITS.
7. PROVIDE COOPERATION WITH OTHER TRADES AND PROVIDE ANY INFORMATION
REQUIRED TO FACILITATE THE COMPLETION OF THEIR WORK. COORDINATE
DEVICE AND EQUIPMENT LOCATIONS AND MOUNTING HEIGHTS WITH OTHER
TRADES PRIOR TO ROUGH-IN AND INSTALLATION. COORDINATE CONDUIT
ROUTING WITH OTHER TRADES PRIOR TO ROUGH-IN AND INSTALLATION.
8. COORDINATE ALL REQUIREMENTS WITH THE LOCAL UTILITY PRIOR TO ROUGH-
IN AND INSTALLATION. COORDINATE LOCATIONS OF UTILITY HANDHOLES,
AERIAL UTILITY TRANSFORMERS, AND/OR PAD-MOUNTED UTILITY
TRANSFORMERS.
9. PROVIDE TEMPORARY ELECTRICAL SERVICE(S) FOR USE BY OTHER TRADES
DURING PROJECT CONSTRUCTION. UPON COMPLETION OF THE PROJECT, THE
TEMPORARY ELECTRICAL SERVICE(S) SHALL BE REMOVED.
10. WITHIN THIRTY (30) DAYS OF SYSTEM ACCEPTANCE, PROVIDE RECORD
DRAWINGS TO THE OWNER.
11. WITHIN THIRTY (30) DAYS OF SYSTEM ACCEPTANCE, PROVIDE AN OPERATING
MANUAL AND MAINTENANCE MANUAL TO THE OWNER. THE MANUALS SHALL
INCLUDE THE FOLLOWING INFORMATION: SUBMITTAL DATA WITH EQUIPMENT
RATINGS AND SELECTED OPTIONS, OPERATION AND MAINTENANCE MANUALS
FOR EQUIPMENT REQUIRING MAINTENANCE, NAMES AND ADDRESSES OF A
MINIMUM OF ONE (1) QUALIFIED SERVICE AGENCY.
12. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF ALL WALL-MOUNTED
ELECTRICAL DEVICES AND EQUIPMENT WITH THE ARCHITECTURAL DRAWINGS,
GENERAL CONTRACTOR, CASEWORK/MILLWORK, AND OTHER TRADES PRIOR TO
ROUGH-IN AND INSTALLATION.
13. EQUIPMENT LOCATIONS SHALL SATISFY THE WORKING CLEARANCE
REQUIREMENTS AND DEDICATED SPACE REQUIREMENTS OF NEC ARTICLE 110.
PROVIDE SHOP DRAWINGS, DEMONSTRATING COMPLIANCE AND INTER-
DISCIPLINARY COORDINATION, FOR ENGINEERING REVIEW.
14. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS, SECTIONS, AND
ELEVATIONS FOR LOCATIONS AND/OR MOUNTING HEIGHTS OF LUMINARIES
LOCATED AT CEILINGS AND/OR WALLS. VERIFY THAT CEILING-MOUNTED
LUMINARIES ARE SUITABLE FOR THE FINISHED CEILING SYSTEM INDICATED AND
PROVIDE ACCORDINGLY. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF
WALL-MOUNTED LUMINARIES WITH CASEWORK, FURNITURE, AND
ARCHITECTURAL ELEMENTS. WHERE ARCHITECTURAL REFLECTED CEILING
PLANS INDICATE FIRE-RATED CEILING SYSTEMS, PROVIDE UL-LISTED LUMINAIRE
ENCLOSURES (AS REQUIRED).
SINGLE POWER TOGGLE SWITCH
(LETTER DENOTES FIXTURE CONTROLLED)
THREE-WAY TOGGLE SWITCH
FOUR-WAY TOGGLE SWITCH
MOTOR SWITCH
FAN SWITCH
THREE POSITION SELECTOR SWITCH
TIMER SWITCH (60 MINUTES)
LOW VOLTAGE SWITCH
HAND-OFF-AUTOMATIC SWITCH
KEY SWITCH
SWITCH - WEATHERPROOF
DUAL TECH WALL SWITCH OCCUPANCY SENSOR
DUAL TECH, DUAL-LEVEL OCCUPANCY SENSOR SWITCH
DUAL TECH OCCUPANCY SENSOR - CEILING MOUNTED
DUAL TECH OCCUPANCY SENSOR - WALL MOUNTED
PHOTOCELL
LIGHTING CONTACTOR
TIME CLOCK
MAGNETIC MOTOR STARTER
ENCLOSED CIRCUIT BREAKER, AS INDICATED
PANELBOARD, 480 / 277V
PANELBOARD, 208 /120V
MANHOLE
HANDHOLE
SURGE PROTECTION DEVICE
ELECTRICAL METER
TRANSFORMER
MOTOR CONNECTION, HP: DENOTES HORSEPOWER RATING
GROUND BUS BAR
PUSHBUTTON
3/4" PLYWOOD TELEPHONE BACKBOARD
CONCRETE ENCASED DUCTBANK
WIRE IN CONDUIT CONCEALED BELOW SLAB OR GRADE
CONDUIT EXPOSED
FLEXIBLE CONDUIT
CONDUIT TURNING UP
CONDUIT TURNING DOWN
CONDUIT STUB
DISCONNECT SWITCH, NON-FUSIBLE
3 POLE, 60 AMP, NF: NON-FUSED, 3R: NEMA 3R ENCLOSURE
DISCONNECT SWITCH, FUSIBLE
3 POLE, 60 AMP, FUSED AT 50 AMPS, 3R: NEMA 3R ENCLOSURE
COMBINATION STARTER / DISCONNECT SWITCH, FUSIBLE
3 POLE, 60 AMP, NEMA x SIZE, 3R: NEMA 3R ENCLOSURE
HOMERUN TO PANEL INDICATED
NUMBER OF ARROWS INDICATE NUMBER OF CIRCUITS
WIRE IN CONDUIT CONCEALED, #12 AWG SIZE WIRE IN
1/2" CONDUIT MINIMUM UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
MOUNTED AT 48" UNLESS NOTED OTHERWISE
QUADRAPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
MOUNTED AT 48" UNLESS NOTED OTHERWISE
GFI - TYPE DUPLEX RECEPTACLE
(WP: DENOTES WEATHERPROOF COVER)
GFI - DUPLEX RECEPTACLE
MOUNTED AT 48" UNLESS OTHERWISE NOTED
GFI - DOUBLE DUPLEX RECEPTACLE
MOUNTED AT 48" UNLESS OTHERWISE NOTED
SPECIAL PURPOSE RECEPTACLE
(NEMA RATING AS INDICATED)
QUADRAPLEX RECEPTACLE, TICK MARKS
DENOTE EMERGENCY (TYPICAL ALL RECEPTACLES)
DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
QUADRAPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
SINGLE RECEPTACLE, 20 AMP, 120V U.O.N.
GFI - TYPE DOUBLE DUPLEX RECEPTACLE
DUPLEX RECEPTACLE - HALF SWITCHED
DUPLEX RECEPTACLE - CEILING MOUNTED
DUPLEX RECEPTACLE WITH ISOLATED GROUND
DUPLEX RECEPTACLE - FLOOR MOUNTED
POWER POLE
JUNCTION BOX - CEILING MOUNTED
JUNCTION BOX - WALL MOUNTED
JUNCTION BOX - FLOOR / GROUND MOUNTED
CEILING MOUNTED 2'x2' / 2'x4' LUMINAIRE - RECESSED
NORMAL POWER
CEILING MOUNTED 2'x2' / 2'x4' LUMINAIRE - RECESSED
EMERGENCY POWER
CEILING MOUNTED 1'x4' LUMINAIRE
RECESSED OR SURFACE MOUNTED - NORMAL POWER
CEILING MOUNTED 1'x4' LUMINAIRE
RECESSED OR SURFACE MOUNTED - EMERGENCY POWER
CEILING MOUNTED 1'x4' LUMINAIRE
PENDANT MOUNTED - NORMAL POWER
CEILING MOUNTED 1'x4' LUMINAIRE
PENDANT MOUNTED - EMERGENCY POWER
STRIP LUMINAIRE - NORMAL POWER
STRIP LUMINAIRE - EMERGENCY POWER
DOWNLIGHT LUMINAIRE - NORMAL POWER
DOWNLIGHT LUMINAIRE - EMERGENCY POWER
WALL MOUNTED LUMINAIRE - NORMAL POWER
WALL MOUNTED LUMINAIRE - EMERGENCY POWER
CEILING FAN
TRACK LIGHTING WITH LUMINAIRE
UNDERCOUNTER LUMINAIRE
FLOOD LIGHT LUMINAIRE
POLE LIGHT LUMINAIRE
BOLLARD LUMINAIRE
STEP LIGHT LUMINAIRE
EMERGENCY BATTERY LIGHT UNIT
EXIT LIGHT - SINGLE FACE WITH DIRECTIONAL ARROW
EXIT LIGHT - DOUBLE FACE
EXIT LIGHT - WALL MOUNTED
3P/60A
NF
3R
3P/60A F:50A
3R
3P/60A Nx
3R
MH
HH
SPD
TX
HP
S
3S
4S
MS
FS
3PS
TS
LVS
HOAS
KS
WPS
OSS
DOSS
PC
LC
TC
OS
OS
IG
PP
J
J
J
COMMISSIONING
1. PRIOR TO FINAL INSPECTION, THE CONTRACTOR SHALL SUBMIT
EVIDENCE TO THE REGISTERED DESIGN PROFESSIONAL (ELECTRICAL
ENGINEER-OF-RECORD) OR REGISTERED DESIGN PROFESSIONAL’S
REPRESENTATIVE THAT THE LIGHTING CONTROL SYSTEMS HAVE BEEN
TESTED TO ENSURE THAT THEY ARE CALIBRATED, ADJUSTED,
PROGRAMMED, AND SATISFY THE INTENT OF THESE CONTRACT
DOCUMENTS AND THE MANUFACTURERS’ WRITTEN INSTRUCTIONS.
FUNCTIONAL TESTING SHALL BE PERFORMED IN ACCORDANCE WITH
FBC C408.3.1.1 (VACANCY / OCCUPANCY SENSOR CONTROLS), FBC
C408.3.1.2 (TIME-SWITCH CONTROLS), AND/OR FBC C408.3.1.3 (DAYLIGHT
RESPONSIVE CONTROLS) (AS REQUIRED).
DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
AUTOMATIC SWITCHED RECEPTACLE
QUADRUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
HALF-AUTOMATIC SWITCHED RECEPTACLE
VFD
VFD-RATED, REMOTE DISCONNECT SWITCH WITH EARLY-
BREAK, AUXILIARY CONTACTS FOR VFD DECELERATE-TO-
STOP SIGNAL. CONNECT CONTROL WIRING TO ASSOCIATED
VFD (AS REQUIRED).
15. PROVIDE A COMPLETE GROUNDING SYSTEM IN ACCORDANCE WITH APPLICABLE
SECTIONS OF THE NEC AND SPECIFICATIONS. BOND SERVICE ENTRANCE
ELECTRICAL EQUIPMENT TO BUILDING STEEL, GROUND RODS, METAL WATER
MAINS, LIGHTNING PROTECTION SYSTEM GROUNDING ELECTRODES (WHERE
PRESENT), AND TELECOMMUNICATIONS SYSTEM GROUNDING ELECTRODES (AS
REQUIRED). EQUIPMENT GROUNDING SHALL BE OF THE WIRE TYPE.
16. MINIMUM CONDUIT SIZE SHALL BE 3/4".
17. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG. ALL FEEDER AND BRANCH
CIRCUIT CONDUCTORS SHALL BE INSTALLED WITHIN CONDUIT, UNLESS
OTHERWISE INDICATED. ALL CONDUCTORS SHALL BE COPPER, UNLESS
OTHERWISE INDICATED.
18. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH CIRCUIT. MULTI-WIRE
BRANCH CIRCUITS SHALL BE PROHIBITED.
19. CONNECTIONS TO TRANSFORMERS AND MECHANICAL EQUIPMENT SHALL BE
MADE WITH FMC OR LFMC, UNLESS OTHERWISE INDICATED.
20. WHERE PRACTICABLE, CONDUITS SHALL BE CONCEALED BELOW SLABS, WITHIN
WALLS, AND ABOVE FINISHED CEILING SYSTEMS. WHERE CONDUITS ARE
EMBEDDED WITHIN CONCRETE SLABS, COORDINATE CONDUIT SIZE LIMITATIONS
AND SPACING REQUIREMENTS WITH THE STRUCTURAL DRAWINGS/ENGINEER
PRIOR TO INSTALLATION.
21. SEAL ALL CONDUIT PENETRATIONS AT FIRE-RATED PARTITIONS.
22. COORDINATE ALL CONDUIT PENETRATIONS WITH ARCHITECTURAL DRAWINGS,
STRUCTURAL DRAWINGS, FIELD CONDITIONS, AND OTHER TRADES. PROVIDE
SEALING FITTINGS TO PROHIBIT CONDENSATION AND/OR THE PASSAGE OF
GASES OR VAPORS (AS REQUIRED).
23. INCREASE FEEDER AND BRANCH CIRCUIT CONDUCTOR SIZES AS REQUIRED IN
ORDER TO MAINTAIN A MAXIMUM, CUMULATIVE VOLTAGE DROP OF 5% AT THE
END LOAD. MAXIMUM VOLTAGE DROP SHALL BE DISTRIBUTED AS FOLLOWS: 3%
FOR FEEDERS, 2% FOR BRANCH CIRCUITS. WHERE THE VOLTAGE DROP
REQUIREMENTS OF THE LOCAL ENERGY CODE ARE MORE STRINGENT, THE
REQUIREMENTS OF THE LOCAL ENERGY CODE SHALL TAKE PRECEDENCE.
WHERE PHASE AND NEUTRAL CONDUCTOR SIZES ARE INCREASED FOR
VOLTAGE DROP, THE EQUIPMENT GROUNDING CONDUCTOR SHALL BE
INCREASED PROPORTIONATELY.
24. PROVIDE ALL REQUIRED DISCONNECT SWITCHES, STARTERS, AND
COMBINATION STARTER/DISCONNECT SWITCHES. MAKE CONNECTIONS TO ALL
ELECTRICALLY-DRIVEN DEVICES AND EQUIPMENT PROVIDED BY THE
MECHANICAL, PLUMBING, AND FIRE PROTECTION CONTRACTORS. EXAMINE
EQUIPMENT NAMEPLATE RATINGS PRIOR TO ROUGH-IN AND INSTALLATION.
PROVIDE OVERCURRENT PROTECTION IN ACCORDANCE WITH EQUIPMENT
NAMEPLATE RATINGS. PROVIDE ALL POWER SUPPLIES, CONTROL
TRANSFORMERS, RELAYS, AND OTHER ACCESSORIES REQUIRED TO FACILITATE
THE PROPER OPERATION OF MECHANICAL EQUIPMENT AS DESCRIBED WITHIN
THE MECHANICAL ENGINEER’S SEQUENCE OF OPERATIONS.
25. ALL INTERIOR ELECTRICAL EQUIPMENT SHALL BE OF NEMA 1 CONSTRUCTION,
UNLESS OTHERWISE INDICATED. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL
BE OF NEMA 3R CONSTRUCTION, UNLESS OTHERWISE INDICATED. EQUIPMENT
RATINGS SHALL CORRESPOND TO THEIR INSTALLED ENVIRONMENTS.
26. ALL NEW PANELBOARDS AND WITHIN THE SCOPE OF THIS PROJECT SHALL BE
PROVIDED WITH NEW, TYPEWRITTEN DIRECTORIES. CIRCUIT DESCRIPTIONS
SHALL CONTAIN ROOM NAMES AND ROOM NUMBERS BASED UPON INSTALLED
ROOM SIGNAGE.
27. PROVIDE PHENOLIC, ENGRAVED IDENTIFICATION PLACARDS AT ALL
PANELBOARDS, DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS, AND
CABINETS. REFER TO DETAILS FOR FURTHER INFORMATION.
29. PROVIDE TYPEWRITTEN OR ENGRAVED PANEL AND CIRCUIT IDENTIFICATION AT
DEVICE RECEPTACLE OUTLET AND TOGGLE SWITCH COVER PLATES.
30. PROVIDE HANDWRITTEN PANEL AND CIRCUIT IDENTIFICATION ON THE
EXTERIORS OF ALL JUNCTION BOXES, PULL BOXES, AND WIREWAYS.
ELECTRICAL ABBREVIATIONS
SYMBOL DESCRIPTION
A
AC
A/C
AFC
AFCI
AHU
AIC
AL
ATS
AWG
C
CATV
CB
C/B
CCTV
CIR
CKT
CU
DC
DIA
EB
EC
EF
ELEV
EM
EMT
EP
EPO
ER
ETR
EWC
EX
F
FA
FAA
FLA
FMC
G, GND
GFCI, GFI
GND
GRC
HOA
HVAC
HZ
IEEE
IG
AMPERES
ALTERNATING CURRENT
AIR CONDITIONING
AVAILABLE FAULT CURRENT
ARC FAULT CIRCUIT INTERRUPTER
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAUGE
CONDUIT
CABLE TELEVISION
CRITICAL BRANCH
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CIRCUIT
COPPER
DIRECT CURRENT
DIAMETER
EQUIPMENT BRANCH
ELECTRICAL CONTRACTOR
EXHAUST FAN
ELEVATOR
EMERGENCY
ELECTRICAL METALLIC TUBING
EMERGENCY POWER
EMERGENCY POWER OFF (BUTTON OR SWITCH)
EXISTING TO BE REMOVED
EXISTING TO BE RELOCATED
ELECTRIC WATER COOLER
EXISTING TO REMAIN
FUSE
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FULL LOAD AMPERES
FLEXIBLE METAL CONDUIT
GROUND
GROUND FAULT CIRCUIT INTERRUPTER
GROUND
GALVANIZED RIGID METAL CONDUIT
HAND-OFF-AUTOMATIC SWITCH
HEATING, VENTILATION, AIR CONDITIONING
HERTZ
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS
ISOLATED GROUND
IMC
KCMIL
KVA
LFMC
LTG
LRA
MC
MCB
MCC
MCP
MLO
MTD
NC
NEC
NEMA
NFPA
NL
NO
P
PB
PNL
PWR
QTY
REQ
RMC
RNC
RTS
RTU
SP
ST
SW
SYM
TEL
TGB
TMCB
TYP
UG
UL
V
VA
VD
VFD
W
WH
WP
XFMR
INTERMEDIATE METAL CONDUIT
THOUSAND CIRCULAR MILS
KILOVOLT - AMPERES
LIQUID TIGHT FLEXIBLE METAL CONDUIT
LIGHTING
LOCK ROTOR AMPS
METAL CLAD CABLE
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTION
MAIN LUGS ONLY
MOUNTED
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NIGHT LIGHT
NORMALLY OPEN OR NUMBER
POLE
PUSH BUTTON, PANIC BUTTON OR PULLBOX
PANEL
POWER
QUANTITY
REQUIRED
RIGID METAL CONDUIT
RIGID NON-METALLIC CONDUIT
REMOTE TEST STATION
ROOF TOP UNIT
SPARE
SHUNT-TRIP
SWITCH
SYMMETRICAL
TELEPHONE
TELECOMMUNICATIONS GROUNDING BUSBAR
THERMAL MAGNETIC CIRCUIT BREAKER
TYPICAL
UNDERGROUND
UNDERWRITERS LABORATORY
VOLT
VOLT - AMPERE
VOLTAGE DROP
VARIABLE FREQUENCY DRIVE
WATT OR WIRE
WATER HEATER
WEATHERPROOF
TRANSFORMER
SYMBOL DESCRIPTION
DAYLIGHT HARVESTING SENSOR - CEILING MOUNTEDDH
DIMMING SWITCHSD
ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE FOLLOWING:
RELAY MODULE WITH 0-10V DIMMING OUTPUTPL
PLUG LOAD RELAY PACKPR
STRUCTURED CABLING SYSTEMS
SYMBOL DESCRIPTION (RACEWAY ONLY)
COMMUNICATIONS OUTLET, MOUNTED AT
RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED.
REFER TO INSTALLER FOR MODULE AND FACEPLATE
DESCRIPTIONS. CABLES PROVIDED BY OTHERS.
CEILING MOUNTED WIRELESS ACCESS POINT
OUTLET.
'X' - MOUNTING (F)LUSH, (S)URFACE, (C)EILING
WALL TELEPHONE OUTLET FOR WALL PHONE.
MTD AT 48" ABOVE FINISHED FLOOR TO CENTER
COMBINED VOICE / DATA, AUDIO / VIDEO AND
POWER OUTLETS IN FLOOR BOX.
WAP
W
SECURITY SYSTEM
SYMBOL DESCRIPTION (RACEWAY ONLY)
BIOMETRIC READER
CARD READER / KEYPAD
CARD READER
KEYPAD
DIRECTIONAL MOTION DETECTOR
360 DEGREE MOTION DETECTOR
ELECTRO MAGNETIC LOCK
ELECTRIC STRIKE FRAME
ELECTRIC MORTISE LOCK
DELAYED EGRESS LOCK
DOOR / WINDOW CONTACT
SECURITY PANEL
KEY SWITCH
REMOTE DOOR RELEASE BUTTON
INTERCOM SUB-STATION
REQUEST TO EXIT MOTION SENSOR
REQUEST TO EXIT PUSH-BUTTON
PERSONAL COMPUTER WORKSTATION
FIXED CCTV CAMERA
ALARM SIREN
WP: WEATHERPROOF
DURESS BUTTON
INTERCOM MASTER STATION
SECURITY CAMERA POLE. POLE TO MATCH
UTILITY PACKAGE SPECIFICATIONS FOR LIGHTING
POLES IN THE SAME AREA
KP
CR
MD
S
DC
CK
BR
MD
ML
ES
EM
DE
KS
RR
D
IM
IS
RS
RB
PC
TP
SECURITY SOUND DETECTORSD
FLORIDA LIC No: AR95989
Carbon design & architecture 263 13th Avenue South Suite 375 St. Petersburg, FL 33701 O:: 941.362.4312 W:: www.carbonAE.com
Project No:
PROJECT DATA
Project Na:
CLIENT DATA
Client:
ARCHITECT DATA
ENGINEER DATA
ISSUE + REVISION DATA
ENGINEER SEAL
CHECKED BY
DRAWN BY
PRINTED:24X36 SHEET
ARCH D
EOR: JULIUS D. DAVIS, P.E. #58005
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIUS D. DAVIS,
P.E. #58005 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES
6005 Benjamin Rd.
Suite A Tampa, FL 33634 O:: 888.891.9713 W:: www.voltairinc.com
COA: #27158
Proj: #01.22029
TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY
WITH THE APPLICABLE MINIMUM BUILDING CODES
8/12/2024 4:45:49 PM
8/12/2024 4:45:49 PM
E-000
LEGEND - ELECTRICAL
100% CD's Set
05.28.2024
24020
OCALA SUNTRAN
RESTROOMS & KIOSK
CITY OF OCALA
501 NE 1st Ave.
Ocala, FL 34470
R.F.W.
R.F.W.
SHEET NUMBER SHEET NAME
E-000 LEGEND - ELECTRICAL
E-001 SPECIFICATIONS - ELECTRICAL
E-002 SCHEDULES - ELECTRICAL
E-100 SITE PLAN - ELECTRICAL
E-201 FIRST FLOOR PLAN - POWER
E-301 FIRST FLOOR PLAN - LIGHTING
E-501 RISER DIAGRAM - ELECTRICAL
E-901 DETAILS - ELECTRICAL
E-902 DETAILS - ELECTRICAL
E-903 DETAILS - ELECTRICAL
No: Description: Date:
SPECIFICATIONS - ELECTRICAL
260100 - BASIC ELECTRICAL SCOPE OF WORK REQUIREMENTS:
A. ALL WORK SHALL BE IN COMPLIANCE WITH THE LATEST APPLICABLE CODES, LAWS AND ORDINANCES AND THE NATIONAL ELECTRICAL CODE. PROVIDE AND INSTALL ALL LABOR, MATERIALS, PERMITS AND INCIDENTALS REQUIRED TO COMPLETE
ALL WORK AS SHOWN ON CONTRACT DOCUMENTS.
B. DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL SCOPE AND ARRANGEMENT OF THE ELECTRICAL INSTALLATION AND ARE NOT INTENDED TO SHOW EVERY CONNECTION. CONDUIT OR EXACT LOCATION AND EXTENT OF WORK. CONTRACTOR SHALL INSTALL THE WORK COMPLETE, INCLUDING DETAILS AND EQUIPMENT NECESSARY TO PERFORM THE FUNCTION INDICATED ON THE DRAWINGS. SUBMIT SHOP DRAWINGS FOR ALL ELECTRICAL EQUIPMENT ASSOCIATED WITH THE PROJECT UNDER ONE SUBMITTAL. SEPARATE SUBMITTALS MAY BE REJECTED. SUBMIT DIMENSIONED ELECTRICAL ROOM LAYOUTS TO 1/4' SCALE WITH MANUFACTURERS EQUIPMENT LOCATIONS SHOWN
THEREIN.
C. ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS AND SHALL BE U.L. LISTED OR BE LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY.
D. INSPECT ALL NEW MATERIAL AND EQUIPMENT PRIOR TO INSTALLATIONS FOR DAMAGES AND SHALL VERIFY EQUIPMENT
OPERATES SATISFACTORILY.
E. WARRANT ALL MATERIAL AND EQUIPMENT FURNISHED TO COMPLETE ALL WORK FOR ONE YEAR AFTER FINAL ACCEPTANCE OF COMPLETION. MATERIALS AND EQUIPMENT DEFECTS OF FAILURES DUE TO ABUSE OR WORKMANSHIP NEGLECT SHALL
BE MADE GOOD BY THE CONTRACTOR WITHOUT COST TO THE OWNER.
F. PROVIDE ONLY NEW, STANDARD UNDERWRITER'S LABORATORY INC. LISTED FIRST-GRADE MATERIALS THROUGHOUT AND SHALL BE MARKED WITH UNDERWRITERS LABORATORY INC. LISTED AND WITH MANUFACTURER'S BRAND OR TRADEMARK.
ALL MATERIALS SHALL BE OF ONE MANUFACTURER.
G. CONTRACTOR SHALL BE EXPERIENCED IN THEIR TRADE. CONTRACTOR'S WORK SHALL PRESENT A NEAT APPEARANCE UPON COMPLETION. MATERIALS AND EQUIPMENT INSTALLED SHALL BE PLUMB, STRAIGHT AND LEVEL.
H. COORDINATE WITH THE ARCHITECT AND OWNER ON EXACT LOCATION OF WIRING DEVICES AND RACEWAYS FOR OWNER- FURNISHED EQUIPMENT PRIOR TO ROUGH-IN. COORDINATE ELECTRICAL EQUIPMENT AND MATERIALS INSTALLATION WITH OTHER BUILDING COMPONENTS AND TRADES. REVIEW AND COORDINATE BETWEEN ALL CONSTRUCTION DOCUMENTS AND
PROJECT SPECIFICATIONS.
I. COORDINATE THE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SLEEVES TO BE SET IN POURED IN PLACE CONCRETE AND OTHER STRUCTURAL COMPONENTS AS THEY ARE CONSTRUCTED. COORDINATE THE CUTTING AND PATCHING OF BUILDING COMPONENTS TO ACCOMMODATE THE INSTALLATION OF ELECTRICAL EQUIPMENT AND MATERIALS
IN RENOVATION PROJECTS.
J. COORDINATE CONNECTION OF ELECTRICAL SYSTEMS AND EQUIPMENT REQUIREMENTS WITH LOCAL UTILITY SERVICES TO
PROVIDE AND COMPLY WITH THE REQUIREMENTS FOR EACH SERVICE.
K. UPON COMPLETION OF WORK, TEST ALL WIRING AND EQUIPMENT INSTALLATION AND SHALL BE IN PERFECT WORKING CONDITION IN ACCORDANCE WITH THE INTENT OF THE CONTRACT DOCUMENTS. MARK DRAWINGS TO INDICATE ACTUAL
FIELD CONDITIONS.
L. THE WORD 'PROVIDE' MEANS FOR THE CONTRACTOR TO FURNISH AND INSTALL.
260519 - CONDUCTORS AND CABLES:
A. WIRING GENERAL: CONDUCTORS SHALL BE COPPER AND HAVE CURRENT CARRYING CAPACITIES AS PER N.E.C. WITH 600 VOLT INSULATION AND COMPLY WITH NEMA WC 70. ALUMINUM CONDUCTORS ARE NOT APPROVED. CONDUCTORS SHALL BE #12 MINIMUM, EXCEPT FOR CONTROLS AND FIXTURE WIRE. SOLID FOR #10 AND SMALLER CONDUCTORS, STRANDED
FOR #8 AND LARGER.
B. FEEDERS: BRANCH CIRCUITS, CLASS 1 AND CLASS 2 CIRCUITS SHALL BE INSULATION TYPE XHHW OR THWN.
C. MAINTAIN STANDARD COLOR CODING OF BLACK, RED AND BLUE FOR 120/208 VOLT, 3 PHASE WIRING AND BROWN, ORANGE
AND YELLOW FOR 277/480 VOLT, 3 PHASE WIRING. COLOR CODING SHALL MATCH EXISTING FACILITIES WHERE THE COLOR
CODING IS NOT STANDARD. WHITE NEUTRAL AND GREEN GROUND.
D. CONCEAL CABLES IN FINISHED WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE INDICATED. INSTALL EXPOSED CABLES PARALLEL AND PERPENDICULAR TO SURFACES OF EXPOSED STRUCTURAL MEMBERS AND FOLLOW SURFACE CONTOURS
WHERE POSSIBLE.
E. MAKE SPLICES AND TAPS THAT ARE COMPATIBLE WITH CONDUCTOR MATERIAL AND THAT POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION RATINGS THAN UNSPLICED CONDUCTORS. SERVICE ENTRANCE AND PANEL FEEDERS SHALL NOT BE SPLICED. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A AND UL 486B.
F. WIRING AT OUTLETS: INSTALL CONDUCTOR AT EACH OUTLET WITH AT LEAST 12 INCHES OF SLACK. WIRING IN LIGHT POLE
HANDHOLES: PROVIDE AT LEAST 18" OF SLACK AT HANDHOLE.
260526 - GROUNDING AND BONDING:
A. GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL CODES AND
REQUIREMENTS.
B. FEEDERS AND BRANCH CIRCUITS SHALL HAVE INSTALLED IN THE SAME RACEWAY AS THE CIRCUIT CONDUCTORS, AN
INSULATED COPPER GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC.
C. DESCRIPTION OF SYSTEM: IN GENERAL, ALL ELECTRICAL EQUIPMENT (METALLIC CONDUIT, MOTOR FRAMES, PANEL BOARDS, ETC.) SHALL BE BONDED TOGETHER WITH A GREEN INSULATED OR BARE COPPER SYSTEM GROUNDING CONDUCTOR IN ACCORDANCE WITH SPECIFIC RULES OF ARTICLE 250 OF THE N.E.C. EQUIPMENT GROUNDING CONDUCTORS THROUGH THE RACEWAY. SYSTEM SHALL BE CONTINUOUS FROM MAIN SWITCH GROUND BUS TO PANEL GROUND BAR OF EACH PANEL BOARD AND FROM PANEL GROUNDING BAR OF EACH PANEL BOARD TO BRANCH CIRCUIT EQUIPMENT AND DEVICES. CONNECTORS LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING LABORATORY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION FOR APPLICATIONS IN WHICH USE AND FOR SPECIFIC TYPES, SIZES AND COMBINATIONS OF CONDUCTORS AND OTHER ITEMS CONNECTED. ALL FEEDER METALLIC CONDUITS AND FLEXIBLE METAL CONDUITS CONNECTIONS TO PANEL CABINETS, EQUIPMENT CABINETS, TRANSFORMER ENCLOSURES, ETC. SHALL
BE PROVIDED WITH GROUNDING BUSHINGS.
D. ELECTRICAL ROOM GROUND BUSS BARS: NEWTON INSTRUMENT COMPANY INSULATED GROUND BAR, MINIMUM SIZE 1/4" x 4" x 10", COPPER, MANUFACTURER PRE-DRILLED HOLES. ALL GROUND BUSS BARS SHALL BE BONDED TO MAIN ELECTRICAL GROUND BUSS BAR WITH MINIMUM 3/0 COPPER GROUND OR SIZED PER CODE FOR A CONTINUOUS COPPER GROUNDING SYSTEM. UTILIZING BUILDING STEEL OR FOOTING IS NOT ACCEPTABLE. TELECOMMUNICATIONS, IDF, DATA, COMPUTER AND SIMILAR ROOMS: NEWTON INSTRUMENT COMPANY INSULATED GROUND BAR, 1/4" x 4" x 20", COPPER, MANUFACTURER PRE-DRILLED HOLES. BOND GROUND BUSS BAR TO MAIN ELECTRICAL GROUND BUSS BAR WITH MINIMUM 3/0 AWG
COPPER.
E. GROUNDING RODS: COPPER-CLAD STEEL, SECTIONAL TYPE; 3/4" INCH IN DIAMETER x 10 FEET. PROVIDE ADDITIONAL LENGTHS IN 10' SECTIONS TO ACHIEVE SPECIFIED MINIMUM RESISTANCE TO GROUND, MEASURED IN OHMS, AT BUILDING SERVICES GROUNDING SYSTEMS. EXOTHERMIC CADWELD SHALL BE USED FOR BUILDING GROUNDING SYSTEM
CONNECTION TO DRIVEN GROUND RODS.
F. GROUNDING AND BONDING FOR PIPING: METAL WATER SERVICE PIPE: INSTALL INSULATED COPPER GROUNDING CONDUCTORS, IN CONDUIT, FROM BUILDING'S MAIN SERVICE EQUIPMENT OR GROUNDING BUSS, TO MAIN METAL WATER SERVICE ENTRANCES TO BUILDING. BOND EACH ABOVE GROUND PORTION OF GAS PIPING SYSTEM DOWNSTREAM FROM EQUIPMENT SHUT-OFF VALVE. CONCRETE ENCASED ELECTRODE IN BUILDING FOOTER SHALL BE A BARE CONDUCTOR, SAME SIZE AS THE BUILDING SYSTEMS GROUNDING CONDUCTOR, ROUTED MINIMUM 20' AND TIE WIRED TO THE
REINFORCING BARS.
G. PERFORM GROUNDING TEST: PERFORM TESTS BY FALL-OF-POTENTIAL METHOD ACCORDING TO IEEE 81, USING MEGOHMETER. REPORT MEASURED GROUND RESISTANCES THAT EXCEED 5 OHMS. EXCESSIVE GROUND RESISTANCE: IF RESISTANCE TO GROUND EXCEEDS 5 OHMS, PROVIDE ADDITIONAL DRIVEN GROUNDING RODS UNTIL THE MEASURED
GROUND RESISTANCE DOES NOT EXCEED 5 OHMS.
260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS:
A. HANGERS AND SUPPORTS FOR ELECTRICAL EQUIPMENT AND RACEWAYS SHALL COMPLY WITH THE NEC AND NECA 1 AND NECA 101. SPACE SUPPORTS FOR EMT, IMC AND RMC AS REQUIRED BY THE NEC. MINIMUM ROD SIZE SHALL BE 1/4 INCH IN
DIAMETER.
B. CONDUIT AND CABLE SUPPORT DEVICES: STEEL HANGERS, CLAMPS AND ASSOCIATED FITTINGS, DESIGNED FOR TYPES AND SIZES OF RACEWAY OR CABLE TO BE SUPPORTED. EXTERIOR AND WET LOCATIONS SHALL BE STAINLESS STEEL OR
ALUMINUM WITH STAINLESS STEEL HARDWARE.
C. SUPPORT FOR CONDUCTORS IN VERTICAL CONDUIT: FACTORY - FABRICATED ASSEMBLY CONSISTING OF THREADED BODY AND INSULATING WEDGING PLUG OR PLUGS FOR NON-ARMORED ELECTRICAL CONDUCTORS OR CABLES IN RISER CONDUITS. PLUGS SHALL HAVE NUMBER, SIZE AND SHAPE OF CONDUCTOR GRIPPING PIECES AS REQUIRED TO SUIT
CABLES SUPPORTED.
D. MOUNTING, ANCHORING AND ATTACHMENT COMPONENTS: ITEMS FOR FASTENING ELECTRICAL ITEMS OR THEIR SUPPORTS TO BUILDING SURFACES INCLUDE: MECHANICAL EXPANSION ANCHORS, INSERT - WEDGE TYPE, ZINC-COATED STEEL OR STAINLESS STEEL FOR USE IN HARDENED PORTLAND CEMENT CONCRETE WITH TENSION, SHEAR AND PULLOUT CAPACITIES APPROPRIATE FOR SUPPORTED LOADS AND BUILDING MATERIALS IN WHICH USED. CONCRETE INSERTS, STEEL OR MALLEABLE-IRON, SLOTTED SUPPORT SYSTEM UNITS SIMILAR TO MSS TYPE 18, COMPLYING WITH MFMA-4 OR MSS SP-58. CLAMPS FOR ATTACHMENT TO STEEL STRUCTURAL ELEMENTS, MSS SP-58, TYPE SUITABLE FOR ATTACHED STRUCTURAL ELEMENT. THROUGH BOLTS, STRUCTURAL TYPE, HEX HEAD AND HIGH STRENGTH. COMPLY WITH ASTM A-325. TOGGLE BOLTS, ALL STEEL SPRINGHEAD TYPE. HANGER RODS, THREADED STEEL. MOUNTING APPARATUS FOR EXTERIOR APPLICATIONS SHALL BE STAINLESS STEEL. EXTERIOR LOCATED SUPPORT APPARATUS SHALL CONSIST OF DIRECT BURIAL CONCRETE POSTS, STAINLESS STEEL OR ALUMINUM CHANNEL AND STAINLESS STEEL SPRINGS, BOLTS, WASHERS, ETC.
E. MULTIPLE RACEWAYS OR CABLES SHALL HAVE L-TRAPEZE TYPE SUPPORTS FABRICATED WITH STEEL SLOTTED OR OTHER SUPPORT SYSTEM, SIZED SO CAPACITY CAN BE INCREASED BY AT LEAST 25 PERCENT IN FUTURE WITHOUT EXCEEDING SPECIFIED DESIGN LOAD LIMITS. SECURE RACEWAYS AND CABLES TO THESE SUPPORTS WITH TWO-BOLT CONDUIT CLAMPS USING SPRING FRICTION ACTION FOR RETENTION IN SUPPORT CHANNEL. SPRING-STEEL CLAMPS DESIGNED FOR SUPPORTING SINGLE CONDUITS WITHOUT BOLTS MAY BE USED FOR 1-1/2 INCH AND SMALLER RACEWAYS SERVING
BRANCH CIRCUITS AND COMMUNICATION SYSTEMS ABOVE SUSPENDED CEILINGS.
F. SUPPORTING RACEWAYS VIA OTHER RACEWAYS CABLE TRAYS AND WIREWAYS ARE NOT APPROVED.
260533 - RACEWAYS AND BOXES:
A. LISTING AND LABELING: METAL CONDUITS AND NON-METALLIC CONDUITS, TUBING AND FITTINGS SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70 AND MARKED FOR INTENDED LOCATION AND APPLICATION.CONDUIT GENERAL: RIGID SHALL BE MINIMUM 1", GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING, E.M.T. SHALL BE MINIMUM 3/4" AND SHALL BE
ELECTRO-GALVANIZED. PROVIDE MINIMUM 1" CONDUIT WITH 4" SQUARE BACK BOX FOR DATA.
B. CONDUITS SHALL BE AS MANUFACTURED BY ALLIED, PITTSBURGH STANDARD, REPUBLIC, THOMAS & BETTS, TRIANGLE, WHEATLAND OR YOUNGSTOWN.
C. PROVIDE END BUSHINGS ON ALL CONDUITS. PROVIDE PULL STRINGS IN ALL EMPTY RACEWAYS. PULL STRINGS SHALL BE NYLON AND SHALL BE IMPERVIOUS TO MOISTURE. PULL STRINGS SHALL HAVE A TENSILE STRENGTH NOT LESS THAN 200 LBS. METALLIC RACEWAY MAY BE BONDED TO CABINETS, BOXES AND PANELBOARDS BY DOUBLE LOCKNUT AND BUSHING
TO ENSURE THE METALLIC PARTS ARE ALL EFFECTIVELY GROUNDED.
D. CONDUIT ABOVE GRADE OR CONCEALED IN WALLS SHALL BE EMT (INTERIOR ONLY), IMC OR GALVANIZED. CONDUIT BELOW GRADE SHALL BE RIGID GALVANIZED (HEAVY WALL), IMC OR PVC (SCHEDULE 40). CONNECTION TO VIBRATING EQUIPMENT, (INCLUDING TRANSFORMERS AND HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID OR MOTOR-DRIVEN EQUIPMENT), FMC, EXCEPT USE LFMC IN DAMP OR WET LOCATIONS, MAXIMUM LENGTH 72 INCHES. CONCEAL CONDUIT WITHIN FINISH WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE INDICATED.
E. CONDUIT OUTSIDE AND EXPOSED TO PHYSICAL DAMAGE OR IN DAMP OR WET LOCATIONS SHALL BE RIGID GALVANIZED
(HEAVY WALL).
F. SEALANT: PROVIDE A CLOSED CELL SILICONE FOAM SEALANT RATED TO PROVIDE A RATING EQUAL TO THE WALL, CEILING OR FLOOR ASSEMBLY RATING. PROVIDE SEALS FOR THE EXTERIOR OF CONDUIT PENETRATIONS CONSISTING OF A CAST- IN-PLACE SLEEVE WITH A COMPRESSIBLE RUBBER GASKET BETWEEN THE CONDUIT AND THE SLEEVE. PROVIDE SEALS FOR THE INTERIOR OF THE CONDUIT PENETRATIONS CONSISTING OF GLAND TYPE SEALING BUSHING OR CLOSED CELL SILICONE FOAM. PROVIDE DUCT SEAL INSIDE AN APPROPRIATE SEAL-OFF FITTING TO SEAL THE INTERIOR OF THE
CONDUIT SYSTEM FROM WATER SEEPAGE OR HAZARDOUS GASES.
G. COUPLINGS: ALL COUPLINGS AND CONNECTORS FOR EMT SHALL BE OF COMPRESSION TYPE.
H. OUTLET SHALL BE STANDARD TYPE WITH KNOCKOUTS, MADE OF HOT DIPPED GALVANIZED STEEL AS MANUFACTURED BY
STEEL CITY, RACO OR APPLETON. BOX EXTENSIONS USED TO ACCOMMODATE NEW BUILDING FINISHES SHALL BE OF SAME
MATERIAL AS RECESSED BOX.
I. CEILING OUTLET BOXES SHALL BE 4 INCH OCTAGON, 1-1/2 INCH DEEP OR LARGER WHEN REQUIRED DUE FOR NUMBER OF CONDUCTORS OR CONDUIT ENTRY. LUMINAIRE OUTLET BOXES: NON-ADJUSTABLE, DESIGNED FOR ATTACHMENT OF LUMINAIRE WEIGHING 50 LB. OUTLET BOXES DESIGNED FOR ATTACHMENT OF LUMINAIRES WEIGHTING MORE THAN 50 LB.
SHALL BE LISTED AND MARKED FOR THE MAXIMUM ALLOWABLE WEIGHT.
J. OUTLET BOXES SHALL BE PROVIDED WITH APPROVED 3/8 INCH FIXTURE STUDS WHERE REQUIRED. PROVIDE JUNCTION OR PULL BOXES WHERE SHOWN ON THE DRAWINGS AS REQUIRED TO FACILITATE INSTALLING CONDUCTORS. BOXES SHALL BE SIZED IN ACCORDANCE WITH THE NEC. ALL JUNCTION BOXES SHALL BE ACCESSIBLE, HORIZONTALLY SEPARATE BOXES MOUNTED ON OPPOSITE SIDES OF WALLS SO THEY ARE NOT IN THE SAME VERTICAL CHANNEL AND TO MAINTAIN WALL
FIRE RATING.
K. METAL FLOOR BOXES: CAST METAL FOR SLAB ON SLAB ON GRADE OR SHEET METAL, FULLY ADJUSTABLE, RECTANGULAR.
METAL FLOOR BOXES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY AND
MARKED FOR INTENDED LOCATION AND APPLICATION.
260544 - SLEEVES AND SEALS FOR ELECTRICAL RACEWAYS AND CABLING:
A. COORDINATE SLEEVE SELECTION AND APPLICATION FOR RACEWAYS AND CABLES THROUGH FIRE RATED PENETRATIONS WITH 'THROUGH-PENETRATION FIRESTOP SYSTEMS' SPECIFIED IN ARCHITECTURAL DRAWINGS AND SPECIFICATIONS. FOR FIRE-RATED ASSEMBLY PENETRATIONS, MAINTAIN INDICATED FIRE RATING OF WALLS, PARTITIONS, CEILINGS AND FLOORS AT CABLE PENETRATIONS. INSTALL SLEEVES AND SEAL WITH FIRESTOP MATERIALS ACCORDING TO LISTING.
B. SLEEVE INSTALLATION FOR NON-FIRE-RATED ELECTRICAL PENETRATIONS: WALL SLEEVES, GALVANIZED-STEEL SHEET;
0.0239 INCH MINIMUM THICKNESS; ROUND TUBE CLOSED WITH TABS FOR SCREW-FASTENING THE SLEEVE TO THE BOARD.
SLEEVES FOR RECTANGULAR OPENINGS: FOR SLEEVE CROSS-SECTION RECTANGLE PERIMETER LESS THAN 50 INCHES AND WITH NO SIDE LARGER THAN 16 INCHES, THICKNESS SHALL BE 0.052 INCH FOR SLEEVE CROSS-SECTION RECTANGLE PERIMETER 50 INCHES OR MORE AND ONE OR MORE SIDES LARGERS THAN 16 INCHES, THICKNESS SHALL BE 0.138 INCH.
CUT SLEEVES TO LENGTH FOR MOUNTING FLUSH WITH BOTH WALL SURFACES. EXTEND SLEEVES INSTALLED IN FLOORS 2 INCHES ABOVE FINISHED FLOOR LEVEL. SIZE PIPE SLEEVES TO PROVIDE 1/4 INCH ANNULAR CLEAR SPACE BETWEEN SLEEVE AND CABLE UNLESS SLEEVE SEAL IS TO BE INSTALLED. SEAL SPACE OUTSIDE OF SLEEVES WITH GROUT FOR PENETRATIONS OF CONCRETE AND MASONRY AND WITH APPROVED JOINT COMPOUND FOR GYPSUM BOARD ASSEMBLIES.
ROOF PENETRATION SLEEVES - SEAL PENETRATION OF INDIVIDUAL CABLES WITH FLEXIBLE BOOT-TYPE FLASHING UNITS APPLIED IN COORDINATION WITH ROOFING WORK. ABOVE GROUND EXTERIOR-WALL PENETRATIONS - SEAL PENETRATIONS USING SLEEVES AND MECHANICAL SLEEVE SEALS AND SIZE SLEEVES TO ALLOW FOR 1 INCH ANNULAR CLEAR SPACE BETWEEN PIPE AND SLEEVE FOR INSTALLING MECHANICAL SLEEVE SEALS. UNDERGROUND EXTERIOR-WALL PENETRATIONS - INSTALL CAST-IRON 'WALL PIPES' FOR SLEEVES, SIZE SLEEVES TO ALLOW FOR 1 INCH ANNULAR CLEAR
SPACE BETWEEN CABLE AND SLEEVE FOR INSTALLING MECHANICAL SLEEVE SEALS.
260553 - ELECTRICAL IDENTIFICATION:
A. NAMEPLATES: ENGRAVED PLASTIC LAMINATE NAMEPLATES: PROVIDE ENGRAVING PHENOLIC PLASTIC LAMINATE IN SIZES AND THICKNESS INDICATED, ENGRAVED WITH 1/16 INCH THICK LINES WITH SQUARE STANDARD PICA LETTERING AND WORDING AS SPECIFIED HEREIN, BLACK FACE AND WHITE LETTER FOR NORMAL SYSTEMS AND RED AND WHITE FOR EMERGENCY AND FIRE ALARM SYSTEMS. PUNCH FOR MECHANICAL FASTENING, EXCEPT WHERE ADHESIVE MOUNTING IS NECESSARY BECAUSE OF SUBSTRATE. MATERIAL THICKNESS SHALL BE 1/16 INCH. PROVIDE BEVELED EDGE IN ORDER TO ELIMINATE SHARP CORNERS. PROVIDE SELF-TAPPING STAINLESS STEEL ROUND HEAD SCREWS. PROVIDE CONTACT TYPE PERMANENT ADHESIVE WHERE SCREWS CANNOT OR SHALL NOT PENETRATE THE SUBSTRATE. ADHESIVE NAMEPLATE SHALL BE PERMANENTLY INSTALLED. TITLES SHALL BE 1/2" INCH HIGH AND ALL OTHER LETTERING SHALL BE 1/4 INCH HIGH.
B. JUNCTION BOX IDENTIFICATION: PROVIDE NEAT INDELIBLE FELT TIP, STENCILED MARKING ON JUNCTION BOXES. LETTER SIZES SHALL BE 1 INCH HIGH MINIMUM. PROVIDE NON-STENCILED MARKINGS INSIDE THE JUNCTION BOX. LABEL TO
INDICATE THE CIRCUITS CONTAINED THEREIN.
C. PULLBOX IDENTIFICATION: PROVIDE NEAT INDELIBLE FELT TIP, STENCILED MARKING ON PULLBOX COVERS. LETTER SIZES SHALL BE 1 INCH HIGH MINIMUM. PROVIDE NON-STENCILED MARKINGS INSIDE THE PULLBOX AND ON THE EXTERIOR EDGE TO MATCH THE COVER MARKINGS. LABEL TO INDICATE THE CIRCUITS CONTAINED THEREIN, SOURCE PANEL AND
DESTINATION.
262416 - PANELBOARDS:
A. ELECTRICAL COMPONENTS, DEVICES AND ACCESSORIES: LISTED AND LABELED AS DEFINED IN NFPA 70 BY A QUALIFIED TESTING AGENCY AND MARKED FOR INTENDED LOCATION AND APPLICATION. PANELBOARDS SHALL BE AS
MANUFACTURED BY EATON, GENERAL ELECTRIC, SIEMENS OR SQUARE D.
B. PROVIDE PANELBOARDS WITH MAIN BREAKER OR MAIN LUBS WHERE SHOWN ON THE DRAWINGS, OF A DEAD FRONT, DISTRIBUTED PHASE SEQUENCE DESIGN. PROVIDE WITH COPPER BUSES. PANELBOARDS SHALL BE EQUIPPED WITH HINGED TRIM FRONT COVER AND KEYED ALIKE. PANELBOARDS CAN BE EITHER FULLY RATED OR SERIES RATED.
C. DISTRIBUTION TYPE PANELBOARDS SHALL BE USED FOR 600 AMP AND LARGER PANELBOARDS. CIRCUIT BREAKERS AND MAIN CIRCUIT BREAKERS SHALL BE ELECTRONIC TRIP CIRCUIT BREAKERS WITH RMS SENSING, FIELD REPLACEABLE RATING PLUG OR ELECTRONIC TRIP WITH FIELD ADJUSTABLE SETTINGS FOR INSTANTANEOUS TRIP, LONG AND SHORT- TIME PICKUP AND ADJUSTABLE LEVELS. FRAME AND TRIP SIZES INDICATED IN THE SCHEDULES. MAIN CIRCUIT BREAKERS
SHALL BE 100 PERCENT RATED MAINS.
D. LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS SHALL BE USED FOR 400 AMP AND SMALLER PANELBOARDS UNLESS OTHERWISE NOTED. CIRCUIT BREAKERS SHALL BE BOLT-ON QUICK-MAKE, QUICK-BREAK THERMAL-MAGNETIC TYPE WITH FRAME AND TRIP SIZES INDICATED IN THE SCHEDULES. ADJUSTABLE MAGNETIC TRIP SETTING FOR CIRCUIT- BREAKER FRAME SIZES 250 AMP AND LARGER. BREAKERS SHALL TRIP FREE OF THE HANDLE AND TRIPPING SHALL BE INDICATED BY THE HANDLE ASSUMING A POSITION BETWEEN OFF AND ON. MULTI-POLE BREAKERS SHALL BE INTERNAL, COMMON TRIP WITH SINGLE OPERATING HANDLE; EXTERNAL HANDLE TIES ARE NOT ACCEPTABLE.
E. FOR FLUSH MOUNTED PANELBOARDS STUB FOUR (4) 1 INCH EMPTY CONDUITS FROM PANELBOARD INTO ACCESSIBLE CEILING SPACE OR SPACE DESIGNATED TO BE CEILING SPACE IN THE FUTURE. ARRANGE CONDUCTORS IN GUTTERS INTO
GROUPS AND BUNDLE AND WRAP WITH WIRE TIES.
F. FIELD QUALITY CONTROL: PERFORM TESTS AND INSPECTIONS. TEST INSULATION RESISTANCE FOR EACH PANELBOARD BUSS, COMPONENT, CONNECTING SUPPLY, FEEDER AND CONTROL CIRCUIT. TEST CONTINUITY OF EACH CIRCUIT.
PERFORM EACH VISUAL AND MECHANICAL INSPECTION AND ELECTRICAL TEST STATED IN NETA ACCEPTANCE TESTING SPECIFICATION. CERTIFY COMPLIANCE WITH TEST PARAMETERS AND CORRECT MALFUNCTIONING UNITS ON-SITE, WHERE POSSIBLE AND RE-TEST TO DEMONSTRATE COMPLIANCE; OTHERWISE, REPLACE WITH NEW UNITS AND RE-TEST.
G. DIRECTORIES: A TYPE PANELBOARD DIRECTORY SHALL BE PROVIDED FOR EACH PANELBOARD AND SHALL INDICATE THE ACTUAL CIRCUIT NUMBER USED, ROOM NAME AND TYPE OF LOAD. ROOM NAMES SHALL BE THE ACTUAL NAME OR ROOM NUMBER USED NOT NECESSARILY AS SHOWN ON THE DRAWINGS. WHERE PANEL SCHEDULES ARE INDICATED ON THE DRAWINGS AS 'RECEPTACLES' OR 'LIGHTING', ETC. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INCLUDE
THE SPECIFIC AREA SERVED.
262726 - WIRING DEVICES:
A. WIRING DEVICES, COMPONENTS AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70 BY A QUALIFIED TESTING AGENCY AND MARKED FOR INTENDED LOCATION AND APPLICATION. WIRING DEVICES SHALL BE AS
MANUFACTURED BY COOPER, HUBBELL, LEVITON OR PASS & SEYMOUR.
B. PROVIDE WHITE COLORED DEVICES FOR NORMAL POWER, UNLESS OTHERWISE NOTED. PROVIDE RED COLORED DEVICES FOR EMERGENCY POWER. PROVIDE BRUSHED STAINLESS STEEL COVER PLATES. COORDINATE WITH ARCHITECT FOR
FINAL COLOR SELECTION OF DEVICES AND COVER PLATES.
C. RECEPTACLES: SPECIFICATION GRADE 20 AMP, 125 VOLT, 3 WIRE GROUNDED, MOUNTED AT 18" A.F.F. TO THE CENTERLINE
UNLESS NOTED OTHERWISE. COLOR SHALL MATCH TOGGLE SWITCHES.
D. TOGGLE SWITCHES: HEAVY DUTY SPECIFICATION GRADE 20 AMP, 120/277 VAC, HEAVY DUTY, QUIET TYPE: SINGLE POLE, TWO POLE, THREE WAY OR FOUR WAY AS REQUIRED FOR APPLICATION.
E. FLUORESCENT DIMMERS: PRESET SLIDE CONTROL: LUTRON OR EQUIVALENT, COMPATIBLE WITH DIMMABLE BALLAST.
F. OCCUPANCY SENSOR SWITCHES, 120/277 VAC, WALL MOUNTED SINGLE POLE - LEVITON OR EQUIVALENT.
G. LED DIMMERS: PRESET SLIDE CONTROL: LUTRON OR EQUIVALENT, COMPATIBLE WITH DIMMABLE DRIVER.
H. INSTALL DEVICE PLATES IN FULL CONTACT WITH WALL SURFACE OR SURFACE MOUNTED BOX. PLATES SHALL NOT
PROJECT OUT FROM THE WALL OR FROM THE EDGE OF THE BOX.
I. ALL DEVICE PLATES FOR RECEPTACLES AND SWITCHES SHALL BE LABELED. SHOW PANEL DESIGNATION AND BRANCH
CIRCUIT SERVING EACH RECEPTACLE.
262813 - FUSES:
A. FUSES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY AND MARKED FOR INTENDED LOCATION AND APPLICATION. PANELBOARDS SHALL BE AS MANUFACTURED BY COOPER BUSSMANN, FERRAS SHAWMUT, LITTLEFUSE OR EDISON. FUSES SHALL BE NON-RENEWABLE CARTRIDGE TYPE RATED 600 V AC AND LESS FOR USE IN ENCLOSED SWITCHES, FUSIBLE PANELBOARDS, SWITCHBOARDS, ENCLOSED CONTROLLERS, MOTOR CONTROL
CENTERS AND CONTROL CIRCUITS.
B. FUSE APPLICATIONS: SERVICE ENTRANCE, CLASS L, TIME DELAY. FEEDERS, CLASS RK5, FAST ACTING. MOTOR BRANCH CIRCUITS AND OTHER BRANCH CIRCUITS: CLASS RK5, TIME DELAY. CONTROL CIRCUITS: CLASS CC, TIME DELAY.
C. INSTALLATION: INSTALL FUSES IN FUSIBLE DEVICES. ARRANGE FUSES SO RATING INFORMATION IS READABLE WITHOUT REMOVING FUSE. FUSES SHALL BE SIZED IN ACCORDANCE WITH THE MANUFACTURER'S MAXIMUM OVER-CURRENT
NAMEPLATE RATING.
262816 - ENCLOSED SWITCHES:
A. GENERAL: ALL DISCONNECT SWITCHES SHALL BE HEAVY-DUTY TYPE, UNLESS SPECIFICALLY NOTED OTHERWISE.
SWITCHES SHALL BE FUSIBLE OR NON-FUSIBLE AND SIZED AS NOTED ON THE DRAWINGS.
B. SWITCHES SHALL BE 240 VOLT RATED ON SYSTEMS UP TO AND INCLUDING 120/240V. ALL SWITCHES SERVING MOTOR LOADS SHALL BE HORSEPOWER RATED. ALL SWITCHES SERVING VFD'S SHALL HAVE AN AUXILIARY CONTACT TO DIS-
ENGAGE THE VFD WHEN SWITCHED OFF.
C. PROVIDE SWITCHES WITH AN EXTERNALLY OPERATED HANDLE: QUICK MAKE QUICK BREAK MECHANISM; THE HANDLE SHALL BE INTERLOCKED WITH THE SWITCH COVER BY MEANS OF A DEFEATABLE INTERLOCK DEVICE. THE SWITCH SHALL
BE LOCKABLE IN THE 'OFF' POSITION WITH A PADLOCK.
265100 - INTERIOR LIGHTING:
A. LUMINAIRES SHALL BE FURNISHED AS SHOWN IN THE LUMINAIRE SCHEDULE AND BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY AND MARKED FOR INTENDED LOCATION AND APPLICATION. IT SHALL SPECIFICALLY BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY EXACT TYPE OF CEILING AND RECESSING DEPTH OF ALL RECESSED FIXTURES AND TO FURNISH THE MOUNTING TRIMS AND ACCESSORIES OF THE SPECIFIED AND / OR APPROVED FIXTURES FOR THE CEILING TO BE INSTALLED. FIXTURES SHALL BE SUPPORTED INDEPENDENTLY OF CEILING
SYSTEMS.
B. LED LUMINAIRES SHALL BE UL 8750 LISTED AND TESTED IN ACCORDANCE WITH LM-79 AND LM-80 STANDARDS. THE LED LUMINAIRE SHALL HAVE A LUMINOUS EFFICACY OF AT LEAST 90 LUMENS / W, A COLOR TEMPERATURE OF 3500K OR 4000K, A CRI OF AT LEAST 80, AN ESTIMATED LIFE OF AT LEAST 50,000 HOURS AT L70 LUMEN MAINTENANCE AND SHALL INCLUDE A
MINIMUM 5 YEAR WARRANTY ON THE ENTIRE LUMINAIRE INCLUDING THE DRIVER.
265600 EXTERIOR LIGHTING:
A. LUMINAIRES SHALL BE FURNISHED AS SHOWN IN THE LUMINAIRE SCHEDULE AND COMPLY WITH UL 1598 AND BE LISTED AND LABELED FOR INSTALLATION IN WET LOCATIONS AS DEFINED IN NFPA 70 AND MARKED FOR INTENDED LOCATION AND APPLICATION. LATERAL LIGHT DISTRIBUTION SHALL COMPLY WITH IESNA RP-8. THE CONTRACTOR SHALL FURNISH STAINLESS STEEL MOUNTING HARDWARE AND REQUIRED ACCESSORIES OF THE SPECIFIED AND / OR APPROVED
FIXTURES.
B. LED LUMINAIRES SHALL BE UL 8750 LISTED AND TESTED IN ACCORDANCE WITH LM-79 AND LM-80 STANDARDS. THE LED LUMINAIRE SHALL HAVE A LUMINOUS EFFICACY OF AT LEAST 90 LUMENS/W, A COLOR TEMPERATURE OF 3500K OR 4000 K, A CRI OF AT LEAST 80, AN ESTIMATED LIFE OF AT LEAST 50,000 HOURS AT L70 LUMEN MAINTENANCE AND SHALL INCLUDE A
MINIMUM 5-YEAR WARRANTY ON THE ENTIRE LUMINAIRE INCLUDING THE DRIVER.
A. LEGEND SHEET AND NOT ALL SYMBOLS MAY BE USED ON DRAWINGS.
B. REFERENCE PLAN SHEETS TO DETERMINE REQUIRED SCOPE OF WORK.
C. THE DRAWINGS ARE DIAGRAMMATIC, AND NOT ALL REQUIRED OFFSETS IN
CONDUIT, CABLE TRAY, BOXES, AND PATHWAY TRANSITIONS ARE SHOWN.
COORDINATE EXACT DIMENSIONAL LOCATIONS WITH EXISTING CONDITIONS
AND OTHER TRADES PRIOR TO INSTALLATION.
D. PROVIDE A MINIMUM OF ONE PULL BOX FOR EVERY 100 FEET OF STRAIGHT
CONDUIT RUNS AND A PULL BOX FOR MORE THAN TWO (2) 90 DEGREE
BENDS IN A CONDUIT RUN. DEBURR, CLEAN, CAP, AND TAG ALL CONDUITS
AND FURNISH WITH A MINIMUM OF TWO (2) PULL STRINGS.
E. INSTALL DEVICES IN AN ORDERLY MANNER AT THE SAME ELEVATION AS
ADJACENT DEVICES, COORDINATED BETWEEN TRADES. WHERE INSTALLED
DEVICES FEED OR ARE ASSOCIATED WITH FURNITURE, COORDINATE EXACT
LOCATIONS WITH FINAL FURNITURE PLAN AND CASEWORK INSTALLER,
PRIOR TO INSTALLATION.
F. COORDINATE OSP / UNDERGROUND COMMUNICATION PATHWAYS WITH CIVIL
ENGINEER PRIOR TO INSTALLATION. COORDINATE OSP / UNDERGROUND
COMMUNICATION PATHWAYS INTO BUILDING WITH STRUCTURAL ENGINEER
PRIOR TO INSTALLATION. WHERE POSSIBLE COLLATE COMMUNICATIONS
OSP / UNDERGROUND PATHWAYS WITH ELECTRICAL OSP / UNDERGROUND
PATHWAYS, U.O.N.
G. COORDINATE ALL REQUIRED CABLING AND COMPONENTS WITH SYSTEM
VENDOR AND/OR INSTALLER.
H. ALL 120V POWER WIRING SHALL BE INSTALLED IN A SEPARATE CONDUIT.
I. ALL CONDUIT ABOVE GRADE SHALL BE METALLIC, ALL CONDUIT BELOW
GRADE SHALL BE PVC UNLESS OTHERWISE NOTED ON DRAWINGS.
J. ALL CONDUIT, WIRING AND ASSOCIATED BACK BOXES SHALL BE FULLY
CONCEALED WITHIN WALLS, FLOORS AND CEILINGS.
K. THE MAXIMUM PULLING TENSION SHALL NOT EXCEED 25 POUNDS TO AVOID
STRETCHING THE CONDUCTORS.
L. COORDINATE LOCATION OF ALL FIRE RATED PENETRATIONS PRIOR TO
PROCEEDING WITH INSTALLATION. ALL PENETRATIONS THROUGH FIRE
RATED BARRIERS SHALL BE COMPLETELY SEALED WITH A LISTED FIRE STOP
SYSTEM IN ACCORDANCE WITH NFPA AND THE AUTHORITY HAVING
JURISDICTION.
M. COORDINATE EXTERIOR AND WALL MOUNTED CAMERA LOCATIONS AND
MOUNTING HEIGHTS PRIOR TO ROUGH-IN. COORDINATION MEETINGS SHALL
BE SCHEDULED THROUGH THE ARCHITECTS AND/OR OWNER.
GENERAL SYSTEM NOTES
FLORIDA LIC No: AR95989
Carbon design & architecture 263 13th Avenue South Suite 375 St. Petersburg, FL 33701 O:: 941.362.4312 W:: www.carbonAE.com
Project No:
PROJECT DATA
Project Na:
CLIENT DATA
Client:
ARCHITECT DATA
ENGINEER DATA
ISSUE + REVISION DATA
ENGINEER SEAL
CHECKED BY
DRAWN BY
PRINTED:24X36 SHEET
ARCH D
EOR: JULIUS D. DAVIS, P.E. #58005
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIUS D. DAVIS,
P.E. #58005 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES
6005 Benjamin Rd.
Suite A Tampa, FL 33634 O:: 888.891.9713 W:: www.voltairinc.com
COA: #27158
Proj: #01.22029
TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY
WITH THE APPLICABLE MINIMUM BUILDING CODES
8/12/2024 4:45:49 PM
8/12/2024 4:45:49 PM
E-001
SPECIFICATIONS - ELECTRICAL
100% CD's Set
05.28.2024
24020
OCALA SUNTRAN
RESTROOMS & KIOSK
CITY OF OCALA
501 NE 1st Ave.
Ocala, FL 34470
R.F.W.
R.F.W.
LUMINAIRE SCHEDULE
IMAGE TYPE DESCRIPTION MANUFACTURER MOUNTING LUMENS LAMP/WATTAGE VOLTAGE
A 2X2 LUMINAIRE (CCT SWITCH TO 3500K)DAYBRITE: 2SBP3040L8CS 2 UNV DIM
RECESSED 4207 LED/39W MVOLT
A1
2X2 LUMINAIRE WITH DRYWALL
CEILING ADAPTOR (CCT SWITCH TO
3500K)
DAYBRITE: 2SBP3040L8CS 2 UNV DIM FMA22
B 4' STRIP FIXTURE (CCT SWITCH TO
4000K)
DAYBRITE: SDS 4 2448 8CST UNV DIM SURFACE 4850 LED/42W MVOLT
C 4' VANDAL WRAP H.E. WILLIAMS: AVX 4 L16/BLU CPC (MAX45W) DIM UNV SURFACE BLUE LED/45W MVOLT
C1 4' VANDAL WRAP H.E. WILLIAMS: AVX 4 L62 835 WPC DIM UNV WALL @ 8' AFF 6200 LED/57W MVOLT
X EXIT SIGN BEGHELLI: PX R SA SURFACE LED MVOLT
EM EMERGENCY UNIT BEGHELLI: BBX SE WH WALL 600L/HEAD LED MVOLT
WP WALL PACK (LUMEN SWITCH TO 40%
AND CCT SWITCH TO 4000K)
TRULY GREEN SOLUTIONS: WPFS S L C U D EM WALL 3404 LED/23W MVOLT
NOTES:
1. ALL INTERIOR LUMINAIRE SHALL HAVE 4000 KELVIN COLOR TEMPERATURE AND EXTERIOR 3500 KELVIN COLOR TEMPERATURE, UNLESS OTHERWISE NOTED.
2. EXIT LIGHTS SHALL BE CONNECTED TO THE NEAREST UNSWITCHED CIRCUIT.
3. FINAL FIXTURE COLORS AND FINISHES SHALL BE SELECTED AND APPROVED BY OWNER/ARCHITECT.
4. COOPER, LITHONIA , AND COLUMBIA LIGHTING MAY SUBMIT APPROVED EQUIVALENTS.
GENERAL NOTES
A. COORDINATE COLORS AND FINISHED WITH ARCHITECT AND / OR OWNER PRIOR TO
ORDERING.
B. WHERE A LUMINAIRE IS AVAILABLE IN TRIM-BASED AND TRIMLESS CONFIGURATIONS,
COORDINATE THE APPROPRIATE CONFIGURATION WITH THE ARCHITECT PRIOR TO
ORDERING.
C. COORDINATE CEILING TYPES WITH THE ARCHITECT PRIOR TO ORDERING. ONE (1)
LUMINAIRE TYPE MAY BE LOCATED WITHIN MULTIPLE CEILING TYPES. REFER TO
ARCHITECTURAL REFLECTED CEILING PLANS FOR FURTHER INFORMATION.
D. PROVIDE INDEPENDENT SUPPORTS TO THE BUILDING STRUCTURE IN ACCORDANCE WITH
THE APPLICABLE DIVISION 26 SPECIFICATION SECTIONS.
E. WHERE A LUMINAIRE IS EQUIPPED WITH A DIMMABLE DRIVER, BUT IS NOT DEPICTED AS
CONTROLLED VIA A DIMMER SWITCH ON THE LIGHTING PLANS, TERMINATE THE 0-10V
CONTROL WIRING IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS TO
ALLOW FOR ON / OFF SWITCHING.
F. VERIFY COMPATIBILITY BETWEEN DIMMER SWITCHES AND DIMMABLE DRIVERS PRIOR TO
ORDERING.
G. COORDINATE LUMINAIRE LOCATIONS, MOUNTING HEIGHTS (WHERE APPLICABLE),
SUSPENSION HEIGHTS (WHERE APPLICABLE) AND SUSPENSION METHODS (WHERE
APPLICABLE) WITH ARCHITECT PRIOR TO ORDERING, ROUGH-IN AND INSTALLATION.
H. START-UP: ELECTRICAL CONTRACTOR SHALL CONTACT LIGHTING CONTROL
MANUFACTURER AT LEAST THIRTY (30) DAYS BEFORE TURNOVER OF PROJECT. LIGHTING
CONTROL MANUFACTURER WILL BE ON SITE TO PROGRAM THE LIGHTING CONTROL
SYSTEM WITH FEEDBACK FROM OWNER.
GENERAL NOTES
A. COORDINATE ALL ELECTRICAL REQUIREMENTS WITH THE DIVISION 22 CONTRACTOR,
DIVISION 23 CONTRACTOR AND APPROVED EQUIPMENT SUBMITTALS PRIOR TO ROUGH-IN
AND INSTALLATION. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR FURTHER
INFORMATION.
B. FOR ALL VFD-DRIVEN EQUIPMENT, PROVIDE A VFD-RATED CABLE ASSEMBLY BETWEEN THE
VFD OUTPUT AND ASSOCIATED EQUIPMENT AS FOLLOWS; XLPE INSULATION RATED AT
2,000V, SHIELDED, 100% EQUIPMENT GROUND. CONDUIT AND CONDUCTORS BETWEEN
SOURCE AND VFD INPUT SHALL BE AS SCHEDULED.
FLORIDA LIC No: AR95989
Carbon design & architecture 263 13th Avenue South Suite 375 St. Petersburg, FL 33701 O:: 941.362.4312 W:: www.carbonAE.com
Project No:
PROJECT DATA
Project Na:
CLIENT DATA
Client:
ARCHITECT DATA
ENGINEER DATA
ISSUE + REVISION DATA
ENGINEER SEAL
CHECKED BY
DRAWN BY
PRINTED:24X36 SHEET
ARCH D
EOR: JULIUS D. DAVIS, P.E. #58005
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIUS D. DAVIS,
P.E. #58005 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON
ANY ELECTRONIC COPIES
6005 Benjamin Rd.
Suite A Tampa, FL 33634 O:: 888.891.9713 W:: www.voltairinc.com
COA: #27158
Proj: #01.22029
TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY
WITH THE APPLICABLE MINIMUM BUILDING CODES
8/12/2024 4:45:50 PM
8/12/2024 4:45:50 PM
E-002
SCHEDULES - ELECTRICAL
100% CD's Set
05.28.2024
24020
OCALA SUNTRAN
RESTROOMS & KIOSK
CITY OF OCALA
501 NE 1st Ave.
Ocala, FL 34470
R.F.W.
R.F.W.
ELECTRICAL MECHANICAL EQUIPMENT SCHEDULE
TAG HP LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
COMMENTSNEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
AC-1 ---- 42 VA 0.2 208 V 1 3/4" CONDUIT WITH 3#12 AND 1#12 GROUND MB 11,13 --- --- --- --- 2 --- 26 PROVIDE MOTORIZED DISCONNECT SWITCH
AC-2 ---- 42 VA 0.2 208 V 1 3/4" CONDUIT WITH 3#12 AND 1#12 GROUND MB 11,13 --- --- --- --- 2 --- 26 PROVIDE MOTORIZED DISCONNECT SWITCH
AC-3 ---- 42 VA 0.2 208 V 1 3/4" CONDUIT WITH 3#12 AND 1#12 GROUND MB 11,13 --- --- --- --- 2 --- 26 PROVIDE MOTORIZED DISCONNECT SWITCH
CU-1 ---- 3910 VA 18.8 208 V 1 1" CONDUIT WITH 3#8 AND 1#10 GROUND MB 11,13 --- --- --- 60A 2 NEMA 3R 26 PROVIDE NON-FUSED DISCONNECT SWITCH
EF-1 ---- 24 VA .2 120 V 1 3/4" CONDUIT WITH 2#12 AND 1#12 GROUND MB 7 --- --- --- --- --- --- 23 PROVIDE MOTORIZED DISCONNECT SWITCH
EF-2 ---- 24 VA .2 120 V 1 3/4" CONDUIT WITH 2#12 AND 1#12 GROUND MB 21 --- --- --- --- --- --- 23 PROVIDE MOTORIZED DISCONNECT SWITCH
ERV-1 ---- 30 VA 0.5 208 V 2 3/4" CONDUIT WITH 2#12 AND 1#12 GROUND MB 35,37 --- --- --- 30A 2 NEMA 1 26 PROVIDE NON-FUSED DISCONNECT SWITCH
EWH-1 ---- 3000 VA 14.4 208 V 2 3/4" CONDUIT WITH 3#12 AND 1#12 GROUND MB 30,32 --- --- --- 30A 2 NEMA 1 26 PROVIDE NON-FUSED DISCONNECT SWITCH
No: Description: Date:
2 PERMIT COMMENTS 08/12/24
2 2
SAN
SD
SAN
SD
SD
FE
HH
WP@ 6' 9"
WP@ 6' 9"
WP@ 6' 9"
WP@ 9' 6"
WP@ 6' 9"
WP@ 6' 9"
WP@ 6' 10"
WP@ 7' 10"
WP@ 6' 10"
Luminaire list
Index Manufacturer Article name Luminous flux Maintenance factor Connected load Quantity
WP tgs WPF-S 65W 4000K 10242 lm 0.40 62.4 W 9
Name Parameter Min Max Average Mean/Min Max/Min
Building Exterior Perpendicular illuminance
1.01 fc 32.2 fc 12.6 fc 12.39 31.83
GENERAL NOTES
A. PROVIDE IN-GRADE HANDHOLES AS REQUIRED TO INSTALL POWER AND SIGNAL CABLES.
KEY NOTES
2'-8"1
4 FLORIDA LIC No: AR95989
Carbon design & architecture 263 13th Avenue South Suite 375 St. Petersburg, FL 33701 O:: 941.362.4312 W:: www.carbonAE.com
Project No:
PROJECT DATA
Project Na:
CLIENT DATA
Client:
ARCHITECT DATA
ENGINEER DATA
ISSUE + REVISION DATA
ENGINEER SEAL
CHECKED BY
DRAWN BY
PRINTED:24X36 SHEET
ARCH D
EOR: JULIUS D. DAVIS, P.E. #58005
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIUS D. DAVIS,
P.E. #58005 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE…
This is the start of the file's text. The full file is on GovTribe.