This is a technical specification document for fiber optic cable associated with an Invitation to Bid (ITB# OFN/261008) issued by the City of Ocala, Florida through Ocala Utility Services/Resource Management for a Non-Stock Fiber Optic Cable Dearman Buildout project in Fiscal Year 2026. The specification details the AFL Flex-Span ADSS (All-Dielectric, Self-Supporting) Fiber Optic Cable (DNA-31683), a 24 single-mode fiber cable designed for aerial installation. The cable features 5 buffer tubes with color-coded fibers (12 blue and 12 orange fibers), an approximate outer diameter of 11.0 millimeters, and a cable weight of approximately 22 pounds per 1,000 feet. The specification includes comprehensive mechanical and optical performance data, including maximum rated cable loads of 587 pounds per foot breaking strength, dynamic bending radius of 17 inches, and maximum stringing tension limits. Installation requirements specify minimum bull wheel diameter of 77 inches, stringing sheave diameter of 46 inches, and maximum aerial stringing tension not to exceed 20 percent of the rated breaking strength. Sealed bids were required to be submitted electronically through the AURSI bidding system by 2:00 P.M. on August 10, 2026.
The specification document establishes rigorous standards for cable design, manufacturing compliance, and installation procedures in accordance with IEEE 1222, ITU-T G.652D/G.657.A1, and NESC/CSA standards, with RoHS compliance required. The cable is rated for environmental temperatures ranging from -50 to +70 degrees Celsius for storage, -40 to +70 degrees Celsius for operation, and -30 to +70 degrees Celsius for installation. Attenuation characteristics are specified at 0.35 dB/km at 1310 nanometers and 0.25 dB/km at 1550 nanometers. The document provides detailed reel capacity information for both wood and steel reels, ranging from 58 to 84 inches in flange diameter, with capacities up to 300-416 kilometers depending on reel type. Installation procedures and handling recommendations reference AFL's official installation instructions and video resources. Inquiries regarding the bid were directed to Mary Ann St. Laurent, Warehouse & Inventory Manager, at mstlaurent@ocalafl.org or (352-351-6705).
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specification DNA-31683 Flex-Span® ADSS Fiber Optic Cable www.aflglobal.com
Additional Resources
Sag / Tension Performance
AE0249C520EA2
Standards / Ratings / Compliance Designed and Manufactured in accordance with the following:
Fiber Single-mode Fiber: ITU-T G.652D/G.657.A1· Cable IEEE 1222·
RoHS Compliant· Color Code ANSI/EIA 359-A, TIA 598-D, IEC 60304·
Wind Radial Ice Load Vert. Horiz. Vector (mi/hr) (inches) (lbs/ft)
Input Data
(ft) (ft) (ft) Vector Tension
Resultant Data
(ft) (lbs) Vert. Horiz
(ft) (ft)
725Span Length (ft)
Add'l
Condition
10.9 361--- --- --- 10.9 --- --- 10.88 --- Installation
--- ------ --- --- --- --- --- --- --- Ice Alone
--- ------ --- --- --- --- --- --- --- Wind Alone
--- ------ --- --- --- --- --- --- --- Ice and Wind
38.9 1,04640.0 0.25 0.2 --- --- --- 25.26 29.6 NESC Medium
--- ------ --- --- --- --- --- --- --- Other
Standard NESC / CSA condition based on Ice Density of 57 lbs/ft³
Binder Tape
Color Coded Buffer Tube
Central Strength Member
Representative 5 unit Fiber Optic Core
Outer Jacket
Aramid Yarn
Optical Core
Representative AFL Flex-Span® Fiber Optic Cable
24 Single-mode
DNA-31683 8/26/2013 Version 27.0 Page 1 of 4
Printed on 3/23/2026 AFL Confidential
Mechanical / Physical Details
Optical Details
60 Fiber ADSS Core (5 - 12 fiber buffer tubes) Fiber Fiber Type CountUnit
Single-mode fibersBlue 12
Single-mode fibersOrange 12
Filler N/A
Filler N/A
Filler N/A
24 Total Fiber Count
Installation and Handling Recommendations
Recommended Installation Procedures for All-Dielectric, Self-Supporting (ADSS) Fiber Optic Cable
AFL-ADSS® Fiber Optic Cable Installation Video
Installation Instructions for Installing All-Dielectric, Self-Supporting (ADSS) in an AFL Splice Enclosure
Fiber Optic Cable Receiving, Handling and Storage.
11.0 0.433Approximate Cable Diameter inmm
4.52 655.7Cable Modulus kpsi kN/mm²
89 0.060 lbs/ftkg/km
1.68E-05 9.35E-06Coefficient of Linear Expansion 1/°F1/°C
Initial
4.88 707.1 kpsi kN/mm² Final
3.77 546.4 kpsi kN/mm² 10 Year
Approximate Cable Weight
22 9 incmDynamic
482 1,062 lbskgfMaximum Rated Cable Load (MRCL)
587 1,294 lbskgfApproximate Cable Breaking Strength
17 7 incmMinimum Bending Radius Static
-50 to +70
Environmental Temperature Recommendations
Storage
Operation
Installation
°C
-40 to +70 °C
-30 to +70 °C
-58 to +158 °F
-40 to +158 °F
-22 to +158 °F
Attenuation Characteristics for Single-mode fibers
0.35 dB/km 1310 nm 0.25 dB/km 1550 nmMax Individual
Standard Fiber Color Code
Fiber No.
Color
Blue
Orange
Green
Brown
Slate
White
Red
Black
Yellow
Violet
Rose
Aqua
Designs with more than 12 fibers per tube will use the standard color code and binders for identification of the fibers.
Designs with mixed fiber types will have multimode or NZDS fibers in the first tube(s) followed by single-mode fibers in the last tube(s).
1)
2)
DNA-31683 8/26/2013 Version 27.0 Page 2 of 4
Quick Reference Installation Notes
Shipping Reels
117 259 lbskgf
77 31Minimum Bull Wheel Diameter incm
Maximum Aerial Stringing Tension (at tensioner)
46 18Stringing Sheave Diameter** incm
17 7
Minimum Bending Radius incm
22 9Dynamic (under tension) incm
Static (No load) Cable
3.8 1.5 incmAfter Installation (Static) Fiber
8 incmAfter Installation (Static)
Plastic Buffer Tube
11.00 0.433Approximate Cable Diameter inmm
* - The stringing tension is always measured at the tensioner side. In general the maximum stringing tension should be a half of the maximum sagging tension and never should exceed 20% RBS of the ADSS Cable.
** - The value indicated is for the first and last structures of the pull and is based on 40 times the cable diameter with a minimum of 18 inches for any cable diameter. Smaller diameters can be used at tangent structures. Reference AFL's installation instructions for more details.
Reference AFL's "Recommended Installation Procedures for All-Dielectric, Self-Supporting (ADSS) Fiber Optic Cable" for detailed installation instructions.
272 600 lbskgfMaximum Pulling Tension in Duct
FL TR DRReel Type
Capacity (meters)(cm) (in) (feet)
OW FL TR DR OW
(kgs) Tare
(lbs) Tare
58Wood 147 3281 2871 3897 200 22,1106,740441
66Wood 168 3691 3691 42107 260 22,9607,000573
72Wood 183 3691 3691 42107 300 22,9607,000662
84Wood 213 3897 3589 44112 416 22,9607,000917
60Steel 152 3281 3281 3897 156 21,7806,640344
72Steel 183 3691 40102 42107 245 22,9607,000540
84Steel 213 45114 42107 51130 351 22,9607,000774
FL - Flange Diameter; TR - Inside Traverse Width; DR - Drum Diameter; OW - Outside Overall Width
Maximum lengths shown are the longest lengths that AFL offers. Longer lengths may be possible.
Ordered lengths should include a distribution of lengths, i.e., all reels cannot be ordered at the maximum. A typical reel length distribution is as follows:
6000m – 7000m ~ 15% of reels 4500m – 6000m ~ 55% of reels 2500m – 4500m ~ 25% of reels <2500m ~ 5% of reels
Wood reels with flex-wrap covering are standard. Non-returnable steel reels and/or wood lagging are available upon request. Additional reel sizes may be available upon request.
Minimum Arbor Hole Diameter:
Steel: 3-1/4in (8.2cm) Wood: 3-1/8in (7.9cm)
Steel reels are recommended for long term storage. Reference AFL's "Fiber Optic Cable Receiving, Handling and Storage" document for additional information.
Reel dimensions are typical and subject to availability at the time of shipment.
DNA-31683 8/26/2013 Version 27.0 Page 3 of 4
The Screen Inputs for ADSS cables in PLS Cad
0.433
Unit weight (lbs/ft) 0.060
Ultimate Tension (lbs)
Cross section area (in^2)
Thermal expansion coeff. (/100 deg F) 9.35E-04
Final modulus of elasticity (psi/100) 7,071
1,294
0.1473
Cable Data
Name:
Description:
Outside diameter (in)
Temperature at which data below were obtained (deg F)
Outer strands
Polynomial coefficients (all strain in %)
6,557
A0 A1 (psi/100) A2 A3 A4
Stress-strain
Creep 5,464
Generate Coefficients
Thermal expansion coeff. (/100 deg F)
Final modulus of elasticity (psi/100)Core strands
Polynomial coefficients (all strain in %)
A0 A1 (psi/100) A2 A3 A4
Stress-strain
Creep
(if different from outer strands)
AFL ADSS DNA-31683 AE0249C520EA2
DNA-31683 8/26/2013 Version 27.0 Page 4 of 4