IP for CM - Full Set of Drawings.pdf
PDF 17 MB Posted
- Solicitation number
- 36C24421R0046
About this file
This document provides details on a federal solicitation to renovate inpatient pharmacy spaces at a Department of Veterans Affairs medical center. The solicitation seeks general construction and alterations to renovate existing compounding, office, files, and mechanical equipment rooms into new chemo mixing labs, a hazardous chemical room, office space, and a relocated dry drug storage area. A mandatory site visit will be held on March 23, 2021 for up to two representatives from each firm, who must confirm attendance by contacting the contracting officer by the specified date and time due to social distancing requirements. The work is to be completed at the Veterans Affairs Medical Center in Philadelphia, Pennsylvania under Solicitation Number 36C24421R0046 issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24421R0046 0003.docx | DOCX document | |
| Revised Dwg AE 111.pdf | ||
| Revised Dwg ES101.pdf | ||
| Addnl Dwg AE 111.1.pdf | ||
| Revised Dwg S301.pdf | ||
| Camera Spec.pdf | ||
| 36C24421R0046 0002.docx | DOCX document | |
| 36C24421R0046 0001.docx | DOCX document | |
| IP for CM - Full Set of Specifications.pdf | ||
| 36C24421R0046.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VAMC
PHILADELPHIA
NORTH
A R C H I T E C T S E N G I N E E R S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
1/8" = 1'-0"
Philadelphia VA Medical Center 3900 Woodland Ave., Philadelphia, PA 19104
08/27/2020
642-17-100
DRKBJ
Renovate Inpatient Pharmacy for Chemotherapy I.V. Mixing
BID SETCOVER SHEET
GI101
Department of Veterans Affairs
A/E RENOVATE INPATIENT PHARMACY
FOR CHEMOTHERAPY I.V. MIXING
CORPORAL MICHAEL J. CRESCENZ VA MEDICAL CENTER
3900 WOODLAND AVENUE, PHILADELPHIA, PA 19104
LOCATION MAP DRAWING LIST
APPLICABLE CODES PROJECT CONTACT DIRECTORY
Approved by Medical Center Director Approved by Project Section Supervisor
Approved by Project CORApproved by Medical Center Assistant Director
Approved by Infection Control Nurse
Approved by Chief Engineer
Approved by Safety Officer
Approved by Bio-Med Engineer
CONTRACTING OFFICER REPRESENTATIVE (COR)
ARCHITECT
MEP/FP ENGINEER
FREDERICK SCHULTZ
PHILADELPHIA VAMC
3900 WOODLAND AVENUE, BUILDING 5
PHONE: (215) 823-5800 x5771 Frederick.Schultz@va.gov
CB DESIGN GROUP, INC
KEN JONES
11720 BELTSVILLE DRIVE, SUITE 350
CALVERTON, MARYLAND 20705
CELL: (443) 388-7351
kjones@cbdg-ae.com
H.F. LENZ COMPANY
BRIAN RAGER
1407 SCALP AVENUE
JOHNSTOWN, PA 15904
PHONE: (814) 269-9312
brager@hflenz.com
GENERAL INFORMATION
ARCHITECTURAL
PLUMBING
MECHANICAL
ELECTRICAL
GI101 COVER SHEET
GI102 SYMBOLS, ABBREVIATIONS AND NOTES
GI103 LIFE SAFETY PLAN
GI104 DOOR SCHEDULE AND DETAILS
AE101 PHASES 2A & 2B
AE102 PHASES 2C & 3A
AE103 PHASES 3B & 3C
AE104 FINISH PLAN, EQUIPMENT PLAN & PARTITION TYPES
AE105 INTERIOR ELEVATIONS
AE106 REFLECTED CEILING PLANS - DEMOLITION AND NEW WORK
AE107 MISCELLANEOUS DETAILS
AE111 EXTERIOR ELEVATIONS AND DETAILS
AE112 EXTERIOR ELEVATIONS AND DETAILS
P001 PLUMBING NOTES, SYMBOLS, ABBREVIATIONS & SCHEDULE
PD101 PLUMBING SECOND FLOOR DEMOLITION
P101 PLUMBING SECOND FLOOR NEW WORK
M001 MECHANICAL NOTES, SYMBOLS, & ABBREVIATIONS
MD101 MECHANICAL SECOND FLOOR DEMO WORK DUCTWORK & PIPING
MD401 MECHANICAL ROOM PLAN 3D100C - DEMOLITION WORK
MH101 MECHANICAL SECOND FLOOR NEW WORK - DUCTWORK AND PIPING
MH102 MECHANICAL ROOF PLAN - PENTHOUSE 3D100C & NINTH FLOOR
MH301 MECHANICAL SECTIONS
MH302 MECHANICAL SECTIONS
MH401 MECHANICAL EQUIPMENT ROOM PLAN 3D100C - NEW WORK
MH402 MECHANICAL THIRD FLOOR PLAN TEMPORARY AC-14
MH901 MECHANICAL 3D ISOMETRIC
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
MI701 MECHANICAL CONTROLS
MI702 MECHANICAL CONTROLS - 1-3NE-AC-14
MI703 MECHANICAL CONTROLS - 1-3NE-PHARM-AC-1
E001 ELECTRICAL NOTES, SYMBOLS, & ABBREVIATIONS
ED101 ELECTRICAL PLANS - SECOND & THIRD FLOORS - DEMOLITION
EL101 ELECTRICAL SECOND FLOOR LIGHTING NEW WORK
EP101 ELECTRICAL FLOOR PLANS - POWER NEW WORK
EP102 OVERALL THIRD FLOOR ELECTRICAL PLAN
ES101 ELECTRICAL FLOOR PLANS - SIGNAL NEW WORK
E501 ELECTRICAL DETAILS
E502 ELECTRICAL DETAILS
E601 ELECTRICAL SCHEDULES
MASTER CONSTRUCTION SPECIFICATIONS (PG-18-1)
LIFE SAFETY CODE NFPA 101 - 2018
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
VA DESIGN MANUALS:
FIRE PROTECTION, SEVENTH EDITION - DECEMBER 2015
INTERIOR DESIGN MANUAL, MAY 2008
VA BARRIER FREE DESIGN STANDARD (PG-18-13), REV
11/1/18
USP CHAPTER 797, PHARMACEUTICAL COMPOUNDING - STERILE
PREPARATIONS, 2019
USP CHAPTER 800, HAZARDOUS DRUGS - HANDLING IN
HEALTHCARE, 2019FIRE PROTECTION
FP101 FIRE PROTECTION SECOND FLOOR NEW WORK
FP102 FIRE PROTECTION THIRD FLOOR NEW WORK
STRUCTURAL
S001 STRUCTURAL GENERAL NOTES
S101 STRUCTURAL FRAMING PLANS
S102 STRUCTURAL FRAMING PLAN AND SECTIONS @ LOUVERS
S301 SECTIONS AND DETAILS
S302 SECTIONS AND DETAILS
S900 3D RENDERING
Approved by Chief of Police
& AND
@ AT
C CENTERLINE
# NUMBER
AB ANCHOR BOLT
ABV ABOVE
ACT ACOUSTIC CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH
DISABILITIES ACT
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF
ARCHITECTS
ALUM ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AUTO AUTOMATIC
AVG AVERAGE
BD BOARD
BLDG BUILDING
BLK BLOCK
BM BEAM
BOT BOTTOM
BRG BEARING
BEL BELOW
BR BUMPER RAIL
BRK BRICK
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CCT CUBICLE CURTAIN TRACK
CG CORNER GUARD
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CT CERAMIC TILE
CLG CEILING
CL CLOSET
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CU CUBIC
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DOOR OPENING
DOZ DOZEN
DP DAMPPROOFING
DR DOOR
DWG DRAWING
DWGS DRAWINGS
DWR DRAWER
E EAST
EA EXHAUST AIR, EACH
EL ELEVATION
ELEV ELEVATION
ELEC ELECTRICAL
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
EP ELECTRICAL PANELBOARD
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWS EYE WASH STATION
EXP EXPANSION
EJ EXPANSION JOINT
EXIST EXISTING
EXT EXTERIOR
FA FIRE ALARM
FB FACE BRICK
FD FLOOR DRAIN
FDC FIRE DEPARTMENT
CONNECTION
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FF FINISH FACE
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FLUOR FLUORESCENT
FO __ FACE OF __
FOC FACE OF CONCRETE
FOS FACE OF STUD
FOW FACE OF WALL
FPRF FIREPROOF(ING)
FR FIRE RATING, FRAME
FRMG FRAMING
FS FULL SIZE
FT FOOT OR FEET
FTG FOOTING
FUR FURRING
FUT FUTURE
GC GENERAL CONTRACTOR
GA GAUGE
GAL GALLON
GALV GALVANIZED
GALV STL GALVANIZED STEEL
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GUARD
GL GLASS
GND GROUND
GR GRADE
GWB GYPSUM WALLBOARD
GYP BD GYPSUM WALLBOARD
HB HOSE BIBB
HC HOLLOW CORE
HD HEAD
HDWR HARDWARE
HDWD HARDWOOD
HT HEIGHT
HNDRL HANDRAIL
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMF HOLLOW METAL FRAME
HR HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HP HIGH POINT
HR HOUR
HVAC HEATING, VENTILATION, AIR
CONDITIONING
IBC INTERNATIONAL BUILDING
CODE
ID IDENTIFICATION, INSIDE
DIAMETER / DIMENSION
IN INCH
INCL INDLUDE(D)
INSUL INSULATION
INT INTERIOR
INV INVERT
JAN JANITOR
JST JOIST
JT JOINT
KP KICK PLATE
KO KNOCKOUT
L LENGTH
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LBS POUND
LED LIGHT EMITTING DIODE
LF LINEAR FEET
LH LEFT HAND
LIN LINEAR
LIQ LIQUID
LKR LOCKER
LG LONG
LL LEAD LINED
LLV LONG LEG VERTICAL
LP LOW POINT
LRG LARGE
LT LIGHT
LT WT LIGHTWEIGHT
LVR LOUVER
MATL MATERIAL
MAS MASONRY
MAX MAXIMUM
MECH MECHANICAL
MTL METAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MP MOP PLATE
MTD MOUNTED
N NORTH
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER /
DIMENSION
OFF OFFICE
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OH OVERHEAD
OZ OUNCE
PAV PAVING
PC PRECAST CONCRETE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PLBG PLUMBING
PMF PREMOLDED FILLER
PR PAIR
PT POINT
PTN PARTITION
QT QUARRY TILE
R RADIUS, RISER
RA RETURN AIR
RAD RADIUS
RB RESILIENT BASE, RUBBER
BASE
RD ROOF DRAIN
RL ROOF LEADER
REF REFERENCE
REFR REFRIGERATOR
REQ'D REQUIRED
REV REVISION
RFI REQUEST FOR
INFORMATION
RFP REQUEST FOR PROPOSAL
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
S SOUTH
SA SUPPLY AIR
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SH SPRINKLER HEAD
SHT SHEET
SIM SIMILAR
SAN SANITARY
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
STA STATION
STD STANDARD
STO STORAGE
STL STEEL
SS STAINLESS STEEL
STOR STEERAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
TEL TELEPHONE
TEMP TEMPERED
T&G TONGUE AND GROOVE
THK THICK
TOC TOP OF CONCRETE
TOP TOP OF PAVEMENT
TOS TOP OF STEEL
TOW TOP OF WALL
TV TELEVISION
TYP TYPICAL
UNFIN UNFINISHED
UON UNLESS OTHERWISE
NOTED
VB BAPOR BARRIER
VERT VERTICAL
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VTR VET THRU ROOF
W WEST
W/ WITH
WD WOOD
W/O WITHOUT
WP WATERPROOF
WT WEIGHT
WWF WELDED WIRE FRAME
ARCHITECTURAL ABBREVIATIONS
NOTE: ALL ABBREVIATIONS SHOWN MAY
NOT BE USED ON THIS PROJECT. CERTAIN
COMMON ABBREVIATIONS MAY NOT BE
SHOWN.
NORTH
NORTH ARROW
Room name
101ROOM TAG
EQUIPMENT TAG
COLUMN GRID TAG 0
A101
BUILDING SECTION
PARTITION TAG
NEW DOOR
CENTERLINE
REVISION CLOUD
BREAK LINE
SPOT ELEVATION
A101
ENLARGED PLAN / DETAIL REFERENCE
x'-
BUILDING ELEVATION
A101
REVISION
INTERIOR ELEVATION
GLAZING TYPE TAG
1tTOILET ACCESSORY TAG
EXISTING COLUMN
GRID TAG
FLOOR LINES IN
EXTERIOR ELEVATION; CENTER
PROPERTY LINE,
BOUNDARY LINES
MATCH LINE
A701
A1
A
SYMBOL LEGEND
EXISTING DOOR
1i
WOOD
WOOD FINISH
ALUMINUM
STEEL
EARTH
GYPSUM - PLASTER
MASONRY -
CONCRETE BLOCK
RIGID INSULATION
BATT INSULATION
PLYWOOD
CONCRETE
MATERIAL SCHEDULE
GENERAL CONDITION NOTES - ARCHITECTURAL
1. PROJECT AREAS WILL BE OCCUPIED DURING PERFORMANCE OF WORK. IMMEDIATE AREAS OF
ALTERATIONS WILL BE VACATED. ALL CONTRACTOR WORK WILL BE PERFORMED DURING NORMAL DAYTIME WORKING HOURS BETWEEN 7:00 AM - 3:30 PM UNLESS ADJACENT VA EMPLOYEES ARE DISTURBED BY A PARTICULAR WORK TASK, THEN THAT WORK SHALL BE PREFORMED BETWEEN 4:00 PM - 11:00 PM
2. BEFORE STARTING WORK WITHIN AN OCCUPIED AREA, THE CONTRACTOR WILL BE RESPONSIBLE TO SET- UP TEMPORARY/PERMANENT CONSTRUCTION/ICRA BARRIERS WITH ANTEROOM AND MAINTAIN NEGATIVE PRESSURE. ALL TEMPORARY CONSTRUCTION BARRIERS OUTSIDE THE INDICATED CONSTRUCTION PHASE AREA WILL BE REMOVED AT THE CONCLUSION OF THE WORK SHIFT. THE CONTRACTOR WILL BE RESPONSIBLE TO
CLEAN AND PREPARE THE AREA TO BE OCCUPIED BY MEDICAL CENTER STAFF AND RESIDENCE.
3. DIMENSIONS SUPERSEDE DRAWINGS. DO NOT SCALE PLANS. DIMENSIONS ARE TO THE FACE OF EXISTING MATERIALS UNLESS OTHERWISE NOTED. DIMENSIONS AND ELEVATIONS SHALL BE VERIFIED AT THE SITE BEFORE PROCEEDING WITH THE WORK. NOTIFY THE ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, AND MATERIALS REQUIRED FOR THE CONTRACTED WORK. REPORT ALL DISCREPANCIES TO ARCHITECT PRIOR TO FABRICATIONS AND ERECTION.
4. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW ALL APPLICABLE SAFETY CODES AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE CONSTRUCTION PROCEDURES/ SEQUENCING AND TO ENSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING CONSTRUCTION. CONTRACTOR SHALL PROVIDE ADEQUATE SHORING AND BRACING DURING DEMOLITION AND CONSTRUCTION TO SUPPORT LOADS, AND REMOVE SHORING AND BRACING
UPON COMPLETION OF THE PROJECT.
5. DO NOT CUT AND PATCH STRUCTURAL ELEMENTS IN A MANNER THAT WOULD REDUCE THEIR LOAD
CARRYING CAPACITY OR LOAD-DEFLECTION RATIO.
6. WHERE EXISTING CONSTRUCTION, EQUIPMENT, ETC. IS REQUIRED TO BE REMOVED, RESTORE EXPOSED FINISHES OF CUT AND PATCHED AREAS AND EXTEND FINISH RESTORATION INTO ADJOINING CONSTRUCTION IN A MANNER THAT WILL ELIMINATE EVIDENCE OF PATCHING AND REFINISHING. CUT EXISTING CONSTRUCTION USING METHODS LEAST LIKELY TO DAMAGE ELEMENTS TO BE RETAINED OR ADJOINING CONSTRUCTION. WHERE INDICATED TO REMOVE FINISHES, REMOVE SO TOTALLY, FROM PLANE TO PLANE, TREAT REMAINING
SUBSURFACE TO RECEIVE NEW FINISHES DESIGNATED.
7. WHERE EXISTING CONSTRUCTION, EQUIPMENT, ETC. SHOWN TO BE RELOCATED SHALL BE COORDINATED BY THE CONTRACTOR WITH THE VA PRIOR TO START OF WORK IN EACH AREA. THE VA WILL REMOVE ALL ITEMS OF SALVAGEABLE VALUE, INCLUDING BUT NOT LIMITED TO DOORS, HARDWARE, MOVEABLE EQUIPMENT NOT ALREADY DESIGNATED FOR REINSTALLATION/REUSE, PRIOR TO CONTRACTOR COMMENCING WORK.
8. WHERE EXISTING PARTITIONS HAVE BEEN REMOVED OR NEW SERVICES PENETRATE EXISTING SURFACES, THE OPENINGS SHALL BE PATCHED TO MATCH THE EXISTING ADJACENT SURFACES FINISH, TEXTURE AND
SHEEN.
9. IN GENERAL, WHEREVER SERVICES ARE REMOVED, THE OPENINGS SHALL BE PATCHED TO MATCH THE EXISTING ADJACENT SURFACES FINISH TEXTURE AND SHEEN. WHERE REMOVAL OF EXISTING CONSTRUCTION, PIPING, DUCTWORK AND OTHER ITEMS CREATES OPENINGS IN THE WALLS, FLOORS OR CEILINGS, PATCH OPENINGS IMMEDIATELY WITH THE SAME MATERIALS AS ADJACENT CONSTRUCTION. MAINTAIN THE REQUIRED FIRE RATING. SEE MEP DRAWINGS FOR ADDITIONAL INFORMATION. FILL IN ALL EXISTING OPENINGS THAT ARE NOT TO REMAIN, UNLESS OTHERWISE NOTED. FINISH TO MATCH FINISH OF ADJACENT SURFACE.
10. WHERE CODED NOTE DESIGNATIONS ARE SHOWN AS "TYP" OR "TYPICAL" IT IS INTENDED THAT THE NOTE
GENERALLY REFERS TO ALL SIMILAR ITEMS OR SURFACES.
11. A HAZARDOUS MATERIALS SURVEY WAS NOT CONDUCTED. IT IS THE CONTRACTORS RESPONSIBILITY TO TAKE PROTECTIVE MEASURES FOR ITS WORKERS PRIOR TO THE BEGINNING OF ANY RENOVATION OR
DEMOLITION WORK.
12. AFTER COMPLETION OF DEMOLITION, SCHEDULE A WALK-THROUGH WITH THE VA COR FOR REVIEW OF
EXISTING CONDITIONS.
13. PATCH AND FIRE STOP ALL ABANDONED PENETRATIONS THROUGH THE CONCRETE FLOORS, WALLS, AND
ROOF DECK.
GENERAL ICRA NOTES
NOTE:
CONTRACTOR MUST PROTECT DEMOLITION AND CONSTRUCTION ACTIVITIES IN ACCORDANCE
WITH THE FOLLOWING PROVISIONS:
TYPE OF CONSTRUCTION ACTIVITY: CLASS IV, TYPE D
DURING CONSTRUCTION OF PROJECT:
1. CONTRACTOR SHALL FOLLOW VA/ICRA REGULATIONS IN PERFORMING ALL WORK.
2. CONTRACTOR SHALL COORDINATE WITH THE VA FOR OFF-HOURS ACCESS TO THE FLOORS
ABOVE AND BELOW THE WORK NEEDED FOR MECHANICAL TIE-INS. TEMPORARY ICRA
BARRIERS ARE TO BE INSTALLED AROUND ALL WORK AREAS PRIOR TO CONSTRUCTION.
3. CONTRACTOR SHALL FOLLOW ALL FIRE SAFETY CODES DURING CONSTRUCTION.
4. CONTRACTOR SHALL PROVIDE THE VA TWO (2) WEEKS (14 CALENDAR DAYS) NOTICE PRIOR
TO ANY SYSTEM SHUTDOWN WORK VIA A SHUTDOWN FORM, (FORM TO BE PROVIDED BY
THE VA).
5. BEFORE COMMENCEMENT OF CONSTRUCTION, COORDINATE THE ICRA PROCEDURE WITH
THE FACILITY INFECTION CONTROL DEPARTMENT. CONTRACTOR MUST ACQUIRE AN ICRA
PERMIT FROM INFECTION CONTROL DEPARTMENT PRIOR TO THE START OF CRITICAL
BARRIER AND ICRA BARRIER CONSTRUCTION.
6. COORDINATE WITH THE VA COR FOR ANY PHASING PLAN REQUIREMENTS TO SCHEDULE
SHUTDOWNS, TEMPORARY RELOCATION OR CLOSED DOWN AREAS THAT MAY BE AFFECTED
DUE TO THE RENOVATION OF THE SCHEDULED PROJECT.
7. ALL CRITICAL BARRIER AND ICRA BARRIER WORK TO BE COMPLETED ON SECOND SHIFT
FROM 4:00 PM - 11:00 PM MONDAY - FRIDAY OR ON SATURDAYS AND SUNDAYS. (SEE
CRITICAL BARRIER DETAIL 1/GI102.)
8. REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEM, PRIOR TO ANY PHASE WORK COMMENCEMENT. HVAC
SYSTEM ISOLATION MATERIALS TO BE REMOVED IN THEIR ENTIRETY, PRIOR TO TURNING
THE SPACE OVER TO THE VA FACILITY AFTER EACH PHASE'S COMPLETION OF WORK.
9. COMPLETE ALL CRITICAL BARRIERS TO 1-HOUR FIRE-RATING I.E. GYP BOARD, PLYWOOD.
PLASTIC, TO SEAL AREA FROM NON-WORK AREA, BEFORE CONSTRUCTION BEGINS.
CRITICAL BARRIERS ARE THE EXTENSION OF EXISTING WALLS TO THE UNDERSIDE OF THE
DECK ABOVE AND ARE TO SEALED WITH FIRE CAULK AT THE DECK/ TOP OF WALL
INTERSECTION AND AROUND ALL GAPS FROM WALL PENETRATIONS OF EXISTING ITEMS
(PIPES CONDUIT, DUCTWORK, ETC.) THAT THE CRITICAL BARRIERS MUST BE BUILT AROUND.
10. WHEN CONSTRUCTING ICRA ANTE-ROOMS, REMOVE AND SECURELY STORE ALL
INTERFERING WALL APPURTENANCES, INCLUDING BUT NOT LIMITED TO HANDRAILS AND
ELECTRICAL DEVICES. ALL ITEMS TO BE SECURELY STORED FOR REINSTALLATION BY THE
CONTRACTOR.
11. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR
FILTRATION UNITS, CONTRACTORS SHALL MAINTAIN 0.001" NEGATIVE PRESSURE. PROVIDE
DIGITALLY RECORDING GAUGE MOUNTED ON THE OUTSIDE OF THE PERIMETER WALL OF
THE PROJECTS WORKSPACE.
12. SEAL ALL HOLES, PIPES, CONDUITS, AND PENETRATIONS IN THE WALLS ABOVE THE CEILING.
13. REPORT TOTAL WEIGHT OF CONSTRUCTION WASTE DISPOSED OF TO THE COR AND
CONTRACTING OFFICER ON THE LAST DAY OF EACH MONTH.
14. CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF SMOKE COMPARTMENTS WITHIN AREA OF
CONSTRUCTION DURING THE ENTIRE PROJECT.
15. COORDINATE A DISCHARGE PLAN FOR EACH PHASE WITH THE VA PRIOR TO COMMENCING
WORK ON THE NEXT PHASE.
16. WHERE THE HEPA FILTER UNIT DISCHARGE DUCT LEAVES THE ICRA CONTAINMENT AREA TO
BE DISCHARGED TO THE OUTSIDE. THE DUCT SHALL BE SHEET METAL WHEN CROSSING
THE ICRA BARRIER TO THE POINT OF DISCHARGE. FLEX DUCT IS PERMITTED INSIDE THE
ICRA BARRIER AND OTHER LOCATIONS AS APPROVED BY THE VA. CONNECTIONS TO THE
OUTSIDE DISCHARGE POINT (I.E. WINDOW) SHALL BE MADE WITH SHEET METAL AND SHALL
BE SECURE. CONNECTIONS SHALL NOT BE MADE WITH DUCT TAPE.
17. ANY MEP WORK OUTSIDE THE ICRA BARRIER MAY NOT REQUIRE FULL BARRIER WALL
PROTECTION. LESS STRINGENT MEASURES SUCH AS PLASTIC SHEETING SHALL BE
PERMITTED, AS APPROVED, BY VA COR FOR AREAS WITH SHORT TERM WORK. THE WORK
IN THESE AREAS IS EXPECTED TO BE COMPLETE OR DONE IN SECTIONS THAT COMPLETE
WORK AND RESTORE THE SPACE IN A ONE DAY WORK SHIFT.
18. CONTRACTOR SHALL COORDINATE FINAL ICRA WALLS WITH VA COR AND PROTECT EXISTING
WALL MOUNTED EQUIPMENT IDENTIFIED TO REMAIN.
19. RELOCATE EXISTING "EXIT" SIGNS TO LOCATIONS AS SHOWN ON ELECTRICAL DRAWING
E301 TO PROVIDE CLEAR PATH EGRESS DIRECTIONS DURING CONSTRUCTION.
20. PROTECT ALL EXISTING FINISHES THAT ARE TO REMAIN.
UPON COMPLETION OF EACH PHASE
1. DO NOT REMOVE ICRA/ ANTE ROOM BARRIERS FROM WORK AREA UNTIL THE PHASE WORK
IS INSPECTED AND APPROVED, IN WRITING, BY VA COR.
2. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS
ASSOCIATED WITH CONSTRUCTION. UTILIZE POLYURETHANE PLASTIC SHEETING DURING
INSTALLATION AND DEMOLITION OF ICRA BARRIERS TO CONTAIN DUST AND DEBRIS.
3. CONTRACTOR'S FINAL CLEANUP THROUGHOUT PHASE WORK AREA, SHALL UTILIZE HEPA
FILTERED VACUUMS. PHASE WORK AREA SHALL NOT BE TURNED OVER TO THE VA FOR USE
UNTIL IT IS THOROUGHLY CLEANED BY THE VA'S ENVIRONMENTAL SERVICES (EMS).
PROVIDE THE VA COR WITH (1) WEEK NOTIFICATION PRIOR TO THE EMS CLEANING, TO
ALLOW FOR SCHEDULING OF EMS.
INFECTIOUS CONTROL PROCEDURES (ICRA)
SEAL W/ FIRE CAULK, CONT.
EXISTING STRUCTURAL DECK
EXISTING WALL FRAMING
2 LAYERS 5/8" TYPE X GYP BOARD
2ND LAYER OF GYP BOARD TO
OVERLAP EXISTING FINISHED WALL
EXISTING SPACE NEW WORK SIDE
SEAL W/ FIRE CAULK, CONT.
NEW ACOUSTIC CEILING TILE
EXISTING FINISHED WALL
EXISTING ACOUSTIC
CEILING TILE
NOTE:
CRITICAL BARRIERS ARE THE EXTENSION OF EXISTING WALLS UP
TO THE EXISTING DECK ABOVE. THE PERIMETER WALLS OF EACH
PHASE MUST EXTEND UP TO THE EXISTING DECK, ABOVE. IF THEY
DO NOT, THE CONTRACTOR IS EXTENDED THE WALLS UP TO THE
EXISTING DECK.
A R C H I T E C T S E N G I N E E R S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
Philadelphia VA Medical Center 3900 Woodland Ave., Philadelphia, PA 19104
08/27/2020
642-17-100
DRKBJ
Renovate Inpatient Pharmacy for Chemotherapy I.V. Mixing
BID SETSYMBOLS, ABBREVIATIONS AND
NOTES
GI102
3/4" = 1'-0"
CRITICAL BARRIER - (TYP. ABOVE CEILING WALL INFILL
DETAIL)
OFFICE
2D135r
OFFICE
2D135t
HD STORAGE
2D135u
2D135s
STERILE HD
COMPOUNDING
2D135w STERILE
COMPOUNDING
2D135x
ANTE-ROOM
2D135v
ORDER ENTRY
2D135q
ANTE-ROOM
2D135n
IV CLEAN ROOM
2D135m
FILES
2D135j
2D135h
2D135r
2D135t
HD STORAGE
PASSAGE
2D135w
2D135x
2D135q
2D135n
FILES
VAULT
2D135h
TRAVEL DISTANCE TO EXIT
146'
SHADED AREAS
DEPICTS PROJECT
SCOPE
T R
A V
E L
D
IS
T A
N C
E T
O E
X
IT
2ND FLOOR KEY PLAN
AREAS OF WORK
FIRE RATING LEGEND
SYMBOL
(NUMBER SHOWS OPENING PARTITION OPENING RATING
CORRIDOR POSITIVE LATCH
(NON-
20 MIN.
20 MIN.
45 MIN.
60 MIN.
90 MIN.
3 HR.
3 HR.
ONE HOUR
ONE HOUR
ONE HOUR
ONE HOUR
TWO HOUR
THREE HOUR
FOUR HOUR
EXISTING EXISTING
NOTE: FOR SCHEDULED OPENINGS WHERE SMOKE AND FIRE SEPARATIONS
COINCIDE,THE MORE STRINGENT
FIRE RATING SHALL APPLY. REFER TO THE 'GX.XX' SERIES FOR FIRE RESISTIVE
REFERENCES.
SMOKE
20 20 20
20 20 20
45 45 45
45 45 45
60 60 60
60 60 60
90 90 90
90 90 90
20 20 20
20 20 20 45 45 45 90 90 90
GENERAL NOTES
A. REFER TO THE PROJECT MANUAL FOR FRAMED OPENING SCHEDULE
AND HARDWARE SCHEDULE.
B. PARTITIONS SHALL BE TYPE D13A UNLESS NOTED OTHERWISE
C. REFER TO SHEET A604 FOR PARTITION TYPES.
D. PARTITIONS ARE DIMENSIONED TO FINISH FACE OF GYPSUM
BOARD UNLESS NOTED OTHERWISE.
E. REFER TO SHEET AE-04 FOR TYPICAL INTERIOR PARTITION
DETAILS.
LIFE SAFETY CODE ANALYSIS
NFPA 101 LIFE SAFETY CODE 2018 INPATIENT PHARMACY
TOTAL PROJECT AREA 1,200 SF
TOTAL FLOOR AREA GROSS FLOOR AREA (100% ALL SPACES): 17,110 SF
OCCUPANCY COUNT HEALTH CARE USE, SLEEPING DEPARTMENTS:
17,110 SF / 120 SF PER
OCCUPANT LOAD = 143 OCCUPANTS
EGRESS CAPACITY PROVIDED STAIR DOORS: 42" DOOR 42/.3 = 140 OCCUPANTS MAX.
TOTAL EGRESS CAPACITY 5 STAIRWELLS * (140) 700
CORRIDOR MINIMUM 72" ALLOWED BY VA STANDARDS 96" EXISTING EXIT
CORRIDORS
7.1.10 MEANS OF EGRESS RELIABILITY
7.1.10.1 MEANS OF EGRESS SHALL BE CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTIONS OR
IMPEDIMENTS TO FULL INSTANT USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
9.2.1 AIR CONDITIONING, HEATING, VENTILATION DUCTWORK, AND RELATED EQUIPMENT. AIR CONDITIONING, HEATING, VENTILATION DUCTWORK, AND RELATED EQUIPMENT SHALL BE IN ACCORDANCE WITH
NFPA 90A.
18.1.1.1.1 ALTERATION OF EXISTING HEALTH CARE OCCUPANCIES
18.1.1.4.3 REHABILITATION
18.1.1.4.3 (2) MINOR RENOVATION: RENOVATION IS LESS THAN 50% AND NOT MORE THAN 4500 SF OF
THE AREA OF A SMOKE COMPARTMENT
18.2.2.2 DOORS
18.2.2.2.4 DOORS WITHIN A REQUIRED MEANS OF EGRESS SHALL NOT BE EQUIPPED WITH A LATCH OR LOCK
THAT REQUIRES THE USE OF A TOOL OR KEY FROM THE EGRESS SIDE, UNLESS OTHERWISE PERMITTED BY ONE OF
THE FOLLOWING:
EXCEPTION NO. 1: KEY-LOCKING DEVICES THAT RESTRICT ACCESS TO THE ROOM FROM THE CORRIDOR AND THAT ARE OPERABLE ONLY BY STAFF FROM THE CORRIDOR SIDE SHALL BE PERMITTED. SUCH DEVICES
SHALL NOT RESTRICT EGRESS FROM THE ROOM.
18.2.3.1 THE CAPACITY OF MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH SECTION 7.3
7.3 / TABLE 7.3.3.1 THE CAPACITY OF MEANS OF EGRESS PROVIDING TRAVEL BY MEANS OF STAIRS SHALL BE
0.3 IN. PER PERSON, AND THE CAPACITY OF MEANS OF EGRESS PROVIDING HORIZONTAL TRAVEL (WITHOUT STAIRS) BY MEANS SUCH AS DOORS, RAMPS, OR HORIZONTAL EXITS SHALL BE 0.2 IN. PER PERSON.
18.2.3.4 AISLES, CORRIDORS, AND RAMPS REQUIRED FOR EXIT ACCESS IN A HOSPITAL OR NURSING HOME SHALL
BE NOT LESS THAN 8 FT IN CLEAR AND UNOBSTRUCTED WIDTH.
18.2.5 ARRANGEMENT OF MEANS OF EGRESS
18.2.5.2 DEAD-END CORRIDORS. DEAD-END CORRIDORS SHALL NOT EXCEED 30 FT
18.2.5.6.1 EVERY HABITABLE ROOM SHALL HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO AN EXIT
ACCESS CORRIDOR
18.2.6 TRAVEL DISTANCE TO EXITS
18.2.6.2.1 THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 200 FT.
18.3 PROTECTION.
18.3.4.1 GENERAL. HEALTH CARE OCCUPANCIES SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM IN
ACCORDANCE WITH SECTION 9.6.
18.3.4.3.1 OCCUPANT NOTIFICATION. OCCUPANT NOTIFICATION SHALL BE ACCOMPLISHED AUTOMATICALLY IN
ACCORDANCE WITH 9.6.3.
18.3.4.5 DETECTION
18.3.4.5.1 GENERAL. DETECTION SYSTEMS, WHERE REQUIRED, SHALL BE IN ACCORDANCE WITH SECTION 9.6.
18.3.5.1 BUILDINGS CONTAINING HEALTH CARE FACILITIES SHALL BE PROTECTED THROUGHOUT BY AN
APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7.
18.3.5.6 PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED IN ALL HEALTH CARE OCCUPANCIES IN
ACCORDANCE WITH 9.7.4.1.
18.3.6 CORRIDORS
18.3.6.1 CORRIDORS SHALL BE SEPARATED FROM ALL OTHER AREAS BY PARTITIONS.
18.3.6.2 CONSTRUCTION OF CORRIDOR WALLS SHALL FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE.
SUCH WALLS SHALL BE PERMITTED TO TERMINATE AT THE CEILING WHERE THE CEILING IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE. NO FIRE RESISTANCE RATING REQUIRED FOR CORRIDOR WALLS..
18.3.6.3 CORRIDOR DOORS
18.3.6.3.1 CONSTRUCTED TO RESIST THE PASSAGE OF SMOKE.
18.3.6.3.2 PROVIDED WITH POSITIVE LATCHING.
18.3.6.3.11 DOOR-CLOSING DEVICES SHALL NOT BE REQUIRED ON DOORS IN CORRIDOR WALL OPENINGS OTHER THAN THOSE SERVING REQUIRED EXITS, SMOKE BARRIERS, OR ENCLOSURES OF VERTICAL OPENINGS
AND HAZARDOUS AREAS
18.3.7.1 (4) TO LIMIT THE TRAVEL DISTANCE FROM ANY POINT TO REACH A DOOR IN THE REQUIRED SMOKE
BARRIER TO A DISTANCE NOT EXCEEDING 200 FEET.
A R C H I T E C T S E N G I N E E R S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
Philadelphia VA Medical Center 3900 Woodland Ave., Philadelphia, PA 19104
08/27/2020
642-17-100
DRKBJ
Renovate Inpatient Pharmacy for Chemotherapy I.V. Mixing
BID SETLIFE SAFETY PLAN
GI103
1/8" = 1'-0"
LIFE SAFETY PLAN
DOOR TYPES
SCALE: 1/4" = 1'-0"
TEMPERED
GLASS
FLUSH, WOOD PRE-HUNG; AUTOMATIC SINGLE
SWING, 36"Wx81"H, 304 STAINLESS
STEEL FRAME, FULL VIEW (BASED ON
TERRA UNIVERSAL 1998-87-L OR R)
FLUSH, HOLLOW
METAL, 1HR RATED
TYPICAL INTERIOR DOOR FRAMES
SCALE: NTS
1 15/16" VARIES VARIES
STANDARD DOOR FRAMEFRAMES IN METAL STUD PARTITIONS
(DOOR SIDE)
/8
1/2" 1/2"
GAGE AS
SPECIFIED
ADD RETURN ON
FRAME WHERE
DRYWALL FINISH IS
REQUIRED
STANDARD FRAME
FOR DRYWALL
CAULK ALL AROUND
BOTH SIDES
WIDTH
METAL STUD
DRYWALL, THICKNESS
SINGLE OR DOUBLE AS
REQUIRED
DOUBLE STUDS BACK
TO BACK
JAMB ANCHORS
J1 H1
THROAT OPENING = PARTITION WIDTH + 1/8" MIN
VERTICAL STUDS @ 1'-4" MAX W/ GYPSUM
WALLBOARD. 1'-4" W/ GYPSUM LATH &
PLASTER DOUBLE STUDS FOR
SUPPORTING CONCRETE BACKER BOARD.
PROVIDE CONTINUOUS BRACING
WHEN STUDS EXCEED 10'-0" & ARE
FINISHED BOTH SIDES.
DETAIL D: JAMB ANCHOR CLIPS (3) PER
SIDE - COORDINATE W/ HINGE
REINFORCEMENT.
NOTE 1: OMIT BRACE WHEN "D" DIMENSION
IS LESS THAN 2'-0" FOR GYPSUM WALLBOARD
OR 16" FOR PLASTER PARTITION.
SEC. B 1/2"
CONSTRUCTION
JOINT
SEE
NOTE 1
RUNNER
BETWEEN
STUDS
HM DOOR
FRAME
DETAIL C
E Q
U A
L E
Q U
A L
E Q
U A
L E
Q U
A L
D
V A
R
IE
S
/2
CRIPPLE STUD, DO
NOT ANCHOR TO
BEARING STUD
GYPSUM
WALLBOARD
PANELS
CONTROL JOINT
1/2" MIN
PROVIDE SOUND
DEADENING WHERE
REQUIRED
ISOMETRIC OF CONSTRUCTION JOINT SECTION B
SECTION CSECTION A
JAMB ANCHORS
(FURNISHED WITH FRAME)
DETAIL D
DOUBLE STUDS
HM FRAME
INTERIOR
PARTITION, SEE
FLOOR PLAN
JAMB
ANCHOR
/4
M
IN
1/2"M
IN
5/8" M
AX
STUD OF INTERIOR
PARTITION, SEE FLOOR
PLAN
TOP TRACK
SANITARY STOP
HM DOOR
FRAME
SHIM AS
REQUIRED
METAL ANCHOR
CLIP
FR
AME FA
CE
MIN
US 3/16"
FR
AME FA
CE
MIN
US 3/16"
/4
M
IN
JAMB DEPTH
STUDWIDTH
STUDWIDTH
/4
M
IN
SEE DOOR SCHEDULE
VARIES
PARTITION FRAMING FOR DOORS
SCALE: NTS
FRONT APPROACH, PULL SIDE HINGE APPROACH, PULL SIDE HINGE APPROACH, PULL SIDE LATCH APPROACH, PULL SIDE
FRONT APPROACH, PUSH SIDE HINGE APPROACH, PUSH SIDE LATCH APPROACH, PUSH SIDE
ADA MANEUVERING CLEARANCES AT MANUAL SWINGING DOORS
1'-6" MIN
'-0
M
IN
'-0
M
IN
3'-0" MIN 3'-6" MIN
'-4
M
IN
2'-0" MIN
'-0
M
IN
1'-0" MIN*
'-0
M
IN
1'-0" MIN*
2'-0" MIN*
'-6
M
IN
'-6
M
IN
*4'-4" MIN IF CLOSER IS PROVIDED
*IF BOTH CLOSER AND LATCH ARE
PROVIDED
*IF BOTH CLOSER AND LATCH ARE PROVIDED
** 4'-0" MIN IF BOTH CLOSER AND LATCH ARE
PROVIDED
*4'-4" MIN IF CLOSER IS PROVIDED
FRAME TYPES
SCALE: 1/4" = 1'-0"
HOLLOW METAL
2"
DOOR WIDTH
2"
D O
O R
H E
IG
H
T
STAINLESS STEEL FRAME,
PRE-HUNG DOOR AND
FRAME SYSTEM
D O
O R
H E
IG
H
T
2"
DOOR WIDTH
2"
ROOM
135q
WIDTH HEIGHT
DOOR SCHEDULE
DOOR NOTES:
1. ALL DOORS SHALL BE FLUSH - 1 3/4" (44mm) THICK
UNLESS NOTED OTHERWISE.
2. TOP & SIDE RAILS SHALL BE 9" (229mm) MIN. UNO.
BOTTOM RAILS SHALL BE 12" (305mm) MIN. UNO.
PAIR MATERIAL FINISH TYPE
DOOR SIGN
TYPE MATERIAL FINISH TYPE
FRAME FIRE
RATING
HDW
SET
REMARKS
DOOR
NO.
ORDER ENTRY 2D135q, FILES 2D135j - 3'-0" 7'-0" HM PTD 3 A HM PTD 1 - 1 TEMPORARY DOOR - PHASE 2A
135p PASSAGE 2D135s - 3'-0" 7'-0" HM PTD 3 A HM PTD 1 - 1
135t OFFICE 2D135t - 3'-0" 7'-0" HM PTD 3 A HM PTD 1 - 1 -
135u HD STORAGE 2D135u - 3'-0" 6'-8" SS - 2 A SS - 2 - 1 PROVIDE TEMPERED GLASS
135v ANTE-ROOM 2D135v - 3'-0" SS - A - - 2
135w STERILE HD COMPOUNDING 2D135w - 3'-0" SS - A - - 2A
135x STERILE COMPOUNDING 2D135x - 3'-0" SS - A - - 2A
6'-8"
6'-8"
6'-8"
SS
SS
SS
PROVIDE TEMPERED GLASS
PROVIDE TEMPERED GLASS
PROVIDE TEMPERED GLASS
TEMPORARY DOOR - PHASE 3A
EX01 FILES 2D135p PAIR 6'-0" 6'-8"
EX02 FILES 2D135j PAIR 6'-0" 6'-8" TEMPORARY CONTRACTOR ACCESS
TEMPORARY CONTRACTOR ACCESS10A
10A
HM
HM
MULTI-LAYERED FIRE RETARDANT
THERMOPLASTIC SHEET WITH
SPECTRIM #13 MAPLE FINISH
(MAGNETICALLY REMOVABLE)
1/8" ANODIZED ALUMINUM DIVIDER BAR
MAGNETICALLY REMOVABLE F-UNIT
1" TEXT, ALL CAPS
AERIAL REGULAR
PHOTOPOLYMER / BRAILLE
3 PLY NON-GLARE ACRYLIC CONSTRUCTION
SUBSURFACE UV VARIABLE DOT DIGITALLY
PRINTED BACKGROUND COLOR WHITE
5 3/16 x 9" CLEAR ACETATE - 1/16" THICK
CLEAR ACRYLIC BACKER WITH FUTURA MED TEXT
SATIN ANODIZED ALUMINUM FRAME
2D-135t
OFFICE
DIMENSION OF INSERT
9"
INSIDE DIMENSION OF FRAME
9 1/8"
F -U
N
IT
6"
IN
S
E R
T
3"
F R
A M
E
1/
8"
F R
A M
E
1/
8"
SIGN SYSTEM MECHANICALLY ATTACHES TO WALL
AND FEATURES INTERCHANGEABLE COMPONENTS
TOP OF SIGN TO BE
MOUNTED AT +5'-0" AFFTYPE A - SLIDER
9"
5'
1. ALL SIGNS SHALL BE ADA/ABA COMPLIANT
2. MOUNT SIGNS WITH TOP OF SIGN AT +5'-0" ABOVE FINISHED FLOOR, UNLESS OTHERWISE
NOTED. SEE DETAIL 2 ON THIS SHEET.
4. SIGN TYPE REQUIREMENTS ARE SHOWN ON DOOR SCHEDULE - SEE GI104.
5. VERIFY ALL FINAL TEXT AND ROOM NUMBERS WITH COR PRIOR TO FABRICATION.
6. ALL SIGNAGE TO MATCH EXISTING FACILITY SIGNAGE. BASIS OF DESIGN FOR SIGNS IS CREATIVE
SIGNAGE. CONTACT PAUL MOSKIOS, 301-345-3700.
SIGNAGE NOTES
A R C H I T E C T S E N G I N E E R S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
Philadelphia VA Medical Center 3900 Woodland Ave., Philadelphia, PA 19104
08/27/2020
642-17-100
DRKBJ
Renovate Inpatient Pharmacy for Chemotherapy I.V. Mixing
BID SETDOOR SCHEDULE AND DETAILS
GI104
3" = 1'-0"
SIGN TYPE A
1/2" = 1'-0"
DOOR SIGN MOUNTING HEIGHT
2ND FLOOR KEY PLAN
AREAS OF WORK
2A01
2A02
2A03
2A04
REMOVABLE
GUARDRAIL
SECTION
TC
SCAFFOLD SECTION WITH STAIR
7' - 0"7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0"
REMOVABLE
GUARDRAIL
SECTION
EXIST. CONC.
CURB BELOW
OFFICE
2D135r
FILES
2D135p
ORDER ENTRY
2D135q
ANTE-ROOM
2D135n
IV CLEAN ROOM
2D135m
OFFICE
2D135k
VAULT
2D135h
COMPOUNDING
ROOM
2D135j
THIS DOOR IS FOR
ISOLATING CONSTRUCTION
AREA AND EMERGENCY
USE ONLY. IT IS NOT FOR
DAILY USE.135q
EX02
2B05
2B05
2B05
2B03
2B03
2B02
2B01
2B04
2B04
2B04
OFFICE
2D135r
FILES
2D135p
ORDER ENTRY
2D135q
ANTE-ROOM
2D135n
IV CLEAN ROOM
2D135m
OFFICE
2D135k
VAULT
2D135h
COMPOUNDING
ROOM
2D135j
135q
EX02
GENERAL DEMOLITION NOTES (ALL PHASES)
1. SCOPE OF DEMOLITION WORK IS NOT LIMITED TO WORK SHOWN ON
DEMOLITION DRAWINGS. CONTRACTOR TO COORDINATE DEMOLITION WITH NEW
WORK AND PATCH EXISTING TO RECEIVE NEW FINISHES.
2. REFER TO MECHANICAL, ELECTRICAL & PLUMBING DRAWINGS FOR
DEMOLITION WORK. WHERE SUCH WORK OCCURS, ARCHITECTURAL ITEMS OR
FINISHES SHALL BE REMOVED ONLY TO THE EXTENT REQUIRED & PATCHED TO
MATCH EXISTING ADJACENT CONSTRUCTION AND FINISHES.
3. REMOVE ALL INTERIOR DOORS, FRAMES AND HARDWARE INDICATED AS
DASHED LINES.
4. REMOVE EXISTING CEILING IN ALL AREAS TO RECEIVE A NEW CEILING.
5. REMOVE EXISTING FLOOR FINISH, BASE AND ADHESIVE IN ALL AREAS WHICH ARE
TO RECEIVE NEW FLOOR FINISHES. SEE FINISHES PLAN, DRAWING AE104.
6. PROTECT EXISTING FINISHED WORK & EQUIPMENT WHICH IS TO REMAIN IN
AREAS OF DEMOLITION WORK.
7. REMOVE PARTITIONS SHOWN DASHED.
8. SEE DOOR SCHEDULE ON SHEET GI104 FOR DOOR SIZES.
9. VERIFY EXISTING FIRE PROTECTION ON ALL STRUCTURAL ELEMENTS IN AREA OF
WORK PRIOR TO INSTALLING NEW WORK. PATCH AND REPAIR AS NECESSARY TO
MAINTAIN REQUIRED RATING.
10. REFER TO SHEET GI104 FOR TEMPORARY CONSTRUCTION BARRIER DOORS.
11. AFTER THE REMOVAL OF ICRA WALLS, CLEAN AND PATCH ALL EXISTING SURFACES
EFFECTED BY CONSTRUCTION AND MATCH EXISTING FINISHES.
12. INSTALL A TEMPORARY ILLUMINATED EXIT SIGN AT THE EXIT DOORS EX01 AND
EX02 DURING THE WHOLE TIME THEY ARE IN USE.
PHASE 2B: KEY NOTES
2B01 REMOVE EXISTING DOOR, HM FRAME, AND HARDWARE.
2B02 REMOVE EXISTING PLUMBING FIXTURE. SEE PLUMBING DRAWINGS.
2B03 REMOVE EXISTING BASE CABINETS, WALL CABINETS AND
COUNTERTOP. PATCH WALLS AS REQUIRED FOR NEW FINISHES.
2B04 REMOVE EXISTING FLOOR FINISH, WALL BASE AND ADHESIVES. PREP
FLOOR AND WALLS FOR NEW FINISHES.
2B05 REMOVE EXISTING INTERIOR PARTITION SHOWN DASHED IN ITS
ENTIRETY. PATCH AND PREP FLOOR AND WALLS FOR NEW FINISHES.
DEMOLITION SYMBOL LEGEND
REMOVE EXISTING PARTITION SHOWN DASHED IN ITS
ENTIRETY.
REMOVE EXISTING DOOR AND HARDWARE. FRAME TO
REMAIN.
REMOVE EXISTING BASE CABINET, COUNTERTOP AND
WALL CABINETS SHOWN DASHED IN THEIR ENTIRETY.
VERIFY EXISTING CONDITIONS.
DETAIL A DETAIL B
A
TYPICAL FLOOR PENETRATION DETAIL
SCALE: 1" = 1'-0"
TEMPORARY HEPA
EXHAUST FAN
VENTILATION DUCT
SEAL AS REQUIRED
EXISTING FLOOR SLAB
CORE DRILL EXISTING
FLOOR SLAB AS REQUIRED
FOR TEMPORARY HEPA
EXHAUST DUCT
INFILL FLOOR PENETRATION
FLUSH WITH CONCRETE TO
MATCH EXISTING
EXISTING FLOOR SLAB
CONSTRUCTION
PATCH UNDERSIDE OF TEMPORARY
PENETRATION WITH METAL DECK
TO MATCH EXISTING, ATTACH AS
REQUIRED.
INFECTION CONTROL RISK
ASSESSMENT (ICRA) POLICY
PRECAUTIONS DURING CONSTRUCTION (ALL PHASES)
1. UTILIZE 6-MIL FIRE-RATED POLY PLASTIC SHEET WITH EXPANDABLE POLES TO
ISOLATE AREA DURING CONSTRUCTION OF ICRA PARTITION WITH SECURITY
DOOR. SEE NOTE 2A01
2. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM
CONSTRUCTION OPERATIONS.
3. ANY CEILING TILES DISPLACED FOR VISUAL INSPECTION MUST BE REMOVED
CAREFULLY AND IMMEDIATELY REPLACED. INSTALL NEW CEILING TILE IN ITS
PLACE IF IT IS DAMAGED IN THE PROCESS.
4. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING
INTO ATMOSPHERE.
5. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING DRY WALL
FOR BARRIERS.
6. BLOCK OFF AND SEAL AIR VENTS IN THE CONSTRUCTION AREA.
7. REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE
TO PREVENT CONTAMINATION OF DUCT SYSTEM.
8. REMOVE CONSTRUCTION WASTE DAILY.
9. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA
FILTER EQUIPPED AIR FILTRATION UNITS. COORDINATE LOCATION OF ABOVE
FLOOR PENETRATION WITH THE VA COR. PATCH FLOOR PENETRATION AFTER
CONSTRUCTION AS REQUIRED TO MATCH EXISTING.
10. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES AIRTIGHT AND/OR FIRE SEAL
AS REQUIRED.
11. COORDINATE ALL INFECTION CONTROL RISK ASSESSMENT (ICRA)
REQUIREMENTS WITH THE VA INFECTION CONTROL OFFICER AND VA COR.
PHASE 2A: KEY NOTES
2A01 ICRA PARTITION WITH SECURITY DOOR SYSTEM. ALL CONTRACTOR CONSTRUCTION SITE
ACCESS WILL BE THROUGH THE TEMPORARY HM DOOR. SEE NOTE 2A03
WALL CONSTRUCTION: ONE (1) HOUR FIRE RATED SYSTEM
3 5/8" METAL STUDS.
5/8" GWB BOTH SIDES.
EXTEND PARTITION FROM FLOOR TO UNDERSIDE OF DECK ABOVE.
PROVIDE AND INSTALL PERIMETER FIRE CAULK.
DOOR SYSTEM: ONE (1) HOUR RATED HM DOOR AND HM FRAME.
3'-0" WIDE X 7'-0" DOOR.
PANIC BAR WITH ALARM.
2A02 TEMPORARY STAIR AND PLATFORM ACCESS SYSTEM.
STAIR: TEMPORARY STEEL SCAFFOLD SECTION WITH STAIRS TO MEET OSHA
STANDARDS.
WALKWAY: TEMPORARY WALKWAY WITH GUARDRAILS. PROVIDE TEMPORARY
STRUCTURAL SYSTEM TO MEET OSHA STANDARDS.
REMOVABLE GUARDRAIL: PROVIDE A REMOVABLE GUARDRAIL FOR ACCESS THROUGH 2ND
FLOOR WINDOWS.
2A03 REMOVE EXISTING WINDOW. INSTALL A TEMPORARY HM DOOR FRAME, WEATHER SEALED HM
DOUBLE DOOR AND ENTRANCE LOCK SET. EXTERIOR WALL TO BE WEATHER TIGHT.
2A04 HEPA FILTERED EXHAUST FAN SYSTEM. SEE DETAIL A/AE101. COORDINATE WITH VA COR.
NO ARCHITECTURAL WORK
UNLESS NOTED OTHERWISE
AREA OF ARCHITECTURAL WORK
UNLESS NOTED OTHERWISE
AREA OF WORK LEGEND
A R C H I T E C T S E N G I N E E R S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
Philadelphia VA Medical Center 3900 Woodland Ave., Philadelphia, PA 19104
08/27/2020
642-17-100
DRKBJ
Renovate Inpatient Pharmacy for Chemotherapy I.V. Mixing
BID SETPHASING PLAN - PHASES 2A & 2B
AE101
1/4" = 1'-0"
PHASE 2A - ICRA CONSTRUCTION 1/4" = 1'-0"
PHASE 2B - DEMOLITION
2C01
2C02
2C02
OFFICE
2D135r
FILES
2D135p
ORDER ENTRY
2D135q
ANTE-ROOM
2D135n
IV CLEAN ROOM
2D135m
FILES
2D135j
VAULT
2D135h
EX01 EX02
135q
3A04
3A013A03
TC
OFFICE
2D135r
ORDER ENTRY
2D135q
ANTE-ROOM
2D135n
IV CLEAN ROOM
2D135m
FILES
2D135j
VAULT
2D135h
FILES
2D135p
3A05
3A02
AE105
135p
EX01 EX02
135q
3A06
2ND FLOOR KEY PLAN
AREAS OF WORK
PHASE 2C: KEY NOTES
2C01 ICRA PARTITION WITH SECURITY DOOR SYSTEM. ALL CONTRACTOR CONSTRUCTION SITE
ACCESS WILL BE THROUGH THIS TEMPORARY HM DOOR.
DOOR SYSTEM: ONE (1) HOUR RATED HM DOOR AND HM FRAME.
DOOR SIZED TO FIT EXISTING EXTERIOR OPENING.
PROVIDE PANIC BAR WITH ALARM.
2C02 RELOCATE EXISTING FILE SYSTEM, SHOWN DASHED, TO FILES 2D135J. MODIFY TRACK AS
REQUIRED. INSTALL NEW FIRE RETARDANT TREATED 3/4" PLYWOOD ON THE FLOOR BELOW THE
FILES. SEE DETAIL H/AE107.
PHASE 3A: KEY NOTES
3A01 REMOVE ICRA BARRIER AND DOOR AND FRAME. PORTION OF ICRA PARTITION TO REMAIN TO
CREATE A SOFFIT AT 7'-0". PATCH FLOOR AND WALL AND PREP FOR FINISHES.
3A02 REMOVE TEMPORARY DOOR AND FRAME. RE-INSTALL EXISTING WINDOW TO MATCH EXISTING.
SEAL PERIMETER OF WINDOW.
3A03 ICRA PARTITION WITH SECURITY DOOR SYSTEM. ALL CONTRACTOR CONSTRUCTION SITE ACCESS
WILL BE THROUGH THE TEMPORARY HM DOOR EX01. REMOVE EXISTING LIGHT FIXTURE.
REPLACE LIGHT FIXTURE AFTER ICRA PARTITION IS REMOVED.
WALL CONSTRUCTION: ONE (1) HOUR FIRE RATED SYSTEM
3 5/8" METAL STUDS.
5/8" GWB BOTH SIDES.
EXTEND PARTITION FROM FLOOR TO UNDERSIDE OF DECK ABOVE.
FIRE CAULK.
DOOR SYSTEM: ONE (1) HOUR RATED HM DOOR AND HM FRAME.
3'-0" WIDE X 7'-0" DOOR.
PANIC BAR WITH ALARM TIED TO SECURITY OFFICE.
3A04 HEPA FILTERED EXHAUST FAN SYSTEM. SEE DETAIL A/GC101. COORDINATE WITH VA COR.
3A05 REMOVE EXISTING INTERIOR PARTITION SHOWN AS DASHED IN ITS ENTIRETY.
3A06 SECURE THIS EXISTING DOOR TO RESTRICT ACCESS DURING CONSTRUCTION.
NO ARCHITECTURAL WORK
UNLESS NOTED OTHERWISE
AREA OF ARCHITECTURAL WORK
UNLESS NOTED OTHERWISE
AREA OF WORK LEGEND
A R C H I T E C T S E N G I N E E R S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
Philadelphia VA Medical Center 3900 Woodland Ave., Philadelphia, PA 19104
08/27/2020
642-17-100
DRKBJ
Renovate Inpatient Pharmacy for Chemotherapy I.V. Mixing
BID SETPHASING PLAN - PHASES 2C & 3A
AE102
1/4" = 1'-0"
PHASE 2C - SHELVING RELOCATION
1/4" = 1'-0"
PHASE 3A - ICRA CONSTRUCTION / ICRA
REMOVAL/DEMOLITION
3C05 3C04
3C03
OFFICE
2D135r
OFFICE
2D135t
HD STORAGE
2D135u
PASSAGE
2D135s
STERILE HD
COMPOUNDING
2D135w
STERILE
COMPOUNDING
2D135x
ANTE-ROOM
2D135v
ORDER ENTRY
2D135q
ANTE-ROOM
2D135n
IV CLEAN ROOM
2D135m
FILES
2D135j
VAULT
2D135h
OFFICE
2D135r
OFFICE
2D135t
HD STORAGE
2D135u
PASSAGE
2D135s
STERILE HD
COMPOUNDING
2D135w
STERILE
COMPOUNDING
2D135x
ANTE-ROOM
2D135v
ORDER ENTRY
2D135q
ANTE-ROOM
2D135n
IV CLEAN ROOM
2D135m
FILES
2D135j
VAULT
2D135h
3C02
3C01
B
SIM
135x
135w
135u
135t
135v
2ND FLOOR KEY PLAN
AREAS OF WORK
PHASE 3B: KEY NOTES
3B01 INSTALL WINDOW BLACKOUT FILM AND GWB PARTITION TO
CLOSE OFF WINDOW VIEW. ALIGN FINISHES WITH EXISTING
WALL SURFACES.
3B02 ALIGN PARTITION WITH EXISTING WALL.
3B03 PASS-THRU. SEE EQUIPMENT PLAN ON DRAWING AE104
3B04 SCRUB SINK WITH EYEWASH. SEE EQUIPMENT PLAN ON
DRAWING AE104.
3B05 REMOVE HEPA FILTERED EXHAUST FAN SYSTEM. COORDINATE
WITH VA COR.
3B06 NOT USED
3B07 DEMARCATION LINE TO DELINEATE BETWEEN "CLEAN" AND
"DIRTY" AREAS.
3B08 REMOVE DOOR USAGE RESTRICTION TO ALLOW OFFICE 2D135r
USE AFTER WALL IS FINISHED AND PAINTED.
NOTE: NEW INTERIOR PARTITIONS NOT LABELED
IN FLOOR PLAN SHALL BE PARTITION TYPE A
PHASE 3C: KEY NOTES
3C01 REMOVE HEPA FILTERED EXHAUST FAN SYSTEM
3C02 INSTALL PARTITION WALL. UTILIZE TEMPORARY FIRE-RATED PLASTIC
BARRIER DURING CONSTRUCTION
3C03 REMOVE ICRA BARRIER AND DOOR AND FRAME. PATCH CEILING AS
REQUIRED. PATCH FLOOR AND WALL AND PREP FOR FINISHES.
3C04 REMOVE TEMPORARY DOOR AND FRAME. RE-INSTALL EXISTING WINDOW
TO MATCH EXISTING. INSTALL BLACKOUT FILM ON INSIDE OF WINDOW.
SEAL PERIMETER OF WINDOW.
3C05 REMOVE TEMPORARY STAIR AND ACCESS PLATFORM. PATCH AND REPAIR
EXISTING EXTERIOR WALL AND SIDEWALKS TO MATCH EXISTING.
NO ARCHITECTURAL WORK
UNLESS NOTED OTHERWISE
AREA OF ARCHITECTURAL WORK
UNLESS NOTED OTHERWISE
AREA OF WORK LEGEND
NEW WORK SYMBOL LEGEND
EXISTING PARTITION. PATCH WALL ON SITE OF
CONSTRUCTION AS REQUIRED FOR NEW FINISHES.
NEW DOOR AND HARDWARE. SEE DOOR SCHEDULE.
NEW INTERIOR PARTITION. SEE PARTITION SCHEDULE. INTERIOR
PARTITIONS NOT KEYED TO BE INTERIOR PARTITION A
X
3B02
3B02
3B04
3B04
/4
3B05
B
SIM
B
A
B
B
B
B
OFFICE
2D135r
OFFICE
2D135t
HD STORAGE
2D135u
PASSAGE
2D135s
STERILE HD
COMPOUNDING
2D135w
STERILE
COMPOUNDING
2D135x
ANTE-ROOM
2D135v
ORDER ENTRY
2D135q
ANTE-ROOM
2D135n
IV CLEAN ROOM
2D135m
FILES
2D135j
VAULT
2D135h
A
4' - 1 1/2" 4' - 2 1/2" 3' - 8"
/4
11' - 0 5/8"
/8
'-6
M
A X
/8
/2
A
A
C
B B
1' - 3 5/8" 4' - 0"
A
A
A
6' - 4 1/4" 3 5/8" 5' - 9"
B
B
A
A
A
A
A.1
3B03
BENCH
D E
M A
R C
A T
IO
N3B03
1' - 4"
1' - 3"
E
AE107
3B01
3B07
135p
135u
135v
135t
135w
135x
B
3B08
A R C H I T E C T S E N G I N E E R S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
Philadelphia VA Medical Center 3900 Woodland Ave., Philadelphia, PA 19104
08/27/2020
642-17-100
DRKBJ
Renovate Inpatient Pharmacy for Chemotherapy I.V. Mixing
BID SETPHASES 3B & 3C
AE103
1/4" = 1'-0"
PHASE 3C - ICRA REMOVAL1/4" = 1'-0"
PHASE 3B - FLOOR PLAN
M
S H
E
LV
IN
G
UPE01,
BENCH
30" WIDE
P3000, SCRUB SINK
WITH EYEWASH
U1200, PASS-
THRU
R6060, LAB REF
M1801, COMPUTER
STATION
U3501, HOOD TYPE
A2 (SG304)
L2280, LAMINAR
FLOW HOOD
(EG6252)
U3500, HOOD
TYPE B2
(BCG601)
M
S H
E
LV
IN
G
M1801, COMPUTER
STATION
U1200, PASS-
THRU
R6060, LAB REF
M2080, SHELVING
M1801, COMPUTER
STATION
P3000, SCRUB
SINK WITH
EYEWASH
A
5, H
O O
K S
3)
M
S H
E
LV
IN
G
WORK COUNTER W/
STORAGE ABOVE
REF. BELOW
OMNICELL ABOVE
M2080, SHELVING
OFFICE
2D135t
HD STORAGE
2D135u
PASSAGE
2D135s
STERILE HD
COMPOUNDING
2D135w STERILE
COMPOUNDING
2D135x
ANTE-ROOM
2D135v
M2080, SHELVINGREFRIGERATOR
PASS-THRU
SHARPS, CONTAINER
COMPUTER, WALL MOUNTED
HOOD, LAMINAR FLOW
HOOD, BIOLOGICAL SAFETY CABINET TYPE B2
R6060
U1200
U3501
M1801
L2280
U3500
BENCH, STAINLESS STEEL WALL MOUNTEDUPE01
HOOK, GARMENT, DOUBLE, SS, SURFACE MOUNTEDA5145
HOOD, BIOLOGICAL SAFETY CABINET TYPE A2 U3501
GC
GC
VA
GC
GC
VA
GC
GC
GC
GC
VA
GC
VA
GC
GC
GC
GC
GC
GC
GC
GC
GC
GC
GC
GC
GC
GC
BAKER
BAKER
BAKER SG304, SterilGARD e3 Class II Type A2, Biological Safety Cabinet
EDGEGARD EG6252: CASTER FOR 36" WORK SURFACE
HEIGHT, IV BAR, 30 AMP POWER CORD w/ TWIST PLUG
BCG601, BioChemGard e3 Class II, Type B2
TERRA UNIVERSAL
#2634-80A-220: GENERAL-USE PASS-THROUGH WITH RECIRCULATING
HEPA FILTRATION, 304 SS, 18"x18"x18" 240V, ELECTRONIC INTERLOCK
LAB COMPANION
AAHE1143U: CLG-1400g LAB REFRIGERATOR 1395L, (GLASS, DOUBLE DOOR) 120V, 60Hz, 13A
SHELVING, STORAGEM2080
SS SCRUB SINK, SENSOR ACTIVATED, EYEWASHP3000
KEY
NOTE ITEM
PURCHASED
BY
INSTALLED
BY
GC
VA VA
GC
SUPPORT *
GC
*CONTRACTOR TO PROVIDE MEP SUPPORT REQUIREMENTS AS INDICATED IN THE CONTRACT DRAWINGS AND SPECIFICATIONS. SUPPORT REQUIREMENTS INCLUDE BUT ARE NOT LIMITED TO OUTLETS, SUPPORT BLOCKING, SA/RA/EXHAUST DUCTS, DATA LINES, ELECTRIC, PLUMBING, ETC.
CONTRACTOR IS RESPONSIBLE FOR ALL EQUIPMENT COORDINATION.
MANUFACTURER MODEL / ACCESSORIES
SEE PLUMBING DRAWINGS
SEE DETAIL G/AE107
EQUIPMENT SCHEDULE
2ND FLOOR KEY PLAN
AREAS OF WORK
TC B
LINE OF ROOF OR FLOOR DECK
SECTION
PLAN
/8
3 5/8" METAL STUDS @ 16" OC, TYP
5/8" GYPSUM BOARD, BOTH SIDES, SEE ROOM FINISH
SCHEDULE FOR FINISHES
CONTINUOUS METAL STUD TOP TRACK. PROVIDE
DEFLECTION TRACK AT ROOM
CONTINUOUS METAL STUD BOTTOM TRACK
LINE OF FINISHED FLOOR, SEE ROOM FINISH
SCHEDULE FOR FLOOR & BASE TYPE
LINE OF CEILING SYSTEM, SEE ROOM FINISH
SCHEDULE FOR TYPE & HEIGHT
CONTINUOUS 3 1/2" SOUND ATTENUATION BATTS,
TYP.
CONTINUOUS METAL HORIZONTAL BRIDGING
CHANNEL @ MID HEIGHT, TYP.
FIRE-RATED SEALANT, BOTH SIDES
3 5/8" METAL STUDS @ 16" OC, 25-GAGE, TYPICAL
5/8" TYPE "X" GYPSUM BOARD, BOTH SIDES,
STAGGER JOINTS ON OPPOSITE SIDES OF ROOM
SEE ROOM FINISH SCHEDULE FOR FINISHES
FIRE-RATED SEALANT, BOTH SIDES
CONTINUOUS METAL STUD TOP TRACK. PROVIDE
DEFLECTION TRACK AT ROOF
CONTINUOUS METAL STUD BOTTOM TRACK
LINE OF FINISHED FLOOR, SEE ROOM FINISH SCHEDULE
FOR FLOOR & BASE TYPE
LINE OF ROOF OR FLOOR DECK
LINE OF CEILING SYSTEM, SEE ROOM FINISH
SCHEDULE FOR TYPE & HEIGHT
3 5/8" METAL STUDS @ 16" OC, TYP
5/8" GYPSUM BOARD, BOTH SIDES, SEE ROOM FINISH
SCHEDULE FOR FINISHES
CONTINUOUS METAL HORIZONTAL BRIDGING
CHANNEL @ MID HEIGHT, TYP.
3 5/8" METAL STUDS @ 16" OC, TYP.
5/8" GYPSUM BOARD, SEE ROOM FINISH SCHEDULE FOR
FINISHES. CONTINUE GWB TO UNDERSIDE OF DECK.
SECTION
PLAN
1-HR RATED PARTITION - U465
TEMPORARY CONSTRUCTION BARRIER
NON-RATED PARTITION
SINGLE SIDED PARTITION
CONTINUOUS METAL STUD BOTTOM TRACK
LINE OF FINISHED FLOOR, SEE ROOM FINISH SCHEDULE
FOR FLOOR & BASE TYPE
LINE OF ROOF OR FLOOR DECK
LINE OF CEILING SYSTEM, SEE ROOM FINISH
SCHEDULE FOR TYPE & HEIGHT
3 5/8" METAL STUDS @ 16" OC, TYP
5/8" GYPSUM BOARD, BOTH SIDES, SEE
ROOM FINISH SCHEDULE FOR FINISHES
SECTION
CONTINUOUS METAL HORIZONTAL BRIDGING
CHANNEL @ MID HEIGHT, TYP.
PLAN
A.1
/8
3/8" ACOUSTICAL SEALANT, BOTH SIDES
5/8" GYPSUM BOARD, BOTH SIDES, SEE ROOM FINISH
SCHEDULE FOR FINISHES
3/8" ACOUSTICAL SEALANT, BOTH SIDES
NON-RATED PARTITION
CONTINUOUS METAL STUD TOP TRACK. PROVIDE
DEFLECTION TRACK AT ROOF
C
CONTINUOUS METAL STUD BOTTOM TRACK
LINE OF FINISHED FLOOR, SEE ROOM FINISH SCHEDULE
FOR FLOOR & BASE TYPE
LINE OF ROOF OR FLOOR DECK
LINE OF CEILING SYSTEM, SEE ROOM FINISH
SCHEDULE FOR TYPE & HEIGHT
6" METAL STUDS @ 16" OC, TYP
5/8" GYPSUM BOARD, BOTH SIDES, SEE ROOM FINISH
SCHEDULE FOR FINISHES
SECTION
CONTINUOUS METAL HORIZONTAL BRIDGING
CHANNEL @ MID HEIGHT, TYP.
PLAN
3/8" ACOUSTICAL SEALANT, BOTH SIDES
6" METAL STUDS @ 16" OC, TYP.
5/8" GYPSUM BOARD, BOTH SIDES, SEE ROOM FINISH
SCHEDULE FOR FINISHES
3/8" ACOUSTICAL SEALANT, BOTH SIDES
NON-RATED PARTITION
CONTINUOUS METAL STUD TOP TRACK. PROVIDE
DEFLECTION TRACK AT ROOF
/4
/4
3 5/8" METAL STUDS @ 16" OC, 25-GAGE, TYPICAL
PARTITION TYPE A.1: CONTINUOUS 3 1/2" SOUND
ATTENUATION BATT INSULATION, TYP.
A
PARTITION TYPE A: SOUND ATTENUATION BATT
INSULATION NOT REQUIRED
PORTION OF PARTITION
TO REMAIN AS SOFFIT
BULKHEAD
PORTION OF
TEMPORARY PARTITION
TO BE REMOVED.
FINISH BOTTOM OF
SOFFIT BULKHEAD WITH
GWB.
OFFICE
2D135r
OFFICE
2D135t
HD STORAGE
2D135u
PASSAGE
2D135s
STERILE HD
COMPOUNDING
2D135w
STERILE
COMPOUNDING
2D135x
ANTE-ROOM
2D135v
ORDER ENTRY
2D135q
ANTE-ROOM
2D135n
IV CLEAN ROOM
2D135m
FILES
2D135j
VAULT
2D135h
135t
135u
135v
135w
135x
2D135a - PASSAGE VSF-1 VSF-1
FINISH SCHEDULE
ROOM
2D135r - OFFICE
2D135t - OFFICE
2D135u - HD STORAGE
2D135v - ANTE-ROOM
2D135w - STERILE HD COMPOUNDING
2D135x - STERILE COMPOUNDING
FLOOR BASE
PT-1 ACT-1
PAINT CEILING
2D135j - FILES VSF-1 VSF-1 PT-1 ACT-1
VSF-1 VSF-1 PT-2 ACT-1
VSF-1 VSF-1 PT-2 ACT-1
VSF-1 VSF-1 PT-1* GWB
VSF-1 VSF-1 PT-1* GWB
VSF-1 VSF-1 PT-1* GWB
VSF-1 VSF-1 PT-1* GWB
REMARKS
DOOR FRAME: P-3 (BOTH SIDES)
* WALLS & CEILINGS
MATERIAL ABBREVIATIONS
VSF-1 VINYL SHEET FLOORING
VSF-1: ARMSTRONG; MEDITONE; GRAYED BLUE LIGHT / H5328
PT PAINT
PT-1: SHERWIN WILLIAMS; WESTHIGHLAND WHITE / SW7566
PT-2: SHERWIN WILLIAMS; WESTHIGHLAND WHITE / SW7566
PT-3: SHERWIN WILLIAMS; SOFT FAWN / SW9097
ACT-1 ACOUSTIC CEILING TILE
SEE SPECIFICATIONS
GWB GYPSUM BOARD CEILING, PATINTED
SEE SPECIFICATIONS
FINISH SCHEDULE NOTES:
1. PROVIDE INTEGRAL VSF BASE WITH HEAT WELDED SEAMS AT VSF FLOORING. SEE DETAIL D/AE107.
2. HEAT WELD ALL JOINTS IN VINYL SHEET FLOORING (VSF).
3. PLASTIC LAMINATE (PLAM-1) TO BE WILSONART; WINDSWEPT BRONZE; MATTE / 4794-60
4. SOLID SURFACE (SS-1) TO BE MEGANITE; WHITE MOSALE GRANITE / 775
REFERENCE SPEC SECTION 09 06 00 FOR FINISHES
DOOR FRAME: P-3 (BOTH SIDES)
* WALLS & CEILINGS
* WALLS & CEILINGS
* WALLS & CEILINGS
A R C H I T E C T S E N G I N E E R S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors - Energy Consultants
As indicated
Philadelphia VA Medical Center 3900 Woodland Ave., Philadelphia, PA 19104
08/27/2020
642-17-100
DRKBJ
Renovate Inpatient Pharmacy for Chemotherapy I.V. Mixing
BID SETFINISH PLAN, EQUIPMENT PLAN &
PARTITION TYPES
AE104
3/8" = 1'-0"
EQUIPMENT PLAN
1/4" = 1'-0"
FINISH PLAN
D E
M A
R C
A T
IO
N
L
IN
E
01AE10502
OFFICE
2D135r
OFFICE
2D135t
HD STORAGE
PASSAGE
2D135s
STERILE HD
COMPOUNDING
2D135w
STERILE
COMPOUNDING
2D135x
ANTE-ROOM
2D135v
2D135u
05AE10503
07AE10509
18AE10516
13AE10511
AE105
AE105
6" INTEGRATED BASE
MODIFY EXISTING
CEILING
NEW SOFFIT
EXISTING GWB WALL,
PREP FOR NEW
FINISHES, PAINT
FINISHED CEILING
SYSTEM
EXISTING FINISHED
FLOOR, PREP FOR
NEW FINISHES
6" INTEGRATED BASE
MODIFY EXISTING
CEILING
NEW SOFFITFINISHED CEILING
SYSTEM
EXISTING FINISHED
FLOOR, PREP FOR
NEW FINISHES
SOLID SURFACE
COUNTERTOP W/ 4"
BACKSPLASH
6" INTEGRATED BASE
FINISHED CEILING
SYSTEM
EXISTING FINISHED
FLOOR, PREP FOR
NEW FINISHES
FINISHED END
PANEL
GWB PAINTED
PASS-THRU
6" INTEGRATED BASE
EXISTING FINISHED
FLOOR, PREP FOR
NEW FINISHES
GWB PAINTED
FINISHED CEILING SYSTEM
6" INTEGRATED BASE
WALL MTD. MONITOR STATION
GWB PAINTED
FINISHED CEILING
SYSTEM
EXISTING FINISHED
FLOOR, PREP FOR
NEW FINISHES
6" INTEGRATED BASE
PASS THRU
GWB PAINTED
FINISHE…