ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_F-1_-_Restroom_and_Kiosk_ELECTRICAL.pdf

PDF 2 MB Posted

Attached to
Construction of Union Station Restroom with Ticketing Kiosk
Solicitation number
ITB# CIP/260231
Issued by
Marion County, Orlando City, Florida

About this file

This electrical design document is a comprehensive set of specifications and drawings for the City of Ocala's construction of a Union Station Restroom with Ticketing Kiosk project located at 501 NE 1st Avenue, Ocala, Florida. The document provides detailed electrical requirements for the approximately 500-square-foot facility that will include public and employee restrooms and a ticketing kiosk. The electrical scope encompasses power distribution, lighting systems, occupancy controls, emergency systems, grounding infrastructure, and various mechanical equipment connections. The project is governed by the 2020 National Electrical Code, 2023 Florida Building Code standards, and applicable fire protection requirements. Key electrical components include a 150-amp, 208/120-volt single-phase service with main disconnect, multiple panelboards (MB) throughout the facility, LED luminaires with dimmable drivers, occupancy sensor-controlled lighting with 20-minute vacancy sensor delays, emergency lighting systems, and weatherproof exterior wall packs. The electrical contractor must provide all labor, materials, and equipment necessary for a complete, code-compliant installation with temporary electrical service for other trades during construction.

The electrical installation budget is embedded within the overall project cost, with the contractor responsible for all associated fees, permits, and surface restoration. Key electrical requirements include copper conductors (minimum #12 AWG), grounding system design achieving maximum 5-ohm resistance, fire-rated penetrations with listed firestop systems, and coordination with mechanical and plumbing systems. All devices, equipment, and materials must be new and UL-listed or approved by a nationally recognized testing agency. The contractor must submit shop drawings, record drawings, and operation/maintenance manuals within 30 days of system acceptance. Building demand load summary indicates approximately 19.9 kilowatt-hours total demand at 95.6 amps for 208-volt, single-phase service. The project is federally funded through the Federal Transit Administration, subjecting work to Davis-Bacon Act prevailing wage requirements and Buy America provisions. Construction is scheduled for 90 calendar days to substantial completion with liquidated damages of $1,609 per day for delays.

View the file

Other files

File Type Posted
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Addendum__3.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Materials_list_for_the_Kiosk_Camera_System.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Addendum__2.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Addendum__1.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Revised_12.2.25_Exhibit_A_-_Scope_of_Work.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_H_-_Suntran_Restroom_and_Kiosk_ARCH.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_J_-_City_of_Ocala_Standard_Specifications_for_Construction_1.31.25.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_G_-_Restroom_and_Kiosk_Structural_Plans.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_I_-_Suntran_Restroom_and_Kiosk_SITEPLAN.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_C_-_FederalClauses-Construction.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_G-3_-_S-402_-_ALL_SCHEDULES.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_B_-_Build_America_Buy_America_Certificate_Steel_Iron_or_Manufactured_Products.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_D_-_DBE_Utilization_Form.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_G-2_-_S-111_-_ROOF_WIND_AND_WALL_DIAGRAM.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_F_-_Restroom_and_Kiosk_MEP.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_A_-_Scope_of_Work.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_E_-_Certification-Regarding-Lobbying.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_G-1_-_S-101_-_STRUCTURAL_NOTES.pdf PDF
ITB_CIP260231_Construction_of_Union_Station_Restroom_with_Ticketing_Kiosk_-_Exhibit_F-1_-_Restroom_and_Kiosk_ELECTRICAL.pdf PDF
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MISCELLANEOUS RECEPTACLE(S) LIGHTING

CODES AND STANDARDS

GENERAL NOTES

SHEET INDEX

SWITCHES

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION

NFPA 70

NFPA 101

NFPA 110

2023 FBC.

2023 FFPC

2023 FBC-EC

NATIONAL ELECTRICAL CODE (2020)

LIFE SAFETY CODE (2021)

STANDARD FOR EMERGENCY AND STAND-BY POWER

SYSTEM (2021)

FLORIDA BUILDING CODE (2023)

FLORIDA FIRE PREVENTION CODE (2023)

FLORIDA BUILDING CODE - ENERGY CONSERVATION (2023)

LOCAL JURISDICTION CODES AND / OR OWNER DESIGN

GUIDELINES

SYMBOL DESCRIPTION

1. THE ELECTRICAL CONTRACT DOCUMENTS ARE SCHEMATIC IN NATURE AND

INDICATE THE GENERAL CONFIGURATION OF SYSTEMS AND WORK. EXAMINE

ARCHITECTURAL, CIVIL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE

PROTECTION DRAWINGS AND SPECIFICATIONS FOR LOCATIONS AND

REQUIREMENTS OF DEVICES, EQUIPMENT, LUMINARIES, AND SYSTEMS.

CONTENT INDICATED ON THE SPECIFICATIONS BUT NOT THE DRAWINGS, OR

CONTENT INDICATED ON THE DRAWINGS BUT NOT THE SPECIFICATIONS, SHALL

BE INTERPRETED AS BEING PRESENT ON BOTH.

2. PROVIDE ALL DEVICES, EQUIPMENT, ACCESSORIES, MATERIALS, AND LABOR

REQUIRED FOR A COMPLETE, FUNCTIONAL, AND CODE-COMPLIANT ELECTRICAL

SYSTEM. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE CODES

AND STANDARDS INDICATED ON THIS SHEET.

3. ALL DEVICES, EQUIPMENT, ACCESSORIES, AND MATERIALS SHALL BE NEW, AND,

WHERE APPLICABLE, SHALL BE LISTED BY U.L. OR ANOTHER APPROVED

ELECTRICAL TESTING AGENCY.

4. COORDINATE LOCATIONS AND REQUIREMENTS OF EQUIPMENT REQUIRING

ELECTRICAL SERVICE (I.E. PRINTERS, APPLIANCES, ETC.) WITH APPROVED

SHOP DRAWINGS, SPECIFICATION SHEETS, MANUFACTURER’S INSTALLATION

LITERATURE, AND EQUIPMENT NAMEPLATE DATA, PRIOR TO ROUGH-IN AND

INSTALLATION. PROVIDE ELECTRICAL CONNECTIONS (AS REQUIRED).

5. BID SHALL INCLUDE COSTS ASSOCIATED WITH BACKFILLING, CORE DRILLING,

DIRECTIONAL BORING, EXCAVATING, AND REPAIRING OF SURFACES.

6. PAY ALL FEES, TAXES, AND OTHER COSTS ASSOCIATED WITH THE WORK

ENCOMPASSED BY THE ELECTRICAL CONTRACT DOCUMENTS. PROVIDE ALL

REQUIRED NOTICES AND OBTAIN ALL REQUIRED PERMITS.

7. PROVIDE COOPERATION WITH OTHER TRADES AND PROVIDE ANY INFORMATION

REQUIRED TO FACILITATE THE COMPLETION OF THEIR WORK. COORDINATE

DEVICE AND EQUIPMENT LOCATIONS AND MOUNTING HEIGHTS WITH OTHER

TRADES PRIOR TO ROUGH-IN AND INSTALLATION. COORDINATE CONDUIT

ROUTING WITH OTHER TRADES PRIOR TO ROUGH-IN AND INSTALLATION.

8. COORDINATE ALL REQUIREMENTS WITH THE LOCAL UTILITY PRIOR TO ROUGH-

IN AND INSTALLATION. COORDINATE LOCATIONS OF UTILITY HANDHOLES,

AERIAL UTILITY TRANSFORMERS, AND/OR PAD-MOUNTED UTILITY

TRANSFORMERS.

9. PROVIDE TEMPORARY ELECTRICAL SERVICE(S) FOR USE BY OTHER TRADES

DURING PROJECT CONSTRUCTION. UPON COMPLETION OF THE PROJECT, THE

TEMPORARY ELECTRICAL SERVICE(S) SHALL BE REMOVED.

10. WITHIN THIRTY (30) DAYS OF SYSTEM ACCEPTANCE, PROVIDE RECORD

DRAWINGS TO THE OWNER.

11. WITHIN THIRTY (30) DAYS OF SYSTEM ACCEPTANCE, PROVIDE AN OPERATING

MANUAL AND MAINTENANCE MANUAL TO THE OWNER. THE MANUALS SHALL

INCLUDE THE FOLLOWING INFORMATION: SUBMITTAL DATA WITH EQUIPMENT

RATINGS AND SELECTED OPTIONS, OPERATION AND MAINTENANCE MANUALS

FOR EQUIPMENT REQUIRING MAINTENANCE, NAMES AND ADDRESSES OF A

MINIMUM OF ONE (1) QUALIFIED SERVICE AGENCY.

12. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF ALL WALL-MOUNTED

ELECTRICAL DEVICES AND EQUIPMENT WITH THE ARCHITECTURAL DRAWINGS,

GENERAL CONTRACTOR, CASEWORK/MILLWORK, AND OTHER TRADES PRIOR TO

ROUGH-IN AND INSTALLATION.

13. EQUIPMENT LOCATIONS SHALL SATISFY THE WORKING CLEARANCE

REQUIREMENTS AND DEDICATED SPACE REQUIREMENTS OF NEC ARTICLE 110.

PROVIDE SHOP DRAWINGS, DEMONSTRATING COMPLIANCE AND INTER-

DISCIPLINARY COORDINATION, FOR ENGINEERING REVIEW.

14. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS, SECTIONS, AND

ELEVATIONS FOR LOCATIONS AND/OR MOUNTING HEIGHTS OF LUMINARIES

LOCATED AT CEILINGS AND/OR WALLS. VERIFY THAT CEILING-MOUNTED

LUMINARIES ARE SUITABLE FOR THE FINISHED CEILING SYSTEM INDICATED AND

PROVIDE ACCORDINGLY. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF

WALL-MOUNTED LUMINARIES WITH CASEWORK, FURNITURE, AND

ARCHITECTURAL ELEMENTS. WHERE ARCHITECTURAL REFLECTED CEILING

PLANS INDICATE FIRE-RATED CEILING SYSTEMS, PROVIDE UL-LISTED LUMINAIRE

ENCLOSURES (AS REQUIRED).

SINGLE POWER TOGGLE SWITCH

(LETTER DENOTES FIXTURE CONTROLLED)

THREE-WAY TOGGLE SWITCH

FOUR-WAY TOGGLE SWITCH

MOTOR SWITCH

FAN SWITCH

THREE POSITION SELECTOR SWITCH

TIMER SWITCH (60 MINUTES)

LOW VOLTAGE SWITCH

HAND-OFF-AUTOMATIC SWITCH

KEY SWITCH

SWITCH - WEATHERPROOF

DUAL TECH WALL SWITCH OCCUPANCY SENSOR

DUAL TECH, DUAL-LEVEL OCCUPANCY SENSOR SWITCH

DUAL TECH OCCUPANCY SENSOR - CEILING MOUNTED

DUAL TECH OCCUPANCY SENSOR - WALL MOUNTED

PHOTOCELL

LIGHTING CONTACTOR

TIME CLOCK

MAGNETIC MOTOR STARTER

ENCLOSED CIRCUIT BREAKER, AS INDICATED

PANELBOARD, 480 / 277V

PANELBOARD, 208 /120V

MANHOLE

HANDHOLE

SURGE PROTECTION DEVICE

ELECTRICAL METER

TRANSFORMER

MOTOR CONNECTION, HP: DENOTES HORSEPOWER RATING

GROUND BUS BAR

PUSHBUTTON

3/4" PLYWOOD TELEPHONE BACKBOARD

CONCRETE ENCASED DUCTBANK

WIRE IN CONDUIT CONCEALED BELOW SLAB OR GRADE

CONDUIT EXPOSED

FLEXIBLE CONDUIT

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT STUB

DISCONNECT SWITCH, NON-FUSIBLE

3 POLE, 60 AMP, NF: NON-FUSED, 3R: NEMA 3R ENCLOSURE

DISCONNECT SWITCH, FUSIBLE

3 POLE, 60 AMP, FUSED AT 50 AMPS, 3R: NEMA 3R ENCLOSURE

COMBINATION STARTER / DISCONNECT SWITCH, FUSIBLE

3 POLE, 60 AMP, NEMA x SIZE, 3R: NEMA 3R ENCLOSURE

HOMERUN TO PANEL INDICATED

NUMBER OF ARROWS INDICATE NUMBER OF CIRCUITS

WIRE IN CONDUIT CONCEALED, #12 AWG SIZE WIRE IN

1/2" CONDUIT MINIMUM UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

MOUNTED AT 48" UNLESS NOTED OTHERWISE

QUADRAPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

MOUNTED AT 48" UNLESS NOTED OTHERWISE

GFI - TYPE DUPLEX RECEPTACLE

(WP: DENOTES WEATHERPROOF COVER)

GFI - DUPLEX RECEPTACLE

MOUNTED AT 48" UNLESS OTHERWISE NOTED

GFI - DOUBLE DUPLEX RECEPTACLE

MOUNTED AT 48" UNLESS OTHERWISE NOTED

SPECIAL PURPOSE RECEPTACLE

(NEMA RATING AS INDICATED)

QUADRAPLEX RECEPTACLE, TICK MARKS

DENOTE EMERGENCY (TYPICAL ALL RECEPTACLES)

DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

QUADRAPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

SINGLE RECEPTACLE, 20 AMP, 120V U.O.N.

GFI - TYPE DOUBLE DUPLEX RECEPTACLE

DUPLEX RECEPTACLE - HALF SWITCHED

DUPLEX RECEPTACLE - CEILING MOUNTED

DUPLEX RECEPTACLE WITH ISOLATED GROUND

DUPLEX RECEPTACLE - FLOOR MOUNTED

POWER POLE

JUNCTION BOX - CEILING MOUNTED

JUNCTION BOX - WALL MOUNTED

JUNCTION BOX - FLOOR / GROUND MOUNTED

CEILING MOUNTED 2'x2' / 2'x4' LUMINAIRE - RECESSED

NORMAL POWER

CEILING MOUNTED 2'x2' / 2'x4' LUMINAIRE - RECESSED

EMERGENCY POWER

CEILING MOUNTED 1'x4' LUMINAIRE

RECESSED OR SURFACE MOUNTED - NORMAL POWER

CEILING MOUNTED 1'x4' LUMINAIRE

RECESSED OR SURFACE MOUNTED - EMERGENCY POWER

CEILING MOUNTED 1'x4' LUMINAIRE

PENDANT MOUNTED - NORMAL POWER

CEILING MOUNTED 1'x4' LUMINAIRE

PENDANT MOUNTED - EMERGENCY POWER

STRIP LUMINAIRE - NORMAL POWER

STRIP LUMINAIRE - EMERGENCY POWER

DOWNLIGHT LUMINAIRE - NORMAL POWER

DOWNLIGHT LUMINAIRE - EMERGENCY POWER

WALL MOUNTED LUMINAIRE - NORMAL POWER

WALL MOUNTED LUMINAIRE - EMERGENCY POWER

CEILING FAN

TRACK LIGHTING WITH LUMINAIRE

UNDERCOUNTER LUMINAIRE

FLOOD LIGHT LUMINAIRE

POLE LIGHT LUMINAIRE

BOLLARD LUMINAIRE

STEP LIGHT LUMINAIRE

EMERGENCY BATTERY LIGHT UNIT

EXIT LIGHT - SINGLE FACE WITH DIRECTIONAL ARROW

EXIT LIGHT - DOUBLE FACE

EXIT LIGHT - WALL MOUNTED

3P/60A

NF

3R

3P/60A F:50A

3R

3P/60A Nx

3R

MH

HH

SPD

TX

HP

S

3S

4S

MS

FS

3PS

TS

LVS

HOAS

KS

WPS

OSS

DOSS

PC

LC

TC

OS

OS

IG

PP

J

J

J

COMMISSIONING

1. PRIOR TO FINAL INSPECTION, THE CONTRACTOR SHALL SUBMIT

EVIDENCE TO THE REGISTERED DESIGN PROFESSIONAL (ELECTRICAL

ENGINEER-OF-RECORD) OR REGISTERED DESIGN PROFESSIONAL’S

REPRESENTATIVE THAT THE LIGHTING CONTROL SYSTEMS HAVE BEEN

TESTED TO ENSURE THAT THEY ARE CALIBRATED, ADJUSTED,

PROGRAMMED, AND SATISFY THE INTENT OF THESE CONTRACT

DOCUMENTS AND THE MANUFACTURERS’ WRITTEN INSTRUCTIONS.

FUNCTIONAL TESTING SHALL BE PERFORMED IN ACCORDANCE WITH

FBC C408.3.1.1 (VACANCY / OCCUPANCY SENSOR CONTROLS), FBC

C408.3.1.2 (TIME-SWITCH CONTROLS), AND/OR FBC C408.3.1.3 (DAYLIGHT

RESPONSIVE CONTROLS) (AS REQUIRED).

DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

AUTOMATIC SWITCHED RECEPTACLE

QUADRUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

HALF-AUTOMATIC SWITCHED RECEPTACLE

VFD

VFD-RATED, REMOTE DISCONNECT SWITCH WITH EARLY-

BREAK, AUXILIARY CONTACTS FOR VFD DECELERATE-TO-

STOP SIGNAL. CONNECT CONTROL WIRING TO ASSOCIATED

VFD (AS REQUIRED).

15. PROVIDE A COMPLETE GROUNDING SYSTEM IN ACCORDANCE WITH APPLICABLE

SECTIONS OF THE NEC AND SPECIFICATIONS. BOND SERVICE ENTRANCE

ELECTRICAL EQUIPMENT TO BUILDING STEEL, GROUND RODS, METAL WATER

MAINS, LIGHTNING PROTECTION SYSTEM GROUNDING ELECTRODES (WHERE

PRESENT), AND TELECOMMUNICATIONS SYSTEM GROUNDING ELECTRODES (AS

REQUIRED). EQUIPMENT GROUNDING SHALL BE OF THE WIRE TYPE.

16. MINIMUM CONDUIT SIZE SHALL BE 3/4".

17. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG. ALL FEEDER AND BRANCH

CIRCUIT CONDUCTORS SHALL BE INSTALLED WITHIN CONDUIT, UNLESS

OTHERWISE INDICATED. ALL CONDUCTORS SHALL BE COPPER, UNLESS

OTHERWISE INDICATED.

18. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH CIRCUIT. MULTI-WIRE

BRANCH CIRCUITS SHALL BE PROHIBITED.

19. CONNECTIONS TO TRANSFORMERS AND MECHANICAL EQUIPMENT SHALL BE

MADE WITH FMC OR LFMC, UNLESS OTHERWISE INDICATED.

20. WHERE PRACTICABLE, CONDUITS SHALL BE CONCEALED BELOW SLABS, WITHIN

WALLS, AND ABOVE FINISHED CEILING SYSTEMS. WHERE CONDUITS ARE

EMBEDDED WITHIN CONCRETE SLABS, COORDINATE CONDUIT SIZE LIMITATIONS

AND SPACING REQUIREMENTS WITH THE STRUCTURAL DRAWINGS/ENGINEER

PRIOR TO INSTALLATION.

21. SEAL ALL CONDUIT PENETRATIONS AT FIRE-RATED PARTITIONS.

22. COORDINATE ALL CONDUIT PENETRATIONS WITH ARCHITECTURAL DRAWINGS,

STRUCTURAL DRAWINGS, FIELD CONDITIONS, AND OTHER TRADES. PROVIDE

SEALING FITTINGS TO PROHIBIT CONDENSATION AND/OR THE PASSAGE OF

GASES OR VAPORS (AS REQUIRED).

23. INCREASE FEEDER AND BRANCH CIRCUIT CONDUCTOR SIZES AS REQUIRED IN

ORDER TO MAINTAIN A MAXIMUM, CUMULATIVE VOLTAGE DROP OF 5% AT THE

END LOAD. MAXIMUM VOLTAGE DROP SHALL BE DISTRIBUTED AS FOLLOWS: 3%

FOR FEEDERS, 2% FOR BRANCH CIRCUITS. WHERE THE VOLTAGE DROP

REQUIREMENTS OF THE LOCAL ENERGY CODE ARE MORE STRINGENT, THE

REQUIREMENTS OF THE LOCAL ENERGY CODE SHALL TAKE PRECEDENCE.

WHERE PHASE AND NEUTRAL CONDUCTOR SIZES ARE INCREASED FOR

VOLTAGE DROP, THE EQUIPMENT GROUNDING CONDUCTOR SHALL BE

INCREASED PROPORTIONATELY.

24. PROVIDE ALL REQUIRED DISCONNECT SWITCHES, STARTERS, AND

COMBINATION STARTER/DISCONNECT SWITCHES. MAKE CONNECTIONS TO ALL

ELECTRICALLY-DRIVEN DEVICES AND EQUIPMENT PROVIDED BY THE

MECHANICAL, PLUMBING, AND FIRE PROTECTION CONTRACTORS. EXAMINE

EQUIPMENT NAMEPLATE RATINGS PRIOR TO ROUGH-IN AND INSTALLATION.

PROVIDE OVERCURRENT PROTECTION IN ACCORDANCE WITH EQUIPMENT

NAMEPLATE RATINGS. PROVIDE ALL POWER SUPPLIES, CONTROL

TRANSFORMERS, RELAYS, AND OTHER ACCESSORIES REQUIRED TO FACILITATE

THE PROPER OPERATION OF MECHANICAL EQUIPMENT AS DESCRIBED WITHIN

THE MECHANICAL ENGINEER’S SEQUENCE OF OPERATIONS.

25. ALL INTERIOR ELECTRICAL EQUIPMENT SHALL BE OF NEMA 1 CONSTRUCTION,

UNLESS OTHERWISE INDICATED. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL

BE OF NEMA 3R CONSTRUCTION, UNLESS OTHERWISE INDICATED. EQUIPMENT

RATINGS SHALL CORRESPOND TO THEIR INSTALLED ENVIRONMENTS.

26. ALL NEW PANELBOARDS AND WITHIN THE SCOPE OF THIS PROJECT SHALL BE

PROVIDED WITH NEW, TYPEWRITTEN DIRECTORIES. CIRCUIT DESCRIPTIONS

SHALL CONTAIN ROOM NAMES AND ROOM NUMBERS BASED UPON INSTALLED

ROOM SIGNAGE.

27. PROVIDE PHENOLIC, ENGRAVED IDENTIFICATION PLACARDS AT ALL

PANELBOARDS, DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS, AND

CABINETS. REFER TO DETAILS FOR FURTHER INFORMATION.

29. PROVIDE TYPEWRITTEN OR ENGRAVED PANEL AND CIRCUIT IDENTIFICATION AT

DEVICE RECEPTACLE OUTLET AND TOGGLE SWITCH COVER PLATES.

30. PROVIDE HANDWRITTEN PANEL AND CIRCUIT IDENTIFICATION ON THE

EXTERIORS OF ALL JUNCTION BOXES, PULL BOXES, AND WIREWAYS.

ELECTRICAL ABBREVIATIONS

SYMBOL DESCRIPTION

A

AC

A/C

AFC

AFCI

AHU

AIC

AL

ATS

AWG

C

CATV

CB

C/B

CCTV

CIR

CKT

CU

DC

DIA

EB

EC

EF

ELEV

EM

EMT

EP

EPO

ER

ETR

EWC

EX

F

FA

FAA

FLA

FMC

G, GND

GFCI, GFI

GND

GRC

HOA

HVAC

HZ

IEEE

IG

AMPERES

ALTERNATING CURRENT

AIR CONDITIONING

AVAILABLE FAULT CURRENT

ARC FAULT CIRCUIT INTERRUPTER

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

ALUMINUM

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

CONDUIT

CABLE TELEVISION

CRITICAL BRANCH

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CIRCUIT

CIRCUIT

COPPER

DIRECT CURRENT

DIAMETER

EQUIPMENT BRANCH

ELECTRICAL CONTRACTOR

EXHAUST FAN

ELEVATOR

EMERGENCY

ELECTRICAL METALLIC TUBING

EMERGENCY POWER

EMERGENCY POWER OFF (BUTTON OR SWITCH)

EXISTING TO BE REMOVED

EXISTING TO BE RELOCATED

ELECTRIC WATER COOLER

EXISTING TO REMAIN

FUSE

FIRE ALARM

FIRE ALARM ANNUNCIATOR PANEL

FULL LOAD AMPERES

FLEXIBLE METAL CONDUIT

GROUND

GROUND FAULT CIRCUIT INTERRUPTER

GROUND

GALVANIZED RIGID METAL CONDUIT

HAND-OFF-AUTOMATIC SWITCH

HEATING, VENTILATION, AIR CONDITIONING

HERTZ

INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS

ISOLATED GROUND

IMC

KCMIL

KVA

LFMC

LTG

LRA

MC

MCB

MCC

MCP

MLO

MTD

NC

NEC

NEMA

NFPA

NL

NO

P

PB

PNL

PWR

QTY

REQ

RMC

RNC

RTS

RTU

SP

ST

SW

SYM

TEL

TGB

TMCB

TYP

UG

UL

V

VA

VD

VFD

W

WH

WP

XFMR

INTERMEDIATE METAL CONDUIT

THOUSAND CIRCULAR MILS

KILOVOLT - AMPERES

LIQUID TIGHT FLEXIBLE METAL CONDUIT

LIGHTING

LOCK ROTOR AMPS

METAL CLAD CABLE

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MOTOR CIRCUIT PROTECTION

MAIN LUGS ONLY

MOUNTED

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NIGHT LIGHT

NORMALLY OPEN OR NUMBER

POLE

PUSH BUTTON, PANIC BUTTON OR PULLBOX

PANEL

POWER

QUANTITY

REQUIRED

RIGID METAL CONDUIT

RIGID NON-METALLIC CONDUIT

REMOTE TEST STATION

ROOF TOP UNIT

SPARE

SHUNT-TRIP

SWITCH

SYMMETRICAL

TELEPHONE

TELECOMMUNICATIONS GROUNDING BUSBAR

THERMAL MAGNETIC CIRCUIT BREAKER

TYPICAL

UNDERGROUND

UNDERWRITERS LABORATORY

VOLT

VOLT - AMPERE

VOLTAGE DROP

VARIABLE FREQUENCY DRIVE

WATT OR WIRE

WATER HEATER

WEATHERPROOF

TRANSFORMER

SYMBOL DESCRIPTION

DAYLIGHT HARVESTING SENSOR - CEILING MOUNTEDDH

DIMMING SWITCHSD

ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE FOLLOWING:

RELAY MODULE WITH 0-10V DIMMING OUTPUTPL

PLUG LOAD RELAY PACKPR

STRUCTURED CABLING SYSTEMS

SYMBOL DESCRIPTION (RACEWAY ONLY)

COMMUNICATIONS OUTLET, MOUNTED AT

RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED.

REFER TO INSTALLER FOR MODULE AND FACEPLATE

DESCRIPTIONS. CABLES PROVIDED BY OTHERS.

CEILING MOUNTED WIRELESS ACCESS POINT

OUTLET.

'X' - MOUNTING (F)LUSH, (S)URFACE, (C)EILING

WALL TELEPHONE OUTLET FOR WALL PHONE.

MTD AT 48" ABOVE FINISHED FLOOR TO CENTER

COMBINED VOICE / DATA, AUDIO / VIDEO AND

POWER OUTLETS IN FLOOR BOX.

WAP

W

SECURITY SYSTEM

SYMBOL DESCRIPTION (RACEWAY ONLY)

BIOMETRIC READER

CARD READER / KEYPAD

CARD READER

KEYPAD

DIRECTIONAL MOTION DETECTOR

360 DEGREE MOTION DETECTOR

ELECTRO MAGNETIC LOCK

ELECTRIC STRIKE FRAME

ELECTRIC MORTISE LOCK

DELAYED EGRESS LOCK

DOOR / WINDOW CONTACT

SECURITY PANEL

KEY SWITCH

REMOTE DOOR RELEASE BUTTON

INTERCOM SUB-STATION

REQUEST TO EXIT MOTION SENSOR

REQUEST TO EXIT PUSH-BUTTON

PERSONAL COMPUTER WORKSTATION

FIXED CCTV CAMERA

ALARM SIREN

WP: WEATHERPROOF

DURESS BUTTON

INTERCOM MASTER STATION

SECURITY CAMERA POLE. POLE TO MATCH

UTILITY PACKAGE SPECIFICATIONS FOR LIGHTING

POLES IN THE SAME AREA

KP

CR

MD

S

DC

CK

BR

MD

ML

ES

EM

DE

KS

RR

D

IM

IS

RS

RB

PC

TP

SECURITY SOUND DETECTORSD

FLORIDA LIC No: AR95989

Carbon design & architecture 263 13th Avenue South Suite 375 St. Petersburg, FL 33701 O:: 941.362.4312 W:: www.carbonAE.com

Project No:

PROJECT DATA

Project Na:

CLIENT DATA

Client:

ARCHITECT DATA

ENGINEER DATA

ISSUE + REVISION DATA

ENGINEER SEAL

CHECKED BY

DRAWN BY

PRINTED:24X36 SHEET

ARCH D

EOR: JULIUS D. DAVIS, P.E. #58005

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIUS D. DAVIS,

P.E. #58005 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON

ANY ELECTRONIC COPIES

6005 Benjamin Rd.

Suite A Tampa, FL 33634 O:: 888.891.9713 W:: www.voltairinc.com

COA: #27158

Proj: #01.22029

TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY

WITH THE APPLICABLE MINIMUM BUILDING CODES

8/12/2024 4:45:49 PM

8/12/2024 4:45:49 PM

E-000

LEGEND - ELECTRICAL

100% CD's Set

05.28.2024

24020

OCALA SUNTRAN

RESTROOMS & KIOSK

CITY OF OCALA

501 NE 1st Ave.

Ocala, FL 34470

R.F.W.

R.F.W.

SHEET NUMBER SHEET NAME

E-000 LEGEND - ELECTRICAL

E-001 SPECIFICATIONS - ELECTRICAL

E-002 SCHEDULES - ELECTRICAL

E-100 SITE PLAN - ELECTRICAL

E-201 FIRST FLOOR PLAN - POWER

E-301 FIRST FLOOR PLAN - LIGHTING

E-501 RISER DIAGRAM - ELECTRICAL

E-901 DETAILS - ELECTRICAL

E-902 DETAILS - ELECTRICAL

E-903 DETAILS - ELECTRICAL

No: Description: Date:

SPECIFICATIONS - ELECTRICAL

260100 - BASIC ELECTRICAL SCOPE OF WORK REQUIREMENTS:

A. ALL WORK SHALL BE IN COMPLIANCE WITH THE LATEST APPLICABLE CODES, LAWS AND ORDINANCES AND THE NATIONAL ELECTRICAL CODE. PROVIDE AND INSTALL ALL LABOR, MATERIALS, PERMITS AND INCIDENTALS REQUIRED TO COMPLETE

ALL WORK AS SHOWN ON CONTRACT DOCUMENTS.

B. DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL SCOPE AND ARRANGEMENT OF THE ELECTRICAL INSTALLATION AND ARE NOT INTENDED TO SHOW EVERY CONNECTION. CONDUIT OR EXACT LOCATION AND EXTENT OF WORK. CONTRACTOR SHALL INSTALL THE WORK COMPLETE, INCLUDING DETAILS AND EQUIPMENT NECESSARY TO PERFORM THE FUNCTION INDICATED ON THE DRAWINGS. SUBMIT SHOP DRAWINGS FOR ALL ELECTRICAL EQUIPMENT ASSOCIATED WITH THE PROJECT UNDER ONE SUBMITTAL. SEPARATE SUBMITTALS MAY BE REJECTED. SUBMIT DIMENSIONED ELECTRICAL ROOM LAYOUTS TO 1/4' SCALE WITH MANUFACTURERS EQUIPMENT LOCATIONS SHOWN

THEREIN.

C. ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS AND SHALL BE U.L. LISTED OR BE LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY.

D. INSPECT ALL NEW MATERIAL AND EQUIPMENT PRIOR TO INSTALLATIONS FOR DAMAGES AND SHALL VERIFY EQUIPMENT

OPERATES SATISFACTORILY.

E. WARRANT ALL MATERIAL AND EQUIPMENT FURNISHED TO COMPLETE ALL WORK FOR ONE YEAR AFTER FINAL ACCEPTANCE OF COMPLETION. MATERIALS AND EQUIPMENT DEFECTS OF FAILURES DUE TO ABUSE OR WORKMANSHIP NEGLECT SHALL

BE MADE GOOD BY THE CONTRACTOR WITHOUT COST TO THE OWNER.

F. PROVIDE ONLY NEW, STANDARD UNDERWRITER'S LABORATORY INC. LISTED FIRST-GRADE MATERIALS THROUGHOUT AND SHALL BE MARKED WITH UNDERWRITERS LABORATORY INC. LISTED AND WITH MANUFACTURER'S BRAND OR TRADEMARK.

ALL MATERIALS SHALL BE OF ONE MANUFACTURER.

G. CONTRACTOR SHALL BE EXPERIENCED IN THEIR TRADE. CONTRACTOR'S WORK SHALL PRESENT A NEAT APPEARANCE UPON COMPLETION. MATERIALS AND EQUIPMENT INSTALLED SHALL BE PLUMB, STRAIGHT AND LEVEL.

H. COORDINATE WITH THE ARCHITECT AND OWNER ON EXACT LOCATION OF WIRING DEVICES AND RACEWAYS FOR OWNER- FURNISHED EQUIPMENT PRIOR TO ROUGH-IN. COORDINATE ELECTRICAL EQUIPMENT AND MATERIALS INSTALLATION WITH OTHER BUILDING COMPONENTS AND TRADES. REVIEW AND COORDINATE BETWEEN ALL CONSTRUCTION DOCUMENTS AND

PROJECT SPECIFICATIONS.

I. COORDINATE THE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SLEEVES TO BE SET IN POURED IN PLACE CONCRETE AND OTHER STRUCTURAL COMPONENTS AS THEY ARE CONSTRUCTED. COORDINATE THE CUTTING AND PATCHING OF BUILDING COMPONENTS TO ACCOMMODATE THE INSTALLATION OF ELECTRICAL EQUIPMENT AND MATERIALS

IN RENOVATION PROJECTS.

J. COORDINATE CONNECTION OF ELECTRICAL SYSTEMS AND EQUIPMENT REQUIREMENTS WITH LOCAL UTILITY SERVICES TO

PROVIDE AND COMPLY WITH THE REQUIREMENTS FOR EACH SERVICE.

K. UPON COMPLETION OF WORK, TEST ALL WIRING AND EQUIPMENT INSTALLATION AND SHALL BE IN PERFECT WORKING CONDITION IN ACCORDANCE WITH THE INTENT OF THE CONTRACT DOCUMENTS. MARK DRAWINGS TO INDICATE ACTUAL

FIELD CONDITIONS.

L. THE WORD 'PROVIDE' MEANS FOR THE CONTRACTOR TO FURNISH AND INSTALL.

260519 - CONDUCTORS AND CABLES:

A. WIRING GENERAL: CONDUCTORS SHALL BE COPPER AND HAVE CURRENT CARRYING CAPACITIES AS PER N.E.C. WITH 600 VOLT INSULATION AND COMPLY WITH NEMA WC 70. ALUMINUM CONDUCTORS ARE NOT APPROVED. CONDUCTORS SHALL BE #12 MINIMUM, EXCEPT FOR CONTROLS AND FIXTURE WIRE. SOLID FOR #10 AND SMALLER CONDUCTORS, STRANDED

FOR #8 AND LARGER.

B. FEEDERS: BRANCH CIRCUITS, CLASS 1 AND CLASS 2 CIRCUITS SHALL BE INSULATION TYPE XHHW OR THWN.

C. MAINTAIN STANDARD COLOR CODING OF BLACK, RED AND BLUE FOR 120/208 VOLT, 3 PHASE WIRING AND BROWN, ORANGE

AND YELLOW FOR 277/480 VOLT, 3 PHASE WIRING. COLOR CODING SHALL MATCH EXISTING FACILITIES WHERE THE COLOR

CODING IS NOT STANDARD. WHITE NEUTRAL AND GREEN GROUND.

D. CONCEAL CABLES IN FINISHED WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE INDICATED. INSTALL EXPOSED CABLES PARALLEL AND PERPENDICULAR TO SURFACES OF EXPOSED STRUCTURAL MEMBERS AND FOLLOW SURFACE CONTOURS

WHERE POSSIBLE.

E. MAKE SPLICES AND TAPS THAT ARE COMPATIBLE WITH CONDUCTOR MATERIAL AND THAT POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION RATINGS THAN UNSPLICED CONDUCTORS. SERVICE ENTRANCE AND PANEL FEEDERS SHALL NOT BE SPLICED. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A AND UL 486B.

F. WIRING AT OUTLETS: INSTALL CONDUCTOR AT EACH OUTLET WITH AT LEAST 12 INCHES OF SLACK. WIRING IN LIGHT POLE

HANDHOLES: PROVIDE AT LEAST 18" OF SLACK AT HANDHOLE.

260526 - GROUNDING AND BONDING:

A. GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL CODES AND

REQUIREMENTS.

B. FEEDERS AND BRANCH CIRCUITS SHALL HAVE INSTALLED IN THE SAME RACEWAY AS THE CIRCUIT CONDUCTORS, AN

INSULATED COPPER GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC.

C. DESCRIPTION OF SYSTEM: IN GENERAL, ALL ELECTRICAL EQUIPMENT (METALLIC CONDUIT, MOTOR FRAMES, PANEL BOARDS, ETC.) SHALL BE BONDED TOGETHER WITH A GREEN INSULATED OR BARE COPPER SYSTEM GROUNDING CONDUCTOR IN ACCORDANCE WITH SPECIFIC RULES OF ARTICLE 250 OF THE N.E.C. EQUIPMENT GROUNDING CONDUCTORS THROUGH THE RACEWAY. SYSTEM SHALL BE CONTINUOUS FROM MAIN SWITCH GROUND BUS TO PANEL GROUND BAR OF EACH PANEL BOARD AND FROM PANEL GROUNDING BAR OF EACH PANEL BOARD TO BRANCH CIRCUIT EQUIPMENT AND DEVICES. CONNECTORS LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING LABORATORY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION FOR APPLICATIONS IN WHICH USE AND FOR SPECIFIC TYPES, SIZES AND COMBINATIONS OF CONDUCTORS AND OTHER ITEMS CONNECTED. ALL FEEDER METALLIC CONDUITS AND FLEXIBLE METAL CONDUITS CONNECTIONS TO PANEL CABINETS, EQUIPMENT CABINETS, TRANSFORMER ENCLOSURES, ETC. SHALL

BE PROVIDED WITH GROUNDING BUSHINGS.

D. ELECTRICAL ROOM GROUND BUSS BARS: NEWTON INSTRUMENT COMPANY INSULATED GROUND BAR, MINIMUM SIZE 1/4" x 4" x 10", COPPER, MANUFACTURER PRE-DRILLED HOLES. ALL GROUND BUSS BARS SHALL BE BONDED TO MAIN ELECTRICAL GROUND BUSS BAR WITH MINIMUM 3/0 COPPER GROUND OR SIZED PER CODE FOR A CONTINUOUS COPPER GROUNDING SYSTEM. UTILIZING BUILDING STEEL OR FOOTING IS NOT ACCEPTABLE. TELECOMMUNICATIONS, IDF, DATA, COMPUTER AND SIMILAR ROOMS: NEWTON INSTRUMENT COMPANY INSULATED GROUND BAR, 1/4" x 4" x 20", COPPER, MANUFACTURER PRE-DRILLED HOLES. BOND GROUND BUSS BAR TO MAIN ELECTRICAL GROUND BUSS BAR WITH MINIMUM 3/0 AWG

COPPER.

E. GROUNDING RODS: COPPER-CLAD STEEL, SECTIONAL TYPE; 3/4" INCH IN DIAMETER x 10 FEET. PROVIDE ADDITIONAL LENGTHS IN 10' SECTIONS TO ACHIEVE SPECIFIED MINIMUM RESISTANCE TO GROUND, MEASURED IN OHMS, AT BUILDING SERVICES GROUNDING SYSTEMS. EXOTHERMIC CADWELD SHALL BE USED FOR BUILDING GROUNDING SYSTEM

CONNECTION TO DRIVEN GROUND RODS.

F. GROUNDING AND BONDING FOR PIPING: METAL WATER SERVICE PIPE: INSTALL INSULATED COPPER GROUNDING CONDUCTORS, IN CONDUIT, FROM BUILDING'S MAIN SERVICE EQUIPMENT OR GROUNDING BUSS, TO MAIN METAL WATER SERVICE ENTRANCES TO BUILDING. BOND EACH ABOVE GROUND PORTION OF GAS PIPING SYSTEM DOWNSTREAM FROM EQUIPMENT SHUT-OFF VALVE. CONCRETE ENCASED ELECTRODE IN BUILDING FOOTER SHALL BE A BARE CONDUCTOR, SAME SIZE AS THE BUILDING SYSTEMS GROUNDING CONDUCTOR, ROUTED MINIMUM 20' AND TIE WIRED TO THE

REINFORCING BARS.

G. PERFORM GROUNDING TEST: PERFORM TESTS BY FALL-OF-POTENTIAL METHOD ACCORDING TO IEEE 81, USING MEGOHMETER. REPORT MEASURED GROUND RESISTANCES THAT EXCEED 5 OHMS. EXCESSIVE GROUND RESISTANCE: IF RESISTANCE TO GROUND EXCEEDS 5 OHMS, PROVIDE ADDITIONAL DRIVEN GROUNDING RODS UNTIL THE MEASURED

GROUND RESISTANCE DOES NOT EXCEED 5 OHMS.

260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS:

A. HANGERS AND SUPPORTS FOR ELECTRICAL EQUIPMENT AND RACEWAYS SHALL COMPLY WITH THE NEC AND NECA 1 AND NECA 101. SPACE SUPPORTS FOR EMT, IMC AND RMC AS REQUIRED BY THE NEC. MINIMUM ROD SIZE SHALL BE 1/4 INCH IN

DIAMETER.

B. CONDUIT AND CABLE SUPPORT DEVICES: STEEL HANGERS, CLAMPS AND ASSOCIATED FITTINGS, DESIGNED FOR TYPES AND SIZES OF RACEWAY OR CABLE TO BE SUPPORTED. EXTERIOR AND WET LOCATIONS SHALL BE STAINLESS STEEL OR

ALUMINUM WITH STAINLESS STEEL HARDWARE.

C. SUPPORT FOR CONDUCTORS IN VERTICAL CONDUIT: FACTORY - FABRICATED ASSEMBLY CONSISTING OF THREADED BODY AND INSULATING WEDGING PLUG OR PLUGS FOR NON-ARMORED ELECTRICAL CONDUCTORS OR CABLES IN RISER CONDUITS. PLUGS SHALL HAVE NUMBER, SIZE AND SHAPE OF CONDUCTOR GRIPPING PIECES AS REQUIRED TO SUIT

CABLES SUPPORTED.

D. MOUNTING, ANCHORING AND ATTACHMENT COMPONENTS: ITEMS FOR FASTENING ELECTRICAL ITEMS OR THEIR SUPPORTS TO BUILDING SURFACES INCLUDE: MECHANICAL EXPANSION ANCHORS, INSERT - WEDGE TYPE, ZINC-COATED STEEL OR STAINLESS STEEL FOR USE IN HARDENED PORTLAND CEMENT CONCRETE WITH TENSION, SHEAR AND PULLOUT CAPACITIES APPROPRIATE FOR SUPPORTED LOADS AND BUILDING MATERIALS IN WHICH USED. CONCRETE INSERTS, STEEL OR MALLEABLE-IRON, SLOTTED SUPPORT SYSTEM UNITS SIMILAR TO MSS TYPE 18, COMPLYING WITH MFMA-4 OR MSS SP-58. CLAMPS FOR ATTACHMENT TO STEEL STRUCTURAL ELEMENTS, MSS SP-58, TYPE SUITABLE FOR ATTACHED STRUCTURAL ELEMENT. THROUGH BOLTS, STRUCTURAL TYPE, HEX HEAD AND HIGH STRENGTH. COMPLY WITH ASTM A-325. TOGGLE BOLTS, ALL STEEL SPRINGHEAD TYPE. HANGER RODS, THREADED STEEL. MOUNTING APPARATUS FOR EXTERIOR APPLICATIONS SHALL BE STAINLESS STEEL. EXTERIOR LOCATED SUPPORT APPARATUS SHALL CONSIST OF DIRECT BURIAL CONCRETE POSTS, STAINLESS STEEL OR ALUMINUM CHANNEL AND STAINLESS STEEL SPRINGS, BOLTS, WASHERS, ETC.

E. MULTIPLE RACEWAYS OR CABLES SHALL HAVE L-TRAPEZE TYPE SUPPORTS FABRICATED WITH STEEL SLOTTED OR OTHER SUPPORT SYSTEM, SIZED SO CAPACITY CAN BE INCREASED BY AT LEAST 25 PERCENT IN FUTURE WITHOUT EXCEEDING SPECIFIED DESIGN LOAD LIMITS. SECURE RACEWAYS AND CABLES TO THESE SUPPORTS WITH TWO-BOLT CONDUIT CLAMPS USING SPRING FRICTION ACTION FOR RETENTION IN SUPPORT CHANNEL. SPRING-STEEL CLAMPS DESIGNED FOR SUPPORTING SINGLE CONDUITS WITHOUT BOLTS MAY BE USED FOR 1-1/2 INCH AND SMALLER RACEWAYS SERVING

BRANCH CIRCUITS AND COMMUNICATION SYSTEMS ABOVE SUSPENDED CEILINGS.

F. SUPPORTING RACEWAYS VIA OTHER RACEWAYS CABLE TRAYS AND WIREWAYS ARE NOT APPROVED.

260533 - RACEWAYS AND BOXES:

A. LISTING AND LABELING: METAL CONDUITS AND NON-METALLIC CONDUITS, TUBING AND FITTINGS SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70 AND MARKED FOR INTENDED LOCATION AND APPLICATION.CONDUIT GENERAL: RIGID SHALL BE MINIMUM 1", GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING, E.M.T. SHALL BE MINIMUM 3/4" AND SHALL BE

ELECTRO-GALVANIZED. PROVIDE MINIMUM 1" CONDUIT WITH 4" SQUARE BACK BOX FOR DATA.

B. CONDUITS SHALL BE AS MANUFACTURED BY ALLIED, PITTSBURGH STANDARD, REPUBLIC, THOMAS & BETTS, TRIANGLE, WHEATLAND OR YOUNGSTOWN.

C. PROVIDE END BUSHINGS ON ALL CONDUITS. PROVIDE PULL STRINGS IN ALL EMPTY RACEWAYS. PULL STRINGS SHALL BE NYLON AND SHALL BE IMPERVIOUS TO MOISTURE. PULL STRINGS SHALL HAVE A TENSILE STRENGTH NOT LESS THAN 200 LBS. METALLIC RACEWAY MAY BE BONDED TO CABINETS, BOXES AND PANELBOARDS BY DOUBLE LOCKNUT AND BUSHING

TO ENSURE THE METALLIC PARTS ARE ALL EFFECTIVELY GROUNDED.

D. CONDUIT ABOVE GRADE OR CONCEALED IN WALLS SHALL BE EMT (INTERIOR ONLY), IMC OR GALVANIZED. CONDUIT BELOW GRADE SHALL BE RIGID GALVANIZED (HEAVY WALL), IMC OR PVC (SCHEDULE 40). CONNECTION TO VIBRATING EQUIPMENT, (INCLUDING TRANSFORMERS AND HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID OR MOTOR-DRIVEN EQUIPMENT), FMC, EXCEPT USE LFMC IN DAMP OR WET LOCATIONS, MAXIMUM LENGTH 72 INCHES. CONCEAL CONDUIT WITHIN FINISH WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE INDICATED.

E. CONDUIT OUTSIDE AND EXPOSED TO PHYSICAL DAMAGE OR IN DAMP OR WET LOCATIONS SHALL BE RIGID GALVANIZED

(HEAVY WALL).

F. SEALANT: PROVIDE A CLOSED CELL SILICONE FOAM SEALANT RATED TO PROVIDE A RATING EQUAL TO THE WALL, CEILING OR FLOOR ASSEMBLY RATING. PROVIDE SEALS FOR THE EXTERIOR OF CONDUIT PENETRATIONS CONSISTING OF A CAST- IN-PLACE SLEEVE WITH A COMPRESSIBLE RUBBER GASKET BETWEEN THE CONDUIT AND THE SLEEVE. PROVIDE SEALS FOR THE INTERIOR OF THE CONDUIT PENETRATIONS CONSISTING OF GLAND TYPE SEALING BUSHING OR CLOSED CELL SILICONE FOAM. PROVIDE DUCT SEAL INSIDE AN APPROPRIATE SEAL-OFF FITTING TO SEAL THE INTERIOR OF THE

CONDUIT SYSTEM FROM WATER SEEPAGE OR HAZARDOUS GASES.

G. COUPLINGS: ALL COUPLINGS AND CONNECTORS FOR EMT SHALL BE OF COMPRESSION TYPE.

H. OUTLET SHALL BE STANDARD TYPE WITH KNOCKOUTS, MADE OF HOT DIPPED GALVANIZED STEEL AS MANUFACTURED BY

STEEL CITY, RACO OR APPLETON. BOX EXTENSIONS USED TO ACCOMMODATE NEW BUILDING FINISHES SHALL BE OF SAME

MATERIAL AS RECESSED BOX.

I. CEILING OUTLET BOXES SHALL BE 4 INCH OCTAGON, 1-1/2 INCH DEEP OR LARGER WHEN REQUIRED DUE FOR NUMBER OF CONDUCTORS OR CONDUIT ENTRY. LUMINAIRE OUTLET BOXES: NON-ADJUSTABLE, DESIGNED FOR ATTACHMENT OF LUMINAIRE WEIGHING 50 LB. OUTLET BOXES DESIGNED FOR ATTACHMENT OF LUMINAIRES WEIGHTING MORE THAN 50 LB.

SHALL BE LISTED AND MARKED FOR THE MAXIMUM ALLOWABLE WEIGHT.

J. OUTLET BOXES SHALL BE PROVIDED WITH APPROVED 3/8 INCH FIXTURE STUDS WHERE REQUIRED. PROVIDE JUNCTION OR PULL BOXES WHERE SHOWN ON THE DRAWINGS AS REQUIRED TO FACILITATE INSTALLING CONDUCTORS. BOXES SHALL BE SIZED IN ACCORDANCE WITH THE NEC. ALL JUNCTION BOXES SHALL BE ACCESSIBLE, HORIZONTALLY SEPARATE BOXES MOUNTED ON OPPOSITE SIDES OF WALLS SO THEY ARE NOT IN THE SAME VERTICAL CHANNEL AND TO MAINTAIN WALL

FIRE RATING.

K. METAL FLOOR BOXES: CAST METAL FOR SLAB ON SLAB ON GRADE OR SHEET METAL, FULLY ADJUSTABLE, RECTANGULAR.

METAL FLOOR BOXES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY AND

MARKED FOR INTENDED LOCATION AND APPLICATION.

260544 - SLEEVES AND SEALS FOR ELECTRICAL RACEWAYS AND CABLING:

A. COORDINATE SLEEVE SELECTION AND APPLICATION FOR RACEWAYS AND CABLES THROUGH FIRE RATED PENETRATIONS WITH 'THROUGH-PENETRATION FIRESTOP SYSTEMS' SPECIFIED IN ARCHITECTURAL DRAWINGS AND SPECIFICATIONS. FOR FIRE-RATED ASSEMBLY PENETRATIONS, MAINTAIN INDICATED FIRE RATING OF WALLS, PARTITIONS, CEILINGS AND FLOORS AT CABLE PENETRATIONS. INSTALL SLEEVES AND SEAL WITH FIRESTOP MATERIALS ACCORDING TO LISTING.

B. SLEEVE INSTALLATION FOR NON-FIRE-RATED ELECTRICAL PENETRATIONS: WALL SLEEVES, GALVANIZED-STEEL SHEET;

0.0239 INCH MINIMUM THICKNESS; ROUND TUBE CLOSED WITH TABS FOR SCREW-FASTENING THE SLEEVE TO THE BOARD.

SLEEVES FOR RECTANGULAR OPENINGS: FOR SLEEVE CROSS-SECTION RECTANGLE PERIMETER LESS THAN 50 INCHES AND WITH NO SIDE LARGER THAN 16 INCHES, THICKNESS SHALL BE 0.052 INCH FOR SLEEVE CROSS-SECTION RECTANGLE PERIMETER 50 INCHES OR MORE AND ONE OR MORE SIDES LARGERS THAN 16 INCHES, THICKNESS SHALL BE 0.138 INCH.

CUT SLEEVES TO LENGTH FOR MOUNTING FLUSH WITH BOTH WALL SURFACES. EXTEND SLEEVES INSTALLED IN FLOORS 2 INCHES ABOVE FINISHED FLOOR LEVEL. SIZE PIPE SLEEVES TO PROVIDE 1/4 INCH ANNULAR CLEAR SPACE BETWEEN SLEEVE AND CABLE UNLESS SLEEVE SEAL IS TO BE INSTALLED. SEAL SPACE OUTSIDE OF SLEEVES WITH GROUT FOR PENETRATIONS OF CONCRETE AND MASONRY AND WITH APPROVED JOINT COMPOUND FOR GYPSUM BOARD ASSEMBLIES.

ROOF PENETRATION SLEEVES - SEAL PENETRATION OF INDIVIDUAL CABLES WITH FLEXIBLE BOOT-TYPE FLASHING UNITS APPLIED IN COORDINATION WITH ROOFING WORK. ABOVE GROUND EXTERIOR-WALL PENETRATIONS - SEAL PENETRATIONS USING SLEEVES AND MECHANICAL SLEEVE SEALS AND SIZE SLEEVES TO ALLOW FOR 1 INCH ANNULAR CLEAR SPACE BETWEEN PIPE AND SLEEVE FOR INSTALLING MECHANICAL SLEEVE SEALS. UNDERGROUND EXTERIOR-WALL PENETRATIONS - INSTALL CAST-IRON 'WALL PIPES' FOR SLEEVES, SIZE SLEEVES TO ALLOW FOR 1 INCH ANNULAR CLEAR

SPACE BETWEEN CABLE AND SLEEVE FOR INSTALLING MECHANICAL SLEEVE SEALS.

260553 - ELECTRICAL IDENTIFICATION:

A. NAMEPLATES: ENGRAVED PLASTIC LAMINATE NAMEPLATES: PROVIDE ENGRAVING PHENOLIC PLASTIC LAMINATE IN SIZES AND THICKNESS INDICATED, ENGRAVED WITH 1/16 INCH THICK LINES WITH SQUARE STANDARD PICA LETTERING AND WORDING AS SPECIFIED HEREIN, BLACK FACE AND WHITE LETTER FOR NORMAL SYSTEMS AND RED AND WHITE FOR EMERGENCY AND FIRE ALARM SYSTEMS. PUNCH FOR MECHANICAL FASTENING, EXCEPT WHERE ADHESIVE MOUNTING IS NECESSARY BECAUSE OF SUBSTRATE. MATERIAL THICKNESS SHALL BE 1/16 INCH. PROVIDE BEVELED EDGE IN ORDER TO ELIMINATE SHARP CORNERS. PROVIDE SELF-TAPPING STAINLESS STEEL ROUND HEAD SCREWS. PROVIDE CONTACT TYPE PERMANENT ADHESIVE WHERE SCREWS CANNOT OR SHALL NOT PENETRATE THE SUBSTRATE. ADHESIVE NAMEPLATE SHALL BE PERMANENTLY INSTALLED. TITLES SHALL BE 1/2" INCH HIGH AND ALL OTHER LETTERING SHALL BE 1/4 INCH HIGH.

B. JUNCTION BOX IDENTIFICATION: PROVIDE NEAT INDELIBLE FELT TIP, STENCILED MARKING ON JUNCTION BOXES. LETTER SIZES SHALL BE 1 INCH HIGH MINIMUM. PROVIDE NON-STENCILED MARKINGS INSIDE THE JUNCTION BOX. LABEL TO

INDICATE THE CIRCUITS CONTAINED THEREIN.

C. PULLBOX IDENTIFICATION: PROVIDE NEAT INDELIBLE FELT TIP, STENCILED MARKING ON PULLBOX COVERS. LETTER SIZES SHALL BE 1 INCH HIGH MINIMUM. PROVIDE NON-STENCILED MARKINGS INSIDE THE PULLBOX AND ON THE EXTERIOR EDGE TO MATCH THE COVER MARKINGS. LABEL TO INDICATE THE CIRCUITS CONTAINED THEREIN, SOURCE PANEL AND

DESTINATION.

262416 - PANELBOARDS:

A. ELECTRICAL COMPONENTS, DEVICES AND ACCESSORIES: LISTED AND LABELED AS DEFINED IN NFPA 70 BY A QUALIFIED TESTING AGENCY AND MARKED FOR INTENDED LOCATION AND APPLICATION. PANELBOARDS SHALL BE AS

MANUFACTURED BY EATON, GENERAL ELECTRIC, SIEMENS OR SQUARE D.

B. PROVIDE PANELBOARDS WITH MAIN BREAKER OR MAIN LUBS WHERE SHOWN ON THE DRAWINGS, OF A DEAD FRONT, DISTRIBUTED PHASE SEQUENCE DESIGN. PROVIDE WITH COPPER BUSES. PANELBOARDS SHALL BE EQUIPPED WITH HINGED TRIM FRONT COVER AND KEYED ALIKE. PANELBOARDS CAN BE EITHER FULLY RATED OR SERIES RATED.

C. DISTRIBUTION TYPE PANELBOARDS SHALL BE USED FOR 600 AMP AND LARGER PANELBOARDS. CIRCUIT BREAKERS AND MAIN CIRCUIT BREAKERS SHALL BE ELECTRONIC TRIP CIRCUIT BREAKERS WITH RMS SENSING, FIELD REPLACEABLE RATING PLUG OR ELECTRONIC TRIP WITH FIELD ADJUSTABLE SETTINGS FOR INSTANTANEOUS TRIP, LONG AND SHORT- TIME PICKUP AND ADJUSTABLE LEVELS. FRAME AND TRIP SIZES INDICATED IN THE SCHEDULES. MAIN CIRCUIT BREAKERS

SHALL BE 100 PERCENT RATED MAINS.

D. LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS SHALL BE USED FOR 400 AMP AND SMALLER PANELBOARDS UNLESS OTHERWISE NOTED. CIRCUIT BREAKERS SHALL BE BOLT-ON QUICK-MAKE, QUICK-BREAK THERMAL-MAGNETIC TYPE WITH FRAME AND TRIP SIZES INDICATED IN THE SCHEDULES. ADJUSTABLE MAGNETIC TRIP SETTING FOR CIRCUIT- BREAKER FRAME SIZES 250 AMP AND LARGER. BREAKERS SHALL TRIP FREE OF THE HANDLE AND TRIPPING SHALL BE INDICATED BY THE HANDLE ASSUMING A POSITION BETWEEN OFF AND ON. MULTI-POLE BREAKERS SHALL BE INTERNAL, COMMON TRIP WITH SINGLE OPERATING HANDLE; EXTERNAL HANDLE TIES ARE NOT ACCEPTABLE.

E. FOR FLUSH MOUNTED PANELBOARDS STUB FOUR (4) 1 INCH EMPTY CONDUITS FROM PANELBOARD INTO ACCESSIBLE CEILING SPACE OR SPACE DESIGNATED TO BE CEILING SPACE IN THE FUTURE. ARRANGE CONDUCTORS IN GUTTERS INTO

GROUPS AND BUNDLE AND WRAP WITH WIRE TIES.

F. FIELD QUALITY CONTROL: PERFORM TESTS AND INSPECTIONS. TEST INSULATION RESISTANCE FOR EACH PANELBOARD BUSS, COMPONENT, CONNECTING SUPPLY, FEEDER AND CONTROL CIRCUIT. TEST CONTINUITY OF EACH CIRCUIT.

PERFORM EACH VISUAL AND MECHANICAL INSPECTION AND ELECTRICAL TEST STATED IN NETA ACCEPTANCE TESTING SPECIFICATION. CERTIFY COMPLIANCE WITH TEST PARAMETERS AND CORRECT MALFUNCTIONING UNITS ON-SITE, WHERE POSSIBLE AND RE-TEST TO DEMONSTRATE COMPLIANCE; OTHERWISE, REPLACE WITH NEW UNITS AND RE-TEST.

G. DIRECTORIES: A TYPE PANELBOARD DIRECTORY SHALL BE PROVIDED FOR EACH PANELBOARD AND SHALL INDICATE THE ACTUAL CIRCUIT NUMBER USED, ROOM NAME AND TYPE OF LOAD. ROOM NAMES SHALL BE THE ACTUAL NAME OR ROOM NUMBER USED NOT NECESSARILY AS SHOWN ON THE DRAWINGS. WHERE PANEL SCHEDULES ARE INDICATED ON THE DRAWINGS AS 'RECEPTACLES' OR 'LIGHTING', ETC. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INCLUDE

THE SPECIFIC AREA SERVED.

262726 - WIRING DEVICES:

A. WIRING DEVICES, COMPONENTS AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70 BY A QUALIFIED TESTING AGENCY AND MARKED FOR INTENDED LOCATION AND APPLICATION. WIRING DEVICES SHALL BE AS

MANUFACTURED BY COOPER, HUBBELL, LEVITON OR PASS & SEYMOUR.

B. PROVIDE WHITE COLORED DEVICES FOR NORMAL POWER, UNLESS OTHERWISE NOTED. PROVIDE RED COLORED DEVICES FOR EMERGENCY POWER. PROVIDE BRUSHED STAINLESS STEEL COVER PLATES. COORDINATE WITH ARCHITECT FOR

FINAL COLOR SELECTION OF DEVICES AND COVER PLATES.

C. RECEPTACLES: SPECIFICATION GRADE 20 AMP, 125 VOLT, 3 WIRE GROUNDED, MOUNTED AT 18" A.F.F. TO THE CENTERLINE

UNLESS NOTED OTHERWISE. COLOR SHALL MATCH TOGGLE SWITCHES.

D. TOGGLE SWITCHES: HEAVY DUTY SPECIFICATION GRADE 20 AMP, 120/277 VAC, HEAVY DUTY, QUIET TYPE: SINGLE POLE, TWO POLE, THREE WAY OR FOUR WAY AS REQUIRED FOR APPLICATION.

E. FLUORESCENT DIMMERS: PRESET SLIDE CONTROL: LUTRON OR EQUIVALENT, COMPATIBLE WITH DIMMABLE BALLAST.

F. OCCUPANCY SENSOR SWITCHES, 120/277 VAC, WALL MOUNTED SINGLE POLE - LEVITON OR EQUIVALENT.

G. LED DIMMERS: PRESET SLIDE CONTROL: LUTRON OR EQUIVALENT, COMPATIBLE WITH DIMMABLE DRIVER.

H. INSTALL DEVICE PLATES IN FULL CONTACT WITH WALL SURFACE OR SURFACE MOUNTED BOX. PLATES SHALL NOT

PROJECT OUT FROM THE WALL OR FROM THE EDGE OF THE BOX.

I. ALL DEVICE PLATES FOR RECEPTACLES AND SWITCHES SHALL BE LABELED. SHOW PANEL DESIGNATION AND BRANCH

CIRCUIT SERVING EACH RECEPTACLE.

262813 - FUSES:

A. FUSES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY AND MARKED FOR INTENDED LOCATION AND APPLICATION. PANELBOARDS SHALL BE AS MANUFACTURED BY COOPER BUSSMANN, FERRAS SHAWMUT, LITTLEFUSE OR EDISON. FUSES SHALL BE NON-RENEWABLE CARTRIDGE TYPE RATED 600 V AC AND LESS FOR USE IN ENCLOSED SWITCHES, FUSIBLE PANELBOARDS, SWITCHBOARDS, ENCLOSED CONTROLLERS, MOTOR CONTROL

CENTERS AND CONTROL CIRCUITS.

B. FUSE APPLICATIONS: SERVICE ENTRANCE, CLASS L, TIME DELAY. FEEDERS, CLASS RK5, FAST ACTING. MOTOR BRANCH CIRCUITS AND OTHER BRANCH CIRCUITS: CLASS RK5, TIME DELAY. CONTROL CIRCUITS: CLASS CC, TIME DELAY.

C. INSTALLATION: INSTALL FUSES IN FUSIBLE DEVICES. ARRANGE FUSES SO RATING INFORMATION IS READABLE WITHOUT REMOVING FUSE. FUSES SHALL BE SIZED IN ACCORDANCE WITH THE MANUFACTURER'S MAXIMUM OVER-CURRENT

NAMEPLATE RATING.

262816 - ENCLOSED SWITCHES:

A. GENERAL: ALL DISCONNECT SWITCHES SHALL BE HEAVY-DUTY TYPE, UNLESS SPECIFICALLY NOTED OTHERWISE.

SWITCHES SHALL BE FUSIBLE OR NON-FUSIBLE AND SIZED AS NOTED ON THE DRAWINGS.

B. SWITCHES SHALL BE 240 VOLT RATED ON SYSTEMS UP TO AND INCLUDING 120/240V. ALL SWITCHES SERVING MOTOR LOADS SHALL BE HORSEPOWER RATED. ALL SWITCHES SERVING VFD'S SHALL HAVE AN AUXILIARY CONTACT TO DIS-

ENGAGE THE VFD WHEN SWITCHED OFF.

C. PROVIDE SWITCHES WITH AN EXTERNALLY OPERATED HANDLE: QUICK MAKE QUICK BREAK MECHANISM; THE HANDLE SHALL BE INTERLOCKED WITH THE SWITCH COVER BY MEANS OF A DEFEATABLE INTERLOCK DEVICE. THE SWITCH SHALL

BE LOCKABLE IN THE 'OFF' POSITION WITH A PADLOCK.

265100 - INTERIOR LIGHTING:

A. LUMINAIRES SHALL BE FURNISHED AS SHOWN IN THE LUMINAIRE SCHEDULE AND BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY AND MARKED FOR INTENDED LOCATION AND APPLICATION. IT SHALL SPECIFICALLY BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY EXACT TYPE OF CEILING AND RECESSING DEPTH OF ALL RECESSED FIXTURES AND TO FURNISH THE MOUNTING TRIMS AND ACCESSORIES OF THE SPECIFIED AND / OR APPROVED FIXTURES FOR THE CEILING TO BE INSTALLED. FIXTURES SHALL BE SUPPORTED INDEPENDENTLY OF CEILING

SYSTEMS.

B. LED LUMINAIRES SHALL BE UL 8750 LISTED AND TESTED IN ACCORDANCE WITH LM-79 AND LM-80 STANDARDS. THE LED LUMINAIRE SHALL HAVE A LUMINOUS EFFICACY OF AT LEAST 90 LUMENS / W, A COLOR TEMPERATURE OF 3500K OR 4000K, A CRI OF AT LEAST 80, AN ESTIMATED LIFE OF AT LEAST 50,000 HOURS AT L70 LUMEN MAINTENANCE AND SHALL INCLUDE A

MINIMUM 5 YEAR WARRANTY ON THE ENTIRE LUMINAIRE INCLUDING THE DRIVER.

265600 EXTERIOR LIGHTING:

A. LUMINAIRES SHALL BE FURNISHED AS SHOWN IN THE LUMINAIRE SCHEDULE AND COMPLY WITH UL 1598 AND BE LISTED AND LABELED FOR INSTALLATION IN WET LOCATIONS AS DEFINED IN NFPA 70 AND MARKED FOR INTENDED LOCATION AND APPLICATION. LATERAL LIGHT DISTRIBUTION SHALL COMPLY WITH IESNA RP-8. THE CONTRACTOR SHALL FURNISH STAINLESS STEEL MOUNTING HARDWARE AND REQUIRED ACCESSORIES OF THE SPECIFIED AND / OR APPROVED

FIXTURES.

B. LED LUMINAIRES SHALL BE UL 8750 LISTED AND TESTED IN ACCORDANCE WITH LM-79 AND LM-80 STANDARDS. THE LED LUMINAIRE SHALL HAVE A LUMINOUS EFFICACY OF AT LEAST 90 LUMENS/W, A COLOR TEMPERATURE OF 3500K OR 4000 K, A CRI OF AT LEAST 80, AN ESTIMATED LIFE OF AT LEAST 50,000 HOURS AT L70 LUMEN MAINTENANCE AND SHALL INCLUDE A

MINIMUM 5-YEAR WARRANTY ON THE ENTIRE LUMINAIRE INCLUDING THE DRIVER.

A. LEGEND SHEET AND NOT ALL SYMBOLS MAY BE USED ON DRAWINGS.

B. REFERENCE PLAN SHEETS TO DETERMINE REQUIRED SCOPE OF WORK.

C. THE DRAWINGS ARE DIAGRAMMATIC, AND NOT ALL REQUIRED OFFSETS IN

CONDUIT, CABLE TRAY, BOXES, AND PATHWAY TRANSITIONS ARE SHOWN.

COORDINATE EXACT DIMENSIONAL LOCATIONS WITH EXISTING CONDITIONS

AND OTHER TRADES PRIOR TO INSTALLATION.

D. PROVIDE A MINIMUM OF ONE PULL BOX FOR EVERY 100 FEET OF STRAIGHT

CONDUIT RUNS AND A PULL BOX FOR MORE THAN TWO (2) 90 DEGREE

BENDS IN A CONDUIT RUN. DEBURR, CLEAN, CAP, AND TAG ALL CONDUITS

AND FURNISH WITH A MINIMUM OF TWO (2) PULL STRINGS.

E. INSTALL DEVICES IN AN ORDERLY MANNER AT THE SAME ELEVATION AS

ADJACENT DEVICES, COORDINATED BETWEEN TRADES. WHERE INSTALLED

DEVICES FEED OR ARE ASSOCIATED WITH FURNITURE, COORDINATE EXACT

LOCATIONS WITH FINAL FURNITURE PLAN AND CASEWORK INSTALLER,

PRIOR TO INSTALLATION.

F. COORDINATE OSP / UNDERGROUND COMMUNICATION PATHWAYS WITH CIVIL

ENGINEER PRIOR TO INSTALLATION. COORDINATE OSP / UNDERGROUND

COMMUNICATION PATHWAYS INTO BUILDING WITH STRUCTURAL ENGINEER

PRIOR TO INSTALLATION. WHERE POSSIBLE COLLATE COMMUNICATIONS

OSP / UNDERGROUND PATHWAYS WITH ELECTRICAL OSP / UNDERGROUND

PATHWAYS, U.O.N.

G. COORDINATE ALL REQUIRED CABLING AND COMPONENTS WITH SYSTEM

VENDOR AND/OR INSTALLER.

H. ALL 120V POWER WIRING SHALL BE INSTALLED IN A SEPARATE CONDUIT.

I. ALL CONDUIT ABOVE GRADE SHALL BE METALLIC, ALL CONDUIT BELOW

GRADE SHALL BE PVC UNLESS OTHERWISE NOTED ON DRAWINGS.

J. ALL CONDUIT, WIRING AND ASSOCIATED BACK BOXES SHALL BE FULLY

CONCEALED WITHIN WALLS, FLOORS AND CEILINGS.

K. THE MAXIMUM PULLING TENSION SHALL NOT EXCEED 25 POUNDS TO AVOID

STRETCHING THE CONDUCTORS.

L. COORDINATE LOCATION OF ALL FIRE RATED PENETRATIONS PRIOR TO

PROCEEDING WITH INSTALLATION. ALL PENETRATIONS THROUGH FIRE

RATED BARRIERS SHALL BE COMPLETELY SEALED WITH A LISTED FIRE STOP

SYSTEM IN ACCORDANCE WITH NFPA AND THE AUTHORITY HAVING

JURISDICTION.

M. COORDINATE EXTERIOR AND WALL MOUNTED CAMERA LOCATIONS AND

MOUNTING HEIGHTS PRIOR TO ROUGH-IN. COORDINATION MEETINGS SHALL

BE SCHEDULED THROUGH THE ARCHITECTS AND/OR OWNER.

GENERAL SYSTEM NOTES

FLORIDA LIC No: AR95989

Carbon design & architecture 263 13th Avenue South Suite 375 St. Petersburg, FL 33701 O:: 941.362.4312 W:: www.carbonAE.com

Project No:

PROJECT DATA

Project Na:

CLIENT DATA

Client:

ARCHITECT DATA

ENGINEER DATA

ISSUE + REVISION DATA

ENGINEER SEAL

CHECKED BY

DRAWN BY

PRINTED:24X36 SHEET

ARCH D

EOR: JULIUS D. DAVIS, P.E. #58005

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIUS D. DAVIS,

P.E. #58005 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON

ANY ELECTRONIC COPIES

6005 Benjamin Rd.

Suite A Tampa, FL 33634 O:: 888.891.9713 W:: www.voltairinc.com

COA: #27158

Proj: #01.22029

TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY

WITH THE APPLICABLE MINIMUM BUILDING CODES

8/12/2024 4:45:49 PM

8/12/2024 4:45:49 PM

E-001

SPECIFICATIONS - ELECTRICAL

100% CD's Set

05.28.2024

24020

OCALA SUNTRAN

RESTROOMS & KIOSK

CITY OF OCALA

501 NE 1st Ave.

Ocala, FL 34470

R.F.W.

R.F.W.

LUMINAIRE SCHEDULE

IMAGE TYPE DESCRIPTION MANUFACTURER MOUNTING LUMENS LAMP/WATTAGE VOLTAGE

A 2X2 LUMINAIRE (CCT SWITCH TO 3500K)DAYBRITE: 2SBP3040L8CS 2 UNV DIM

RECESSED 4207 LED/39W MVOLT

A1

2X2 LUMINAIRE WITH DRYWALL

CEILING ADAPTOR (CCT SWITCH TO

3500K)

DAYBRITE: 2SBP3040L8CS 2 UNV DIM FMA22

B 4' STRIP FIXTURE (CCT SWITCH TO

4000K)

DAYBRITE: SDS 4 2448 8CST UNV DIM SURFACE 4850 LED/42W MVOLT

C 4' VANDAL WRAP H.E. WILLIAMS: AVX 4 L16/BLU CPC (MAX45W) DIM UNV SURFACE BLUE LED/45W MVOLT

C1 4' VANDAL WRAP H.E. WILLIAMS: AVX 4 L62 835 WPC DIM UNV WALL @ 8' AFF 6200 LED/57W MVOLT

X EXIT SIGN BEGHELLI: PX R SA SURFACE LED MVOLT

EM EMERGENCY UNIT BEGHELLI: BBX SE WH WALL 600L/HEAD LED MVOLT

WP WALL PACK (LUMEN SWITCH TO 40%

AND CCT SWITCH TO 4000K)

TRULY GREEN SOLUTIONS: WPFS S L C U D EM WALL 3404 LED/23W MVOLT

NOTES:

1. ALL INTERIOR LUMINAIRE SHALL HAVE 4000 KELVIN COLOR TEMPERATURE AND EXTERIOR 3500 KELVIN COLOR TEMPERATURE, UNLESS OTHERWISE NOTED.

2. EXIT LIGHTS SHALL BE CONNECTED TO THE NEAREST UNSWITCHED CIRCUIT.

3. FINAL FIXTURE COLORS AND FINISHES SHALL BE SELECTED AND APPROVED BY OWNER/ARCHITECT.

4. COOPER, LITHONIA , AND COLUMBIA LIGHTING MAY SUBMIT APPROVED EQUIVALENTS.

GENERAL NOTES

A. COORDINATE COLORS AND FINISHED WITH ARCHITECT AND / OR OWNER PRIOR TO

ORDERING.

B. WHERE A LUMINAIRE IS AVAILABLE IN TRIM-BASED AND TRIMLESS CONFIGURATIONS,

COORDINATE THE APPROPRIATE CONFIGURATION WITH THE ARCHITECT PRIOR TO

ORDERING.

C. COORDINATE CEILING TYPES WITH THE ARCHITECT PRIOR TO ORDERING. ONE (1)

LUMINAIRE TYPE MAY BE LOCATED WITHIN MULTIPLE CEILING TYPES. REFER TO

ARCHITECTURAL REFLECTED CEILING PLANS FOR FURTHER INFORMATION.

D. PROVIDE INDEPENDENT SUPPORTS TO THE BUILDING STRUCTURE IN ACCORDANCE WITH

THE APPLICABLE DIVISION 26 SPECIFICATION SECTIONS.

E. WHERE A LUMINAIRE IS EQUIPPED WITH A DIMMABLE DRIVER, BUT IS NOT DEPICTED AS

CONTROLLED VIA A DIMMER SWITCH ON THE LIGHTING PLANS, TERMINATE THE 0-10V

CONTROL WIRING IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS TO

ALLOW FOR ON / OFF SWITCHING.

F. VERIFY COMPATIBILITY BETWEEN DIMMER SWITCHES AND DIMMABLE DRIVERS PRIOR TO

ORDERING.

G. COORDINATE LUMINAIRE LOCATIONS, MOUNTING HEIGHTS (WHERE APPLICABLE),

SUSPENSION HEIGHTS (WHERE APPLICABLE) AND SUSPENSION METHODS (WHERE

APPLICABLE) WITH ARCHITECT PRIOR TO ORDERING, ROUGH-IN AND INSTALLATION.

H. START-UP: ELECTRICAL CONTRACTOR SHALL CONTACT LIGHTING CONTROL

MANUFACTURER AT LEAST THIRTY (30) DAYS BEFORE TURNOVER OF PROJECT. LIGHTING

CONTROL MANUFACTURER WILL BE ON SITE TO PROGRAM THE LIGHTING CONTROL

SYSTEM WITH FEEDBACK FROM OWNER.

GENERAL NOTES

A. COORDINATE ALL ELECTRICAL REQUIREMENTS WITH THE DIVISION 22 CONTRACTOR,

DIVISION 23 CONTRACTOR AND APPROVED EQUIPMENT SUBMITTALS PRIOR TO ROUGH-IN

AND INSTALLATION. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR FURTHER

INFORMATION.

B. FOR ALL VFD-DRIVEN EQUIPMENT, PROVIDE A VFD-RATED CABLE ASSEMBLY BETWEEN THE

VFD OUTPUT AND ASSOCIATED EQUIPMENT AS FOLLOWS; XLPE INSULATION RATED AT

2,000V, SHIELDED, 100% EQUIPMENT GROUND. CONDUIT AND CONDUCTORS BETWEEN

SOURCE AND VFD INPUT SHALL BE AS SCHEDULED.

FLORIDA LIC No: AR95989

Carbon design & architecture 263 13th Avenue South Suite 375 St. Petersburg, FL 33701 O:: 941.362.4312 W:: www.carbonAE.com

Project No:

PROJECT DATA

Project Na:

CLIENT DATA

Client:

ARCHITECT DATA

ENGINEER DATA

ISSUE + REVISION DATA

ENGINEER SEAL

CHECKED BY

DRAWN BY

PRINTED:24X36 SHEET

ARCH D

EOR: JULIUS D. DAVIS, P.E. #58005

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIUS D. DAVIS,

P.E. #58005 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON

ANY ELECTRONIC COPIES

6005 Benjamin Rd.

Suite A Tampa, FL 33634 O:: 888.891.9713 W:: www.voltairinc.com

COA: #27158

Proj: #01.22029

TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY

WITH THE APPLICABLE MINIMUM BUILDING CODES

8/12/2024 4:45:50 PM

8/12/2024 4:45:50 PM

E-002

SCHEDULES - ELECTRICAL

100% CD's Set

05.28.2024

24020

OCALA SUNTRAN

RESTROOMS & KIOSK

CITY OF OCALA

501 NE 1st Ave.

Ocala, FL 34470

R.F.W.

R.F.W.

ELECTRICAL MECHANICAL EQUIPMENT SCHEDULE

TAG HP LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

COMMENTSNEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

AC-1 ---- 42 VA 0.2 208 V 1 3/4" CONDUIT WITH 3#12 AND 1#12 GROUND MB 11,13 --- --- --- --- 2 --- 26 PROVIDE MOTORIZED DISCONNECT SWITCH

AC-2 ---- 42 VA 0.2 208 V 1 3/4" CONDUIT WITH 3#12 AND 1#12 GROUND MB 11,13 --- --- --- --- 2 --- 26 PROVIDE MOTORIZED DISCONNECT SWITCH

AC-3 ---- 42 VA 0.2 208 V 1 3/4" CONDUIT WITH 3#12 AND 1#12 GROUND MB 11,13 --- --- --- --- 2 --- 26 PROVIDE MOTORIZED DISCONNECT SWITCH

CU-1 ---- 3910 VA 18.8 208 V 1 1" CONDUIT WITH 3#8 AND 1#10 GROUND MB 11,13 --- --- --- 60A 2 NEMA 3R 26 PROVIDE NON-FUSED DISCONNECT SWITCH

EF-1 ---- 24 VA .2 120 V 1 3/4" CONDUIT WITH 2#12 AND 1#12 GROUND MB 7 --- --- --- --- --- --- 23 PROVIDE MOTORIZED DISCONNECT SWITCH

EF-2 ---- 24 VA .2 120 V 1 3/4" CONDUIT WITH 2#12 AND 1#12 GROUND MB 21 --- --- --- --- --- --- 23 PROVIDE MOTORIZED DISCONNECT SWITCH

ERV-1 ---- 30 VA 0.5 208 V 2 3/4" CONDUIT WITH 2#12 AND 1#12 GROUND MB 35,37 --- --- --- 30A 2 NEMA 1 26 PROVIDE NON-FUSED DISCONNECT SWITCH

EWH-1 ---- 3000 VA 14.4 208 V 2 3/4" CONDUIT WITH 3#12 AND 1#12 GROUND MB 30,32 --- --- --- 30A 2 NEMA 1 26 PROVIDE NON-FUSED DISCONNECT SWITCH

No: Description: Date:

2 PERMIT COMMENTS 08/12/24

2 2

SAN

SD

SAN

SD

SD

FE

HH

WP@ 6' 9"

WP@ 6' 9"

WP@ 6' 9"

WP@ 9' 6"

WP@ 6' 9"

WP@ 6' 9"

WP@ 6' 10"

WP@ 7' 10"

WP@ 6' 10"

Luminaire list

Index Manufacturer Article name Luminous flux Maintenance factor Connected load Quantity

WP tgs WPF-S 65W 4000K 10242 lm 0.40 62.4 W 9

Name Parameter Min Max Average Mean/Min Max/Min

Building Exterior Perpendicular illuminance

1.01 fc 32.2 fc 12.6 fc 12.39 31.83

GENERAL NOTES

A. PROVIDE IN-GRADE HANDHOLES AS REQUIRED TO INSTALL POWER AND SIGNAL CABLES.

KEY NOTES

2'-8"1

4 FLORIDA LIC No: AR95989

Carbon design & architecture 263 13th Avenue South Suite 375 St. Petersburg, FL 33701 O:: 941.362.4312 W:: www.carbonAE.com

Project No:

PROJECT DATA

Project Na:

CLIENT DATA

Client:

ARCHITECT DATA

ENGINEER DATA

ISSUE + REVISION DATA

ENGINEER SEAL

CHECKED BY

DRAWN BY

PRINTED:24X36 SHEET

ARCH D

EOR: JULIUS D. DAVIS, P.E. #58005

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY JULIUS D. DAVIS,

P.E. #58005 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE…